transitional cluster study6 2012 heavy summer pre-cluster base case n. gila - imperial valley 500 kv...

74
Transitional Cluster Study Attachment B Group 2012 Cluster Study Transient Stability Plots

Upload: others

Post on 09-Oct-2020

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

Transitional Cluster Study

Attachment B

Group 2012 Cluster Study Transient Stability Plots

Page 2: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

1

2012 Heavy Summer Pre-Cluster Base Case No Outage Transient Bus Voltage Plots

2012 Heavy Summer Pre-Cluster Base Case No Outage Transient Frequency Plots

Page 3: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

2

2012 Heavy Summer Pre-Cluster Base Case Coachella – Devers 230 kV line outage Transient Bus Voltage Plots

2012 Heavy Summer Pre-Cluster Base Case Coachella – Devers 230 kV line outage Transient Frequency Plots

Page 4: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

3

2012 Heavy Summer Pre-Cluster Base Case Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots

2012 Heavy Summer Pre-Cluster Base Case Ramon – Mirage 230 kV line outage Transient Frequency Plots

Page 5: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

4

2012 Heavy Summer Pre-Cluster Base Case Imperial Valley – El Centro 230 kV line outage Transient Bus Voltage Plots

2012 Heavy Summer Pre-Cluster Base Case Imperial Valley – El Centro 230 kV line outage Transient Frequency Plots

Page 6: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

5

2012 Heavy Summer Pre-Cluster Base Case Imperial Valley – Miguel 500 kV line outage Transient Bus Voltage Plots

2012 Heavy Summer Pre-Cluster Base Case Imperial Valley– Miguel 500 kV line outage Transient Frequency Plots

Page 7: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

6

2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage Transient Bus Voltage Plots

2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage Transient Frequency Plots

Page 8: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

7

2012 Heavy Summer Pre-Cluster Base Case Palo Verde - Devers 500 kV line outage Transient Bus Voltage Plots

2012 Heavy Summer Pre-Cluster Base Case Palo Verde - Devers 500 kV line outage Transient Frequency Plots

Page 9: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

8

2012 Heavy Summer Pre-Cluster Base Case ELSTM2 and REPU2 generator outages Transient Bus Voltage Plots

2012 Heavy Summer Pre-Cluster Base Case ELSTM2 and REPU2 generator outages Transient Frequency Plots

Page 10: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

9

2012 Heavy Summer Pre-Cluster Base Case Path 42 outage w/ RAS Transient Bus Voltage Plots

2012 Heavy Summer Pre-Cluster Base Case Path 42 outage w/RAS Transient Frequency Plots

Page 11: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

10

2012 Heavy Summer Pre-Cluster Base Case El Centro – Highline #1 & 2 230 kV line outages Transient Bus Voltage Plots

2012 Heavy Summer Pre-Cluster Base Case El Centro – Highline #1 & 2 230 kV line outages Transient Frequency Plots

Page 12: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

11

2012 Heavy Summer Pre-Cluster Base Case Imperial Valley - El Centro #1 & 2 230 kV line outages Transient Bus Voltage Plots

2012 Heavy Summer Pre-Cluster Base Case Imperial Valley - El Centro #1 & 2 230 kV line outages Transient Frequency Plots

Page 13: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

12

2012 Heavy Summer Pre-Cluster Base Case Coachela – Devrs & Coachela-Ramon 230kV line outages Transient Bus Voltage Plots

2012 Heavy Summer Pre-Cluster Base Case Coachela – Devrs & Coachela-Ramon 230kV line outages Transient Frequency Plots

Page 14: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

13

2012 Heavy Summer Post-Cluster Base Case No Outage Transient Bus Voltage Plots

2012 Heavy Summer Post-Cluster Base Case No Outage Transient Frequency Plots

Page 15: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

14

2012 Heavy Summer Post-Cluster Base Case Coachella – Devers 230 kV line outage Transient Bus Voltage Plots

2012 Heavy Summer Post-Cluster Base Case Coachella – Devers 230 kV line outage Transient Frequency Plots

Page 16: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

15

2012 Heavy Summer Post-Cluster Base Case Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots

2012 Heavy Summer Post-Cluster Base Case Ramon – Mirage 230 kV line outage Transient Frequency Plots

Page 17: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

16

2012 Heavy Summer Post-Cluster Base Case Imperial Valley – El Centro 230 kV line outage Transient Bus Voltage Plots

2012 Heavy Summer Post-Cluster Base Case Imperial Valley – El Centro 230 kV line outage Transient Frequency Plots

Page 18: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

17

2012 Heavy Summer Post-Cluster Base Case Imperial Valley – Miguel 500 kV line outage Transient Bus Voltage Plots

2012 Heavy Summer Post-Cluster Base Case Imperial Valley– Miguel 500 kV line outage Transient Frequency Plots

Page 19: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

18

2012 Heavy Summer Post-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage Transient Bus Voltage Plots

2012 Heavy Summer Post-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage Transient Frequency Plots

Page 20: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

19

2012 Heavy Summer Post-Cluster Base Case Palo Verde - Devers 500 kV line outage Transient Bus Voltage Plots

2012 Heavy Summer Post-Cluster Base Case Palo Verde - Devers 500 kV line outage Transient Frequency Plots

Page 21: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

20

2012 Heavy Summer Post-Cluster Base Case ELSTM2 and REPU2 generator outages Transient Bus Voltage Plots

2012 Heavy Summer Post-Cluster Base Case ELSTM2 and REPU2 generator outages Transient Frequency Plots

Page 22: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

21

2012 Heavy Summer Post-Cluster Base Case Path 42 outage w/ RAS Transient Bus Voltage Plots

2012 Heavy Summer Post-Cluster Base Case Path 42 outage w/RAS Transient Frequency Plots

Page 23: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

22

2012 Heavy Summer Post-Cluster Base Case El Centro – Highline #1 & 2 230 kV line outages Transient Bus Voltage Plots

2012 Heavy Summer Post-Cluster Base Case El Centro – Highline #1 & 2 230 kV line outages Transient Frequency Plots

Page 24: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

23

2012 Heavy Summer Post-Cluster Base Case Imperial Valley - El Centro #1 & 2 230 kV line outages Transient Bus Voltage Plots

2012 Heavy Summer Post-Cluster Base Case Imperial Valley - El Centro #1 & 2 230 kV line outages Transient Frequency Plots

Page 25: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

24

2012 Heavy Summer Post-Cluster Base Case Coachela – Devrs & Coachela-Ramon 230kV line outages Transient Bus Voltage Plots

2012 Heavy Summer Post-Cluster Base Case Coachela – Devrs & Coachela-Ramon 230kV line outages Transient Frequency Plots

Page 26: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

25

2012 Heavy Summer Post-Cluster w/ Mitigation Case No Outage Transient Bus Voltage Plots

2012 Heavy Summer Post-Cluster w/ Mitigation Case No Outage Transient Frequency Plots

Page 27: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

26

2012 Heavy Summer Post-Cluster w/ Mitigation Case Coachella – Devers 230 kV line outage Transient Bus Voltage Plots

2012 Heavy Summer Post-Cluster w/ Mitigation Case Coachella – Devers 230 kV line outage Transient Frequency Plots

Page 28: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

27

2012 Heavy Summer Post-Cluster w/ Mitigation Case Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots

2012 Heavy Summer Post-Cluster w/ Mitigation Case Ramon – Mirage 230 kV line outage Transient Frequency Plots

Page 29: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

28

2012 Heavy Summer Post-Cluster w/ Mitigation Case Imperial Valley – El Centro 230 kV line outage Transient Bus Voltage Plots

2012 Heavy Summer Post-Cluster w/ Mitigation Case Imperial Valley – El Centro 230 kV line outage Transient Frequency Plots

Page 30: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

29

2012 Heavy Summer Post-Cluster w/ Mitigation Case Imperial Valley – Miguel 500 kV line outage Transient Bus Voltage Plots

2012 Heavy Summer Post-Cluster w/ Mitigation Case Imperial Valley– Miguel 500 kV line outage Transient Frequency Plots

Page 31: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

30

2012 Heavy Summer Post-Cluster w/ Mitigation Case N. Gila - Imperial Valley 500 kV line outage Transient Bus Voltage Plots

2012 Heavy Summer Post-Cluster w/ Mitigation Case N. Gila - Imperial Valley 500 kV line outage Transient Frequency Plots

Page 32: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

31

2012 Heavy Summer Post-Cluster w/ Mitigation Case Palo Verde - Devers 500 kV line outage Transient Bus Voltage Plots

2012 Heavy Summer Post-Cluster w/ Mitigation Case Palo Verde - Devers 500 kV line outage Transient Frequency Plots

Page 33: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

32

2012 Heavy Summer Post-Cluster w/ Mitigation Case ELSTM2 and REPU2 generator outages Transient Bus Voltage Plots

2012 Heavy Summer Post-Cluster w/ Mitigation Case ELSTM2 and REPU2 generator outages Transient Frequency Plots

Page 34: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

33

2012 Heavy Summer Post-Cluster w/ Mitigation Case Path 42 outage w/ RAS Transient Bus Voltage Plots

2012 Heavy Summer Post-Cluster w/ Mitigation Case Path 42 outage w/RAS Transient Frequency Plots

Page 35: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

34

2012 Heavy Summer Post-Cluster w/ Mitigation Case Imperial Valley – El Centro #1 &2 230 kV lines outage Transient Bus Voltage Plots

2012 Heavy Summer Post-Cluster w/ Mitigation Case Imperial Valley – El Centro #1 &2 230 kV lines outage Transient Frequency Plots

Page 36: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

35

2012 Heavy Summer Post-Cluster w/ Mitigation Case Highline –El Centro #1 &2 230 kV lines outage Transient Bus Voltage Plots

2012 Heavy Summer Post-Cluster w/ Mitigation Case Highline –El Centro #1 &2 230 kV lines outage Transient Frequency Plots

Page 37: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

36

2012 Heavy Summer Post-Cluster w/Mitigation Case Coachela – Devrs & Coachela-Ramon 230kV line outages Transient Bus Voltage Plots

2012 Heavy Summer Post-Cluster w/Mitigation Case Coachela – Devrs & Coachela-Ramon 230kV line outages Transient Frequency Plots

Page 38: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

37

2012 Light Winter Transient Stability Plots

Page 39: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

38

2012 Light Winter Pre-Cluster Base Case No Outage Transient Bus Voltage Plots

2012 Light Winter Pre-Cluster Base Case No Outage Transient Frequency Plots

Page 40: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

39

2012 Light Winter Pre-Cluster Base Case Coachella – Devers 230 kV line outage Transient Bus Voltage Plots

2012 Light Winter Pre-Cluster Base Case Coachella – Devers 230 kV line outage Transient Frequency Plots

Page 41: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

40

2012 Light Winter Pre-Cluster Base Case Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots

2012 Light Winter Pre-Cluster Base Case Ramon – Mirage 230 kV line outage Transient Frequency Plots

Page 42: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

41

2012 Light Winter Pre-Cluster Base Case Imperial Valley – El Centro 230 kV line outage Transient Bus Voltage Plots

2012 Light Winter Pre-Cluster Base Case Imperial Valley – El Centro 230 kV line outage Transient Frequency Plots

Page 43: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

42

2012 Light Winter Pre-Cluster Base Case Imperial Valley – Miguel 500 kV line outage Transient Bus Voltage Plots

2012 Light Winter Pre-Cluster Base Case Imperial Valley– Miguel 500 kV line outage Transient Frequency Plots

Page 44: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

43

2012 Light Winter Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage Transient Bus Voltage Plots

2012 Light Winter Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage Transient Frequency Plots

Page 45: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

44

2012 Light Winter Pre-Cluster Base Case Palo Verde - Devers 500 kV line outage Transient Bus Voltage Plots

2012 Light Winter Pre-Cluster Base Case Palo Verde - Devers 500 kV line outage Transient Frequency Plots

Page 46: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

45

2012 Light Winter Pre-Cluster Base Case ELSTM2 and REPU2 generator outages Transient Bus Voltage Plots

2012 Light Winter Pre-Cluster Base Case ELSTM2 and REPU2 generator outages Transient Frequency Plots

Page 47: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

46

2012 Light Winter Pre-Cluster Base Case Path 42 outage w/ RAS Transient Bus Voltage Plots

2012 Light Winter Pre-Cluster Base Case Path 42 outage w/RAS Transient Frequency Plots

Page 48: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

47

2012 Light Winter Pre-Cluster Base Case Imperial Valley – El Centro #1 &2 230 kV lines outage Transient Bus Voltage Plots

2012 Light Winter Pre-Cluster Base Case Imperial Valley – El Centro #1 &2 230 kV lines outage Transient Frequency Plots

Page 49: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

48

2012 Light Winter Pre-Cluster Base Case Highline – El Centro #1 &2 230 kV lines outage Transient Bus Voltage Plots

2012 Light Winter Pre-Cluster Base Case Highline – El Centro #1 &2 230 kV lines outage Transient Frequency Plots

Page 50: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

49

2012 Light Winter Pre-Cluster Base Case Coachela – Devrs & Coachela-Ramon 230kV line outages Transient Bus Voltage Plots

2012 Light Winter Pre-Cluster Base Case Coachela – Devrs & Coachela-Ramon 230kV line outages Transient Frequency Plots

Page 51: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

50

2012 Light Winter Post-Cluster Base Case No Outage Transient Bus Voltage Plots

2012 Light Winter Post-Cluster Base Case No Outage Transient Frequency Plots

Page 52: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

51

2012 Light Winter Post-Cluster Base Case Coachella – Devers 230 kV line outage Transient Bus Voltage Plots

2012 Light Winter Post-Cluster Base Case Coachella – Devers 230 kV line outage Transient Frequency Plots

Page 53: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

52

2012 Light Winter Post-Cluster Base Case Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots

2012 Light Winter Post-Cluster Base Case Ramon – Mirage 230 kV line outage Transient Frequency Plots

Page 54: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

53

2012 Light Winter Post-Cluster Base Case Imperial Valley – El Centro 230 kV line outage Transient Bus Voltage Plots

2012 Light Winter Post-Cluster w/ Mitigation Case Imperial Valley – El Centro 230 kV line outage Transient Frequency Plots

Page 55: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

54

2012 Light Winter Post-Cluster Base Case Imperial Valley – Miguel 500 kV line outage Transient Bus Voltage Plots

2012 Light Winter Post-Cluster Base Case Imperial Valley– Miguel 500 kV line outage Transient Frequency Plots

Page 56: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

55

2012 Light Winter Post-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage Transient Bus Voltage Plots

2012 Light Winter Post-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage Transient Frequency Plots

Page 57: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

56

2012 Light Winter Post-Cluster Base Case Palo Verde - Devers 500 kV line outage Transient Bus Voltage Plots

2012 Light Winter Post-Cluster Base Case Palo Verde - Devers 500 kV line outage Transient Frequency Plots

Page 58: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

57

2012 Light Winter Post-Cluster Base Case ELSTM2 and REPU2 generator outages Transient Bus Voltage Plots

2012 Light Winter Post-Cluster Base Case ELSTM2 and REPU2 generator outages Transient Frequency Plots

Page 59: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

58

2012 Light Winter Post-Cluster Base Case Path 42 outage w/ RAS Transient Bus Voltage Plots

2012 Light Winter Post-Cluster Base Case Path 42 outage w/RAS Transient Frequency Plots

Page 60: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

59

2012 Light Winter Post-Cluster Base Case Imperial Valley – El Centro #1 &2 230 kV lines outage Transient Bus Voltage Plots

2012 Light Winter Post-Cluster Base Case Imperial Valley – El Centro #1 &2 230 kV lines outage Transient Frequency Plots

Page 61: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

60

2012 Light Winter Post-Cluster Base Case Highline – El Centro #1 &2 230 kV lines outage Transient Bus Voltage Plots

2012 Light Winter Post-Cluster Base Case Highline – El Centro #1 &2 230 kV lines outage Transient Frequency Plots

Page 62: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

61

2012 Light Winter Post-Cluster Base Case Coachela – Devrs & Coachela-Ramon 230kV line outages Transient Bus Voltage Plots

2012 Light Winter Post-Cluster Base Case Coachela – Devrs & Coachela-Ramon 230kV line outages Transient Frequency Plots

Page 63: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

62

2012 Light Winter Post-Cluster w/ Mitigation Case No Outage Transient Bus Voltage Plots

2012 Light Winter Post-Cluster w/ Mitigation Case No Outage Transient Frequency Plots

Page 64: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

63

2012 Light Winter Post-Cluster w/ Mitigation Case Coachella – Devers 230 kV line outage Transient Bus Voltage Plots

2012 Light Winter Post-Cluster w/ Mitigation Case Coachella – Devers 230 kV line outage Transient Frequency Plots

Page 65: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

64

2012 Light Winter Post-Cluster w/ Mitigation Case Ramon – Mirage 230 kV line outage Transient Bus Voltage Plots

2012 Light Winter Post-Cluster w/ Mitigation Case Ramon – Mirage 230 kV line outage Transient Frequency Plots

Page 66: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

65

2012 Light Winter Post-Cluster w/ Mitigation Case Imperial Valley – El Centro 230 kV line outage Transient Bus Voltage Plots

2012 Light Winter Post-Cluster w/ Mitigation Case Imperial Valley – El Centro 230 kV line outage Transient Frequency Plots

Page 67: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

66

2012 Light Winter Post-Cluster w/ Mitigation Case Imperial Valley – Miguel 500 kV line outage Transient Bus Voltage Plots

2012 Light Winter Post-Cluster w/ Mitigation Case Imperial Valley– Miguel 500 kV line outage Transient Frequency Plots

Page 68: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

67

2012 Light Winter Post-Cluster w/ Mitigation Case N. Gila - Imperial Valley 500 kV line outage Transient Bus Voltage Plots

2012 Light Winter Post-Cluster w/ Mitigation Case N. Gila - Imperial Valley 500 kV line outage Transient Frequency Plots

Page 69: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

68

2012 Light Winter Post-Cluster w/ Mitigation Case Palo Verde - Devers 500 kV line outage Transient Bus Voltage Plots

2012 Light Winter Post-Cluster w/ Mitigation Case Palo Verde - Devers 500 kV line outage Transient Frequency Plots

Page 70: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

69

2012 Light Winter Post-Cluster w/ Mitigation Case ELSTM2 and REPU2 generator outages Transient Bus Voltage Plots

2012 Light Winter Post-Cluster w/ Mitigation Case ELSTM2 and REPU2 generator outages Transient Frequency Plots

Page 71: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

70

2012 Light Winter Post-Cluster w/ Mitigation Case Path 42 outage w/ RAS Transient Bus Voltage Plots

2012 Light Winter Post-Cluster w/ Mitigation Case Path 42 outage w/RAS Transient Frequency Plots

Page 72: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

71

2012 Light Winter Post-Cluster w/ Mitigation Case Imperial Valley – El Centro #1 &2 230 kV lines outage Transient Bus Voltage Plots

2012 Light Winter Post-Cluster w/ Mitigation Case Imperial Valley – El Centro #1 &2 230 kV lines outage Transient Frequency Plots

Page 73: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

72

2012 Light Winter Post-Cluster w/ Mitigation Case Highline – El Centro #1 &2 230 kV lines outage Transient Bus Voltage Plots

2012 Light Winter Post-Cluster w/ Mitigation Case Highline – El Centro #1 &2 230 kV lines outage Transient Frequency Plots

Page 74: Transitional Cluster Study6 2012 Heavy Summer Pre-Cluster Base Case N. Gila - Imperial Valley 500 kV line outage ... Imperial Valley - El Centro #1 & 2 230 kV line outages Transient

73

2012 Light Winter Post-Cluster w/Mitigation Case Coachela – Devrs & Coachela-Ramon 230kV line outages Transient Bus Voltage Plots

2012 Light Winter Post-Cluster w/Mitigation Case Coachela – Devrs & Coachela-Ramon 230kV line outages Transient Frequency Plots