transient analysis of grounding systems

11
389 IEEE Transactions on Power Apparatus and Systems, Vol. PAS-102, No. 2, February 1983 TRANSIENT ANALYSIS OF GROUNDING SYSTEMS A. P. Meliopoulos IEEE, Member M. G. Moharam IEEE, Member School of Electrical Engineering Georgia Institute of Technology Atlanta, Georgia 30332 Abstract This paper addresses the problem of computing the ground potential rise of grounding systems during transients. Finite element analysis is employed to model the constituent parts of a grounding system. Short lengths of earth embedded electrodes are charac- terized as transmission lines with distributed induc- tance, capacitance and leakage resistance to earth. Leakage resistance to earth is accurately computed with the method of moments. The other parameters of the finite element, namely inductance and capacitance, are computed from the resistance utilizing Maxwell's equa- tions. This modeling enables the computation of the transient response of substation grounding systems to fast or slow waves striking the substation. The result is obtained in terms of a convolution of the step re- sponse of the system and the striking wave. In this way the impedance of substation systems to 60 cycles is accurately computed. Results demonstrate the depen- dence of the 60 cycle impedance on system parameters. The methodology allows to interface this model of a substation ground mat with the Electromagnetic Trans- ient Analysis Program thus, allowing explicit represen- tation of earth effects in electromagmatic transients computations. 1. INTRODUCTION The transient response characteristics of ground- ing systems play an important role in the protection of electrical installations. For example, the voltage drop along a ground rod connecting a surge arrester and the transformer it is protecting can obtain a value which is a substantial percentage of the basic impulse level of the transformer insulation. Depending on the configuration, the surge arrester experiences an over- voltage which is less than the one reaching the trans- former. Thus system protection is reduced. The intro- duction of solid state arresters and the every shrink- ing safety margins demand more accurate analysis proce- dures for substation design and protection. In this context, analysis procedures predicting the transient response of substation grounding systems are very im- portant. The transient response of grounding structures has been studied many years ago by Rudenberg [1], Bewley [2], Sunde [3] and others. The classical experiments performed by Bewley [21 on counterpoises provide much information about the transient characteristic of 82 SM 369-7 A paper recommended and approved by the IEEE Substations Committee of the IEEE Power Engineer- ing Society for presentation at the IEEE PES 1982 Summer Meeting, San Francisco, California, July 18-23, 1982. Manuscript submitted February 4, 1982; made avail- able for prinfting April 19, 1982. grounding systems. Verma and Mukhedkar [51 showed that distributed resistance and inductance models of buried ground wires predict transient response of such systems in agreement with the experiments of Bewley. However, they do not provide any models for practical substation grounding systems. Kostaluk, Loboda and Mukhedkar [15] provide experimental data for transient ground impe- dances. Similarly, Rogers [6] reports on actual system transient response of a large tower footing. Bellashi et al. [8], [91, [10], have given a complete treatment of driven rods characteristics. Gupta and Thapar [7] provide empirical formulae for the impulse impedance of substation ground grids, defined as the ratio of the peak value of the voltage developed at the feeding point to the peak value of the current. This defini- tion of impulse impedance leads to uncertainty because the peak values of voltage and current do not necessar- ily occur at the same time. The so defined impulse impedance strongly depends on the rise time of the wave considered, the mesh size of the grid, soil resistivity and permittivity, the feeding point, etc. This paper presents data which further illustrate the point. Thus, the definition of impulse impedance of reference [71 is at best ambiguous. The work reported in this paper addresses the problem of transient analysis of practical grounding systems consisting of ground mats, ground rods, etc. The developed models are in good agreement with experi- mental results. The paper is organized as follows. First, the simple case of an earth embedded conductor is treated. This case is extended to the case of a substation ground mat. These two cases clearly illustrate the methodology. Sample test cases are presented and com- pared to known experimental data. The comparison is favorable. Finally, a methodology is outlined for the interface of the grounding system models of this paper with the EMTP computer program which enables the study of the impact of grounding systems on electromagnetic transients. 2. TRANSIENT RESPONSE OF AN EARTH EMBEDDED CONDUCTOR 2.1 Problem Formulation Development of models of grounding structures suitable for the computation of their transient re- sponse can be demonstrated with the simple system of a single buried conductor. Such a system is illustrated in Figure 1. A small segment of length Q of the conductor of Figure 1, is characterized with a series resistance Ar, a series inductance AL, conductance Ag to remote earth and capacitance AC. This representa- tion is illustrated in Figure 2. These parameters are distributed along the length Q of the segment. The thick solid line signifies the tact. The numerical values of the quantities Ag, AL, AC can be directly computed from two quantities, namely the conductance Ag and the speed of electromagnetic waves in the soil V , as follows. The speed V is 0018-9510/83/0002-0389$01.00 ( 1983 IEEE

Upload: gilberto-mejia

Post on 26-Jan-2017

37 views

Category:

Engineering


4 download

TRANSCRIPT

Page 1: Transient analysis of grounding systems

389IEEE Transactions on Power Apparatus and Systems, Vol. PAS-102, No. 2, February 1983

TRANSIENT ANALYSIS OF GROUNDING SYSTEMS

A. P. MeliopoulosIEEE, Member

M. G. MoharamIEEE, Member

School of Electrical EngineeringGeorgia Institute of Technology

Atlanta, Georgia 30332

Abstract

This paper addresses the problem of computing theground potential rise of grounding systems duringtransients. Finite element analysis is employed tomodel the constituent parts of a grounding system.Short lengths of earth embedded electrodes are charac-terized as transmission lines with distributed induc-tance, capacitance and leakage resistance to earth.Leakage resistance to earth is accurately computed withthe method of moments. The other parameters of thefinite element, namely inductance and capacitance, arecomputed from the resistance utilizing Maxwell's equa-tions. This modeling enables the computation of thetransient response of substation grounding systems tofast or slow waves striking the substation. The resultis obtained in terms of a convolution of the step re-sponse of the system and the striking wave. In this waythe impedance of substation systems to 60 cycles isaccurately computed. Results demonstrate the depen-dence of the 60 cycle impedance on system parameters.The methodology allows to interface this model of asubstation ground mat with the Electromagnetic Trans-ient Analysis Program thus, allowing explicit represen-tation of earth effects in electromagmatic transientscomputations.

1. INTRODUCTION

The transient response characteristics of ground-ing systems play an important role in the protection ofelectrical installations. For example, the voltagedrop along a ground rod connecting a surge arrester andthe transformer it is protecting can obtain a valuewhich is a substantial percentage of the basic impulselevel of the transformer insulation. Depending on theconfiguration, the surge arrester experiences an over-voltage which is less than the one reaching the trans-former. Thus system protection is reduced. The intro-duction of solid state arresters and the every shrink-ing safety margins demand more accurate analysis proce-dures for substation design and protection. In thiscontext, analysis procedures predicting the transientresponse of substation grounding systems are very im-portant.

The transient response of grounding structures hasbeen studied many years ago by Rudenberg [1], Bewley[2], Sunde [3] and others. The classical experimentsperformed by Bewley [21 on counterpoises provide muchinformation about the transient characteristic of

82 SM 369-7 A paper recommended and approved by theIEEE Substations Committee of the IEEE Power Engineer-ing Society for presentation at the IEEE PES 1982Summer Meeting, San Francisco, California, July 18-23,1982. Manuscript submitted February 4, 1982; made avail-able for prinfting April 19, 1982.

grounding systems. Verma and Mukhedkar [51 showed thatdistributed resistance and inductance models of buriedground wires predict transient response of such systemsin agreement with the experiments of Bewley. However,they do not provide any models for practical substationgrounding systems. Kostaluk, Loboda and Mukhedkar [15]provide experimental data for transient ground impe-dances. Similarly, Rogers [6] reports on actual systemtransient response of a large tower footing. Bellashiet al. [8], [91, [10], have given a complete treatmentof driven rods characteristics. Gupta and Thapar [7]provide empirical formulae for the impulse impedance ofsubstation ground grids, defined as the ratio of thepeak value of the voltage developed at the feedingpoint to the peak value of the current. This defini-tion of impulse impedance leads to uncertainty becausethe peak values of voltage and current do not necessar-ily occur at the same time. The so defined impulseimpedance strongly depends on the rise time of the waveconsidered, the mesh size of the grid, soil resistivityand permittivity, the feeding point, etc. This paperpresents data which further illustrate the point.Thus, the definition of impulse impedance of reference[71 is at best ambiguous.

The work reported in this paper addresses theproblem of transient analysis of practical groundingsystems consisting of ground mats, ground rods, etc.The developed models are in good agreement with experi-mental results.

The paper is organized as follows. First, thesimple case of an earth embedded conductor is treated.This case is extended to the case of a substationground mat. These two cases clearly illustrate themethodology. Sample test cases are presented and com-pared to known experimental data. The comparison isfavorable. Finally, a methodology is outlined for theinterface of the grounding system models of this paperwith the EMTP computer program which enables the studyof the impact of grounding systems on electromagnetictransients.

2. TRANSIENT RESPONSE OF AN EARTH EMBEDDED CONDUCTOR

2.1 Problem Formulation

Development of models of grounding structuressuitable for the computation of their transient re-sponse can be demonstrated with the simple system of asingle buried conductor. Such a system is illustratedin Figure 1. A small segment of length Q of theconductor of Figure 1, is characterized with a seriesresistance Ar, a series inductance AL, conductance Agto remote earth and capacitance AC. This representa-tion is illustrated in Figure 2. These parameters aredistributed along the length Q of the segment. Thethick solid line signifies the tact.

The numerical values of the quantities Ag, AL, ACcan be directly computed from two quantities, namelythe conductance Ag and the speed of electromagneticwaves in the soil V , as follows. The speed V is

0018-9510/83/0002-0389$01.00 ( 1983 IEEE

Page 2: Transient analysis of grounding systems

AIR/ /t ts/ / / / I I J J -1 / /

eQs / (x,y,z)

hIs.Tej EARTH) (conductivity a)

Figure 1. Single Conductor Buried in Uniform Soil.A Short Segment of Length R. is Indicated.

AC = a Ag

AL = a S

0 0

(3)

(4)

E0= E/cEr permittivity for free space.It is obvious that knowledge of Ag and soil pro-

perties suffice to determine the parameters of the fi-nite element. Computation of Ag is outlined in Section2.2.

Applying Kirchoff's laws to a small section Ax,one obtains the usual equation of a distributed param-eter line:

321tr 321

+ (Ar-AC + AL-Ag)31i + Ar.Ag I0

There are two approaches of solving this equation:

(5)

Ar AL- - ~~~~~~~~Figure 2. Representation of a Finite Element with Circuit Elements.

readily computed from the soil properties with the aidof Equation (1).

I~~~~

where

CV = °s ,

rr

(1)

C0 is the speed of light in free space, andE£ is the relative permittivity of the soil.r

The computation of the conductances Ag has beenreported in an earlier publication [13] and it is sum-

marized in Section 2.2 of this paper.

Maxwell's equations dictate that

AC C (2)Aga

where: soil permittivity

C : soil conductivity

Also, considering the segment Q as a transmission linewith distributed inductance ASL and capacitance ACyields:

Q__ Cs = 0

/ AL *AC x

where r

Q length of the finite element under consid er-

ation

Above relationships yield the inductance and capaci-tance of the finite element:

(a) By direct solution (i.e. FFT) which leads tocomputationally infeasible procedure forthis problem; and

(b) Using approximate analysis techniques.

The latter approach will be described. Consider againa finite element of the conductor. Since the elementis very short the circuit of Figure 2 can be approxi-mated with the circuit of Figure 3. The middle part canbe recognized as a lossless transmission line. Theequivalent circuit of Figure 3 is the basis for thedevelopment of the methodology. To this purpose

Dommel's method [14], can be directly employed to yieldthe resistive equivalent circuit of Figure 4. The pasthistory current sources of Figure 4 are defined as fol-lows:

O 0o

I e (t-T) + 2g e (t-T) +2Z ik(tT) (6b)

+ ) ik(t-T)

Lossless Transmission Line

Ar/2 AL Ar/2

g I TAg/2

Figure 3. Approximate Equivalent Circuit of a Short Lengthof an Earth Embedded Conductor.

390

dS ~ dl

dS

..-. -1

Page 3: Transient analysis of grounding systems

(i) 'k"t; i 'X m(t) / i

+ ikm(t) imk(t)

Bk(t) Ag/2 > Z0< ' Ik(tT) ,zo Ag/2 em(t)

Figure 4. Resistive Equivalent Circuit of a ShortLength of an Earth Embedded Conductor.

391

TABLE 1. Algorithm for the Computation of theTransient Response of Grounding Systems.

Step 1: Partition the grounding system into finiteelements.

Step 2: Compute the parameters of each finite element.

Step 3: Compute the equivalent resistive networkparameters for each element.

Step 4: Compute the admittance matrix Y. Invert ma-trix Y using sparcity techniques. Let k=O.

Derivation of above formulae is given in the appendix.

The equivalent circuit of Figure 4, which will bereferred to as the equivalent resistive network, is thebasis of the method. Consider an earth embedded con-ductor of length Q. Assume a partition of this conduc-tor into n segments. n is selected according to thedesired degree of accuracy in the computations. Eachone of the segments can be represented with the equiva-lent circuit of Figure 4, and associated equations.The resulting equivalent circuit is resistive. Thus,nodal analysis is most suitably applied to yield:

Y e(t) = i(t) + b(t-h) (7)

where

ye(t)

i(t)

b(t-h)

is the admittance matrix of the circuitis the vector of voltages at the nodes ofthe circuit (terminals of the segments)is the vector of currents injected at thenodes of the circuitis the vector of past history.

In this particular application, the admittance matrixhas a special structure. All entries are zero exceptthe diagonal and those which are located one positionover or under the diagonal

Y. . #01 1

Y #0 for every i

Y #0Yi+l,i °

all others zero.

This special structure of the matrix Y admits theefficient use of sparcity techniques for the solutionof Equation (7). The vector of past history is con-structed from the current sources I (t-h). It is ex-pedient to select h=T, where - is thme wave travel timealong any one of the finite elements.

The nodal equations enable the solution of thevoltages e(t) at the various nodes of the system if thecurrent injections i(t) are known. Table 1 illustratesthe algorithm for the computation of the transient re-sponse for a period of tmax seconds with time step h.

The same analysis methodology can be applied to aset of interconnected earth embedded conductors forminga ground mat. This analysis is presented in Section 3.

Step 5: Let k=k+l. Compute the past history currentsources of the equivalent circuits at timet=(k-l)h.

Step 6: Compute the external current sources at timet=kh. Compute the vector i(kh) + b((k-l)h).

Step 7: Solve for the voltages e(kh) = Y 1(i(kh) +b((k-l)h)).

Step 8: If kh > tmax terminate. Otherwise go to Step

2.2 Computation of the-Ground Resistance

This section describes the procedure for the com-putation of the conductance Ag of a finite element of agrounding system. It is based on the rigorous solutionof Laplace's equation in the seminfinite conductingmedium of the earth. The description of the method israther sketchy. More details can be found in [13].

The computation of the ground resistance includesthe following steps. Consider an earth embedded con-ductor. Further consider an infinitesimal surface dSof the conductor emanating total current dI. The flowof current dl generates a voltage field in earth whichis governed by Laplace's equation

V2V(x,y,z) = 0 (8)

The solution for the voltage at point (x,y,z) dueto current dI has the following general form:

dV(x,y,z) = dI f(x,y,z,ds) (9)

where f is a function of point (x,y,z), the infini-tesimal surface dS and the soil properties.

Now consider a finite length of the earth embeddedconductor of length i . Under the assumption of uni-form current distribution on the surface of this seg-ment the voltage at (x,y,z) due to the current emanat-ing from the outside surface of the finite segment is

V1 (x,y,z) = f dV(x,y,z)whchiscopuedt b

which is computed to be l13]

Vsl(x,y,z) = Ri(x,y,z,j)I.

(10)

(11)

Consider now that the conductor is partitioned in-to n segments of lengths k1,i ...v Q , respectively.Further assume that the current is uni%ormly emanatingfrom the surface of each segment and has a total value

11 I29" In- The voltage at point (x,y,z) shall becomputed from the superposition of all contributions,i.e.

Page 4: Transient analysis of grounding systems

392

V(x,y,z) = z V (x,y,z) = R (x,y,z,i)I. (12)i

1

Specifically, the voltage of segment k can be computedas:

Vk = Vi(kxky,kz i) =zRkiIi (13)

Writing one such equation for every segment weobtain

[VI = [R][I]

where

wherE

[ 1

V in

(14)

I = i]

LIni

V. is the voltage of the outside surface of1

ment i;Ii is the current emanating from the surfac

segment i; and[RI is an nxn matrix which is symmetric.

Above matrix equation can be inverted to yiel

[I = [Y[V]

[Y[ = [RI1

Matrix Y represents an admittance matrix wcorresponds to an equivalent circuit for the e[131, as follows:

(a) Entry y.. of [Y] equals the negative contance oiJa element connected between segi and j; and

(b) yYi. equals the conductance of an equivadirEAit element connected between segmeand remote earth.

The equivalent conductance -y.. between remote elemi and j is in general very sirJall and can be omitThus, for every segment an equivalent conductancremote earth is computed. This conductance provthe basis for the computation of the other parameof the f inite element as it has been shown in Sec2.1.

3. TRANSIENT ANALYSIS OF GROUND MATS

seg-

-e of

Y e(t) = i(t) + b(t-h) (16)

where the admittance matrix Y is highly sparse (maximumof three non-zero elements per row), i(t) is the exter-nally injected currents. Solution of above equationfor times t=0, h, 2h, 3h, ... yields the voltages e(t)everywhere in the substation ground system, as it isoutlined in Table 1.

In Equation (16) depending on the excitation ofthe grounding system, the known quantities will be:

(a) The externally injected current vector i(t)(for example, a lightning current wave im-pending at a certain location);

(b) Some of the entries of vector e(t) (for exam-ple, a voltage wave impeding the groundingsystem); and

(c) Combination of above.

In general, every type of surge injected in thegrounding system can be accommodated with Equation(16). In Section 6, the procedure will be generalizedto the extent of interfacing this model of the groundmat with the Electromagnetic Transient Analysis Program[141.

4. 60-CYCLE IMPEDANCE OF GROUNDING SYSTEMS

The developed models are suitable for the computa-d tion of the power frequency impedance of grounding sys-

tems. The 60-cycle impedance of a grounding system (or(15) the impedance at any given frequency) can be computed

in two ways:

(a) Inject a sinusoidal current wave (peak valuehich I ) to the grounding system and compute its

marth voltage elevation. This voltage will also be

sinusoidal at steady state. The impedance ofthe grounding system is computed from the

Lduc- peak value of the voltage wave, V , and themtment phase difference, C, between voltage and cur-

rent:V

lent z (17)nti I

(b) Compute the current response, s(t), of thegrounding system to a unit step voltage (see

Lents Figure 11). The impedance of the grounding:ted. system at frequency f is thene toridesters:tion

The transient response of substation ground matscan be similarly computed with the finite element anal-ysis procedure described. To this purpose the conduc-tors of the substation ground mat, ground rods, fences,etc., are segmented into a number of finite elements.The equivalent circuit representation of the earth as-

sociated with above segmentation of the substationground mat is then computed with the procedure outlinedin Section 2.2. Then using Equations (3) and (4), eachfinite element is represented with a lossless transmis-sion line, series resistance and shunt conductance as

it is shown in Section 2.1. Next each finite element isrepresented with the equivalent circuit of Figure 4.Nodal analysis for the resulting equivalent circuityields

f s

Z = 1.0/| ejj27rft s' (t)dt (18)

where s'(t) is the time derivative of thestep response s(t).

Computationally, the second way is more efficient be-cause the first method requires the simulation of thegrounding system response for a long time until sinu-soidal steady state is achieved. Computation of theintegral of Equation (18) is straightforward and compu-tationally efficient. A computer program has been de-veloped for the computation of the Equation (18).

5. TEST RESULTS

The methodology described in this paper has beenimplemented and a number of grounding systems have beenstudied. These are:

(1) A 60 meter long earth embedded 4/0 copperconductor (burial depth = 0.6 meters).

Page 5: Transient analysis of grounding systems

(2) A 6 x 6 mesh ground mat with 10 meter squaremeshes buried at 0.6 meters under the earthsurface. This system will be referred to asMAT A.

(3) A 10 x 10 mesh ground mat with 6 meter squaremeshes buried at 0.6 meters under the earthsurface. This system will be referred to asMAT B.

(4) A 10 x 10 mesh ground mat with 12 metersquare mesh buried at 0.6 meters under theearth surface. This system will be referredto as MAT C.

Mats A, B, and C are assumed to be constructed from 2/0copper conductor.

Figures 5 and 6 illustrate the response of a 60meter long 4/0 copper conductor embedded in 125 Qm soilat depth of 0.6 meters, to a step and a 1/20 us currentwave respectively: l 0 t < 0

i (t) =a 1 kA 1 t > 0

-0.4t -1.8tib (t) = 1.1152 (e - e ) A

In both cases the current is injected at one end of theconductor. The voltage at both ends of the conductorand the middle is plotted versus time.

Figure 7 and Figure 8 curve A, illustrate thetransient response of MAT A to a step current and a 1/20ps current wave respectively. Figure 7 illustrates thevoltage at the feeding point, corner and a middlepoint.

The following general observations apply:

(a) During the rise time of the current surge theconductor demonstrates an impedance equal toits characteristic iInpedance for the stepsurge and a lower value for the exponentialwave.

(b) As time progresses in Figures 5 and 7, thevoltage of the conductor approaches a steadyvalue which is verif ied to be equal to RIwhere R is the dc resistance to remote earthof the grounding system. In these cases, theresistance is computed to be 4.1777 and1.0104 ohms respectively.

(c) The earth embedded conductor behaves as a

highly lossy transmission line. For example,in Figure 5 it appears that the time totravel from point A to point C is more thantwice the time to travel from point A topoint B. This is in conformity with experi-mental results carried out by Bewley andothers. The phenomenon is due to the jointeffects of the self-inductance and ground re-

sistance which leads to a lower and ever de-creasing wave velocity with length.

Figure 8 illustrates, on a common system of coor-

dinates, the responses of ground mats A and B to a 1/20Pis current surge. These two ground mats cover the samearea and have approximately equal DC resistance toearth (1.0104 and .9876 ohms respectively). However,their transient response is different. Specifically,the 1/20 impulse generates a much higher overvoltage on

mat A than mat B. This is due to the fact that theconductors of mat B are closer spaced than the conduc-tors of mat A. Results obtained with the models de-

393

scribed in this paper indicate the following. Thelevel of overvoltages resulting from direct strokes onsubstation depend strongly on: (a) conductor spacing,(b) rise time of stroke, (c) soil resistivity and per-mittivity, and (d) others. These characteristics ofground mats are very important in the design of over-voltage protection. Closer spacing of ground mat con-ductors yields lesser overvoltages and thus reduces thepossibility of backstroke in the case of direct light-ning stroke on a substation grounded structure.

The ac impedance of the test grounding systemshave been computed and listed in Table 2. The effec-tive resistance, reactance, and inductance for 60 Hz aswell as for a number of harmonics are tabulated. Thesoil is assumed to be dry or wet with the indicatedparameters. From the table, it is obvious that thereactance of a grounding system depends strongly on itslength and the soil permittivity. For medium sizegrounding systems the reactance at 60 Hz is substan-tial. Wet soil, which is characterized with greaterpermittivity values tends to decrease the inductance ofgrounding systems. The resistance, as it is expectedis approximately proportional to the soil resistivity.These results are in agreement with results obtainedthrough sophisticated measurements techniques of powersystem ground impedances [12].

TABLE 2. Impedance of Test Systems

A. Dry Soil: p - 1000 ohm-m, Sr M 9.0

Frequency(Hz)3r-

60 meter 60Conductor 120

180240300

Mat A 60120180240300

Mat B

Mat C

60120180240300

60120180240300

B.

60120180240300

60 meterConductor

Mat A

Mat B

Mat c

Resistance(ohms)}

33 .42133.42133.42133.42133.421

8.0838.0838.0838.0838.083

7.6617.6617.6637.6657.668

3.9543.9693.9944.0284.072

Wet Soil: p - 100 nm,

3.3423.3423.3423.3423.342

Reactance-(ohms)

.0349

.0698

.1047

.1396

.1745

.0356

.0712

.1068

.1424

.1780

.0571

.1143

.1714

.2284

.2854

.1366

.2717

.4037

.5308

.6512

C - 36.0r

.0348

.0697

.1045

.1394

.1743

.808 .0360

.808 .0721

.808 .1082

.808 .1443

.809 .1805

60120180240300

60120180240300

60120180240300

.766

.766

.767

.767

.768

.0438

.0875

.1311

.1745

.2176

.395 .0867

.397 .1733

.400 .2587

.402 .3421

.402 .4256

Inductance(EHenry)_.0926.0926.0926.0926.0926

.0944

.0944

.0944

.0944

.0944

.1516

.1516

.1515

.1515

.15 14

.3623

.3603

.3569

.3520

.3455

.0924

.0924

.0924

.0924

.0924

.0956

.0956

.0956

.0956

.0956

.1163

.1161

.1159

.1157

.1154

.2299

.2298

.2288

.2268

.2257

Page 6: Transient analysis of grounding systems

\0 A a C

AtHeGomo_

8

8

918u-

8.

8-

00 2o 4.0 6.0 16.0 12.0 14.0

TIME (MICRO SECONDS)

FIGURE S. TRANSIENT RESPONSE OF A 60 METER, 410 COPPERCONDUCTOR TO A STEP CURRENT OF i KA.

0.0 20 4.0 .0 8.0 10.0 ZO 14.0 16.0

TIME(MICRO SECONDS)

FIGURE6

TRANSIENT RESPONSE OF A 60 METER, 4/0 COPPERCONDUCTOR TO A 1/20 As. 1 KA CREST SURGE.

8

i'$

8

8.

8.

60 10.0 20.0 26.0 40.0 50.0 60.o 70.0

TIME lMICRO SECONDS)

FIGURE 7. TRANSIENT RESPONSE OF MAT A TOA STEP CURRENT OF 1 KA.

r-

leqt-h) t G

l ~ ~ ~ AA- Y -l

G = YAAAB BB YBA

leq(t-h) = bA(t-h)- AByBB bB(t-h)

Figure 9. Equivalent Representation of a GroundingSystem Compatible with the EMTP.

0.0 2.0 4.0 .0 a'o I0. i20TIME (MICRO SECONDS)

FIGURE 6. TRANSIENT RESPONSE OF GROUND MATS A AND BTO A lJ20 s; 1 KA CREST SURGE.

ad'

.; -

zf 0:

8.

0.0 20. 40.0 6.0 60.0 100.0 120.0

TIME (MICRO SECONDS)

FIGURE 10. TRANSIENT CURRENT RESPONSB TO A STEP VOLTAGE OF kI.

394

8

g

8

S.

8

8

8

8

8

V

8

8

0

8

8

A B

so

Page 7: Transient analysis of grounding systems

395

6. INTERFACE WITH THE EMTP

The methodology described in this paper for thecomputation of the transient response of grounding sys-tems is compatible with the methodology of the Electro-magnetic Transient Analysis Program (EMTP), developedby BPA. Thus, it can be interfaced with this computerprogram. In this case, the effects of substationgrounding systems on overvoltages, surge arrester per-formance and, in general, transient performance of sub-station can be evaluated. The introduction of newtechnologies in substation design, such as gaplesssurge arresters and computers and the ever shrinkingsafety margins demand more accurate transient analysisprocedures for susbtation design and protection. Thus,the specific modeling of substation grounding systemsin the EMTP is important. This section briefly out-lines the process by which the substation ground modeldescribed in this paper can be interfaced with theEMTP.

There are at least two ways to interface thismodel with the EMTP:

(a) The direct method; and(b) With linear convolution.

While the direct method is straightforward, the methodbased on time-domain linear convolutions is numericallymore efficient. Both methods will be' described.

6.1. The Direct Method

Consider Equation (7) which is repeated here forconvenience

Y e(t) = i(t) + b(t-h)

Assume there are m connections of the grounding systemto the rest of the system. Let the vector eA(t) repre-sent the voltages at the interconnections. Equation(7) can be rearranged in the following form:

FYAA yAB1 eA(t)l bA(t-h)l iA(tTh BA BBJ eB(t)j bB(t-h) BL 0 (18)

The form of the vector i(t) should be obvious sincecurrent injections will occur only at the connections.

From the last equations, the vector e (t) can beeliminated to yield: B

(YAA YABYBBYBA)eA(t) bA(t-h)-1

AY

B b (t-h) + i (t)ABYBB B A (19)

Above equation can be directly interfaced with theEMTP. If for simplicity it is assumed that the mat isconnected with only one connector to the overhead skywire, above equation is a scalar equation. In thiscase it represents the equivalent circuit of Figure 9.Note that in above representation, the equivalent cur-rent source Ieq(t-h) needs to be computed at each iter-ation.

assumed that there is only one connection of thegrounding system to the system. Generalization istrivial.

The step response of the grounding system is com-puted with the methodology of this paper. Figure 10illustrates the response s(t) to a unit step voltage inthe middle of a 10 x 10 mesh ground mat. If a timedependent voltage V(t) is applied to the mat, the elec-tric current response will be [11].

i(t) = V(t) s(0) +f v(t-T) ds(T) dT

0o

(20)

For numerical calculations, above expression canbe written as:

N

where

i(t) = v(t) s(0) + I v(t - kAT) d(kA)k=0 dT

(21)

N =t

NTor

i(t) =v(t) [s(0)+ ds (°) ]+ E v (t-kAT) ls(kA AT (22)dt k=l O

LetN

I (t-h) = E v(t - kA,) ds(kAT) ATk=l d

(23)

and observe that it depends on past time values of thevoltage and the known function s(t). Now above expres-sion represents the equivalent circuit of Figure 11.Obviously, this circuit can be interfaced with theEMTP. In this approach, at every time step the quanti-ty Ic(t-h) need to be computed with a numerical convo-lution. The computation of this convolution can beperformed much more efficiently than the computation ofIe (t-h) in the previous approach. Explicit expres-si ns of the linear convolutions are developed next.

I ~~~~~~~~~~~.- _.to system

I(t-h) t ',GC

G gms(O) + dS(O ATdi

IC(t-h) z: I v(t-kat) -sdskr) ArTk=1 1

6.2. Linear-Convolutions

This method requires the knowledge of the step orimpulse response of the grounding system. The methodhas' been successfully applied to model lossy transmis-sion lines in the EMTP program [111. The method will bedemonstrated assuming knowledge of the step response ofthe grounding system. For simplicity, it will also be

Figure 11. Equivalent Circuit Representation of a GroundingSystem Compatible with EMTP (Convolution Approach).

Page 8: Transient analysis of grounding systems

396

Let the step response, s(t), of the system be ap-proximated with a piecewise linear function as in Fig-ure 10. The function is defined with a number, m, ofpoints: (t.,s(t.)), i=1,2,...,m . For usual ground-ing systems he step response can be accurately approx-imated with a maximum of 20 linear segments (m=20).

ds(kATr)In this case, the derivative of Equation(23) will be constant for an4_RWte val of time t. < t <

t.11 i=1,29 . .. ,m-1. Let d'-aT 1 for t. < t <t1. Then Equation (23) becomes:

m-1

Ic(t-h) = I ai I v(t-k AT) AThere Iite eoi=l kEI v

where I. is the set of index k values such that

De f ine

Then

(24)

ti < kAT < ti+l

Ei(t) = I v(t-kAT)k£l.

I

(25)

m-i

IC(t-h) = a. E.(t) AT(26)

i=1

At every iteration the quality Ei(t) is updated with

Ei(t+h) = Ei(t) + v(t + h - t.) - v(t + h - ti+)

and the equivalent current source I C(t-h) is computedwith Equation (26). Equation (26) requires only m-1multiplications and thus is very efficient.

7. CONCLUSIONS

This paper presents an efficient finite elementanalysis methodology for the computation of the trans-ient response of grounding systems. The parameters of

the finite elements are rigorously computed from thesolution of Laplace's equation. Predicted character-istics of grounding systems with the developed modelare in agreement with experimental data.

Major conclusions reached are summarized as fol-lows: (a) The 60 Hz reactance of medium size substa-tion grounding systems is substantial. In larger sys-

tems the reactance may be the largest component of theimpedance. (b) Overvoltages resulting from directstrokes on substations depend strongly on ground matconductor separation, stroke rise time, soil resistivi-ty and permittivity and others. Further studies are

under way to investigate the dependence of 60 cycleimpedance and surge overvoltages on grounding systemsparameters.

The developed models and computer program is com-

patible with the EMTP program of BPA. Two schemes are

described for interfacing these models with the EMTP.

8. REFERENCES

1. R. Rudenberg, "Grounding Principles and Practice,Part I - Fundamental Considerations on Ground Cir-

cuits," Electrical-Engineering, Vol. 64, No. 1,pp. 1-13, January 1945.

2. L. V. Bewley, "Theory and Tests of the Counter-poise," Electrical-Engineering, Vol. 53, pp. 1163-1172, August 1934.

3. E. D. Sunde, "Surge Characteristics of a BuriedBare Wire," AIEE Transactions, Vol. 59, pp. 987-991, 1940.

4. R. Verma, D. Mukhedkar, "Fundamental Considera-tions and Impulse Impedance of Grounding Grids,"IEEE -Transactions on-Power-Apparatus-and- Systems,Vol. PAS-100, No. 3, pp. 1023-1030, March 1981.

5. R. Verma, D. Mukhedkar, "Impulse Impedance of Bur-ied Ground Wire," IEEE-Transactions- on- Power -Ap-paratus -and- Systems, Vol. PAS-99, No. 5, pp.2003-2007, September/October 1980.

6. E. J. Rogers, "Impedance Characteristics of LargeTower Footings to a 100 s Wide Square Wave ofCurrent," IEEE -Transactions -on -Power Apparatus- andSystems, Vol. PAS-100, No. 1, p. 66-71, January1981.

7. B. R. Gupta, B. Thapar, "Impulse Impedance ofGrounding Grids," IEEE Transactions- on -Power -Ap-paratus -and Systems, Vol. PAS-99, No. 6, pp.2357-2362, November/December 1980.

8. P. L. Bellaschi, "Impulse and 60-Cycle Character-istics of Driven Grounds, Part I," AIEE- Transac-tions, Vol. 60, pp. 123-128, March 1941.

9. P. L. Bellaschi, R. E. Armington, and A. E.Snowden, "Impulse and 6o-Cycle Characteristics ofDriven Rods, Part II," AIEE- Transac-tions, Vol.61, pp. 349-363, 1942.

10. P. L. Bellaschi, R. E. Armington, "Impulse and 60-Cycle Characteristics of Driven Grounds, PartIII," AIEE-Transactions, Vol. 62, pp. 334-345,1943.

11. A. Ametani, "A Highly Efficient Method for Calcu-lating Transmission Line Transients," IEEE -Trans-actions on Power Apparatus -and-Syst-ems, Vo1. PAS-95, no. 5, pp. 1545-1551, September/October 1976.

12. I. D. Lu, R. M.Shier, "Application of a DigitalSignal Analyzer to the Measurement of Power SystemGround Impedances," IEEE Transactions -on Power Ap-paratus and- -Systems, Vol. PAS-100 , No. 4 , pp.1918-1922, April 1981.

13. A. P. Meliopoulos, R. P. Webb, and E. B. Joy,"Analysis of Grounding Systems," IEEE Transac-tions on Power -Apraratus- -and -Systems, Vol. PAS-100, no. 3, pp. 1039-1048, March 1981.

14. H. W. Dommel, "Digital Computer Solution of Elec-tromagnetic Transients in Single and MultiphaseNetworks, " IEEE- Trans-act-ions- on - Power- -Apparatusand Systems, Vol. PAS-88, No. 4, pp. 388-399,April 1969.

15. R. Kosztaluk, M. Loboda, D. Mukhedkar, "Experimen-tal Study of Transient Ground Impedances," Paper81 SM 399-5, presented at the 1981 IEEE-PES SummerMeeting, Portland, Oregon, 1981.

APPENDIX

The Equations (6a) and (6b) of the past historyequivalent currents are derived in this appendix. Con-sider the resistive equivalent circuit of iFigure 4.T4e past history equivalent current sources Ik(t-T) andI (t-T) result from Bergeron's method [14]:

Page 9: Transient analysis of grounding systems

II(t-) = - k1( tU) kmi( t ')

I (t-T) = - Z ek(t-T) - i (t-T)Z m mk0

397

=1 1mkl Z ++A2 - (Ar )2

0

The circuit of Figure 4 also satisfies the followingrelationships:

k ( t-T) =ek ( t- [) - 21 i Ct--u)ek(-T ekt) 2 km

(-(A+Ar(Ag)2 Ar°mfk2 (2 8 2Z20

(1 + g)2_ Ar )20

I~~~~~~re (t-T) = i (t--) - i (t--u)

km km 2 mk

= (1 A+ A Ak(-l g k-k(t r) (1+ -) i Ct--) -g (t-T)km km 24 km

+~~rAg) Age t0

mk ~~4 mk 2 m

e'(t) I

ikCt) =- --+ I(Ct--u)mk Z m0

el jt)i km(t + Ik(t)

0

Upon elimination of the variables ik (t), imk(t),ek(t), and em(t):

____ ~~Ar ek(t)A(1+ )imk(t) + k (t) = + g e (t) + I (t-u)

o 0~~~0o o

where

m(Ct-i=) -.1 eC(t-i) + 2 e t-l)m Z 2 k0

+i2 (t--)2Z "

0

-(1 +L4) imCt--u)+km

IkCt-1) =-.1 e (t-T) + g e (t-T)k ~z k m0

+ r iCt-l)2Z km

0

- (1+L ) i+ Ct-u)4 m

Solution of above equations in terms of ik(t), ;km(t)yields

imk ( t) a°mkl em( t) + amk2ek (t

mk3 mk mk4k

Ol~ _Ockml mk2

km2 mkl

°'mk3= (1+ AA+

1 (Ar0

Ar12Z (1+ ArAg)2 (r )24 - 2Zw)

0

km3 mk4

0km4 O'mk3Above relationships are realized with the equivalentresistive companion network of Figure A.1. The ele-ments of this network are:

Rkm = -l/%k2Rk = l(/Cmkl +amk2

R = Rkmk

ICmm(t--u) = amk3 mC(t-u[) + amk4Ik ( T)

Ikk(t- T) = km3Im(t- I) + amk4Ik( t-I)

ORkm®1,<Ikk(t--T) Rk Rmn (t-mmf)

Figure A.1 Equivalent Resistance Companion Networkfor a Finite Element of Earth Embedded Conductor.

km(t) =akmlem() °akm2ek (t)+ akm3Im(t1) + ctkm4Ik(tr-)

where:

Page 10: Transient analysis of grounding systems

398

Discussion

Eldon J. Rogers (Bonneville Power Administration, Vancouver, WA):The authors are to be congratulated for developing techniques tocalculate the grounding-complex impedance characteristics during im-pulse, transient and fault current flow. Has the author's had confirma-tion of their method from staged fault tests on a large EHV groundinggrid? It is interesting to note that the 60Hz impedance calculated forgrounding grid C is only 1.024 times its d.c. resistance with a phaseangle of 12.40. This increace in impedance is negligible. During arecently staged in-station single line to ground fault test of a large230/500kV grounding grid (area 69,450m2) phase angle between gridvoltage and earth current was estimated to be 100 lagging. Thus, thereactive component of grid impedance (0.14 ohms) was not significant.However, the high frequency impedance of grid conductors was signifi-cant. At fault initiation, near voltage peak, the transient potential riseof the current insertion point on the grid was 9kV. Yet, potential dif-ferences to phone company cables terminating 150m away were verysmall. This corresponds to the work of Gupta and Thaper [7] (and myexperience) that high frequency grid impedance is confined to a smallarea on the grid located around the point of current insertion.Would the author's comment on the difference between their

theoretical calculation of the transient response of a buried horizontalconductor (Fig 5), the theoretical work of Sunde [3] and the discussionof references [2] and [3] by Hagenguth? For a 9.2ns rise time step func-tion of current the measured impedance of a buried wire starts at zero,increases in 29ns to its maximum 57 ohms than decreases to below thelow frequency impedance, finally rising to its low frequency impedance(Refer to discussion of [5] by E. Rogers). This characteristic wouldfollow even for a current step with zero rise time.The authors in determining grid impedance characteristics have in-

serted the current at grid center. Field measurements on actual grids aremade by current insertion either at a grid corner or at the center of oneside. Assuming a very remote current probe, what effect on measuredgrid impedance (resistance and reactance) will these locations have?

Manuscript received August 10, 1982.

E. P. Dick, (Ontario Hydro, Toronto, Ontario, Canada: The authorshave achieved the* development of a relatively simple model for therather involved electromagnetic behavior of grounding systems.However, to confirm the validation of the model, more commentaryshould have been included regarding many of the assumptions made inthe paper:

1. Vs in equation (1) appears to assume the soil is non-conductive.This may be reasonable for frequencies such that wc >> 5, sayabove 10 MHz.

2. AL in (4) must assume either zero soil conductivity or dc condi-tions since skin effect is neglected. In typical soil, L would be fair-ly frequency dependent, decreasing by 50% between 60 Hz and 1MHz.

3. Ar in Figure 2 seems not to include earth return resistance, whichtypically dominates conductor resistance above 200 Hz and isalmost linearly frequency dependent .

4. Equation (2) appears to assume that e is zero in air. The resultingerror may in fact be minor for large EQ.

5. The model assumes no mutual impedance between elements. In-ductive or earth return resistive coupling would seem to be signifi-cant for frequencies such that the skin depth is greater than thespacing of grid conductors, say below 600 KHz. Capacitive orconductive coupling might be significant at higher frequencies.

Can the authors estimate the relative error resulting from each of theseassumptions?Due to the uncretainty of these assumptions, and their significance,

the model should be verified experimentally. The model "tests" of sec-tion 5 could have included more confirmation with the data ofreferences [3-10]. Although agreement with [121 is claimed, a maximumphase angle of 450 was measured (which may be related to the surge im-pedance of a buried line, with phase angles for series Z of 900 and shuntY of 00). However, in Table 2B, Mat C, the reactance has passedresistance at 300 Hz with no indication the X/R is levelling off. Do theauthors intend to do further testing of this model?

Finally, comments by the authors would be appreciated on thefollowing:

1. Why would Mat B with more parallel conductors have a higher in-ductance than Mat A?

2. Are the exponents correct in the Section 5 equation for ib(t)?3. Shouldn't- the term "finite element" be reserved for variational

methods? "Lumped element" is suggested.4. Could the program calculate the maximum electric field in the soil

so that non-linear ionization effects may be anticipated?

Manuscript received August 11, 1982.

A. P. Meliopoulos and M. G. Moharam: The authors are appreciativeof the comments and questions raised by the discussors. Before attemp-ting to answer specific questions, we would like to make the followinggeneral comment. In the development of the model for the prediction ofthe transient response of grounding systems, emphasis was placed onsimplicity and practicality. Thus many questions raised by thediscussors are legitimate and in our opinion their discussion is avaluable compliment of the paper. However, discussion of all points indeserving detail will make this closue unacceptably long. For this reasononly a brief discussion is offered.Mr. Dick raises five interesting points. We will respond to each one

individually.With all due respect we disagree with Mr. Dick's first comment that

equation (1) of the paper implies that the soil is nonconductive. Equa-tion (1) is in agreement with the early work of Bewley [4] and Sunde [3]who have shown that:

(a) For a conductor half buried at the surface of the earth

cIV-0

r r

(b) For a conductor deeply buried in earch

C0

r r

In addition, Bewley has reported (reference [4] of paper) thatmeasurements of speed of propagation with an ingenius schemedeveloped by E. J. Wade have resulted in verification of equation (1).Mr. Dick's second point is correct. However, the method can accom-modate the frequency dependence of the inductance AL in equation (4)at the expense of computer time. To this purpose the lossless transmis-sion line of Figure 3 of the paper must be treated as a line with frequen-cy dependent parameters. The pertinent equations can be obtainedfrom the work of Sunde (reference [3] of the paper). This procedure willresult in an equivalent circuit similar to that of Figure 4 of the paperwith the only difference that the "past history" current sources Ik(t-T)and Im(t-T) must be computed with a convolution operation. This ap-proach was ruled out as computationally impractical., However, aftermuch thought, we are presently investigating this procedure working onthe highly efficient scheme for the computation of the required con-volutions.With respect to point 3 that Ar in Figure 3 of the paper should include

the earth return resistance we would like to point out that the earthreturn resistance is treated separately. In Figure 3 the earth returnresistance will be the series combination of the two conductances ofAg/2. In fact the model is more complex because there are mutual con-ductances between any two finite segments which are not shown.Mr. Dick suspects that equation (2) of the paper implies that the air

permittivity is zero. This is not true. Equation (2) results directly fromMaxwell's equations and as such is as accurate as Maxwell's equationthemselves. The question that may be raised with regard to equation (2)is how accurate is the computation of the conductance Ag. The onlyassumption employed is the computation of Ag is that the length of thefinite segment is much larger than its diameter, which is met in practicalgrounding systems.The model as presented in the paper does not consider mutual im-

pedance between elements. In a previous investigation, it has beenfound that exclusion of mutual impedance resulted in an error of 20%.In the interest of obtaining a simple model the error has been tolerated.Presently, work is underway with the full model (considering mutualimpedance between elements) with the objective of decreasing the com-putational requirements of the model.

Presently, we do not have an explanation why mat B with more

parallel conductors has a higher inductance than mat A. The exponentsin section 5 for the surge current ib(t) are incorrect. It should read

Page 11: Transient analysis of grounding systems

i (t) = 1.1152(e- 04t - e1*8t )kA

399in the first 10 to 30 nanoseconds of an impeding wave. With referenceto the example cited by Mr. Rogers, our model will assume that the im-pedance of a buried wire to a 9.2 its rise time step function will start atits maximum (57 ohms) then decrease to below the low freciuencv im-

We appreciate the observation. The method can calculate the maximum pedance and finaly will gradually rise to its low frequerelectric field in the soil so that nonlinear ionization effects may be an- (b) The frequency dependence of both the earth return rticipated. Ag, and the conductor resistance, Ar, is not modeled (seeThe answer to the question of Messrs Dick and Rogers whether tests paper). At this point we would like to offer a clarificati

were performed to validate the model is yes. Tests were performed on a ferences are not due to model shortcomings. They wereGeorgia Power Company substation [16]. However the only reliable order to minimize the computational requirements of thmeasurement related to the model of this paper was the measurement of has already been mentioned (see discussion of point 2),the phase angle of the substation impedance at 60 Hz. It was 90 versus be extended to incorporate both these effects at the ex70 predicted by the model. The point of current injection was near the tional computer time. As a matter of fact, we are pre:center of the ground mat. The reported measurement by Mr. Rogers is towards this end.most interesting. The measured phase angle of 100 at 60 Hz depends on Finally, at the present time we have not completed an i]soil resistivity, point of current insertion and grid size. Unfortunately, the effects of point of current insertion on measures grMr. Rogers does not provide all these data. On the basis of our model, Therefore, we cannot offer any comments at this time.our guess would be that the substation is located in soil of approximate-ly 1000 ohm-meters and the point of current insertion at the peripheryof the ground mat. In any case we would like to obtain more data and REFERENCEcompare these measurements to our model. Regarding Mr. Roger'scomment that the high frequency grid impedance is confined to a small 16. S. G. Patel, "Field Measurements at Texas Valle)area on the grid, we totally agree. As a matter of fact, careful examina- Proceedings of the Workshop on High Voltage Ition of Figure 6 of the paper exemplifies exactly this coment. Grounding, Georgia Institute of Technology, AtlaiThe major differences between our model and the theoretical work of 12-14, 1982.

Sunde [31 and the discussion of references [2] and [3] by Hagenguth aretwo: (a) our work does not model the behavior of the buried conductor Manuscript received September 21, 1982.

ncy impedance.path resistance,Figure 3 of theion. These dif-e introduced inle model. As itthe model cancpense of addi-sently working

investigation ofrid impedance.

y Substation,"Power Systemsnta, GA, May