Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao Indian Institute of Technology Madras Transformers 1 Introduction Michael Faraday propounded the principle of electro-magnetic induction in 1831. It states that a voltage appears across the terminals of an electric coil when the flux linked with the same changes. The magnitude of the induced voltage is proportional to the rate of change of the flux linkages. This finding forms the basis for many magneto electric machines. The earliest use of this phenomenon was in the development of induction coils. These coils were used to generate high voltage pulses to ignite the explosive charges in the mines. As the d.c. power system was in use at that time, very little of transformer principle was made use of. In the d.c. supply system the generating station and the load center have to be necessarily close to each other due to the requirement of economic transmission of power. Also the d.c. generators cannot be scaled up due to the limitations of the commutator. This made the world look for other efficient methods for bulk power generation and transmis- sion. During the second half of the 19th century the alternators, transformers and induction motors were invented. These machines work on alternating power supply. The role of the transformers became obvious. The transformer which consisted of two electric circuits linked by a common magnetic circuit helped the voltage and current levels to be changed keeping the power invariant. The efficiency of such conversion was extremely high. Thus one could choose a moderate voltage for the generation of a.c. power, a high voltage for the transmis- sion of this power over long distances and finally use a small and safe operating voltage at the user end. All these are made possible by transformers. The a.c. power systems thus got well established. 1

Upload: others

Post on 07-Oct-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

Transformers

1 Introduction

Michael Faraday propounded the principle of electro-magnetic induction in 1831.

It states that a voltage appears across the terminals of an electric coil when the flux linked

with the same changes. The magnitude of the induced voltage is proportional to the rate of

change of the flux linkages. This finding forms the basis for many magneto electric machines.

The earliest use of this phenomenon was in the development of induction coils. These coils

were used to generate high voltage pulses to ignite the explosive charges in the mines. As

the d.c. power system was in use at that time, very little of transformer principle was made

use of. In the d.c. supply system the generating station and the load center have to be

necessarily close to each other due to the requirement of economic transmission of power.

Also the d.c. generators cannot be scaled up due to the limitations of the commutator. This

made the world look for other efficient methods for bulk power generation and transmis-

sion. During the second half of the 19th century the alternators, transformers and induction

motors were invented. These machines work on alternating power supply. The role of the

transformers became obvious. The transformer which consisted of two electric circuits linked

by a common magnetic circuit helped the voltage and current levels to be changed keeping

the power invariant. The efficiency of such conversion was extremely high. Thus one could

choose a moderate voltage for the generation of a.c. power, a high voltage for the transmis-

sion of this power over long distances and finally use a small and safe operating voltage at

the user end. All these are made possible by transformers. The a.c. power systems thus got

well established.

1

Page 2: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

Transformers can link two or more electric circuits. In its simple form two electric

circuits can be linked by a magnetic circuit, one of the electric coils is used for the creation

of a time varying magnetic filed. The second coil which is made to link this field has an

induced voltage in the same. The magnitude of the induced emf is decided by the number

of turns used in each coil. Thus the voltage level can be increased or decreased by changing

the number of turns. This excitation winding is called a primary and the output winding

is called a secondary. As a magnetic medium forms the link between the primary and the

secondary windings there is no conductive connection between the two electric circuits. The

transformer thus provides an electric isolation between the two circuits. The frequency on

the two sides will be the same. As there is no change in the nature of the power, the re-

sulting machine is called a ‘transformer’ and not a ‘converter’. The electric power at one

voltage/current level is only ‘transformed’ into electric power, at the same frequency, to an-

other voltage/current level.

Even though most of the large-power transformers can be found in the power systems,

the use of the transformers is not limited to the power systems. The use of the principle

of transformers is universal. Transformers can be found operating in the frequency range

starting from a few hertz going up to several mega hertz. Power ratings vary from a few

milliwatts to several hundreds of megawatts. The use of the transformers is so wide spread

that it is virtually impossible to think of a large power system without transformers. Demand

on electric power generation doubles every decade in a developing country. For every MVA

of generation the installed capacity of transformers grows by about 7MVA. These figures

show the indispensable nature of power transformers.

2

Page 3: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

2 Basic Principles

As mentioned earlier the transformer is a static device working on the principle of

Faraday’s law of induction. Faraday’s law states that a voltage appears across the terminals

of an electric coil when the flux linkages associated with the same changes. This emf is

proportional to the rate of change of flux linkages. Putting mathematically,

e =dψ

dt(1)

Where, e is the induced emf in volt and ψ is the flux linkages in Weber turn. Fig. 1 shows a

Figure 1: Flux linkages of a coil

coil of N turns. All these N turns link flux lines of φ Weber resulting in the Nφ flux linkages.

In such a case,

ψ = Nφ (2)

and

e = Ndφ

dtvolt (3)

The change in the flux linkage can be brought about in a variety of ways

• coil may be static and unmoving but the flux linking the same may change with time.

3

Page 4: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

• flux lines may be constant and not changing in time but the coil may move in space

linking different value of flux with time.

• both 1 and 2 above may take place. The flux lines may change in time with coil moving

in space.

These three cases are now elaborated in sequence below, with the help of a coil with a simple

geometry.

L

B

X

+-

Figure 2: Static coil

Fig. 2 shows a region of length L m, of uniform flux density B Tesla, the

flux lines being normal to the plane of the paper. A loop of one turn links part of this flux.

The flux φ linked by the turn is L ∗B ∗X Weber. Here X is the length of overlap in meters

as shown in the figure. If now B does not change with time and the loop is unmoving then

no emf is induced in the coil as the flux linkages do not change. Such a condition does not

yield any useful machine. On the other hand if the value of B varies with time a voltage is

induced in the coil linking the same coil even if the coil does not move. The magnitude of B

4

Page 5: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

is assumed to be varying sinusoidally, and can be expressed as,

B = Bm sinωt (4)

where Bm is the peak amplitude of the flux density. ω is the angular rate of change with

time. Then, the instantaneous value of the flux linkage is given by,

ψ = Nφ = NLXBm sinωt (5)

The instantaneous value of the induced emf is given by,

e =dψ

dt= Nφm.ω cosωt = Nφm.ω. sin(ωt+

π

2) (6)

Here φm = Bm.L.X. The peak value of the induced emf is

em = Nφm.ω (7)

and the rms value is given by

E =Nφm.ω√

2volt.

Further, this induced emf has a phase difference of π/2 radian with respect to the

flux linked by the turn. This emf is termed as ‘transformer’ emf and this principle is used

in a transformer. Polarity of the emf is obtained by the application of Lenz’s law. Lenz’s

law states that the reaction to the change in the flux linkages would be such as to oppose

the cause. The emf if permitted to drive a current would produce a counter mmf to oppose

this changing flux linkage. In the present case, presented in Fig. 2 the flux linkages are

assumed to be increasing. The polarity of the emf is as indicated. The loop also experiences

a compressive force.

Fig. 2(b) shows the same example as above but with a small difference. The flux

density is held constant at B Tesla. The flux linked by the coil at the current position is

5

Page 6: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

φ = B.L.X Weber. The conductor is moved with a velocity v = dx/dt normal to the flux,

cutting the flux lines and changing the flux linkages. The induced emf as per the application

of Faraday’s law of induction is e = N.B.L.dx/dt = B.L.v volt.(Here N=1)

Please note,the actual flux linked by the coil is immaterial. Only the change in the

flux linkages is needed to be known for the calculation of the voltage. The induced emf is

in step with the change in ψ and there is no phase shift. If the flux density B is distributed

sinusoidally over the region in the horizontal direction, the emf induced also becomes sinu-

soidal. This type of induced emf is termed as speed emf or rotational emf, as it arises out of

the motion of the conductor. The polarity of the induced emf is obtained by the application

of the Lenz’s law as before. Here the changes in flux linkages is produced by motion of the

conductor. The current in the conductor, when the coil ends are closed, makes the conductor

experience a force urging the same to the left. This is how the polarity of the emf shown in

fig.2b is arrived at. Also the mmf of the loop aids the field mmf to oppose change in flux

linkages. This principle is used in d.c machines and alternators.

The third case under the application of the Faraday’s law arises when the flux changes

and also the conductor moves. This is shown in Fig. 2(c).

The uniform flux density in space is assumed to be varying in magnitude in time as

B = Bm sinωt. The conductor is moved with a uniform velocity of dx

dt= v m/sec. The

change in the flux linkages and hence induced emf is given by

e = N.d(Bm. sinωt.L.X)

dt= N.L.X.Bm.ω. cosωt.+N.Bm. sinωt.L.

dx

dtV olt. (8)

6

Page 7: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

The first term is due to the changing flux and hence is a transformer emf. The second

term is due to moving conductor or is a speed emf. When the terminals are closed such as

to permit a current the conductor experiences a force and also the mmf of the coil opposes

the change in flux linkages. This principle is used in a.c. machines where the field is time

varying and conductors are moving under the same.

The first case where there is a time varying field and a stationary coil resulting in

a transformer emf is the subject matter in the present section. The case two will be re-

visited under the study of the d.c machines and synchronous machines. Case three will be

extensively used under the study of a.c machines such as induction machines and also in a.c.

commutator machines.

Next in the study of the transformers comes the question of creating a time varying

filed. This is easily achieved by passing a time varying current through a coil. The winding

which establishes the field is called the primary. The other winding, which is kept in that

field and has a voltage induced in it, is called a secondary. It should not be forgotten that

the primary also sees the same time varying field set up by it linking its turns and has an

induced emf in the same. These aspects will be examined in the later sections. At first

the common constructional features of a transformer used in electric power supply system

operating at 50 Hz are examined.

7

Page 8: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

3 Constructional features

Transformers used in practice are of extremely large variety depending upon the

end use. In addition to the transformers used in power systems, in power transmission and

distribution, a large number of special transformers are in use in applications like electronic

supplies, rectification, furnaces, traction etc. Here the focus is on power transformers only.

The principle of operation of these transformers also is the same but the user requirements

differ. Power transformers of smaller sizes could be air cooled while the larger ones are

oil cooled. These machines are highly material intensive equipments and are designed to

match the applications for best operating conditions. Hence they are ‘tailor made’ to a

job. This brings in a very large variety in their constructional features. Here more common

constructional aspects alone are discussed. These can be broadly divided into

1. Core construction

2. Winding arrangements

3. Cooling aspects

3.1 Core construction

Transformer core for the power frequency application is made of highly permeable

material. The high value of permeability helps to give a low reluctance for the path of

the flux and the flux lines mostly confine themselves to the iron. Relative permeability µr

well over 1000 are achieved by the present day materials. Silicon steel in the form of thin

laminations is used for the core material. Over the years progressively better magnetic prop-

erties are obtained by going in for Hot rolled non-oriented to Hot rolled grain oriented steel.

8

Page 9: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

Later better laminations in the form of cold Rolled Grain Oriented (CRGO), -High B (HiB)

grades became available. The thickness of the laminations progressively got reduced from

over 0.5mm to the present 0.25mm per lamination. These laminations are coated with a thin

layer of insulating varnish, oxide or phosphate. The magnetic material is required to have

a high permeability µ and a high saturation flux density, a very low remanence Br and a

small area under the B-H loop-to permit high flux density of operation with low magnetizing

current and low hysteresis loss. The resistivity of the iron sheet itself is required to be high

to reduce the eddy current losses. The eddy current itself is highly reduced by making the

laminations very thin. If the lamination is made too thin then the production cost of steel

laminations increases. The steel should not have residual mechanical stresses which reduce

their magnetic properties and hence must be annealed after cutting and stacking.

In the case of very small transformers (from a few volt-amperes to a few kilo volt-

amperes) hot rolled silicon steel laminations in the form of E & I, C & I or O as shown in

Fig. 3 are used and the core cross section would be a square or a rectangle. The percentage

of silicon in the steel is about 3.5. Above this value the steel becomes very brittle and also

very hard to cut. The saturation flux density of the present day steel lamination is about 2

Tesla.

Broadly classifying, the core construction can be separated into core type and

shell type. In a core type construction the winding surrounds the core. A few examples of

single phase and three phase core type constructions are shown in Fig. 4. In a shell type on

the other hand the iron surrounds the winding.

In the case of very small transformers the conductors are very thin and round.

These can be easily wound on a former with rectangular or square cross section. Thus no

special care is needed for the construction of the core. The cross section of the core also

would be square or rectangular. As the rating of the transformer increases the conductor size

9

Page 10: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

(a ) (b)

(c)

Figure 3: E and I,C and I and O Type Laminations

10

Page 11: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

HV LVHVLV

coreHVLV

Single phase Three phase

1.phase

3.phase

(a)Core type (b) Shell type

Figure 4: Core and Shell Type Construction

also increases. Flat conductors are preferred to round ones. To wind such conductor on a

rectangular former is not only difficult but introduces stresses in the conductor, at the bends.

From the short circuit force with stand capability point of view also this is not desirable.

Also, for a given area enclosed the length of the conductor becomes more. Hence it results in

more load losses. In order to avoid all these problems the coils are made cylindrical and are

wound on formers on heavy duty lathes. Thus the core construction is required to be such as

to fill the circular space inside the coil with steel laminations. Stepped core construction thus

becomes mandatory for the core of large transformers. Fig. 5 shows a few typical stepped core

constructions. When the core size increases it becomes extremely difficult to cool the same

(Even though the core losses are relatively very small). Cooling ducts have to be provided

in the core. The steel laminations are grain oriented exploiting the simple geometry of the

transformer to reduce the excitation losses. The iron losses in the lamination, when the flux

11

Page 12: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

d d dduct

duct

0.71D

0.160.16

0.1 0.1

0.53

0.14 0.14

0.42

0.12 0.120.09 0.09

0.07 0.07

0.3

Figure 5: Stepped Core Construction

12

Page 13: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

is oriented in the direction of grain orientation, is about 30% of that in the normal direction.

Another important aspect to be carefully checked and monitored is the air gaps in

Windings

Core

Path of

flux

LV

HV

(a) (b)

Figure 6: Typical stacked Core and wound core Construction

series in the path of the main flux. As the reluctance of air path is about 1000 times more

than that of the steel, an air path of 1mm will require a mmf needed by a 1 meter path in iron.

Hence butt joints between laminations must be avoided. Lap joints are used to pro-

vide alternate paths for flux lines thus reducing the reluctance of the flux paths. Some typical

constructional details are shown in Fig. 6. In some power transformers the core is built up

by threading a long strip of steel through the coil in the form of a toroid. This construction

is normally followed in instrument transformers to reduce the magnetizing current and hence

the errors.

13

Page 14: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

Large cores made up of laminations must be rendered adequately stiff by the provi-

sion of stiffening plates usually called as flitch plates. Punched through holes and bolts are

progressively being avoided to reduce heating and melting of the through bolts. The whole

stack is wrapped up by strong epoxy tapes to give mechanical strength to the core which

can stand in upright position. Channels and angles are used for the frame and they hold the

bottom yoke rigidly.

3.2 Windings

Windings form another important part of transformers. In a two winding trans-

former two windings would be present. The one which is connected to a voltage source and

creates the flux is called as a primary winding. The second winding where the voltage is

induced by induction is called a secondary. If the secondary voltage is less than that of the

primary the transformer is called a step down transformer. If the secondary voltage is more

then it is a step up transformer. A step down transformer can be made a step up transformer

by making the low voltage winding its primary. Hence it may be more appropriate to desig-

nate the windings as High Voltage (HV) and Low Voltage (LV) windings. The winding with

more number of turns will be a HV winding. The current on the HV side will be lower as

V-I product is a constant and given as the VA rating of the machines. Also the HV winding

needs to be insulated more to withstand the higher voltage across it. HV also needs more

clearance to the core, yoke or the body. These aspects influence the type of the winding

used for the HV or LV windings.

Transformer coils can be broadly classified in to concentric coils and sandwiched

coils Fig. 7. The former are very common with core type transformers while the latter one

14

Page 15: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

LV

HV

Core

HV LV

(a)Concentric coil

LVHV

Core

(b) Sandwich coil

Figure 7: Concentric and Sandwich Coils

15

Page 16: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

are common with shell type transformers. In the figure the letters L and H indicate the low

voltage and high voltage windings. In concentric arrangement, in view of the lower insulation

and clearance requirements, the LV winding is placed close to the core which is at ground

potential. The HV winding is placed around the LV winding. Also taps are provided on HV

winding when voltage change is required. This is also facilitated by having the HV winding

as the outer winding.

Three most common types of coils viz. helical, cross over and disc coils are shown in Fig. 8.

cross over coilsDisc coils

Helical coils

Figure 8: Disc, Crossover and Helical Coil Construction

Helical Windings One very common cylindrical coil arrangement is the helical winding.

This is made up of large cross section rectangular conductor wound on its flat side.

The coil progresses as a helix. This is commonly used for LV windings. The insulation

16

Page 17: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

requirement also is not too high. Between layers no insulation (other than conductor

insulation) is needed as the voltage between layers is low. The complexity of this

type of winding rapidly increases as the current to be handled becomes more. The

conductor cross section becomes too large and difficult to handle. The eddy current

losses in the conductor rapidly increases. Hence two or more conductors have to be

wound and connected in parallel. The parallel circuits bring in problems of current

sharing between the circuits. Transpositions of the parallel paths have to be adopted

to reduce unequal current distribution. The modern practice is to use continuously

transposed and bunched conductors.

Cross over coils The second popular winding type is the cross over coil. These are made

of circular conductors not exceeding 5 to 6 sq mm in cross section. These are used for

HV windings of relatively small transformers. These turns are wound in several layers.

The length and thickness of each block is made in line with cooling requirements. A

number of such blocks can be connected in series, leaving cooling ducts in between the

blocks, as required by total voltage requirement.

Disc coils Disc coils consist of flat conductors wound in a spiral form at the same place

spiralling outwards. Alternate discs are made to spiral from outside towards the center.

Sectional discs or continuous discs may be used. These have excellent thermal prop-

erties and the behavior of the winding is highly predictable. Winding of a continuous

disc winding needs specialized skills.

Sandwich coils Sandwich windings are more common with shell type core construction.

They permit easy control over the short circuit impedance of the transformer. By

bringing HV and LV coils close on the same magnetic axis the leakage is reduced

and the mutual flux is increased. By increasing the number of sandwiched coils the

17

Page 18: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

reactance can be substantially reduced.

3.3 Insulation

The insulation used in the case of electrical conductors in a transformer is varnish

or enamel in dry type of transformers. In larger transformers to improve the heat transfer

characteristics the conductors are insulated using un-impregnated paper or cloth and the

whole core-winding assembly is immersed in a tank containing transformer oil. The trans-

former oil thus has dual role. It is an insulator and also a coolant. The porous insulation

around the conductor helps the oil to reach the conductor surface and extract the heat. The

conductor insulation may be called the minor insulation as the voltage required to be with-

stood is not high. The major insulation is between the windings. Annular bakelite cylinders

serve this purpose. Oil ducts are also used as part of insulation between windings. The oil

used in the transformer tank should be free from moisture or other contamination to be of

any use as an insulator.

3.4 Cooling of transformers

Scaling advantages make the design of larger and larger unit sizes of transformers

economically attractive. This can be explained as below. Consider a transformer of certain

rating designed with certain flux density and current density. If now the linear dimensions

are made larger by a factor of K keeping the current and flux densities the same the core and

conductor areas increase by a factor of K2. The losses in the machine, which are proportional

to the volume of the materials used, increase by a factor of K3.The rating of the machine

increases by a factor of K4.

18

Page 19: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

The surface area however increases by a factor of K2 only. Thus the ratio of loss per

surface area goes on increasing by a factor of K. The substantial increase in the output is

the major attraction in going in for larger units. However cooling of the transformer becomes

more and more difficult. As the rating increases better cooling techniques are needed.

Simple air cooling of the transformers is adopted in dry type transformers. The limit

for this is reached by the time the rating is a few kVA. Hence air cooling is used in low

voltage machines. This method of cooling is termed as AN(Air Natural). Air Blast(AB)

method improves on the above by directing the blast of air at the core and windings. This

permits some improvement in the unit sizes.

Substantial improvement is obtained when the transformer is immersed in an oil tank.

The oil reaches the conductor surface and extracts the heat and transports the same to the

surface of the tank by convection. This is termed as ON (Oil Natural) type of cooling. This

method permits the increase in the surface available for the cooling further by the use of

ducts, radiators etc.

OB(Oil Blast) method is an improvement over the ON-type and it directs a blast of

air on the cooling surface. In the above two cases the flow of oil is by natural convective

forces. The rate of circulation of oil can be increased with the help of a pump, with the

cooling at the surface remaining natural cooling to air. This is termed as OFN (Oil Forced

Natural). If now a forced blast of air is also employed, the cooling method become OFB(

Oil Forced Blast). A forced circulation of oil through a radiator is done with a blast of air

19

Page 20: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

Tubes

Radiator

Main tank

(a)

Radiator

water inlet

water outlet

oil pump

Bushing

Conservator

& Breather

(b)

Conservator&

Breather

Radiator

Fan motorOil pump

for O.F.B

Bushing

(c)

Figure 9: Some Typical Cooling Arrangements20

Page 21: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

over the radiator surface. Substantial amount of heat can be removed by employing a water

cooling. Here the hot oil going into the radiator is cooled by a water circuit. Due to the

high specific heat of water, heat can be evacuated effectively. Next in hierarchy comes OFW

which is similar to OFB except that instead of blast of air a forced circulation of cool water

in the radiator is used in this. Some cooling arrangements are shown in Fig. 9.

In many large sized transformers the cooling method is matched with the amount

of heat that is required to be removed. As the load on the transformer changes the heat

generated within also changes. Suitable cooling method can be pressed into service at that

time. This gives rise to the concept of mixed cooling technique.

ON/OB Works as ON but with increased load additional air blast is adopted. This gives

the ratings to be in the ratio of 1:1.5

ON/OB/OFB Similarly gives the ratings in the ratio of 1:1.5:2

The temperature rise permitted in the British standard specification for power transformers

are tabulated below.

Type winding oil core

Class A Class B

◦C ◦C ◦C

AN,AB 55 75 - As

ON,OB,OW 60 - 50 for

OFN,OFB 65 - 50 adjacent

OFW 70 - 50 winding

21

Page 22: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

3.4.1 Properties of the transformer coil

Even though the basic functions of the oil used in transformers are a) heat conduc-

tion and b) electrical insulation, there are many other properties which make a particular oil

eminently suitable. Organic oils of vegetative or animal origin are good insulators but tend

to decompose giving rise to acidic by-products which attack the paper or cloth insulation

around the conductors.

Mineral oils are suitable from the point of electrical properties but tend to form sludge.

The properties that are required to be looked into before selecting an oil for transformer

application are as follows:

Insulting property This is a very important property. However most of the oils naturally

fulfil this. Therefore deterioration in insulating property due to moisture or contami-

nation may be more relevant.

Viscosity It is important as it determines the rate of flow of the fluid. Highly viscous fluids

need much bigger clearances for adequate heat removal.

Purity The oil must not contain impurities which are corrosive. Sulphur or its compounds

as impurities cause formation of sludge and also attack metal parts.

Sludge formation Thickening of oil into a semisolid form is called a sludge. Sludge for-

mation properties have to be considered while choosing the oil as the oil slowly forms

semi-solid hydrocarbons. These impede flows and due to the acidic nature, corrode

metal parts. Heat in the presence of oxygen is seen to accelerate sludge formation. If

the hot oil is prevented from coming into contact with atmospheric air sludge formation

22

Page 23: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

can be greatly reduced.

Acidity Oxidized oil normally produces CO2 and acids. The cellulose which is in the paper

insulation contains good amount of moisture. These form corrosive vapors. A good

breather can reduce the problems due to the formation of acids.

Flash point And Fire point Flash point of an oil is the temperature at which the oil

ignites spontaneously. This must be as high as possible (not less than 160◦C from the

point of safety). Fire point is the temperature at which the oil flashes and continuously

burns. This must be very high for the chosen oil (not less than 200◦C).

Inhibited oils and synthetic oils are therefore used in the transformers. Inhibited oils

contain additives which slow down the deterioration of properties under heat and moisture

and hence the degradation of oil. Synthetic transformer oil like chlorinated diphenyl has

excellent properties like chemical stability, non-oxidizing, good dielectric strength, moisture

repellant, reduced risk due fire and explosion.

It is therefore necessary to check the quality of the oil periodically and take corrective

steps to avoid major break downs in the transformer.

There are several other structural and insulating parts in a large transformer. These

are considered to be outside the scope here.

23

Page 24: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

4 Ideal Transformer

Earlier it is seen that a voltage is induced in a coil when the flux linkage associated

with the same changed. If one can generate a time varying magnetic field any coil placed in

the field of influence linking the same experiences an induced emf. A time varying field can

be created by passing an alternating current through an electric coil. This is called mutual

induction. The medium can even be air. Such an arrangement is called air cored transformer.

Indeed such arrangements are used in very high frequency transformers. Even though the

principle of transformer action is not changed, the medium has considerable influence on the

working of such devices. These effects can be summarized as the followings.

1. The magnetizing current required to establish the field is very large, as the reluctance

of the medium is very high.

2. There is linear relationship between the mmf created and the flux produced.

3. The medium is non-lossy and hence no power is wasted in the medium.

4. Substantial amount of leakage flux exists.

5. It is very hard to direct the flux lines as we desire, as the whole medium is homogeneous.

If the secondary is not loaded the energy stored in the magnetic field finds its way

back to the source as the flux collapses. If the secondary winding is connected to a load then

part of the power from the source is delivered to the load through the magnetic field as a link.

The medium does not absorb and lose any energy. Power is required to create the field and

not to maintain the same. As the winding losses can be made very small by proper choice

of material, the ideal efficiency of a transformer approaches 100%. The large magnetizing

24

Page 25: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

x

Primary

Leakage

flux

Mutual flux

Secondary

(a)

Leakage flux

Primary

Mutual flux

Secondary

Iron core

X

(b)

Figure 10: Mutual Induction a) air core b) iron core

25

Page 26: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

current requirement is a major deterrent. However if now a piece of magnetic material is

introduced to form the magnetic circuit Fig. 10(b) the situation changes dramatically. These

can be enumerated as below.

1. Due to the large value for the permeance ( µr of the order of 1000 as compared to

air) the magnetizing current requirement decreases dramatically. This can also be

visualized as a dramatic increase in the flux produced for a given value of magnetizing

current.

2. The magnetic medium is linear for low values of induction and exhibits saturation type

of non-linearity at higher flux densities.

3. The iron also has hysteresis type of non-linearity due to which certain amount of power

is lost in the iron (in the form of hysteresis loss), as the B-H characteristic is traversed.

4. Most of the flux lines are confined to iron path and hence the mutual flux is increased

very much and leakage flux is greatly reduced.

5. The flux can be easily ‘directed’ as it takes the path through steel which gives great

freedom for the designer in physical arrangement of the excitation and output windings.

6. As the medium is made of a conducting material eddy currents are induced in the

same and produce losses. These are called ‘eddy current losses’. To minimize the

eddy current losses the steel core is required to be in the form of a stack of insulated

laminations.

From the above it is seen that the introduction of magnetic core to carry the flux

introduced two more losses. Fortunately the losses due to hysteresis and eddy current for

the available grades of steel is very small at power frequencies. Also the copper losses in the

26

Page 27: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

winding due to magnetization current is reduced to an almost insignificant fraction of the

full load losses. Hence steel core is used in power transformers.

In order to have better understanding of the behavior of the transformer, initially

certain idealizations are made and the resulting ‘ideal’ transformer is studied. These ideal-

izations are as follows:

1. Magnetic circuit is linear and has infinite permeability. The consequence is that a van-

ishingly small current is enough to establish the given flux. Hysteresis loss is negligible.

As all the flux generated confines itself to the iron, there is no leakage flux.

2. Windings do not have resistance. This means that there are no copper losses, nor there

is any ohmic drop in the electric circuit.

In fact the practical transformers are very close to this model and hence no major

departure is made in making these assumptions.

Fig. 11 shows a two winding ideal transformer. The primary winding has T1 turns and is

connected to a voltage source of V1 volts. The secondary has T2 turns. Secondary can be

connected to a load impedance for loading the transformer. The primary and secondary are

shown on the same limb and separately for clarity.

As a current I0 amps is passed through the primary winding of T1 turns it sets up an

mmf of I0T1 ampere which is in turn sets up a flux φ through the core. Since the reluctance

of the iron path given by R = l/µAis zero as µ −→ ∞, a vanishingly small value of current

I0 is enough to setup a flux which is finite. As I0 establishes the field inside the transformer

27

Page 28: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

++

+

-

-

T1

T2

e1

e2

φ µ

~

8v1=V1mcosωt

io 0

+

e1

i1

+

e2

i2

+ -

v1=V1sinωt

(a)Unloaded machine (b) Circuit

form

N

++

+

-

-

T1

T2

e1

e2

φ µ 8

-

i1

i2

ZL

v1=V1cosωt

(c)Loaded machine

Figure 11: Two winding Ideal Transformer unloaded and loaded

28

Page 29: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

it is called the magnetizing current of the transformer.

F lux φ =mmf

Reluctance=I0T1

l

µA

=I0T1Aµ

l. (9)

This current is the result of a sinusoidal voltage V applied to the primary. As the

current through the loop is zero (or vanishingly small), at every instant of time, the sum of

the voltages must be zero inside the same. Writing this in terms of instantaneous values we

have,

v1 − e1 = 0 (10)

where v1 is the instantaneous value of the applied voltage and e1 is the induced emf due to

Faradays principle. The negative sign is due to the application of the Lenz’s law and shows

that it is in the form of a voltage drop. Kirchoff’s law application to the loop will result in

the same thing.

This equation results in v1 = e1 or the induced emf must be same in magnitude to

the applied voltage at every instant of time. Let v1 = V1peak cosωt where V1peak is the peak

value and ω = 2πf t. f is the frequency of the supply. As v1 = e1; e1 = dψ1/dt but

e1 = E1peak cosωt ∴ E1 = V1 . It can be easily seen that the variation of flux linkages can

be obtained as ψ1 = ψ1peak sinωt. Here ψ1peak is the peak value of the flux linkages of the

primary.

Thus the RMS primary induced emf is

e1 =dψ1

dt=d(ψ1peak sinωt)

dt(11)

= ψ1peak.ω. cosωt or the rms value (12)

E1 =ψ1peak.ω

√2

=2πfT1φm

√2

= 4.44fφmT1 volts

29

Page 30: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

Here ψ1peak is the peak value of the flux linkages of the primary. The same mutual

flux links the secondary winding. However the magnitude of the flux linkages will be ψ2peak =

T2.φm. The induced emf in the secondary can be similarly obtained as ,

e2 =dψ2

dt=d(ψ2peak sinωt)

dt(13)

= ψ2peak.ω. cosωt or the rms value (14)

E2 =2πfT2φm

√2

= 4.44fφmT2 volt

which yields the voltage ratio as

E1

E2

=T1

T2

(15)

+

-

E1

I1

V1

+

-

E2

I2

V2

Figure 12: Dot Convention

The voltages E1 and E2 are obtained by the same mutual flux and hence they are

in phase. If the winding sense is opposite i.e., if the primary is wound in clockwise sense

and the secondary counter clockwise sense then if the top terminal of the first winding is

at maximum potential the bottom terminal of the second winding would be at the peak

potential. Similar problem arises even when the sense of winding is kept the same, but the

30

Page 31: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

two windings are on opposite limbs (due to the change in the direction of flux). Hence in

the circuit representation of transformers a dot convention is adopted to indicate the ter-

minals of the windings that go high (or low) together. (Fig. 12). This can be established

experimentally by means of a polarity test on the transformers. At a particular instant of

time if the current enters the terminal marked with a dot it magnetizes the core. Similarly

a current leaving the terminal with a dot demagnetizes the core.

So far, an unloaded ideal transformer is considered. If now a load impedance ZL is

connected across the terminals of the secondary winding a load current flows as marked in

Fig. 11(c). This load current produces a demagnetizing mmf and the flux tends to collapse.

However this is detected by the primary immediately as both E2 and E1 tend to collapse.

The current drawn from supply increases up to a point the flux in the core is restored back

to its original value. The demagnetizing mmf produced by the secondary is neutralized by

additional magnetizing mmf produces by the primary leaving the mmf and flux in the core

as in the case of no-load. Thus the transformer operates under constant induced emf mode.

Thus,

i1T1 − i2T2 = i0T1 but i0 → 0 (16)

i2T2 = i1T1 and the rms value I2T2 = I1T1. (17)

If the reference directions for the two currents are chosen as in the Fig. 12, then the above

equation can be written in phasor form as,

I1T1 = I2T2 or I1 =T2

T1

.I2 (18)

AlsoE1

E2

=T1

T2

=I2I1

E1I1 = E2I2 (19)

31

Page 32: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

Thus voltage and current transformation ratio are inverse of one another. If an impedance

of ZL is connected across the secondary,

I2 =E2

ZL

or ZL =E2

I2(20)

The input impedance under such conditions is

Zi =E1

I1= (

T1

T2

)2.E2

I2= (

T1

T2

)2.ZL (21)

An impedance of ZL when viewed ‘through’ a transformer of turns ratio (T1

T2

) is seen

as (T1

T2

)2.ZL. Transformer thus acts as an impedance converter. The transformer can be

interposed in between a source and a load to ‘match’ the impedance.

E1

I1

θ1

φ

V1

E2

I2

θ2

φ

V2

Figure 13: Phasor diagram of Operation of an Ideal Transformer

Finally, the phasor diagram for the operation of the ideal transformer is shown in

Fig. 13 in which θ1 and θ2 are power factor angles on the primary and secondary sides. As

32

Page 33: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

the transformer itself does not absorb any active or reactive power it is easy to see that

θ1 = θ2.

Thus, from the study of the ideal transformer it is seen that the transformer provides

electrical isolation between two coupled electric circuits while maintaining power invariance

at its two ends. However, grounding of loads and one terminal of the transformer on the

secondary/primary side are followed with the provision of leakage current detection devices

to safe guard the persons working with the devices. Even though the isolation aspect is

a desirable one its utility cannot be over emphasized. It can be used to step up or step

down the voltage/current at constant volt-ampere. Also, the transformer can be used for

impedance matching. In the case of an ideal transformer the efficiency is 100% as there are

no losses inside the device.

33

Page 34: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

5 Practical Transformer

An ideal transformer is useful in understanding the working of a transformer. But it

cannot be used for the computation of the performance of a practical transformer due to the

non-ideal nature of the practical transformer. In a working transformer the performance as-

pects like magnetizing current, losses, voltage regulation, efficiency etc are important. Hence

the effects of the non-idealization like finite permeability, saturation, hysteresis and winding

resistances have to be added to an ideal transformer to make it a practical transformer.

Conversely, if these effects are removed from a working transformer what is left behind is an

ideal transformer.

Finite permeability of the magnetic circuit necessitates a finite value of the current

to be drawn from the mains to produce the mmf required to establish the necessary flux.

The current and mmf required is proportional to the flux density B that is required to be

established in the core.

B = µH ; B =φ

A(22)

where A is the area of cross section of the iron core m2. H is the magnetizing force which is

given by,

H = i.T1

l(23)

where l is the length of the magnetic path, m. or

φ = B.A =Aµ(iT1)

l= permeance ∗ mmf(here that of primary) (24)

The magnetizing force and the current vary linearly with the applied voltage as long

as the magnetic circuit is not saturated. Once saturation sets in, the current has to vary in

34

Page 35: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

a nonlinear manner to establish the flux of sinusoidal shape. This non-linear current can be

resolved into fundamental and harmonic currents. This is discussed to some extent under

harmonics. At present the effect of this non-linear behavior is neglected as a secondary

effect. Hence the current drawn from the mains is assumed to be purely sinusoidal and

directly proportional to the flux density of operation. This current can be represented by a

current drawn by an inductive reactance in the circuit as the net energy associated with the

same over a cycle is zero. The energy absorbed when the current increases is returned to

the electric circuit when the current collapses to zero. This current is called the magnetizing

current of the transformer. The magnetizing current Im is given by Im = E1/Xm where Xm

is called the magnetizing reactance. The magnetic circuit being lossy absorbs and dissipates

the power depending upon the flux density of operation. These losses arise out of hysteresis,

eddy current inside the magnetic core. These are given by the following expressions:

Ph ∝ B1.6f (25)

Pe ∝ B2f 2t2 (26)

Ph -Hysteresis loss, Watts

B- Flux density of operation Tesla.

f - Frequency of operation, Hz

t - Thickness of the laminations of the core, m.

For a constant voltage, constant frequency operation B is constant and so are these

losses. An active power consumption by the no-load current can be represented in the input

circuit as a resistance Rc connected in parallel to the magnetizing reactance Xm. Thus the

no-load current I0 may be made up of Ic(loss component) and Im (magnetizing component

35

Page 36: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

as )

I0 = Ic − jIm (27)

I2

cRc– gives the total core losses (i.e. hysteresis + eddy current loss)

I2

mXm- Reactive volt amperes consumed for establishing the mutual flux.

Finite µ of the magnetic core makes a few lines of flux take to a path through the air.

Thus these flux lines do not link the secondary winding. It is called as leakage flux. As the

path of the leakage flux is mainly through the air the flux produced varies linearly with the

primary current I1. Even a large value of the current produces a small value of flux. This

flux produces a voltage drop opposing its cause, which is the current I1. Thus this effect of

the finite permeability of the magnetic core can be represented as a series inductive element

jxl1. This is termed as the reactance due to the primary leakage flux. As this leakage flux

varies linearly with I1, the flux linkages per ampere and the primary leakage inductance

are constant (This is normally represented by ll1 Henry). The primary leakage reactance

therefore becomes

xl1 = 2πfll1 ohm (28)

A similar effect takes place on the secondary side when the transformer is loaded.

The secondary leakage reactance jxl2 arising out of the secondary leakage inductance ll2 is

given by

xl2 = 2πfll2 (29)

Finally, the primary and secondary windings are wound with copper (sometimes alu-

minium in small transformers) conductors; thus the windings have a finite resistance (though

36

Page 37: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

~

+

+

+

-

Rc

I2

φ

-

ZL

I’2

V2

r1

r2

I1

jXm

E1

-

V1

E2 T2

Io

jxl1

jxl2

T1

(a)Physical arrangement

r1

RcjXm

V1

Ic Im

Io

ZLV2

E1 E2

I’2I1I2

r2

jXl1

jXl2

(b)Equivalent circuit

Figure 14: A Practical Transformer

37

Page 38: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

small). This is represented as a series circuit element, as the power lost and the drop pro-

duced in the primary and secondary are proportional to the respective currents. These are

represented by r1 and r2 respectively on primary and secondary side. A practical transformer

sans these imperfections (taken out and represented explicitly in the electric circuits) is an

ideal transformer of turns ratio T1 : T2 (voltage ratio E1 : E2). This is seen in Fig. 14. I′

2

in the circuit represents the primary current component that is required to flow from the

mains in the primary T1 turns to neutralize the demagnetizing secondary current I2 due to

the load in the secondary turns. The total primary current

vectorially is I1 = I′

2+ I0 (30)

Here I′

2T1 = I2T2 or I

2= I2

T2

T1

(31)

Thus I1 = I2

T2

T1

+ I0 (32)

By solving this circuit for any load impedance ZL one can find out the performance of the

loaded transformer.

The circuit shown in Fig. 14(b). However, it is not very convenient for use due to

the presence of the ideal transformer of turns ratio T1 : T2. If the turns ratio could be made

unity by some transformation the circuit becomes very simple to use. This is done here by

replacing the secondary by a ‘hypothetical’ secondary having T1 turns which is ‘equivalent ’

to the physical secondary. The equivalence implies that the ampere turns, active and reactive

power associated with both the circuits must be the same. Then there is no change as far

as their effect on the primary is considered. Thus

V′

2= aV2, I

2=

I2

a, r

2= a2r2, x

l2= a2xl2 Z

L= a2ZL.

where a -turns ratio T1

T2

38

Page 39: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

This equivalent circuit is as shown in Fig. ??(a). As the ideal transformer in this

case has a turns ratio of unity the potentials on either side are the same and hence they

may be conductively connected dispensing away with the ideal transformer. This particular

equivalent circuit is as seen from the primary side. It is also possible to refer all the pri-

mary parameters to secondary by making the hypothetical equivalent primary winding on

the input side having the number of turns to be T2. Such an equivalent circuit having all

the parameters referred to the secondary side is shown in fig. 15.

The equivalent circuit can be derived, with equal ease, analytically using the Kir-

choff’s equations applied to the primary and secondary. Referring to fig. 14(a), we have (by

neglecting the shunt branch)

V1 = E1 + I1(r1 + jxl1) (33)

E2 = V2 + I2(r2 + jxl2) (34)

T1I0 = T1I1 + T2I2 or I1 = −I2

a+ I0 (35)

= −I2

a+ Ic + Im

a =T1

T2

.

Multiply both sides of Eqn.34 by ‘a’ [This makes the turns ratio unity and retains the power

invariance].

aE2 = aV2 + aI2(r2 + jxl2) but aE2 = E1 (36)

Substituting in Eqn.33 we have

39

Page 40: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

V1 = aV2 + aI2(r2 + jxl2) + I1(r1 + jxl1)

= V′

2+ I1(a

2r2 + ja2xl2) + I1(r1 + jxl1)

= V′

2+ I1(r1 + r

2+ jxl1 + x

l2) (37)

A similar procedure can be used to refer all parameters to secondary side. (Shown in fig. 15.)

r’1

R’c jX’

mV’1

I’o

ZLV2

jx’l1 jxl2r2

I2I’1

I’c I’m

Figure 15: Equivalent Circuit Referred to the Secondary Side

40

Page 41: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

6 Phasor diagrams

r1

RcjXmV1

Io

Z’LV’

2

jxl1 jx’l2r’2

Ic Im

I1

(a)

r1

Io

Z’L

jxl1 jx’l2r’2

I’2I1

Ic Im

jxmRcV1

V’2V’

2V1

I1R jX

I’2

R=r1+r’2

x=xl1+x’l2

I1=I’2

(b) (c)

Figure 16: Exact,approximate and simplified equivalent circuits

The resulting equivalent circuit as shown in Fig. 16 is known as the exact

equivalent circuit. This circuit can be used for the analysis of the behavior of the transform-

ers. As the no-load current is less than 1% of the load current a simplified circuit known

as ‘approximate’ equivalent circuit (see Fig. 16(b)) is usually used, which may be further

41

Page 42: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

simplified to the one shown in Fig. 16(c).

On similar lines to the ideal transformer the phasor diagram of operation can be

drawn for a practical transformer also. The positions of the current and induced emf phasor

are not known uniquely if we start from the phasor V1. Hence it is assumed that the phasor

φ is known. The E1 and E2 phasor are then uniquely known. Now, the magnetizing and loss

components of the currents can be easily represented. Once I0 is known, the drop that takes

place in the primary resistance and series reactance can be obtained which when added to

E1 gives uniquely the position of V1 which satisfies all other parameters. This is represented

in Fig. 17(a) as phasor diagram on no-load.

Next we proceed to draw the phasor diagram corresponding to a loaded transformer.

The position of the E2 vector is known from the flux phasor. Magnitude of I2 and the load

power factor angle θ2 are assumed to be known. But the angle θ2 is defined with respect

to the terminal voltage V2 and not E2. By trial and error the position of I2 and V2 are

determined. V2 should also satisfy the Kirchoff’s equation for the secondary. Rest of the

construction of the phasor diagram then becomes routine. The equivalent primary current

I′

2is added vectorially to I0 to yield I1. I1(r1 + jxl1)is added to E1 to yield V1. This is shown

in fig. 17(b) as phasor diagram for a loaded transformer.

42

Page 43: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

V1

E1

IoXl1

Ior1

Io

Im Il

φ φ

E2

(a)No-load

V1

E1

I1Xl1

I1r1

Io

I’2

Il

φ φ

E2

V2

I2

I2x2I2r2

(b)On-load

Figure 17: Phasor Diagram of a Practical Transformer

43

Page 44: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

7 Testing of Transformers

The structure of the circuit equivalent of a practical transformer is developed earlier.

The performance parameters of interest can be obtained by solving that circuit for any load

conditions. The equivalent circuit parameters are available to the designer of the transformers

from the various expressions that he uses for designing the transformers. But for a user

these are not available most of the times. Also when a transformer is rewound with different

primary and secondary windings the equivalent circuit also changes. In order to get the

equivalent circuit parameters test methods are heavily depended upon. From the analysis of

the equivalent circuit one can determine the electrical parameters. But if the temperature

rise of the transformer is required, then test method is the most dependable one. There are

several tests that can be done on the transformer; however a few common ones are discussed

here.

7.1 Winding resistance test

This is nothing but the resistance measurement of the windings by applying a small

d.c voltage to the winding and measuring the current through the same. The ratio gives

the winding resistance, more commonly feasible with high voltage windings. For low voltage

windings a resistance-bridge method can be used. From the d.c resistance one can get the

a.c. resistance by applying skin effect corrections.

44

Page 45: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

V1

V2

V3

Vs

~

A2

A1

a2

a1

V

S

+

-

+

A2

A1

a2

a1

(a)A.C.test (b)D.C.test

Figure 18: Polarity Test

7.2 Polarity Test

This is needed for identifying the primary and secondary phasor polarities. It is

a must for poly phase connections. Both a.c. and d.c methods can be used for detecting

the polarities of the induced emfs. The dot method discussed earlier is used to indicate the

polarities. The transformer is connected to a low voltage a.c. source with the connections

made as shown in the fig. 18(a). A supply voltage Vs is applied to the primary and the

readings of the voltmeters V1, V2 and V3 are noted. V1 : V2 gives the turns ratio. If V3 reads

V1−V2 then assumed dot locations are correct (for the connection shown). The beginning and

end of the primary and secondary may then be marked by A1 −A2 and a1 − a2 respectively.

If the voltage rises from A1 to A2 in the primary, at any instant it does so from a1 to a2 in

the secondary. If more secondary terminals are present due to taps taken from the windings

they can be labeled as a3, a4, a5, a6. It is the voltage rising from smaller number towards

larger ones in each winding. The same thing holds good if more secondaries are present.

45

Page 46: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

Fig. 18(b) shows the d.c. method of testing the polarity. When the switch S is closed if the

secondary voltage shows a positive reading, with a moving coil meter, the assumed polarity

is correct. If the meter kicks back the assumed polarity is wrong.

7.3 Open Circuit Test

A

VV1

W

V2

Rc

jXmV1

IcIm

Io

(a)Physical Arrangement

(b)Equivalent Circuit

Figure 19: No Load Test

As the name suggests, the secondary is kept open circuited and nominal value

of the input voltage is applied to the primary winding and the input current and power are

measured. In Fig. 19(a) V, A, W are the voltmeter, ammeter and wattmeter respectively.

Let these meters read V1, I0 and W0 respectively.Fig. 19(b) shows the equivalent circuit of

the transformer under this test. The no load current at rated voltage is less than 1 percent of

nominal current and hence the loss and drop that take place in primary impedance r1 + jxl1

due to the no load current I0 is negligible. The active component Ic of the no load current I0

46

Page 47: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

represents the core losses and reactive current Im is the current needed for the magnetization.

Thus the watt meter reading

W0 = V1Ic = Pcore (38)

∴ Ic =W0

V1

(39)

∴ Im =√

I2

0− I2

cor (40)

Rc =V1

Ic

andXm =V1

Im

(41)

Io

V1

Figure 20: Open Circuit Characteristics

The parameters measured already are in terms of the primary. Sometimes the pri-

mary voltage required may be in kilo-Volts and it may not be feasible to apply nominal

voltage to primary from the point of safety to personnel and equipment. If the secondary

voltage is low, one can perform the test with LV side energized keeping the HV side open

circuited. In this case the parameters that are obtained are in terms of LV . These have to

be referred to HV side if we need the equivalent circuit referred to HV side.

47

Page 48: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

Sometimes the nominal value of high voltage itself may not be known, or in doubt,

especially in a rewound transformer. In such cases an open circuit characteristics is first

obtained, which is a graph showing the applied voltage as a function of the no load current.

This is a non linear curve as shown in Fig. 20. This graph is obtained by noting the current

drawn by transformer at different applied voltage, keeping the secondary open circuited. The

usual operating point selected for operation lies at some standard voltage around the knee

point of the characteristic. After this value is chosen as the nominal value the parameters

are calculated as mentioned above.

7.4 Short Circuit Test

The purpose of this test is to determine the series branch parameters of the equiv-

alent circuit of Fig. 21(b). As the name suggests, in this test primary applied voltage, the

current and power input are measured keeping the secondary terminals short circuited. Let

these values be Vsc, Isc and Wsc respectively. The supply voltage required to circulate rated

current through the transformer is usually very small and is of the order of a few percent

of the nominal voltage. The excitation current which is only 1 percent or less even at rated

voltage becomes negligibly small during this test and hence is neglected. The shunt branch

is thus assumed to be absent. Also I1 = I′

2as I0 ≃ 0. Therefore Wsc is the sum of the

copper losses in primary and secondary put together. The reactive power consumed is that

absorbed by the leakage reactance of the two windings.

Wsc = I2

sc(r1 + r

2) (42)

Zsc =Vsc

Isc

(43)

(xl1 + x′

l2) =

Z2sc− (r1 + r

2)2 (44)

48

Page 49: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

A

VVsc

W

(a)Physical Arrangement

r1

Isc

Vsc

jxl1 jx’l2r’2

(b)Equivalent Circuit

Figure 21: Short Circuit Test

49

Page 50: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

If the approximate equivalent circuit is required then there is no need to separate r1

and r′

2or xl1 and x

l2. However if the exact equivalent circuit is needed then either r1 or

r′

2is determined from the resistance measurement and the other separated from the total.

As for the separation of xl1 and x′

l2is concerned, they are assumed to be equal. This is a

fairly valid assumption for many types of transformer windings as the leakage flux paths are

through air and are similar.

7.5 Load Test

Load Test helps to determine the total loss that takes place, when the transformer

is loaded. Unlike the tests described previously, in the present case nominal voltage is applied

across the primary and rated current is drown from the secondary. Load test is used mainly

1. to determine the rated load of the machine and the temperature rise

2. to determine the voltage regulation and efficiency of the transformer.

Rated load is determined by loading the transformer on a continuous basis and observ-

ing the steady state temperature rise. The losses that are generated inside the transformer

on load appear as heat. This heats the transformer and the temperature of the transformer

increases. The insulation of the transformer is the one to get affected by this rise in the

temperature. Both paper and oil which are used for insulation in the transformer start get-

ting degenerated and get decomposed. If the flash point of the oil is reached the transformer

goes up in flames. Hence to have a reasonable life expectancy the loading of the transformer

must be limited to that value which gives the maximum temperature rise tolerated by the

insulation. This aspect of temperature rise cannot be guessed from the electrical equivalent

circuit. Further, the losses like dielectric losses and stray load losses are not modeled in the

50

Page 51: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

equivalent circuit and the actual loss under load condition will be in error to that extent.

Many external means of removal of heat from the transformer in the form of different cooling

methods give rise to different values for temperature rise of insulation. Hence these permit

different levels of loading for the same transformer. Hence the only sure way of ascertaining

the rating is by conducting a load test.

It is rather easy to load a transformer of small ratings. As the rating increases it

becomes difficult to find a load that can absorb the requisite power and a source to feed the

necessary current. As the transformers come in varied transformation ratios, in many cases

it becomes extremely difficult to get suitable load impedance.

Further, the temperature rise of the transformer is due to the losses that take place

‘inside’ the transformer. The efficiency of the transformer is above 99% even in modest sizes

which means 1 percent of power handled by the transformer actually goes to heat up the

machine. The remaining 99% of the power has to be dissipated in a load impedance external

to the machine. This is very wasteful in terms of energy also. ( If the load is of unity power

factor) Thus the actual loading of the transformer is seldom resorted to. Equivalent loss

methods of loading and ‘Phantom’ loading are commonly used in the case of transformers.

The load is applied and held constant till the temperature rise of transformer reaches a

steady value. If the final steady temperature rise is lower than the maximum permissible

value, then load can be increased else it is decreased. That load current which gives the

maximum permissible temperature rise is declared as the nominal or rated load current and

the volt amperes are computed using the same.

51

Page 52: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

In the equivalent loss method a short circuit test is done on the transformer. The

short circuit current is so chosen that the resulting loss taking place inside the transformer

is equivalent to the sum of the iron losses, full load copper losses and assumed stray load

losses. By this method even though one can pump in equivalent loss inside the transformer,

the actual distribution of this loss vastly differs from that taking place in reality. Therefore

this test comes close to a load test but does not replace one.

A

V

Io

I2I’2

V

A

I2I’2

Vs

W 2

W 1

2Io

V1

Io

Figure 22: Back to Back Test - Phantom Loading

In Phantom loading method two identical transformers are needed. The windings

are connected back to back as shown in Fig. 22. Suitable voltage is injected into the loop

formed by the two secondaries such that full load current passes through them. An equiv-

52

Page 53: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

alent current then passes through the primary also. The voltage source V1 supplies the

magnetizing current and core losses for the two transformers. The second source supplies

the load component of the current and losses due to the same. There is no power wasted

in a load ( as a matter of fact there is no real load at all) and hence the name Phantom

or virtual loading. The power absorbed by the second transformer which acts as a load is

pushed back in to the mains. The two sources put together meet the core and copper losses

of the two transformers. The transformers work with full flux drawing full load currents and

hence are closest to the actual loading condition with a physical load.

53

Page 54: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

8 Per Unit Calculations

As stated earlier, transformers of various sizes, ratings, voltage ratios can be seen

being used in a power system. The parameters of the equivalent circuits of these machines

also vary over a large range. Also the comparison of these machines are made simple if all

the parameters are normalized. If simple scaling of the parameters is done then one has

to carry forward the scaling factors in the calculations. Expressing in percent basis is one

example of scaling. However if the scaling is done on a logical basis one can have a simple

representation of the parameters without the bother of the scaling factors. Also different

units of measurement are in use in the different countries (FPS, CGS, MKS, etc;). These

units also underwent several revisions over the years. If the transformer parameter can be

freed from the units then the system becomes very simple. The ‘per unit’ system is developed

keeping these aspects in mind. The parameters of the transformer are referred to some base

values and thus get scaled. In the case of power system a common base value is adopted

in view of different ratings of the equipments used. In the case of individual equipments,

its own nominal parameters are used as base values. Some base parameters can be chosen

as independent base values while some others become derived base parameters. Once the

base values are identified the per unit values are calculated for any parameter by dividing

the same by its base value. The units must be the same for both the parameters and their

bases. Thus the per unit value is a unit-less dimensionless number. Let us choose nominal

voltage and nominal current on the primary side of a transformer as the base values Vbase

and Ibase. Other base values like volt ampere Sbase, short circuit impedance Zbase can be

54

Page 55: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

calculated from those values.

Pbase, Qbase, Sbase = Vbase ∗ Ibase (45)

Rbase, Xbase, Zbase =Vbase

Ibase

(46)

Gbase, Bbase, Ybase =Ibase

Vbase

(47)

Normally Sbase and Vbase are known from name plate details. Other base values can be

derived from them.

Vp.u =V (volt)

Vbase(volt),

Ip.u =I(Amps)

Ibase(amps)=

I(amps)Sbase

Vbase

(48)

Zp.u =Z(ohm)

Zbase(ohm)= Z(ohm) ∗

Ibase

Vbase

= Z(ohm).Sbase

V 2

base

(49)

Many times, when more transformers are involved in a circuit one is required to choose

a common base value for all of them. Parameters of all the machines are expressed on this

common base. This is a common problem encountered in the case of parallel operation of

two or more transformers. The conversion of the base values naturally lead to change in the

per unit values of their parameters. An impedance Zp.u.old on the old base of Sbaseold and

Vbaseold shall get modified on new base Sbasenew,Vbasenew as

Zp.u.new = (Zp.u.old.V 2

base old

Sbase old

)Sbase new

V 2

base new

(50)

The term inside the bracket is nothing but the ohmic value of the impedance and this gets

converted into the new per unit value by the new Sbase and Vbase.

If all the equivalent circuit parameters are referred to the secondary side and per unit

values of the new equivalent circuit parameters are computed with secondary voltage and

55

Page 56: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

current as the base values, there is no change in the per unit values. This can be easily seen by,

Z′

p.u.= Z

ohm.S

base

V′2

base

but Z′

ohm=

1

a2.Zohm (51)

Where a - is the turns ratio of primary to secondary

Z - impedance as seen by primary,

Z′

- impedance as seen by secondary.

S′

base= Sbase - as the transformer rating is unaltered.

V′

base= Vbase.

1

a

From the above relationships it can be seen that Z′

p.u.= Zp.u..

This becomes obvious if we realize that the mmf of the core for establishing a given

flux is the same whether it is supplied through primary or the secondary. Also the active

power and reactive power absorbed inside the transformer are not dependant on the winding

connected to supply. This is further illustrated by taking the equivalent circuit of a trans-

former derived earlier and expressing the same in per unit form.

Thus the per unit values help in dispensing away the scaling constants. The veracity

of the parameters can be readily checked. Comparison of the parameters of the machines

with those of similar ones throw in useful information about the machines. Comparing the

efficiencies of two transformers at any load one can say that the transformer with a higher

p.u.resistance has higher copper losses without actually computing the same.

Application of per unit values for the calculation of voltage regulation, efficiency and

load sharing of parallel connected transformers will be discussed later at appropriate places.

56

Page 57: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

9 Voltage Regulation

Modern power systems operate at some standard voltages. The equipments work-

ing on these systems are therefore given input voltages at these standard values, within

certain agreed tolerance limits. In many applications this voltage itself may not be good

enough for obtaining the best operating condition for the loads. A transformer is interposed

in between the load and the supply terminals in such cases. There are additional drops

inside the transformer due to the load currents. While input voltage is the responsibility of

the supply provider, the voltage at the load is the one which the user has to worry about.

If undue voltage drop is permitted to occur inside the transformer the load voltage becomes

too low and affects its performance. It is therefore necessary to quantify the drop that takes

place inside a transformer when certain load current, at any power factor, is drawn from its

output leads. This drop is termed as the voltage regulation and is expressed as a ratio of

the terminal voltage (the absolute value per se is not too important).

The voltage regulation can be defined in two ways - Regulation Down and Regulation

up. These two definitions differ only in the reference voltage as can be seen below.

Regulation down: This is defined as ” the change in terminal voltage when a load current

at any power factor is applied, expressed as a fraction of the no-load terminal voltage”.

Expressed in symbolic form we have,

Regulation =|Vnl| − |Vl|

|Vnl|(52)

Vnl and Vl are no-load and load terminal voltages. This is the definition normally used

in the case of the transformers, the no-load voltage being the one given by the power

57

Page 58: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

supply provider on which the user has no say. Hence no-load voltage is taken as the

reference.

Regulation up: Here again the regulation is expressed as the ratio of the change in the

terminal voltage when a load at a given power factor is thrown off, and the on load

voltage. This definition if expressed in symbolic form results in

Regulation =|Vnl| − |Vl|

|Vl|(53)

Vnl is the no-load terminal voltage.

Vl is load voltage. Normally full load regulation is of interest as the part load regulation

is going to be lower.

This definition is more commonly used in the case of alternators and power systems

as the user-end voltage is guaranteed by the power supply provider. He has to generate

proper no-load voltage at the generating station to provide the user the voltage he has asked

for. In the expressions for the regulation, only the numerical differences of the voltages are

taken and not vector differences.

In the case of transformers both definitions result in more or less the same value for

the regulation as the transformer impedance is very low and the power factor of operation is

quite high. The power factor of the load is defined with respect to the terminal voltage on

load. Hence a convenient starting point is the load voltage. Also the full load output voltage

is taken from the name plate. Hence regulation up has some advantage when it comes to its

application. Fig. 23 shows the phasor diagram of operation of the transformer under loaded

condition. The no-load current I0 is neglected in view of the large magnitude of I′

2. Then

58

Page 59: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

Re jXe

V1

I’2

V’2

(a) Equivalent Circuit

O

V1

C

I2’

φ V’2

θ B

D

I2’Re

I2’Xe

E

A

(b)Phasor Diagram

Figure 23: Regulation of Transformer

59

Page 60: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

I1= I′

2.

V1 = I′

2(Re + jXe) + V

2(54)

OD = V1 =√

[OA + AB + BC]2 + [CD]2

=√

[V′

2+ I

2Re cos φ + I

2Xe sin φ]2 + [I

2Xe cos φ − I

2Re sin φ]2 (55)

φ - power factor angle,

θ- internal impedance angle=tan−1 Xe

Re

Also,

V1 = V′

2+ I

2.(Re + jXe) (56)

= V′

2+ I

2(cos φ − j sin φ)(Re + jXe)

∴ RegulationR =|V1| − |V

2|

|V′

2|

=√

(1 + v1)2 + v2

2− 1 (57)

(1 + v1)2 + v2

2≃ (1 + v1)

2 + v2

2.2(1 + v1)

2(1 + v1)+ [

v2

2

2(1 + v1)]2 = (1 + v1 +

v2

2

2(1 + v1))2 (58)

Taking the square root (59)√

(1 + v1)2 + v2

2= 1 + v1 +

v2

2

2(1 + v1)(60)

where v1 = er cos φ + ex sin φ and v2 = ex cos φ − er sin φ

er =I′

2Re

V′

2

=per unit resistance drop

ex =I′

2Xe

V′

2

=per unit reactance drop

as v1 and v2 are small.

∴ R ≃ 1 + v1 +v2

2

2(1 + e1)− 1 ≃ v1 +

v2

2

2(61)

∴ regulation R = er cos φ ± ex sin φ +(ex sin φ − er cos φ)2

2(62)

60

Page 61: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

v2

2

2(1 + v1)≃

v2

2

2.(1 − v1)

(1 − v2

1)≃

v2

2

2.(1 − v1) ≃

v2

2

2(63)

Powers higher than 2 for v1 and v2 are negligible as v1 and v2 are already small. As

v2 is small its second power may be neglected as a further approximation and the expression

for the regulation of the transform boils down to

regulation R = er cos φ ± ex sin φ

The negative sign is applicable when the power factor is leading. It can be seen from

the above expression, the full load regulation becomes zero when the power factor is leading

and er cos φ = ex sin φ or tan φ = er/ex

or the power factor angle φ = tan−1(er/ex) = tan−1(Re/Xe) leading.

Similarly, the value of the regulation is maximum at a power factor angle φ =

tan−1(ex/er) = tan−1(Xe/Re) lagging.

An alternative expression for the regulation of a transformer can be derived by the

method shown in Fig. 24. Here the phasor are resolved along the current axis and normal

to it.

We have,

OD2 = (OA + AB)2 + (BC + CD)2 (64)

= (V′

2cos φ + I

2Re)

2 + (V′

2sin φ + I

2Xe)

2 (65)

∴ RegulationR =OD − V

2

V′

2

=OD

V′

2

− 1 (66)

(V′

2cos φ + I

2Re)

V′

2

2

+(V

2sin φ + I

2Xe)

V′

2

2

− 1 (67)

=√

(cos φ + Rp.u)2 + (sin φ + X2

p.u)− 1 (68)

61

Page 62: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

A

B

O

D

C

θφ

I2’

I2’Re

I2’Xe

V1

V2

Figure 24: An Alternate Method for the Calculation of Regulation

Thus this expression may not be as convenient as the earlier one due to the square root

involved.

Fig. 25 shows the variation of full load regulation of a typical transformer as the

power factor is varied from zero power factor leading, through unity power factor, to zero

power factor lagging.

It is seen from Fig. 25 that the full load regulation at unity power factor is nothing but

the percentage resistance of the transformer. It is therefore very small and negligible. Only

with low power factor loads the drop in the series impedance of the transformer contributes

substantially to the regulation. In small transformers the designer tends to keep the Xe very

low (less than 5%) so that the regulation performance of the transformer is satisfactory.

62

Page 63: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

1

2

3

4

5

leading lagging

power factor

%Regulation

1.0 0.5 00 0.5

-1

-2

-3

-4

-5

Figure 25: Variation of Full Load Regulation with Power Factor

63

Page 64: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

A low value of the short circuit impedance /reactance results in a large short circuit

current in case of a short circuit. This in turn results in large mechanical forces on the

winding. So, in large transformers the short circuit impedance is made high to give better

short circuit protection to the transformer which results in poorer regulation performance.

In the case of transformers provided with taps on windings, so that the turns ratio can be

changed, the voltage regulation is not a serious issue. In other cases care has to be exercised

in the selection of the short circuit impedance as it affects the voltage regulation.

64

Page 65: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

10 Efficiency

Transformers which are connected to the power supplies and loads and are in op-

eration are required to handle load current and power as per the requirements of the load.

An unloaded transformer draws only the magnetization current on the primary side, the

secondary current being zero. As the load is increased the primary and secondary currents

increase as per the load requirements. The volt amperes and wattage handled by the trans-

former also increases. Due to the presence of no load losses and I2R losses in the windings

certain amount of electrical energy gets dissipated as heat inside the transformer. This gives

rise to the concept of efficiency.

Efficiency of a power equipment is defined at any load as the ratio of the power output to

the power input. Putting in the form of an expression,

Efficiency η =output power

input power=

Input power − losses inside the machine

Input power(69)

= 1 −losses inside the machine

input power= 1 − defficiency

=output power

output + losses inside the machine

More conveniently the efficiency is expressed in percentage. %η = output power

input power∗ 100

While the efficiency tells us the fraction of the input power delivered to the load, the

deficiency focuses our attention on losses taking place inside transformer. As a matter of

fact the losses heat up machine. The temperature rise decides the rating of the equipment.

The temperature rise of the machine is a function of heat generated the structural configu-

ration, method of cooling and type of loading (or duty cycle of load). The peak temperature

attained directly affects the life of the insulations of the machine for any class of insulation.

These aspects are briefly mentioned under section 7.5 on load test.

65

Page 66: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

25

50

75

100

0.5 1x

Effic

iency%

0

Figure 26: Efficiency

A typical curve for the variation of efficiency as a function of output is given in Fig. 26

The losses that take place inside the machine expressed as a fraction of the input is some

times termed as deficiency. Except in the case of an ideal machine, a certain fraction of

the input power gets lost inside the machine while handling the power. Thus the value for

the efficiency is always less than one. In the case of a.c. machines the rating is expressed

in terms of apparent power. It is nothing but the product of the applied voltage and the

current drawn. The actual power delivered is a function of the power factor at which this

current is drawn. As the reactive power shuttles between the source and the load and has a

zero average value over a cycle of the supply wave it does not have any direct effect on the

efficiency. The reactive power however increases the current handled by the machine and

the losses resulting from it. Therefore the losses that take place inside a transformer at any

66

Page 67: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

given load play a vital role in determining the efficiency. The losses taking place inside a

transformer can be enumerated as below:

1. Primary copper loss

2. Secondary copper loss

3. Iron loss

4. Dielectric loss

5. Stray load loss

These are explained in sequence below.

Primary and secondary copper losses take place in the respective winding resistances

due to the flow of the current in them.

Pc = I2

1r1 + I2

2r2 = I

′2

2Re (70)

The primary and secondary resistances differ from their d.c. values due to skin effect and the

temperature rise of the windings. While the average temperature rise can be approximately

used, the skin effect is harder to get analytically. The short circuit test gives the value of Re

taking into account the skin effect.

The iron losses contain two components - Hysteresis loss and Eddy current loss. The

Hysteresis loss is a function of the material used for the core.

Ph = KhB1.6f

67

Page 68: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

For constant voltage and constant frequency operation this can be taken to be con-

stant. The eddy current loss in the core arises because of the induced emf in the steel

lamination sheets and the eddies of current formed due to it. This again produces a power

loss Pe in the lamination.

Pe = KeB2f 2t2

where t is the thickness of the steel lamination used. As the lamination thickness is much

smaller than the depth of penetration of the field, the eddy current loss can be reduced by

reducing the thickness of the lamination. Present day laminations are of 0.25 mm thickness

and are capable of operation at 2 Tesla. These reduce the eddy current losses in the core.

This loss also remains constant due to constant voltage and frequency of operation. The

sum of hysteresis and eddy current losses can be obtained by the open circuit test.

The dielectric losses take place in the insulation of the transformer due to the large

electric stress. In the case of low voltage transformers this can be neglected. For constant

voltage operation this can be assumed to be a constant.

The stray load losses arise out of the leakage fluxes of the transformer. These leakage

fluxes link the metallic structural parts, tank etc. and produce eddy current losses in them.

Thus they take place ’all round’ the transformer instead of a definite place , hence the name

’stray’. Also the leakage flux is directly proportional to the load current unlike the mutual

flux which is proportional to the applied voltage. Hence this loss is called ’stray load’ loss.

This can also be estimated experimentally. It can be modeled by another resistance in the

series branch in the equivalent circuit. The stray load losses are very low in air-cored trans-

formers due to the absence of the metallic tank.

68

Page 69: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

Thus, the different losses fall in to two categories Constant losses (mainly voltage

dependant) and Variable losses (current dependant). The expression for the efficiency of the

transformer operating at a fractional load x of its rating, at a load power factor of θ2, can

be written as

η =xS cos θ2

xS cos θ2 + Pconst + x2Pvar

(71)

Here S in the volt ampere rating of the transformer (V′

2I

2at full load), Pconst being constant

losses and Pvar the variable losses at full load.

For a given power factor an expression for η in terms of the variable x is thus obtained.

By differentiating η with respect to x and equating the same to zero, the condition for

maximum efficiency is obtained. In the present case that condition comes out to be

Pconst = x2Pvar or x =

Pconst

Pvar

(72)

That is, when constant losses equal the variable losses at any fractional load x the

efficiency reaches a maximum value. The maximum value of that efficiency at any given

power factor is given by,

ηmax =xS cos θ2

xS cos θ2 + 2Pconst

=xS cos θ2

xS cos θ2 + 2x2Pvar

(73)

From the expression for the maximum efficiency it can be easily deduced that this

maximum value increases with increase in power factor and is zero at zero power factor of

the load. It may be considered a good practice to select the operating load point to be at the

maximum efficiency point. Thus if a transformer is on full load, for most part of the time

then the ηmax can be made to occur at full load by proper selection of constant and variable

69

Page 70: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

losses. However, in the modern transformers the iron losses are so low that it is practically

impossible to reduce the full load copper losses to that value. Such a design wastes lot of

copper. This point is illustrated with the help of an example below.

Two 100 kVA transformers A nd B are taken. Both transformers have total full load

losses to be 2 kW. The break up of this loss is chosen to be different for the two transformers.

Transformer A: iron loss 1 kW, and copper loss is 1 kW. The maximum efficiency of 98.04%

occurs at full load at unity power factor. Transformer B: Iron loss =0.3 kW and full load

copper loss =1.7 kW. This also has a full load η of 98.04%. Its maximum η occurs at

a fractional load of√

0.3

1.7= 0.42. The maximum efficiency at unity power factor being

42

42+0.6∗ 100 = 98.59%. At the corresponding point the transformer A has an efficiency of

42

42+1.0+0.1764∗ 100 = 97.28%. Transformer A uses iron of more loss per kg at a given flux

density, but transformer B uses lesser quantity of copper and works at higher current density.

10.1 All day efficiency

Large capacity transformers used in power systems are classified broadly into Power trans-

formers and Distribution transformers. The former variety is seen in generating stations and

large substations. Distribution transformers are seen at the distribution substations. The

basic difference between the two types arise from the fact that the power transformers are

switched in or out of the circuit depending upon the load to be handled by them. Thus at

50% load on the station only 50% of the transformers need to be connected in the circuit.

On the other hand a distribution transformer is never switched off. It has to remain in the

circuit irrespective of the load connected. In such cases the constant loss of the transformer

continues to be dissipated. Hence the concept of energy based efficiency is defined for such

70

Page 71: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

50

100

6 12 18 24

Load %

of

full load

Time,hrs

s

P

50

100

1224

Po

we

r L

oss %

(a)Load factor (b) Loss factor

Figure 27: Calculation of Load Factor and Loss Factor

71

Page 72: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

transformers. It is called ’all day’ efficiency. The all day efficiency is thus the ratio of the

energy output of the transformer over a day to the corresponding energy input. One day

is taken as a duration of time over which the load pattern repeats itself. This assumption,

however, is far from being true. The power output varies from zero to full load depending

on the requirement of the user and the load losses vary as the square of the fractional loads.

The no-load losses or constant losses occur throughout the 24 hours. Thus, the comparison

of loads on different days becomes difficult. Even the load factor, which is given by the

ratio of the average load to rated load, does not give satisfactory results. The calculation

of the all day efficiency is illustrated below with an example. The graph of load on the

transformer, expressed as a fraction of the full load is plotted against time in Fig. 27. In an

actual situation the load on the transformer continuously changes. This has been presented

by a stepped curve for convenience. The average load can be calculated by

Average load over a day =

n

i=1Pi

24=

Sn

n

i=1xiti cos θi

24(74)

where Pi is the load during an interval i. n intervals are assumed. xi is the fractional load.

Si = xiSn where Sn is nominal load. The average loss during the day is given by

Average loss = Pi +Pc

n

i=1x2

iti

24(75)

This is a non-linear function. For the same load factor different average loss can be

there depending upon the values of xi and ti. Hence a better option would be to keep the

constant losses very low to keep the all day efficiency high. Variable losses are related to

load and are associated with revenue earned. The constant losses on the other hand has to

be incurred to make the service available. The concept of all day efficiency may therefore be

more useful for comparing two transformers subjected to the same load cycle.

72

Page 73: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

The concept of minimizing the lost energy comes into effect right from the time of

procurement of the transformer. The constant losses and variable losses are capitalized and

added to the material cost of the transformer in order to select the most competitive one,

which gives minimum cost taking initial cost and running cost put together. Obviously the

iron losses are capitalized more in the process to give an effect to the maximization of energy

efficiency. If the load cycle is known at this stage, it can also be incorporated in computation

of the best transformer.

73

Page 74: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

11 Auto Transformer

V1

T1

T2

I1

V2 ZL

I1

I2

I2

A

B

C

Figure 28: Autotransformer - Physical Arrangement

The primary and secondary windings of a two winding transformer have

induced emf in them due to a common mutual flux and hence are in phase. The currents

drawn by these two windings are out of phase by 180◦. This prompted the use of a part

of the primary as secondary. This is equivalent to fusing the secondary turns into primary

turns. The fused section need to have a cross sectional area of the conductor to carry (I2−I1)

ampere! This ingenious thought led to the invention of an auto transformer. Fig. 28 shows

the physical arrangement of an auto transformer. Total number of turns between A and C

are T1. At point B a connection is taken. Section AB has T2 turns. As the volts per turn,

which is proportional to the flux in the machine, is the same for the whole winding,

V1 : V2 = T1 : T2 (76)

For simplifying analysis, the magnetizing current of the transformer is neglected.

74

Page 75: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

When the secondary winding delivers a load current of I2 ampere the demagnetizing ampere

turns is I2T2 . This will be countered by a current I1 flowing from the source through the

T1 turns such that,

I1T1 = I2T2 (77)

A current of I1 ampere flows through the winding between B and C . The current

in the winding between A and B is (I2 − I1) ampere. The cross section of the wire to be

selected for AB is proportional to this current assuming a constant current density for the

whole winding. Thus some amount of material saving can be achieved compared to a two

winding transformer. The magnetic circuit is assumed to be identical and hence there is

no saving in the same. To quantify the saving the total quantity of copper used in an auto

transformer is expressed as a fraction of that used in a two winding transformer as,

copper in auto transformer

copper in two winding transformer=

(T1 − T2)I1 + T2(I2 − I1)

T1I1 + T2I2

(78)

= 1 −2T2I1

T1I1 + T2I2

But T1I1 = T2I2 (79)

∴ The Ratio = 1 −2T2I1

2T1I1

= 1 −T2

T1

(80)

This means that an auto transformer requires the use of lesser quantity of copper

given by the ratio of turns. This ratio therefore denotes the savings in copper. As the

space for the second winding need not be there, the window space can be less for an auto

transformer, giving some saving in the lamination weight also. The larger the ratio of the

voltages, smaller is the savings. As T2 approaches T1 the savings become significant. Thus

auto transformers become ideal choice for close ratio transformations. The savings in mate-

rial is obtained, however, at a price. The electrical isolation between primary and secondary

75

Page 76: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

V1

I1+I2

V1+V2

V2

I2

I1

ZL

I1+I2 I1

I2

I2

φ

Figure 29: Two Winding Transformer used as auto transformer

has to be sacrificed.

If we are not looking at the savings in the material, even then going in for the auto

transformer type of connection can be used with advantage, to obtain higher output. This

can be illustrated as follows. Fig. 29 shows a regular two winding transformer of a voltage

ratio V1 : V2, the volt ampere rating being V1I1 = V2I2 = S. If now the primary is connected

across a supply of V1 volt and the secondary is connected in series addition manner with the

primary winding, the output voltage becomes (V1 + V2) volt. The new output of this auto

transformer will now be

I2(V1 + V2) = I2V2(1 +V1

V2

) = S(1 +V1

V2

) (81)

= V1(I1 + I2) = S(1 +I2

I1

) (82)

76

Page 77: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

Thus an increased rating can be obtained compared to a two winding transformer

with the same material content. The windings can be connected in series opposition fashion

also. Then the new output rating will be

I2(V1 − V2) = I2V2(V1

V2

− 1) = S(V1

V2

− 1) (83)

The differential connection is not used as it is not advantageous as the cumulative

connection.

11.1 Equivalent circuit

V1

(I2 -I1)

V2

I2

I1

I1

I1 I2

r1,xl1

r2,xl2

Figure 30: Kirchoff’s Law Application to auto transformer

As mentioned earlier the magnetizing current can be neglected, for simplicity. Writing

77

Page 78: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

the Kirchoff’s equation to the primary and secondary of Fig. 30 we have

V1 = E1 + I1(r1 + jxl1) − (I2 − I1)(r2 + jxl2) (84)

Note that the resistance r1 and leakage reactance xl1 refer to that part of the winding where

only the primary current flows. Similarly on the load side we have,

E2 = V2 + (I2 − I1)(r2 + jxl2) (85)

The voltage ratio V1 : V2 = E1 : E2 = T1 : T2 = a where T1 is the total turns of the

primary.

Then E1 = aE2 and I2 = aI1

multiplying equation(84) by ’a’ and substituting in (83) we have

V1 = aV2 + a(I2 − I1)(r2 + jxl2) + I1(r1 + jxl1) − (I2 − I1)(r2 + jxl2)

= aV2 + I1(r1 + jxl1 + r2 + jxl2 − ar2 − ajxl2) + I2(ar2 + jaxl2 − r2 − jxl2)

= aV2 + I1(r1 + jxl1 + r2 + jxl2 + a2r2 + ja2xl2 − ar2 − ajxl2 − ar2 − jaxl2)

= aV2 + I1(r1 + r2(1 + a2 − 2a) + jxl1 + xl2(1 + a2 − 2a))

= aV2 + I1(r1 + (a − 1)2r2 + jxl1 + (a − 1)2xl2) (86)

Equation (85) yields the equivalent circuit of Fig. 31 where Re = r1 + (a − 1)2r2 and

Xe = xl1 + (a − 1)2xl2.

The magnetization branch can now be hung across the mains for completeness. The

above equivalent circuit can now be compared with the approximate equivalent circuit of

a two winding case Re = r1 + a2r2 and Xe = xl1 + a2xl2. Thus in the case of an auto

transformer total value of the short circuit impedance is lower and so also the percentage

resistance and reactance. Thus the full load regulation is lower. Having a smaller value

of short circuit impedance is sometimes considered to be a disadvantage. That is because

78

Page 79: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

Re jXe

Rc jXmV1

Ic Im

Io

V’2=aV1

Re=r1+(a-1)2r2

Xl=xl1+(a-1)2xl2

Figure 31: Equivalent Circuit of auto transformers

the short circuit currents become very large in those cases. The efficiency is higher in auto

transformers compared to their two winding counter part at the same load. The phasor

diagram of operation for the auto transformer drawing a load current at a lagging power

factor angle of θ2 is shown in Fig. 32. The magnetizing current is omitted here again for

simplicity.

From the foregoing study it is seen that there are several advantages in going in for the

autotransformer type of arrangement. The voltage/current transformation and impedance

conversion aspects of a two winding transformer are retained but with lesser material (and

hence lesser weight) used. The losses are reduced increasing the efficiency. Reactance is

reduced resulting in better regulation characteristics. All these benefits are enhanced as

the voltage ratio approaches unity. The price that is required to be paid is loss of electri-

cal isolation and a larger short circuit current (and larger short circuit forces on the winding).

79

Page 80: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

φ

I1

E1

I1r1

I1x1

(I2-I1)x2

V1

(I2-I1)r2

(I2-I1)x2

(I2-I1)r2

V2

I2

E2

I2

θ1

θ2

Figure 32: Phasor Diagram of Operation of an autotransformer

80

Page 81: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

Auto transformers are used in applications where electrical isolation is not a critical

requirement. When the ratio V2 : V1 is 0.3 or more they are used with advantage. The

normal applications are motor starters, boosters or static balancers.

Vin

M oving contact

Variable

a.c output

Figure 33: Variable Secondary Voltage Arrangement

Another wide spread application of auto transformer type of arrangement is in ob-

taining a variable a.c. voltage from a fixed a.c. voltage supply. Here only one winding is used

as in the auto transformer. The secondary voltage is tapped by a brush whose position and

hence the output voltage is variable. The primary conductor is bared to facilitate electrical

contact Fig. 33. Such arrangement cannot exploit the savings in the copper as the output

voltage is required right from zero volts upwards.

The conductor is selected based on the maximum secondary current that could be

drawn as the output voltage varies in practically continuous manner. These are used in

81

Page 82: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

voltage stabilizers, variable d.c. arrangements (with a diode bridge) in laboratories, motor

starters, dimmers etc.

82

Page 83: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

12 Harmonics

In addition to the operation of transformers on the sinusoidal supplies, the harmonic

behavior becomes important as the size and rating of the transformer increases. The effects

of the harmonic currents are

1. Additional copper losses due to harmonic currents

2. Increased core losses

3. Increased electro magnetic interference with communication circuits.

On the other hand the harmonic voltages of the transformer cause

1. Increased dielectric stress on insulation

2. Electro static interference with communication circuits.

3. Resonance between winding reactance and feeder capacitance.

In the present times a greater awareness is generated by the problems of harmonic

voltages and currents produced by non-linear loads like the power electronic converters.

These combine with non-linear nature of transformer core and produce severe distortions in

voltages and currents and increase the power loss. Thus the study of harmonics is of great

practical significance in the operation of transformers. The discussion here is confined to the

harmonics generated by transformers only.

83

Page 84: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

e

t’ t’’ t iϕi’ϕ

i’’ϕiϕ

i’ϕ i’’ϕ

ϕ

ϕ’

ϕ’’

ϕ

ϕ’

ϕ’’

Figure 34: Harmonics Generated by Transformers

12.1 Single phase transformers

Modern transformers operate at increasing levels of saturation in order to reduce

the weight and cost of the core used in the same. Because of this and due to the hysteresis,

the transformer core behaves as a highly non-linear element and generates harmonic voltages

and currents. This is explained below. Fig. 34 shows the manner in which the shape of the

magnetizing current can be obtained and plotted. At any instant of the flux density wave

the ampere turns required to establish the same is read out and plotted, traversing the

hysteresis loop once per cycle. The sinusoidal flux density curve represents the sinusoidal

applied voltage to some other scale. The plot of the magnetizing current which is peaky is

analyzed using Fourier analysis. The harmonic current components are obtained from this

analysis. These harmonic currents produce harmonic fields in the core and harmonic voltages

in the windings. Relatively small value of harmonic fields generate considerable magnitude

of harmonic voltages. For example a 10% magnitude of 3rd harmonic flux produces 30%

84

Page 85: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

magnitude of 3rd harmonic voltage. These effects get even more pronounced for higher

order harmonics. As these harmonic voltages get short circuited through the low impedance

of the supply they produce harmonic currents. These currents produce effects according to

Lenz’s law and tend to neutralize the harmonic flux and bring the flux wave to a sinusoid.

Normally third harmonic is the largest in its magnitude and hence the discussion is based on

it. The same can be told of other harmonics also. In the case of a single phase transformer

the harmonics are confined mostly to the primary side as the source impedance is much

smaller compared to the load impedance. The understanding of the phenomenon becomes

more clear if the transformer is supplied with a sinusoidal current source. In this case current

has to be sinusoidal and the harmonic currents cannot be supplied by the source and hence

the induced emf will be peaky containing harmonic voltages. When the load is connected on

the secondary side the harmonic currents flow through the load and voltage tends to become

sinusoidal. The harmonic voltages induce electric stress on dielectrics and increased electro

static interference. The harmonic currents produce losses and electro magnetic interference

as already noted above.

12.2 Three phase banks of single phase transformers

In the case of single phase transformers connected to form three phase bank, each

transformer is magnetically decoupled from the other. The flow of harmonic currents are

decided by the type of the electrical connection used on the primary and secondary sides.

Also, there are three fundamental voltages in the present case each displaced from the other

by 120 electrical degrees. Because of the symmetry of the a.c. wave about the time axis

only odd harmonics need to be considered. The harmonics which are triplen (multiples of

three) behave in a similar manner as they are co-phasal or in phase in the three phases. The

85

Page 86: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

non-triplen harmonics behave in a similar manner to the fundamental and have ±120◦ phase

displacement between them. The harmonic behavior of poly-phase banks can be discussed

now.

Dd connection In three phase banks with mesh connection on both primary side and sec-

ondary side a closed path is available for the triplen harmonics to circulate currents.

Thus the supply current is nearly sinusoidal (but for the non-triplen harmonic cur-

rents). The triplen harmonic currents inside the closed mesh winding correct the flux

density wave to be nearly sinusoidal. The secondary voltages will be nearly sinusoidal.

Third harmonics currents flow both in the primary and the secondary and hence the

magnitudes of these currents, so also the drops due to them will be lower.

Dy and Yd connection (without neutral connection) Behavior of the bank with mesh

connection on one side is similar to the one discussed under Dd connection. The har-

monic currents and drops and the departure of the flux density from sinusoidal are

larger in the present case compared to Dd banks.

Yy connection without neutral wires With both primary and secondary connected in

star no closed path exists. As the triplen harmonics are always in phase, by virtue

of the Y connection they get canceled in the line voltages. Non-triplen harmonics

like fundamental, become√

3 times phase value and appear in the line voltages. Line

currents remain sinusoidal except for non-triplen harmonic currents. Flux wave in each

transformer will be flat topped and the phase voltages remain peaked. The potential

of the neutral is no longer steady. The star point oscillates due to the third harmonic

voltages. This is termed as ”oscillating neutral”.

Yy connection with neutral wires When a neutral wire is provided the triplen har-

86

Page 87: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

monic current can flow and the condition is similar to the single phase case (with a

star connected 4 wire source or with the system earth). The neutral wire carries three

times the triplen harmonic current of one transformer as these currents are co-phasal.

Unloaded secondary neutral will not be operative. Other polyphase connections not

discussed above explicitly will fall under one type or the other of the cases discussed.

In a Yy connection, to obtain third harmonic suppression one may provide a third

winding which is connected in mesh, which can be an unloaded winding. It is called a

tertiary. This winding improves the single phase to earth fault detection also. Further,

this winding can be used to feed some permanent station loads also. Such transform-

ers are designated as Yyd transformers. If the neutral wires are provided and also

mesh connected winding is present, then triplen harmonics are ’shared’ between them

depending upon their impedances.

12.3 Three phase transformers units

As against a bank of three single phase transformers connected to three phase

mains, a three phase transformer generally has the three magnetic circuits that are inter-

acting. The exception to this rule is a 3-phase shell type transformer. In the shell type of

construction, even though the three cores are together, they are non-interacting. Three limb

core type 3-phase transformer is the one in which the phases are magnetically also linked.

Flux of each limb uses the other two limbs for its return path. This is true for fundamental

and non-triplen harmonics. The triplen harmonics being co-phasal cannot use other limbs

for the return path (this holds good for zero sequence, unbalanced fundamental mmf also).

The flux path is completed through the air. So substantially large value of the mmf produces

a low value of third harmonic flux as the path of the flux is through the air and has a very

87

Page 88: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

high reluctance. Thus the flux in the core remains nearly sinusoidal, so also the induced emf.

This happens irrespective of the type of connection used. The triplen order flux, sometimes

links the tank and produces loss in the same.

Other harmonics can be suppressed by connecting tuned filters at the terminals.

Harmonic current compensation using special magnetic circuit design is considered to be

outside the scope here.

88

Page 89: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

13 Poly Phase connections and Poly phase Transform-

ers

The individual transformers are connected in a variety of ways in a power system.

Due to the advantages of polyphase power during generation, transmission and utilization

polyphase power handling is very important. As an engineering application is driven by

techno-economic considerations, no single connection or setup is satisfactory for all appli-

cations. Thus transformers are deployed in many forms and connections. Star and mesh

connections are very commonly used. Apart from these, vee or open delta connections, zig

zag connections , T connections, auto transformer connections, multi winding transformers

etc. are a few of the many possibilities. A few of the common connections and the tech-

nical and economic considerations that govern their usage are discussed here. Literature

abounds in the description of many other. Apart from the characteristics and advantages

of these, one must also know their limitations and problems, to facilitate proper selection of

a configuration for an application. Many polyphase connections can be formed using single

phase transformers. In some cases it may be preferable to design, develop and deploy a

polyphase transformer itself. In a balanced two phase system we encounter two voltages

that are equal in magnitude differing in phase by 90◦. Similarly, in a three phase system

there are three equal voltages differing in phase 120 electrical degrees. Further there is an

order in which they reach a particular voltage magnitude. This is called the phase sequence.

In some applications like a.c. to d.c. conversion, six phases or more may be encountered.

Transformers used in all these applications must be connected properly for proper function-

ing. The basic relationship between the primary and secondary voltages (brought about by

a common mutual flux and the number of turns), the polarity of the induced emf (decided

by polarity test and used with dot convention) and some understanding of the magnetic

89

Page 90: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

circuit are all necessary for the same. To facilitate the manufacturer and users, interna-

tional standards are also available. Each winding has two ends designated as 1 and 2. The

HV winding is indicated by capital letters and the LV winding by small letters. If more

terminals are brought out from a winding by way of taps there are numbered in the increas-

ing numbers in accordance to their distance from 1 (eg A1, A2, A3...). If the induced emf

at an instant is from A1 to A2 on the HV winding it will rise from a1 to a2 on the LV winding.

Out of the different polyphase connections three phase connections are mostly en-

countered due to the wide spread use of three phase systems for generation, transmission

and utilization. Three balanced 3-phase voltages can be connected in star or mesh fashion

to yield a balanced 3-phase 3-wire system. The transformers that work on the 3-phase sup-

ply have star, mesh or zig-zag connected windings on either primary secondary or both. In

addition to giving different voltage ratios, they introduce phase shifts between input and

output sides. These connections are broadly classified into 4 popular vector groups.

1. Group I: zero phase displacement between the primary and the secondary.

2. Group II: 180◦ phase displacement.

3. Group III: 30◦ lag phase displacement of the secondary with respect to the primary.

4. Group IV: 30◦ lead phase displacement of the secondary with respect to the primary.

A few examples of the physical connections and phasor diagrams are shown in Fig. 35

and Fig. 36 corresponding to each group. The capital letters indicates primary and the

small letters the secondary. D/d stand for mesh, Y/y - for star, Z/z for zig-zag. The angu-

lar displacement of secondary with respect to the primary are shown as clock position, 0◦

90

Page 91: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

Group1 00 Phase shift

W indings & Term inals E.M .F Vector diagram s

A2 a2

B2 b2

C2 c2

N n

a1

b1

c1

A1

B1

C1

A2 a2

B2 b2

C2 c2

A1

B1

C1

a1

b1

c1

a4

b4

c4

A2

B2

C2

A1

B1

C1

n

a1

b1

c1

A2

C2 B2

a2

A2

C2

B2

a2

A2

C2B2

(a)

Group2 1800 Phase shift

W indings & Term inals E.M .F Vector diagram s

A2

C2 B2

A2 a1

B2 b1

C2 c1

n

A1

B1

C1

a1

b1

c1

N

a1

b1

c1

a1

b1

c1

a2

b2

c2

A2

B2

C2

A1

B1

C1

a3

b3

c3

n

a1

b1

c1

A2

B2

C2

A1

B1

C1

A2

C2 B2A2

C2 B2

(b)

Figure 35: Vector Groups for 3-phase Transformer Connections91

Page 92: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

Group3 300 Phase shift

W indings & Term inals E.M .F Vector diagram s

A2 a2

B2 b2

C2 c2

n

A1

B1

C1

a1

b1

c1

A2 a2

B2 b2

C2 c2

N

A1

B1

C1

a1

b1

c1

A2 a4

B2 b4

C2 c4

N

A1

B1

C1

n

a1

b1

c1

A2

C2 B2

a2

A2

C2 B2

A2

C2 B2

a2

(a)

Group4 + 300 Phase shift

W indings & Term inals E.M .F Vector diagram s

A2

B2

A1

B1

C1

a2

b2

c2

n

a1

b1

c1

A2

B2

C2

NA1

B1

C1

a1

b1

c1

a1

b1

c1

a2

b2

c2

A2

B2

C2

NA1

B1

C1

n

a1

b1

c1

a3

b3

c3

a4

b4

c4

A2

C2

B2

a2

C2 B2

C 2

B 2

A2

B2

C2

(b)

Figure 36: Vector Groups for 3-phase Transformer Connections92

Page 93: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

referring to 12 o’clock position. These vector groups are especially important when two or

more transformers are to be connected in parallel.

Star connection is normally cheaper as there are fewer turns and lesser cost of insula-

tion. The advantage becomes more with increase in voltage above 11kv. In a star connected

winding with earthed-neutral the maximum voltage to the earth is ( 1√

3)of the line voltage.

Also star connection permits mixed loading due to the presence of the neutral. Mesh con-

nections are advantageous in low voltage transformers as insulation costs are insignificant

and the conductor size becomes ( 1√

3) of that of star connection and permits ease of winding.

The common polyphase connections are briefly discussed now.

Star/star (Yy0, Yy6)connection This is the most economical one for small high voltage

transformers. Insulation cost is highly reduced. Neutral wire can permit mixed load-

ing. Triplen harmonics are absent in the lines. These triplen harmonic currents cannot

flow, unless there is a neutral wire. This connection produces oscillating neutral. Three

phase shell type units have large triplen harmonic phase voltage. However three phase

core type transformers work satisfactorily. A tertiary mesh connected winding may be

required to stabilize the oscillating neutral due to third harmonics in three phase banks.

Mesh/mesh (Dd0, Dd6) This is an economical configuration for large low voltage trans-

formers. Large amount of unbalanced load can be met with ease. Mesh permits a cir-

culating path for triplen harmonics thus attenuates the same. It is possible to operate

with one transformer removed in open delta or Vee connection meeting 58 percent of

the balanced load. Three phase units cannot have this facility. Mixed single phase

loading is not possible due to the absence of neutral.

93

Page 94: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

Star/mesh(Dy or Yd ) This arrangement is very common for power supply transform-

ers. The delta winding permits triplen harmonic currents to circulate in the closed

path and attenuates them.

Zig zag/ star (ZY1 or Zy11) Zigzag connection is obtained by inter connection of phases.

4-wire system is possible on both sides. Unbalanced loading is also possible. Oscillat-

ing neutral problem is absent in this connection. This connection requires 15% more

turns for the same voltage on the zigzag side and hence costs more.

Generally speaking a bank of three single phase transformers cost about 15% more

than their 3-phase counter part. Also, they occupy more space. But the spare capac-

ity cost will be less and single phase units are easier to transport.

Mesh connected three phase transformers resemble 3- single phase units but kept in

a common tank. In view of this single tank, the space occupied is less. Other than

that there is no big difference. The 3-phase core type transformer on the other hand

has a simple core arrangement. The three limbs are equal in cross section. Primary

and secondary of each phase are housed on the same limb. The flux setup in any limb

will return through the other two limbs as the mmf of those limbs are in the proper

directions so as to aid the same. Even though magnetically this is not a symmetrical

arrangement, as the reluctance to the flux setup by side limbs is different from that of

the central limb, it does not adversely affect the performance. This is due to the fact

that the magnetizing current itself forms a small fraction of the total phase current

drawn on load. The added advantage of 3-phase core is that it can tolerate substantially

94

Page 95: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

large value of 3rd harmonic mmf without affecting the performance. The 3rd harmonic

mmf of the three phases will be in phase and hence rise in all the limbs together.

The 3rd harmonic flux must therefore find its path through the air. Due to the high

reluctance of the air path even a substantially large value of third harmonic mmf

produces negligible value of third harmonic flux. Similarly unbalanced operation of the

transformer with large zero sequence fundamental mmf content also does not affect its

performance. Even with Yy type of poly phase connection without neutral connection

the oscillating neutral does not occur with these cores. Finally, three phase cores

themselves cost less than three single phase units due to compactness.

95

Page 96: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

14 Parallel operation of one phase and two phase trans-

formers

By parallel operation we mean two or more transformers are connected to the same

supply bus bars on the primary side and to a common bus bar/load on the secondary side.

Such requirement is frequently encountered in practice. The reasons that necessitate parallel

operation are as follows.

1. Non-availability of a single large transformer to meet the total load requirement.

2. The power demand might have increased over a time necessitating augmentation of the

capacity. More transformers connected in parallel will then be pressed into service.

3. To ensure improved reliability. Even if one of the transformers gets into a fault or is

taken out for maintenance/repair the load can continued to be serviced.

4. To reduce the spare capacity. If many smaller size transformers are used one machine

can be used as spare. If only one large machine is feeding the load, a spare of similar

rating has to be available. The problem of spares becomes more acute with fewer

machines in service at a location.

5. When transportation problems limit installation of large transformers at site, it may

be easier to transport smaller ones to site and work them in parallel.

Fig. 37 shows the physical arrangement of two single phase transformers working in

parallel on the primary side. Transformer A and Transformer B are connected to input

voltage bus bars. After ascertaining the polarities they are connected to output/load bus

96

Page 97: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

E1 E2

V1 V2IA

E1 E2

load

A

B

supply bus Load bus

IB

Figure 37: Parallel Operation of Two Single Phase Transformers - Physical

97

Page 98: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

bars. Certain conditions have to be met before two or more transformers are connected in

parallel and share a common load satisfactorily. They are,

1. The voltage ratio must be the same.

2. The per unit impedance of each machine on its own base must be the same.

3. The polarity must be the same, so that there is no circulating current between the

transformers.

4. The phase sequence must be the same and no phase difference must exist between the

voltages of the two transformers.

These conditions are examined first with reference to single phase transformers and then the

three phase cases are discussed.

Same voltage ratio Generally the turns ratio and voltage ratio are taken to be the same.

If the ratio is large there can be considerable error in the voltages even if the turns ratios

are the same. When the primaries are connected to same bus bars, if the secondaries

do not show the same voltage, paralleling them would result in a circulating current

between the secondaries. Reflected circulating current will be there on the primary

side also. Thus even without connecting a load considerable current can be drawn

by the transformers and they produce copper losses. In two identical transformers

with percentage impedance of 5 percent, a no-load voltage difference of one percent

will result in a circulating current of 10 percent of full load current. This circulating

current gets added to the load current when the load is connected resulting in unequal

sharing of the load. In such cases the combined full load of the two transformers can

never be met without one transformer getting overloaded.

98

Page 99: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

Per unit impedance Transformers of different ratings may be required to operate in par-

allel. If they have to share the total load in proportion to their ratings the larger

machine has to draw more current. The voltage drop across each machine has to be

the same by virtue of their connection at the input and the output ends. Thus the

larger machines have smaller impedance and smaller machines must have larger ohmic

impedance. Thus the impedances must be in the inverse ratios of the ratings. As the

voltage drops must be the same the per unit impedance of each transformer on its

own base, must be equal. In addition if active and reactive power are required to be

shared in proportion to the ratings the impedance angles also must be the same. Thus

we have the requirement that per unit resistance and per unit reactance of both the

transformers must be the same for proper load sharing.

Polarity of connection The polarity of connection in the case of single phase transform-

ers can be either same or opposite. Inside the loop formed by the two secondaries

the resulting voltage must be zero. If wrong polarity is chosen the two voltages get

added and short circuit results. In the case of polyphase banks it is possible to have

permanent phase error between the phases with substantial circulating current. Such

transformer banks must not be connected in parallel. The turns ratios in such groups

can be adjusted to give very close voltage ratios but phase errors cannot be compen-

sated. Phase error of 0.6 degree gives rise to one percent difference in voltage. Hence

poly phase transformers belonging to the same vector group alone must be taken for

paralleling.

Transformers having −30◦ angle can be paralleled to that having +30◦ angle by re-

versing the phase sequence of both primary and secondary terminals of one of the

transformers. This way one can overcome the problem of the phase angle error.

99

Page 100: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

Phase sequence The phase sequence of operation becomes relevant only in the case of

poly phase systems. The poly phase banks belonging to same vector group can be

connected in parallel. A transformer with +30◦ phase angle however can be paralleled

with the one with −30◦ phase angle, the phase sequence is reversed for one of them

both at primary and secondary terminals. If the phase sequences are not the same

then the two transformers cannot be connected in parallel even if they belong to same

vector group. The phase sequence can be found out by the use of a phase sequence

indicator.

Performance of two or more single phase transformers working in parallel can be com-

puted using their equivalent circuit. In the case of poly phase banks also the approach

is identical and the single phase equivalent circuit of the same can be used. Basically

two cases arise in these problems. Case A: when the voltage ratio of the two trans-

formers is the same and Case B: when the voltage ratios are not the same. These are

discussed now in sequence.

14.1 Case A: Equal voltage ratios

Always two transformers of equal voltage ratios are selected for working in parallel.

This way one can avoid a circulating current between the transformers. Load can be switched

on subsequently to these bus bars. Neglecting the parallel branch of the equivalent circuit the

above connection can be shown as in Fig. 38(a),(b). The equivalent circuit is drawn in terms

of the secondary parameters. This may be further simplified as shown under Fig. 38(c). The

voltage drop across the two transformers must be the same by virtue of common connection

at input as well as output ends. By inspection the voltage equation for the drop can be

100

Page 101: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

V2’

V1

ZA

ZB

IA

IB

RA

RB

jXA

jXB

V2’IV1

IA

IB

RA

RB

jXA

jXB

(a) (b)

V’L

IA

IB

ZL

I

ZA

ZB

VLoad

VL

(c)

Figure 38: Equivalent Circuit for Transformers working in Parallel -Simplified circuit and

Further simplification for identical voltage ratio

101

Page 102: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

written as

IAZA = IBZB = IZ = v (say) (87)

HereI = IA + IB (88)

And Z is the equivalent impedance of the two transformers given by,

Z =ZAZB

ZA + ZB

(89)

Thus IA =v

ZA

=IZ

ZA

= I.ZB

ZA + ZB

(90)

and IB =v

ZB

=IZ

ZB

= I.ZA

ZA + ZB

If the terminal voltage is V = IZL then the active and reactive power supplied by each of

the two transformers is given by

PA = Real(V I∗

A) and QA = Imag(V I∗

A) and (91)

PB = Real(V I∗

B) and QB = Imag(V I∗

B) (92)

From the above it is seen that the transformer with higher impedance supplies lesser

load current and vice versa. If transformers of dissimilar ratings are paralleled the trans-

former with larger rating shall have smaller impedance as it has to produce the same drop

as the other transformer, at a larger current. Thus the ohmic values of the impedances must

be in the inverse ratio of the ratings of the transformers. IAZA = IBZB, therefore IA

IB

= ZB

ZA

.

Expressing the voltage drops in p.u basis, we aim at the same per unit drops at any load for

the transformers. The per unit impedances must therefore be the same on their respective

bases.

Fig. 39 shows the phasor diagram of operation for these conditions. The drops are

magnified and shown to improve clarity. It is seen that the total voltage drop inside the

102

Page 103: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

φBφA

E

θBθA

IB

IA

φ

IL

V2

V

IARA

IRIBRB

IBXBIX

IAXA

Figure 39: Phasor Diagram of Operation for two Transformers working in Parallel

transformers is v but the currents IA and IB are forced to have a different phase angle due

to the difference in the internal power factor angles θA and θB. This forces the active and

reactive components of the currents drawn by each transformer to be different ( even in

the case when current in each transformer is the same). If we want them to share the load

current in proportion to their ratings, their percentage ( or p.u) impedances must be the

same. In order to avoid any divergence and to share active and reactive powers also properly,

θA = θB . Thus the condition for satisfactory parallel operation is that the p.u resistances

and p.u reactance must be the same on their respective bases for the two transformers. To

determine the sharing of currents and power either p.u parameters or ohmic values can be

used.

103

Page 104: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

14.2 Case B :Unequal voltage ratios

VL

IA

IB

ZL

EA EB

I

RAjXA

RB jXB

Figure 40: Equivalent Circuit for unequal Voltage Ratio

One may not be able to get two transformers of identical voltage ratio in

spite of ones best efforts. Due to manufacturing differences, even in transformers built as

per the same design, the voltage ratios may not be the same. In such cases the circuit

representation for parallel operation will be different as shown in Fig. 40. In this case the

two input voltages cannot be merged to one, as they are different. The load brings about a

common connection at the output side. EA and EB are the no-load secondary emf. ZL is

the load impedance at the secondary terminals. By inspection the voltage equation can be

written as below:

EA = IAZA + (IA + IB)ZL = V + IAZA ·

EB = IBZB + (IA + IB)ZL = V + IBZB· (93)

Solving the two equations the expression for IA and IB can be obtained as

104

Page 105: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

IA =EAZB + (EA − EB)ZL

ZAZB + ZL(ZA + ZB)and (94)

IB =EBZA + (EB − EA)ZL

ZAZB + ZL(ZA + ZB)

ZA and ZB are phasors and hence there can be angular difference also in addition to

the difference in magnitude. When load is not connected there will be a circulating current

between the transformers. The currents in that case can be obtained by putting ZL = ∞

( after dividing the numerator and the denominator by ZL ). Then,

IA = −IB =(EA − EB)

(ZA + ZB)(95)

If the load impedance becomes zero as in the case of a short circuit, we have,

IA =EA

ZA

and IB =EB

ZB

(96)

Instead of the value of ZL if the value of V is known , the currents can be easily determined

( from Eqns. 93 ) as

IA =EA − V

ZA

and IB =EB − V

ZB

(97)

If more than two transformers are connected across a load then the calculation of

load currents following the method suggested above involves considerable amount of compu-

tational labor. A simpler and more elegant method for the case depicted in Fig. 41 is given

below. It is known by the name parallel generator theorem.

IL = IA + IB + IC + ......

But IA =EA − V

ZA

, IB =EB − V

ZB

, IC =EC − V

ZC

V = IL.ZL (98)

105

Page 106: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

V

IA

IB

IC

ZL

EA

EB

EC

I

RA

RB

jXA

jXB

RCjXC

Figure 41: Parallel Generator Theorem

Combining these equations

V

ZL

=EA − V

ZA

+EB − V

ZB

+EC − V

ZC

+ ... (99)

Grouping the terms together

V (1

ZL

+1

ZA

+1

ZB

+1

ZC

+ ...) =EA

ZA

+EB

ZB

+EC

ZC

+ ...

= ISCA + ISCB + ISCC + .... (100)

(1

ZL

+1

ZA

+1

ZB

+1

ZC

+ ...) =1

Z(101)

V = Z(ISCA + ISCB + ISCC + ....) (102)

From this V can be obtained. Substituting V in Eqn. 98, IA, IB etc can be obtained.

Knowing the individual current phasor, the load shared by each transformer can be com-

puted.

106

Page 107: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

15 Transformer voltage control and Tap changing

Regulating the voltage of a transformer is a requirement that often arises in a power

application or power system.

In an application it may be needed

1. To supply a desired voltage to the load.

2. To counter the voltage drops due to loads.

3. To counter the input supply voltage changes on load.

On a power system the transformers are additionally required to perform the task of

regulation of active and reactive power flows.

Reverser

Booster transformer

Regulation

transformer

Booster transformer

Reverser

Main

transformer

tertiary

B B

1

2

1

2

Figure 42: Tap changing and Buck Boost arrangement

The voltage control is performed by changing the turns ratio. This is done by provi-

sion of taps in the winding. The volts per turn available in large transformers is quite high

and hence a change of even one turn on the LV side represents a large percentage change

in the voltage. Also the LV currents are normally too large to take out the tapping from

the windings. LV winding being the inner winding in a core type transformer adds to the

107

Page 108: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

difficulty of taking out of the taps. Hence irrespective of the end use for which tapping is put

to, taps are provided on the HV winding. Provision of taps to control voltage is called tap

changing. In the case of power systems, voltage levels are some times changed by injecting a

suitable voltage in series with the line. This may be called buck-boost arrangement. In ad-

dition to the magnitude, phase of the injected voltage may be varied in power systems. The

tap changing arrangement and buck boost arrangement with phase shift are shown in Fig. 42.

Tap changing can be effected when a) the transformers is on no- load and b) the load

is still remains connected to the transformer. These are called off load tap changing and

on load tap changing. The Off load tap changing relatively costs less. The tap positions

are changed when the transformer is taken out of the circuit and reconnected. The on-load

tap changer on the other hand tries to change the taps without the interruption of the load

current. In view of this requirement it normally costs more. A few schemes of on-load tap

changing are now discussed.

108

Page 109: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

HV LV

Reactor

s

1

2

3

4

5

Figure 43: Reactor Method of Tap Changer ( with table of switching)

109

Page 110: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

Tap switches closed

1 1,s

2 1,2

3 2,s

4 2,3

5 3,s

6 3,4

7 4,s

8 4,5

9 5,s

Reactor method The diagram of connections is shown in Fig. 43. This method employs

an auxiliary reactor to assist tap changing. The switches for the taps and that across

the reactor(S) are connected as shown. The reactor has a center tapped winding on

a magnetic core. The two ends of the reactor are connected to the two bus bars to

which tapping switches of odd/even numbered taps are connected. When only one tap

is connected to the reactor the shorting switch S is closed minimizing the drop in the

reactor. The reactor can also be worked with both ends connected to two successive

taps. In that case the switch ’S’ must be kept open. The reactor limits the circulating

current between the taps in such a situation. Thus a four step tapped winding can be

used for getting seven step voltage on the secondary(see the table of switching). The

advantage of this type of tap changer are

1. Load need not be switched off.

2. More steps than taps are obtained.

3. Switches need not interrupt load current as a alternate path is always provided.

110

Page 111: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

The major objection to this scheme seems to be that the reactor is in the circuit always

generating extra loss.

Parallel winding, transformer method In order to maintain the continuity of supply

the primary winding is split into two parallel circuits each circuit having the taps as

shown in Fig. 44. Two circuit breakers A and B are used in the two circuits. Initially

tap 1a and 1b are closed and the transformer is energized with full primary voltage.

To change the tap the circuit breaker A is opened momentarily and tap is moved from

1a to 2a. Then circuit breaker A is closed. When the circuit A is opened whole of the

primary current of the transformer flows through the circuit B. A small difference in

the number of turns between the two circuit exists. This produces a circulating current

between them. Next, circuit breaker B is opened momentarily, the tap is changed from

1b to 2b and the breaker is closed. In this position the two circuits are similar and there

is no circulating current. The circulating current is controlled by careful selection of

the leakage reactance. Generally, parallel circuits are needed in primary and secondary

to carry the large current in a big transformer. Provision of taps switches and circuit

breakers are to be additionally provided to achieve tap changing in these machines.

Series booster method In this case a separate transformer is used to buck/boost the

voltage of the main transformer. The main transformer need not be having a tapped

arrangement. This arrangement can be added to an existing system also. Fig. 42shows

the booster arrangement for a single phase supply. The reverser switch reverses the

polarity of the injected voltage and hence a boost is converted into a buck and vice

versa. The power rating of this transformer need be a small fraction of the main

transformer as it is required to handle only the power associated with the injected

voltage. One precaution to be taken with this arrangement is that the winding must

111

Page 112: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

A B

HVLV

a1a2

a3a4

b1 b2 b3 b4

Figure 44: Parallel Primary Winding Tap Changing

112

Page 113: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

not be open circuited. If it gets open circuited the core (B in fig) gets highly saturated.

In spite of the small ratings and low voltages and flexibility, this method of voltage

control costs more mainly due to the additional floor space it needs. The methods of

voltage regulation discussed so far basically use the principle of tap changing and hence

the voltage change takes place in steps. Applications like a.c. and d.c. motor speed

control, illumination control by dimmers, electro-chemistry and voltage stabilizers need

continuous control of voltage. This can be obtained with the help of moving coil voltage

regulators.

Vin

5%

95%

a1

b1

S

a2

b2

Vout

Figure 45: Moving Coil Voltage Regulator

moving coil voltage regulators Fig. 45 shows the physical arrangement of one such trans-

former. a, b are the two primary windings wound on a long core, wound in the opposite

113

Page 114: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

sense. Thus the flux produced by each winding takes a path through the air to link

the winding. These fluxes link their secondaries a2 and b2. A short circuited moving

coil s is wound on the same limb and is capable of being held at any desired position.

This moving coil alters the inductances of the two primaries. The sharing of the total

applied voltage thus becomes different and also the induced emf in the secondaries a2

and b2. The total secondary voltage in the present case varies from 10 percent to 20

percent of the input in a continuous manner. The turns ratios of a1 : a2 and b1 : b2

are 4.86 and 10.6 respectively. 5

4.86+ 95

10.6= 10% when s is in the top position. In

the bottom position it becomes 95

4.86+ 5

10.6= 20%. By selecting proper ratios for the

secondaries a2 and b2 one can get the desired voltage variation.

V1

sliding contact

Variable secondary

a.c voltage

V2

a) without electrical isolation

V1

b) with electrical isolation

Figure 46: Sliding Contact Regulator

Sliding contact regulators These have two winding or auto transformer like construction.

The winding from which the output is taken is bared and a sliding contact taps the

voltage. The minimum step size of voltage change obtainable is the voltage across a

single turn. The conductor is chosen on the basis of the maximum load current on the

114

Page 115: Transformers - Weeblykurratul.weebly.com/uploads/3/3/4/6/3346099/transformer-1.pdf · The second coil which is made to link this field has an induced voltage in the same. The magnitude

Electrical Machines I Prof. Krishna Vasudevan, Prof. G. Sridhara Rao, Prof. P. Sasidhara Rao

Indian Institute of Technology Madras

output side. In smaller ratings this is highly cost effective. Two winding arrangements

are also possible. The two winding arrangement provides electrical isolation also.These

are shown in Fig. 46.