TRANSFORMERSD E S C R I P T I O N
NEVER USED, NEVER ASSEMBLED—A set of five transformers, ranging from 100 to 1250 KVA, and designed to withstand the harsh conditions and demands of a mine site.
The following transformers are included in this package:
¡ Schneider Dry Transformer 0.69-0.42 kV – 100kVA
(See Appendix A)
¡ Schneider Dry Transformer 0.69-0.42 kV – 400kVA
(See Appendix B)
¡ Schneider Oil Transformer 15-0.72 kV – 630kVA
(See Appendix C)
¡ Schneider Oil Transformer 15-0.72 kV – 1000kVA
(See Appendix D)
¡ Schneider Oil Transformer 15-0.420 kV – 1250kVA
(See Appendix E)
ID 10C-AR-A5
OEM SCHNEIDER
YOM 2013
LOCATION WAREHOUSE, DUNKIRK FRANCE
CONDITION NEVER USED
PACKAGING ORIGINAL CRATES
Pre-Owned Mining, Processing & Construction Equipment Since 1979
DATAS H E E TS & I D PL AT E
APPENDIX A
+1 (530) [email protected]
Dry Transformer 0.69-0.42 kV – 100kVA
Rev
1 ITEM:
2 Job specification: 9806J 0440 JSS 1641 002 Standards, codes: IEC
3 Manufacturer:
4 ENVIRONMENTAL CONDITIONS
5 Installation (indoor/outdoor) / Ambient Type
6 Ambient Design Temperature Max: 30 °C Min: 10°C
7 Altitude/Relative Humidity a.s.l.: <1000m
8 GENERAL REQUIREMENTS (VENDOR TO COMPLY WITH)
9 Type Dry type: Impregnated Cast resin
10 Kind of transformer With separate windings
11 No Load Voltage Ratio / Highest voltage Um KV / KV kV / kV
12 Secondary voltage at rated power & P.F. of 0.8 kV
13 Mode of operation (individual / parallel)
14 Frequency/Phases 50 Hz 2+/- % No: 3 phase
15 Maximum primary system short circuit rating
16 Maximum short circuit duration
17 Off Circuit Tap Changer ± 2,5 % per step N° steps: 5 Total range: ± 5 %
18 Windings
19 Winding Connection and Vector Group
20 Insulation class
21
22 Transformer mounting Skid Rollers Bidirectionnal roller
23 Metallic enclosure protection : IP 31
Copper
Dyn 11
Class F minimum
Ambient / climate / fire resistance Certified E2/C2/F1 according to standard CEI 60076-11
0,690 / 0,420-0,240 Refer to IEC 60076-3
0,400 - 0,230
individual operation
50 kA rms
2 sec According to IEC 60076-5
DRY LV/LV (0.69/0,420kV) TRANSFORMER
QUANTITY 2
Indoor , in safe areaIndustrial, dusty & corrosive atmosphere (Mining).
Autotransformer
Doc code
DISTRIBUTION TRANSFORMERS
24 Accessories
25 Lifting rings Yes No
26 2 grouding clamps Yes No
27 Lugs and hooks Yes No
28 Monitoring box for temperature sensors Yes No
29
30 TRANSFORMER SPECIFIC'S DATA (VENDOR TO COMPLY WITH)
31
32 Transformer tag: See line 1 Quantity: See line 1
33 Nominal Rating Natural Cooling (AN)
34 Cooling type
35 Impedance Voltage
36 Primary Connections Bus Duct Cable 5G120 mm²
37 Secondary Connections Bus Duct Cable 5G95 mm²
38 Cable Type & n° per phase Primary:
39 Cable Type & n° per phase Secondary :
40 Primary terminals Suppliers to specify transformers facilities for the cables connection
41 Secondary terminals on all terminals, primary, secondary and neutral. ( to be included in
42 Secondary: neutral brought out: YES scope and supply )
43 Neutral connection: cable type / section HOLD HOLD mm²
44 CT on neutral (ratio / class) NA
45 System earthing
46 Sound press. Level at 1 m / Sound power level < 85 LPA (dB) LWA (dB)
47 TRANSFORMER MANUFACTURER'S DATA (PART TO BE FILLED IN BY VENDOR)
48 Manufacturer / Model type Schneider Electric Tricast
100 kVAAN
4%
HOLD
HOLD
Primary : TNC Secondary: TNS
Page : 1
Doc code
DISTRIBUTION TRANSFORMERS
49 No Load Losses / No Load Current (primary) 600 W After Order %
50 Load Losses 4/4 Load: 2000 3/4 Load: 1130 2/4 Load: 500
51 Full Load Voltage Drop at 0.8 Power Factor 3,69 %
52 Efficiency at 0,8 Power Factor 4/4 Load: 96,85% 3/4 Load: 97,21% 2/4 Load: 97,32%
53 Efficiency at 1 Power Factor 4/4 Load: 97,47% 3/4 Load: 97,75% 2/4 Load: 97,85%
54 Impedance voltage (%) / with tolerance of % 4 Ucc: % Tolerance: 10 %
55 Magnetizing / Inrush current After Order A After Order A
56 Primary Bushing Quantity / Type N°: 3 copper termil plate
57 Secondary Bushing Quantity / Type N°: 4 copper termil plate
58 Total Weight 955 kg
59 Overall Dimensions (Length/Width/Height) L 1525mm W 1200mm H 1600mm
60 When applicable, dimensions between rollers mm
61 Painting (Mfr standard,... / color) Specification: acc. N21240023 / color 7032
62 Tropicalization Yes No
63 Sound press. Level at 1 m / Sound power level 45 LPA (dB) 58 LWA (dB)
64 current density A/ mm2
65 Core material and grade M5 Type cold grain-oriented steel
Page : 2
1 2 I 3 I 4
148
A A
0 Seider 0
,...._ Electric -
I Schneider Enerji End. San. ve Tic. AS 41420 Kocaeli - Turkey I 3-PHASE DRY TYPE TRANSFORMER WITH ENCLOSURE
B B FOR INDOOR INSTALLATION
I TYPE Tricast NO.: STANDARD : IEC 60076-11
I RATED POWER 100 kVA YEAR
-POS. 1 723 V FREQUENCY 50 Hz -
POS.2 7 09 V VECTOR GROUP Dyn11
I RA TED VOLTAGE POS. 3 690 V 420 V TYPE OF COOLING AN
POS. 4 676 V PROTECTION IP 3 1 0
POS. 5 658 V WEIGHT : 955 kg co
C T"""
C
Cf) RATED CURRENT 83.7 A 137.5 A I U m < 1.1 kV INSULATION LEVEL LI: AC: 3 / LI: AC:3 kV
RATED IMPED.VOLTAGE % DURATION OF SHORT-CIRCUIT MAX. 2 s w
- -SHORT-CIRCUIT CURRENT kA THERMAL CLASS HV/LV H / H
-
w
Cf) MAX. AMBIENT TEMPERATURE 3 0 'C COILS MATERIAL HV/LV cu/ cu w
_J _J
1V 2V
mD
?-w POS.1 POS.2 POS.3 POS.4 POS.5
D
1U1W B 1W 1V 1U 2W 2V 2U 2N
2U
' i i I -
CONNECTION TAPPING CONNECTION -
0 CONNECTION DIAGRAM 0
5853195 1
E PLATE D 148x180 CR-NI E
FOR APPROVAL Blank fields will be filled out after the test.
EN
Dimensions Approved by Definition: Class code -
without tol.acc.to ISO 2768-m
Date 01.11.2013 Description: Scale Group ADH-E1
Rating Plate F
1 : 1 F
Seider Drawing No: Sh.No: Sheet:
CAD Electric1 1
Replaces by
I Canceled by AutoCAD
Pos Revision Date Name Drawing no: Drawing no:
1 2 I 3 I 4
Pre-Owned Mining, Processing & Construction Equipment Since 1979
DATAS H E E TS & I D PL AT E
APPENDIX B
+1 (530) [email protected]
Dry Transformer 0.69-0.42 kV – 400kVA
Rev
1 ITEM:
2 Job specification: 9806J 0440 JSS 1641 002 Standards, codes: IEC
3 Manufacturer:
4 ENVIRONMENTAL CONDITIONS
5 Installation (indoor/outdoor) / Ambient Type
6 Ambient Design Temperature Max: 30 °C Min: 10°C
7 Altitude/Relative Humidity a.s.l.: <1000m
8 GENERAL REQUIREMENTS (VENDOR TO COMPLY WITH)
9 Type Dry type: Impregnated Cast resin
10 Kind of transformer With separate windings
11 No Load Voltage Ratio / Highest voltage Um KV / KV kV / kV
12 Secondary voltage at rated power & P.F. of 0.8 kV
13 Mode of operation (individual / parallel)
14 Frequency/Phases 50 Hz 2+/- % No: 3 phase
15 Maximum primary system short circuit rating
16 Maximum short circuit duration
17 Off Circuit Tap Changer ± 2,5 % per step N° steps: 5 Total range: ± 5 %
18 Windings
19 Winding Connection and Vector Group
50 kA rms
DRY LV/LV (0,690/0,420kV) TRANSFORMER
QUANTITY 1
Indoor , in safe areaIndustrial, dusty & corrosive atmosphere.
Autotransformer
0,690 / 0,420-0,240 Refer to IEC 60076-3
0,400 - 0,230
individual operation
2 sec According to IEC 60076-5
Copper
Dyn 11
Project n - Unit Doc code Mat. code Serial n Rev n
DISTRIBUTION TRANSFORMERS
20 Insulation class
21
22 Transformer mounting Skid Rollers Bidirectionnal roller
23 Metallic enclosure protection : IP 31
24 Accessories
25 Lifting rings Yes No
26 2 grouding clamps Yes No
27 Lugs and hooks Yes No
28 Monitoring box for temperature sensors Yes No
29
30 TRANSFORMER SPECIFIC'S DATA (VENDOR TO COMPLY WITH)
31
32 Transformer tag: See line 1 Quantity: See line 1
4 33 Nominal Rating Natural Cooling (AN)
34 Cooling type
35 Impedance Voltage
4 36 Primary Connections : See line 38 Bus Duct Cable line 38 mm²
4 37 Secondary Connections: See line 39 Bus Duct Cable line 39 mm²
4 38 Cable Type & n° per phase Primary:
4 39 Cable Type & n° per phase Secondary :
40 Primary terminals Suppliers to specify transformers facilities for the cables connection
41 Secondary terminals on all terminals, primary, secondary and neutral. ( to be included in
42 Secondary: neutral brought out: YES scope and supply )
43 Neutral connection: cable type / section line39 mm²
44 CT on neutral (ratio / class) NA
45 System earthing
4 46 Sound press. Level at 1 m / Sound power level < 85 LPA (dB) LWA (dB)
Class F minimum
Ambient / climate / fire resistance Certified E2/C2/F1 according to standard CEI 60076-11
Primary : IT Secondary: TNS
400 kVAAN
4%
2 cables 4G120 mm² / CU-XLPE-GSTA-PVC
2cables 5G240 mm² / CU-XLPE-GSTA-PVC
Page : 1
DISTRIBUTION TRANSFORMERS
47 TRANSFORMER MANUFACTURER'S DATA (PART TO BE FILLED IN BY VENDOR)
48 Manufacturer / Model type Schneider Tricast
49 No Load Losses / No Load Current (primary) 1700 W %
50 Load Losses 4/4 Load: 4700 W 3/4 Load: 2640 W 2/4 Load: 1180 W
51 Full Load Voltage Drop at 0.8 Power Factor 3.26 %
52 Efficiency at 0,8 Power Factor 4/4 Load: 98.04% 3/4 Load: 98.22% 2/4 Load: 98.23%
53 Efficiency at 1 Power Factor 4/4 Load: 98.43% 3/4 Load: 98.57% 2/4 Load: 98.58%
54 Impedance voltage (%) / with tolerance of % Ucc: 4% Tolerance: 10%
55 Magnetizing / Inrush current A A
56 Primary Bushing Quantity / Type N°: 3 copper termi l plate
57 Secondary Bushing Quantity / Type N°: 4 copper ter mil plate
58 Total Weight 2030 kg
59 Overall Dimensions (Length/Width/Height) L 2025 W 2148 H 1800
60 When applicable, dimensions between rollers mm
61 Painting (Mfr standard,... / color) Specification: acc. N21240023 / color 7032
62 Tropicalization Yes No
63 Sound press. Level at 1 m / Sound power level 48 LPA (dB) 62 LWA (dB)
64 current density A/ mm2
65 Core material and grade
Page : 2
1 2 I 3 I 4
148
A A
0 Seider 0
,...._ Electric -
I Schneider Enerji End. San. ve Tic. AS 41420 Kocaeli - Turkey I 3-PHASE DRY TYPE TRANSFORMER WITH ENCLOSURE
B B FOR INDOOR INSTALLATION
I TYPE Tricast NO.: STANDARD : IEC 60076-11
I RATED POWER 400 kVA YEAR
-POS. 1 727 V FREQUENCY 50 Hz -
POS. 2 704 V VECTOR GROUP Dyn11
I RA TED VOLTAGE POS. 3 693 V 420 V TYPE OF COOLING AN
POS. 4 670 V PROTECTION IP 31 0
POS. 5 658 V WEIGHT : 2030 kg co
C T"""
C
Cf) RATED CURRENT 333.25 A 549.9 A I U m 1.1 kV INSULATION LEVEL LI: AC: 3 I LI: AC:3 kV
RATED IMPED.VOLTAGE % DURATION OF SHORT-CIRCUIT MAX. 2 s w
- -SHORT-CIRCUIT CURRENT kA THERMAL CLASS HV/LV H / H
-
w
Cf) MAX. AMBIENT TEMPERATURE 30 'C COILS MATERIAL HV/LV cu/ cu w
_J _J
1V 2V
mD
?-w POS.1 POS.2 POS.3 POS.4 POS.5
D
1U1W B 1W 1V 1U 2W 2V 2U 2N
2U
' i i I -
CONNECTION TAPPING CONNECTION -
0 CONNECTION DIAGRAM 0
5853105 1
E PLATE D 148x180 CR-NI E
FOR APPROVAL Blank fields will be filled out after the test.
EN
Dimensions Approved by Definition: Class code -
without tol.acc.to ISO 2768-m
Date 22.08.2013 Description: Scale Group ADH-E1
Rating Plate F
1 : 1 F
Seider Drawing No: Sh.No: Sheet:
CAD 02 18.09.13 Electric1 1
Replaces by
I Canceled by AutoCAD
Pos Revision Date Name Drawing no: Drawing no:
1 2 I 3 I 4
Pre-Owned Mining, Processing & Construction Equipment Since 1979
DATAS H E E TS & I D PL AT E
APPENDIX C
+1 (530) [email protected]
Oil Transformer 15-0.72 kV – 630kVA
Rev
1 ITEM :
2 Job specification: 9806J 0440 JSS 1641 002 Standards, codes: IEC3 Manufacturer:4 ENVIRONMENTAL CONDITIONS
5 Installation (indoor/outdoor) / Ambient Type
6 Ambient Design Temperature Max: 47 °C Min: 5°C7 Altitude/Relative Humidity a.s.l.: <1000m8 GENERAL REQUIREMENTS (VENDOR TO COMPLY WITH)9 Type
10 Dry type: Impregnated Cast resin11 Kind of transformer With separate windings Autotransformer12 No Load Voltage Ratio / Highest voltage Um KV / KV kV / kV13 Secondary voltage at rated power & P.F. of 0.8 V14 Mode of operation (individual / parallel)15 Frequency/Phases 50 Hz 2 +/- % No: 3 phase16 Maximum primary system short circuit current rating 31,5 kA rms17 Maximum short circuit duration18 Off Circuit Tap Changer ± 2,5 % per step N° steps: 5 Total range: ± 5 %19 On Load Tap Changer ± % per step N° steps: Total range: ± %20 Winding Connection and Vector Group Dyn 1121 Insulation class22 Oil / Winding Temperature Rise (with ambient at 47°C) Oil: 53 °C Winding: 58 °C23 Oil type24 Transformer mounting Skid Rollers Bidirectionnal roller25 Accessories26 "DGPT2" type multifunction relay Yes No27 Buchholz relay with 2 contacts (alarm / trip) Yes No28 Air breather and dryer Yes No29 Oil filler plug Yes No30 Conservator oil drain plug Yes No31 Top oil thermometer with 2 contacts (alarm / trip) Yes No32 Dial thermometer with 2 contacts (alarm / trip) Yes No
OIL IMMERSED HV/LV (15/0,72kV) SEALED TRANSFORMER
QUANTITY
Outd oor , under sun shade, in safe area
Industrial, Dusty & corrosive atmosphere (Mining), sand storm
With conservator Sealed
15 / 0,720 Refer to IEC 60076-3690
(Yes / Yes)
2 sec According to IEC 60076-5
Class A
Mineral oil
Doc code
DISTRIBUTION TRANSFORMERS
32 Dial thermometer with 2 contacts (alarm / trip) Yes No33 Liquid level gauge Yes No34 Pressure relief valve with operating signal contact Yes No35 Oil level gauge with alarm contact Yes No3637 Lifting rings Yes No38 Safety valve Yes No39 Filling valve Yes No40 Tank oil drain plug Yes No41 2 filterpress connections Yes No42 Insulation for tank earth protection Yes No43 2 earthing clamps Yes No44 Lugs and hooks Yes No4546 Drip pan Yes No47 TRANSFORMER SPECIFIC'S DATA (VENDOR TO COMPLY WITH)48 Transformer tag See line 1 Quantity: 49 Cooling type (ONAN, ONAF,…)
50 Nominal Rating Natural Cooling (ONAN)
51 Nominal Rating Forced Cooling (ONAF)52 Impedance Voltage53 Primary Connections Bus Duct Cable line55 mm²54 Secondary Connections Bus Duct Cable line56 mm²55 Primary
56 Secondary
57 CT on secondary (number per phase / ratio / class)
58 Primary terminals Box Plug in
59 Secondary terminals Box Plug in
60 Secondary / neutral brought out Box Plug in Yes No61 Neutral connection: cable type / section HOLD mm²
630 kVA @ 47°CONAN
4%
Cable Type & n° per phase
3 x 95 mm² multipolar
1 unipolar 300 mm² per phase1 unipolar 95 mmĮ for SP0
NA NA NA
Plug in connectors (mobile and fix part) to be supplied by Vendor
Cable glands out of scope
HOLD
Page : 1
OIL IMMERSED HV/LV (15/0,72kV) SEALED TRANSFORMER
Doc code
DISTRIBUTION TRANSFORMERS
62 CT ring on neutral (ratio / class) NA63 Earthing resistor / resistor rating Yes No NA Ω
64 Earthing resistor box / installation /protection degree Yes No
65 Earthing system
66 Auxiliary Connections67 Sound press. level at 1 m / Sound power level < 85 LPA (dB) LWA (dB)68 Tropicalization Yes No69 TRANSFORMER MANUFACTURER'S DATA (PART TO BE FILLED IN BY VENDOR)70 Manufacturer / Model71 Highest Voltage (rms) Primary Winding: 17.5 kV Secondary Winding: 1.1 kV72 Short Duration Power Frequency Withst. Volt. (rms) Primary Line Term.: 38 kV Second. Line Term.: 3 kV73 Lightning Impulse Withstand Voltage (peak) Primary Line Term.: 95 kV Second. Line Term.: - kV74 Short Duration Power Frequency Withst. Volt. (rms) Primary Neut. Term.: 38 kV Second. Neut. Term.: 3 kV75 Lightning Impulse Withstand Voltage (peak) Primary Neut. Term.: 95 kV Second. Neut. Term.: - kV76 No Load Losses / No Load Current (primary) 1.4 KW 0,8 % of full load 1,25%77 Load Losses 4/4 Load: 9 kW 3/4 Load: 5.1 kW 2/4 Load: 2.3 kW78 Full Load Voltage Drop at 0.8 Power Factor 3,41 %79 Efficiency at 0,8 Power Factor 4/4 Load: 97,91% 3/4 Load: 98,28% 2/4 Load: 98,55%80 Efficiency at 1 Power Factor 4/4 Load: 98,35% 3/4 Load: 98,64% 2/4 Load: 98,85%81 Impedance voltage (%) / with tolerance of % Ucc: 4 % Tolerance: ±10 %82 Zero- Sequence Impedance 3.6 %83 X/R 3.4584 Magnetizing / Inrush current 0.3 A 273 (Peak) A85 Primary Bushing Quantity / Type N°: 3 Plug-in 86 Secondary Bushing Quantity / Type N°: 3 + 1 N Porcelain87 Fan Motors (Quantity / Rating / Voltage) N°: NA kW V88 Weight Iron / Copper 680 kg 260 kg89 Oil Weight 400 kg90 Total Weight 1740 kg91 Overall Dimensions (Length/Width/Height) 1710 mm 1120 mm 1530 mm92 When applicable, dimensions between rollers 670 mm93 Painting (Mfr standard,... / color) Spec: according TR-DC-0002-A010694 Tropicalization Yes No95 Sound press. level at 1 m / Sound power level LPA (dB) LWA (dB)
Prim.: IT through neutral earthing transformer (at main substation)Sec.: IT (neutral resistor in the LV swichboard)
NA
55
Schneider Electric DCU 4132
6795 Sound press. level at 1 m / Sound power level LPA (dB) LWA (dB)96 Current density Primary / Secondary A/mm² A/mm²97 Core material and grade Conventional Grain Oriented Steel (CGOS)98 Regulation at 47°C 96,5999 Earthing resistor rating - A100 Straight fault current limitation - A101 Straight fault short time rating - S
553,55 3,45
67
Page : 2
i - 8.
g
-·
];e
!:!
w
0 s1,eider 0
Electric
I Schneider Enerji End. San. ve Tic. AS Kocaeli - Turkey ITYPE DCU 3832 IINR I RA TED POWER 630 kVAIIMODEL
POS.1 15750 V POS.2 15375 V
I RA TED VOLTAGE POS.3 15000 V POS.4 14625 V POS.5 14250 V
RATED CURRENT 24,25 A RATED IMPED.VOLTAGE %
SHORT-CIRCUIT CURRENT kA OIL TYPE WINDING TEMPERATURE RISE 58 °K OIL TEMPERATURE RISE 53 °K
A T T E N T I O N! HERMETICALLY SEALED TRANSFORMER
IIYEAR LT II PHASE
V V
720 V V V
505,2 A
II IEC 60076 311 FREQUENCY 50 Hz
AMBIENT TEMP. 47 °c SERVICE CONTINUOUS VECTOR GROUP Dyn11 COOLING METHOD ONAN
TOTAL WEIGHT 1,74 t OIL WEIGHT 0,40 t
ACTIVE PART WEIGHT 0,99 t INSULATION LEVEL LI 95 kV AC 38 kV/ LI -AC 3 kVI DURATION OF SHORT-CIRCUIT 2 sl OIL DRAIN IN 20°c 0 It I
I
z I N..,
TRANSFORMER IS FILLED UP AS HERMETIC ::::,
'----....
::::,
AND READY FOR OPERATING > N..,
.... DO NOT OPEN IT ! L-... >
!!: N..,
DO NOT VENT BUSHINGS ! .... !!: N..,
Empty fields shall be engraved after factory tests.
I TAG NO I Plate D148x148 CR-NI T0947
Dimensions App. Class without tolerance ace
ISO 2768 RPL Fb.No:
Date 05.11.2013 Department ADH-T1 Rating plate Designer
Check
Drawing no Page no Pages
5c&raeider 1 1 Electric Cancelled b Replaced by
NO Rev Date Name drawing drawing
Code Nr.
Autocad
Pre-Owned Mining, Processing & Construction Equipment Since 1979
DATAS H E E TS & I D PL AT E
APPENDIX D
+1 (530) [email protected]
Oil Transformer 15-0.72 kV – 1000kVA
Page : 1
Rev
1 ITEM :
2 Job specification: 9806J 0440 JSS 1641 002 Standards, codes: IEC3 Manufacturer:4 ENVIRONMENTAL CONDITIONS
5 Installation (indoor/outdoor) / Ambient Type
6 Ambient Design Temperature Max: 47 °C Min: 5°C7 Altitude/Relative Humidity a.s.l.: <1000m8 GENERAL REQUIREMENTS (VENDOR TO COMPLY WITH)9 Type
10 Dry type: Impregnated Cast resin11 Kind of transformer With separate windings Autotransformer12 No Load Voltage Ratio / Highest voltage Um KV / KV kV / kV13 Secondary voltage at rated power & P.F. of 0.8 V14 Mode of operation (individual / parallel)15 Frequency/Phases 50 Hz 2 +/- % No: 3 phase16 Maximum primary system short circuit current rating 31,5 kA rms17 Maximum short circuit duration18 Off Circuit Tap Changer ± 2,5 % per step N° steps: 5 Total range: ± 5 %19 On Load Tap Changer ± % per step N° steps: Total range: ± %20 Winding Connection and Vector Group Dyn 1121 Insulation class22 Oil / Winding Temperature Rise (with ambient at 47°C) Oil: 53 °C Winding: 58 °C23 Oil type24 Transformer mounting Skid Rollers Bidirectionnal roller
25 LV protection integrated.
26 Accessories27 "DGPT2" type multifunction relay Yes No28 Buchholz relay with 2 contacts (alarm / trip) Yes No29 Air breather and dryer Yes No30 Oil filler plug Yes No31 Conservator oil drain plug Yes No32 Top oil thermometer with 2 contacts (alarm / trip) Yes No33 Dial thermometer with 2 contacts (alarm / trip) Yes No34 Liquid level gauge Yes No35 Pressure relief valve with operating signal contact Yes No36 Oil level gauge with alarm contact Yes No37 Surge arrester (primary side) Yes No38 Lifting rings Yes No39 Safety valve Yes No40 Filling valve Yes No41 Tank oil drain valve / oil sampler Yes No42 2 filterpress connections Yes No43 Insulation for tank earth protection Yes No44 2 earthing clamps Yes No45 Lugs and hooks Yes No46 Drip pan Yes No47 TRANSFORMER SPECIFIC'S DATA (VENDOR TO COMPLY WITH)48 Transformer tag See line 1 Quantity: see SR rev 249 Cooling type (ONAN, ONAF,…)50 Nominal Rating Natural Cooling (ONAN)51 Nominal Rating Forced Cooling (ONAF)52 Impedance Voltage53 Primary Connections Bus Duct Cable line 55 mm²54 Secondary Connections Bus Duct Cable line 56 mm²55 Primary56 Secondary57 CT on secondary (number per phase / ratio / class)
58 Primary terminals Box Plug in
59 Secondary terminals Box Plug in
60 Secondary / neutral brought out Box Plug in Yes No61 Neutral connection: cable type / section HOLD mm²62 CT ring on neutral (ratio / class) NA63 Earthing resistor / resistor rating Yes No NA Ω64 Earthing resistor box / installation /protection degree Yes No
OIL IMMERSED HV/LV (15/0,72kV) SEALED TRANSFORMER
QUANTITY
Outdoor, under sun shade, in safe area
Industrial, Dusty & corrosive atmosphere (Mining), sand storm
ONAN
With conservator Sealed
15 / 0,720 Refer to IEC 60076-3690
(Yes / No)
2 sec According to IEC 60076-5
Class A
Mineral oil
NA
HOLD
1000 kVA @ 47°C
5%
Cable Type & n° per phase 3X95mm² - multicore2x(3X1x300mm²) unipolar
NA NA NAPlug in connectors to be supplied by Vendor
Cable glands out of scope
NA
TR-DC-0012-A4101
Page : 2
TR-DC-0012-A4101
65 Earthing system
66 Auxiliary Connections67 Sound press. level at 1 m / Sound power level < 85 LPA (dB) LWA (dB)68 Tropicalization Yes No69 TRANSFORMER MANUFACTURER'S DATA (PART TO BE FILLED IN BY VENDOR)70 Manufacturer / Model71 Highest Voltage (rms) Primary Winding: 17.5 kV Secondary Winding: 1.1 kV72 Short Duration Power Frequency Withst. Volt. (rms) Primary Line Term.: 38 kV Second. Line Term.: 3 kV73 Lightning Impulse Withstand Voltage (peak) Primary Line Term.: 95 kV Second. Line Term.: - kV74 Short Duration Power Frequency Withst. Volt. (rms) Primary Neut. Term.: 38 kV Second. Neut. Term.: 3 kV75 Lightning Impulse Withstand Voltage (peak) Primary Neut. Term.: 95 kV Second. Neut. Term.: - kV76 No Load Losses / No Load Current (primary) 1.9 KW 0,8 % of full load 1,05%77 Load Losses 4/4 Load: 13 kW 3/4 Load: 7.31 kW 2/4 Load: 3.25 kW78 Full Load Voltage Drop at 0.8 Power Factor 3,98 %79 Efficiency at 0,8 Power Factor 4/4 Load: 98,17% 3/4 Load: 98,49% 2/4 Load: 98,73%80 Efficiency at 1 Power Factor 4/4 Load: 98,53% 3/4 Load: 98,79% 2/4 Load: 98,98%81 Impedance voltage (%) / with tolerance of % Ucc: 5 % Tolerance: ±10 %82 Zero- Sequence Impedance 4.8 %83 X/R 4.284 Magnetizing / Inrush current 0.42 A 208.20 (Peak) A85 Primary Bushing Quantity / Type N°: 3 Porcelain86 Secondary Bushing Quantity / Type N°: 3 + 1 N Porcelain87 Fan Motors (Quantity / Rating / Voltage) N°: NA kW V88 Weight Iron / Copper 900 kg 350 kg89 Oil Weight 570 kg90 Total Weight 2800 kg91 Overall Dimensions (Length/Width/Height) 2010 mm 1500 mm 1880 mm92 When applicable, dimensions between rollers 820 mm mm93 Painting (Mfr standard,... / color) Spec 94 Tropicalization Yes No95 Sound press. level at 1 m / Sound power level LPA (dB) LWA (dB)96 Current density Primary / Secondary A/mm² A/mm²97 Core material and grade Conventional Grain Oriented Steel (CGOS)98 Regulation at 47°C 96,0299 Earthing resistor rating - A100 Straight fault current limitation - A101 Straight fault short time rating - S
Schneider Electric DCU 4032
70
Prim.: IT through neutral earthing transformer (at main substation)Sec.:
583,85 3,65
Pre-Owned Mining, Processing & Construction Equipment Since 1979
DATAS H E E TS & I D PL AT E
APPENDIX E
+1 (530) [email protected]
Oil Transformer 15-0.420 kV – 1250kVA
Page : 1
Rev1 ITEM:2 Job specification: 9806J 0440 JSS 1641 002 Standards, codes: IEC3 Manufacturer:4 ENVIRONMENTAL CONDITIONS
5 Installation (indoor/outdoor) / Ambient Type
6 Ambient Design Temperature Max: 47 °C Min: 5°C7 Altitude/Relative Humidity a.s.l.: <1000m8 GENERAL REQUIREMENTS (VENDOR TO COMPLY WITH)9 Type
10 Dry type: Impregnated Cast resin11 Kind of transformer With separate windings Autotransformer12 No Load Voltage Ratio / Highest voltage Um KV / KV kV / kV13 Secondary voltage at rated power & P.F. of 0.8 kV14 Mode of operation (individual / parallel)15 Frequency/Phases 50 Hz 2 +/- % No: 3 phase16 Maximum primary system short circuit current rating 31,5 kA rms17 Maximum short circuit duration18 Off Circuit Tap Changer ± 2,5 % per step N° steps: 5 Total range: ± 5 %19 On Load Tap Changer ± % per step N° steps: Total range: ± %20 Winding Connection and Vector Group Dyn 1121 Insulation class22 Oil / Winding Temperature Rise (with ambient at 47°C) Oil: 53 °C Winding: 58 °C23 Oil type24 Transformer mounting Skid Rollers Bidirectionnal roller25 Accessories26 "DGPT2" type multifunction relay Yes No27 Buchholz relay with 2 contacts (alarm / trip) Yes No28 Air breather and dryer Yes No29 Oil filler plug Yes No30 Conservator oil drain plug Yes No31 Top oil thermometer with 2 contacts (alarm / trip) Yes No32 Dial thermometer with 2 contacts (alarm / trip) Yes No33 Liquid level gauge Yes No34 Pressure relief valve with operating signal contact Yes No35 Oil level gauge with alarm contact Yes No36 Surge arrester (primary side) Yes No37 Lifting rings Yes No38 Safety valve Yes No39 Filling valve Yes No40 Tank oil drain plug Yes No41 2 filterpress connections Yes No42 Insulation for tank earth protection Yes No43 2 earthing clamps Yes No44 Lugs and hooks Yes No45 Drip pan Yes No46 TRANSFORMER SPECIFIC'S DATA (VENDOR TO COMPLY WITH)47 Transformer tag See line 1 Quantity: 148 Cooling type (ONAN, ONAF,…)49 Nominal Rating Natural Cooling (ONAN)50 Nominal Rating Forced Cooling (ONAF)51 Impedance Voltage52 Primary Connections Bus Duct Cable line 54 mm²53 Secondary Connections Bus Duct Cable line 55 mm²54 Primary
55
56 CT on secondary (number per phase / ratio / class)
57 Primary terminals Box Plug in
58 Secondary terminals Box Plug in
59 Secondary / neutral brought out Box Plug in Yes No60 Neutral connection: cable type / section HOLD mm²61 CT ring on neutral (ratio / class) NA62 Earthing resistor / resistor rating Yes No NA Ω63 Earthing resistor box / installation /protection degree Yes No
-5%
Cable Type & n° per phase3 x 95 mm² mulpipolar
4 uni 500 mm² per phase + 4 uni 150 mm² for PEN for 143-TR-36-1.
Plug in connectors (mobile and fix part) to be supplied by Vendor
Cable glands out of scope
HOLDNA
1250 kVA @ 47°C
With conservator Sealed
15 / 0,420 Refer to IEC 60076-30,4
(Yes / Yes)
2 sec According to IEC 60076-5
Class A
Mineral oil
ONAN
OIL IMMERSED HV/LV (15/0,420 kV) SEALED TRANSFORMER QUANTITY 1
Outdoor, under sun shade, in safe area
Industrial, Dusty & corrosive atmosphere (Mining), sand storm
DISTRIBUTION TRANSFORMERS
Page : 2
O S / (1 /0 420 ) S S O
DISTRIBUTION TRANSFORMERS
64 Earthing system
65 Auxiliary Connections66 Sound press. level at 1 m / Sound power level < 85 LPA (dB) LWA (dB)67 Tropicalization Yes No68 TRANSFORMER MANUFACTURER'S DATA (PART TO BE FILLED IN BY VENDOR)69 Manufacturer / Model70 Highest Voltage (rms) Primary Winding: 17.5 kV Secondary Winding: 1.1 kV71 Short Duration Power Frequency Withst. Volt. (rms) Primary Line Term.: 38 kV Second. Line Term.: 3 kV72 Lightning Impulse Withstand Voltage (peak) Primary Line Term.: 95 kV Second. Line Term.: - kV73 Short Duration Power Frequency Withst. Volt. (rms) Primary Neut. Term.: 38 kV Second. Neut. Term.: 3 kV74 Lightning Impulse Withstand Voltage (peak) Primary Neut. Term.: 95 kV Second. Neut. Term.: - kV75 No Load Losses / No Load Current (primary) 2 KW 0,8 % of full load 0,95%76 Load Losses 4/4 Load: 15 kW 3/4 Load: 8.5 kW 2/4 Load: 3.75 kW77 Full Load Voltage Drop at 0.8 Power Factor 3,92 %78 Efficiency at 0,8 Power Factor 4/4 Load: 98,26% 3/4 Load: 98,59% 2/4 Load: 98,84%79 Efficiency at 1 Power Factor 4/4 Load: 98,64% 3/4 Load: 98,89% 2/4 Load: 99,08%80 Impedance voltage (%) / with tolerance of % Ucc: 5 % Tolerance: ±10 %81 Zero- Sequence Impedance 4.5 %82 X/R 4.3583 Magnetizing / Inrush current 0.45 A 455.96 (Peak) A84 Primary Bushing Quantity / Type N°: 3 Plug-in85 Secondary Bushing Quantity / Type N°: 3 + 1 N Porcelain86 Fan Motors (Quantity / Rating / Voltage) N°: NA kW V87 Weight Iron / Copper 1050 kg 440 kg88 Oil Weight 580 kg89 Total Weight 3100 kg90 Overall Dimensions (Length/Width/Height) 1950 mm 1440 mm 2080 mm91 When applicable, dimensions between rollers 820 mm92 Painting (Mfr standard,... / color) Spec 93 Tropicalization Yes No94 Sound press. level at 1 m / Sound power level LPA (dB) LWA (dB)95 Current density Primary / Secondary A/mm² A/mm²96 Core material and grade Conventional Grain Oriented Steel (CGOS)97 Regulation at 47°C 96,08 %98 Earthing resistor rating - A99 Straight fault current limitation - A100 Straight fault short time rating - S
603,4 3,8
Schneider Electric DCU 4132
72
Prim.: IT through neutral earthing transformer (at main substation)Sec.: TNC ( neutral solidly earthed)
I
a
:1
! [
f
----b
·!!'
005
004
003
002
NO
L
TAG NO
w
0 Seider 0
Electric
I Schneider Enerji End. San. ve Tic. AS 41420 Kocaeli - Turkey ITYPE DCU 4132 IINR IIYEAR II IEC 60076 I RATED POWER 1250 kVAIIMODEL
POS.1 15750 V POS.2 15375 V
I RATED VOLTAGE POS.3 15000 V POS.4 14625 V POS.5 14250 V
RATED CURRENT 48, 11 A RATED IMPED.VOLTAGE % SHORT-CIRCUIT CURRENT kA OIL TYPE NYNAS NYTRO LYRA X WINDING TEMPERATURE RISE 58 °K OIL TEMPPERATURE RISE 53 °K
A T T E N T I O N! HERMETICALLY SEALED TRANSFORMER
LT II PHASE 311 FREQUENCY 50 Hz V AMBIENT TEMP. 47 °C V SERVICE CONTINUOUS
420 V VECTOR GROUP Dyn11 V COOLING METHOD ONAN
V TOTAL WEIGHT 3,20 t 1718,3 A OIL WEIGHT 0,66 t
VOLUME OF OIL 741 It ACTIVE PART WEIGHT 1,67 t INSULATION LEVEL LI 95 kV AC 38 kV/ LI - AC 3 kV DURATION OF SHORT-CIRCUIT 2 s
OIL DRAIN IN 20°C 0 It
z N
TRANSFORMER IS FILLED UP AS HERMETIC ;? ::, AND READY FOR OPERATING N
DO NOT OPEN IT ! .__ N-
DO NOT VENT BUSHINGS ! - N
E2834958
Empty fields shall be engraved after factory tests.
Plate D148x148 CR-NI T0947 UNIT NO
Dimensions App. Class without tolerance ace
ISO 2768 RPL
Date 06.08.2013 Department Rating plate Designer
Check
Drawing no Paae no Paaes
Scrmer 1 1 Electric Cancelled b Replaced by Rev Date Name drawing drawing
&
Code Nr.
Autocad
Pre-Owned Mining, Processing & Construction Equipment Since 1979
TRANSFORMERSS CH NE I DE R ORI GI NAL PACK I NG L I STS
APPENDIX F
+1 (530) [email protected]
Date : 30/04/2014
SCHNEIDER ELECTRIC INDUSTRIES (M) SDN BHD
PL N° 3058
Activité-Unité Code Eng N° ordre avt
IM22032 PO 9806J-0440 1641 002 2
Number of Packages
Nombre de colis
.........…4…………….
Package N° Quantity
Colis N° Net Gross N° Quantités
Net Brut Code de Stockage
1/4 SEI 4C 3200 3720 222 172 266 10.157 143-TR-36-1 1 1250 KVA TRANSFORMER BF : 223283 01 xxxx
2/4 SEI 4C 1740 2120 197 136 204 5.466 14-TR-35-1 1 630 KVA TRANSFORMER FB : 223284 01 xxxx
3/4 SEI 4C 915 1265 174.5 142 192.1 4.760 143-TR-66-1 1 100 KVA TRANSFORMER FB : 480668 01 xxxx
4/4 SEI 4C 2030 2635 225 238 224.1 12.001 14-TR-56-1 1 400 KVA TRANSFORMER FB : 480669 01 xxxx
7 885 9 740 32.384 Country of origin/Pays d'origine : TURKEY Page N° 1/1….
PL 001 REV : 1 - F/ANG
Volume
unitaire en
M3
Unit weight in Kg
Poids unitaire en Kg Length x Width x Height
Nature du
colis
Type of
Package
Dimensions ( en centimeters )
Longueur x Largeur x Hauteur
Description of goods
Poids Net Total Poids Brut Total Volume Total
.………32,384………… M3
Unit volume
in M3
PACKING LIST
Liste de colisage
N° P0 Chrono
....7885... KGS ..9740...... KGS.
Total Net Weight Total Gross Weight
Unit TB-18-2, Level 18, Tower B, Plaza 33, No 1, Jalan
Kemajuan, Seksyen 13, 46200 Petaling Jaya, Selangor,
Malaysia
TOTAL
Désignation des marchandises
Total Volume
Measurement ( in centimeters)
ITEM / TAG
Date : 12/06/2015
SCHNEIDER ELECTRIC INDUSTRIES (M) SDN BHD
PL 3077Activité-Unité Code Eng N° ordre avt
IM22032 PO 9806J-0440 1641 002 2
Number of PackagesNombre de colis
.........…1…………….
Package N° Quantity
Colis N° Net Gross N° Quantités
Net Brut Code de Stockage
1/1 2800 3270 223 x 172 x 222 8,515 140-TR-35-1 1 1000 KVA TRANSFORMER BF : 224401 01
2 800 3 270 8,515 Country of origin/Pays d'origine : TURKEY Page N° 1/1….
PL 001 REV : 1 - F/ANG
xxxx
TOTAL
Désignation des marchandises
Total Volume
Measurement ( in centimeters)
PACKING LIST Liste de colisage
N° P0 Chrono
....2800... KGS ..3270...... KGS.
Total Net Weight Total Gross Weight
Unit TB-18-2, Level 18, Tower B, Plaza 33, No 1, Jalan Kemajuan, Seksyen 13, 46200 Petaling Jaya, Selangor, Malaysia
Poids Net Total Poids Brut Total Volume Total
.………8,515………… M3
Unit volume in M3Volume
unitaire en M3
ITEM / TAG
Description of goodsUnit weight in KgPoids unitaire en Kg Length x Width x Height
Nature du colis
Type of Package
Dimensions ( en centimeters )
Longueur x Largeur x Hauteur