Protection of Transformer• A: Electrical Protection:
Differential Protection HT & LT Over Current Protection Restricted Earth Fault Protection Standby Earth Fault Protection
• B: Mechanical Protection: Buchholz Protection Pressure Relief Device Explosion Vent Oil Surge Relay
• C: Thermal Protection: OT/WT Protection Overload Trimming Protection
• D: Lightning Protection: Lightning Arrestors Spark gaps
![Page 2: Transformer Protection](https://reader036.vdocuments.site/reader036/viewer/2022081820/546052c5b1af9f6b5c8b4d66/html5/thumbnails/2.jpg)
Transformer Differential Protection Merz-Prize 95% Differential
Protection HT/LT CTs connected
differentially CTs on Star side connected in delta
and vice-versa CT mismatch compensated by
slope setting In-rush currents taken care by
Harmonic Restraint Unit Stable for through faults High set unit takes care heavy un-
cleared through faults High Speed, reliable, dedicated but
expensive protection Not very sensitive for earth faults
closer to neutral end
![Page 3: Transformer Protection](https://reader036.vdocuments.site/reader036/viewer/2022081820/546052c5b1af9f6b5c8b4d66/html5/thumbnails/3.jpg)
Transformer Over Current Protection Simple Over Current Relays on
HT & LT. HT Over current isolates
transformer. LT Over current relives load
and the transformer remains energized from HT
Can mal-operate during in-rush and for through faults if not set properly.
Unstable for through faults. Backup protection for un-
cleared feeder faults. Moderate Speed, dependable
inexpensive protection
![Page 4: Transformer Protection](https://reader036.vdocuments.site/reader036/viewer/2022081820/546052c5b1af9f6b5c8b4d66/html5/thumbnails/4.jpg)
Transformer-Restricted & Standby Earth Fault Protection
• Restricted Earth fault Protection: Over Current relay connected
across the summation of 3 and Neutral CT
Very sensitive, dedicated, reliable, expensive protection for Star windings.
• Stand by Earth Fault Protection: Over Current relay connected on
the neutral CT Back up for un-cleared feeder
earth faults– In-expensive and simple protection
![Page 5: Transformer Protection](https://reader036.vdocuments.site/reader036/viewer/2022081820/546052c5b1af9f6b5c8b4d66/html5/thumbnails/5.jpg)
Transformer-Mechanical Protection• 1. Buchholz Protection:
Located on the oil pipe connecting the main tank with conservator above the tank
Gas evolution principle Alarm and trip at different levels
of gas evolution Very sensitive, inexpensive,
reliable for incipient evolving faults
• 2. Pressure Relief Device: Relives the hydraulic pressure
developed inside due to faults Slow protection
• 3. Oil Surge Relay: Operates due to Oil surges caused
by internal faults
![Page 6: Transformer Protection](https://reader036.vdocuments.site/reader036/viewer/2022081820/546052c5b1af9f6b5c8b4d66/html5/thumbnails/6.jpg)
Transformer- Thermal Protection- Operates due to thermal stresses
developed due to overload.- Can detect inadequate cooling.- The temperatures of the Oil
/winding simulated through image coil Can detect inadequate cooling.
- Protects the transformer from thermal overloads
- Relieves the load fully or partially
- Starts/stops the oil pumps and fans
![Page 7: Transformer Protection](https://reader036.vdocuments.site/reader036/viewer/2022081820/546052c5b1af9f6b5c8b4d66/html5/thumbnails/7.jpg)
Transformer -Lightning Protection• Lightning Arrestors &
Spark Gaps: Protects from lightning
and switching over voltages
Spark gaps for small and non-vital transformers
Lightning arrestors for large and vital transformers