transformer explosion prevention tp successful activation · 2019-09-02 · tp performance analysis...
TRANSCRIPT
TRANSFORMER EXPLOSION PREVENTION
TP Successful Activation
1
• INTRODUCTION
• TP PERFORMANCE ANALYSIS
• SCADA Recording During the Short Circuit
• Signals Recorded on the TP Control Box After the Fault
• Rupture Disk Activation
• Rupture Disk Opening Section Comparison with TP Live Test No. 25
• Comparison of Activation Parameter with TP Live Test No. 25
• Pressure Relief Valve Behavior During Short Circuit
• BPC INVESTIGATIONS
• Transformer Oil Analysis After the Electrical Fault
• Electrical Arcing in Transformer Tank
• CONCLUSION
• BPC CERTIFICATE OF TP SUCCESSFUL ACTIVATION
• BIBLIOGRAPHY
OUTLINE
2
The TRANSFORMER PROTECTOR (TP) installed at Thamaga SS on
a 125 MVA transformer was activated by an internal fault on January 9, 2006.
The Site Engineers report to SERGI that during the short circuit a big explosion
sound was heard in a 3km radius.
It was mentioned that one surge insulator exploded and shorted to the ground.
As a result, a 4.8 KA current fault was generated.
The TP was activated within milliseconds by the first dynamic pressure peak,
before static pressure increased, avoiding transformer tank explosion.
INTRODUCTION
3
INTRODUCTION
TPC scientific articles ref. 2, 3, 4 should be read to understand the TP behavior during
the incident:
• The maximum of gas is produced at the exact time of the creation of the electrical arc.
During the first milliseconds, 80 ft³ [2.3 m³]of explosive gas are produced by the first Mega
Joule.
• The gas generated during the first milliseconds creates one dynamic pressure peak,
amplitude from115 to 200 psi [8 to 14 bar].
• As soon as appearing, the dynamic pressure peak travels at the speed of sound inside the
oil, 4,000 feet per second [1,200 meter per second].
• Then, the dynamic pressure peak generates secondary peaks when travelling inside the
tank.
• The integration of the dynamic pressure peak and its secondary peaks are building up
static pressure inside the tank, within 20 to 100 milliseconds depending on tank size.
4
TP PERFORMANCE ANALYSISSCADA RECORDING DURING THE SHORT CIRCUIT
5
TP PERFORMANCE ANALYSISSCADA RECORDING DURING THE SHORT CIRCUIT
SEQUENCE OF EVENTS
t = 0 ms, Low Impedance Fault is detected by the Reactor Relay Oscillograph.
t = 4 ms, Reactor Relay actuates and sends the signal to trip the Circuit Breaker.
t = 5 ms, TP Rupture Risk opens before the static pressure increases.
t = 14 ms, Electrical Protection signal is received by the TP Control Box.
t = 28 ms, Automatic Nitrogen Injection is initiated by the two signals coming from the Electrical
Protection and the Rupture Disk Burst Indicator.
t = 56 ms, Breaker opens after receiving Reactor Relay signal sent at t = 4 ms.
t = 322 ms, Conservator Shutter closes to avoid draining the Oil Conservator Tank.
6
TP PERFORMANCE ANALYSISSIGNALS RECORDED ON THE TP CONTROL BOX AFTER THE
FAULT• TP Control Box
Electrical Protections LED On
• TP Rupture Disk LED On
Indication that the TP Rupture Disk is opened.
• Nitrogen Low Level LED On
Meaning that the TP Nitrogen injection was
performed to evacuate all explosive gases from
tank to render the evacuation safe.
• Oil Filtration Electro-Valve Not Ready LED On
The OLTC oil filtration unit was isolated before
Nitrogen injection.
7
TP PERFORMANCE ANALYSIS
TP RUPTURE DISK ACTIVATION
• The Rupture Disk Petals have been
opened.
• The Burst Indicator wire has been cut,
therefore the RD opening signal was
sent to the TP Control Box.
• The RD opening section seems small
because the RD diameter is sized for
the strongest short circuits.
To estimate short circuit energy, the RD opening section is compared with the opening
sections versus energy obtained during the TP Live Tests
8
TP PERFORMANCE ANALYSISRUPTURE DISK OPENING SECTION COMPARISON WITH TP LIVE
TEST No. 25
For the same Rupture Disk opening section during the TP Live tests, the characteristics of
the electrical fault and the consequences on the tank pressure are listed on the table
below.
9
TP PERFORMANCE ANALYSISCOMPARISON OF ACTIVATION PARAMETERS WITH TP LIVE
TEST No. 25
• The comparison of the RD opening section obtained during the TP live tests have shown
the RD opening section was corresponding to an electrical arc energy of 0.25 MJ, ref. 2
and 4.
• During the TP live tests it was measured that an electrical arc of 0.25 MJ generates 80
ft³ [0.5m³] of explosive gas, ref. 2 and 4.
• Calculations have also demonstrated that 80 ft³ [0.5m³] of explosive gas generated
inside transformer tank resulted to an internal pressure of 44 psi [3 bar] atmospheric
for tank not equipped with TP, ref. 2 and 4.
• Transformer tanks are exploding at 15 psi [1 bar] above atmospheric pressure.
Consequently, if not protected by the TP the transformer tank would have exploded
during this incident. A fire could have occurred, destroying the transformer and all
surrounding equipments.
10
TP PERFORMANCE ANALYSISCOMPARISON OF ACTIVATION PARAMETERS WITH TP LIVE
TEST No. 25
• For an energy of 0.25 MJ, the Dynamic Pressure Peak had an amplitude of 75 psi [5
bar], as shown in the graph below, ref. 2 and 4.
• During the fault, the current peak was 4.8kA, closed to the current peak created for the
test No. 25, 7.3kA.
11
TP PERFORMANCE ANALYSISPRESSURE RELIEF VALVE (PRV) BEHAVIOR DURING SHORT CIRCUIT
The Pressure Relief Valve yellow pin at the
top center was found in its original position,
showing the PRV was not activated during
the short circuit.
For TPC scientific article ref. 1 should be
read
to understand the PRV behavior during
short
circuit
12
TP PERFORMANCE ANALYSISPRESSURE RELIEF VALVE (PRV) BEHAVIOR DURING SHORT CIRCUIT
• During the incident, the PRV was not activated because:
• The dynamic pressure peak of 75 psi [5 bar] amplitude has travelled inside the tank at
the speed of the sound inside oil, which is 4,000 feet per second [1,200 meter per
second], ref. 2 and 4.
• The PRV section is 6 inch, 150 mm, consequently the PRV has seen the dynamic
pressure peak only during 0.1millisecond, ref. 1.
• The PRV springs have an opening inertia of approximately 5 millisecond; therefore, the
PRV had no time to activate because of the dynamic pressure peak speed, ref.1.
Because the PRV had no time to open, the TP has therefore depressurized the
transformer
tank before the static pressure increased.
13
BPC INVESTIGATIONSTRANSFORMER OIL ANALYSIS AFTER THE ELECTRICAL FAULT
The results of the transformer oil analysis show that the following gases were present:
• Hydrogen, Oxygen, Nitrogen, Methane, Carbon Monoxide and Carbon Dioxide and
Acetylene.
According to the chemical component present in this sample, the Dissolved Gas Analysis
(DGA) and DUVAL Triangle were used to determine which kind of fault had occurred inside
the tank.
14
BPC INVESTIGATIONSTRANSFORMER OIL ANALYSIS AFTER THE ELECTRICAL FAULT
• First the concentration of the three gases in PPM: S = A + B + C
• Second, the calculation of the relative proportions of these three gases:
X = % CH4 = 100(A/S)
Y = % C2H4 = 100(B/S)
Z = % C2H2 = 100(C/S)
• Third, place the coordinates X, Y, Z on the triangle to find the type of fault.
15
BPC INVESTIGATIONSTRANSFORMER OIL ANALYSIS AFTER THE ELECTRICAL FAULT
The Yellow Phase Transformer Analysis gives:
• A = 10.41 PPM ; X = CH4 76.65%
• B = 0.72 PPM ; Y = C2H4 5.30%
• C = 2.45 PPM ; Z = C2H2 18.04%
With these percentages, the Duval Triangle
Method shows:
The fault is a D1 Type, “Arc Discharges”.
16
BPC INVESTIGATIONSELECTRICAL ARCING IN TRANSFORMER TANK
During the transformer internal inspection, the electrical partial discharges proven by the
oil
chemical analysis has been confirmed.
The 2 pictures below show the arcing points.
17
CONCLUSION
The TP has been activated 5 millisecond after the origin of the fault.
The transformer Pressure Relief Valve had no time to open, which demonstrates that the
TP
has been activated by the first dynamic pressure peak of the shockwave before the static
pressure increased.
The activation of the TP has therefore saved the transformer tank from explosion.
The transformer could be repaired on site and was back to service one week after the
incident, thanks to the TRANSFORMER PROTECTOR.
Without the TP, the transformer would have exploded and a fire would have spread to the
all surrounding equipments. According to BPC the total cost of the damages this incident
would have reached USD 120 Millions, ref. 5.
18
����
����
����
����
����
BPC CERTIFICATION OF TP SUCCESSFUL ACTIVATION
“ On 01.09.2006 an autotransformer of 125 MVA,
located at our Thamaga Substation
developed troubles. A serious internal failure
occurred and the SERGI system activated. The
SERGI system therefore correctly operated and
released the pressure developed internally.
Furthermore and according to transformer
manufacturer investigation, it was reported
that thanks to the Transformer Protector, the
transformer tank was not deformed and
secondary damages were limited. An isolating
Bakelite plate replaced and new tests
performed before the transformer was put
back to service.”
19
BIBLIOGRAPHY
1. Pressure Relief Valve efficiency calculations by comparison to the TRANSFORMER PROTECTOR
during transformer short-circuit, ref. AtTPradb01e.
2. Prevention of Transformer Tank Explosion, Part 1: Experimental Tests on Large Transformers,
ref.Arpibp01a.
3. Prevention of Transformer Tank Explosion, Part 2: Development and Application of a Numerical
Simulation Tool, ref.Arpibp02a.
4. An Answer to Prevent Transformer Explosion and Fire: Live Test and Simulations on Large
Transformers, ref. AtTPrajo1e Power-Gen Europe Best Paper Award 2008, Track 5, Electrical and
Information & Control Systems.
5. Transformer Explosion and Fire Incidents, Guideline for Damage Cost Evaluation, Transformer
Protector Financial Benefit, ref. AtTPraeb03e.
20
21
22
SERGI FRANCE
186, avenue du General de Gaulle
78 260, Achères
FRANCE
Phone (0033) 1.39.22.48.40
Fax (0033) 1.39.22.11.11
www.sergi-france.com