trane communications interface ( comm3 / comm4 )

12
Installers Guide Trane Communications Interface ( Comm3 / Comm4 ) December 2005 ACC-SVN18C-EN Models: Used With: BAYICSI003A 3 - 10 Ton Packaged Rooftop units with Reliatel Communications Module, 7½ - 20 Ton Split System units with Reliatel Communications Module BAYICSI004B 12 1/2 - 25 Ton Packaged Rooftop units with Reliatel Communications Module, 27 1/2 - 50 Ton Packaged Rooftop units with Reliatel Communications Module

Upload: others

Post on 22-Oct-2021

10 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Trane Communications Interface ( Comm3 / Comm4 )

Installers Guide

Trane Communications Interface( Comm3 / Comm4 )

December 2005

ACC-SVN18C-EN

Models: Used With:BAYICSI003A 3 - 10 Ton Packaged Rooftop units with

Reliatel™ Communications Module,7½ - 20 Ton Split System units withReliatel™ Communications Module

BAYICSI004B 12 1/2 - 25 Ton Packaged Rooftop unitswith Reliatel™ Communications Module,27 1/2 - 50 Ton Packaged Rooftop unitswith Reliatel™ Communications Module

Page 2: Trane Communications Interface ( Comm3 / Comm4 )

2 ACC-SVN18C-EN

Table of Contents

General Information .............................................................................................. 3Inspection ............................................................................................................... 3Parts List ................................................................................................................ 3Typical Reliatel Communications Applications ................................................ 4Mounting and Wiring ............................................................................................. 5ICS Communication Link Wiring Requirements ................................................ 6DIP Switch Address Settings ............................................................................... 6

TCI Board Mounting and Wiring

3 - 5 Ton Packaged Rooftop units (except WSC060E) ....................................... 87 ½ - 10 Ton Split System units ............................................................................ 815 - 20 Ton Split System units .............................................................................. 86 - 10 Ton Packaged Rooftop units (and WSC060E) .......................................... 912 1/2 - 25 Ton Packaged Rooftop units ............................................................. 927 1/2 - 50 Ton Packaged Rooftop units ........................................................... 10

Page 3: Trane Communications Interface ( Comm3 / Comm4 )

3ACC-SVN18C-EN

Installation

NOTICE:Warnings and Cautions appear atappropriate sections throughout thismanual. Read these carefully.

WARNING– Indicates apotentially hazardous situationwhich, if not avoided, could result indeath or serious injury.

CAUTION – Indicates apotentially hazardous situationwhich, if not avoided, may result inminor or moderate injury. It may alsobe used to alert against unsafepractices.

CAUTION – Indicates a situationthat may result in equipment orproperty-damage-only accidents.

General Information

The first generation of Reliatel™ Com-munications Module incorporates com-munications capabilities of the TCI-1(Isolated Comm 3), TCI-2 (Non-IsolatedComm 3 or Comm 4 or Isolated Comm3) board and TCI-3 (Non-IsolatedComm 3 or Comm 4).

The TCI Module allows digital commu-nication between Reliatel™ controlsand Trane ICS systems which includeTracer Summit®, Tracker Stat 4, TrackerStat 7, Tracker Stat 16, and theVariTrac® zoning system.

Note: The TCI Module in this kitis shipped in the comm 4position.

The TCI Module in the non-insulatedComm 3 / Comm 4 position allowscommunication between a Reliatel™controlled unit and a Tracer Summit®or VariTrac® zoning system.

By turning the Comm Link Board 90°,the Comm 3/4 Communications Modulenow becomes Isolated Comm 3 andcan be used to communicate withTracker® or Tracer™ 100 systems.

Inspection

1. Unpack all components of the kit.

2. Check carefully for any shippingdamage. If any damage is found itmust be reported immediately and aclaim made against the transporta-tion company.

3. The kit must be stored in an ambientbetween -40F(-40C) and 150F(65.6C), 10% - 90% non-condens-ing.

Parts List1 - TCI Module Board1 - Wiring Harness2 - Screws1 - Wire Tie

Page 4: Trane Communications Interface ( Comm3 / Comm4 )

4 ACC-SVN18C-EN

InstallationFigure 1Typical Reliatel Communications Applications

Figure 2 Figure 3

Trane Building Trane Building

Management SystemManagement System

VariTrac CCPVariTrac CCP

VariTrac VariTrac

Zone DampersZone Dampers

(Optional)(Optional)

Isolated Com 3Isolated Com 3

Communication OptionCommunication Option

Non - Isolated Non - Isolated

Com 3 or Com 4Com 3 or Com 4

Communication OptionCommunication Option

TRACKER, TRACER 100TRACKER, TRACER 100 VARITRACVARITRAC

Non - Isolated Non - Isolated

Com 3, Com 4 or Isolated Com 3 Com 3, Com 4 or Isolated Com 3

Communication OptionCommunication Option

Trane Building Trane Building

Management SystemManagement System

TRACER SUMMIT

Non - Isolated Non - Isolated

Com 3, Com 4 or Isolated Com 3 Com 3, Com 4 or Isolated Com 3

Communication OptionCommunication Option

Isolated Com 3Isolated Com 3

Communication OptionCommunication Option

Non - Isolated Non - Isolated

Com 3 or Com 4Com 3 or Com 4

Communication OptionCommunication Option

TRACER SUMMITTRACER SUMMIT

Trane Building Trane Building

Management SystemManagement System

Trane Building Trane Building

Management SystemManagement System

TRACKER, TRACER 100TRACKER, TRACER 100VariTrac VariTrac

Zone DampersZone Dampers

VariTrac CCPVariTrac CCP

(Optional)(Optional)

VARITRACVARITRAC

Packaged Units

Split System UnitsSplit System Units

Page 5: Trane Communications Interface ( Comm3 / Comm4 )

5ACC-SVN18C-EN

WARNINGHazardous Voltage w/Capacitors!Disconnect all electric power, including remote discon-nects and discharge all motor start/run capacitors beforeservicing. Follow proper lockout/tagout procedures to en-sure the power cannot be inadvertently energized. Verifywith an appropriate voltmeter that all capacitors have dis-charged. Failure to disconnect power and discharge ca-pacitors before servicing could result in death or seriousinjury.

To change the configuration of the Comm 3/4 Communica-tions Module :

1. Remove the four screws that attach the Comm Link Boardto the TCI Module base board.

2. Gently lift the Comm Link Board off the TCI Module baseboard and away from the pin set located above TB1.

3. Rotate the Comm Link Board 90° so that the Non-IsolatedComm 3 or Comm 4 connector is above the pin set.

4. Gently lower the Comm Link Board onto the TCI Modulebase board.

5. Screw the Comm Link Board to the TCI Module baseboard with the four screws that were removed in stepnumber 1.

Mounting and Wiring

The TCI board mounts directly to the Unit Control Box. Thefollowing procedure explains how to mount and wire the TCIboard. See Figure 4,5,6,7 or Figure 8 for Comm 3/4 boardmounting location and wire bundle placement.

Note: Skip steps 1 – 9 of the Reliatel™™™™™Communications Interface is already factory installed.

1. Disconnect the power source to the unit and remove theAccess Panel to gain access to the electronic controls.

2. Installation of TCI board:3 - 5 ton Packaged Rooftop (except WSC060E) and 7½- 10 ton Split System units mount the TCI board to therear side of the Reliatel™ Refrigeration Module mountingpanel by sliding the TCI board mounting feet into themounting extrusions on the Reliatel™ Refrigeration Mod-ule mounting panel. Secure with 1 screw. See Figure 4.

15 - 20 ton Split System units mount the TCI boardabove the Reliatel™ Refrigeration Module on the controlbox mounting panel. Secure with 2 screws. See Figure 5.

Installation

6 - 10 ton Packaged Rooftop units (and WSC060E)mount the TCI board to the right side of the Reliatel™ Re-frigeration Module by sliding the TCI board mounting feetinto the mounting extrusions on the control box mountingpanel. Secure with 1 screw. See Figure 6.

12 1/2 - 25 ton Packaged Rooftopunits mount the TCIboard to the right side of the Reliatel™ RefrigerationModule by sliding the TCI board mounting feet into themounting extrusions on the control box bottom panel. Se-cure with 2 screws. See Figure 7.

27 1/2 through 50 Ton Packaged Rooftop Units:Mount the TCI board to the right side of the ReliaTel™Refrigeration Module on the control box back panel. Se-cure with 2 screws. See Figure 8.

3. Remove the five pin (four wire) connector from J4 on theRTRM and connect to J2 on the TCI board.

4. Connect the four pin (four wire) end of the TCI board wireharness to J1 on the TCI board.

5. Connect the five pin (four wire) end of the TCI board wireharness to J4 on the Reliatel™ Refrigeration Module.

6. Route the TCI board wire harness and secure with onewire tie.

7. Route the twisted pair communications wire from the BMSor CCP, through the hole located below TB1 on the TCIboard and connect these wires to TB1. Refer to the ICSCommunications Link Wiring Requirements section forwire information.

8. Secure the wires connected to TB1 using the pop-in wiretie under the control box.

9. Set the DIP switch (SW1) on the TCI board to the desiredunit address setting. (See DIP switch settings section)

Page 6: Trane Communications Interface ( Comm3 / Comm4 )

6 ACC-SVN18C-EN

Installation

ICS Communication Link Wiring Requirements

The ICS communications link is for communication betweenTrane Building Management Systems and various TraneICS equipment controllers.

Note: Observe polarity when wiring all devices on thecommunications link to aid troubleshootingcommunication wiring problems.

At the ICS equipment, or VAV-UCMs and Reliatel™ Commu-nications Interface, the shield must be spliced with the shieldfrom the next section of communication link wiring and tapedto prevent any connection between the shield and ground.The shield at the last ICS device must be cut and tapedback.

See equipment installation literature for correct wire type, re-sistors, and maximum length.

DIP Switch Address Settings

The DIP switch (SW1) is located on the left corner of theComm 3/4 board. DIP switches SW1-1 through SW1-5 areused to set the Comm 3/4 board addresses.

Setting for Tracker/ComforTrac (Pre Version 10 Trackers)The Comm 3/4 board is supported by Tracker/ComforTracBuilding Management Systems. The Comm Link Board mustbe positioned for Isolated Comm 3 communications. A maxi-mum of 12 Interfaces can be defined for each Tracker/ComforTrac system.

Table 1TCI Communications Module Address Setting forTracker/ComforTrac

AddressNumbers SW1-1 SW1-2 SW1-3 SW1-4 SW1-5

1 OFF OFF OFF OFF OFF2 OFF OFF OFF OFF ON3 OFF OFF OFF ON OFF4 OFF OFF OFF ON ON5 OFF OFF ON OFF OFF6 OFF OFF ON OFF ON7 OFF OFF ON ON OFF8 OFF OFF ON ON ON9 OFF ON OFF OFF OFF10 OFF ON OFF OFF ON11 OFF ON OFF ON OFF12 OFF ON OFF ON ON

The Reliatel Communications Interface boardDIP Switch Settings

Table 2Comm 3/4 Communications ModuleAddress Setting for VariTrac I Comfort Manager andVariTrac II Central Control Panel

AddressNumbers SW1-1 SW1-2 SW1-3 SW1-4 SW1-5

ALL ON ON ON ON ON

The Reliatel Communications Interface boardDIP Switch Settings

Table 3TCI Communications ModuleAddress Setting for VariTrac III Central Control Panel

AddressNumbers SW1-1 SW1-2 SW1-3 SW1-4 SW1-5

ALL OFF OFF OFF OFF OFF

The Reliatel Communications Interface boardDIP Switch Settings

VeriTrac I Comfort Manager and VariTrac II Central ControlPanel are vertically mounted with an access door. VariTrac IIICentral Control Panel is horizontally mounted with no accessdoor.

Page 7: Trane Communications Interface ( Comm3 / Comm4 )

7ACC-SVN18C-EN

Installation

Settings for Tracer 100 Series Panels andTracer Summit Systems

Tracer 100 has a maximum of 32 Comm 3/4 CommunicationsModules that can be defined for each Tracer 100 and Tracer100i. A maximum of 20 Comm 3/4 Communications Modulescan be defined for each Tracer L and Tracer Monitor.

Note: The number of ReliaTel CommunicationsInterfaces supported by Tracers is dependent on thesoftware version being used. Refer to Tracer 100Series literature for specific quantities.

Tracer Summit allows a maximum of 32 Tracer addresses perlink for high capacity or 16 addresses for standard capacity.

The range of Tracer address numbers that may be defined forComm 3/4 Communications Modules is 50 through 81. Toconfigure an address for a unit, assign its point number (i.e.30-01, 30-02, 30-03, etc.) to a Tracer address within the ac-ceptable range (50-81) as shown in Table 4. Set the Comm 3/4 Communications Module DIP switches for this address.

Table 4TCI Communications Module Address Setting for Tracer100 Series Panels and Tracer Summit

AddressNumbers SW1-1 SW1-2 SW1-3 SW1-4 SW1-5

50 OFF OFF OFF OFF OFF51 OFF OFF OFF OFF ON52 OFF OFF OFF ON OFF53 OFF OFF OFF ON ON54 OFF OFF ON OFF OFF55 OFF OFF ON OFF ON56 OFF OFF ON ON OFF57 OFF OFF ON ON ON58 OFF ON OFF OFF OFF59 OFF ON OFF OFF ON60 OFF ON OFF ON OFF61 OFF ON OFF ON ON62 OFF ON ON OFF OFF63 OFF ON ON OFF ON64 OFF ON ON ON OFF65 OFF ON ON ON ON66 ON OFF OFF OFF OFF67 ON OFF OFF OFF ON68 ON OFF OFF ON OFF69 ON OFF OFF ON ON70 ON OFF ON OFF OFF71 ON OFF ON OFF ON72 ON OFF ON ON OFF73 ON OFF ON ON ON74 ON ON OFF OFF OFF75 ON ON OFF OFF ON76 ON ON OFF ON OFF77 ON ON OFF ON ON78 ON ON ON OFF OFF79 ON ON ON OFF ON80 ON ON ON ON OFF81 ON ON ON ON ON

The Reliatel Communications Interface boardDIP Switch Settings

Page 8: Trane Communications Interface ( Comm3 / Comm4 )

8 ACC-SVN18C-EN

Installation

Figure 4TCI Board Mounting and Wiring3 - 5 Ton Packaged Rooftop units (except WSC060E)7 ½ - 10 Ton Split System units

Figure 5TCI Board Mounting and Wiring15 - 20 Ton Split System units

Page 9: Trane Communications Interface ( Comm3 / Comm4 )

9ACC-SVN18C-EN

Installation

Figure 6TCI Board Mounting and Wiring6 - 10 Ton Packaged Rooftop units (and WSC060E)

Figure 7TCI Board Mounting and Wiring12 1/2 - 25 Ton Packaged Rooftop units

Page 10: Trane Communications Interface ( Comm3 / Comm4 )

10 ACC-SVN18C-EN

Figure 8TCI Board Mounting and Wiring27 1/2 - 50 Ton Packaged Rooftop units

Installation

Page 11: Trane Communications Interface ( Comm3 / Comm4 )

11ACC-SVN18C-EN

Page 12: Trane Communications Interface ( Comm3 / Comm4 )

12 ACC-SVN18C-EN