touch and step potential testing - aemc · touch and step potential testing ... determine the...

8
Touch and Step Potential Testing Why Ground faults could reasonably be expected to occur near the ground to be tested or near equipment grounded by the ground to be tested When It is physically impossible to disconnect the subject ground from service The footprint of the grounded equipment is comparable to the size of the ground to be tested

Upload: others

Post on 18-Mar-2020

4 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Touch and Step Potential Testing - AEMC · Touch and Step Potential Testing ... Determine the expected fault current and multiply it by the resistance reading to get the step potential

Touch and Step Potential Testing

Why

Ground faults could reasonably be expected to occurnear the ground to be tested or near equipment grounded by the ground to be tested

When

It is physically impossible to disconnect the subjectground from service

The footprint of the grounded equipment is comparable tothe size of the ground to be tested

Page 2: Touch and Step Potential Testing - AEMC · Touch and Step Potential Testing ... Determine the expected fault current and multiply it by the resistance reading to get the step potential

Touch and Step Potential Testing

Touch Potential

Step Potential

Page 3: Touch and Step Potential Testing - AEMC · Touch and Step Potential Testing ... Determine the expected fault current and multiply it by the resistance reading to get the step potential

The importance of testing and designing a low resistance grounding system

Touch and Step Potential

Page 4: Touch and Step Potential Testing - AEMC · Touch and Step Potential Testing ... Determine the expected fault current and multiply it by the resistance reading to get the step potential

The importance of testing and designing a low resistance grounding system

Touch and Step Potential

Page 5: Touch and Step Potential Testing - AEMC · Touch and Step Potential Testing ... Determine the expected fault current and multiply it by the resistance reading to get the step potential

The importance of testing and designing a low resistance grounding system

Step Potential: Difference in surface potential experienced by a person’s feet bridging a distance of 1 meter (3 feet) without contacting any other grounded surface.

Page 6: Touch and Step Potential Testing - AEMC · Touch and Step Potential Testing ... Determine the expected fault current and multiply it by the resistance reading to get the step potential

Step Potential Test 1. Connect the X lead to the grounding system

2. Insert the injector electrode at the approximate distance of the projected fault away from the grounding system and connect the Z lead to it

3. Insert two electrodes 3 feet apart (the distance of a human step) at the approximate location of the expected position of the person. All electrodes should be in a straight line.

4. Attach the Xv lead to the electrode closest to Z and the Y lead to the other electrode

5. Start the test and record the resistance reading

6. Determine the expected fault current and multiply it by the resistance reading to get the step potential voltage

Example: Resistance reading (R) = 0.5 ohms

Fault current (I) = 4000 Amps

Step potential (E) = R*I = 0.5*4000= 2,000 Volts

1 Meter (3 Ft)

Page 7: Touch and Step Potential Testing - AEMC · Touch and Step Potential Testing ... Determine the expected fault current and multiply it by the resistance reading to get the step potential

The importance of testing and designing a low resistance grounding system

Touch Potential: Potential difference between grounded metallic structure and the surface potential at the point where a person is standing, while at the same time having hands in contact with a grounded structure

Page 8: Touch and Step Potential Testing - AEMC · Touch and Step Potential Testing ... Determine the expected fault current and multiply it by the resistance reading to get the step potential

Touch Potential Test 1. Connect the X and Xv leads to the metal object that would be touched 2. Insert an electrode approximately 1 meter (3 ft) from the object and connect the Y lead to it 3. Insert an electrode at the approximate location of the expected fault and connect the Z lead to it 4. Start the test and record the resistance reading 5. Determine the expected fault current and multiply it by the resistance reading to get the touch

potential voltage Example: Resistance reading (R) = 0.5 ohms

Fault current (I) = 5000 Amps

Touch potential (E) = R*I = 0.5*5000= 2,500 Volts

1 Meter (3 Ft)

© Copyright 2016 Chauvin Arnoux ®, Inc. d.b.a. AEMC® Instruments