9/18/2013 Copyright © 2013 Honeywell International Inc. 1 HPS Automation College written permission required to distribute Honeywell Confidential and Proprietary Topic: Productivity Tools in Control Builder Contents Instructions for Productivity Tools in Control Builder .............................................................................3 Export/Import a Control Module.............................................................................................................5

Upload: others

Post on 30-May-2020

12 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Topic: Productivity Tools in Control Builderhw.server.tracorp.com/.../14613LabProductivityToolsinControlBuilder.pdf · Instructions for Productivity Tools in Control Builder Introduction

9/18/2013 Copyright © 2013 Honeywell International Inc. 1

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Topic: Productivity Tools in Control Builder

Contents

Instructions for Productivity Tools in Control Builder.............................................................................3

Export/Import a Control Module.............................................................................................................5

Page 2: Topic: Productivity Tools in Control Builderhw.server.tracorp.com/.../14613LabProductivityToolsinControlBuilder.pdf · Instructions for Productivity Tools in Control Builder Introduction

2 Copyright © 2013 Honeywell International Inc. 9/18/2013

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

This page was intentionally left blank.

Page 3: Topic: Productivity Tools in Control Builderhw.server.tracorp.com/.../14613LabProductivityToolsinControlBuilder.pdf · Instructions for Productivity Tools in Control Builder Introduction

Productivity Tools in Control Builder

Instructions for Productivity Tools in Control Builder

9/18/2013 Copyright © 2013 Honeywell International Inc. 3

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Instructions for Productivity Tools in Control Builder

Introduction

This portion of the document contains important information required to perform to ‘Export-Import Control module’ lab.

Procedure

Step Action

1

Read the following IMPORTANT information carefully.

Decide if you will be performing labs for C200E (and Series A I/O modules) OR C300 (and Series C I/O Modules). You can opt for either one but not both.

_______ C200E (and Series A I/O modules)

_______ C300 (and Series C I/O Modules)

2

ATTENTION

You must perform the remaining steps of this lab if you skipped any of the prior lessons of this course, else skip the remaining instructions and proceed to the next lab.

Locate the “GUI_DB_Load” Shortcut on desktop.

1. Double click “GUI_DB_Load” Shortcut to launch the import utility.

2. In Controller drop down select either C200 or C300 Controller (as per the option selected in step#1).

3. In Lesson number drop down select Lesson11.

4. Click the LOAD button.

Page 4: Topic: Productivity Tools in Control Builderhw.server.tracorp.com/.../14613LabProductivityToolsinControlBuilder.pdf · Instructions for Productivity Tools in Control Builder Introduction

Productivity Tools in Control Builder

Instructions for Productivity Tools in Control Builder

4 Copyright © 2013 Honeywell International Inc. 9/18/2013

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Step Action

3

ATTENTION

If you are facing any of the following situation while loading the data base:

1. Import wrong Lesson Database

2. Error prompt appears while loading data base.

Then students should wait for at least one minute before reloading the database.

4 Open Control Builder if not already open.

Download and activate Controller and control modules.

5 Ensure that the Controller and Control Modules are indicated in green color.

6 Open the Excel Spreadsheet if not already open. Open either from C:\Users\Student\Documents\Tie_Back_New.xls OR by double clicking the shortcut on your desktop.

Proceed to next Lab

Page 5: Topic: Productivity Tools in Control Builderhw.server.tracorp.com/.../14613LabProductivityToolsinControlBuilder.pdf · Instructions for Productivity Tools in Control Builder Introduction

Productivity Tools in Control Builder

Export/Import a Control Module

9/18/2013 Copyright © 2013 Honeywell International Inc. 5

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Export/Import a Control Module

Practice

Objective

• Use the Import and Export functionality of Control Builder to incorporate parts from one Control Builder Project into another Project

• Export the Control Module 11_TI20

• Import Analog Indicator points

• Use Bulk Edit Parameters to change parameter values

Prerequisites

• Experion PKS server or client machine loaded with Experion PKS Engineering Tools

• 11_TI20 CM configured in Control Builder

• Exported files of the Analog Indicator CMs for SIM C200E available in the path: C:\Users\Public\Public Documents\Honeywell\Experion PKS\ Ixport\C200E\L11_Productivity tools in CB

• Exported files of the Analog Indicator CMs for SIM C300 available in the path: C:\ Users\Public\Public Documents\Honeywell\Experion PKS\ Ixport\C300\L11_Prodcutivity tools in CB

• Control Builder running with at least one Project/Monitor tree window open

• SIM_C200E/SIMC300 Controller and IOMs configured

Introduction

A Project file can contain many items, such as IOMs and CMs, for up to 20 controllers. From Control Builder, use the Import/Export tool to copy some or all of one project to another.

• Export - copies the designated portion of a project from Control Builder to a specified directory

• Import - copies the designated CMs into Control Builder’s Project Tab

Page 6: Topic: Productivity Tools in Control Builderhw.server.tracorp.com/.../14613LabProductivityToolsinControlBuilder.pdf · Instructions for Productivity Tools in Control Builder Introduction

Productivity Tools in Control Builder

Export/Import a Control Module

6 Copyright © 2013 Honeywell International Inc. 9/18/2013

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Procedure

Export Function Block Configuration

Step Action

1 In Control Builder, click on the Project window, then from the menu bar select File > Export, to call up the dialog box, as shown below.

• Select 11_TI20

ATTENTION

Your point list may be different. The point list contains all items in the current project.

Page 7: Topic: Productivity Tools in Control Builderhw.server.tracorp.com/.../14613LabProductivityToolsinControlBuilder.pdf · Instructions for Productivity Tools in Control Builder Introduction

Productivity Tools in Control Builder

Export/Import a Control Module

9/18/2013 Copyright © 2013 Honeywell International Inc. 7

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Step Action

2 11_TI20 now appears in the Selected Objects For Export field.

Browse to the path of:

C:\Users\Public\Public Documents\Honeywell\Experion PKS\Ixport\Export

TIP

Create a folder with name Export at given path if not created already.

Double-click Export and click OK.

Page 8: Topic: Productivity Tools in Control Builderhw.server.tracorp.com/.../14613LabProductivityToolsinControlBuilder.pdf · Instructions for Productivity Tools in Control Builder Introduction

Productivity Tools in Control Builder

Export/Import a Control Module

8 Copyright © 2013 Honeywell International Inc. 9/18/2013

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Step Action

3 Click the Export Button.

• The Exporting Data dialog box appears.

ATTENTION

This dialog box automatically closes if there were no errors during the export.

4 Open Windows Explorer and navigate to the exported CM location:

• C:\ Users\Public\Public Documents\Honeywell\Experion PKS\Ixport\Export

• The following files are generated:

Module Name.bcd (In this case, module name is 11_TI20.)

Module Name.cnf.xml

Export.sl

global.gui

global.snl.xml

• The Export.sl is the successful list file. It contains a list of all the exported objects.

ATTENTION

Here, 11_TI20 was successfully exported. You can import this CM to any other Project with the Import facility.

Page 9: Topic: Productivity Tools in Control Builderhw.server.tracorp.com/.../14613LabProductivityToolsinControlBuilder.pdf · Instructions for Productivity Tools in Control Builder Introduction

Productivity Tools in Control Builder

Export/Import a Control Module

9/18/2013 Copyright © 2013 Honeywell International Inc. 9

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Import a Control Module

Import copies designated Control Modules from the Import/Export files located in the specified directory (shown in the Import form) to a Control Builder Project.

In this lab, import the Analog Indicator points. These are pre-built CMs and already exported into the following directory:

• Exported files of the Analog Indicator CMs for SIM C200E available in the path: C:\ Users\Public\Public Documents\Honeywell\Experion PKS\Ixport\C200E\\L11_Productivity tools in CB

• Exported files of the Analog Indicator CMs for SIM C300 available in the path: C:\ Users\Public\Public Documents\Honeywell\Experion PKS\Ixport\C300\\L11_Productivity tools in CB

Page 10: Topic: Productivity Tools in Control Builderhw.server.tracorp.com/.../14613LabProductivityToolsinControlBuilder.pdf · Instructions for Productivity Tools in Control Builder Introduction

Productivity Tools in Control Builder

Export/Import a Control Module

10 Copyright © 2013 Honeywell International Inc. 9/18/2013

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Step Action

1 From Control Builder, select File>Import to call up the dialog box, as shown below.

ATTENTION

When the above dialog box opens, the Project Tree window automatically closes.

2 Click the Browse button and change the Import path to the following folder:

C:\ Users\Public\Public Documents\Honeywell\Experion PKS\ IXPORT\C200E (C300)\L11_Productivity tools in CB

Click OK.

Page 11: Topic: Productivity Tools in Control Builderhw.server.tracorp.com/.../14613LabProductivityToolsinControlBuilder.pdf · Instructions for Productivity Tools in Control Builder Introduction

Productivity Tools in Control Builder

Export/Import a Control Module

9/18/2013 Copyright © 2013 Honeywell International Inc. 11

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Step Action

3 Import the Analog Indicator points listed below.

Selection can be made with <SHIFT> select (for contiguous items) or <CTRL> select (for noncontiguous items).

ATTENTION

Select only the following, from the list, to import:

11_PI14, 11_TI21, 11_TI22, 11_TI23, 11_TI24, 11_TI25, 11_TI26 and 11_TI40.

4 Maintain the Import CEE Assignments checkbox selection. This checkbox imports and assigns the above CMs to the CEESCEFB61 (or SIM_CEEC300).

• If this option is NOT selected, then the imported items are imported as Unassigned.

Page 12: Topic: Productivity Tools in Control Builderhw.server.tracorp.com/.../14613LabProductivityToolsinControlBuilder.pdf · Instructions for Productivity Tools in Control Builder Introduction

Productivity Tools in Control Builder

Export/Import a Control Module

12 Copyright © 2013 Honeywell International Inc. 9/18/2013

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Step Action

5 Click the Import button.

• The following dialog box appears:

ATTENTION

This dialog box automatically closes after a successful Import.

Page 13: Topic: Productivity Tools in Control Builderhw.server.tracorp.com/.../14613LabProductivityToolsinControlBuilder.pdf · Instructions for Productivity Tools in Control Builder Introduction

Productivity Tools in Control Builder

Export/Import a Control Module

9/18/2013 Copyright © 2013 Honeywell International Inc. 13

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Step Action

6 Open the Project Tree window and expand the Project.

• CEESCEFB61 (or SIM_CEEC300) with all the imported CMs appears, as shown below.

Page 14: Topic: Productivity Tools in Control Builderhw.server.tracorp.com/.../14613LabProductivityToolsinControlBuilder.pdf · Instructions for Productivity Tools in Control Builder Introduction

Productivity Tools in Control Builder

Export/Import a Control Module

14 Copyright © 2013 Honeywell International Inc. 9/18/2013

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Use Bulk Edit Parameters

Step Action

1 Open the Bulk Editor.

• Click Tools > Bulk Edit Parameters > Create Bulk Edit List

2 Click on Show All Points button.

Page 15: Topic: Productivity Tools in Control Builderhw.server.tracorp.com/.../14613LabProductivityToolsinControlBuilder.pdf · Instructions for Productivity Tools in Control Builder Introduction

Productivity Tools in Control Builder

Export/Import a Control Module

9/18/2013 Copyright © 2013 Honeywell International Inc. 15

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Step Action

3 Select 11_TI21.DACA from the Available Points window then

• Click the arrow button

• 11_TI21.DACA now appears in the Selected Points window

Similarly, select 11_TI22.DACA, 11_TI23.DACA, 11_TI24.DACA and 11_TI26.DACA and move them to the Selected Points window.

ATTENTION

Press <CNTRL> key for selecting multiple points.

Page 16: Topic: Productivity Tools in Control Builderhw.server.tracorp.com/.../14613LabProductivityToolsinControlBuilder.pdf · Instructions for Productivity Tools in Control Builder Introduction

Productivity Tools in Control Builder

Export/Import a Control Module

16 Copyright © 2013 Honeywell International Inc. 9/18/2013

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Step Action

4 In the Available Parameters window, find and select PVEUHI and PVEXHILM. Select the arrow button.

ATTENTION

Press <CNTRL> key for selecting multiple parameters.

5 For C300 students only (C200E students skip this step):

From ‘Available Points’, select and move the following to ‘Selected Points’:

11_TI21.TI, 11_TI22.TI, 11_TI23.TI, 11_TI24.TI, 11_TI26.TI

6 For C300 students only (C200E students skip this step):

From ‘Available Parameters’ select and move the following to ‘Selected Parameters’:

PVEXEUHI

7 Click the Browse button for the Output Directory.

• Select C:\Users\Student\Documents in the ‘Browse for Folder’ window

• Click OK

Page 17: Topic: Productivity Tools in Control Builderhw.server.tracorp.com/.../14613LabProductivityToolsinControlBuilder.pdf · Instructions for Productivity Tools in Control Builder Introduction

Productivity Tools in Control Builder

Export/Import a Control Module

9/18/2013 Copyright © 2013 Honeywell International Inc. 17

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Step Action

8 Select Excel Spread Sheet [.xls] from the Select File Type pull down menu.

Click the Save button.

ATTENTION

If the file already exists in the folder, a prompt will appear asking you to overwrite the existing file. Press YES.

9 Click OK.

10 Close the ‘Create Bulk Edit List’ window.

Page 18: Topic: Productivity Tools in Control Builderhw.server.tracorp.com/.../14613LabProductivityToolsinControlBuilder.pdf · Instructions for Productivity Tools in Control Builder Introduction

Productivity Tools in Control Builder

Export/Import a Control Module

18 Copyright © 2013 Honeywell International Inc. 9/18/2013

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Step Action

11 Open Windows Explorer and navigate to C:\Users\Student\Documents

• Double click the BulkEdit.xls file

• Result: Excel opens, displaying the points as shown below

Screen capture shown for SIMC300. You will see this only when using SIMC300.

Page 19: Topic: Productivity Tools in Control Builderhw.server.tracorp.com/.../14613LabProductivityToolsinControlBuilder.pdf · Instructions for Productivity Tools in Control Builder Introduction

Productivity Tools in Control Builder

Export/Import a Control Module

9/18/2013 Copyright © 2013 Honeywell International Inc. 19

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Step Action

12 In the PVEUHI column, select each 100 value and change it to ‘260.

In the PVEXHILM, select each 100 value and change it to ‘260.

ATTENTION

The single quote “ ‘ “ before 260 tells Excel that this value is text.

For C300 students only:

Enter the PVEXEUHI as 260 for each Series C Analog Input channel.

Screen capture shown for SIMC300. You will see this only when using SIMC300.

Page 20: Topic: Productivity Tools in Control Builderhw.server.tracorp.com/.../14613LabProductivityToolsinControlBuilder.pdf · Instructions for Productivity Tools in Control Builder Introduction

Productivity Tools in Control Builder

Export/Import a Control Module

20 Copyright © 2013 Honeywell International Inc. 9/18/2013

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Step Action

13 Save and close the Excel spreadsheet.

Accept the default “C:\Users\student” file location.

14 In Control Builder, select Tools > Bulk Edit Parameters > Read Bulk Edit List.

• Result: the Read Bulk Edit List tool opens.

Page 21: Topic: Productivity Tools in Control Builderhw.server.tracorp.com/.../14613LabProductivityToolsinControlBuilder.pdf · Instructions for Productivity Tools in Control Builder Introduction

Productivity Tools in Control Builder

Export/Import a Control Module

9/18/2013 Copyright © 2013 Honeywell International Inc. 21

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Step Action

15 Click the Browse button.

From the “C:\Users\Student\Documents”, select the BulkEdit.xls file.

Click the Open button.

Page 22: Topic: Productivity Tools in Control Builderhw.server.tracorp.com/.../14613LabProductivityToolsinControlBuilder.pdf · Instructions for Productivity Tools in Control Builder Introduction

Productivity Tools in Control Builder

Export/Import a Control Module

22 Copyright © 2013 Honeywell International Inc. 9/18/2013

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

1 Select the Update Project option.

Click the Start button.

2 Click the OK button to acknowledge the warning.

3 Close the Bulk Edit tool.

Page 23: Topic: Productivity Tools in Control Builderhw.server.tracorp.com/.../14613LabProductivityToolsinControlBuilder.pdf · Instructions for Productivity Tools in Control Builder Introduction

Productivity Tools in Control Builder

Export/Import a Control Module

9/18/2013 Copyright © 2013 Honeywell International Inc. 23

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

4 In Control Builder, verify that PVEUHI changed (to 260) for the five points above (11_TI21, 11_TI22, 11_TI23, 11_TI24, 11_TI26).

ATTENTION

If necessary, open the Project Tree, and expand the Project.

Page 24: Topic: Productivity Tools in Control Builderhw.server.tracorp.com/.../14613LabProductivityToolsinControlBuilder.pdf · Instructions for Productivity Tools in Control Builder Introduction

Productivity Tools in Control Builder

Export/Import a Control Module

24 Copyright © 2013 Honeywell International Inc. 9/18/2013

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

5 Select the 11_PI14, 11_TI21, 11_TI22, 11_TI23, 11_TI24, 11_TI25, 11_TI26, and 11_TI40 points.

Click the Download button.

Click Continue on the Load dialog window.

Select the checkbox with Automatically change… in the Load dialog box, and click OK to begin the download.

After a successful download, go to the Monitoring Tree window, expand your SCE/CEE and verify that the CMs are activated (green).

ATTENTION

Your Project screen may appear slightly different than the example above.

Page 25: Topic: Productivity Tools in Control Builderhw.server.tracorp.com/.../14613LabProductivityToolsinControlBuilder.pdf · Instructions for Productivity Tools in Control Builder Introduction

Productivity Tools in Control Builder

Export/Import a Control Module

9/18/2013 Copyright © 2013 Honeywell International Inc. 25

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

6 In Station, open the Debutanizer_123 graphic and verify that the downloaded points are displaying values. If Debutanizer_123 is already displayed, refresh the display.

• 11_TI40, 11_TI21, and 11_TI23 are shown below

Page 26: Topic: Productivity Tools in Control Builderhw.server.tracorp.com/.../14613LabProductivityToolsinControlBuilder.pdf · Instructions for Productivity Tools in Control Builder Introduction

Productivity Tools in Control Builder

Export/Import a Control Module

26 Copyright © 2013 Honeywell International Inc. 9/18/2013

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

7 • 11_TI25, 11_TI24 and 11_TI21 are shown below

• 11_TI22 is shown below

ATTENTION

Your displays may differ.

If values for 11_TI20 are not updating, close and re-open Tie_back_new.xls and verify the following is selected: Tools > Microsoft Excel Data Exchange > Recalculate Every 5 seconds

This file is used for simulation purposes.