topic: data acquisition control module -...

58
9/18/2013 Copyright © 2013 Honeywell International Inc. 1 HPS Automation College written permission required to distribute Honeywell Confidential and Proprietary Topic: Data Acquisition Control Module Contents Instructions for: Data Acquisition Control Module .................................................................................3 Configure Series A IO Channel .............................................................................................................5 Configure Series C IO Channel ...........................................................................................................21 Configure the Data Acquisition Control Module ..................................................................................35

Upload: others

Post on 12-Jun-2020

13 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Topic: Data Acquisition Control Module - TraCorphw.server.tracorp.com/courses/ac/EXP2001R410B/... · Instructions for: Data Acquisition Control Module Introduction This portion of

9/18/2013 Copyright © 2013 Honeywell International Inc. 1

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Topic: Data Acquisition Control Module

Contents

Instructions for: Data Acquisition Control Module .................................................................................3

Configure Series A IO Channel .............................................................................................................5

Configure Series C IO Channel ...........................................................................................................21

Configure the Data Acquisition Control Module ..................................................................................35

Page 2: Topic: Data Acquisition Control Module - TraCorphw.server.tracorp.com/courses/ac/EXP2001R410B/... · Instructions for: Data Acquisition Control Module Introduction This portion of

2 Copyright © 2013 Honeywell International Inc. 9/18/2013

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

This page was intentionally left blank.

Page 3: Topic: Data Acquisition Control Module - TraCorphw.server.tracorp.com/courses/ac/EXP2001R410B/... · Instructions for: Data Acquisition Control Module Introduction This portion of

Data Acquisition Control Module

Instructions for: Data Acquisition Control Module

9/18/2013 Copyright © 2013 Honeywell International Inc. 3

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Instructions for: Data Acquisition Control Module

Introduction

This portion of the document contains important information required to perform to ‘Data Acquisition Control Module’ lab.

Procedure

Step Action

1

Read the following IMPORTANT information carefully.

Decide if you will be performing labs for C200E (and Series A I/O modules) OR C300 (and Series C I/O Modules). You can opt for either one but not both.

_______ C200E (and Series A I/O modules)

_______ C300 (and Series C I/O Modules)

2

ATTENTION

You must perform the remaining steps of this lab if you skipped any of the prior lessons of this course, else skip the remaining instructions and proceed to the next lab.

Locate the “GUI_DB_Load” Shortcut on desktop.

1. Double click “GUI_DB_Load” Shortcut to launch the import utility.

2. In Controller drop down select either C200 or C300 Controller (as per the option selected in step#1).

3. In Lesson number drop down select Lesson10.

4. Click the LOAD button.

Page 4: Topic: Data Acquisition Control Module - TraCorphw.server.tracorp.com/courses/ac/EXP2001R410B/... · Instructions for: Data Acquisition Control Module Introduction This portion of

Data Acquisition Control Module

Instructions for: Data Acquisition Control Module

4 Copyright © 2013 Honeywell International Inc. 9/18/2013

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Step Action

3

ATTENTION

If you are facing any of the following issues while loading the data base:

1. Import wrong Lesson Database

2. Error prompt appears while loading data base.

Then you should wait for at least one minute before reloading the database.

4 Open Control Builder if not already open.

Download and activate Controller and control modules.

5 Ensure that the Controller and Control Modules are indicated in green color.

Go to the next lab.

6 Open the Excel Spreadsheet if not already open. Open either from C:\Users\Student\Documents\Tie_Back_New.xls OR by double clicking the shortcut on your desktop.

Proceed to next Lab

Page 5: Topic: Data Acquisition Control Module - TraCorphw.server.tracorp.com/courses/ac/EXP2001R410B/... · Instructions for: Data Acquisition Control Module Introduction This portion of

Data Acquisition Control Module

Configure Series A IO Channel

9/18/2013 Copyright © 2013 Honeywell International Inc. 5

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Configure Series A IO Channel

Practice

Objective

• Configure a Control Module (CM)

• Understand the naming of the Control Module and the function blocks within the Control Module

• Configure an indicator Control Module for an analog input point

Prerequisites

• Experion PKS Server or Client machine with Experion PKS Engineering Tools loaded

• Debutanizer_123 graphic loaded on the server (This is required at a later time to check the control strategy.)

• SIM-C200E/C200E controller and IOMs configured

• Excel Data Exchange configured and loaded with the simulation spreadsheet

Introduction

To create a Control Strategy, you must first create a Control Module, and then insert and connect function blocks into the Control Module. The point 11_TI20 is built in this lab. 11_TI20 will have alarming and be in a group and detail display. 11_TI20 will also be historized.

The Control Module is built, loaded and activated. The CM is linked to a Microsoft Excel worksheet for process simulation. The remaining Control Modules of a similar type are then imported into the project.

Page 6: Topic: Data Acquisition Control Module - TraCorphw.server.tracorp.com/courses/ac/EXP2001R410B/... · Instructions for: Data Acquisition Control Module Introduction This portion of

Data Acquisition Control Module

Configure Series A IO Channel

6 Copyright © 2013 Honeywell International Inc. 9/18/2013

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Configure a Control Module (CM)

Step Action

1 Read the attention box.

ATTENTION

This section should be done only by students who have selected C200E (and Series A I/O Modules).

2 Open Control Builder through Configuration Studio.

• Open one or two Project/Monitor tree windows as desired.

3 Open the Excel spreadsheet by double-clicking on:

C:\Users\Student\Documents\Tie_back_NEW.xls

(or by double clicking the shortcut on the desktop if it is available).

Page 7: Topic: Data Acquisition Control Module - TraCorphw.server.tracorp.com/courses/ac/EXP2001R410B/... · Instructions for: Data Acquisition Control Module Introduction This portion of

Data Acquisition Control Module

Configure Series A IO Channel

9/18/2013 Copyright © 2013 Honeywell International Inc. 7

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Step Action

4 From Control Builder, expand System in the Library tab, as shown below:

Page 8: Topic: Data Acquisition Control Module - TraCorphw.server.tracorp.com/courses/ac/EXP2001R410B/... · Instructions for: Data Acquisition Control Module Introduction This portion of

Data Acquisition Control Module

Configure Series A IO Channel

8 Copyright © 2013 Honeywell International Inc. 9/18/2013

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Step Action

5 Select and drag the CONTROL MODULE into a blank area in the Project tree.

A dialog box, as seen below, will appear.

ATTENTION

If you have a problem finding blank space which will allow you to drop the CM, collapse the trees in the Project window.

It is important to use the CM names given in this document, because they are used in the Excel simulation.

Page 9: Topic: Data Acquisition Control Module - TraCorphw.server.tracorp.com/courses/ac/EXP2001R410B/... · Instructions for: Data Acquisition Control Module Introduction This portion of

Data Acquisition Control Module

Configure Series A IO Channel

9/18/2013 Copyright © 2013 Honeywell International Inc. 9

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Step Action

6 Enter the following information:

Destination Tag names: 11_TI20 (name of the new CM)

Destination Item Names: 11_TI20_Item.

Click Finish.

ATTENTION

In this tag name, the character after the letter T is the letter I.

When adding a new CM, Control Builder numbers the CM sequentially, by default. You can assign any 16-character unique Project name to the CM.

It is important to use the CM names given in this document because they are used in the Excel simulation.

The Source Names contain random numbers generated by Control Builder. Therefore, the ones in this picture may be different than yours.

Page 10: Topic: Data Acquisition Control Module - TraCorphw.server.tracorp.com/courses/ac/EXP2001R410B/... · Instructions for: Data Acquisition Control Module Introduction This portion of

Data Acquisition Control Module

Configure Series A IO Channel

10 Copyright © 2013 Honeywell International Inc. 9/18/2013

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Step Action

7 Verify 11_TI20 is added to the Unassigned section in the Project Tree window.

8 Configure the parameters for 11_TI20.

• Right-click 11_TI20

• Select Module Properties

Page 11: Topic: Data Acquisition Control Module - TraCorphw.server.tracorp.com/courses/ac/EXP2001R410B/... · Instructions for: Data Acquisition Control Module Introduction This portion of

Data Acquisition Control Module

Configure Series A IO Channel

9/18/2013 Copyright © 2013 Honeywell International Inc. 11

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Step Action

9 Enter parameter details, in the Main tab, as given below.

Name: 11_TI20 (Maximum 16 characters allowed)

Description: T-100 Bottom (Maximum 24 characters allowed)

Parent Asset: Level_C11.

Eng Units: Deg C (Maximum 16 characters allowed)

ATTENTION

If you want help on any of the parameters in this form, press <F1> or click the Help button located at the bottom of the form.

Page 12: Topic: Data Acquisition Control Module - TraCorphw.server.tracorp.com/courses/ac/EXP2001R410B/... · Instructions for: Data Acquisition Control Module Introduction This portion of

Data Acquisition Control Module

Configure Series A IO Channel

12 Copyright © 2013 Honeywell International Inc. 9/18/2013

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Step Action

10 Click the Server Displays tab, and enter the display details, as shown below.

ATTENTION

This lab uses the standard Honeywell analog point detail and group display for the point 11_TI20 in Station.

11 Click OK.

Page 13: Topic: Data Acquisition Control Module - TraCorphw.server.tracorp.com/courses/ac/EXP2001R410B/... · Instructions for: Data Acquisition Control Module Introduction This portion of

Data Acquisition Control Module

Configure Series A IO Channel

9/18/2013 Copyright © 2013 Honeywell International Inc. 13

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Step Action

12 Assign the CM to the Controller CEESCEFB61.

• With 11_TI20 selected, click the Assign Button on the toolbar to open the Execution Environment Assignment screen.

• If not already highlighted, select 11_TI20 in the CM/SCMs tab.

• Select CEESCEFB61 in the Assign To window.

• Click the Assign Button.

Page 14: Topic: Data Acquisition Control Module - TraCorphw.server.tracorp.com/courses/ac/EXP2001R410B/... · Instructions for: Data Acquisition Control Module Introduction This portion of

Data Acquisition Control Module

Configure Series A IO Channel

14 Copyright © 2013 Honeywell International Inc. 9/18/2013

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Step Action

13 Assigned Modules will show 11_TI20.

Click the Close Button.

14 11_TI20 is assigned to CEESCEFB61, as indicated below.

Page 15: Topic: Data Acquisition Control Module - TraCorphw.server.tracorp.com/courses/ac/EXP2001R410B/... · Instructions for: Data Acquisition Control Module Introduction This portion of

Data Acquisition Control Module

Configure Series A IO Channel

9/18/2013 Copyright © 2013 Honeywell International Inc. 15

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Add Function Blocks to a CM

Use the IOMs, configured in the lab “Configure C200E Hardware”, here.

Step Action

1 Double click 11_TI20 in the Project Tree window to open the chart view.

ATTENTION

Your screen may vary from the example shown.

Page 16: Topic: Data Acquisition Control Module - TraCorphw.server.tracorp.com/courses/ac/EXP2001R410B/... · Instructions for: Data Acquisition Control Module Introduction This portion of

Data Acquisition Control Module

Configure Series A IO Channel

16 Copyright © 2013 Honeywell International Inc. 9/18/2013

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Step Action

2 Add Function Blocks to CM 11_TI20.

• Click the Library Tree window.

• Expand the IOCHANNEL, by clicking the ‘+’ sign adjacent to it.

• Select the AICHANNEL block.

3 Drag and drop the AICHANNEL to the 11_TI20 chart view.

4 Click the icon on the toolbar to Save your CM to the Project database.

Page 17: Topic: Data Acquisition Control Module - TraCorphw.server.tracorp.com/courses/ac/EXP2001R410B/... · Instructions for: Data Acquisition Control Module Introduction This portion of

Data Acquisition Control Module

Configure Series A IO Channel

9/18/2013 Copyright © 2013 Honeywell International Inc. 17

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Step Action

5 Configure AI Channel parameters.

• Double-click on the AICHANNELA to open the Block Properties.

6 Enter the following details, as given below:

Channel Name: TI

Module Name: AI_8_4_4

Page 18: Topic: Data Acquisition Control Module - TraCorphw.server.tracorp.com/courses/ac/EXP2001R410B/... · Instructions for: Data Acquisition Control Module Introduction This portion of

Data Acquisition Control Module

Configure Series A IO Channel

18 Copyright © 2013 Honeywell International Inc. 9/18/2013

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Step Action

7 Enter the following details as given below:

Select Channel Number: 1

Click the Assign Channel Block button.

ATTENTION

The Module Type displays automatically when selecting the module name.

11_TI20.TI is assigned to the channel number 1 of AI_8_4_4, as seen in the Channel Number/Channel Name list.

8 Click OK.

Page 19: Topic: Data Acquisition Control Module - TraCorphw.server.tracorp.com/courses/ac/EXP2001R410B/... · Instructions for: Data Acquisition Control Module Introduction This portion of

Data Acquisition Control Module

Configure Series A IO Channel

9/18/2013 Copyright © 2013 Honeywell International Inc. 19

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Step Action

9

ATTENTION

You have completed this section of the lab. Go to the third section of this lab which is titled ‘Configure the Data Acquisition Control Module’.

Do NOT perform the section titled ‘Configure Series C I/O Channel’.

10 Save and close 11_TI20.

Page 20: Topic: Data Acquisition Control Module - TraCorphw.server.tracorp.com/courses/ac/EXP2001R410B/... · Instructions for: Data Acquisition Control Module Introduction This portion of

Data Acquisition Control Module

Configure Series A IO Channel

20 Copyright © 2013 Honeywell International Inc. 9/18/2013

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

This page was intentionally left blank.

Page 21: Topic: Data Acquisition Control Module - TraCorphw.server.tracorp.com/courses/ac/EXP2001R410B/... · Instructions for: Data Acquisition Control Module Introduction This portion of

Data Acquisition Control Module

Configure Series C IO Channel

9/18/2013 Copyright © 2013 Honeywell International Inc. 21

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Configure Series C IO Channel

Practice

Objective

• Configure a Control Module (CM)

• Understand the naming of the Control Module and the function blocks within the Control Module

• Configure an indicator Control Module for an analog input point

• Refer “Guide to Debutanizer model for C200E/C300 Labs” document available in Appendix lesson (or Document available on Desktop) for IO channel assignment.

Prerequisites

• Experion PKS Server or Client machine with Experion PKS Engineering Tools loaded

• Debutanizer_123 graphic loaded on the server (This is required at a later time to check the control strategy.)

• SIM-C300/C300 Controller and IOMs configured

• Excel Data Exchange configured and loaded with the simulation spreadsheet

Introduction

To create a Control Strategy, you must first create a Control Module, and then insert and connect function blocks into the Control Module. The point 11_TI20 is built in this lab. 11_TI20 will have alarming and be in a group and detail display. 11_TI20 will also be historized.

The Control Module is built, loaded and activated. The CM is linked to a Microsoft Excel worksheet for process simulation. The remaining Control Modules of a similar type are then imported into the project.

Page 22: Topic: Data Acquisition Control Module - TraCorphw.server.tracorp.com/courses/ac/EXP2001R410B/... · Instructions for: Data Acquisition Control Module Introduction This portion of

Data Acquisition Control Module

Configure Series C IO Channel

22 Copyright © 2013 Honeywell International Inc. 9/18/2013

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Configure a Control Module (CM)

Step Action

1 Read the attention box.

ATTENTION

This section should be done only by students who have selected C300 (and Series C I/O Modules).

2 Open Control Builder through Configuration Studio.

• Open one or two Project/Monitor tree windows as desired.

3 Open the Excel spread sheet by double-clicking on:

C:\Users\Student\Documents\Tie_back_NEW.xls

(or by double clicking the shortcut on the desktop if it is available).

Page 23: Topic: Data Acquisition Control Module - TraCorphw.server.tracorp.com/courses/ac/EXP2001R410B/... · Instructions for: Data Acquisition Control Module Introduction This portion of

Data Acquisition Control Module

Configure Series C IO Channel

9/18/2013 Copyright © 2013 Honeywell International Inc. 23

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Step Action

4 From Control Builder expand System in the Library tab, as indicated.

Page 24: Topic: Data Acquisition Control Module - TraCorphw.server.tracorp.com/courses/ac/EXP2001R410B/... · Instructions for: Data Acquisition Control Module Introduction This portion of

Data Acquisition Control Module

Configure Series C IO Channel

24 Copyright © 2013 Honeywell International Inc. 9/18/2013

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Step Action

5 Select and drag the CONTROLMODULE into a blank area in the Project tree.

A dialog box, as seen below, will appear.

ATTENTION

If you have a problem finding blank space which will allow you to drop the CM, collapse the trees in the Project window.

It is important to use the CM names given in this document, because they are used in the Excel simulation.

Page 25: Topic: Data Acquisition Control Module - TraCorphw.server.tracorp.com/courses/ac/EXP2001R410B/... · Instructions for: Data Acquisition Control Module Introduction This portion of

Data Acquisition Control Module

Configure Series C IO Channel

9/18/2013 Copyright © 2013 Honeywell International Inc. 25

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Step Action

6 Enter the following information:

Destination Tag names: 11_TI20 (name of the new CM)

Destination Item Names: 11_TI20_Item.

Click Finish.

ATTENTION

In this tag name, the character after the letter T is the letter I.

When adding a new CM, Control Builder numbers the CM sequentially, by default. You can assign any 16-character unique Project name to the CM.

It is important to use the CM names, given in this document, because they are used in the Excel simulation.

The Source Names contain random numbers generated by Control Builder. Therefore, the ones in this picture may be different than yours.

Page 26: Topic: Data Acquisition Control Module - TraCorphw.server.tracorp.com/courses/ac/EXP2001R410B/... · Instructions for: Data Acquisition Control Module Introduction This portion of

Data Acquisition Control Module

Configure Series C IO Channel

26 Copyright © 2013 Honeywell International Inc. 9/18/2013

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Step Action

7 Verify 11_TI20 is added to the Unassigned section in the Project Tree window.

8 Configure the parameters for 11_TI20.

• Right-click 11_TI20

• Select Module Properties

Page 27: Topic: Data Acquisition Control Module - TraCorphw.server.tracorp.com/courses/ac/EXP2001R410B/... · Instructions for: Data Acquisition Control Module Introduction This portion of

Data Acquisition Control Module

Configure Series C IO Channel

9/18/2013 Copyright © 2013 Honeywell International Inc. 27

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Step Action

9 Enter parameter details, in the Main tab, as given below.

Name: 11_TI20 (Maximum 16 characters allowed)

Description: T-100 Bottom (Maximum 24 characters allowed)

Parent Asset: Level_C11.

Eng Units: Deg C (Maximum 16 characters allowed)

ATTENTION

If you want help on any of the parameters in this form, press <F1> or click the Help button located at the bottom of the form.

Page 28: Topic: Data Acquisition Control Module - TraCorphw.server.tracorp.com/courses/ac/EXP2001R410B/... · Instructions for: Data Acquisition Control Module Introduction This portion of

Data Acquisition Control Module

Configure Series C IO Channel

28 Copyright © 2013 Honeywell International Inc. 9/18/2013

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Step Action

10 Click the Server Displays tab, and enter the display details, as shown below.

ATTENTION

This lab uses the standard Honeywell analog point detail and group display for the point 11_TI20 in Station.

11 Click OK.

Page 29: Topic: Data Acquisition Control Module - TraCorphw.server.tracorp.com/courses/ac/EXP2001R410B/... · Instructions for: Data Acquisition Control Module Introduction This portion of

Data Acquisition Control Module

Configure Series C IO Channel

9/18/2013 Copyright © 2013 Honeywell International Inc. 29

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Step Action

12 Assign the CM to the Controller SIM_CEEC300.

• With 11_TI20 selected, click the Assign Button on the toolbar to open the Execution Environment Assignment screen

• If not already highlighted, select 11_TI20 in the CM/SCMs tab.

• Select SIM_CEEC300 in the Assign To window

• Click the Assign Button

Page 30: Topic: Data Acquisition Control Module - TraCorphw.server.tracorp.com/courses/ac/EXP2001R410B/... · Instructions for: Data Acquisition Control Module Introduction This portion of

Data Acquisition Control Module

Configure Series C IO Channel

30 Copyright © 2013 Honeywell International Inc. 9/18/2013

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Step Action

13 Assigned Modules will show 11_TI20.

Click the Close Button.

14 11_TI20 is assigned to SIM_CEEC300, as indicated below.

Page 31: Topic: Data Acquisition Control Module - TraCorphw.server.tracorp.com/courses/ac/EXP2001R410B/... · Instructions for: Data Acquisition Control Module Introduction This portion of

Data Acquisition Control Module

Configure Series C IO Channel

9/18/2013 Copyright © 2013 Honeywell International Inc. 31

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Add Function Blocks to a CM

Use the IOMs, configured in the lab “Configure C300/SIM C300 Hardware”, here.

Step Action

1 Double click 11_TI20 in the Project Tree window to open the chart view.

ATTENTION

Your screen may vary from the example shown.

Page 32: Topic: Data Acquisition Control Module - TraCorphw.server.tracorp.com/courses/ac/EXP2001R410B/... · Instructions for: Data Acquisition Control Module Introduction This portion of

Data Acquisition Control Module

Configure Series C IO Channel

32 Copyright © 2013 Honeywell International Inc. 9/18/2013

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Step Action

2 Add Function Blocks to CM 11_TI20.

• Select the Series_C_IOLINK Link

• Expand the C_AI_3, by clicking the ‘+’ sign adjacent to it

• Select the AICHANNEL_01 block

ATTENTION

You can add Series C IO function blocks to a CM in two ways:

1. The Project Tree method.

2. The Library Tree method (covered in Describe C300 and Series C IO Configuration presentation)

We will use the Project Tree method. This method uses the fact that Series C IO modules contain their own configuration databases. Therefore when you add an IOM, its configuration parameters are available from project.

In this case, select the first AI channel from your AI IOM.

Refer to “Guide to Debutanizer model for C200/C300 Labs” document in Appendix Lesson (or Document available on Desktop) for IO channel assignment.

Page 33: Topic: Data Acquisition Control Module - TraCorphw.server.tracorp.com/courses/ac/EXP2001R410B/... · Instructions for: Data Acquisition Control Module Introduction This portion of

Data Acquisition Control Module

Configure Series C IO Channel

9/18/2013 Copyright © 2013 Honeywell International Inc. 33

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Step Action

3 Drag and drop the AICHANNEL_01 onto 11_TI20 chart view.

4 Click the icon on the toolbar to Save your CM to the Project database.

5 Configure AI Channel parameters.

• Double click on the AICHANNEL_01 from the chart view of 11_TI20.

6 Enter the following details, as given below:

Channel Name: TI

ATTENTION

IO Channel is automatically assigned to the IOM when you drag and drop it from the IOLINK.

Page 34: Topic: Data Acquisition Control Module - TraCorphw.server.tracorp.com/courses/ac/EXP2001R410B/... · Instructions for: Data Acquisition Control Module Introduction This portion of

Data Acquisition Control Module

Configure Series C IO Channel

34 Copyright © 2013 Honeywell International Inc. 9/18/2013

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Step Action

7 Click on the Configuration tab and enter the Channel PV Ranges details as given below:

• PV Extended High Range: 267.54

• PV High Range: 260

• PV Low Range: 0

• PV Extended Low Range: -7.54

ATTENTION

In all Labs, you need to configure the Channel PV Range parameters for all Analog Input Channel blocks; it should match with DACA block Process Variable details.

Click OK.

8 Save and close 11_TI20.

9

TIP

In the future, when building Control Modules, follow the steps above.

Page 35: Topic: Data Acquisition Control Module - TraCorphw.server.tracorp.com/courses/ac/EXP2001R410B/... · Instructions for: Data Acquisition Control Module Introduction This portion of

Data Acquisition Control Module

Configure the Data Acquisition Control Module

9/18/2013 Copyright © 2013 Honeywell International Inc. 35

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Configure the Data Acquisition Control Module

Practice

Objective

• Configure a Data Acquisition Control Module (CM)

• Understand the naming of the Control Module and the function blocks within the Control Module

• Configure On-Delay and Off-Delay Time for Alarms (Alarm Debounce)

• Configure and use “Load Values While Active Functionality”

Prerequisites

• Experion PKS Server or Client machine with Experion PKS Engineering Tools loaded

• Debutanizer_123 graphic loaded on the server (This is required at a later time to check the control strategy.)

• SIM C200E/C200E, or C300/SIM-C300 Controller and IOMs configured

• Excel Data Exchange configured and loaded with the simulation spreadsheet

Introduction

To create a Control Strategy, you must first create a Control Module, and then insert and connect function blocks into the Control Module. The point 11_TI20 is built in this lab. 11_TI20 will have alarming and be in a group and detail display. 11_TI20 will also be historized.

The Control Module is built, loaded and activated. The CM is linked to a Microsoft Excel worksheet for process simulation. The remaining Control Modules of a similar type are then imported into the project.

Page 36: Topic: Data Acquisition Control Module - TraCorphw.server.tracorp.com/courses/ac/EXP2001R410B/... · Instructions for: Data Acquisition Control Module Introduction This portion of

Data Acquisition Control Module

Configure the Data Acquisition Control Module

36 Copyright © 2013 Honeywell International Inc. 9/18/2013

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Add Function Blocks to a CM

Use the IOMs, configured in the lab “Controller Hardware Configuration”, here.

Step Action

1 Read the attention box.

ATTENTION

This section should be done by ALL students (C200E & C300).

2 Open Control Builder and open 11_TI20 to the chart view.

3 Add a DACA Function Block to CM 11_TI20.

• Click the Library Tree window.

• Expand the DATAACQ, by clicking the ‘+’ sign adjacent to it.

• Select the DATAACQ block.

• Drag and drop the DATAACQ block on the 11_TI20 chart view.

ATTENTION

For more information on adding function blocks to a CM, refer to the Control Building Guide in Knowledge Builder along the path,

Experion R410 > Configuration > Control Building users Guide > Creating a Control Module > Creating and Saving a Control Module > Creating an Instance of a Basic Function Block.

4 Maximize the chart view by clicking the icon.

Page 37: Topic: Data Acquisition Control Module - TraCorphw.server.tracorp.com/courses/ac/EXP2001R410B/... · Instructions for: Data Acquisition Control Module Introduction This portion of

Data Acquisition Control Module

Configure the Data Acquisition Control Module

9/18/2013 Copyright © 2013 Honeywell International Inc. 37

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Step Action

5 Arrange the blocks as shown below.

ATTENTION

In this lab, the screen capture is shown for SIMC200E/C200E. If you are using SIMC300/C300 the AI channel will be different from Series A.

Page 38: Topic: Data Acquisition Control Module - TraCorphw.server.tracorp.com/courses/ac/EXP2001R410B/... · Instructions for: Data Acquisition Control Module Introduction This portion of

Data Acquisition Control Module

Configure the Data Acquisition Control Module

38 Copyright © 2013 Honeywell International Inc. 9/18/2013

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Step Action

6 Click the icon on the toolbar to Save your CM to the Project database.

7 Double-click the Data Acquisition Block that was just added to the CM.

8 Enter the following information :

Name: DACA

Description: T-100 Bottoms

Engr Units: Deg C

ATTENTION

This block must be named DACA so that the Honeywell-supplied analog point detail display will function properly when called from Station.

Page 39: Topic: Data Acquisition Control Module - TraCorphw.server.tracorp.com/courses/ac/EXP2001R410B/... · Instructions for: Data Acquisition Control Module Introduction This portion of

Data Acquisition Control Module

Configure the Data Acquisition Control Module

9/18/2013 Copyright © 2013 Honeywell International Inc. 39

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Step Action

9 Enter the Process Variable details, as given below:

• PVEU Range Hi: 260

• PVEU Range Lo: 0

• PV Extended Hi Limit: 267.54

• PV Extended Lo Limit: -7.54

• Low Signal Cut Off: NaN

10 Enable Clamping Option.

Page 40: Topic: Data Acquisition Control Module - TraCorphw.server.tracorp.com/courses/ac/EXP2001R410B/... · Instructions for: Data Acquisition Control Module Introduction This portion of

Data Acquisition Control Module

Configure the Data Acquisition Control Module

40 Copyright © 2013 Honeywell International Inc. 9/18/2013

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Step Action

11

ATTENTION

The PV High must set before the PV High High will appear.

Configure Alarms for the CM.

• Click the Alarms Tab of the DACA Block.

• Enter the information as given below :

Trip Point Priority On-Delay Time (sec) Off-Delay Time (sec)

PV High High 260 URGENT 0 0

PV High 210 HIGH 10 0

PV Low 20 LOW 0 10

Here we have configured On-Delay Timer of 10 sec for PV High. It means Controller waits for 10 sec after the value reached to 210 (Alarm Condition) and then it triggers an alarm.

In case of PV Low, we have configured Off-Delay Timer of 10 sec. Controller triggers an Alarm when PV is below 20. But Controller waits for 10 sec, even if the condition is Normal.

ATTENTION

Alarm debounce feature is introduced to avoid a false alarm generated by process disturbances. In the field, alarms may be generated due to fluctuations; to avoid this, On-Delay or Off-Delay timer can be configured on Block level.

Timer can be configured in Seconds only.

12 Click OK.

Page 41: Topic: Data Acquisition Control Module - TraCorphw.server.tracorp.com/courses/ac/EXP2001R410B/... · Instructions for: Data Acquisition Control Module Introduction This portion of

Data Acquisition Control Module

Configure the Data Acquisition Control Module

9/18/2013 Copyright © 2013 Honeywell International Inc. 41

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Connect Function Blocks

After adding the Function Blocks, connect them together to form a control strategy. Connect blocks together anytime, before or after configuring block parameters.

Step Action

1 Select Chart > Insert > Wire or click icon in the toolbar.

• Cursor changes to PLUS “+” sign inside the Project chart window.

• Click the PV Pin of AICHANNEL block (TI).

ATTENTION

Note the change in color for the PV pin of block TI. This indicates the block pin is selected.

Page 42: Topic: Data Acquisition Control Module - TraCorphw.server.tracorp.com/courses/ac/EXP2001R410B/... · Instructions for: Data Acquisition Control Module Introduction This portion of

Data Acquisition Control Module

Configure the Data Acquisition Control Module

42 Copyright © 2013 Honeywell International Inc. 9/18/2013

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Step Action

2 Click the P1 pin of DATAACQ Block DACA.

3 Save the CM by clicking the icon on the toolbar.

Page 43: Topic: Data Acquisition Control Module - TraCorphw.server.tracorp.com/courses/ac/EXP2001R410B/... · Instructions for: Data Acquisition Control Module Introduction This portion of

Data Acquisition Control Module

Configure the Data Acquisition Control Module

9/18/2013 Copyright © 2013 Honeywell International Inc. 43

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Step Action

4 To show the cross reference connections made between function blocks:

• Click Tools > System Preferences to open the window, as shown in the display below.

• Select the Display Cross-References checkbox under the General tab.

• Click OK.

5 Click OK. (Your dialog box may not look exactly like this one.)

Page 44: Topic: Data Acquisition Control Module - TraCorphw.server.tracorp.com/courses/ac/EXP2001R410B/... · Instructions for: Data Acquisition Control Module Introduction This portion of

Data Acquisition Control Module

Configure the Data Acquisition Control Module

44 Copyright © 2013 Honeywell International Inc. 9/18/2013

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Step Action

6 The display below shows cross references.

TIP

This cross reference may not be shown on a C300 Control Module.

Page 45: Topic: Data Acquisition Control Module - TraCorphw.server.tracorp.com/courses/ac/EXP2001R410B/... · Instructions for: Data Acquisition Control Module Introduction This portion of

Data Acquisition Control Module

Configure the Data Acquisition Control Module

9/18/2013 Copyright © 2013 Honeywell International Inc. 45

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Step Action

7 History collection.

• Double-click CM 11_TI20 in the white space to open the configuration form.

• Click the Server History tab. Verify that the Control Level is 200.

8 Select the parameters for historization.

• Click the blank Row 1 under the Parameter column in the History Configuration table.

• Click the Point selection button to open the Point Selection form.

Page 46: Topic: Data Acquisition Control Module - TraCorphw.server.tracorp.com/courses/ac/EXP2001R410B/... · Instructions for: Data Acquisition Control Module Introduction This portion of

Data Acquisition Control Module

Configure the Data Acquisition Control Module

46 Copyright © 2013 Honeywell International Inc. 9/18/2013

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Step Action

9 The Point Selection form appears, as shown below.

Select Point 11_TI20 DACA, as indicated below.

Select parameter PV from the Parameters of 11_TI20.DACA list.

Click OK to close the Point Selection form.

10 11_TI20.DACA.PV appears in the History Configuration table.

• Select the FAST and STD history checkboxes.

ATTENTION

From Experion R410, for CDA points, Exception History can be configured using Control Builder and Station.

On selection of a String data type, only the Exception History type is available for selection from the Control Builder.

Page 47: Topic: Data Acquisition Control Module - TraCorphw.server.tracorp.com/courses/ac/EXP2001R410B/... · Instructions for: Data Acquisition Control Module Introduction This portion of

Data Acquisition Control Module

Configure the Data Acquisition Control Module

9/18/2013 Copyright © 2013 Honeywell International Inc. 47

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Step Action

11 Click the Server Displays tab and enter the following information to add the CM to a Trend and Group.

ATTENTION

You can also do this by entering the trend/group number and the pen/position, in the trend and group window, after building the control strategy in the CM.

12 Click OK to close the Control Module Properties window.

13 Save the CM 11_TI20 and close the chart window.

• This CM now appears with the symbol “ “indicating that the CM has not yet been loaded to the controller.

Page 48: Topic: Data Acquisition Control Module - TraCorphw.server.tracorp.com/courses/ac/EXP2001R410B/... · Instructions for: Data Acquisition Control Module Introduction This portion of

Data Acquisition Control Module

Configure the Data Acquisition Control Module

48 Copyright © 2013 Honeywell International Inc. 9/18/2013

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Step Action

14 Download this CM.

• Select 11_TI20.

• Click the button on the toolbar.

• Select Continue in the Load Box.

15 Select the ‘Automatically change ALL control elements to the state selected in “Post Load State” after load is completed’. The Post Load State is selected as ACTIVE by default.

• Click the OK button.

Page 49: Topic: Data Acquisition Control Module - TraCorphw.server.tracorp.com/courses/ac/EXP2001R410B/... · Instructions for: Data Acquisition Control Module Introduction This portion of

Data Acquisition Control Module

Configure the Data Acquisition Control Module

9/18/2013 Copyright © 2013 Honeywell International Inc. 49

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Step Action

16 A Load dialog box appears, as shown below, that automatically closes on a successful download.

ATTENTION

In the Project window, notice there is no “ ” sign in front of 11_TI20.

17 Click the Monitoring Tree window to verify that 11_TI20 is green, which means it is active.

1 If active (green), skip the next step.

2 If inactive (blue), perform the next step.

Page 50: Topic: Data Acquisition Control Module - TraCorphw.server.tracorp.com/courses/ac/EXP2001R410B/... · Instructions for: Data Acquisition Control Module Introduction This portion of

Data Acquisition Control Module

Configure the Data Acquisition Control Module

50 Copyright © 2013 Honeywell International Inc. 9/18/2013

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Step Action

18 Activate the CM. To activate a CM, right-click and select “Activate > Selected Items” or select 11_TI20, and click the Toggle State button on the toolbar.

The following screen appears.

Click Yes.

Notice 11_TI20 is now green.

19 Open Station, if not already open.

Page 51: Topic: Data Acquisition Control Module - TraCorphw.server.tracorp.com/courses/ac/EXP2001R410B/... · Instructions for: Data Acquisition Control Module Introduction This portion of

Data Acquisition Control Module

Configure the Data Acquisition Control Module

9/18/2013 Copyright © 2013 Honeywell International Inc. 51

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Step Action

20 Call up Debutanizer_123 on Station, as shown below.

The 11_TI20 point is at the bottom of the T-100 tower.

In this example, the temperature shown is approximately 105.00 DegC.

If you click the parameter block in your graphic, point parameter details appear in the message zone: E20ESV##_Server:11_TI20.DACA.PV with real-time value and the CM description.

ATTENTION

If you do not see the value for 11_TI20 varying, then close and open the Tie_back_new.xls file.

Use this file for simulation purpose.

E20ESV##_Server is the server alias name defined for this class. In real environment this will be a different name specific to your site requirements.

The ## is the student number.

Page 52: Topic: Data Acquisition Control Module - TraCorphw.server.tracorp.com/courses/ac/EXP2001R410B/... · Instructions for: Data Acquisition Control Module Introduction This portion of

Data Acquisition Control Module

Configure the Data Acquisition Control Module

52 Copyright © 2013 Honeywell International Inc. 9/18/2013

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Step Action

21

ATTENTION

The actual value may be different on your screen.

If the 11_TI20 CM is inactive, the value in the parameter box is NaN.

If the point is not loaded and you select the parameter block, the parameter box will appear as follows.

Page 53: Topic: Data Acquisition Control Module - TraCorphw.server.tracorp.com/courses/ac/EXP2001R410B/... · Instructions for: Data Acquisition Control Module Introduction This portion of

Data Acquisition Control Module

Configure the Data Acquisition Control Module

9/18/2013 Copyright © 2013 Honeywell International Inc. 53

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Check for Alarm Debounce

Alarm Debounce functionality is introduced in R410. It avoids a false alarm generated by process disturbances. Here we will perform the steps to check ‘Alarm Debounce Functionality’.

Step Action

1 Note down the PV value of 11_TI20.

If PV < 20, Controller triggers an PV Low alarm.

TIP

Tie_back_new.xls calculates 11_TI20.PV range from 0 to 260.

Wait to change PV value to 0.

2 Call Alarm Summary on Station.

View Alarms

3 PV Low alarm for 11_TI20 is displays in Alarm Summary (If PV < 20).

Page 54: Topic: Data Acquisition Control Module - TraCorphw.server.tracorp.com/courses/ac/EXP2001R410B/... · Instructions for: Data Acquisition Control Module Introduction This portion of

Data Acquisition Control Module

Configure the Data Acquisition Control Module

54 Copyright © 2013 Honeywell International Inc. 9/18/2013

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Step Action

4 Select Alarm. Right click and select Acknowledge Alarm.

This acknowledges alarm in Alarm Summary.

5 Note that with a PV greater than 20, alarm still appears in Alarm Summary for 10 sec on Normal.

TIP

For PV Low Alarm, Off-Delay Timer is configured as 10 sec.

In the same way, you can check for PV High alarm. On-Delay Timer configured for PV High Alarm is of 10 sec.

Page 55: Topic: Data Acquisition Control Module - TraCorphw.server.tracorp.com/courses/ac/EXP2001R410B/... · Instructions for: Data Acquisition Control Module Introduction This portion of

Data Acquisition Control Module

Configure the Data Acquisition Control Module

9/18/2013 Copyright © 2013 Honeywell International Inc. 55

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Perform Load While Active

Step Action

1 Open Control Builder application if not already opened.

2 Go to Tools System Preferences.

Enable “Allow only active loadable parameter changes” option.

Click OK.

Page 56: Topic: Data Acquisition Control Module - TraCorphw.server.tracorp.com/courses/ac/EXP2001R410B/... · Instructions for: Data Acquisition Control Module Introduction This portion of

Data Acquisition Control Module

Configure the Data Acquisition Control Module

56 Copyright © 2013 Honeywell International Inc. 9/18/2013

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Step Action

3 Click OK to Control Builder window.

4 Close Control Builder and re-open it.

5 Select ‘Project window’.

Select 11_TI20, Right click and Select ‘Module Properties’.

Select the property which have “ # ” sign with its name, e.g. Parent Asset.

Parameters with “#” sigh are the minor parameters which can be loaded to the controller in Run Mode; it will not disturb the process, so it can be loaded while the process is running.

6 Change Parent Asset from Level_C11 to TANK_C11.

Page 57: Topic: Data Acquisition Control Module - TraCorphw.server.tracorp.com/courses/ac/EXP2001R410B/... · Instructions for: Data Acquisition Control Module Introduction This portion of

Data Acquisition Control Module

Configure the Data Acquisition Control Module

9/18/2013 Copyright © 2013 Honeywell International Inc. 57

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Step Action

7 Click OK. Save and Close 11_TI20.

8 Now with the 11_TI20, A Green Downward Arrow appears.

9 Right-click on 11_TI20 and Select “Load Value While Active”.

10 Load value while Active” window open.

Click Continue.

Page 58: Topic: Data Acquisition Control Module - TraCorphw.server.tracorp.com/courses/ac/EXP2001R410B/... · Instructions for: Data Acquisition Control Module Introduction This portion of

Data Acquisition Control Module

Configure the Data Acquisition Control Module

58 Copyright © 2013 Honeywell International Inc. 9/18/2013

HPS Automation College written permission required to distribute

Honeywell Confidential and Proprietary

Step Action

11 “Load value while Active” confirmation.

Click Continue.

12 After Loading the green arrows disappears.

13 Open Module Properties of 11_TI20 in Monitoring mode. You can see the new Parent Asset is assigned to 11_TI20.

TIP

You can online load all the parameters shown with ‘#’ sign.