topic 8 fault calculation methods

Upload: raja-nurulhani

Post on 05-Apr-2018

251 views

Category:

Documents


1 download

TRANSCRIPT

  • 7/31/2019 Topic 8 Fault Calculation Methods

    1/13

    Topic 8: Fault Calculation

    Methods

    Problems in electrical circuits

    Open circuits Supply is disconnected to the load

    Short circuits Supply bypasses the load

    Very dangerous Lead to high fault currents

    Disastrous effects on equipment

    Thermal heating

    Electromechanical effects

    Fires

    Protection must detect abnormal fault currents Isolate in a time consistent with short circuit fault

    current

    Therefore fault current must be accurately predictedfor a fault in any location

  • 7/31/2019 Topic 8 Fault Calculation Methods

    2/13

  • 7/31/2019 Topic 8 Fault Calculation Methods

    3/13

    Types of short-circuits and their currents

    Balanced three-

    phase short-circuit

    Line-to-line short-

    circuit

    Types of short-circuits and their currents

    Line-to-line short-circuit

    with earth connection

    Line-to-earth short-circuit

  • 7/31/2019 Topic 8 Fault Calculation Methods

    4/13

    Comparison of magnitude of short-

    circuit currents

    Fault type Magnitude

    3-phase (most severe) (E/Z) x multiplier

    Line-to-line 0.87 x 3-phase fault

    Line-to-ground(usually least severe)

    Depends on systemgrounding

    Per Unit System

    Fault calculations must be done using per-unit system

    Vpu = V/VB VB is the voltage base

    Ipu = I/IB IB is the current base

    Spu = S/SB SB is the kVA base

    Zpu = Z/ZB ZB is the impedance base

    Usually base values VB and SB are specified

    IB and and ZB are determined from VB and SBIB = SB/VBZB = VB

    2/SB = VB/IB VB is taken as the rated system voltage

    SB is arbitrarily specified (100/10/1 MVA)

    Rating of transformer is normally used as the base

  • 7/31/2019 Topic 8 Fault Calculation Methods

    5/13

    Use of pu system

    For balanced symmetrical 3-phase faults

    Fault calculation must be done on single phase

    basis

    Use the pu phase impedance of one-line

    diagram

    Care must be taken to ensure the proper phase kVA

    and voltage levels are used in the calculation

    IB = (SB/3)/(VB/3) = SB/ (3 VB)

    ZB = [(VB/3)2]/(SB/3) = VB2/SB

    Where VB is the line voltage

    And SB is the three phase kVA value

    Change of base

    Fault calculations must include all significant components ofimpedance

    Must be expressed in pu terms using the appropriate base value

    Sometimes may need to be changed if they are expressed usingdifferent bases, e.g transformer impedances

    Zpu = Z/ZB = Z(SB/VB2)

    For change of kVA base (SB): Zpu(new) = Zpu(old)[SB(new)/SB(old)]

    Change of voltage base (VB): Zpu(new) = Zpu(old)[VB2

    (old)/VB2

    (new)]

    Change of both kVA and voltage bases at the same time:

    Zpu(new) = Zpu(old)[SB(new)/SB(old)][VB2

    (old)/VB2

    (new)]

    Impedances of transformers, motors, etc will be given in puterms based on their rated voltage and power levels

    Impedances of cables, overhead lines, etc will be given in ohmsand must be converted to pu with the appropriate base

  • 7/31/2019 Topic 8 Fault Calculation Methods

    6/13

    Fault Calculation Effects and Requirements

    Fault levels in a power system must be calculated atthe design stage to determine:

    Overcurrent protection

    Peak electromagnetic forces

    Thermal heating effects

    Maximum and minimum fault current

    Time discrimination requirements of protection

    Touch voltages on earth objects

    Sources of fault currents

    Electrical utility supply system

    In-house generation systems operating at time of fault

    Motors operating within the system at time of fault

    Any electrical storage elements in the system, e.g.capacitors

    Fault current contribution

    Static equipment are not sources of fault

    current

    Inverters, converters, transformers, induction

    heaters

    Capacitors and battery operated UPS are low-

    level sources of fault current

    Supply utility and in-house generation providesconstant fault current (stiff source)

    Motors will provide decaying fault current as

    their magnetic excitation fields collapse

  • 7/31/2019 Topic 8 Fault Calculation Methods

    7/13

    Fault current contribution from motors

    Time-varying impedance

    Sub-transient reactance (Xd) effective impedance in

    first few cycles

    Transient reactance (Xd) - effective impedance in 2 20

    cycles

    Synchronous reactance (Xs) impedance in steady state

    Synchronous reactance is generally not used since

    protection will operate before it comes into effect

    For synchronous motors, only the sub-transient and

    transient reactance are normally used

    For induction motors, only the sub-transient reactance is

    used

    DC Offset

    Must be included in fault calculations,

    especially LV systems

    DC offset can increase initial current levels

    substantially

    Magnitude of DC offset depends on X/R ratio

    of fault circuit

  • 7/31/2019 Topic 8 Fault Calculation Methods

    8/13

    Short-circuit current waveforms

    (far from generator short-circuit)

    Short-circuit current waveforms

    (near to generator short-circuit)

  • 7/31/2019 Topic 8 Fault Calculation Methods

    9/13

    Short-circuit current waveforms from

    different sources

    Utility

    Generator

    Synchronous

    motor

    Induction

    motor

    Symmetrical short-circuit current from 3 sources(utility, motors and generator combined into a total)

  • 7/31/2019 Topic 8 Fault Calculation Methods

    10/13

    Fault calculation methodsTo simplify calculations, the following assumptions are made:

    Fault is balanced 3-phase symmetrical

    Pu impedances are pure reactances for MV

    systems, any resistance is neglected

    For LV systems where resistance is important,

    impedance is [Z] = (R2 + X2)1/2

    All significant component impedances are

    included

    The fault itself has zero impedance (i.e. boltedshort circuit)

    Fault calculation methods

    Earth circuit impedance is neglected

    balanced 3-phase nature of fault eliminates earth

    impedance

    Rated voltage is used as the voltage base

    X/R for all equipment

    used to calculate level of DC offset multiplier

    after symmetrical fault current has been calculated

    Convert all impedances to pu values Use these to draw single line diagram of fault circuit

    All possible sources modeled as ideal voltage source

    With appropriate source impedance value connected

  • 7/31/2019 Topic 8 Fault Calculation Methods

    11/13

    Fault calculation methods

    Circuit simplification

    Impedance diagram reduced to single pu

    impedance Zf

    Connected to true earth and to ideal voltage

    source

    Fault current (pu):

    If (pu) = Vpu/Zf(pu)

    = 1/Zf(pu) (since Vpu = 1) If= If(pu) . IB Amps

    Parameters for fault calculation

  • 7/31/2019 Topic 8 Fault Calculation Methods

    12/13

  • 7/31/2019 Topic 8 Fault Calculation Methods

    13/13