Roofing Membrane SystemRhepanol® fk

TechnicalManual

Edition 2004

Rhepanol® fk

Page 2: TM Rhepanol g

7/28/2019 TM Rhepanol g

http://slidepdf.com/reader/full/tm-rhepanol-g 2/73

Imprint

Roofing membrane system Rhepanol fk

Technical manual

Edition 2004

Editor:

FDT

FlachdachTechnologie

GmbH & Co. KG

Eisenbahnstraße 6 - 8D-68199 Mannheim

Tel +49 6 21-85 04-0

Fax +49 6 21-85 04-2 05

www.flachdachtec.de

Copyright 2004 by:

FDT

FlachdachTechnologieGmbH & Co. KG

This manual corresponds with the

FDT manufacturer application instructions

for designers and applicators in theFederal Republic of Germany.

It cannot, however, replace professional

knowledge.Every user is obliged to keep his

knowledge up to date!

Valid from January 2004.

Technical changes reserved.

Page 3: TM Rhepanol g

7/28/2019 TM Rhepanol g

http://slidepdf.com/reader/full/tm-rhepanol-g 3/73

Roofing membrane systemRhepanol® fk 3

Contents

Roofing membrane system Rhepanol fk

The system – an overview 5

Rhepanol fk, mechanically fastened with Gripfix system

Application techniques 11

Technical details 19

Rhepanol fk, loosely laid with ballast

Application techniques 30

Technical details 34

Rhepanol fk, bonded fixing

Application techniques 39

Technical details 44

Data sheets, product information, accessories

Data sheet Roofing membrane Rhepanol fk 57

Data sheet Vapour barrier fk 59

Data sheet Fire retardant layer fk 60Data sheet Protection layer TS fk 61

Data sheet Adhesive system Rhepanol adhesive 90 62

Data sheet Adhesive U 64

Accessories 66

Technical Approval

5

10

29

38

56

71

Page

Page 4: TM Rhepanol g

7/28/2019 TM Rhepanol g

http://slidepdf.com/reader/full/tm-rhepanol-g 4/73

4

The world of Rhepanol® fk

 allrounder winter world, Neuss/Germany

rocontrol,ren/Belgium

 Edinburghconference centre,United Kingdom

kswagennan/Poland 

 John Dewards Ltd.,United Destillers, Scotland/ United Kingdom

Canary Wharf, London/ United Kingdom

Page 5: TM Rhepanol g

7/28/2019 TM Rhepanol g

http://slidepdf.com/reader/full/tm-rhepanol-g 5/73

The system – an overview

Rhepanol® fk – advantages

Tried and tested long-term reliability, over50 years of experience with polyisobutylene

The oldest synthetic roofing membrane

made in Germany

With a unique self-sealing edge for reliable

and fast sealing of seamsFleece backing with extremely high tensile

strength

Made of polyisobutylene (PIB), therefore

compatible with bitumen

One roofing membrane for all applicationmethods

The only roofing membrane to be applied

with the Gripfix systemResistant to UV-radiation

Flexible at temperatures as low as – 60 °CFree of plasticizers

Application without open flame

No need for surface protection

Comprehensive warranty on materials

Ideal for refurbishment

The self-sealing edge system

The pre-fabricated self-sealing edge system is

different from conventional adhesive bonding.

Sealing of the seams is carried out by firmly joining homogenous materials. Immediately

after the self-sealing edge has been pressed tothe connecting membrane the seam is already

waterproof. Owing to the integrated self-

sealing edge, seams can be sealed withoutopen flame, hot air, solvent welding or addi-

tional adhesives, making application more

efficient and almost independent of weather

conditions.

The roofing membrane with a strong

character

 Industrially pre-fabricated  self-sealing edge for reliable and 

 fast sealing of  seams.

 It only takesthree steps:

 Rhepanol fkwith self-sealing 

edge system.

... roll out 

... roll on the edge ... sealed! ... clean the seam, pull off the protective strip

One,

two,

three,

sealed!

Application is incredibly easy and safe: Roll

out Rhepanol fk, clean the seam area, pull off

the protective strip and press down the edge –sealed! The same goes for all preformed details,

which are also equipped with the unique self-

sealing edge system.

Roofing membrane systemRhepanol® fk 5

Page 6: TM Rhepanol g

7/28/2019 TM Rhepanol g

http://slidepdf.com/reader/full/tm-rhepanol-g 6/73

Rhepanol® fk – advantages

If you want more detailed information on thelong-term qualities of Rhepanol, we are able to

provide you with the extended test reports.

Continental AG, Hanover:Workshop hall 

with more than10,000 m 2 of roof 

 area, covered with Rhepanol fk grey,

bonded fixing.

 Schade KG, Plettenberg: Practical testing 

 after 14 yearsof weather 

exposure has proven out-

 standing water- proofing quality and ageing 

resistance of  Rhepanol fk.

Preformed details with self-sealing edge

system:

External cornerInternal cornerUniversal roof light corner

Collars

Cover tape for cross joints and flashings

For further technical information Rhepanol fkroofing membranes please see product data

sheets on p. 56 ff.

Long-term reliability – signed and sealed

Regular quality tests of Rhepanol fk are carried

out by in-house material testing as well as byindependent test institutes.

Additionally, Rhepanol roofs that have been

established many years are opened and tested.The result: Rhepanol fk surpasses all require-

ments set up for new roofing membranes

according to DIN 16731. This has been proven

in a survey carried out by the independent

Material Testing Institute Darmstadt on theroof of the workshop hall of Schade KG in

Plettenberg.

Roofing membrane systemRhepanol® fk The system – an overview6

Page 7: TM Rhepanol g

7/28/2019 TM Rhepanol g

http://slidepdf.com/reader/full/tm-rhepanol-g 7/73

Official seal of approval for Rhepanol fk

Rhepanol fk is known as “the long-term reliable

roofing membrane”. There are many reasons forthat: FDT does not focus on short-term profit,

but on high-quality and durable products.Therefore we have established stringent quality

control requirements that eliminate sources of

error. This in-house quality assurance system for

the whole company has been certified according

to DIN EN ISO 9001, the world’s most strictquality standard, and is

constantly monitored by

TÜV CERT. We pay the

same attention to materials

control carried out during

production as to the qualityassurance measures and the highly mechanized

production.

Control measures (amongst others):

No blisters or cracks

Thickness, width

Weight per square metre

Maximum tensile force, elongation atmaximum tensile force

Dimensional stability after storage at + 80 °C

Bending at low temperatures

In addition, Rhepanol fk is permanently moni-tored by an officially approved testing institute.

In 1980 we signed a quality control agreement

with the State Material Testing Institute

Darmstadt, plastics department. The regular

controls carried out by the Material TestingInstitute not only include production, but also

external stores and building sites. The quality

control of an independent testing institute

provides additional security when waterproofing

flat roofs with Rhepanol fk.

Warranty on materials

Warranty certificates are avail-

able for all roofing membranessupplied by FDT. FDT offers

comprehensive warranty, secur-ing everybody’s investments in

new buildings or refurbishment.

Quality assurance

Testing according to DIN EN ISO

9001. We shall be glad to send

you a copy of the TÜV certificate

on request.

Ecology

Since 1990, Rhepanol fk has

been subjected to a life cycle

assessment, carried out by therenowned and independent

Batelle-Institute. It confirmed

the outstanding ecological

profile of Rhepanol fk during

its whole life cycle.Further technical information is

available on application.

Quality control

Oualitätsmanagement

nach DIN EN ISO 9001

70 100 M 543

Roofing membrane systemRhepanol® fkThe system – an overview 7

Page 8: TM Rhepanol g

7/28/2019 TM Rhepanol g

http://slidepdf.com/reader/full/tm-rhepanol-g 8/73

Roofing membrane systemRhepanol® fk The system – an overview

Rhepanol® fk – overview

Application methods and roof build-ups

Non-traffic roof areas

   N  o  n  -  v  e  n   t   i   l  a   t  e   d  r  o  o   f   (  w  a  r  m   r

  o  o   f   )

   V  e  n   t   i   l  a   t  e   d  r  o  o   f   (  c  o   l   d  r  o  o   f   )

Supporting deckRoof type Slope up to 20°

Pofiled steel decking

Reinforced concrete

Lightweight concrete

Timber board cladding

Chipboards/veneer boards

Rhepanol fk, mechanically fastenedwith Gripfix system

Rhepanol fk, mechanically fastenedwith Gripfix system

Rhepanol fk, mechanically fastenedwith Gripfix system

Rhepanol fk, mechanically fastenedwith Gripfix system

Rhepanol fk, mechanically fastenedwith Gripfix system

Rhepanol fk, mechanically fastenedwith Gripfix system

8

Page 9: TM Rhepanol g

7/28/2019 TM Rhepanol g

http://slidepdf.com/reader/full/tm-rhepanol-g 9/73

Roofing membrane systemRhepanol® fkThe system – an overview 9

Rhepanol® fk – overview

Application methods and roof build-ups

Used roofs

Rhepanol fkbonded fixing

Rhepanol fkbonded fixing

Rhepanol fkloose laying with ballast*

Rhepanol fkloose laying with ballast*

Rhepanol fkloose laying with ballast*

Rhepanol fkloose laying with ballast*

Rhepanol fkloose laying with ballast*

Rhepanol fkloose laying with ballast*

Rhepanol fkloose laying with ballast*

Rhepanol fkbonded fixing

Rhepanol fkbonded fixing

Rhepanol fkbonded fixing

* For waterproofing roofs for vehicular traffic and green roofs we recommendour roofing system Rhenofol or Rhenofol RG system, we recommend a max. roof slope of 3°.

   T  e  r  r  a  c  e  s ,   b  a   l  c  o  n   i  e  s

Page 10: TM Rhepanol g

7/28/2019 TM Rhepanol g

http://slidepdf.com/reader/full/tm-rhepanol-g 10/73

Rhepanol® fk

mechanically fastened

with Gripfix system

10

 RABO-bank, Huizen/  Netherland 

Volkswagen, Poznan/  Poland 

 Swimming bath, Breistroff/ 

 France

Velodrome Kaarst/Germany

Page 11: TM Rhepanol g

7/28/2019 TM Rhepanol g

http://slidepdf.com/reader/full/tm-rhepanol-g 11/73

Rhepanol® fkmechanically fastened with Gripfix systemApplication techniques 11

Safety and functional efficiency,

supporting construction

Safety and functional efficiency

With mechanical fastening the roof sealing

is separated from the lower layers and com-

ponents across the complete area. Movements

of these layers and components can thereforenot pass on stresses to the sealing, which is

significant for the prevention of damage,

especially on lightweight roofs. The roofing

membrane Rhepanol fk is rolled onto mechani-

cally fastened Gripfix strips, providing optimalwind load distribution and securing the

membrane permanently to the roof.

The membrane seams run perpendicular to theGripfix strips and thus are not affected by wind

uplift forces.

The integrated highly tear-resistant synthetic

fleece of Rhepanol fk allows diffusion of anyretained moisture.

The supporting deck structure has to meet

the requirements with regard to load-bearingcapacity, deflection, anchorage and drainage.

Substrates for application must be free

of open cracks, concrete, rough and sharpprojections.

Joints have to be formed according to

constructional requirements, as their width

or movement may impede the functional

efficiency of the roof seal.

Clean, dry and even roof surfaces.

If Rhepanol fk is directly laid on concrete

decks/screed allow the concrete/screed to setfor at least 28 days.

The effect of air escaping from the building

at the roof perimeter and at roof penetra-

tions must be prevented. Therefore theseareas have to be made airtight. In the case

of profiled steel decking, seal around all

openings and perimeters.

For compatibility reasons, timber boardcladding, chipboards and similar may be

treated only with salt-based wood preserva-

tives. Oil or solvent based impregnation

agents must not be used.

National standards and regulations must be

observed.

The mechanical 

 fastening of  Rhepanol fk with

Gripfix system

ensures secure, fast and effective

laying.

Rhepanol fk is compatible with bitumen and

can be applied without additional separation

layers directly on to old bituminous sheets.

The integrated synthetic fleece protects themembrane against movement originating

from the substrate.

Application instructions

Supporting construction

Page 12: TM Rhepanol g

7/28/2019 TM Rhepanol g

http://slidepdf.com/reader/full/tm-rhepanol-g 12/73

Vapour control layer,

thermal insulation layer

For non air-conditioned rooms (e.g. living

rooms and offices or similar rooms withoutsuspended ceiling): vapour barrier fk

(ethylene).

In the case of lightweight concrete support-

ing decks with correctly calculated thermalinsulation, you may leave out a vapour

control layer, if the room temperature stays

below 20 °C and the relative air humidity

inside the room will not exceed 65 %. In

case of doubt, we recommend a calculationof the building physics in order to identify the

diffusion characteristics of the roof build-up.

With lightweight steel deckings, we also

recommend in principle the installation of aseparate vapour control layer, which should

be formed as an air barrier according to the

provisions of the Thermal Insulation

Regulation.

The vapour barrier fk is applied with a seamoverlap of 10 cm, with the seams being

sealed with connection or seam tape. The

vapour barrier must be taken up and flashed

at connections and cappings; at roof pene-trations it must be flashed.

For rooms with high air condition loads:

In case of air-conditioned rooms and rooms

with high air condition loads, as well as

high pressure rooms, there should be nomechanical fastening through the vapour

barrier. In these cases please consult our

experts to identify the right layer build-up

and application method.

National standards and regulations must be

observed.

Vapour control layer

In the case of non-ventilated roofs, we rec-

ommend the following vapour control layers:

Thermal insulation layer

When designing the thermal insulation layer on

steel profile supporting decks, attention mustbe given to load bearing capacity.

As materials for thermal insulation layers we

recommend:

For roof slopes up to 20°: large-sized

insulation boards made of quality assured

rigid polyurethene or rigid polystyrene foam

with rebated edge, size 1.20 x 1.20 m or1.20 x 1.00 m.

On top of the insulation boards, for fire

protection reasons, the application of a fire

protection layer – a specially coated wovenglass cloth – will be necessary.

Compressed mineral fibre insulation may

also be used.

Folding insulation boards or rigid poly-styrene foam boards with backing. For

fire protection reasons, bituminous sheets

with an integrated glass fleece or fabric

≥ 60 g/m2 may be necessary as a lining.

Use linings with a PE foil or fleece facing.

Large-sized non-flammable mineral fibreboards. Because of better suitability for

mechanical fastening we recommend

boards with a greater resistance to pointloads (min. 500 N at 5 mm deformation)

and a higher compression strength (com-

pressive strain at 10 % compression set

min. 0.06 N/mm2).

Small-sized insulation boards can be used,

provided they can be properly fastened.

National standards and regulations must be

observed.

Rhepanol® fkmechanically fastened with Gripfix system Application techniques12

Page 13: TM Rhepanol g

7/28/2019 TM Rhepanol g

http://slidepdf.com/reader/full/tm-rhepanol-g 13/73

Themal insulation layer,

Rhepanol

®

fk, mechanically fastened withGripfix system

Insulation boards or board sections that are notsufficiently fixed with Gripfix must be secured

in a stable position with additional fasteners

(at least 2 fasteners/m2) prior to applying theroofing membrane.

Insulation materials that are not dimension-

ally stable and which buckle or bulge must

not be installed. Generally insulation boards

must be laid brick-bond pattern.

Rhepanol® fk, mechanically fastened withGripfix system

The Gripfix strips are placed according tothe wind uplift calculation and mechanically

fastened. The Gripfix strip spacing is variable

depending on the wind load requirements.

The roofing membrane Rhepanol fk is thenloosely laid with a seam overlap of 5°

perpendicular to the Gripfix strips. The grip

is achieved by thoroughly rolling the roofing

membrane Rhepanol fk to the Gripfix strip.

The membrane width is always 1.05 m.Depending on the substrate a variety of

different fasteners may be used.

 System sketch Rhepanol fkGripfix systemwith fire retarding layer fk (for poly- styrene insulation).

 Rhepanol fk

Gripfix stripmechanically fastened 

 Fire retarding layer fk

Thermal insulation

Vapour barrier fk

 Profiled steel decking,corrosion protected 

Rhepanol® fkmechanically fastened with Gripfix systemApplication techniques 13

Page 14: TM Rhepanol g

7/28/2019 TM Rhepanol g

http://slidepdf.com/reader/full/tm-rhepanol-g 14/73

Rhepanol® fkmechanically fastened with Gripfix system Application techniques

I With the Gripfix system you must use only

the specially marked Rhepanol fk roofing

membranes.

I The max. wind force (including safety

factor 1.5) per m Gripfix strip is 1.5 kN.

The design load is max. 0.5 kN/fastener.

Instructions of the fastener manufacturer mustbe observed.

At building heights over 20 m and in special

cases (e.g. airplane hangars, buildings near the

coast, extreme exposure) each characteristic ofthe project location and special conditions must

be taken into account.

On request, computer-based project specific cal-

culations of the necessary amount of fastenersand Gripfix strip spacing are carried out, which

may result in lesser amounts of fasteners than

indicated in the table, provided the building has

a favourable geometry.

Rhepanol fk can be mechanically fastened on

roofs with any slope.

At slopes exceeding 20°, application should beagreed with our experts.

On profiled steel deckings and timber board

cladding the Gripfix strips must be arranged per-

pendicularly to the corrugations or boards toachieve the most regular wind load distribution

possible into the supporting deck.

At all flashings and cappings, roof lights etc.

the build-up must be specially secured bycircumferential rows of fasteners or Gripfix strips

(min. 4 fasteners/m).

Note:

I Max. spacing of Gripfix strips see table above.

I Fastening spacing on the Gripfix strip min.

15 cm, max. 60 cm.

I Fastener spacing on the same corrugation at

profiled steel deckings must not be less than

20 cm.

I Use only fasteners with washers of max. 5 cmwidth.

Roof areas

Inner area

Perimeter area

Corner area

Inner area

Perimeter area

Corner area

Number offasteners

3

4

6

4

6

10

Spacing of Gripfix strips (examples)2)

1.20 m 1.00 m 0.80 m 0.60 m 0.40 m

max. spacing on the Gripfix strip (cm)28 33 – – –

– 25 31 – –

– – – 28 42

– 25 31 42 –

– – – 28 42

– – – – 25

Height of eavesabove ground1)

Fasteners/m2 and spacing on the Gripfix system

Maximum Gripfix strip spacing

Building height Inner area Perimeter area Corner area

up to 12 m 1.20 m 1.00 m 0.80 m12 – 20 m 1.00 m 1.00 m 0.60 m

1) Not for tower-style detached buildings. Not for exposed positions.2) Since the Gripfix strip spacing is continuously adjustable, only examples can be given.

Fasteners / fastener spacing

0 – 8 m

8 – 20 m

14

Page 15: TM Rhepanol g

7/28/2019 TM Rhepanol g

http://slidepdf.com/reader/full/tm-rhepanol-g 15/73

Rhepanol® fkmechanically fastened with Gripfix systemApplication techniques 15

Fastening example

Corner area a/16

Corner area

   C  o  r  n  e  r  a  r  e  a  a

   /   1   6

   0 .   2

   0  m

Fastening at component edges at a distance of max. 0.25 m

Perimeterarea

Inner area

Membrane edge

Mechanically fastened Gripfix strip

Perimeter area a/8

   P  e  r   i  m  e

   t  e  r  a  r  e  a  a

   /   8

  =  c  o  v  e  r   i  n  g  w

   i   d   t   h  o

   f   t   h  e  r  o  o

   f   i  n  g  m  e  m

   b  r  a  n  e

min. width 1.00 m

  m   i  n

 .  w

   i   d   t   h   1

 .   0   0  m

   0 .   2

   0  m

   0 .   4

   0  m

   1 .   0

   0  m

1.00 m

Page 16: TM Rhepanol g

7/28/2019 TM Rhepanol g

http://slidepdf.com/reader/full/tm-rhepanol-g 16/73

Rhepanol® fkmechanically fastened with Gripfix system Application techniques

Flashings and cappings

All flashings and cappings are carried out with

Rhepanol fk flashing strips.

If the connecting membrane is bonded, then atflashing heights over 20 cm a full-size adhesive

bond is necessary. Valley areas are left unbonded

at a width of 20 cm to allow movement com-pensation. If the connecting membrane is

mechanically fastened with Gripfix strips the fol-

lowing spacing must be observed (s. also sketch):

– Distance of the first Gripfix strip from the

internal corner of the parapet max. 10 cm– Spacing between the Gripfix strips or distance

between Gripfix strip and upper capping max.

50 cm.

With wall flashings, the upper edge of theRhepanol fk roofing membrane is pressed to

the substrate with rigid wall connection profiles

such as “Classic” and additionally secured with

sealant A or S. The two-part FDT roof edgetrims ensure flexible, yet windproof capping of

the roof perimeter. Forming of flashings and

cappings is identical for all application methods.

You will find details on this topic in the drawings

“Technical details”.

Additional requirements for roofrefurbishment:

I In the case of uneven substrates, protection

layers are necessary. Rigid polystyrene foam

insulation boards or sheets can be recom-

mended.

I The strength of the supporting deck is

crucial for the anchoring of the fastening

elements. If there is doubt about the

strength, e.g. of old pumice stone orlightweight concrete panels, pullout tests

will be necessary to define the amount offasteners depending on the object.

 Sketch Parapet flashing/ capping with

Gripfix strips.

   m   a   x .

   5   0   c   m

   m   a   x .

   1   0   c   m

Gripfix strip

Gripfix strip

16

Page 17: TM Rhepanol g

7/28/2019 TM Rhepanol g

http://slidepdf.com/reader/full/tm-rhepanol-g 17/73

Rhepanol® fkmechanically fastened with Gripfix systemApplication techniques 17

ᕃ Lightweight concrete

ᕄ Gripfix strip, mechanically fastened

ᕅ Rhepanol fk, laid perpendicularly to the

Gripfix strips

Examples of layer build-ups

Non-ventilated roof (warm roof)

ᕃ Profiled steel decking

ᕄ Vapour barrier fk

ᕅ Mineral fibre boards

ᕆ Gripfix strip, mechanically fastened,

laid perpendicularly to the corrugations

ᕇ Rhepanol fk, laid perpendicularly to the

Gripfix strips

ᕃ Profiled steel decking

ᕄ Vapour barrier fk

ᕅ Thermal insulation layer

ᕆ Fire retarding layer fk

ᕇ Gripfix strip, mechanically fastened,

laid perpendicularly to the corrugations

ᕈ Rhepanol fk, laid perpendicularly to the

Gripfix strips

Layer build-ups

ᕇᕅ

ᕈᕇ

ᕆᕅ

Page 18: TM Rhepanol g

7/28/2019 TM Rhepanol g

http://slidepdf.com/reader/full/tm-rhepanol-g 18/73

Rhepanol® fkmechanically fastened with Gripfix system Application techniques

Layer build-ups

Examples of layer build-ups

Ventilated roof (cold roof)

ᕃ Timber board cladding*ᕄ Gripfix strip, mechanically fastened,laid perpendicularly to the boards

ᕅ Rhepanol fk, laid perpendicularly to

the Gripfix strips

ᕃ Chipboards*

ᕄ Gripfix strip, mechanically fastened

ᕅ Rhepanol fk, laid perpendicularly to

the Gripfix strips

18

* Note: All sheet timber products must be CE marked (UK only).

Page 19: TM Rhepanol g

7/28/2019 TM Rhepanol g

http://slidepdf.com/reader/full/tm-rhepanol-g 19/73

Rhepanol® fkmechanically fastened with Gripfix systemTechnical details

Parapet

Non ventilated roof

19

Scale 1:5

ᕃ Galvanized profiled Steel Decking

ᕄ Steel Angle

ᕅ Vapour Control Layer

ᕆ Insulation to Specification

ᕇ Fire retarding Fleece (for use only with

polystyrene Insulation, mechanically fixed)

ᕈ Rhepanol fk mechanically fixed

with Gripfixᕉ Linear Perimeter Fixing

ᕊ Sealing Tape for Vapour Control Layer

ᕋ Rhepanol fk-Flashing Strip

ᕍᕠ Rhepanol-Contact Adhesive No. 11

ᕍᕗ Continuous Steel Angle

ᕍᕘ Aluminium Foil

ᕍᕙ Sealing Tape

ᕍᕚ Capping

ᕍᕛ External Cladding Panel

ᕍᕜ Airtight Sealing Tape

Page 20: TM Rhepanol g

7/28/2019 TM Rhepanol g

http://slidepdf.com/reader/full/tm-rhepanol-g 20/73

Rhepanol® fkmechanically fastened with Gripfix system Technical details

Parapet

Non ventilated roof

20

Scale 1:5

ᕃ Galvanised profiled Steel Decking

ᕄ Steel Angle

ᕅ Vapour Control Layer

ᕆ Insulation to Specification

ᕇ Fire retarding Fleece (for use only with

polystyrene Insulation, mechanically fixed)

ᕈ Rhepanol fk, mechanically fixed

with GripFix

ᕉ Linear Perimeter Fixing

ᕊ Sealing Tape for Vapour Control Layer

ᕋ Rhepanol fk-Flashing Strip

ᕍᕠ Rhepanol-Contact Adhesive No. 11

ᕍᕗ Continuous Steel Angle

ᕍᕘ Aluminium Foil

ᕍᕙ Sealing Tape

ᕍᕚ Capping

ᕍᕛ External Cladding

ᕍᕜ Airtight Sealing Tape

ᕍᕝ GripFix Strip

Page 21: TM Rhepanol g

7/28/2019 TM Rhepanol g

http://slidepdf.com/reader/full/tm-rhepanol-g 21/73

Rhepanol® fkmechanically fastened with Gripfix systemTechnical details

Parapet with Insulation Fillet

Non ventilated roof

21

ᕃ Galvanized profiled Steel Decking

ᕄ Thermal Insulation

ᕅ Steel Angle

ᕆ Vapour Control Layer

ᕇ Insulation to Specification

ᕈ Insulation Fillet

ᕉ Fire retarding Fleece (for use only with

polysyrene Insulation, mechanically fixed)

ᕊ Rhepanol fk, mechanically fixedwith GripFix

ᕋ Linear Perimeter Fixing

ᕍᕠ Sealing Tape for Vapour Control Layer

ᕍᕗ Rhepanol fk-Flashing Strip

ᕍᕘ Rhepanol-Contact Adhesive No. 11

ᕍᕙ Continuous Steel Angle

ᕍᕚ Aluminium Foil

ᕍᕛ Sealing Tape

ᕍᕜ Capping

ᕍᕝ External Cladding Panel

ᕍᕞ Airtight Sealing Tape

ᕍᕟ GripFix Strip

Scale 1:5

Page 22: TM Rhepanol g

7/28/2019 TM Rhepanol g

http://slidepdf.com/reader/full/tm-rhepanol-g 22/73

Rhepanol® fkmechanically fastened with Gripfix system Technical details

Parapet

Non ventilated roof

22

Scale 1:5

ᕃ Reinforced Concrete

ᕄ Vapour Control layer

ᕅ Insulation to Specification

ᕆ Fire retarding Fleece (for use only

with polystyrene Insulation,

mechanically fixed)

ᕇ Rhepanol fk, mechanically fixedwith GripFix

ᕈ Linear Perimeter Fixing

ᕉ Sealing Tape for Vapour Control Layer

ᕊ Insulation as Specification

ᕋ GripFix Strips

ᕍᕠ Rhepanol fk-Flashing Strip

ᕍᕗ Treated Timber Profile

ᕍᕘ Rhepanol-Contact Adhesive

No. 11

ᕍᕙ Roof Edge Trim

ᕍᕚ GripFix Strip

Page 23: TM Rhepanol g

7/28/2019 TM Rhepanol g

http://slidepdf.com/reader/full/tm-rhepanol-g 23/73

Rhepanol® fkmechanically fastened with Gripfix systemTechnical details

Wall connection

Non ventilated roof

23

Scale 1:5

ᕃ Galvanized profiled Steel Decking

ᕄ Thermal Insulation

ᕅ Steel Angle

ᕆ Vapour Control Layer

ᕇ Insulation to Specification

ᕈ Fire retarding Fleece (for use only, with

polystyrene Insulation, mechanically fixed)

ᕉ Linear Perimeter Fixing

ᕊ Rhepanol fk, mechanically fixedwith GripFix

ᕋ Sealing Tape for Vapour Control Layer

ᕍᕠ Rhepanol fk-Flashing Strip

ᕍᕗ Insulation as Specification

ᕍᕘ Z-Profile

ᕍᕙ Fixing Profile

ᕍᕚ Corrugated Steel Sheet

ᕍᕛ Insulation as Specification

ᕍᕜ Airtight Sealing Tape

ᕍᕝ Steel Structure

ᕍᕞ External Cladding

ᕍᕟ Corrugated Steel Sheet

Page 24: TM Rhepanol g

7/28/2019 TM Rhepanol g

http://slidepdf.com/reader/full/tm-rhepanol-g 24/73

Rhepanol® fkmechanically fastened with Gripfix system Technical details

Rooflight Connection

Non ventilated roof

24

-Scale 1:5

ᕃ Steel Angle

ᕄ Galvanized profiled Steel Decking

ᕅ Vapour Control Layer fk

ᕆ Thermal Insulation to Specification

ᕇ Rhepanol fk, mechanically fixed

with GripFix

ᕈ Fixing

ᕉ Thermal Insulation to Specification

ᕊ GripFix Strip

ᕋ Rhepanol fk-Flashing Strip

ᕍᕠ Rooflight

ᕍᕗ Rhepanol-Contact Adhesive No. 11

ᕍᕘ Rooflight Kerb

ᕍᕙ Sealing Tape for Vapour Control Layer

Page 25: TM Rhepanol g

7/28/2019 TM Rhepanol g

http://slidepdf.com/reader/full/tm-rhepanol-g 25/73

Rhepanol® fkmechanically fastened with Gripfix systemTechnical details

Rooflight Connection

Non ventilated roof

25

Scale 1:5

ᕃ Reinforced Concrete

ᕄ Vapour Control Layer

ᕅ Insulation to Specification

ᕆ Fire retarding Fleece (for use only with

polystyrene Insulation, mechanically fixed)

ᕇ Sealing Tape for Vapour Control Layer

ᕈ Rhepanol fk, mechanically fixed

with GripFix

ᕉ Linear Perimeter Fixing

ᕊ Rhepanol fk-Flashing Strip

ᕋ Rhepanol-Contact Adhesive No. 11

ᕍᕠ Rooflight Kerb

ᕍᕗ Render

ᕍᕘ Metal Lathing

ᕍᕙ GripFix Strip

Page 26: TM Rhepanol g

7/28/2019 TM Rhepanol g

http://slidepdf.com/reader/full/tm-rhepanol-g 26/73

Rhepanol® fkmechanically fastened with Gripfix system Technical details

Vent pipe

Non ventilated roof/Ventilated roof

26

Maßstab 1:5

ᕃ Steel angle

ᕄ Thermal Insulation Collar

ᕅ Galvanized profiled Steel Decking

ᕆ Fixing

ᕇ Vapour Control Layer

ᕈ Thermal Insulation to Specification

ᕉ Rhepanol fk, mechanically fixedwith GripFix

ᕊ Sealing tape for Vapour Control Layer

ᕋ GripFix Ring

ᕍᕠ Rhepanol Collar, Self welding Sealing

ᕍᕗ Vent Pipe Hood-removable

ᕍᕘ Vent Pipe

ᕍᕙ Sealing Skirt

ᕍᕚ Timber Deck

Page 27: TM Rhepanol g

7/28/2019 TM Rhepanol g

http://slidepdf.com/reader/full/tm-rhepanol-g 27/73

Rhepanol® fkmechanically fastened with Gripfix systemTechnical details

Cold roof ventilator

Ventilated roof

27

Scale 1:5

ᕃ Timber Deck

ᕄ Rhepanol fk

ᕅ GripFix Ring

ᕆ Rhepanol Collar, Self-welding / Sealing

ᕇ Fixing

ᕈ Cold Roof Ventilator Weather Cap

ᕉ Cold Roof Ventilator

ᕊ Sealing Skirt

Page 28: TM Rhepanol g

7/28/2019 TM Rhepanol g

http://slidepdf.com/reader/full/tm-rhepanol-g 28/73

Rhepanol® fkmechanically fastened with Gripfix system Technical details

Lightning Conductor Collar

Non ventilated roof

28

Scale 1:5

ᕃ Thermal Insulation to Specification

ᕄ Rhepanol fk mechanically fixed

ᕅ Fixing with Counter sunk Screw

ᕆ Rhepanol Collar

with Self-welding Sealing

ᕇ Cutting Edge for 50 mm Pipe

ᕈ Lightning Conductor Collar

ᕉ Jubilee Clip

ᕊ Lightning Conductor

Page 29: TM Rhepanol g

7/28/2019 TM Rhepanol g

http://slidepdf.com/reader/full/tm-rhepanol-g 29/73

Rhepanol® fk

loosely laid with ballast 29

 School centre, Stadthagen/ Germany

 Edinburgh conference centre/ United Kingdom

 Eurocontrol, Haren/  Belgium

Page 30: TM Rhepanol g

7/28/2019 TM Rhepanol g

http://slidepdf.com/reader/full/tm-rhepanol-g 30/73

Rhepanol® fkloosely laid with ballast Application techniques

Safety and functional efficiency

Because of loose laying, the roof covering is

separated from the other layers of the build-upacross the complete area. Movements andcracks in the supporting construction are not

transferred into the roof covering.

The ballast ensures the membrane remains

secure against wind uplift forces.

Rhepanol fk is compatible with bitumen and can

be applied without additional separation layers

directly on old bituminous sheets.

The integrated, highly tear-resistant synthetic

fleece of Rhepanol fk allows diffusion,ensuring reliable vapour pressure compensation.

Furthermore the fleece backing provides

protection against stresses originating fromthe substrate.

Application instructions

Supporting construction

I The supporting deck structure has to meet

the requirements with regard to load-bearing

capacity, deflection, anchorage and drainage.

I Clean, dry and even roof surfaces.

I If Rhepanol fk is directly laid on concrete

decks/screed allow the concrete/screed to

set for at least 28 days.

I Substrates for application must be free of

open cracks, rough concrete, sharp edges

and stones.

I Joints have to be formed according to

constructional requirements, as their width

or movement may impede the functionalefficiency of the roof sealing.

Safety and functional efficiency,

supporting construction,vapour control layer

I The roof slope should not exceed 3° to prevent

the ballast slipping off.

I An intrusion of air underneath the roofcovering at the roof perimeter and at roofpenetrations must be prevented. Therefore

these areas have to be made windtight.

I For compatibility reasons, timber board clad-

ding, chipboards and similar may be treatedonly with salt-based wood preservatives. Oil

or solvent based impregnation agents must

not be used.

I National standards and regulations must beobserved.

Vapour control layer

In the case of non-ventilated roofs, werecommend the following vapour control layers:

I For non air-conditioned rooms (e.g. living

rooms and offices or similar rooms without

suspended ceiling): vapour barrier fk (poly-ethylene) with µ x s = 120 m.

In the case of lightweight concrete supporting

decks with correctly calculated thermal insulation,

you may leave out a vapour control layer, if theroom temperature stays below 20 °C and the

relative air humidity inside the room will not

exceed 65 %.

The vapour barrier fk can be laid with differentoverlap: either 10 cm if sealing the seams with

connection or seam tape, or 20 cm loose overlap

(without seam connection in the area).

Preconditions:

– seamless solid deck and– dimensionally stable insulation material,

µ larger than 40, e.g. polystyrene,

– standard room air conditions.

30

Page 31: TM Rhepanol g

7/28/2019 TM Rhepanol g

http://slidepdf.com/reader/full/tm-rhepanol-g 31/73

Rhepanol® fkloosely laid with ballastApplication techniques 31

Thermal insulation layer,

Rhepanol

®

fk, loosely laid,ballast

I For rooms with high air condition loads (e.g.

swimming pools, air-conditioned rooms):

– aluminium compound foils,

– vapour control membrane with metal tapereinforcement, e.g. AL + V 60 S 4.

I National standards and regulations must be

observed.

Thermal insulation layer

You must bear in mind tread-fastness when

designing the thermal insulation layer on steel

profile supporting decks. Quality assured rigid

polystyrene foam boards with rebated edgeand a length of max. 1.25 m are especially

suitable materials for thermal insulation layers.

With roof areas for walking on, insulation

materials with higher compression strength,e.g. rigid polystyrene foam, must be used in

accordance with the expected loads.

Insulation materials that are not dimensionally

stable and which buckle or bulge must not beinstalled.

The insulation elements must be laid with

pressed joints in bond.

National standards and regulations must be

observed.

Rhepanol fk, loosely laid

Rhepanol fk roofing membrane is loosely laid

with a seam overlap of 5 cm. The membrane

seams are quickly sealed with the prefabricated

self-sealing edge almost independent from

weather conditions. At all flashings and cap-pings, built-in details etc. you will need linear

perimeter fixing with at least 4 fastening

elements/m.

Ballast

Immediately apply ballast on loosely laid

roofing membranes to secure its positionagainst wind uplift.

Suitable materials are:

I bulk gravel layers, min. 5 cm thick, washed

natural uncrushed stones, fraction 16/32.

I paving slabs in a fine gravel bed on a

protection layer.

If appropriate gravel is not available or thegravel is applied pneumatically, then, as under

paving slabs, you will need an additional pro-tection layer (e.g. synthetic fleece or protection

sheet TS fk). Under screed you will have

to apply the protection sheet TS fk.

PE layers and coarse rubber protective sheets

must have an underlying synthetic fleece layer.

Inner area

min. 5 cmbulk gravel

min. 5 cmbulk gravel

Perimeter area

min. 7 cmbulk gravel

min. 11 cmbulk gravel

Corner area

min. 7 cmbulk gravel

min. 11 cmbulk gravel

Height ofeavesabove ground

0 – 8 m

over 8–20 m

For ballast, the provisions of national wind load

standards must be observed.

At building heights over 20 m and for roofs

with high wind exposure (e.g. tower-style,

detached buildings, airplane hangars and

buildings near the coast) it is necessary to

define appropriate object-related measuresfor membrane position stability.

Examples for ballast

Page 32: TM Rhepanol g

7/28/2019 TM Rhepanol g

http://slidepdf.com/reader/full/tm-rhepanol-g 32/73

Rhepanol® fkloosely laid with ballast Application techniques

Flashings and cappings,

roof refurbishment,layer build-ups

Flashings and cappings

All flashings and cappings are carried out

with Rhepanol fk flashing strips. With flashingheights of over 20 cm, full-size adhesivebonding of the covering at the upstand is

necessary. Valley areas are left unbonded at a

width of 20 cm to allow movement compen-

sation. The upper edge of the Rhepanol fk

roofing membrane is pressed to the substratewith rigid wall connection profiles such as

“Classic” and additionally secured with sealant

A or S. The two-part FDT roof edge trims

ensure flexible, yet windproof capping of theroof perimeter.

The forming of flashings and cappings is iden-tical for all application methods. You will find

details on this topic in the drawings “Technicaldetails”.

Additional requirements for roof

refurbishment:

I Thoroughly sweep the roof area. Removeany blisters, projections and coarse rough-

ness.

I On rough substrates (such as pressed gravel),

a protection layer is necessary. We recom-mend polystyrene insulation boards, which

provide additional insulation at the same

time.

I Temporary storage of gravel must not exceedthe maximum load of the supporting deck.

I Soiled gravel must be cleaned (e.g. by

sieving). Otherwise, appropriate protection

layers such as synthetic fleece 300 g/m2

must be applied.

ᕃ Timber board cladding/derived timber products

ᕄ Rhepanol fk

ᕅ Bulk gravel, fraction 16/32

ᕃ Timber board cladding/derived timber products

ᕄ Rhepanol fk

ᕅ Protection layer, e.g. protection sheet TS fk

ᕆ Gravel layer, fraction 8/16, min. 3 cm thick

ᕇ Paving slabs, e.g. 50/50/5 cm

Examples of layer build-ups

Ventilated roof (cold roof)

32

Page 33: TM Rhepanol g

7/28/2019 TM Rhepanol g

http://slidepdf.com/reader/full/tm-rhepanol-g 33/73

Rhepanol® fkloosely laid with ballastApplication techniques 33

Layer build-ups

ᕃ Reinforced concrete

ᕄ Vapour barrier fk

ᕅ Thermal insulation layer

ᕆ Rhepanol fk

ᕇ Bulk gravel, fraction 16/32

ᕃ Reinforced concrete

ᕄ Vapour barrier fk

ᕅ Thermal insulation

ᕆ Rhepanol fk

ᕇ Protection layer, e.g. protection sheet TS fk

ᕈ Gravel layer, fraction 8/16, min. 3 cm thick

ᕉ Paving slabs, e.g. 50/50/5 cm

Examples of layer build-ups

Non-ventilated roof (warm roof)

ᕃ Lightweight concreteᕄ Rhepanol fk

ᕅ Bulk gravel

Page 34: TM Rhepanol g

7/28/2019 TM Rhepanol g

http://slidepdf.com/reader/full/tm-rhepanol-g 34/73

Technical details34Rhepanol® fkloosely laid with ballast

Parapet

Non ventilated roof

Scale 1:5

ᕃ Reinforced Concrete

ᕄ Vapour Control Layer fk

ᕅ Thermal Insulation to Specification

ᕆ Rhepanol fk loosley laid

ᕇ Min. 50 mm round washed Gravel

(20 – 40 mm)

ᕈ Linear Perimeter Fixing

ᕉ Sealing Tape for Vapour Control Layer

ᕊ Adhesive bond

ᕋ Thermal Insulation to Specification

ᕍᕠ Rhepanol fk-Flashing Strip

ᕍᕗ Rhepanol-Contact Adhesive No. 11

ᕍᕘ Treated Timber Profile

ᕍᕙ Capping

ᕍᕚ Cladding

Page 35: TM Rhepanol g

7/28/2019 TM Rhepanol g

http://slidepdf.com/reader/full/tm-rhepanol-g 35/73

Technical details 35Rhepanol® fkloosely laid with ballast

Parapet

Non ventilated roof

Scale 1:5

ᕃ Reinforced Concrete

ᕄ Vapour Control Layer fk

ᕅ Thermal Insulation to Specification

ᕆ Rhepanol fk loosley laid

ᕇ Min. 50 mm round washed Gravel

(20 – 40 mm)

ᕈ Linear Perimeter Fixing

ᕉ Adhesive bond

ᕊ Sealing Tape for Vapour Control Layer

ᕋ Thermal Insulation to Specification

ᕍᕠ Rhepanol fk Flashing Strip

ᕍᕗ Rhepanol-Contact Adhesive No. 11

ᕍᕘ Treated Timber Profile

ᕍᕙ FDT-Roof EdgeTrim

ᕍᕚ Cladding

Page 36: TM Rhepanol g

7/28/2019 TM Rhepanol g

http://slidepdf.com/reader/full/tm-rhepanol-g 36/73

Technical details36Rhepanol® fkloosely laid with ballast

Wall Connection

Non ventilated roof

Scale 1:5

ᕃ Reinforced Concrete

ᕄ Vapour Control Layer fk

ᕅ Thermal Insulation to Specification

ᕆ Rhepanol fk loosley laid

ᕇ Min. 50 mm round washed Gravel(20 – 40 mm)

ᕈ Linear Perimeter Fixing

ᕉ Rhepanol fk-Flashing Strip

ᕊ Sealing Tape for Vapour Control Layer

ᕋ Adhesive bond

ᕍᕠ Thermal Insulation to Specification

ᕍᕗ FDT-Wall Connection Profile

ᕍᕘ Flashing

ᕍᕙ Treated Timber Profile

ᕍᕚ FDT Acrylic Paste

ᕍᕛ Blockwork

Page 37: TM Rhepanol g

7/28/2019 TM Rhepanol g

http://slidepdf.com/reader/full/tm-rhepanol-g 37/73

Technical details 37Rhepanol® fkloosely laid with ballast

Rooflight connection

Non ventilated roof

Scale1:5

ᕃ Reinforced Concrete

ᕄ Vapour Control Layer fk

ᕅ Thermal Insulation to Specification

ᕆ Rhepanol fk loosley laid

ᕇ Sealing Tape for Vapour Control Layer

ᕈ Min. 50 mm round washed Gravel

(20 – 40 mm)

ᕉ Linear Perimeter Fixing

ᕊ Rhepanol fk-Flashing Strip

ᕋ Rhepanol-Contact Adhesive No. 11

ᕍᕠ Rooflight Upstand

ᕍᕗ Render Finish

ᕍᕘ Metal Lathing

Page 38: TM Rhepanol g

7/28/2019 TM Rhepanol g

http://slidepdf.com/reader/full/tm-rhepanol-g 38/73

Rhepanol® fk

bonded fixing

 John Dewards Ltd,United Distillers,

 Scotland/United Kingdom

Galerie Monnaie, Brussels/Belgium

38

Television tower, Hamburg/Germany

Canary Wharf, London/ United Kingdom

Page 39: TM Rhepanol g

7/28/2019 TM Rhepanol g

http://slidepdf.com/reader/full/tm-rhepanol-g 39/73

Rhepanol® fkbonded fixingApplication techniques 39

Safety and functional efficiency,

supporting structure,vapour control layer

Safety and functional efficiency

Bonding Rhepanol fk in stripes ensures maximum

possible mobility of the roofing membrane. Theintegrated, highly tear-resistant synthetic fleece

of Rhepanol fk allows diffusion, thus ensuring

reliable vapour pressure compensation and

secure bonding to the substrate. Rhepanol fk iscompatible with bitumen and can be bonded

without additional separation layers, directly to

old bituminous sheets. The integrated synthetic

fleece protects the membrane against stresses

originating from the substrate.

Application instructions

Supporting construction

I The supporting deck structure has to meet

the technical requirements, especially for load-

bearing capacity, deflection, anchorage and

drainage.

I Substrates for application must be free of open

cracks, rough concrete and sharp projections.

I Joints have to be formed according toconstructional requirements, as their width

or movement may impede the functional

efficiency of the roof sealing.

I An intrusion of air underneath the roofcovering at the roof perimeter and at roof

penetrations must be prevented. Therefore

these areas have to be made windtight.

I Clean, dry and even roof surfaces.

I If Rhepanol fk is directly laid on concrete

decks/screed allow the concrete/screed to

set for at least 28 days.

I The necessity for pre-coating to providereliable adhesion and dust bonding depends

on the substrate conditions.

– Lightweight concrete panels must always

be pre-coated, except when using Rhepanoladhesive 90.

I – It is not necessary to pre-coat coated profiled

steel deckings, except when welding onbituminous sheets (only as bonding agent).

I – National standards and regulations must be

observed.

Vapour control layer

As vapour control layers, in the case of non-

ventilated roofs, we recommend:

I For non air-conditioned rooms (e.g. living

rooms and offices or similar rooms without

suspended ceiling): Vapour control membrane.

In the case of lightweight concrete supporting

decks with correctly calculated thermal insula-tion, you may leave out a vapour control layer,

if the room temperature stays below 20 °C

und the relative air humidity inside the room

will not exceed 65 %.

I For rooms with high air condition loads

(e.g. swimming pools, air-conditioned rooms):

Vapour control membrane with metal tape,

glass fleece or woven glass cloth reinforce-

ment.

In case of doubt, we recommend a calculation

of the building physics in order to identify the

diffusion characteristics of the roof build-up.

Page 40: TM Rhepanol g

7/28/2019 TM Rhepanol g

http://slidepdf.com/reader/full/tm-rhepanol-g 40/73

Rhepanol® fkbonded fixing Application techniques

Vapour control layer,

thermal insulation layer

With lightweight steel deckings, we also recom-

mend in principle the installation of a separate

vapour control layer, which should be formed as

an air barrier according to the provisions of theThermal Insulation Regulation.

I The vapour barrier must be taken up and

flashed at connections and cappings, at roofpenetrations it must be flashed.

I National standards and regulations must be

observed.

Note:

For bonding the insulation layer with adhesive U,

use vapour control membranes without PEbacking or talcum coating.

Thermal insulation layer

The thermal insulation layer is to be designed in

accordance with the thermal protection require-ments.

As materials for thermal insulation layers we

recommend:

I Folding insulation boards or rigid polystyrenefoam boards with backing.

For fire protection reasons, bituminous sheetswith an integrated glass fleece or fabric

≥ 60 g/m2 may be necessary as a lining.

I Mineral fibre boards or sheets

With bonded application using mineral fibre

insulation material, the type of insulation

material and the adhesive/amount of ad-hesive needed is to be defined depending

on the object.

As a lining, use bituminous sheets without PEbacking.

Generally insulation boards must be laid brick-

bond pattern. Insulation materials that are

not dimensionally stable and which buckle orbulge, or insulation elements with insufficient

lining stability must not be installed.

Bonding of the thermal insulation layer ispreferably done with adhesive U, a one-com-ponent polyurethane adhesive.

For roof slopes exceeding 7°, additional sup-

porting measures are necessary to prevent the

materials slipping off while the adhesive iscuring.

For further information on the adhesive and its

application see data sheet adhesive U.

I National standards and regulations must be

observed.

Inner area

180 g/m2

200 g/m2

Perimeter andcorner area

250 g/m2

300 g/m2

Min. amount ofadhesive stripes/m3)

10

10

Building height2)

0 – 8 m

over 8 – 20 m

Consumption of adhesive U for thermal insulation1)

1) For mineral fibre insulation materials, the adhesive consumption is to be defined depending on the object.

2) Not for tower-style, detached buildings. Not for exposed positions.3) With profiled steel decking, 2 adhesive stripes per corrugation. As the vapour control membrane may sag, the adhesive

stripes must be placed on the corrugation shoulders.

40

Page 41: TM Rhepanol g

7/28/2019 TM Rhepanol g

http://slidepdf.com/reader/full/tm-rhepanol-g 41/73

Rhepanol® fkbonded fixingApplication techniques 41

Rhepanol® fk

bonded with Rhepanol-Adhesive 90

Rhepanol fk bonded with

Rhepanol-Adhesive 90

With the Rhepanol-Adhesive 90 speciallydesigned for Rhepanol fk, the roofing mem-

brane is securely bonded to the substrate.The adhesive is applied in stripes with at least

8 stripes/m.

Adhesive consumption depends on the place

and height of the building and on the bonding

substrate.

With building heights over 20 m and in the

case of roofs with high wind exposure (e.g.

tower-style, detached buildings, airplane

hangars and buildings near the coast), it isnecessary to define the amount of adhesive

needed or appropriate object-related measures

for membrane position stability.

For roof slopes exceeding 15°, additionalmechanical fastening may be necessary to

prevent the roofing membrane slipping off

while the adhesive is curing. At slopes exceed-

ing 20°, application should be agreed with

our experts. For information on the adhesive,its application and processing see data sheet

Rhepanol-Adhesive 90 (page 63).

Consumption of Rhepanol-Adhesive 90 for the roofing membrane Rhepanol fk1)

160 g/m2

200 g/m2

240 g/m2

280 g/m2

8

8

0 – 8 m

over 8 m – 20 m

1) If the base is of mineral fibre insulation materials the adhesive/adhesive consumption is to be defined depending on the object.2) Not for tower-style detached buildings. Not for exposed positions.

Building height2) Inner area Perimeter and Min. amount ofcorner areas adhesive stripes/m1)

Page 42: TM Rhepanol g

7/28/2019 TM Rhepanol g

http://slidepdf.com/reader/full/tm-rhepanol-g 42/73

Rhepanol® fkbonded fixing Application techniques

Linear perimeter fixing,

flashings and cappings,roof refurbishment

Linear perimeter fixing

A linear perimeter fixing at flashings and

cappings is necessary with supporting decksmade of galvanized profiled steel.

I In general, with bonded roof build-ups with

mineral fibre insulation materials, independ-

ent from the supporting deck.

The perimeter fixing of the roof build-up,

including the roofing membrane, is achieved

in each instance with at least 4 fixings/m in

line.

Flashings and cappings

All flashings and cappings are carried out with

Rhepanol fk flashing strips. With flashing heightsof over 20 cm, full-size adhesive bonding of the

covering at the upstand is necessary. Valley areas

are left unbonded at a width of 20 cm to allow

movement compensation. The upper edge of

the Rhepanol fk roofing membrane is pressed tothe substrate with rigid wall connection profiles

such as “Classic” and additionally secured with

sealant A or S. The two-part FDT roof edge

trims ensure flexible, yet windproof capping of

the roof perimeter. Forming of flashings andcappings is identical for all application methods.

For drawing example see “Technical details”.

Additional requirements for roof

refurbishment:

I Before overlaying with Rhepanol fk

the adhesion between the old roofing layers,

as well as to the supporting deck must becompletely secure. Otherwise mechanical

fastening will be necessary.

I With old roofs bonded with cold bituminous

adhesive a mechanical fastening of the old

roof is obligatory due to the plastic dimen-sional dynamics of the cold bituminous

adhesive.

I The substrate must be suitable for bonding,free from chippings and thoroughly cleaned.

 Sketch Linear perimeter  fixing 

42

Page 43: TM Rhepanol g

7/28/2019 TM Rhepanol g

http://slidepdf.com/reader/full/tm-rhepanol-g 43/73

Rhepanol® fkbonded fixingApplication techniques 43

Roof build-up

Examples for layer

build-up

Non-ventilated roof(warm roof)

ᕃ Reinforced concrete

ᕄ Vapour control layer, bondedwith adhesive U

ᕅ Thermal insulation layerconsisting of folding poly-

styrene insulation boards,

with bitumen facing, bondedwith adhesive U

ᕆ Rhepanol fk, bonded with

Rhepanol-Adhesive 90

ᕃ Lightweight concrete,

pre-coated as required

ᕄ Adhesive stripes Rhepanol-Adhesive 90

ᕅ Rhepanol fk, not bonded

over board joints (slidingstrips over cross joints as

required)

ᕃ Timber board cladding

ᕄ Bituminous sheet with

tear-resistant reinforcement,

mechanically fastened,closed seams

ᕅ Adhesive stripes Rhepanol-

Adhesive 90ᕆ Rhepanol fk

Ventilated roof (cold roof)

ᕃ Chipboards/veneer boards

ᕄ Adhesive stripes Rhepanol-

Adhesive 90

ᕅ Rhepanol fk, not bonded

over board joints (sliding

strips as required)

Page 44: TM Rhepanol g

7/28/2019 TM Rhepanol g

http://slidepdf.com/reader/full/tm-rhepanol-g 44/73

Technical details44Rhepanol® fkbonded fixing

Wall Connection

Non ventilated roof

Scale 1:5

ᕃ Steel Angle

ᕄ Galvanized profiled Steel Decking

ᕅ Steel Angle

ᕆ Cold Bitumen Primer

ᕇ Vapour Control Layer

ᕈ Expanded Polystyrene with

Bituminised Felt facing

ᕉ Rhepanol fk bonded with Adhesive No. 90

ᕊ Linear Perimeter Fixing

(4 piece per meter)

ᕋ Airtight Sealing Tape

ᕍᕠ Blockwork

ᕍᕗ Rhepanol-Contact Adhesive No. 11

ᕍᕘ Rhepanol fk-Flashing Strip

ᕍᕙ Wall connection Profile

ᕍᕚ Sealant A

Page 45: TM Rhepanol g

7/28/2019 TM Rhepanol g

http://slidepdf.com/reader/full/tm-rhepanol-g 45/73

Technical details 45Rhepanol® fkbonded fixing

Parapet

Non ventilated roof

Scale 1:5

ᕃ Roof structure

ᕄ Sloping screed

ᕅ Existing roofing layers Vapour Control Layer

Thermal Insulation to Specification Bitumen Felt

ᕆ FDT Adhesive U

ᕇ Thermal Insulation to Specification

ᕈ Rhepanol fk bonded with Rhepanol-AdhesiveNo. 90

ᕉ Rhepanol fk-Flashing Strip

ᕊ Thermal Insulation

ᕋ Rhepanol-Contact Adhesive No. 11

ᕍᕠ Treated Timber Profile

ᕍᕗ FDT Roof Edge Trim

Page 46: TM Rhepanol g

7/28/2019 TM Rhepanol g

http://slidepdf.com/reader/full/tm-rhepanol-g 46/73

Technical details46Rhepanol® fkbonded fixing

Roof Perimeter

Non ventilated roof

0

Scale 1:5

ᕃ Structure

ᕄ Structure

ᕅ Precast Concrete

ᕆ Existing roofing covering Bitumen-Vapour

Control Layer Thermal Insulation to

Specification 3 Layers roofing membrane

ᕇ Expended polystyrene with

Bituminised Felt facing

ᕈ Rhepanol fk bonded with Rhepanol-Adhesive

No. 90 (horizontally) Rhepanol-Contact

Adhesive No. 11 (sloped, vertically)

ᕉ Wall structure

ᕊ Continuous Insulation

ᕋ Rhepanol fk-Flashing Strip

ᕍᕠ Treated Timber Profile

ᕍᕗ FDT Roof Edge Trim

Page 47: TM Rhepanol g

7/28/2019 TM Rhepanol g

http://slidepdf.com/reader/full/tm-rhepanol-g 47/73

Technical details 47Rhepanol® fkbonded fixing

Parapet

Ventilated roof

Scale 1:5

ᕃ Pre-cast-concrete to falls

ᕄ Rhepanol-Adhesive 90

ᕅ Rhepanol fk bonded

ᕆ Rhepanol fk-Flashing Strip

ᕇ Rhepanol-Contact Adhesive 11

ᕈ Treated Timber Profile

ᕉ Treated Timber Profile

ᕊ FDT-Roof Edge Trim

Page 48: TM Rhepanol g

7/28/2019 TM Rhepanol g

http://slidepdf.com/reader/full/tm-rhepanol-g 48/73

Technical details48Rhepanol® fkbonded fixing

Rooflight – refurbishment

Non ventilated roof

Scale 1:5

ᕃ Prefabrication Element

ᕄ Existing Roof Layers – Vapour Control Layer

Thermal Insulation to Specification, Bitumen Felt

ᕅ Adhesive U

ᕆ Thermal Insulation to Specification

ᕇ Rhepanol fk bonded with Adhesive No. 90

ᕈ Treated Timber Profile

ᕉ Rhepanol fk-Flashing Strip

ᕊ Rhepanol-Contact Adhesive No. 11

ᕋ FDT Rhepanol-Acrylic Paste

ᕍᕠ Rooflight

ᕍᕗ Thermal Insulation to Specification

ᕍᕘ Timber Profile

Page 49: TM Rhepanol g

7/28/2019 TM Rhepanol g

http://slidepdf.com/reader/full/tm-rhepanol-g 49/73

Technical details 49Rhepanol® fkbonded fixing

Non ventilated roof

Scale 1:5

ᕃ Steel Construction

ᕄ Steel Angle

ᕅ Galvanized Profiled Steel Decking

ᕆ Vapour Control Layer

ᕇ Thermal Insulation to Specification

ᕈ Rhepanol fk bonded with

Rhepanol-Adhesive No. 90

ᕉ Treated Timber Profile

ᕊ Gutter support bracket

ᕋ Steel Drip Angel

ᕍᕠ Rhepanol-Contact Adhesive No. 11

ᕍᕗ Bonded with contact Rhepanol-Adhesive No. 11

ᕍᕘ Gutter

Page 50: TM Rhepanol g

7/28/2019 TM Rhepanol g

http://slidepdf.com/reader/full/tm-rhepanol-g 50/73

Technical details50Rhepanol® fkbonded fixing

Building movement joint with upstand

Non ventilated roof

Scale 1:5

ᕃ Reinforced Concrete

ᕄ Cold bitumen primer

ᕅ Vapour control Layer

ᕆ Thermal Insulation to Specification

ᕇ Rhepanol fk bonded with adhesive No. 90

ᕈ Steel Angles at 800 mm c/c

ᕉ Treated Timber Profile

ᕊ Expended polystyrene with Bituminised

Felt facing

ᕋ Rhepanol fk-Flashing Strip

ᕍᕠ Rhepanol-Contact Adhesive No. 11

ᕍᕗ Capping

ᕍᕘ Treated Timber Profile

ᕍᕙ Compressible Thermal Insulation

Page 51: TM Rhepanol g

7/28/2019 TM Rhepanol g

http://slidepdf.com/reader/full/tm-rhepanol-g 51/73

Technical details 51Rhepanol® fkbonded fixing

Rainwater Outlet

Non ventilated roof

Scale 1:5

ᕃ Structure

ᕄ Precast Concrete

ᕅ Existing roof layers bitumen

Vapour Control Layer Thermal Insulation

3 layers Bitumen Felt

ᕆ Expanded polystyrene

with Bituminised Felt facing

ᕇ Rhepanol fk bonded with Rhepanol-

Adhesive No. 90 (horizontally) withRhepanol-Contact Adhesive No. 11 (sloped)

ᕈ Rhepanol Collar with Self-welding Sealing

ᕉ FDT Rainwater Outlet

ᕊ GripFix collar

Page 52: TM Rhepanol g

7/28/2019 TM Rhepanol g

http://slidepdf.com/reader/full/tm-rhepanol-g 52/73

Technical details52Rhepanol® fkbonded fixing

FDT VarioGully Outlet

Non ventilated roof

Scale 1:5

ᕃ Rainwater Outlet Fixings (3/Gully)

ᕄ Stiffening Profile

ᕅ Galvanized profiled Steel Decking

ᕆ Vapour Control Layer

ᕇ Cold Bitumen Primer

ᕈ Thermal Insulation to Specification

ᕉ Vapour Control Layer (Collar)

ᕊ FDT Rainwater Outlet

ᕋ GripFix Ring

ᕍᕠ Rhepanol-Collar with Self-welding Sealing

ᕍᕗ Rhepanol fk, bonded with Rhepanol-Adhesive No. 90

Page 53: TM Rhepanol g

7/28/2019 TM Rhepanol g

http://slidepdf.com/reader/full/tm-rhepanol-g 53/73

Technical details 53Rhepanol® fkbonded fixing

FDT-Rainwater outlet for Refurbishment

Non ventilated roof

Scale 1:5

ᕃ Existing Rainwater Outlet

ᕄ Existing Thermal Insulation

ᕅ Existing Waterproofing Layers (Bitumen)

ᕆ GripFix Ring

ᕇ Sieve

ᕈ Rainwater Outlet Fixings (3/Gully)

ᕉ Rhepanol Collar with Self-welding Sealing

ᕊ Rhepanol fk bonded with Rhepanol-Adhesive

No. 90

ᕋ Screw Ring

ᕍᕠ FDT Rainwalter Outlet fur Refurbishment

Page 54: TM Rhepanol g

7/28/2019 TM Rhepanol g

http://slidepdf.com/reader/full/tm-rhepanol-g 54/73

Technical details54Rhepanol® fkbonded fixing

Internal gutter closing

Ventilated roof

Scale 1:5

ᕃ Internal gutter

ᕄ Rhepanol-Adhesive No. 90

ᕅ Prestressed concrete

ᕆ Timber profile

ᕇ Bit. Felt mechanically fixed

ᕈ Rhepanol fk bonded with Rhepanol-Adhesive

No. 90

Page 55: TM Rhepanol g

7/28/2019 TM Rhepanol g

http://slidepdf.com/reader/full/tm-rhepanol-g 55/73

Technical details 55

   F   D   T   F   l  a  c

   h   d  a  c

   h   T  e  c

   h  n  o

   l  o  g

   i  e   G  m

   b   H   &   C  o .

   K   G

 .   E   d   i   t   i  o  n

   2   0   0   4

Rhepanol® fkbonded fixing

Rhepanol weir overflow pipe

Scale 1:5

ᕃ Reinforced Concrete

ᕄ Rhepanol-Contact Adhesive No. 11

ᕅ Rhepanol fk

ᕆ Rhepanol Collar with Self-welding Sealingwelded with Rhepanol solvent-welding Agent

ᕇ Rhepanol Paste

ᕈ FDT Lightning Conductor Collar

ᕉ Pipe with Spigot and Socket Joint DN 50

ᕊ Rhepanol Collar with Self-welding Sealing

Page 56: TM Rhepanol g

7/28/2019 TM Rhepanol g

http://slidepdf.com/reader/full/tm-rhepanol-g 56/73

Data sheets

Product information

Accessories

56

Page 57: TM Rhepanol g

7/28/2019 TM Rhepanol g

http://slidepdf.com/reader/full/tm-rhepanol-g 57/73

Roofing membraneRhepanol® fkData sheet 57

Roofing membrane Rhepanol® fk

Rhepanol® fk

The roofing membrane for all application methods

Rhepanol fk is made of polyisobutylene (PIB), with a prefabricated self-sealing edge and anintegrated synthetic fleece backing. The self-sealing edge makes it easier to seal the seams

and provides a permanently secure joint. The fleece backing provides additional protection

against stresses originating from the substrate. Furthermore, the fleece backing allowsdiffusion and ensures secure fastening onto the substrate.

 Rol l out , cle an the seam, pul l off the protec tiv e str ip, pre ss down the edg e – sea led ! 

Material properties

I Roofing membrane according to

DIN 16731 – PIB-2,5-K-PV.

I Weather-resistant, even without additional

surface protection.

I Resistant to atmospheric influence such as

UV-radiation or exhaust gas from industrial

and heating plants.

I Remains flexible, even at temperatures as

low as – 60 °C.

I Outstanding resistance to natural ageing.

I Free of plasticizers and halogens, resistant to

rotting, non-porous (factory high-frequencytesting).

I Bitumen-resistant.

I Resistant to flying sparks and radiant heat

according to DIN 4102, confirmed by official

test certificates, building materials class B 2.

I In terms of resistance to root penetration

Rhepanol fk meets the test requirements of

DIN 4062, sections 4.7 and 5.7.

I Hail-resistant according to SIA 280.

Not resistant to organic solvents such as benzene,

toluene, paraffin, trichloroethylene; solvent-

containing materials such as lacquers, paints;

fats, oils, such as oily cements, forming oils.

Quality assurance

Rhepanol fk is subject to

constant in-house and externalquality control. The in-house

quality assurance system for

the whole company has been

certified according to DIN EN

ISO 9001, the world’s moststrict quality standard, and is

constantly monitored by TÜV

CERT.

Ecology

Rhepanol fk has gone through

a life cycle assessment according

to ISO EN 14040-49, carried

out by the independent institute

C.A.U. GmbH (Gesellschaftfür Consulting und Analytik im

Umweltbereich) (Company

for Ecological Consulting and

Analytics Ltd.).

FDT will be glad to send youa summary on the life cycle

assessment on request.

Range of application

Depending on the supportingdeck and the substrate

conditions, Rhepanol fk can

be applied in different ways:

I bonded fixing,

I mechanically fastenedwith Gripfix system

I loose laying with ballast

Rhepanol fk with a double-sided self-sealing edge is

used for expansion joints and

flashings.

Page 58: TM Rhepanol g

7/28/2019 TM Rhepanol g

http://slidepdf.com/reader/full/tm-rhepanol-g 58/73

Roofing membraneRhepanol® fk Data sheet

Rhepanol® fk

58

Material Colour Thickness* Width Length Weight

mm m m kg/m2

Rhepanol fk grey, black, white 2.5 1.05 15 2.60

with synthetic grey, black, white 2.5 1.05 10 2.60

fleece backing grey, black, white 2.5 0.65 15 2.60

grey, black, white 2.5 0.52 15 2.70

grey, black, white 2.5 0.35 15 2.80

Rhepanol fk grey, black, white 2.5 1.05 15 2.70

with double-sided grey, black, white 2.5 0.65 15 2.80

sealing edge grey, black 2.5 0.52 15 2.80

grey, black, white 2.5 0.35 15 2.90

grey, black, white 2.5 0.25 15 3.00

*incl. 1 mm synthetic fleece

Max. tensile force

Elongation atmax. tensile force

Tear-growth resistance

Resistance tohydrostatic pressure

Resistance to perforation

Dimensional stability afterwarm storage (6 h, 80 °C)

Bending at

low temperatures

Resistance to watervapour diffusion

Linear coefficient ofthermal expansion

Area compression strength(no pressure on edges)

Thermal conductivity

Hail resistance

DIN 16726s. 5.6

DIN 16726s. 5.6

DIN 53515

DIN 16726s. 5.11

DIN 16726s. 5.12

DIN 16726s. 5.13

DIN 53361

DIN 16726s. 5.15

DIN 52612/1

SIA 280

N/5 cm

%

N

%

(air = 1)

K–1

N/mm2

W/mK

≥ 400

≥ 50

≥ 60

watertight

watertight atfall 600 mm

≤ 0.5

no cracks

at – 60 °C

≥ 260,000

4 x 10–5

10

0.26

passed

Properties Testingaccording to

Unit Value

Page 59: TM Rhepanol g

7/28/2019 TM Rhepanol g

http://slidepdf.com/reader/full/tm-rhepanol-g 59/73

Vapour barrier fkData sheet 59

Vapour barrier fk

Vapour barrier fk

Made of polyethylene foil (PE).

Works as diffusion retarding layer.

Properties

I Highly vapour-retardant

I Good stability characteristics

I Compatible with bitumen

I Not resistant to UV-radiation

Range of application

I For non air-conditioned rooms (e.g. living rooms

and offices or similar rooms without suspendedceiling).

I In loosely laid or mechanically fastened layer

build-ups with Rhepanol fk.

Physical data

Properties Testing according to DIN Unit Value

Tensile strength 53455 N/mm2 17

Elongation at break 53455 % 450–550

Thermal conductivity 52612 W/m x K 0.35

Water vapour diffusionresistance coefficient µ 53122 (air = 1) 300 000

Air space width equivalent

to water vapour diffusion

(sd = µ x s) m ≥ 120

Forms of supply

Material Colour Nominal thickness Width Length

Vapour barrier fk blue 0.4 mm 4 m 25 m

Sealing tape for vapour barrier fk 8 cm 12 m

Seam tape grey 1.5 cm 25 m

Page 60: TM Rhepanol g

7/28/2019 TM Rhepanol g

http://slidepdf.com/reader/full/tm-rhepanol-g 60/73

Fire retardant layer fk Data sheet

Fire retardant layer fk

Fire retardant layer fk

A special flame-retarding woven glass clothwith a weight of 175 g/m2.

Range of application

As a fire retardant layer with mechanicalfastening of Rhepanol fk with Gripfix system

at roofs up to 20° slope on unbacked poly-

styrene thermal insulation.

Properties

I Protection against flying sparks andradiant heat

I Easy and clean application

I Membrane width of 2.00 m meanseconomical application

I Resistant to rotting

Application instructions

 Rhepanol fk,mechanically fastened with Gripfix system

 Fire retardant layer fk

Thermal insulation

Vapour barrier fk

 Profiled steel decking,corrosion protected 

The fire retardant layer fk is loosely laid under

the Gripfix strips at a seam overlap of 8 cm.

Properties Unit Value

Flame resistance – flame chamber test according to

DIN 4102-1 (A2) passed

Max. tensile force N/50 mm ≥ 1000

Elongation at max. tensile force % ≥ 4

Weight per square metre g/m2 175

Physical data

Form of supply

Material Colour Width Length Weightm m kg/roll

Fire retardant white 2.00 100 approx.layer fk 36

60

Page 61: TM Rhepanol g

7/28/2019 TM Rhepanol g

http://slidepdf.com/reader/full/tm-rhepanol-g 61/73

Protection layer TS fkData sheet 61

Protection layer TS fk

Protection layer TS fk

Protects the roof sealing.

The protection layer consists of a 1.2 mmnon-rigid PVC membrane with glass fleece

reinforcement, with polyester fleece backing

150 g/m2.The overall thickness is 1.8 mm.

For easy sealing of the seams, the protection

layer TS fk has no fleece backing along the

whole length of one edge.

Range of application

For layer build-ups with synthetic roofing

membrane Rhepanol fk:

I As a separation layer if non-standard gravelis used

I As a protection layer for roof terraces with

paving slabs

Properties

I Protection of the sealing against mechanical

damage

I The fleece backing provides full-size reliable

separation from the sealing layer

I Membrane width of 2.05 m means

economical application

Application instructions

The protection layer TS fk is loosely laid with

the fleece-backed side down.

Depending on the type of application, the

seam connection can be carried out in differentways:

I With 8 cm seam overlap, without sealing.

I For easy sealing of the seams the protection

layer TS fk has no fleece backing along the

whole length of one edge.

I With 5 cm seam overlap and sealing bysolvent or hot air welding.

I With 5 cm seam overlap and sealing with

Rhenofol paste, applied in straight beads in

the centre of the overlap and spread towards

the seam edge by rolling on the overlappedmembrane.

Paste consumption: approx. 30 g/m.

The seams must be closed if used as protection

layer under screed or slabs in a bed of mortar.

The protection layer TS fk is not designed

for weather exposure and must always be

covered.

At the edges of building elements, the protec-

tion layer TS fk is applied in the form of a

loosely overlapping skirt projecting approx.25 cm into the covering area and remaining

unwelded.

 Paving slabs

 Fine gravel bed 

 Protection layer TS fk

 Rhepanol fk

Thermal insulation

Vapour control layer 

Concrete floor 

Forms of supply

Colour Width Length Overall thicknessm m mm

grey, 2.05 10 1.8lower side white

Page 62: TM Rhepanol g

7/28/2019 TM Rhepanol g

http://slidepdf.com/reader/full/tm-rhepanol-g 62/73

Adhesive systemRhepanol-Adhesive 90 Data sheet

Rhepanol-Adhesive 90,

Universal application trolly

Application

I For a stable application of roofing membranes

Rhepanol fkI Is applied in stripes with the Universal

application trolley

I Is supplied in containers that can be

completely drained and thus recycled

Range of application

For bonding of Rhepanol fk on the following

substrates:

I Reinforced concrete

I Lightweight concrete, pre-coated as required

I Chipboards, veneer boards

I New bituminous sheets (also as a lining for

thermal insulation boards and sheets, withoutPE backing)

I Aged bituminous sheets (with solid and cleansurface)

Properties

I Rhepanol-Adhesive 90 is a liquid, solvent-con-taining and synthetic-rubber-based adhesive

I High adhesiveness

I Elastic, no embrittling

I Stable at temperatures from – 40 °C to+130 °C

I High thermal stabilityI Application method which needs no power

supply

Substrate

The substrate has to be solid, even, clean, dry

and free of grease and oil. Polystyrene rigid-

foam boards or sheets must have a bituminousfacing.

Universal applicationtrolly with attached (completelydrainable) 25 kg containers of  Rhepanol-Adhesive 90

Application method

The adhesive is applied either with theUniversal application trolley, or manually.

Manual application should be limited to roof

areas that cannot be worked on with the

Universal application trolley, such as small

areas between roof lights.

The Universal application trolley

I Easy to handle application tool which needsno power supply.

I For the application of stripes of Rhepanol-

Adhesive 90 from 25 kg containers. The

amount of adhesive applied is regulated by

the speed of application.

62

Page 63: TM Rhepanol g

7/28/2019 TM Rhepanol g

http://slidepdf.com/reader/full/tm-rhepanol-g 63/73

Adhesive systemRhepanol-Adhesive 90Data sheet 63

Rhepanol-Adhesive 90

Sloping areas

I At roof slopes over 15°: if necessary, apply

additional mechanical fastening to preventthe roofing membrane slipping off while

the adhesive is curing.

I At roof slopes over 20°: application must be

agreed with our experts.

Curing

I Under normal conditions a sufficient initial

hardness is reached within 4 to 8 hours.

The curing time of the adhesive dependson the evaporation of the solvents. Longer

evaporation time reduces curing time.

Technical data

Base Colour Bulk density Class of hazard Compulsory notification Installation Open(VBF) accord. to Hazardous temperature time

Material Regulationsynthetic white 1.0 g/cm3 A1 yes min. + 5 °C up to 20rubber minutes

depending onthe weather

Adhesive consumption

Building height Adhesive consumption Number of adhesive stripes/mInner area Perimeter and corner area

0 – 8 m1) 160 g/m2 240 g/m2 min. 8

over 8 m – 20 m 200 g/m2 280 g/m2 min. 8

1) At a consumption of 160 g/m2, the running adhesive stripe should be 8 mm wide.

Forms of supply

Product name Form of supply Application

Rhepanol-Adhesive 90 9 kg container for adhesive application with Universal application trolley (using adapter) or

manual application

Rhepanol-Adhesive 90 12 kg container1) for manual adhesive application

Rhepanol-Adhesive 90 25 kg container1) for adhesive application with Universal application trolley

1) Owing to the clamping ring cover, the containers can be completely drained and thus be recycled.

I If bituminous layers are used as a sealing

sublayer curing time may be extended.

However, even in very unfavourable

conditions, the adhesive will be completelyhardened within several days.

Storage

Not frost-proof. Best storage in a dry placeat + 10 °C.

Maximum period of storage: 24 months in

tightly closed original containers.

For further application instructions, see

container and installation instructions

Rhepanol fk.

Hazard identification, safety precautions, transport markings, see EC safety data sheet.

Page 64: TM Rhepanol g

7/28/2019 TM Rhepanol g

http://slidepdf.com/reader/full/tm-rhepanol-g 64/73

Adhesive U Data sheet

Adhesive U

Application

I For stable bonding of thermal insulation

materials, bituminous vapour control sheetsand bituminous sheets.

I To be applied in stripes with the Universal

application trolley, equipped with a specialadapter.

Properties

I Liquid, one-component solvent and CFC free

polyurethane adhesive

I High adhesiveness

I Elastic, no embrittling

I Stable at temperatures from – 40 to + 100 °C

I High thermal stabilityI Solvent and CFC free, does not affect rigid

polystyrene foam

I Foams and compensates small height

differences of the substrate

I Simple application method which needs no

power supply

I No risk of burning or fire

Substrate

The bonding areas have to be solid, even, clean,

dry and free of grease and oil.

Adhesive consumption

For building heights up to 20 m the consump-

tion and the amount of necessary adhesive

stripes are indicated on page 40 in the table

“Adhesive U consumption for thermal insula-tion”.

For detailed application instructions see the

installation instructions Rhepanol fk and the

containers.

Application method

I With the Universal application trolley and

adapter for adhesive U (6.5 kg containers) foreven substrates.

I Manual application should be limited to roof

areas that cannot be worked on with the appli-cation trolley, such as small areas between roof

lights.

Sloping areas

At roof slopes over 7°:

I Preferably, the adhesive should be applied in

direction of the slope.

I Supporting measures should be applied to

prevent the materials slipping off while theadhesive is curing.

Fascia boards, for example, can be used as

abutment. At roof slopes over 20°, application

must be agreed with our experts.

Curing

I The curing time of the adhesive depends on the

temperature as well as on the ambient humidityand the air humidity. Normally a sufficient initial

hardness is reached within 1 to 3 hours. A slight

moistening reduces the curing time.

I In case of bonding vapour-proof materials, thecuring time may be extended. However, even invery unfavourable conditions, the adhesive will

be completely hardened within several days.

I With high summer temperatures (approx. 25 °C

and above) and low air humidity, it is recom-

mended slightly moistening the substrate afterapplying the adhesive to ensure a sufficient

degree of moisture for foaming.

Universal  application trollywith adapter and  attached 6.5 kg containers of  adhesive U 

64

Page 65: TM Rhepanol g

7/28/2019 TM Rhepanol g

http://slidepdf.com/reader/full/tm-rhepanol-g 65/73

Adhesive UData sheet 65

Adhesive U

Substrates Vapour control, compensation Rigid foam boards Mineral fibre

and separation layers made of and sheets boards/sheets

bituminous sheetsReinforced concrete X

Lightweight concrete with X X

cold bitumen primer

Chipboards X

Steel profile sheets

– with plastic coating X X

– with aluminium-zinc coating X X

– galvanized

with anticorrosive coating X X

Bituminous vapour

control sheets1) X XRigid foam boards/sheets X X

New bituminous sheets1) X X

Old bituminous sheets, if

the surface is solid and clean X X X1) Without PE backing or talcum coating.

Do not use adhesive U for bonding Rhepanol fk!

Technical data

Base Colour Consistence Bulk density Non-volatile Class of

matter hazard

(VBF) isocyanate brownish liquid 1.1 g/cm3 100 % nonprepolymer

Flash point Compulsory notification Installation temperature Open time Height difference

according to Hazardous (air and substrate) compensation

Material Regulation

non yes min. + 5 °C, max. 50 °C up to 15 minutes depending ondepending on humidity, temperature

the weather and amount applied:

scheduled 5 mm

Storage

Not frost-proof Best storage Maximum period of storage

no in a dry place at temperatures from + 10 °C to + 20 °C 12 months in tightly closed original containers.

Form of supply

Product name Form of supply Application

Adhesive U 6.5 kg container Universal application trolly with adapter for adhesive U

Hazard identification, safety precautions, transport markings, see EC safety data sheet.

Range of application

Page 66: TM Rhepanol g

7/28/2019 TM Rhepanol g

http://slidepdf.com/reader/full/tm-rhepanol-g 66/73

Rhepanol® fk Accessories

Contact adhesive,

sealants,primers,

roof paints

Product name Properties Range of application

Rhepanol-Contact Synthetic-rubber-based For bonding Rhepanol to walls, roof

Adhesive 11 contact adhesive. lights and parapets.

Rhepanol-Adhesive 9 Acryl ic-based dispersion adhesive. For bonding Rhepanol fk to chipboards and

veneer boards on roof slopes of 15°.

Sealant A Solvent-free plasto-elastic Sealing of joints, cracks with limited movementone-component joint sealant stress. Good adhesion to e.g. ceramics, render

(acrylic-based dispersion). finish, brick work, concrete, lightweight concrete,

natural stone.

Sealant S Elastic solvent-containing joint For expansion and connection joints e.g. in thesealant (synthetic rubber based). facade, in glass, in bathrooms and toi lets and on

the roof. Good adhesion to Rhepanol fk.

Primer 1 Blue coloured polymer solution with Bonding agent for Rhepanol-Contact Adhesive 11.

outstanding adhesion to steel, concrete,render finish, wood and rigid PVC.

Primer 2 Transparent polymer solution with Especially reliable adhesive bond is reached,

good adhesion to most nonferrous if coating with primer 2 is followed by coating

metals and special steels. with primer 1.

Primer Precol Black relatively high-viscous Adhesive qualities on various substrates. Bonding

pre-coat with outstanding agent for waterproof connection of Rhepanol

adhesive qualities. to different materials such as concrete, brickwork,

rigid PVC, metal.

Roof paint Special PIB-based roof paint. For a decorative coating of all Rhepanol membranes.

Colours: silver, copper, other colours on request.

66

Page 67: TM Rhepanol g

7/28/2019 TM Rhepanol g

http://slidepdf.com/reader/full/tm-rhepanol-g 67/73

Rhepanol® fkAccessories 67

Gripfix strips,

sealing and cover tapes,preformed corners,

collars

Product name Properties Range of application

Sealing tape Double-sided self-adhesive, For waterproof connection of Rhepanol fk to

good adhesion. various substrates such as concrete, coatedmetal sheets, in connection with Rhepanolprimer Precol.

Gripfix strips Highly tear-resistant polyester For fastening Rhepanol fk with Gripfix system.

backing with velcro grips. To be fastened with standard fasteners and

washers.

Cover tape With self-sealing edge system, For cross joints and flashings at roofing

as sealing tape on membranes Rhepanol fk.

Rhepanol f-backing.

Internal corner 90° With self-seal ing edge system. Preformed detai l for sealing internal corners at

roofing membranes Rhepanol fk.

Internal corner 90° rapid With self-seal ing edge system. Internal corner with integrated cover tape strips.

External corner 90° With self-seal ing edge system. Preformed detai l for sealing external corners

at roofing membranes Rhepanol fk.

Universal roof light corner With self-seal ing edge system. Preformed detai l for sealing roof light cornersat roofing membranes Rhepanol fk.

Roof light corner With self-seal ing edge system. Preformed detai l for sealing roof light corners,

Universal rapid if the flashing strip projects more than 15 cm

onto the roof area.

Universal collar With self-sealing edge system Preformed detail for built-in details and roof

with Gripfix ring. penetrations at roofing membranes

Rhepanol fk, collar diameter 34 cm.

Collar loose/fixed flange Up to ø 350 mm with self-sealing For all standard rainwater outlets with bolt

edge system and from ø 350 mm connection (6 or 8 holes).

on with Rhepanol f.

EPDM framing ring As set (4 framing rings). For flashing to loose/fixed flange rainwateroutlets at Rhepanol fk.

Rhepanol collar With self-sealing edge system For reliable flashing of Rhepanol fk against the

incl. Gripfix ring. VarioGully. The Gripfix ring replaces contactbonding with Rhepanol-Contact Adhesive 11.

Page 68: TM Rhepanol g

7/28/2019 TM Rhepanol g

http://slidepdf.com/reader/full/tm-rhepanol-g 68/73

Rhepanol® fk Accessories

VarioGully

VarioGully vertical, DN 125without reducer

Roof penetration Ø 190 mm Roof penetration 190 x 240 mm

Roof penetration 190 x 270 mm

Adjustableto anythermalinsulationthicknessfrom35 mm to240 mmwithoutadditionalparts

VarioGully vertical, DN 125with warm roof upstand,

without reducer

VarioGully vertical, DN 100with reducer DN 125/100

VarioGully angled, DN 100extremely flat, overall height 110 mm,with transition piece DN 70/100

VarioGully angled, DN 125

overall hight 189 mm

VarioGully

I A proven flat roof rainwater outlet, which

is regularly tested by the external testinginstitute LGA Bavaria.

Properties

I Made of rigid PVC with increased impact

strength, including gravel and leaf catcher

and can be used without additional ele-

ments with any layer thickness from 35 to

240 mm.

I In case of heatable VarioGully versions,

the splash-proof installed – not foamed-in –

heater unit is doubly protected by the two

integrated safety systems (heat monitoringrelay and fuse). Connection via safety

transformer 220/24 V (10 W per outlet).

Range of application

I In warm and cold roof structures in vertical

and angled version.

I Corresponding warm roof frames are availa-

ble for insulation material thicknesses from

35 to 160 mm and 160 to 240 mm1). Directconnection to all vapour control membranes

or roofing membranes, or with separately

preformed collar.

ᕃ Rainwater outlet DN 125

ᕄ Insulating sleeve

ᕅ Sealing ring

ᕆ Roofing membrane collar

ᕇ Screw ring

ᕈ Roll ring

ᕉ Warm roof upstand

ᕊ Vapour control layer collar

ᕋ Sieve (leaf guard)

ᕍᕠ Roll ring DN 125

ᕍᕗ Reducer DN 125/100

Nominal Roofs without ballast Gravelled Greenoutlet width Slope roofs roofsDN ≥ 15° ≤ 15°

70 57 70 114 190

100 150 187 300 500125 233 291 466 776

   D   N    1

   0   0

1) Other insulation material thicknesses on request.

68

Page 69: TM Rhepanol g

7/28/2019 TM Rhepanol g

http://slidepdf.com/reader/full/tm-rhepanol-g 69/73

Rhepanol® fkAccessories 69

VarioGully refurbishment,

accessories for VarioGully: leaf guard

VarioGully refurbishment

I Ensures installation in the existing old roof

without backflow.I Supplied complete with bolts and sealing

cord.

I To be used with old roof outlets up to

DN 150, depending on the diameter of the

run-in area.

Accessories for VarioGully: leaf guard

Made of aluminium with lift ring. For application

on flat roofs with paving slabs or on invertedroofs.

The installation height of 67 to 90 mm can be

adapted to the terrace structure in steps of 3 mm.

With a slab height of 90 mm or more, additional

lift rings will be necessary.

ᕃ Existing old roof rainwater

outlet

ᕄ Existing layer build-up

ᕅ VarioGully refurbishmentᕆ Thermal insulation layer

ᕇ Rhepanol fk

ᕈ Rhepanol-Contact

Adhesive 11 (alternatively

Gripfix ring)

ᕉ Rhepanol collar with

self-sealing edge system

ᕊ Leaf guard

ᕋ Mechanical fastening(4 fast./rainwater outlet)

ᕍᕠ Sealing cord

Page 70: TM Rhepanol g

7/28/2019 TM Rhepanol g

http://slidepdf.com/reader/full/tm-rhepanol-g 70/73

Rhepanol® fk Accessories

Flat roof vent pipe,

cold roof vent,lightning conductor collar,

wall connection profile/roof edge trim

        1        1        0

        1        7        5

259595 25   1   1   0

   1   7   5

Made of rigid PVC with increased impactstrength. With removable cap and bearing ring.

Ready for installation with integrated collar(Version for Rhepanol fk with self-sealing edgesystem incl. Gripfix ring).

Consisting of an extruded aluminium mountingrail and roll-formed stove enamel cover (colour:silver metal grey, similar to RAL 9007), as wellas plastic clamps for fixing roofing membranesup to 5 mm thickness. Roofing membranes≤

1.5 mm must be folded back once in theclamping area.

Rigid aluminium profile in punched 3 msections. For fixing Rhepanol and Rhenofolroofing membranes at vertical surfaces.Fastening with 5 fasteners per meter, holediameter 6.5 mm.

Highly rigid aluminium profile in punched 4 msections with slot for hooking up metal sheets.For fixing Rhepanol and Rhenofol roofingmembranes at vertical surfaces. Fastening with5 fasteners per meter, hole diameter 6.5 mm.

Rigid aluminium profile in punched 4 msections. For fixing Rhepanol fk roofingmembranes at vertical surfaces. Flashing ofRhepanol fk in the profile. Fastening with5 fasteners per meter, hole diameter 6.5 mm.

With self-sealing edge system and collar.For flashing against lightning protectors andfor penetrations up to ø 51 mm or as water

spout and emergency outlet with connectionto DN 50.

Made of rigid PVC with increased impactstrength. Vent cross-section of 88 cm2.Weather cap can be removed for maintenance.Ready for installation with integrated collar(Version for Rhepanol fk with self-sealing edgesystem incl. Gripfix ring).

Properties/applicationProduct name

Flat roof vent pipe DN 100

Cold roof vent DN 100

Lightning conductor collar Rhepanol

Aluminium wall connection profile

Economy

Aluminium wall connection profile

Classic

Aluminium wall connection profile

Gripfix

Aluminium roof edge trim 110/175

70

Page 71: TM Rhepanol g

7/28/2019 TM Rhepanol g

http://slidepdf.com/reader/full/tm-rhepanol-g 71/73

Rhepanol® fkTechnical Approval 71

Page 72: TM Rhepanol g

7/28/2019 TM Rhepanol g

http://slidepdf.com/reader/full/tm-rhepanol-g 72/73

Export department:

Phone +49 621-8504-3 72

Fax +49 6 21- 85 04 -3 78

E-Mail [email protected]

111| 01|05/04| 1500 | GB|

FlachdachTechnologieGmbH & Co. KG

Eisenbahnstraße 6 - 8D-68199 MannheimGermany

Tel +49-621-8504-0Fax +49-6 21-85 04-2 05www.flachdachtec.de