Roofing Membrane SystemRhepanol® fk
TechnicalManual
Edition 2004
Rhepanol® fk
![Page 2: TM Rhepanol g](https://reader031.vdocuments.site/reader031/viewer/2022021220/577cdc0c1a28ab9e78a9bd53/html5/thumbnails/2.jpg)
7/28/2019 TM Rhepanol g
http://slidepdf.com/reader/full/tm-rhepanol-g 2/73
Imprint
Roofing membrane system Rhepanol fk
Technical manual
Edition 2004
Editor:
FDT
FlachdachTechnologie
GmbH & Co. KG
Eisenbahnstraße 6 - 8D-68199 Mannheim
Tel +49 6 21-85 04-0
Fax +49 6 21-85 04-2 05
www.flachdachtec.de
Copyright 2004 by:
FDT
FlachdachTechnologieGmbH & Co. KG
This manual corresponds with the
FDT manufacturer application instructions
for designers and applicators in theFederal Republic of Germany.
It cannot, however, replace professional
knowledge.Every user is obliged to keep his
knowledge up to date!
Valid from January 2004.
Technical changes reserved.
![Page 3: TM Rhepanol g](https://reader031.vdocuments.site/reader031/viewer/2022021220/577cdc0c1a28ab9e78a9bd53/html5/thumbnails/3.jpg)
7/28/2019 TM Rhepanol g
http://slidepdf.com/reader/full/tm-rhepanol-g 3/73
Roofing membrane systemRhepanol® fk 3
Contents
Roofing membrane system Rhepanol fk
The system – an overview 5
Rhepanol fk, mechanically fastened with Gripfix system
Application techniques 11
Technical details 19
Rhepanol fk, loosely laid with ballast
Application techniques 30
Technical details 34
Rhepanol fk, bonded fixing
Application techniques 39
Technical details 44
Data sheets, product information, accessories
Data sheet Roofing membrane Rhepanol fk 57
Data sheet Vapour barrier fk 59
Data sheet Fire retardant layer fk 60Data sheet Protection layer TS fk 61
Data sheet Adhesive system Rhepanol adhesive 90 62
Data sheet Adhesive U 64
Accessories 66
Technical Approval
5
10
29
38
56
71
Page
![Page 4: TM Rhepanol g](https://reader031.vdocuments.site/reader031/viewer/2022021220/577cdc0c1a28ab9e78a9bd53/html5/thumbnails/4.jpg)
7/28/2019 TM Rhepanol g
http://slidepdf.com/reader/full/tm-rhepanol-g 4/73
4
The world of Rhepanol® fk
allrounder winter world, Neuss/Germany
rocontrol,ren/Belgium
Edinburghconference centre,United Kingdom
kswagennan/Poland
John Dewards Ltd.,United Destillers, Scotland/ United Kingdom
Canary Wharf, London/ United Kingdom
![Page 5: TM Rhepanol g](https://reader031.vdocuments.site/reader031/viewer/2022021220/577cdc0c1a28ab9e78a9bd53/html5/thumbnails/5.jpg)
7/28/2019 TM Rhepanol g
http://slidepdf.com/reader/full/tm-rhepanol-g 5/73
The system – an overview
Rhepanol® fk – advantages
Tried and tested long-term reliability, over50 years of experience with polyisobutylene
The oldest synthetic roofing membrane
made in Germany
With a unique self-sealing edge for reliable
and fast sealing of seamsFleece backing with extremely high tensile
strength
Made of polyisobutylene (PIB), therefore
compatible with bitumen
One roofing membrane for all applicationmethods
The only roofing membrane to be applied
with the Gripfix systemResistant to UV-radiation
Flexible at temperatures as low as – 60 °CFree of plasticizers
Application without open flame
No need for surface protection
Comprehensive warranty on materials
Ideal for refurbishment
The self-sealing edge system
The pre-fabricated self-sealing edge system is
different from conventional adhesive bonding.
Sealing of the seams is carried out by firmly joining homogenous materials. Immediately
after the self-sealing edge has been pressed tothe connecting membrane the seam is already
waterproof. Owing to the integrated self-
sealing edge, seams can be sealed withoutopen flame, hot air, solvent welding or addi-
tional adhesives, making application more
efficient and almost independent of weather
conditions.
The roofing membrane with a strong
character
Industrially pre-fabricated self-sealing edge for reliable and
fast sealing of seams.
It only takesthree steps:
Rhepanol fkwith self-sealing
edge system.
... roll out
... roll on the edge ... sealed! ... clean the seam, pull off the protective strip
One,
two,
three,
sealed!
Application is incredibly easy and safe: Roll
out Rhepanol fk, clean the seam area, pull off
the protective strip and press down the edge –sealed! The same goes for all preformed details,
which are also equipped with the unique self-
sealing edge system.
Roofing membrane systemRhepanol® fk 5
![Page 6: TM Rhepanol g](https://reader031.vdocuments.site/reader031/viewer/2022021220/577cdc0c1a28ab9e78a9bd53/html5/thumbnails/6.jpg)
7/28/2019 TM Rhepanol g
http://slidepdf.com/reader/full/tm-rhepanol-g 6/73
Rhepanol® fk – advantages
If you want more detailed information on thelong-term qualities of Rhepanol, we are able to
provide you with the extended test reports.
Continental AG, Hanover:Workshop hall
with more than10,000 m 2 of roof
area, covered with Rhepanol fk grey,
bonded fixing.
Schade KG, Plettenberg: Practical testing
after 14 yearsof weather
exposure has proven out-
standing water- proofing quality and ageing
resistance of Rhepanol fk.
Preformed details with self-sealing edge
system:
External cornerInternal cornerUniversal roof light corner
Collars
Cover tape for cross joints and flashings
For further technical information Rhepanol fkroofing membranes please see product data
sheets on p. 56 ff.
Long-term reliability – signed and sealed
Regular quality tests of Rhepanol fk are carried
out by in-house material testing as well as byindependent test institutes.
Additionally, Rhepanol roofs that have been
established many years are opened and tested.The result: Rhepanol fk surpasses all require-
ments set up for new roofing membranes
according to DIN 16731. This has been proven
in a survey carried out by the independent
Material Testing Institute Darmstadt on theroof of the workshop hall of Schade KG in
Plettenberg.
Roofing membrane systemRhepanol® fk The system – an overview6
![Page 7: TM Rhepanol g](https://reader031.vdocuments.site/reader031/viewer/2022021220/577cdc0c1a28ab9e78a9bd53/html5/thumbnails/7.jpg)
7/28/2019 TM Rhepanol g
http://slidepdf.com/reader/full/tm-rhepanol-g 7/73
Official seal of approval for Rhepanol fk
Rhepanol fk is known as “the long-term reliable
roofing membrane”. There are many reasons forthat: FDT does not focus on short-term profit,
but on high-quality and durable products.Therefore we have established stringent quality
control requirements that eliminate sources of
error. This in-house quality assurance system for
the whole company has been certified according
to DIN EN ISO 9001, the world’s most strictquality standard, and is
constantly monitored by
TÜV CERT. We pay the
same attention to materials
control carried out during
production as to the qualityassurance measures and the highly mechanized
production.
Control measures (amongst others):
No blisters or cracks
Thickness, width
Weight per square metre
Maximum tensile force, elongation atmaximum tensile force
Dimensional stability after storage at + 80 °C
Bending at low temperatures
In addition, Rhepanol fk is permanently moni-tored by an officially approved testing institute.
In 1980 we signed a quality control agreement
with the State Material Testing Institute
Darmstadt, plastics department. The regular
controls carried out by the Material TestingInstitute not only include production, but also
external stores and building sites. The quality
control of an independent testing institute
provides additional security when waterproofing
flat roofs with Rhepanol fk.
Warranty on materials
Warranty certificates are avail-
able for all roofing membranessupplied by FDT. FDT offers
comprehensive warranty, secur-ing everybody’s investments in
new buildings or refurbishment.
Quality assurance
Testing according to DIN EN ISO
9001. We shall be glad to send
you a copy of the TÜV certificate
on request.
Ecology
Since 1990, Rhepanol fk has
been subjected to a life cycle
assessment, carried out by therenowned and independent
Batelle-Institute. It confirmed
the outstanding ecological
profile of Rhepanol fk during
its whole life cycle.Further technical information is
available on application.
Quality control
Oualitätsmanagement
nach DIN EN ISO 9001
70 100 M 543
Roofing membrane systemRhepanol® fkThe system – an overview 7
![Page 8: TM Rhepanol g](https://reader031.vdocuments.site/reader031/viewer/2022021220/577cdc0c1a28ab9e78a9bd53/html5/thumbnails/8.jpg)
7/28/2019 TM Rhepanol g
http://slidepdf.com/reader/full/tm-rhepanol-g 8/73
Roofing membrane systemRhepanol® fk The system – an overview
Rhepanol® fk – overview
Application methods and roof build-ups
Non-traffic roof areas
N o n - v e n t i l a t e d r o o f ( w a r m r
o o f )
V e n t i l a t e d r o o f ( c o l d r o o f )
Supporting deckRoof type Slope up to 20°
Pofiled steel decking
Reinforced concrete
Lightweight concrete
Timber board cladding
Chipboards/veneer boards
Rhepanol fk, mechanically fastenedwith Gripfix system
Rhepanol fk, mechanically fastenedwith Gripfix system
Rhepanol fk, mechanically fastenedwith Gripfix system
Rhepanol fk, mechanically fastenedwith Gripfix system
Rhepanol fk, mechanically fastenedwith Gripfix system
Rhepanol fk, mechanically fastenedwith Gripfix system
8
![Page 9: TM Rhepanol g](https://reader031.vdocuments.site/reader031/viewer/2022021220/577cdc0c1a28ab9e78a9bd53/html5/thumbnails/9.jpg)
7/28/2019 TM Rhepanol g
http://slidepdf.com/reader/full/tm-rhepanol-g 9/73
Roofing membrane systemRhepanol® fkThe system – an overview 9
Rhepanol® fk – overview
Application methods and roof build-ups
Used roofs
Rhepanol fkbonded fixing
Rhepanol fkbonded fixing
Rhepanol fkloose laying with ballast*
Rhepanol fkloose laying with ballast*
Rhepanol fkloose laying with ballast*
Rhepanol fkloose laying with ballast*
Rhepanol fkloose laying with ballast*
Rhepanol fkloose laying with ballast*
Rhepanol fkloose laying with ballast*
Rhepanol fkbonded fixing
Rhepanol fkbonded fixing
Rhepanol fkbonded fixing
* For waterproofing roofs for vehicular traffic and green roofs we recommendour roofing system Rhenofol or Rhenofol RG system, we recommend a max. roof slope of 3°.
T e r r a c e s , b a l c o n i e s
![Page 10: TM Rhepanol g](https://reader031.vdocuments.site/reader031/viewer/2022021220/577cdc0c1a28ab9e78a9bd53/html5/thumbnails/10.jpg)
7/28/2019 TM Rhepanol g
http://slidepdf.com/reader/full/tm-rhepanol-g 10/73
Rhepanol® fk
mechanically fastened
with Gripfix system
10
RABO-bank, Huizen/ Netherland
Volkswagen, Poznan/ Poland
Swimming bath, Breistroff/
France
Velodrome Kaarst/Germany
![Page 11: TM Rhepanol g](https://reader031.vdocuments.site/reader031/viewer/2022021220/577cdc0c1a28ab9e78a9bd53/html5/thumbnails/11.jpg)
7/28/2019 TM Rhepanol g
http://slidepdf.com/reader/full/tm-rhepanol-g 11/73
Rhepanol® fkmechanically fastened with Gripfix systemApplication techniques 11
Safety and functional efficiency,
supporting construction
Safety and functional efficiency
With mechanical fastening the roof sealing
is separated from the lower layers and com-
ponents across the complete area. Movements
of these layers and components can thereforenot pass on stresses to the sealing, which is
significant for the prevention of damage,
especially on lightweight roofs. The roofing
membrane Rhepanol fk is rolled onto mechani-
cally fastened Gripfix strips, providing optimalwind load distribution and securing the
membrane permanently to the roof.
The membrane seams run perpendicular to theGripfix strips and thus are not affected by wind
uplift forces.
The integrated highly tear-resistant synthetic
fleece of Rhepanol fk allows diffusion of anyretained moisture.
The supporting deck structure has to meet
the requirements with regard to load-bearingcapacity, deflection, anchorage and drainage.
Substrates for application must be free
of open cracks, concrete, rough and sharpprojections.
Joints have to be formed according to
constructional requirements, as their width
or movement may impede the functional
efficiency of the roof seal.
Clean, dry and even roof surfaces.
If Rhepanol fk is directly laid on concrete
decks/screed allow the concrete/screed to setfor at least 28 days.
The effect of air escaping from the building
at the roof perimeter and at roof penetra-
tions must be prevented. Therefore theseareas have to be made airtight. In the case
of profiled steel decking, seal around all
openings and perimeters.
For compatibility reasons, timber boardcladding, chipboards and similar may be
treated only with salt-based wood preserva-
tives. Oil or solvent based impregnation
agents must not be used.
National standards and regulations must be
observed.
The mechanical
fastening of Rhepanol fk with
Gripfix system
ensures secure, fast and effective
laying.
Rhepanol fk is compatible with bitumen and
can be applied without additional separation
layers directly on to old bituminous sheets.
The integrated synthetic fleece protects themembrane against movement originating
from the substrate.
Application instructions
Supporting construction
![Page 12: TM Rhepanol g](https://reader031.vdocuments.site/reader031/viewer/2022021220/577cdc0c1a28ab9e78a9bd53/html5/thumbnails/12.jpg)
7/28/2019 TM Rhepanol g
http://slidepdf.com/reader/full/tm-rhepanol-g 12/73
Vapour control layer,
thermal insulation layer
For non air-conditioned rooms (e.g. living
rooms and offices or similar rooms withoutsuspended ceiling): vapour barrier fk
(ethylene).
In the case of lightweight concrete support-
ing decks with correctly calculated thermalinsulation, you may leave out a vapour
control layer, if the room temperature stays
below 20 °C and the relative air humidity
inside the room will not exceed 65 %. In
case of doubt, we recommend a calculationof the building physics in order to identify the
diffusion characteristics of the roof build-up.
With lightweight steel deckings, we also
recommend in principle the installation of aseparate vapour control layer, which should
be formed as an air barrier according to the
provisions of the Thermal Insulation
Regulation.
The vapour barrier fk is applied with a seamoverlap of 10 cm, with the seams being
sealed with connection or seam tape. The
vapour barrier must be taken up and flashed
at connections and cappings; at roof pene-trations it must be flashed.
For rooms with high air condition loads:
In case of air-conditioned rooms and rooms
with high air condition loads, as well as
high pressure rooms, there should be nomechanical fastening through the vapour
barrier. In these cases please consult our
experts to identify the right layer build-up
and application method.
National standards and regulations must be
observed.
Vapour control layer
In the case of non-ventilated roofs, we rec-
ommend the following vapour control layers:
Thermal insulation layer
When designing the thermal insulation layer on
steel profile supporting decks, attention mustbe given to load bearing capacity.
As materials for thermal insulation layers we
recommend:
For roof slopes up to 20°: large-sized
insulation boards made of quality assured
rigid polyurethene or rigid polystyrene foam
with rebated edge, size 1.20 x 1.20 m or1.20 x 1.00 m.
On top of the insulation boards, for fire
protection reasons, the application of a fire
protection layer – a specially coated wovenglass cloth – will be necessary.
Compressed mineral fibre insulation may
also be used.
Folding insulation boards or rigid poly-styrene foam boards with backing. For
fire protection reasons, bituminous sheets
with an integrated glass fleece or fabric
≥ 60 g/m2 may be necessary as a lining.
Use linings with a PE foil or fleece facing.
Large-sized non-flammable mineral fibreboards. Because of better suitability for
mechanical fastening we recommend
boards with a greater resistance to pointloads (min. 500 N at 5 mm deformation)
and a higher compression strength (com-
pressive strain at 10 % compression set
min. 0.06 N/mm2).
Small-sized insulation boards can be used,
provided they can be properly fastened.
National standards and regulations must be
observed.
Rhepanol® fkmechanically fastened with Gripfix system Application techniques12
![Page 13: TM Rhepanol g](https://reader031.vdocuments.site/reader031/viewer/2022021220/577cdc0c1a28ab9e78a9bd53/html5/thumbnails/13.jpg)
7/28/2019 TM Rhepanol g
http://slidepdf.com/reader/full/tm-rhepanol-g 13/73
Themal insulation layer,
Rhepanol
®
fk, mechanically fastened withGripfix system
Insulation boards or board sections that are notsufficiently fixed with Gripfix must be secured
in a stable position with additional fasteners
(at least 2 fasteners/m2) prior to applying theroofing membrane.
Insulation materials that are not dimension-
ally stable and which buckle or bulge must
not be installed. Generally insulation boards
must be laid brick-bond pattern.
Rhepanol® fk, mechanically fastened withGripfix system
The Gripfix strips are placed according tothe wind uplift calculation and mechanically
fastened. The Gripfix strip spacing is variable
depending on the wind load requirements.
The roofing membrane Rhepanol fk is thenloosely laid with a seam overlap of 5°
perpendicular to the Gripfix strips. The grip
is achieved by thoroughly rolling the roofing
membrane Rhepanol fk to the Gripfix strip.
The membrane width is always 1.05 m.Depending on the substrate a variety of
different fasteners may be used.
System sketch Rhepanol fkGripfix systemwith fire retarding layer fk (for poly- styrene insulation).
Rhepanol fk
Gripfix stripmechanically fastened
Fire retarding layer fk
Thermal insulation
Vapour barrier fk
Profiled steel decking,corrosion protected
Rhepanol® fkmechanically fastened with Gripfix systemApplication techniques 13
![Page 14: TM Rhepanol g](https://reader031.vdocuments.site/reader031/viewer/2022021220/577cdc0c1a28ab9e78a9bd53/html5/thumbnails/14.jpg)
7/28/2019 TM Rhepanol g
http://slidepdf.com/reader/full/tm-rhepanol-g 14/73
Rhepanol® fkmechanically fastened with Gripfix system Application techniques
I With the Gripfix system you must use only
the specially marked Rhepanol fk roofing
membranes.
I The max. wind force (including safety
factor 1.5) per m Gripfix strip is 1.5 kN.
The design load is max. 0.5 kN/fastener.
Instructions of the fastener manufacturer mustbe observed.
At building heights over 20 m and in special
cases (e.g. airplane hangars, buildings near the
coast, extreme exposure) each characteristic ofthe project location and special conditions must
be taken into account.
On request, computer-based project specific cal-
culations of the necessary amount of fastenersand Gripfix strip spacing are carried out, which
may result in lesser amounts of fasteners than
indicated in the table, provided the building has
a favourable geometry.
Rhepanol fk can be mechanically fastened on
roofs with any slope.
At slopes exceeding 20°, application should beagreed with our experts.
On profiled steel deckings and timber board
cladding the Gripfix strips must be arranged per-
pendicularly to the corrugations or boards toachieve the most regular wind load distribution
possible into the supporting deck.
At all flashings and cappings, roof lights etc.
the build-up must be specially secured bycircumferential rows of fasteners or Gripfix strips
(min. 4 fasteners/m).
Note:
I Max. spacing of Gripfix strips see table above.
I Fastening spacing on the Gripfix strip min.
15 cm, max. 60 cm.
I Fastener spacing on the same corrugation at
profiled steel deckings must not be less than
20 cm.
I Use only fasteners with washers of max. 5 cmwidth.
Roof areas
Inner area
Perimeter area
Corner area
Inner area
Perimeter area
Corner area
Number offasteners
3
4
6
4
6
10
Spacing of Gripfix strips (examples)2)
1.20 m 1.00 m 0.80 m 0.60 m 0.40 m
max. spacing on the Gripfix strip (cm)28 33 – – –
– 25 31 – –
– – – 28 42
– 25 31 42 –
– – – 28 42
– – – – 25
Height of eavesabove ground1)
Fasteners/m2 and spacing on the Gripfix system
Maximum Gripfix strip spacing
Building height Inner area Perimeter area Corner area
up to 12 m 1.20 m 1.00 m 0.80 m12 – 20 m 1.00 m 1.00 m 0.60 m
1) Not for tower-style detached buildings. Not for exposed positions.2) Since the Gripfix strip spacing is continuously adjustable, only examples can be given.
Fasteners / fastener spacing
0 – 8 m
8 – 20 m
14
![Page 15: TM Rhepanol g](https://reader031.vdocuments.site/reader031/viewer/2022021220/577cdc0c1a28ab9e78a9bd53/html5/thumbnails/15.jpg)
7/28/2019 TM Rhepanol g
http://slidepdf.com/reader/full/tm-rhepanol-g 15/73
Rhepanol® fkmechanically fastened with Gripfix systemApplication techniques 15
Fastening example
Corner area a/16
Corner area
C o r n e r a r e a a
/ 1 6
0 . 2
0 m
Fastening at component edges at a distance of max. 0.25 m
Perimeterarea
Inner area
Membrane edge
Mechanically fastened Gripfix strip
Perimeter area a/8
P e r i m e
t e r a r e a a
/ 8
= c o v e r i n g w
i d t h o
f t h e r o o
f i n g m e m
b r a n e
min. width 1.00 m
m i n
. w
i d t h 1
. 0 0 m
0 . 2
0 m
0 . 4
0 m
1 . 0
0 m
1.00 m
![Page 16: TM Rhepanol g](https://reader031.vdocuments.site/reader031/viewer/2022021220/577cdc0c1a28ab9e78a9bd53/html5/thumbnails/16.jpg)
7/28/2019 TM Rhepanol g
http://slidepdf.com/reader/full/tm-rhepanol-g 16/73
Rhepanol® fkmechanically fastened with Gripfix system Application techniques
Flashings and cappings
All flashings and cappings are carried out with
Rhepanol fk flashing strips.
If the connecting membrane is bonded, then atflashing heights over 20 cm a full-size adhesive
bond is necessary. Valley areas are left unbonded
at a width of 20 cm to allow movement com-pensation. If the connecting membrane is
mechanically fastened with Gripfix strips the fol-
lowing spacing must be observed (s. also sketch):
– Distance of the first Gripfix strip from the
internal corner of the parapet max. 10 cm– Spacing between the Gripfix strips or distance
between Gripfix strip and upper capping max.
50 cm.
With wall flashings, the upper edge of theRhepanol fk roofing membrane is pressed to
the substrate with rigid wall connection profiles
such as “Classic” and additionally secured with
sealant A or S. The two-part FDT roof edgetrims ensure flexible, yet windproof capping of
the roof perimeter. Forming of flashings and
cappings is identical for all application methods.
You will find details on this topic in the drawings
“Technical details”.
Additional requirements for roofrefurbishment:
I In the case of uneven substrates, protection
layers are necessary. Rigid polystyrene foam
insulation boards or sheets can be recom-
mended.
I The strength of the supporting deck is
crucial for the anchoring of the fastening
elements. If there is doubt about the
strength, e.g. of old pumice stone orlightweight concrete panels, pullout tests
will be necessary to define the amount offasteners depending on the object.
Sketch Parapet flashing/ capping with
Gripfix strips.
m a x .
5 0 c m
m a x .
1 0 c m
Gripfix strip
Gripfix strip
16
![Page 17: TM Rhepanol g](https://reader031.vdocuments.site/reader031/viewer/2022021220/577cdc0c1a28ab9e78a9bd53/html5/thumbnails/17.jpg)
7/28/2019 TM Rhepanol g
http://slidepdf.com/reader/full/tm-rhepanol-g 17/73
Rhepanol® fkmechanically fastened with Gripfix systemApplication techniques 17
ᕃ Lightweight concrete
ᕄ Gripfix strip, mechanically fastened
ᕅ Rhepanol fk, laid perpendicularly to the
Gripfix strips
Examples of layer build-ups
Non-ventilated roof (warm roof)
ᕃ Profiled steel decking
ᕄ Vapour barrier fk
ᕅ Mineral fibre boards
ᕆ Gripfix strip, mechanically fastened,
laid perpendicularly to the corrugations
ᕇ Rhepanol fk, laid perpendicularly to the
Gripfix strips
ᕃ Profiled steel decking
ᕄ Vapour barrier fk
ᕅ Thermal insulation layer
ᕆ Fire retarding layer fk
ᕇ Gripfix strip, mechanically fastened,
laid perpendicularly to the corrugations
ᕈ Rhepanol fk, laid perpendicularly to the
Gripfix strips
Layer build-ups
ᕇᕅ
ᕄ
ᕃ
ᕆ
ᕈᕇ
ᕆᕅ
ᕄ
ᕅ
ᕄ
ᕃ
ᕃ
![Page 18: TM Rhepanol g](https://reader031.vdocuments.site/reader031/viewer/2022021220/577cdc0c1a28ab9e78a9bd53/html5/thumbnails/18.jpg)
7/28/2019 TM Rhepanol g
http://slidepdf.com/reader/full/tm-rhepanol-g 18/73
Rhepanol® fkmechanically fastened with Gripfix system Application techniques
Layer build-ups
Examples of layer build-ups
Ventilated roof (cold roof)
ᕃ Timber board cladding*ᕄ Gripfix strip, mechanically fastened,laid perpendicularly to the boards
ᕅ Rhepanol fk, laid perpendicularly to
the Gripfix strips
ᕃ Chipboards*
ᕄ Gripfix strip, mechanically fastened
ᕅ Rhepanol fk, laid perpendicularly to
the Gripfix strips
ᕅ
ᕅ
ᕃ
ᕃ
ᕄ
ᕄ
18
* Note: All sheet timber products must be CE marked (UK only).
![Page 19: TM Rhepanol g](https://reader031.vdocuments.site/reader031/viewer/2022021220/577cdc0c1a28ab9e78a9bd53/html5/thumbnails/19.jpg)
7/28/2019 TM Rhepanol g
http://slidepdf.com/reader/full/tm-rhepanol-g 19/73
Rhepanol® fkmechanically fastened with Gripfix systemTechnical details
Parapet
Non ventilated roof
19
Scale 1:5
ᕃ Galvanized profiled Steel Decking
ᕄ Steel Angle
ᕅ Vapour Control Layer
ᕆ Insulation to Specification
ᕇ Fire retarding Fleece (for use only with
polystyrene Insulation, mechanically fixed)
ᕈ Rhepanol fk mechanically fixed
with Gripfixᕉ Linear Perimeter Fixing
ᕊ Sealing Tape for Vapour Control Layer
ᕋ Rhepanol fk-Flashing Strip
ᕍᕠ Rhepanol-Contact Adhesive No. 11
ᕍᕗ Continuous Steel Angle
ᕍᕘ Aluminium Foil
ᕍᕙ Sealing Tape
ᕍᕚ Capping
ᕍᕛ External Cladding Panel
ᕍᕜ Airtight Sealing Tape
![Page 20: TM Rhepanol g](https://reader031.vdocuments.site/reader031/viewer/2022021220/577cdc0c1a28ab9e78a9bd53/html5/thumbnails/20.jpg)
7/28/2019 TM Rhepanol g
http://slidepdf.com/reader/full/tm-rhepanol-g 20/73
Rhepanol® fkmechanically fastened with Gripfix system Technical details
Parapet
Non ventilated roof
20
Scale 1:5
ᕃ Galvanised profiled Steel Decking
ᕄ Steel Angle
ᕅ Vapour Control Layer
ᕆ Insulation to Specification
ᕇ Fire retarding Fleece (for use only with
polystyrene Insulation, mechanically fixed)
ᕈ Rhepanol fk, mechanically fixed
with GripFix
ᕉ Linear Perimeter Fixing
ᕊ Sealing Tape for Vapour Control Layer
ᕋ Rhepanol fk-Flashing Strip
ᕍᕠ Rhepanol-Contact Adhesive No. 11
ᕍᕗ Continuous Steel Angle
ᕍᕘ Aluminium Foil
ᕍᕙ Sealing Tape
ᕍᕚ Capping
ᕍᕛ External Cladding
ᕍᕜ Airtight Sealing Tape
ᕍᕝ GripFix Strip
![Page 21: TM Rhepanol g](https://reader031.vdocuments.site/reader031/viewer/2022021220/577cdc0c1a28ab9e78a9bd53/html5/thumbnails/21.jpg)
7/28/2019 TM Rhepanol g
http://slidepdf.com/reader/full/tm-rhepanol-g 21/73
Rhepanol® fkmechanically fastened with Gripfix systemTechnical details
Parapet with Insulation Fillet
Non ventilated roof
21
ᕃ Galvanized profiled Steel Decking
ᕄ Thermal Insulation
ᕅ Steel Angle
ᕆ Vapour Control Layer
ᕇ Insulation to Specification
ᕈ Insulation Fillet
ᕉ Fire retarding Fleece (for use only with
polysyrene Insulation, mechanically fixed)
ᕊ Rhepanol fk, mechanically fixedwith GripFix
ᕋ Linear Perimeter Fixing
ᕍᕠ Sealing Tape for Vapour Control Layer
ᕍᕗ Rhepanol fk-Flashing Strip
ᕍᕘ Rhepanol-Contact Adhesive No. 11
ᕍᕙ Continuous Steel Angle
ᕍᕚ Aluminium Foil
ᕍᕛ Sealing Tape
ᕍᕜ Capping
ᕍᕝ External Cladding Panel
ᕍᕞ Airtight Sealing Tape
ᕍᕟ GripFix Strip
Scale 1:5
![Page 22: TM Rhepanol g](https://reader031.vdocuments.site/reader031/viewer/2022021220/577cdc0c1a28ab9e78a9bd53/html5/thumbnails/22.jpg)
7/28/2019 TM Rhepanol g
http://slidepdf.com/reader/full/tm-rhepanol-g 22/73
Rhepanol® fkmechanically fastened with Gripfix system Technical details
Parapet
Non ventilated roof
22
Scale 1:5
ᕃ Reinforced Concrete
ᕄ Vapour Control layer
ᕅ Insulation to Specification
ᕆ Fire retarding Fleece (for use only
with polystyrene Insulation,
mechanically fixed)
ᕇ Rhepanol fk, mechanically fixedwith GripFix
ᕈ Linear Perimeter Fixing
ᕉ Sealing Tape for Vapour Control Layer
ᕊ Insulation as Specification
ᕋ GripFix Strips
ᕍᕠ Rhepanol fk-Flashing Strip
ᕍᕗ Treated Timber Profile
ᕍᕘ Rhepanol-Contact Adhesive
No. 11
ᕍᕙ Roof Edge Trim
ᕍᕚ GripFix Strip
![Page 23: TM Rhepanol g](https://reader031.vdocuments.site/reader031/viewer/2022021220/577cdc0c1a28ab9e78a9bd53/html5/thumbnails/23.jpg)
7/28/2019 TM Rhepanol g
http://slidepdf.com/reader/full/tm-rhepanol-g 23/73
Rhepanol® fkmechanically fastened with Gripfix systemTechnical details
Wall connection
Non ventilated roof
23
Scale 1:5
ᕃ Galvanized profiled Steel Decking
ᕄ Thermal Insulation
ᕅ Steel Angle
ᕆ Vapour Control Layer
ᕇ Insulation to Specification
ᕈ Fire retarding Fleece (for use only, with
polystyrene Insulation, mechanically fixed)
ᕉ Linear Perimeter Fixing
ᕊ Rhepanol fk, mechanically fixedwith GripFix
ᕋ Sealing Tape for Vapour Control Layer
ᕍᕠ Rhepanol fk-Flashing Strip
ᕍᕗ Insulation as Specification
ᕍᕘ Z-Profile
ᕍᕙ Fixing Profile
ᕍᕚ Corrugated Steel Sheet
ᕍᕛ Insulation as Specification
ᕍᕜ Airtight Sealing Tape
ᕍᕝ Steel Structure
ᕍᕞ External Cladding
ᕍᕟ Corrugated Steel Sheet
![Page 24: TM Rhepanol g](https://reader031.vdocuments.site/reader031/viewer/2022021220/577cdc0c1a28ab9e78a9bd53/html5/thumbnails/24.jpg)
7/28/2019 TM Rhepanol g
http://slidepdf.com/reader/full/tm-rhepanol-g 24/73
Rhepanol® fkmechanically fastened with Gripfix system Technical details
Rooflight Connection
Non ventilated roof
24
-Scale 1:5
ᕃ Steel Angle
ᕄ Galvanized profiled Steel Decking
ᕅ Vapour Control Layer fk
ᕆ Thermal Insulation to Specification
ᕇ Rhepanol fk, mechanically fixed
with GripFix
ᕈ Fixing
ᕉ Thermal Insulation to Specification
ᕊ GripFix Strip
ᕋ Rhepanol fk-Flashing Strip
ᕍᕠ Rooflight
ᕍᕗ Rhepanol-Contact Adhesive No. 11
ᕍᕘ Rooflight Kerb
ᕍᕙ Sealing Tape for Vapour Control Layer
![Page 25: TM Rhepanol g](https://reader031.vdocuments.site/reader031/viewer/2022021220/577cdc0c1a28ab9e78a9bd53/html5/thumbnails/25.jpg)
7/28/2019 TM Rhepanol g
http://slidepdf.com/reader/full/tm-rhepanol-g 25/73
Rhepanol® fkmechanically fastened with Gripfix systemTechnical details
Rooflight Connection
Non ventilated roof
25
Scale 1:5
ᕃ Reinforced Concrete
ᕄ Vapour Control Layer
ᕅ Insulation to Specification
ᕆ Fire retarding Fleece (for use only with
polystyrene Insulation, mechanically fixed)
ᕇ Sealing Tape for Vapour Control Layer
ᕈ Rhepanol fk, mechanically fixed
with GripFix
ᕉ Linear Perimeter Fixing
ᕊ Rhepanol fk-Flashing Strip
ᕋ Rhepanol-Contact Adhesive No. 11
ᕍᕠ Rooflight Kerb
ᕍᕗ Render
ᕍᕘ Metal Lathing
ᕍᕙ GripFix Strip
![Page 26: TM Rhepanol g](https://reader031.vdocuments.site/reader031/viewer/2022021220/577cdc0c1a28ab9e78a9bd53/html5/thumbnails/26.jpg)
7/28/2019 TM Rhepanol g
http://slidepdf.com/reader/full/tm-rhepanol-g 26/73
Rhepanol® fkmechanically fastened with Gripfix system Technical details
Vent pipe
Non ventilated roof/Ventilated roof
26
Maßstab 1:5
ᕃ Steel angle
ᕄ Thermal Insulation Collar
ᕅ Galvanized profiled Steel Decking
ᕆ Fixing
ᕇ Vapour Control Layer
ᕈ Thermal Insulation to Specification
ᕉ Rhepanol fk, mechanically fixedwith GripFix
ᕊ Sealing tape for Vapour Control Layer
ᕋ GripFix Ring
ᕍᕠ Rhepanol Collar, Self welding Sealing
ᕍᕗ Vent Pipe Hood-removable
ᕍᕘ Vent Pipe
ᕍᕙ Sealing Skirt
ᕍᕚ Timber Deck
![Page 27: TM Rhepanol g](https://reader031.vdocuments.site/reader031/viewer/2022021220/577cdc0c1a28ab9e78a9bd53/html5/thumbnails/27.jpg)
7/28/2019 TM Rhepanol g
http://slidepdf.com/reader/full/tm-rhepanol-g 27/73
Rhepanol® fkmechanically fastened with Gripfix systemTechnical details
Cold roof ventilator
Ventilated roof
27
Scale 1:5
ᕃ Timber Deck
ᕄ Rhepanol fk
ᕅ GripFix Ring
ᕆ Rhepanol Collar, Self-welding / Sealing
ᕇ Fixing
ᕈ Cold Roof Ventilator Weather Cap
ᕉ Cold Roof Ventilator
ᕊ Sealing Skirt
![Page 28: TM Rhepanol g](https://reader031.vdocuments.site/reader031/viewer/2022021220/577cdc0c1a28ab9e78a9bd53/html5/thumbnails/28.jpg)
7/28/2019 TM Rhepanol g
http://slidepdf.com/reader/full/tm-rhepanol-g 28/73
Rhepanol® fkmechanically fastened with Gripfix system Technical details
Lightning Conductor Collar
Non ventilated roof
28
Scale 1:5
ᕃ Thermal Insulation to Specification
ᕄ Rhepanol fk mechanically fixed
ᕅ Fixing with Counter sunk Screw
ᕆ Rhepanol Collar
with Self-welding Sealing
ᕇ Cutting Edge for 50 mm Pipe
ᕈ Lightning Conductor Collar
ᕉ Jubilee Clip
ᕊ Lightning Conductor
![Page 29: TM Rhepanol g](https://reader031.vdocuments.site/reader031/viewer/2022021220/577cdc0c1a28ab9e78a9bd53/html5/thumbnails/29.jpg)
7/28/2019 TM Rhepanol g
http://slidepdf.com/reader/full/tm-rhepanol-g 29/73
Rhepanol® fk
loosely laid with ballast 29
School centre, Stadthagen/ Germany
Edinburgh conference centre/ United Kingdom
Eurocontrol, Haren/ Belgium
![Page 30: TM Rhepanol g](https://reader031.vdocuments.site/reader031/viewer/2022021220/577cdc0c1a28ab9e78a9bd53/html5/thumbnails/30.jpg)
7/28/2019 TM Rhepanol g
http://slidepdf.com/reader/full/tm-rhepanol-g 30/73
Rhepanol® fkloosely laid with ballast Application techniques
Safety and functional efficiency
Because of loose laying, the roof covering is
separated from the other layers of the build-upacross the complete area. Movements andcracks in the supporting construction are not
transferred into the roof covering.
The ballast ensures the membrane remains
secure against wind uplift forces.
Rhepanol fk is compatible with bitumen and can
be applied without additional separation layers
directly on old bituminous sheets.
The integrated, highly tear-resistant synthetic
fleece of Rhepanol fk allows diffusion,ensuring reliable vapour pressure compensation.
Furthermore the fleece backing provides
protection against stresses originating fromthe substrate.
Application instructions
Supporting construction
I The supporting deck structure has to meet
the requirements with regard to load-bearing
capacity, deflection, anchorage and drainage.
I Clean, dry and even roof surfaces.
I If Rhepanol fk is directly laid on concrete
decks/screed allow the concrete/screed to
set for at least 28 days.
I Substrates for application must be free of
open cracks, rough concrete, sharp edges
and stones.
I Joints have to be formed according to
constructional requirements, as their width
or movement may impede the functionalefficiency of the roof sealing.
Safety and functional efficiency,
supporting construction,vapour control layer
I The roof slope should not exceed 3° to prevent
the ballast slipping off.
I An intrusion of air underneath the roofcovering at the roof perimeter and at roofpenetrations must be prevented. Therefore
these areas have to be made windtight.
I For compatibility reasons, timber board clad-
ding, chipboards and similar may be treatedonly with salt-based wood preservatives. Oil
or solvent based impregnation agents must
not be used.
I National standards and regulations must beobserved.
Vapour control layer
In the case of non-ventilated roofs, werecommend the following vapour control layers:
I For non air-conditioned rooms (e.g. living
rooms and offices or similar rooms without
suspended ceiling): vapour barrier fk (poly-ethylene) with µ x s = 120 m.
In the case of lightweight concrete supporting
decks with correctly calculated thermal insulation,
you may leave out a vapour control layer, if theroom temperature stays below 20 °C and the
relative air humidity inside the room will not
exceed 65 %.
The vapour barrier fk can be laid with differentoverlap: either 10 cm if sealing the seams with
connection or seam tape, or 20 cm loose overlap
(without seam connection in the area).
Preconditions:
– seamless solid deck and– dimensionally stable insulation material,
µ larger than 40, e.g. polystyrene,
– standard room air conditions.
30
![Page 31: TM Rhepanol g](https://reader031.vdocuments.site/reader031/viewer/2022021220/577cdc0c1a28ab9e78a9bd53/html5/thumbnails/31.jpg)
7/28/2019 TM Rhepanol g
http://slidepdf.com/reader/full/tm-rhepanol-g 31/73
Rhepanol® fkloosely laid with ballastApplication techniques 31
Thermal insulation layer,
Rhepanol
®
fk, loosely laid,ballast
I For rooms with high air condition loads (e.g.
swimming pools, air-conditioned rooms):
– aluminium compound foils,
– vapour control membrane with metal tapereinforcement, e.g. AL + V 60 S 4.
I National standards and regulations must be
observed.
Thermal insulation layer
You must bear in mind tread-fastness when
designing the thermal insulation layer on steel
profile supporting decks. Quality assured rigid
polystyrene foam boards with rebated edgeand a length of max. 1.25 m are especially
suitable materials for thermal insulation layers.
With roof areas for walking on, insulation
materials with higher compression strength,e.g. rigid polystyrene foam, must be used in
accordance with the expected loads.
Insulation materials that are not dimensionally
stable and which buckle or bulge must not beinstalled.
The insulation elements must be laid with
pressed joints in bond.
National standards and regulations must be
observed.
Rhepanol fk, loosely laid
Rhepanol fk roofing membrane is loosely laid
with a seam overlap of 5 cm. The membrane
seams are quickly sealed with the prefabricated
self-sealing edge almost independent from
weather conditions. At all flashings and cap-pings, built-in details etc. you will need linear
perimeter fixing with at least 4 fastening
elements/m.
Ballast
Immediately apply ballast on loosely laid
roofing membranes to secure its positionagainst wind uplift.
Suitable materials are:
I bulk gravel layers, min. 5 cm thick, washed
natural uncrushed stones, fraction 16/32.
I paving slabs in a fine gravel bed on a
protection layer.
If appropriate gravel is not available or thegravel is applied pneumatically, then, as under
paving slabs, you will need an additional pro-tection layer (e.g. synthetic fleece or protection
sheet TS fk). Under screed you will have
to apply the protection sheet TS fk.
PE layers and coarse rubber protective sheets
must have an underlying synthetic fleece layer.
Inner area
min. 5 cmbulk gravel
min. 5 cmbulk gravel
Perimeter area
min. 7 cmbulk gravel
min. 11 cmbulk gravel
Corner area
min. 7 cmbulk gravel
min. 11 cmbulk gravel
Height ofeavesabove ground
0 – 8 m
over 8–20 m
For ballast, the provisions of national wind load
standards must be observed.
At building heights over 20 m and for roofs
with high wind exposure (e.g. tower-style,
detached buildings, airplane hangars and
buildings near the coast) it is necessary to
define appropriate object-related measuresfor membrane position stability.
Examples for ballast
![Page 32: TM Rhepanol g](https://reader031.vdocuments.site/reader031/viewer/2022021220/577cdc0c1a28ab9e78a9bd53/html5/thumbnails/32.jpg)
7/28/2019 TM Rhepanol g
http://slidepdf.com/reader/full/tm-rhepanol-g 32/73
Rhepanol® fkloosely laid with ballast Application techniques
Flashings and cappings,
roof refurbishment,layer build-ups
Flashings and cappings
All flashings and cappings are carried out
with Rhepanol fk flashing strips. With flashingheights of over 20 cm, full-size adhesivebonding of the covering at the upstand is
necessary. Valley areas are left unbonded at a
width of 20 cm to allow movement compen-
sation. The upper edge of the Rhepanol fk
roofing membrane is pressed to the substratewith rigid wall connection profiles such as
“Classic” and additionally secured with sealant
A or S. The two-part FDT roof edge trims
ensure flexible, yet windproof capping of theroof perimeter.
The forming of flashings and cappings is iden-tical for all application methods. You will find
details on this topic in the drawings “Technicaldetails”.
Additional requirements for roof
refurbishment:
I Thoroughly sweep the roof area. Removeany blisters, projections and coarse rough-
ness.
I On rough substrates (such as pressed gravel),
a protection layer is necessary. We recom-mend polystyrene insulation boards, which
provide additional insulation at the same
time.
I Temporary storage of gravel must not exceedthe maximum load of the supporting deck.
I Soiled gravel must be cleaned (e.g. by
sieving). Otherwise, appropriate protection
layers such as synthetic fleece 300 g/m2
must be applied.
ᕃ Timber board cladding/derived timber products
ᕄ Rhepanol fk
ᕅ Bulk gravel, fraction 16/32
ᕃ Timber board cladding/derived timber products
ᕄ Rhepanol fk
ᕅ Protection layer, e.g. protection sheet TS fk
ᕆ Gravel layer, fraction 8/16, min. 3 cm thick
ᕇ Paving slabs, e.g. 50/50/5 cm
Examples of layer build-ups
Ventilated roof (cold roof)
ᕆ
ᕇ
ᕃ
ᕄ
ᕅ
ᕃ
ᕄ
ᕅ
32
![Page 33: TM Rhepanol g](https://reader031.vdocuments.site/reader031/viewer/2022021220/577cdc0c1a28ab9e78a9bd53/html5/thumbnails/33.jpg)
7/28/2019 TM Rhepanol g
http://slidepdf.com/reader/full/tm-rhepanol-g 33/73
Rhepanol® fkloosely laid with ballastApplication techniques 33
Layer build-ups
ᕃ Reinforced concrete
ᕄ Vapour barrier fk
ᕅ Thermal insulation layer
ᕆ Rhepanol fk
ᕇ Bulk gravel, fraction 16/32
ᕃ Reinforced concrete
ᕄ Vapour barrier fk
ᕅ Thermal insulation
ᕆ Rhepanol fk
ᕇ Protection layer, e.g. protection sheet TS fk
ᕈ Gravel layer, fraction 8/16, min. 3 cm thick
ᕉ Paving slabs, e.g. 50/50/5 cm
Examples of layer build-ups
Non-ventilated roof (warm roof)
ᕆ
ᕇ
ᕃ
ᕄ
ᕅ
ᕆ
ᕇ
ᕈ
ᕉ
ᕃ
ᕄ
ᕅ
ᕃ Lightweight concreteᕄ Rhepanol fk
ᕅ Bulk gravel
ᕃ
ᕄ
ᕅ
![Page 34: TM Rhepanol g](https://reader031.vdocuments.site/reader031/viewer/2022021220/577cdc0c1a28ab9e78a9bd53/html5/thumbnails/34.jpg)
7/28/2019 TM Rhepanol g
http://slidepdf.com/reader/full/tm-rhepanol-g 34/73
Technical details34Rhepanol® fkloosely laid with ballast
Parapet
Non ventilated roof
Scale 1:5
ᕃ Reinforced Concrete
ᕄ Vapour Control Layer fk
ᕅ Thermal Insulation to Specification
ᕆ Rhepanol fk loosley laid
ᕇ Min. 50 mm round washed Gravel
(20 – 40 mm)
ᕈ Linear Perimeter Fixing
ᕉ Sealing Tape for Vapour Control Layer
ᕊ Adhesive bond
ᕋ Thermal Insulation to Specification
ᕍᕠ Rhepanol fk-Flashing Strip
ᕍᕗ Rhepanol-Contact Adhesive No. 11
ᕍᕘ Treated Timber Profile
ᕍᕙ Capping
ᕍᕚ Cladding
![Page 35: TM Rhepanol g](https://reader031.vdocuments.site/reader031/viewer/2022021220/577cdc0c1a28ab9e78a9bd53/html5/thumbnails/35.jpg)
7/28/2019 TM Rhepanol g
http://slidepdf.com/reader/full/tm-rhepanol-g 35/73
Technical details 35Rhepanol® fkloosely laid with ballast
Parapet
Non ventilated roof
Scale 1:5
ᕃ Reinforced Concrete
ᕄ Vapour Control Layer fk
ᕅ Thermal Insulation to Specification
ᕆ Rhepanol fk loosley laid
ᕇ Min. 50 mm round washed Gravel
(20 – 40 mm)
ᕈ Linear Perimeter Fixing
ᕉ Adhesive bond
ᕊ Sealing Tape for Vapour Control Layer
ᕋ Thermal Insulation to Specification
ᕍᕠ Rhepanol fk Flashing Strip
ᕍᕗ Rhepanol-Contact Adhesive No. 11
ᕍᕘ Treated Timber Profile
ᕍᕙ FDT-Roof EdgeTrim
ᕍᕚ Cladding
![Page 36: TM Rhepanol g](https://reader031.vdocuments.site/reader031/viewer/2022021220/577cdc0c1a28ab9e78a9bd53/html5/thumbnails/36.jpg)
7/28/2019 TM Rhepanol g
http://slidepdf.com/reader/full/tm-rhepanol-g 36/73
Technical details36Rhepanol® fkloosely laid with ballast
Wall Connection
Non ventilated roof
Scale 1:5
ᕃ Reinforced Concrete
ᕄ Vapour Control Layer fk
ᕅ Thermal Insulation to Specification
ᕆ Rhepanol fk loosley laid
ᕇ Min. 50 mm round washed Gravel(20 – 40 mm)
ᕈ Linear Perimeter Fixing
ᕉ Rhepanol fk-Flashing Strip
ᕊ Sealing Tape for Vapour Control Layer
ᕋ Adhesive bond
ᕍᕠ Thermal Insulation to Specification
ᕍᕗ FDT-Wall Connection Profile
ᕍᕘ Flashing
ᕍᕙ Treated Timber Profile
ᕍᕚ FDT Acrylic Paste
ᕍᕛ Blockwork
![Page 37: TM Rhepanol g](https://reader031.vdocuments.site/reader031/viewer/2022021220/577cdc0c1a28ab9e78a9bd53/html5/thumbnails/37.jpg)
7/28/2019 TM Rhepanol g
http://slidepdf.com/reader/full/tm-rhepanol-g 37/73
Technical details 37Rhepanol® fkloosely laid with ballast
Rooflight connection
Non ventilated roof
Scale1:5
ᕃ Reinforced Concrete
ᕄ Vapour Control Layer fk
ᕅ Thermal Insulation to Specification
ᕆ Rhepanol fk loosley laid
ᕇ Sealing Tape for Vapour Control Layer
ᕈ Min. 50 mm round washed Gravel
(20 – 40 mm)
ᕉ Linear Perimeter Fixing
ᕊ Rhepanol fk-Flashing Strip
ᕋ Rhepanol-Contact Adhesive No. 11
ᕍᕠ Rooflight Upstand
ᕍᕗ Render Finish
ᕍᕘ Metal Lathing
![Page 38: TM Rhepanol g](https://reader031.vdocuments.site/reader031/viewer/2022021220/577cdc0c1a28ab9e78a9bd53/html5/thumbnails/38.jpg)
7/28/2019 TM Rhepanol g
http://slidepdf.com/reader/full/tm-rhepanol-g 38/73
Rhepanol® fk
bonded fixing
John Dewards Ltd,United Distillers,
Scotland/United Kingdom
Galerie Monnaie, Brussels/Belgium
38
Television tower, Hamburg/Germany
Canary Wharf, London/ United Kingdom
![Page 39: TM Rhepanol g](https://reader031.vdocuments.site/reader031/viewer/2022021220/577cdc0c1a28ab9e78a9bd53/html5/thumbnails/39.jpg)
7/28/2019 TM Rhepanol g
http://slidepdf.com/reader/full/tm-rhepanol-g 39/73
Rhepanol® fkbonded fixingApplication techniques 39
Safety and functional efficiency,
supporting structure,vapour control layer
Safety and functional efficiency
Bonding Rhepanol fk in stripes ensures maximum
possible mobility of the roofing membrane. Theintegrated, highly tear-resistant synthetic fleece
of Rhepanol fk allows diffusion, thus ensuring
reliable vapour pressure compensation and
secure bonding to the substrate. Rhepanol fk iscompatible with bitumen and can be bonded
without additional separation layers, directly to
old bituminous sheets. The integrated synthetic
fleece protects the membrane against stresses
originating from the substrate.
Application instructions
Supporting construction
I The supporting deck structure has to meet
the technical requirements, especially for load-
bearing capacity, deflection, anchorage and
drainage.
I Substrates for application must be free of open
cracks, rough concrete and sharp projections.
I Joints have to be formed according toconstructional requirements, as their width
or movement may impede the functional
efficiency of the roof sealing.
I An intrusion of air underneath the roofcovering at the roof perimeter and at roof
penetrations must be prevented. Therefore
these areas have to be made windtight.
I Clean, dry and even roof surfaces.
I If Rhepanol fk is directly laid on concrete
decks/screed allow the concrete/screed to
set for at least 28 days.
I The necessity for pre-coating to providereliable adhesion and dust bonding depends
on the substrate conditions.
– Lightweight concrete panels must always
be pre-coated, except when using Rhepanoladhesive 90.
I – It is not necessary to pre-coat coated profiled
steel deckings, except when welding onbituminous sheets (only as bonding agent).
I – National standards and regulations must be
observed.
Vapour control layer
As vapour control layers, in the case of non-
ventilated roofs, we recommend:
I For non air-conditioned rooms (e.g. living
rooms and offices or similar rooms without
suspended ceiling): Vapour control membrane.
In the case of lightweight concrete supporting
decks with correctly calculated thermal insula-tion, you may leave out a vapour control layer,
if the room temperature stays below 20 °C
und the relative air humidity inside the room
will not exceed 65 %.
I For rooms with high air condition loads
(e.g. swimming pools, air-conditioned rooms):
Vapour control membrane with metal tape,
glass fleece or woven glass cloth reinforce-
ment.
In case of doubt, we recommend a calculation
of the building physics in order to identify the
diffusion characteristics of the roof build-up.
![Page 40: TM Rhepanol g](https://reader031.vdocuments.site/reader031/viewer/2022021220/577cdc0c1a28ab9e78a9bd53/html5/thumbnails/40.jpg)
7/28/2019 TM Rhepanol g
http://slidepdf.com/reader/full/tm-rhepanol-g 40/73
Rhepanol® fkbonded fixing Application techniques
Vapour control layer,
thermal insulation layer
With lightweight steel deckings, we also recom-
mend in principle the installation of a separate
vapour control layer, which should be formed as
an air barrier according to the provisions of theThermal Insulation Regulation.
I The vapour barrier must be taken up and
flashed at connections and cappings, at roofpenetrations it must be flashed.
I National standards and regulations must be
observed.
Note:
For bonding the insulation layer with adhesive U,
use vapour control membranes without PEbacking or talcum coating.
Thermal insulation layer
The thermal insulation layer is to be designed in
accordance with the thermal protection require-ments.
As materials for thermal insulation layers we
recommend:
I Folding insulation boards or rigid polystyrenefoam boards with backing.
For fire protection reasons, bituminous sheetswith an integrated glass fleece or fabric
≥ 60 g/m2 may be necessary as a lining.
I Mineral fibre boards or sheets
With bonded application using mineral fibre
insulation material, the type of insulation
material and the adhesive/amount of ad-hesive needed is to be defined depending
on the object.
As a lining, use bituminous sheets without PEbacking.
Generally insulation boards must be laid brick-
bond pattern. Insulation materials that are
not dimensionally stable and which buckle orbulge, or insulation elements with insufficient
lining stability must not be installed.
Bonding of the thermal insulation layer ispreferably done with adhesive U, a one-com-ponent polyurethane adhesive.
For roof slopes exceeding 7°, additional sup-
porting measures are necessary to prevent the
materials slipping off while the adhesive iscuring.
For further information on the adhesive and its
application see data sheet adhesive U.
I National standards and regulations must be
observed.
Inner area
180 g/m2
200 g/m2
Perimeter andcorner area
250 g/m2
300 g/m2
Min. amount ofadhesive stripes/m3)
10
10
Building height2)
0 – 8 m
over 8 – 20 m
Consumption of adhesive U for thermal insulation1)
1) For mineral fibre insulation materials, the adhesive consumption is to be defined depending on the object.
2) Not for tower-style, detached buildings. Not for exposed positions.3) With profiled steel decking, 2 adhesive stripes per corrugation. As the vapour control membrane may sag, the adhesive
stripes must be placed on the corrugation shoulders.
40
![Page 41: TM Rhepanol g](https://reader031.vdocuments.site/reader031/viewer/2022021220/577cdc0c1a28ab9e78a9bd53/html5/thumbnails/41.jpg)
7/28/2019 TM Rhepanol g
http://slidepdf.com/reader/full/tm-rhepanol-g 41/73
Rhepanol® fkbonded fixingApplication techniques 41
Rhepanol® fk
bonded with Rhepanol-Adhesive 90
Rhepanol fk bonded with
Rhepanol-Adhesive 90
With the Rhepanol-Adhesive 90 speciallydesigned for Rhepanol fk, the roofing mem-
brane is securely bonded to the substrate.The adhesive is applied in stripes with at least
8 stripes/m.
Adhesive consumption depends on the place
and height of the building and on the bonding
substrate.
With building heights over 20 m and in the
case of roofs with high wind exposure (e.g.
tower-style, detached buildings, airplane
hangars and buildings near the coast), it isnecessary to define the amount of adhesive
needed or appropriate object-related measures
for membrane position stability.
For roof slopes exceeding 15°, additionalmechanical fastening may be necessary to
prevent the roofing membrane slipping off
while the adhesive is curing. At slopes exceed-
ing 20°, application should be agreed with
our experts. For information on the adhesive,its application and processing see data sheet
Rhepanol-Adhesive 90 (page 63).
Consumption of Rhepanol-Adhesive 90 for the roofing membrane Rhepanol fk1)
160 g/m2
200 g/m2
240 g/m2
280 g/m2
8
8
0 – 8 m
over 8 m – 20 m
1) If the base is of mineral fibre insulation materials the adhesive/adhesive consumption is to be defined depending on the object.2) Not for tower-style detached buildings. Not for exposed positions.
Building height2) Inner area Perimeter and Min. amount ofcorner areas adhesive stripes/m1)
![Page 42: TM Rhepanol g](https://reader031.vdocuments.site/reader031/viewer/2022021220/577cdc0c1a28ab9e78a9bd53/html5/thumbnails/42.jpg)
7/28/2019 TM Rhepanol g
http://slidepdf.com/reader/full/tm-rhepanol-g 42/73
Rhepanol® fkbonded fixing Application techniques
Linear perimeter fixing,
flashings and cappings,roof refurbishment
Linear perimeter fixing
A linear perimeter fixing at flashings and
cappings is necessary with supporting decksmade of galvanized profiled steel.
I In general, with bonded roof build-ups with
mineral fibre insulation materials, independ-
ent from the supporting deck.
The perimeter fixing of the roof build-up,
including the roofing membrane, is achieved
in each instance with at least 4 fixings/m in
line.
Flashings and cappings
All flashings and cappings are carried out with
Rhepanol fk flashing strips. With flashing heightsof over 20 cm, full-size adhesive bonding of the
covering at the upstand is necessary. Valley areas
are left unbonded at a width of 20 cm to allow
movement compensation. The upper edge of
the Rhepanol fk roofing membrane is pressed tothe substrate with rigid wall connection profiles
such as “Classic” and additionally secured with
sealant A or S. The two-part FDT roof edge
trims ensure flexible, yet windproof capping of
the roof perimeter. Forming of flashings andcappings is identical for all application methods.
For drawing example see “Technical details”.
Additional requirements for roof
refurbishment:
I Before overlaying with Rhepanol fk
the adhesion between the old roofing layers,
as well as to the supporting deck must becompletely secure. Otherwise mechanical
fastening will be necessary.
I With old roofs bonded with cold bituminous
adhesive a mechanical fastening of the old
roof is obligatory due to the plastic dimen-sional dynamics of the cold bituminous
adhesive.
I The substrate must be suitable for bonding,free from chippings and thoroughly cleaned.
Sketch Linear perimeter fixing
42
![Page 43: TM Rhepanol g](https://reader031.vdocuments.site/reader031/viewer/2022021220/577cdc0c1a28ab9e78a9bd53/html5/thumbnails/43.jpg)
7/28/2019 TM Rhepanol g
http://slidepdf.com/reader/full/tm-rhepanol-g 43/73
Rhepanol® fkbonded fixingApplication techniques 43
Roof build-up
Examples for layer
build-up
Non-ventilated roof(warm roof)
ᕃ Reinforced concrete
ᕄ Vapour control layer, bondedwith adhesive U
ᕅ Thermal insulation layerconsisting of folding poly-
styrene insulation boards,
with bitumen facing, bondedwith adhesive U
ᕆ Rhepanol fk, bonded with
Rhepanol-Adhesive 90
ᕃ Lightweight concrete,
pre-coated as required
ᕄ Adhesive stripes Rhepanol-Adhesive 90
ᕅ Rhepanol fk, not bonded
over board joints (slidingstrips over cross joints as
required)
ᕆ
ᕃ
ᕃ
ᕄ
ᕄ
ᕅ
ᕅ
ᕃ Timber board cladding
ᕄ Bituminous sheet with
tear-resistant reinforcement,
mechanically fastened,closed seams
ᕅ Adhesive stripes Rhepanol-
Adhesive 90ᕆ Rhepanol fk
Ventilated roof (cold roof)
ᕃ Chipboards/veneer boards
ᕄ Adhesive stripes Rhepanol-
Adhesive 90
ᕅ Rhepanol fk, not bonded
over board joints (sliding
strips as required)
ᕆ
ᕃ
ᕄ
ᕅ
ᕃ
ᕄ
ᕅ
![Page 44: TM Rhepanol g](https://reader031.vdocuments.site/reader031/viewer/2022021220/577cdc0c1a28ab9e78a9bd53/html5/thumbnails/44.jpg)
7/28/2019 TM Rhepanol g
http://slidepdf.com/reader/full/tm-rhepanol-g 44/73
Technical details44Rhepanol® fkbonded fixing
Wall Connection
Non ventilated roof
Scale 1:5
ᕃ Steel Angle
ᕄ Galvanized profiled Steel Decking
ᕅ Steel Angle
ᕆ Cold Bitumen Primer
ᕇ Vapour Control Layer
ᕈ Expanded Polystyrene with
Bituminised Felt facing
ᕉ Rhepanol fk bonded with Adhesive No. 90
ᕊ Linear Perimeter Fixing
(4 piece per meter)
ᕋ Airtight Sealing Tape
ᕍᕠ Blockwork
ᕍᕗ Rhepanol-Contact Adhesive No. 11
ᕍᕘ Rhepanol fk-Flashing Strip
ᕍᕙ Wall connection Profile
ᕍᕚ Sealant A
![Page 45: TM Rhepanol g](https://reader031.vdocuments.site/reader031/viewer/2022021220/577cdc0c1a28ab9e78a9bd53/html5/thumbnails/45.jpg)
7/28/2019 TM Rhepanol g
http://slidepdf.com/reader/full/tm-rhepanol-g 45/73
Technical details 45Rhepanol® fkbonded fixing
Parapet
Non ventilated roof
Scale 1:5
ᕃ Roof structure
ᕄ Sloping screed
ᕅ Existing roofing layers Vapour Control Layer
Thermal Insulation to Specification Bitumen Felt
ᕆ FDT Adhesive U
ᕇ Thermal Insulation to Specification
ᕈ Rhepanol fk bonded with Rhepanol-AdhesiveNo. 90
ᕉ Rhepanol fk-Flashing Strip
ᕊ Thermal Insulation
ᕋ Rhepanol-Contact Adhesive No. 11
ᕍᕠ Treated Timber Profile
ᕍᕗ FDT Roof Edge Trim
![Page 46: TM Rhepanol g](https://reader031.vdocuments.site/reader031/viewer/2022021220/577cdc0c1a28ab9e78a9bd53/html5/thumbnails/46.jpg)
7/28/2019 TM Rhepanol g
http://slidepdf.com/reader/full/tm-rhepanol-g 46/73
Technical details46Rhepanol® fkbonded fixing
Roof Perimeter
Non ventilated roof
0
Scale 1:5
ᕃ Structure
ᕄ Structure
ᕅ Precast Concrete
ᕆ Existing roofing covering Bitumen-Vapour
Control Layer Thermal Insulation to
Specification 3 Layers roofing membrane
ᕇ Expended polystyrene with
Bituminised Felt facing
ᕈ Rhepanol fk bonded with Rhepanol-Adhesive
No. 90 (horizontally) Rhepanol-Contact
Adhesive No. 11 (sloped, vertically)
ᕉ Wall structure
ᕊ Continuous Insulation
ᕋ Rhepanol fk-Flashing Strip
ᕍᕠ Treated Timber Profile
ᕍᕗ FDT Roof Edge Trim
![Page 47: TM Rhepanol g](https://reader031.vdocuments.site/reader031/viewer/2022021220/577cdc0c1a28ab9e78a9bd53/html5/thumbnails/47.jpg)
7/28/2019 TM Rhepanol g
http://slidepdf.com/reader/full/tm-rhepanol-g 47/73
Technical details 47Rhepanol® fkbonded fixing
Parapet
Ventilated roof
Scale 1:5
ᕃ Pre-cast-concrete to falls
ᕄ Rhepanol-Adhesive 90
ᕅ Rhepanol fk bonded
ᕆ Rhepanol fk-Flashing Strip
ᕇ Rhepanol-Contact Adhesive 11
ᕈ Treated Timber Profile
ᕉ Treated Timber Profile
ᕊ FDT-Roof Edge Trim
![Page 48: TM Rhepanol g](https://reader031.vdocuments.site/reader031/viewer/2022021220/577cdc0c1a28ab9e78a9bd53/html5/thumbnails/48.jpg)
7/28/2019 TM Rhepanol g
http://slidepdf.com/reader/full/tm-rhepanol-g 48/73
Technical details48Rhepanol® fkbonded fixing
Rooflight – refurbishment
Non ventilated roof
Scale 1:5
ᕃ Prefabrication Element
ᕄ Existing Roof Layers – Vapour Control Layer
Thermal Insulation to Specification, Bitumen Felt
ᕅ Adhesive U
ᕆ Thermal Insulation to Specification
ᕇ Rhepanol fk bonded with Adhesive No. 90
ᕈ Treated Timber Profile
ᕉ Rhepanol fk-Flashing Strip
ᕊ Rhepanol-Contact Adhesive No. 11
ᕋ FDT Rhepanol-Acrylic Paste
ᕍᕠ Rooflight
ᕍᕗ Thermal Insulation to Specification
ᕍᕘ Timber Profile
![Page 49: TM Rhepanol g](https://reader031.vdocuments.site/reader031/viewer/2022021220/577cdc0c1a28ab9e78a9bd53/html5/thumbnails/49.jpg)
7/28/2019 TM Rhepanol g
http://slidepdf.com/reader/full/tm-rhepanol-g 49/73
Technical details 49Rhepanol® fkbonded fixing
Non ventilated roof
Scale 1:5
ᕃ Steel Construction
ᕄ Steel Angle
ᕅ Galvanized Profiled Steel Decking
ᕆ Vapour Control Layer
ᕇ Thermal Insulation to Specification
ᕈ Rhepanol fk bonded with
Rhepanol-Adhesive No. 90
ᕉ Treated Timber Profile
ᕊ Gutter support bracket
ᕋ Steel Drip Angel
ᕍᕠ Rhepanol-Contact Adhesive No. 11
ᕍᕗ Bonded with contact Rhepanol-Adhesive No. 11
ᕍᕘ Gutter
![Page 50: TM Rhepanol g](https://reader031.vdocuments.site/reader031/viewer/2022021220/577cdc0c1a28ab9e78a9bd53/html5/thumbnails/50.jpg)
7/28/2019 TM Rhepanol g
http://slidepdf.com/reader/full/tm-rhepanol-g 50/73
Technical details50Rhepanol® fkbonded fixing
Building movement joint with upstand
Non ventilated roof
Scale 1:5
ᕃ Reinforced Concrete
ᕄ Cold bitumen primer
ᕅ Vapour control Layer
ᕆ Thermal Insulation to Specification
ᕇ Rhepanol fk bonded with adhesive No. 90
ᕈ Steel Angles at 800 mm c/c
ᕉ Treated Timber Profile
ᕊ Expended polystyrene with Bituminised
Felt facing
ᕋ Rhepanol fk-Flashing Strip
ᕍᕠ Rhepanol-Contact Adhesive No. 11
ᕍᕗ Capping
ᕍᕘ Treated Timber Profile
ᕍᕙ Compressible Thermal Insulation
![Page 51: TM Rhepanol g](https://reader031.vdocuments.site/reader031/viewer/2022021220/577cdc0c1a28ab9e78a9bd53/html5/thumbnails/51.jpg)
7/28/2019 TM Rhepanol g
http://slidepdf.com/reader/full/tm-rhepanol-g 51/73
Technical details 51Rhepanol® fkbonded fixing
Rainwater Outlet
Non ventilated roof
Scale 1:5
ᕃ Structure
ᕄ Precast Concrete
ᕅ Existing roof layers bitumen
Vapour Control Layer Thermal Insulation
3 layers Bitumen Felt
ᕆ Expanded polystyrene
with Bituminised Felt facing
ᕇ Rhepanol fk bonded with Rhepanol-
Adhesive No. 90 (horizontally) withRhepanol-Contact Adhesive No. 11 (sloped)
ᕈ Rhepanol Collar with Self-welding Sealing
ᕉ FDT Rainwater Outlet
ᕊ GripFix collar
![Page 52: TM Rhepanol g](https://reader031.vdocuments.site/reader031/viewer/2022021220/577cdc0c1a28ab9e78a9bd53/html5/thumbnails/52.jpg)
7/28/2019 TM Rhepanol g
http://slidepdf.com/reader/full/tm-rhepanol-g 52/73
Technical details52Rhepanol® fkbonded fixing
FDT VarioGully Outlet
Non ventilated roof
Scale 1:5
ᕃ Rainwater Outlet Fixings (3/Gully)
ᕄ Stiffening Profile
ᕅ Galvanized profiled Steel Decking
ᕆ Vapour Control Layer
ᕇ Cold Bitumen Primer
ᕈ Thermal Insulation to Specification
ᕉ Vapour Control Layer (Collar)
ᕊ FDT Rainwater Outlet
ᕋ GripFix Ring
ᕍᕠ Rhepanol-Collar with Self-welding Sealing
ᕍᕗ Rhepanol fk, bonded with Rhepanol-Adhesive No. 90
![Page 53: TM Rhepanol g](https://reader031.vdocuments.site/reader031/viewer/2022021220/577cdc0c1a28ab9e78a9bd53/html5/thumbnails/53.jpg)
7/28/2019 TM Rhepanol g
http://slidepdf.com/reader/full/tm-rhepanol-g 53/73
Technical details 53Rhepanol® fkbonded fixing
FDT-Rainwater outlet for Refurbishment
Non ventilated roof
Scale 1:5
ᕃ Existing Rainwater Outlet
ᕄ Existing Thermal Insulation
ᕅ Existing Waterproofing Layers (Bitumen)
ᕆ GripFix Ring
ᕇ Sieve
ᕈ Rainwater Outlet Fixings (3/Gully)
ᕉ Rhepanol Collar with Self-welding Sealing
ᕊ Rhepanol fk bonded with Rhepanol-Adhesive
No. 90
ᕋ Screw Ring
ᕍᕠ FDT Rainwalter Outlet fur Refurbishment
![Page 54: TM Rhepanol g](https://reader031.vdocuments.site/reader031/viewer/2022021220/577cdc0c1a28ab9e78a9bd53/html5/thumbnails/54.jpg)
7/28/2019 TM Rhepanol g
http://slidepdf.com/reader/full/tm-rhepanol-g 54/73
Technical details54Rhepanol® fkbonded fixing
Internal gutter closing
Ventilated roof
Scale 1:5
ᕃ Internal gutter
ᕄ Rhepanol-Adhesive No. 90
ᕅ Prestressed concrete
ᕆ Timber profile
ᕇ Bit. Felt mechanically fixed
ᕈ Rhepanol fk bonded with Rhepanol-Adhesive
No. 90
![Page 55: TM Rhepanol g](https://reader031.vdocuments.site/reader031/viewer/2022021220/577cdc0c1a28ab9e78a9bd53/html5/thumbnails/55.jpg)
7/28/2019 TM Rhepanol g
http://slidepdf.com/reader/full/tm-rhepanol-g 55/73
Technical details 55
F D T F l a c
h d a c
h T e c
h n o
l o g
i e G m
b H & C o .
K G
. E d i t i o n
2 0 0 4
Rhepanol® fkbonded fixing
Rhepanol weir overflow pipe
Scale 1:5
ᕃ Reinforced Concrete
ᕄ Rhepanol-Contact Adhesive No. 11
ᕅ Rhepanol fk
ᕆ Rhepanol Collar with Self-welding Sealingwelded with Rhepanol solvent-welding Agent
ᕇ Rhepanol Paste
ᕈ FDT Lightning Conductor Collar
ᕉ Pipe with Spigot and Socket Joint DN 50
ᕊ Rhepanol Collar with Self-welding Sealing
![Page 56: TM Rhepanol g](https://reader031.vdocuments.site/reader031/viewer/2022021220/577cdc0c1a28ab9e78a9bd53/html5/thumbnails/56.jpg)
7/28/2019 TM Rhepanol g
http://slidepdf.com/reader/full/tm-rhepanol-g 56/73
Data sheets
Product information
Accessories
56
![Page 57: TM Rhepanol g](https://reader031.vdocuments.site/reader031/viewer/2022021220/577cdc0c1a28ab9e78a9bd53/html5/thumbnails/57.jpg)
7/28/2019 TM Rhepanol g
http://slidepdf.com/reader/full/tm-rhepanol-g 57/73
Roofing membraneRhepanol® fkData sheet 57
Roofing membrane Rhepanol® fk
Rhepanol® fk
The roofing membrane for all application methods
Rhepanol fk is made of polyisobutylene (PIB), with a prefabricated self-sealing edge and anintegrated synthetic fleece backing. The self-sealing edge makes it easier to seal the seams
and provides a permanently secure joint. The fleece backing provides additional protection
against stresses originating from the substrate. Furthermore, the fleece backing allowsdiffusion and ensures secure fastening onto the substrate.
Rol l out , cle an the seam, pul l off the protec tiv e str ip, pre ss down the edg e – sea led !
Material properties
I Roofing membrane according to
DIN 16731 – PIB-2,5-K-PV.
I Weather-resistant, even without additional
surface protection.
I Resistant to atmospheric influence such as
UV-radiation or exhaust gas from industrial
and heating plants.
I Remains flexible, even at temperatures as
low as – 60 °C.
I Outstanding resistance to natural ageing.
I Free of plasticizers and halogens, resistant to
rotting, non-porous (factory high-frequencytesting).
I Bitumen-resistant.
I Resistant to flying sparks and radiant heat
according to DIN 4102, confirmed by official
test certificates, building materials class B 2.
I In terms of resistance to root penetration
Rhepanol fk meets the test requirements of
DIN 4062, sections 4.7 and 5.7.
I Hail-resistant according to SIA 280.
Not resistant to organic solvents such as benzene,
toluene, paraffin, trichloroethylene; solvent-
containing materials such as lacquers, paints;
fats, oils, such as oily cements, forming oils.
Quality assurance
Rhepanol fk is subject to
constant in-house and externalquality control. The in-house
quality assurance system for
the whole company has been
certified according to DIN EN
ISO 9001, the world’s moststrict quality standard, and is
constantly monitored by TÜV
CERT.
Ecology
Rhepanol fk has gone through
a life cycle assessment according
to ISO EN 14040-49, carried
out by the independent institute
C.A.U. GmbH (Gesellschaftfür Consulting und Analytik im
Umweltbereich) (Company
for Ecological Consulting and
Analytics Ltd.).
FDT will be glad to send youa summary on the life cycle
assessment on request.
Range of application
Depending on the supportingdeck and the substrate
conditions, Rhepanol fk can
be applied in different ways:
I bonded fixing,
I mechanically fastenedwith Gripfix system
I loose laying with ballast
Rhepanol fk with a double-sided self-sealing edge is
used for expansion joints and
flashings.
![Page 58: TM Rhepanol g](https://reader031.vdocuments.site/reader031/viewer/2022021220/577cdc0c1a28ab9e78a9bd53/html5/thumbnails/58.jpg)
7/28/2019 TM Rhepanol g
http://slidepdf.com/reader/full/tm-rhepanol-g 58/73
Roofing membraneRhepanol® fk Data sheet
Rhepanol® fk
58
Material Colour Thickness* Width Length Weight
mm m m kg/m2
Rhepanol fk grey, black, white 2.5 1.05 15 2.60
with synthetic grey, black, white 2.5 1.05 10 2.60
fleece backing grey, black, white 2.5 0.65 15 2.60
grey, black, white 2.5 0.52 15 2.70
grey, black, white 2.5 0.35 15 2.80
Rhepanol fk grey, black, white 2.5 1.05 15 2.70
with double-sided grey, black, white 2.5 0.65 15 2.80
sealing edge grey, black 2.5 0.52 15 2.80
grey, black, white 2.5 0.35 15 2.90
grey, black, white 2.5 0.25 15 3.00
*incl. 1 mm synthetic fleece
Max. tensile force
Elongation atmax. tensile force
Tear-growth resistance
Resistance tohydrostatic pressure
Resistance to perforation
Dimensional stability afterwarm storage (6 h, 80 °C)
Bending at
low temperatures
Resistance to watervapour diffusion
Linear coefficient ofthermal expansion
Area compression strength(no pressure on edges)
Thermal conductivity
Hail resistance
DIN 16726s. 5.6
DIN 16726s. 5.6
DIN 53515
DIN 16726s. 5.11
DIN 16726s. 5.12
DIN 16726s. 5.13
DIN 53361
DIN 16726s. 5.15
DIN 52612/1
SIA 280
N/5 cm
%
N
–
–
%
–
(air = 1)
K–1
N/mm2
W/mK
–
≥ 400
≥ 50
≥ 60
watertight
watertight atfall 600 mm
≤ 0.5
no cracks
at – 60 °C
≥ 260,000
4 x 10–5
10
0.26
passed
Properties Testingaccording to
Unit Value
![Page 59: TM Rhepanol g](https://reader031.vdocuments.site/reader031/viewer/2022021220/577cdc0c1a28ab9e78a9bd53/html5/thumbnails/59.jpg)
7/28/2019 TM Rhepanol g
http://slidepdf.com/reader/full/tm-rhepanol-g 59/73
Vapour barrier fkData sheet 59
Vapour barrier fk
Vapour barrier fk
Made of polyethylene foil (PE).
Works as diffusion retarding layer.
Properties
I Highly vapour-retardant
I Good stability characteristics
I Compatible with bitumen
I Not resistant to UV-radiation
Range of application
I For non air-conditioned rooms (e.g. living rooms
and offices or similar rooms without suspendedceiling).
I In loosely laid or mechanically fastened layer
build-ups with Rhepanol fk.
Physical data
Properties Testing according to DIN Unit Value
Tensile strength 53455 N/mm2 17
Elongation at break 53455 % 450–550
Thermal conductivity 52612 W/m x K 0.35
Water vapour diffusionresistance coefficient µ 53122 (air = 1) 300 000
Air space width equivalent
to water vapour diffusion
(sd = µ x s) m ≥ 120
Forms of supply
Material Colour Nominal thickness Width Length
Vapour barrier fk blue 0.4 mm 4 m 25 m
Sealing tape for vapour barrier fk 8 cm 12 m
Seam tape grey 1.5 cm 25 m
![Page 60: TM Rhepanol g](https://reader031.vdocuments.site/reader031/viewer/2022021220/577cdc0c1a28ab9e78a9bd53/html5/thumbnails/60.jpg)
7/28/2019 TM Rhepanol g
http://slidepdf.com/reader/full/tm-rhepanol-g 60/73
Fire retardant layer fk Data sheet
Fire retardant layer fk
Fire retardant layer fk
A special flame-retarding woven glass clothwith a weight of 175 g/m2.
Range of application
As a fire retardant layer with mechanicalfastening of Rhepanol fk with Gripfix system
at roofs up to 20° slope on unbacked poly-
styrene thermal insulation.
Properties
I Protection against flying sparks andradiant heat
I Easy and clean application
I Membrane width of 2.00 m meanseconomical application
I Resistant to rotting
Application instructions
Rhepanol fk,mechanically fastened with Gripfix system
Fire retardant layer fk
Thermal insulation
Vapour barrier fk
Profiled steel decking,corrosion protected
The fire retardant layer fk is loosely laid under
the Gripfix strips at a seam overlap of 8 cm.
Properties Unit Value
Flame resistance – flame chamber test according to
DIN 4102-1 (A2) passed
Max. tensile force N/50 mm ≥ 1000
Elongation at max. tensile force % ≥ 4
Weight per square metre g/m2 175
Physical data
Form of supply
Material Colour Width Length Weightm m kg/roll
Fire retardant white 2.00 100 approx.layer fk 36
60
![Page 61: TM Rhepanol g](https://reader031.vdocuments.site/reader031/viewer/2022021220/577cdc0c1a28ab9e78a9bd53/html5/thumbnails/61.jpg)
7/28/2019 TM Rhepanol g
http://slidepdf.com/reader/full/tm-rhepanol-g 61/73
Protection layer TS fkData sheet 61
Protection layer TS fk
Protection layer TS fk
Protects the roof sealing.
The protection layer consists of a 1.2 mmnon-rigid PVC membrane with glass fleece
reinforcement, with polyester fleece backing
150 g/m2.The overall thickness is 1.8 mm.
For easy sealing of the seams, the protection
layer TS fk has no fleece backing along the
whole length of one edge.
Range of application
For layer build-ups with synthetic roofing
membrane Rhepanol fk:
I As a separation layer if non-standard gravelis used
I As a protection layer for roof terraces with
paving slabs
Properties
I Protection of the sealing against mechanical
damage
I The fleece backing provides full-size reliable
separation from the sealing layer
I Membrane width of 2.05 m means
economical application
Application instructions
The protection layer TS fk is loosely laid with
the fleece-backed side down.
Depending on the type of application, the
seam connection can be carried out in differentways:
I With 8 cm seam overlap, without sealing.
I For easy sealing of the seams the protection
layer TS fk has no fleece backing along the
whole length of one edge.
I With 5 cm seam overlap and sealing bysolvent or hot air welding.
I With 5 cm seam overlap and sealing with
Rhenofol paste, applied in straight beads in
the centre of the overlap and spread towards
the seam edge by rolling on the overlappedmembrane.
Paste consumption: approx. 30 g/m.
The seams must be closed if used as protection
layer under screed or slabs in a bed of mortar.
The protection layer TS fk is not designed
for weather exposure and must always be
covered.
At the edges of building elements, the protec-
tion layer TS fk is applied in the form of a
loosely overlapping skirt projecting approx.25 cm into the covering area and remaining
unwelded.
Paving slabs
Fine gravel bed
Protection layer TS fk
Rhepanol fk
Thermal insulation
Vapour control layer
Concrete floor
Forms of supply
Colour Width Length Overall thicknessm m mm
grey, 2.05 10 1.8lower side white
![Page 62: TM Rhepanol g](https://reader031.vdocuments.site/reader031/viewer/2022021220/577cdc0c1a28ab9e78a9bd53/html5/thumbnails/62.jpg)
7/28/2019 TM Rhepanol g
http://slidepdf.com/reader/full/tm-rhepanol-g 62/73
Adhesive systemRhepanol-Adhesive 90 Data sheet
Rhepanol-Adhesive 90,
Universal application trolly
Application
I For a stable application of roofing membranes
Rhepanol fkI Is applied in stripes with the Universal
application trolley
I Is supplied in containers that can be
completely drained and thus recycled
Range of application
For bonding of Rhepanol fk on the following
substrates:
I Reinforced concrete
I Lightweight concrete, pre-coated as required
I Chipboards, veneer boards
I New bituminous sheets (also as a lining for
thermal insulation boards and sheets, withoutPE backing)
I Aged bituminous sheets (with solid and cleansurface)
Properties
I Rhepanol-Adhesive 90 is a liquid, solvent-con-taining and synthetic-rubber-based adhesive
I High adhesiveness
I Elastic, no embrittling
I Stable at temperatures from – 40 °C to+130 °C
I High thermal stabilityI Application method which needs no power
supply
Substrate
The substrate has to be solid, even, clean, dry
and free of grease and oil. Polystyrene rigid-
foam boards or sheets must have a bituminousfacing.
Universal applicationtrolly with attached (completelydrainable) 25 kg containers of Rhepanol-Adhesive 90
Application method
The adhesive is applied either with theUniversal application trolley, or manually.
Manual application should be limited to roof
areas that cannot be worked on with the
Universal application trolley, such as small
areas between roof lights.
The Universal application trolley
I Easy to handle application tool which needsno power supply.
I For the application of stripes of Rhepanol-
Adhesive 90 from 25 kg containers. The
amount of adhesive applied is regulated by
the speed of application.
62
![Page 63: TM Rhepanol g](https://reader031.vdocuments.site/reader031/viewer/2022021220/577cdc0c1a28ab9e78a9bd53/html5/thumbnails/63.jpg)
7/28/2019 TM Rhepanol g
http://slidepdf.com/reader/full/tm-rhepanol-g 63/73
Adhesive systemRhepanol-Adhesive 90Data sheet 63
Rhepanol-Adhesive 90
Sloping areas
I At roof slopes over 15°: if necessary, apply
additional mechanical fastening to preventthe roofing membrane slipping off while
the adhesive is curing.
I At roof slopes over 20°: application must be
agreed with our experts.
Curing
I Under normal conditions a sufficient initial
hardness is reached within 4 to 8 hours.
The curing time of the adhesive dependson the evaporation of the solvents. Longer
evaporation time reduces curing time.
Technical data
Base Colour Bulk density Class of hazard Compulsory notification Installation Open(VBF) accord. to Hazardous temperature time
Material Regulationsynthetic white 1.0 g/cm3 A1 yes min. + 5 °C up to 20rubber minutes
depending onthe weather
Adhesive consumption
Building height Adhesive consumption Number of adhesive stripes/mInner area Perimeter and corner area
0 – 8 m1) 160 g/m2 240 g/m2 min. 8
over 8 m – 20 m 200 g/m2 280 g/m2 min. 8
1) At a consumption of 160 g/m2, the running adhesive stripe should be 8 mm wide.
Forms of supply
Product name Form of supply Application
Rhepanol-Adhesive 90 9 kg container for adhesive application with Universal application trolley (using adapter) or
manual application
Rhepanol-Adhesive 90 12 kg container1) for manual adhesive application
Rhepanol-Adhesive 90 25 kg container1) for adhesive application with Universal application trolley
1) Owing to the clamping ring cover, the containers can be completely drained and thus be recycled.
I If bituminous layers are used as a sealing
sublayer curing time may be extended.
However, even in very unfavourable
conditions, the adhesive will be completelyhardened within several days.
Storage
Not frost-proof. Best storage in a dry placeat + 10 °C.
Maximum period of storage: 24 months in
tightly closed original containers.
For further application instructions, see
container and installation instructions
Rhepanol fk.
Hazard identification, safety precautions, transport markings, see EC safety data sheet.
![Page 64: TM Rhepanol g](https://reader031.vdocuments.site/reader031/viewer/2022021220/577cdc0c1a28ab9e78a9bd53/html5/thumbnails/64.jpg)
7/28/2019 TM Rhepanol g
http://slidepdf.com/reader/full/tm-rhepanol-g 64/73
Adhesive U Data sheet
Adhesive U
Application
I For stable bonding of thermal insulation
materials, bituminous vapour control sheetsand bituminous sheets.
I To be applied in stripes with the Universal
application trolley, equipped with a specialadapter.
Properties
I Liquid, one-component solvent and CFC free
polyurethane adhesive
I High adhesiveness
I Elastic, no embrittling
I Stable at temperatures from – 40 to + 100 °C
I High thermal stabilityI Solvent and CFC free, does not affect rigid
polystyrene foam
I Foams and compensates small height
differences of the substrate
I Simple application method which needs no
power supply
I No risk of burning or fire
Substrate
The bonding areas have to be solid, even, clean,
dry and free of grease and oil.
Adhesive consumption
For building heights up to 20 m the consump-
tion and the amount of necessary adhesive
stripes are indicated on page 40 in the table
“Adhesive U consumption for thermal insula-tion”.
For detailed application instructions see the
installation instructions Rhepanol fk and the
containers.
Application method
I With the Universal application trolley and
adapter for adhesive U (6.5 kg containers) foreven substrates.
I Manual application should be limited to roof
areas that cannot be worked on with the appli-cation trolley, such as small areas between roof
lights.
Sloping areas
At roof slopes over 7°:
I Preferably, the adhesive should be applied in
direction of the slope.
I Supporting measures should be applied to
prevent the materials slipping off while theadhesive is curing.
Fascia boards, for example, can be used as
abutment. At roof slopes over 20°, application
must be agreed with our experts.
Curing
I The curing time of the adhesive depends on the
temperature as well as on the ambient humidityand the air humidity. Normally a sufficient initial
hardness is reached within 1 to 3 hours. A slight
moistening reduces the curing time.
I In case of bonding vapour-proof materials, thecuring time may be extended. However, even invery unfavourable conditions, the adhesive will
be completely hardened within several days.
I With high summer temperatures (approx. 25 °C
and above) and low air humidity, it is recom-
mended slightly moistening the substrate afterapplying the adhesive to ensure a sufficient
degree of moisture for foaming.
Universal application trollywith adapter and attached 6.5 kg containers of adhesive U
64
![Page 65: TM Rhepanol g](https://reader031.vdocuments.site/reader031/viewer/2022021220/577cdc0c1a28ab9e78a9bd53/html5/thumbnails/65.jpg)
7/28/2019 TM Rhepanol g
http://slidepdf.com/reader/full/tm-rhepanol-g 65/73
Adhesive UData sheet 65
Adhesive U
Substrates Vapour control, compensation Rigid foam boards Mineral fibre
and separation layers made of and sheets boards/sheets
bituminous sheetsReinforced concrete X
Lightweight concrete with X X
cold bitumen primer
Chipboards X
Steel profile sheets
– with plastic coating X X
– with aluminium-zinc coating X X
– galvanized
with anticorrosive coating X X
Bituminous vapour
control sheets1) X XRigid foam boards/sheets X X
New bituminous sheets1) X X
Old bituminous sheets, if
the surface is solid and clean X X X1) Without PE backing or talcum coating.
Do not use adhesive U for bonding Rhepanol fk!
Technical data
Base Colour Consistence Bulk density Non-volatile Class of
matter hazard
(VBF) isocyanate brownish liquid 1.1 g/cm3 100 % nonprepolymer
Flash point Compulsory notification Installation temperature Open time Height difference
according to Hazardous (air and substrate) compensation
Material Regulation
non yes min. + 5 °C, max. 50 °C up to 15 minutes depending ondepending on humidity, temperature
the weather and amount applied:
scheduled 5 mm
Storage
Not frost-proof Best storage Maximum period of storage
no in a dry place at temperatures from + 10 °C to + 20 °C 12 months in tightly closed original containers.
Form of supply
Product name Form of supply Application
Adhesive U 6.5 kg container Universal application trolly with adapter for adhesive U
Hazard identification, safety precautions, transport markings, see EC safety data sheet.
Range of application
![Page 66: TM Rhepanol g](https://reader031.vdocuments.site/reader031/viewer/2022021220/577cdc0c1a28ab9e78a9bd53/html5/thumbnails/66.jpg)
7/28/2019 TM Rhepanol g
http://slidepdf.com/reader/full/tm-rhepanol-g 66/73
Rhepanol® fk Accessories
Contact adhesive,
sealants,primers,
roof paints
Product name Properties Range of application
Rhepanol-Contact Synthetic-rubber-based For bonding Rhepanol to walls, roof
Adhesive 11 contact adhesive. lights and parapets.
Rhepanol-Adhesive 9 Acryl ic-based dispersion adhesive. For bonding Rhepanol fk to chipboards and
veneer boards on roof slopes of 15°.
Sealant A Solvent-free plasto-elastic Sealing of joints, cracks with limited movementone-component joint sealant stress. Good adhesion to e.g. ceramics, render
(acrylic-based dispersion). finish, brick work, concrete, lightweight concrete,
natural stone.
Sealant S Elastic solvent-containing joint For expansion and connection joints e.g. in thesealant (synthetic rubber based). facade, in glass, in bathrooms and toi lets and on
the roof. Good adhesion to Rhepanol fk.
Primer 1 Blue coloured polymer solution with Bonding agent for Rhepanol-Contact Adhesive 11.
outstanding adhesion to steel, concrete,render finish, wood and rigid PVC.
Primer 2 Transparent polymer solution with Especially reliable adhesive bond is reached,
good adhesion to most nonferrous if coating with primer 2 is followed by coating
metals and special steels. with primer 1.
Primer Precol Black relatively high-viscous Adhesive qualities on various substrates. Bonding
pre-coat with outstanding agent for waterproof connection of Rhepanol
adhesive qualities. to different materials such as concrete, brickwork,
rigid PVC, metal.
Roof paint Special PIB-based roof paint. For a decorative coating of all Rhepanol membranes.
Colours: silver, copper, other colours on request.
66
![Page 67: TM Rhepanol g](https://reader031.vdocuments.site/reader031/viewer/2022021220/577cdc0c1a28ab9e78a9bd53/html5/thumbnails/67.jpg)
7/28/2019 TM Rhepanol g
http://slidepdf.com/reader/full/tm-rhepanol-g 67/73
Rhepanol® fkAccessories 67
Gripfix strips,
sealing and cover tapes,preformed corners,
collars
Product name Properties Range of application
Sealing tape Double-sided self-adhesive, For waterproof connection of Rhepanol fk to
good adhesion. various substrates such as concrete, coatedmetal sheets, in connection with Rhepanolprimer Precol.
Gripfix strips Highly tear-resistant polyester For fastening Rhepanol fk with Gripfix system.
backing with velcro grips. To be fastened with standard fasteners and
washers.
Cover tape With self-sealing edge system, For cross joints and flashings at roofing
as sealing tape on membranes Rhepanol fk.
Rhepanol f-backing.
Internal corner 90° With self-seal ing edge system. Preformed detai l for sealing internal corners at
roofing membranes Rhepanol fk.
Internal corner 90° rapid With self-seal ing edge system. Internal corner with integrated cover tape strips.
External corner 90° With self-seal ing edge system. Preformed detai l for sealing external corners
at roofing membranes Rhepanol fk.
Universal roof light corner With self-seal ing edge system. Preformed detai l for sealing roof light cornersat roofing membranes Rhepanol fk.
Roof light corner With self-seal ing edge system. Preformed detai l for sealing roof light corners,
Universal rapid if the flashing strip projects more than 15 cm
onto the roof area.
Universal collar With self-sealing edge system Preformed detail for built-in details and roof
with Gripfix ring. penetrations at roofing membranes
Rhepanol fk, collar diameter 34 cm.
Collar loose/fixed flange Up to ø 350 mm with self-sealing For all standard rainwater outlets with bolt
edge system and from ø 350 mm connection (6 or 8 holes).
on with Rhepanol f.
EPDM framing ring As set (4 framing rings). For flashing to loose/fixed flange rainwateroutlets at Rhepanol fk.
Rhepanol collar With self-sealing edge system For reliable flashing of Rhepanol fk against the
incl. Gripfix ring. VarioGully. The Gripfix ring replaces contactbonding with Rhepanol-Contact Adhesive 11.
![Page 68: TM Rhepanol g](https://reader031.vdocuments.site/reader031/viewer/2022021220/577cdc0c1a28ab9e78a9bd53/html5/thumbnails/68.jpg)
7/28/2019 TM Rhepanol g
http://slidepdf.com/reader/full/tm-rhepanol-g 68/73
Rhepanol® fk Accessories
VarioGully
VarioGully vertical, DN 125without reducer
Roof penetration Ø 190 mm Roof penetration 190 x 240 mm
Roof penetration 190 x 270 mm
Adjustableto anythermalinsulationthicknessfrom35 mm to240 mmwithoutadditionalparts
VarioGully vertical, DN 125with warm roof upstand,
without reducer
VarioGully vertical, DN 100with reducer DN 125/100
VarioGully angled, DN 100extremely flat, overall height 110 mm,with transition piece DN 70/100
VarioGully angled, DN 125
overall hight 189 mm
VarioGully
I A proven flat roof rainwater outlet, which
is regularly tested by the external testinginstitute LGA Bavaria.
Properties
I Made of rigid PVC with increased impact
strength, including gravel and leaf catcher
and can be used without additional ele-
ments with any layer thickness from 35 to
240 mm.
I In case of heatable VarioGully versions,
the splash-proof installed – not foamed-in –
heater unit is doubly protected by the two
integrated safety systems (heat monitoringrelay and fuse). Connection via safety
transformer 220/24 V (10 W per outlet).
Range of application
I In warm and cold roof structures in vertical
and angled version.
I Corresponding warm roof frames are availa-
ble for insulation material thicknesses from
35 to 160 mm and 160 to 240 mm1). Directconnection to all vapour control membranes
or roofing membranes, or with separately
preformed collar.
ᕃ Rainwater outlet DN 125
ᕄ Insulating sleeve
ᕅ Sealing ring
ᕆ Roofing membrane collar
ᕇ Screw ring
ᕈ Roll ring
ᕉ Warm roof upstand
ᕊ Vapour control layer collar
ᕋ Sieve (leaf guard)
ᕍᕠ Roll ring DN 125
ᕍᕗ Reducer DN 125/100
Nominal Roofs without ballast Gravelled Greenoutlet width Slope roofs roofsDN ≥ 15° ≤ 15°
70 57 70 114 190
100 150 187 300 500125 233 291 466 776
D N 1
0 0
1) Other insulation material thicknesses on request.
68
![Page 69: TM Rhepanol g](https://reader031.vdocuments.site/reader031/viewer/2022021220/577cdc0c1a28ab9e78a9bd53/html5/thumbnails/69.jpg)
7/28/2019 TM Rhepanol g
http://slidepdf.com/reader/full/tm-rhepanol-g 69/73
Rhepanol® fkAccessories 69
VarioGully refurbishment,
accessories for VarioGully: leaf guard
VarioGully refurbishment
I Ensures installation in the existing old roof
without backflow.I Supplied complete with bolts and sealing
cord.
I To be used with old roof outlets up to
DN 150, depending on the diameter of the
run-in area.
Accessories for VarioGully: leaf guard
Made of aluminium with lift ring. For application
on flat roofs with paving slabs or on invertedroofs.
The installation height of 67 to 90 mm can be
adapted to the terrace structure in steps of 3 mm.
With a slab height of 90 mm or more, additional
lift rings will be necessary.
ᕃ Existing old roof rainwater
outlet
ᕄ Existing layer build-up
ᕅ VarioGully refurbishmentᕆ Thermal insulation layer
ᕇ Rhepanol fk
ᕈ Rhepanol-Contact
Adhesive 11 (alternatively
Gripfix ring)
ᕉ Rhepanol collar with
self-sealing edge system
ᕊ Leaf guard
ᕋ Mechanical fastening(4 fast./rainwater outlet)
ᕍᕠ Sealing cord
![Page 70: TM Rhepanol g](https://reader031.vdocuments.site/reader031/viewer/2022021220/577cdc0c1a28ab9e78a9bd53/html5/thumbnails/70.jpg)
7/28/2019 TM Rhepanol g
http://slidepdf.com/reader/full/tm-rhepanol-g 70/73
Rhepanol® fk Accessories
Flat roof vent pipe,
cold roof vent,lightning conductor collar,
wall connection profile/roof edge trim
1 1 0
1 7 5
259595 25 1 1 0
1 7 5
Made of rigid PVC with increased impactstrength. With removable cap and bearing ring.
Ready for installation with integrated collar(Version for Rhepanol fk with self-sealing edgesystem incl. Gripfix ring).
Consisting of an extruded aluminium mountingrail and roll-formed stove enamel cover (colour:silver metal grey, similar to RAL 9007), as wellas plastic clamps for fixing roofing membranesup to 5 mm thickness. Roofing membranes≤
1.5 mm must be folded back once in theclamping area.
Rigid aluminium profile in punched 3 msections. For fixing Rhepanol and Rhenofolroofing membranes at vertical surfaces.Fastening with 5 fasteners per meter, holediameter 6.5 mm.
Highly rigid aluminium profile in punched 4 msections with slot for hooking up metal sheets.For fixing Rhepanol and Rhenofol roofingmembranes at vertical surfaces. Fastening with5 fasteners per meter, hole diameter 6.5 mm.
Rigid aluminium profile in punched 4 msections. For fixing Rhepanol fk roofingmembranes at vertical surfaces. Flashing ofRhepanol fk in the profile. Fastening with5 fasteners per meter, hole diameter 6.5 mm.
With self-sealing edge system and collar.For flashing against lightning protectors andfor penetrations up to ø 51 mm or as water
spout and emergency outlet with connectionto DN 50.
Made of rigid PVC with increased impactstrength. Vent cross-section of 88 cm2.Weather cap can be removed for maintenance.Ready for installation with integrated collar(Version for Rhepanol fk with self-sealing edgesystem incl. Gripfix ring).
Properties/applicationProduct name
Flat roof vent pipe DN 100
Cold roof vent DN 100
Lightning conductor collar Rhepanol
Aluminium wall connection profile
Economy
Aluminium wall connection profile
Classic
Aluminium wall connection profile
Gripfix
Aluminium roof edge trim 110/175
70
![Page 71: TM Rhepanol g](https://reader031.vdocuments.site/reader031/viewer/2022021220/577cdc0c1a28ab9e78a9bd53/html5/thumbnails/71.jpg)
7/28/2019 TM Rhepanol g
http://slidepdf.com/reader/full/tm-rhepanol-g 71/73
Rhepanol® fkTechnical Approval 71
![Page 72: TM Rhepanol g](https://reader031.vdocuments.site/reader031/viewer/2022021220/577cdc0c1a28ab9e78a9bd53/html5/thumbnails/72.jpg)
7/28/2019 TM Rhepanol g
http://slidepdf.com/reader/full/tm-rhepanol-g 72/73
Export department:
Phone +49 621-8504-3 72
Fax +49 6 21- 85 04 -3 78
E-Mail [email protected]
111| 01|05/04| 1500 | GB|