KITCHEN VENTILATION SYSTEMS DESIGN
New Ideas & Technologies 2015
![Page 2: TION STEMS DESIGN - Home Page for the Triangle chapter of ...€¦ · DEMAND CONTROL VENTILATION ... Triangle ASHRAE 2015 Created Date: 20150313134249Z](https://reader033.vdocuments.site/reader033/viewer/2022050521/5fa4a077102cc20964272684/html5/thumbnails/2.jpg)
TOO OFTEN, THE KITCHEN IS...
As suggested by John A. Clark, P.E., Minneapolis
• Hot• Noisy• Smelly• Greasy• Slippery• Energy Consuming
![Page 3: TION STEMS DESIGN - Home Page for the Triangle chapter of ...€¦ · DEMAND CONTROL VENTILATION ... Triangle ASHRAE 2015 Created Date: 20150313134249Z](https://reader033.vdocuments.site/reader033/viewer/2022050521/5fa4a077102cc20964272684/html5/thumbnails/3.jpg)
MODERN SOLUTIONS
• Lowest Exhaust Rate at Peak Performance
• Robust Filtration• Dedicated Makeup Air• Demand Control Ventilation• Factory-Welded Ductwork• Water-Based Fire Suppression
RESULT: Integrated Design
![Page 4: TION STEMS DESIGN - Home Page for the Triangle chapter of ...€¦ · DEMAND CONTROL VENTILATION ... Triangle ASHRAE 2015 Created Date: 20150313134249Z](https://reader033.vdocuments.site/reader033/viewer/2022050521/5fa4a077102cc20964272684/html5/thumbnails/4.jpg)
INTEGRATED KVS DESIGN
• Avoids dynamic effects• Saves energy costs• Ensures peak
performance• Focus on safety,
comfort, efficiency
![Page 5: TION STEMS DESIGN - Home Page for the Triangle chapter of ...€¦ · DEMAND CONTROL VENTILATION ... Triangle ASHRAE 2015 Created Date: 20150313134249Z](https://reader033.vdocuments.site/reader033/viewer/2022050521/5fa4a077102cc20964272684/html5/thumbnails/5.jpg)
LOW EXHAUST RATES
![Page 6: TION STEMS DESIGN - Home Page for the Triangle chapter of ...€¦ · DEMAND CONTROL VENTILATION ... Triangle ASHRAE 2015 Created Date: 20150313134249Z](https://reader033.vdocuments.site/reader033/viewer/2022050521/5fa4a077102cc20964272684/html5/thumbnails/6.jpg)
LOW EXHAUST RATES
• Commercial kitchens are notorious for high energy use
• Poor design, inefficiency• Results in wasted $$$ to
restaurant owner
• Maximizing efficiency is crucial• ASTM1704 & UL710
![Page 7: TION STEMS DESIGN - Home Page for the Triangle chapter of ...€¦ · DEMAND CONTROL VENTILATION ... Triangle ASHRAE 2015 Created Date: 20150313134249Z](https://reader033.vdocuments.site/reader033/viewer/2022050521/5fa4a077102cc20964272684/html5/thumbnails/7.jpg)
ENERGY USE IN RESTAURANTS
RefrigerationSanitationFood PrepCoolingHeatingVentilationOtherLighting
Refrigeration
Sanitation
Food Prep
Heating
Cooling
Lighting
Ventilation
Other
SustainableFoodservice.com
HVAC 29%
![Page 8: TION STEMS DESIGN - Home Page for the Triangle chapter of ...€¦ · DEMAND CONTROL VENTILATION ... Triangle ASHRAE 2015 Created Date: 20150313134249Z](https://reader033.vdocuments.site/reader033/viewer/2022050521/5fa4a077102cc20964272684/html5/thumbnails/8.jpg)
HOW HOODS WORK
Effluent Rises
“Buoyant Thermal Plume”
• Newton (1687) described gravity, by which hot air rises
• Cooking effluents and products of combustion rise
• Effluent volume expands to fill space
![Page 9: TION STEMS DESIGN - Home Page for the Triangle chapter of ...€¦ · DEMAND CONTROL VENTILATION ... Triangle ASHRAE 2015 Created Date: 20150313134249Z](https://reader033.vdocuments.site/reader033/viewer/2022050521/5fa4a077102cc20964272684/html5/thumbnails/9.jpg)
ACHIEVING LOW EXHAUST RATES
• Adequate overhangs & vertical end panels reduce exhaust flow and ensure capture and containment
• Listed duct systems reduce static pressure
![Page 10: TION STEMS DESIGN - Home Page for the Triangle chapter of ...€¦ · DEMAND CONTROL VENTILATION ... Triangle ASHRAE 2015 Created Date: 20150313134249Z](https://reader033.vdocuments.site/reader033/viewer/2022050521/5fa4a077102cc20964272684/html5/thumbnails/10.jpg)
WHAT THE EYE SEES
Courtesy of FSTC CKV Lab
![Page 11: TION STEMS DESIGN - Home Page for the Triangle chapter of ...€¦ · DEMAND CONTROL VENTILATION ... Triangle ASHRAE 2015 Created Date: 20150313134249Z](https://reader033.vdocuments.site/reader033/viewer/2022050521/5fa4a077102cc20964272684/html5/thumbnails/11.jpg)
SCHLIEREN TECHNOLOGYAllows for Accurate Visualization of Air Temperature Gradients
![Page 12: TION STEMS DESIGN - Home Page for the Triangle chapter of ...€¦ · DEMAND CONTROL VENTILATION ... Triangle ASHRAE 2015 Created Date: 20150313134249Z](https://reader033.vdocuments.site/reader033/viewer/2022050521/5fa4a077102cc20964272684/html5/thumbnails/12.jpg)
SCHLIEREN TECHNOLOGY
Courtesy of FSTC CKV Lab
`
![Page 13: TION STEMS DESIGN - Home Page for the Triangle chapter of ...€¦ · DEMAND CONTROL VENTILATION ... Triangle ASHRAE 2015 Created Date: 20150313134249Z](https://reader033.vdocuments.site/reader033/viewer/2022050521/5fa4a077102cc20964272684/html5/thumbnails/13.jpg)
EFFLUENT CIRCULATION
Courtesy FSTC
Effluent circulates
in the hood
Coanda EffectFluid moving past a surface is drawn
to the surface
![Page 14: TION STEMS DESIGN - Home Page for the Triangle chapter of ...€¦ · DEMAND CONTROL VENTILATION ... Triangle ASHRAE 2015 Created Date: 20150313134249Z](https://reader033.vdocuments.site/reader033/viewer/2022050521/5fa4a077102cc20964272684/html5/thumbnails/14.jpg)
VISUALIZE LACK OF OVERHANG FOR FIRE CONDITIONS
![Page 15: TION STEMS DESIGN - Home Page for the Triangle chapter of ...€¦ · DEMAND CONTROL VENTILATION ... Triangle ASHRAE 2015 Created Date: 20150313134249Z](https://reader033.vdocuments.site/reader033/viewer/2022050521/5fa4a077102cc20964272684/html5/thumbnails/15.jpg)
RECOMMENDED OVERHANG
EQUIPMENTOVERHANG
FRONT SIDECharbroiler 18” - 24” 12”
Electric Fryer or Griddle 12” 6”Gas Fryer or Griddle 12” 12”
Conveyor Oven 12” 12” past conveyorConvection Oven 24” 6”
Open Burner Range 12” 12”Range with Shelves or
Salamander 24” 12”
Upright Broilers 18” - 24” 12”Solid Fuel 24” 24”
Woks 24” 24”Dishwasher 12” 24” inlet & discharge
Wall Canopy Hoods
![Page 16: TION STEMS DESIGN - Home Page for the Triangle chapter of ...€¦ · DEMAND CONTROL VENTILATION ... Triangle ASHRAE 2015 Created Date: 20150313134249Z](https://reader033.vdocuments.site/reader033/viewer/2022050521/5fa4a077102cc20964272684/html5/thumbnails/16.jpg)
END PANEL PERFORMANCE
Courtesy FSTC
![Page 17: TION STEMS DESIGN - Home Page for the Triangle chapter of ...€¦ · DEMAND CONTROL VENTILATION ... Triangle ASHRAE 2015 Created Date: 20150313134249Z](https://reader033.vdocuments.site/reader033/viewer/2022050521/5fa4a077102cc20964272684/html5/thumbnails/17.jpg)
VERTICAL END PANEL
![Page 18: TION STEMS DESIGN - Home Page for the Triangle chapter of ...€¦ · DEMAND CONTROL VENTILATION ... Triangle ASHRAE 2015 Created Date: 20150313134249Z](https://reader033.vdocuments.site/reader033/viewer/2022050521/5fa4a077102cc20964272684/html5/thumbnails/18.jpg)
EXHAUST RATES (LISTED VS. IMC)Type of Hood UNLISTED
IMC MINIMUM REQUIRED CFM per Linear Foot of HoodLight Duty Equip Medium Duty Equip Heavy Duty Equip Extra Heavy Duty
EquipUnlisted
Wall Canopy200 300 400 550
Unlisted Backshelf
250 300 400 Not allowed
Type of Hood LISTED
ETL / UL 710
TYPICAL LISTED CFM per Linear Foot of Hood
Light Duty Equip Medium Duty Equip Heavy Duty EquipExtra Heavy Duty
Equip
Listed Wall Canopy
150-200 200-300 200-400 350+
Listed Backshelf
100-200 200-300 300-400 Not recommended
LISTED
ASTM 1704Light Duty Equip Medium Duty Equip Heavy Duty Equip
Extra Heavy Duty Equip
Listed Wall Canopy
175 220 275 300
![Page 19: TION STEMS DESIGN - Home Page for the Triangle chapter of ...€¦ · DEMAND CONTROL VENTILATION ... Triangle ASHRAE 2015 Created Date: 20150313134249Z](https://reader033.vdocuments.site/reader033/viewer/2022050521/5fa4a077102cc20964272684/html5/thumbnails/19.jpg)
EQUIPMENT CLASSIFICATIONLight Duty Equipment
(400-450° F)
Medium Duty Equipment
(400-450° F)
Heavy Duty Equipment (600° F)
Extra Heavy Duty Equipment (700° F)
Ovens
Cheesemelters
Rethermalizers
Steam-Jacketed Kettles
Compartment Steamers
GriddlesFryers
Pasta CookersTilting SkilletsBraising PansRotisseries
Conveyor (Pizza) Ovens
Open-Burner Ranges
Electric/Gas Underfired Broilers
Salamander (Upright) Broilers
Chain Broilers
Wok Ranges
Appliances using Solid Fuel
(Wood, Charcoal, Briquettes and Mesquite) to
provide all or part of the heat source
Source: IMC
![Page 20: TION STEMS DESIGN - Home Page for the Triangle chapter of ...€¦ · DEMAND CONTROL VENTILATION ... Triangle ASHRAE 2015 Created Date: 20150313134249Z](https://reader033.vdocuments.site/reader033/viewer/2022050521/5fa4a077102cc20964272684/html5/thumbnails/20.jpg)
ROBUST FILTRATION
![Page 21: TION STEMS DESIGN - Home Page for the Triangle chapter of ...€¦ · DEMAND CONTROL VENTILATION ... Triangle ASHRAE 2015 Created Date: 20150313134249Z](https://reader033.vdocuments.site/reader033/viewer/2022050521/5fa4a077102cc20964272684/html5/thumbnails/21.jpg)
WHY FILTRATION? EFFLUENT
•Includes gaseous, liquid and solid contaminants•Products of combustion: Carbon monoxide, carbon dioxide and nitrogen oxide
•Harmful to human health, IAQ•Grease Characteristics:
• Both Vapor, Small and Large Particles
• Grease Vapor• Hotter cooking process =
more grease vapor
![Page 22: TION STEMS DESIGN - Home Page for the Triangle chapter of ...€¦ · DEMAND CONTROL VENTILATION ... Triangle ASHRAE 2015 Created Date: 20150313134249Z](https://reader033.vdocuments.site/reader033/viewer/2022050521/5fa4a077102cc20964272684/html5/thumbnails/22.jpg)
GREASE PROBLEMS
• Greasy Exhaust• Rooftop Damage• Environmental Impact• Grease Accumulation Behind Filters• Significant Buildup on Fusible Links• Fire Hazard with Grease Accumulation
in Duct and Plenum
![Page 23: TION STEMS DESIGN - Home Page for the Triangle chapter of ...€¦ · DEMAND CONTROL VENTILATION ... Triangle ASHRAE 2015 Created Date: 20150313134249Z](https://reader033.vdocuments.site/reader033/viewer/2022050521/5fa4a077102cc20964272684/html5/thumbnails/23.jpg)
GREASE PROBLEMS
![Page 24: TION STEMS DESIGN - Home Page for the Triangle chapter of ...€¦ · DEMAND CONTROL VENTILATION ... Triangle ASHRAE 2015 Created Date: 20150313134249Z](https://reader033.vdocuments.site/reader033/viewer/2022050521/5fa4a077102cc20964272684/html5/thumbnails/24.jpg)
GREASE EMISSIONS
ASHRAE RP-745
ASHRAE RP-1375
![Page 25: TION STEMS DESIGN - Home Page for the Triangle chapter of ...€¦ · DEMAND CONTROL VENTILATION ... Triangle ASHRAE 2015 Created Date: 20150313134249Z](https://reader033.vdocuments.site/reader033/viewer/2022050521/5fa4a077102cc20964272684/html5/thumbnails/25.jpg)
FILTER EFFICIENCY TEST
• ASTM F2519: • “Grease Particle Capture Efficiency of
Commercial Kitchen Filters and Extractors”• Pressure drop as function of airflow
through the filter• Particulate capture efficiency by particle
size• Incorporation of filter selection and effect on
design of entire system, including IAQ
![Page 26: TION STEMS DESIGN - Home Page for the Triangle chapter of ...€¦ · DEMAND CONTROL VENTILATION ... Triangle ASHRAE 2015 Created Date: 20150313134249Z](https://reader033.vdocuments.site/reader033/viewer/2022050521/5fa4a077102cc20964272684/html5/thumbnails/26.jpg)
FILTER EFFICIENCY TESTStandard Baffle
Cartridge Filter
HE-1
HE-2
2-Stage
![Page 27: TION STEMS DESIGN - Home Page for the Triangle chapter of ...€¦ · DEMAND CONTROL VENTILATION ... Triangle ASHRAE 2015 Created Date: 20150313134249Z](https://reader033.vdocuments.site/reader033/viewer/2022050521/5fa4a077102cc20964272684/html5/thumbnails/27.jpg)
ROBUST FILTRATION
• Improved baffle design increases grease capture at the source
• S-Baffle + Slotted Rear Baffle = Multi-Stage Filtration
• Issue of grease on the roof solved• Fewer duct cleanings required• Daily manual filter cleaning combined with
integrated self-cleaning of hood plenum results in very little grease, reduced fire risk
![Page 28: TION STEMS DESIGN - Home Page for the Triangle chapter of ...€¦ · DEMAND CONTROL VENTILATION ... Triangle ASHRAE 2015 Created Date: 20150313134249Z](https://reader033.vdocuments.site/reader033/viewer/2022050521/5fa4a077102cc20964272684/html5/thumbnails/28.jpg)
DEDICATED MAKEUP AIR
![Page 29: TION STEMS DESIGN - Home Page for the Triangle chapter of ...€¦ · DEMAND CONTROL VENTILATION ... Triangle ASHRAE 2015 Created Date: 20150313134249Z](https://reader033.vdocuments.site/reader033/viewer/2022050521/5fa4a077102cc20964272684/html5/thumbnails/29.jpg)
MAKEUP AIR PROBLEM?
System design incorporates makeup air tempering and delivery strategy
![Page 30: TION STEMS DESIGN - Home Page for the Triangle chapter of ...€¦ · DEMAND CONTROL VENTILATION ... Triangle ASHRAE 2015 Created Date: 20150313134249Z](https://reader033.vdocuments.site/reader033/viewer/2022050521/5fa4a077102cc20964272684/html5/thumbnails/30.jpg)
MAKEUP AIR• IMC 508.1.1 The temperature differential between
makeup air and the air in the conditioned space shall not exceed 10°F.• Exceptions:
1. Makeup air that is part of the air-conditioning system
2. Makeup air that does not decrease the comfort conditions of the occupied space
![Page 31: TION STEMS DESIGN - Home Page for the Triangle chapter of ...€¦ · DEMAND CONTROL VENTILATION ... Triangle ASHRAE 2015 Created Date: 20150313134249Z](https://reader033.vdocuments.site/reader033/viewer/2022050521/5fa4a077102cc20964272684/html5/thumbnails/31.jpg)
MAKEUP AIR: HOW & WHY
• Do No Harm: Deliver makeup air in an energy efficient manner without harming hood performance
• Makeup Air Options:• HVAC air via displacement diffusers, ceiling
diffusers, or perforated ceiling diffusers• Dedicated MUA: Exhaust hood with integrated
makeup air
![Page 32: TION STEMS DESIGN - Home Page for the Triangle chapter of ...€¦ · DEMAND CONTROL VENTILATION ... Triangle ASHRAE 2015 Created Date: 20150313134249Z](https://reader033.vdocuments.site/reader033/viewer/2022050521/5fa4a077102cc20964272684/html5/thumbnails/32.jpg)
HVAC AIR PROBLEMS
• Higher energy costs• Humidity gains with
continuous RTU cycling • May lead to high transfer air
velocities• Must separate HVAC & MUA
• Directional diffusers must be min.10’ from hood
• Perforated diffusers must be min. 5’ from hood
![Page 33: TION STEMS DESIGN - Home Page for the Triangle chapter of ...€¦ · DEMAND CONTROL VENTILATION ... Triangle ASHRAE 2015 Created Date: 20150313134249Z](https://reader033.vdocuments.site/reader033/viewer/2022050521/5fa4a077102cc20964272684/html5/thumbnails/33.jpg)
DEDICATED MAKEUP AIR APPROACH
![Page 34: TION STEMS DESIGN - Home Page for the Triangle chapter of ...€¦ · DEMAND CONTROL VENTILATION ... Triangle ASHRAE 2015 Created Date: 20150313134249Z](https://reader033.vdocuments.site/reader033/viewer/2022050521/5fa4a077102cc20964272684/html5/thumbnails/34.jpg)
DEDICATED MAKEUP AIR APPROACH
+
Makeup Air Delivery Moderate Heat/Cool
![Page 35: TION STEMS DESIGN - Home Page for the Triangle chapter of ...€¦ · DEMAND CONTROL VENTILATION ... Triangle ASHRAE 2015 Created Date: 20150313134249Z](https://reader033.vdocuments.site/reader033/viewer/2022050521/5fa4a077102cc20964272684/html5/thumbnails/35.jpg)
DEDICATED MAKEUP AIR
• Use DMUA unless all outside is satisfied by ventilation req’s without over-stressing RTUs
• Sensible Heating & Cooling: 55-85° F
• Supply plenum or dual plenum • 80% DMUA: Additional air
provided through HVAC RTU
![Page 36: TION STEMS DESIGN - Home Page for the Triangle chapter of ...€¦ · DEMAND CONTROL VENTILATION ... Triangle ASHRAE 2015 Created Date: 20150313134249Z](https://reader033.vdocuments.site/reader033/viewer/2022050521/5fa4a077102cc20964272684/html5/thumbnails/36.jpg)
DUAL PLENUM APPROACH
![Page 37: TION STEMS DESIGN - Home Page for the Triangle chapter of ...€¦ · DEMAND CONTROL VENTILATION ... Triangle ASHRAE 2015 Created Date: 20150313134249Z](https://reader033.vdocuments.site/reader033/viewer/2022050521/5fa4a077102cc20964272684/html5/thumbnails/37.jpg)
DUAL PLENUM APPROACH
![Page 38: TION STEMS DESIGN - Home Page for the Triangle chapter of ...€¦ · DEMAND CONTROL VENTILATION ... Triangle ASHRAE 2015 Created Date: 20150313134249Z](https://reader033.vdocuments.site/reader033/viewer/2022050521/5fa4a077102cc20964272684/html5/thumbnails/38.jpg)
DUAL PLENUM APPROACH
• Air velocity is critical • 140-160 FPM when plenum is placed 18” above
front edge of hood• 165-185 FPM when plenum is placed 24” above
front edge of hood• Air temperature
• 55-85° F• Supply risers
• Velocity 200-400 FPM• Multiple risers on longer hoods for better
distribution
![Page 39: TION STEMS DESIGN - Home Page for the Triangle chapter of ...€¦ · DEMAND CONTROL VENTILATION ... Triangle ASHRAE 2015 Created Date: 20150313134249Z](https://reader033.vdocuments.site/reader033/viewer/2022050521/5fa4a077102cc20964272684/html5/thumbnails/39.jpg)
VISUAL PERFORMANCE TESTSupply plenum approach aids in capture & containment performance
![Page 40: TION STEMS DESIGN - Home Page for the Triangle chapter of ...€¦ · DEMAND CONTROL VENTILATION ... Triangle ASHRAE 2015 Created Date: 20150313134249Z](https://reader033.vdocuments.site/reader033/viewer/2022050521/5fa4a077102cc20964272684/html5/thumbnails/40.jpg)
PACKAGED MUA UNIT•100% outside air applications
•Moderate tempering as needed
•Satisfies IMC 508.1
•Multiple Stage Cooling
•Up to 600 CFM/ton
![Page 41: TION STEMS DESIGN - Home Page for the Triangle chapter of ...€¦ · DEMAND CONTROL VENTILATION ... Triangle ASHRAE 2015 Created Date: 20150313134249Z](https://reader033.vdocuments.site/reader033/viewer/2022050521/5fa4a077102cc20964272684/html5/thumbnails/41.jpg)
PROPER TEMPERING HEATING
•Direct Fired Heater - 92% efficient
•Indirect Fired
•Electric
•Steam/Hot Water Coils
COOLING
•Direct Expansion (DX)
•Chilled Water Coils
![Page 42: TION STEMS DESIGN - Home Page for the Triangle chapter of ...€¦ · DEMAND CONTROL VENTILATION ... Triangle ASHRAE 2015 Created Date: 20150313134249Z](https://reader033.vdocuments.site/reader033/viewer/2022050521/5fa4a077102cc20964272684/html5/thumbnails/42.jpg)
DEMAND CONTROL VENTILATION
![Page 43: TION STEMS DESIGN - Home Page for the Triangle chapter of ...€¦ · DEMAND CONTROL VENTILATION ... Triangle ASHRAE 2015 Created Date: 20150313134249Z](https://reader033.vdocuments.site/reader033/viewer/2022050521/5fa4a077102cc20964272684/html5/thumbnails/43.jpg)
DEMAND CONTROL VENTILATION
• Automatically adjusts exhaust & makeup air fans according to cooking load
• Temperature sensor and variable frequency drives modulate fan speed
• Satisfies IMC 507.2.1.1, automatic activation requirement
• Rebates and incentives from many utility companies
![Page 44: TION STEMS DESIGN - Home Page for the Triangle chapter of ...€¦ · DEMAND CONTROL VENTILATION ... Triangle ASHRAE 2015 Created Date: 20150313134249Z](https://reader033.vdocuments.site/reader033/viewer/2022050521/5fa4a077102cc20964272684/html5/thumbnails/44.jpg)
FAN ENERGY SAVINGS & PENALTIES
Reduce Exhaust CFM
Savings in Fan Energy
0.1 0.27
0.2 0.47
0.3 0.66
0.4 0.78
0.5 0.87
Increase Exhaust CFM
Increase in Fan Energy
0.1 0.33
0.2 0.73
0.3 1.2
0.4 1.74
0.5 2.37
![Page 45: TION STEMS DESIGN - Home Page for the Triangle chapter of ...€¦ · DEMAND CONTROL VENTILATION ... Triangle ASHRAE 2015 Created Date: 20150313134249Z](https://reader033.vdocuments.site/reader033/viewer/2022050521/5fa4a077102cc20964272684/html5/thumbnails/45.jpg)
EXHAUST TEMPS VARY
74.893'
100.389
75.973
129.976
77.593
129.09
77.307
70
80
90
100
110
120
130
140
6:00:2
0
6:30:2
0
7:00:2
0
7:30:2
0
8:00:2
0
8:30:2
0
9:00:2
0
9:30:2
0
10:00
:20
10:30
:20
11:00
:20
11:30
:20
12:00
:20
12:30
:20
13:00
:20
13:30
:20
14:00
:20
14:30
:20
15:00
:20
15:30
:20
16:00
:20
16:30
:20
17:00
:20
17:30
:20
18:00
:20
18:30
:20
19:00
:20
19:30
:20
20:00
:20
20:30
:20
21:00
:20
21:30
:20
22:00
:20
22:30
:20
23:00
:20
Tem
per
atu
re (
F°)
Time
Golden'Corral'Raleigh,'NC'Sunday'4.24.11'
Grillhouse Pagoda
Pizza Hacienda
Large Buffet Chain Restaurant Raleigh, NC
![Page 46: TION STEMS DESIGN - Home Page for the Triangle chapter of ...€¦ · DEMAND CONTROL VENTILATION ... Triangle ASHRAE 2015 Created Date: 20150313134249Z](https://reader033.vdocuments.site/reader033/viewer/2022050521/5fa4a077102cc20964272684/html5/thumbnails/46.jpg)
FACTORY-WELDED DUCTWORK
![Page 47: TION STEMS DESIGN - Home Page for the Triangle chapter of ...€¦ · DEMAND CONTROL VENTILATION ... Triangle ASHRAE 2015 Created Date: 20150313134249Z](https://reader033.vdocuments.site/reader033/viewer/2022050521/5fa4a077102cc20964272684/html5/thumbnails/47.jpg)
GREASE DUCT ISSUES
• Liquid-tight welded ducts leak• Size and velocity• Static pressure drop• Integrity of welds and joints• Number of tees and elbows• Mitered elbows, non-radius• Access for cleaning• Clearance requirements
![Page 48: TION STEMS DESIGN - Home Page for the Triangle chapter of ...€¦ · DEMAND CONTROL VENTILATION ... Triangle ASHRAE 2015 Created Date: 20150313134249Z](https://reader033.vdocuments.site/reader033/viewer/2022050521/5fa4a077102cc20964272684/html5/thumbnails/48.jpg)
LEAKING DUCT: FIRE RISK
• IMC: Must be fully welded liquid-tight
• Heavy gauge black iron or stainless steel
• Duct leakage test: light bulb, smoke, pressure
![Page 49: TION STEMS DESIGN - Home Page for the Triangle chapter of ...€¦ · DEMAND CONTROL VENTILATION ... Triangle ASHRAE 2015 Created Date: 20150313134249Z](https://reader033.vdocuments.site/reader033/viewer/2022050521/5fa4a077102cc20964272684/html5/thumbnails/49.jpg)
DUCT CONSTRUCTION
IMC 506.3.2 • Joints, seams and penetrations: continuous liquid-
tight weld or braze made on external surface• Exceptions: Penetrations shall not be
required... where sealed by devices listed for application• Internal welding shall not be prohibited
provided that the joint is formed or ground smooth and provided with ready access
• Factory-built commercial kitchen grease ducts listed and labeled
![Page 50: TION STEMS DESIGN - Home Page for the Triangle chapter of ...€¦ · DEMAND CONTROL VENTILATION ... Triangle ASHRAE 2015 Created Date: 20150313134249Z](https://reader033.vdocuments.site/reader033/viewer/2022050521/5fa4a077102cc20964272684/html5/thumbnails/50.jpg)
CLEARANCE TO COMBUSTIBLESIMC 2009• 506.3.6 Grease duct…
serving a Type I hood shall have a clearance to combustible construction of not less than 18 inches (457 mm), and shall have a clearance to noncombustible construction and gypsum wallboard attached to noncombustible structures of not less than 3 inches (76 mm).
Hinged upblast exhaust fan
Roof
Ceiling
Exhaust Hood
10 ft
40inches
18 inches
Grease Duct
NFPA 96-2008 Appendix
Ductwork
![Page 51: TION STEMS DESIGN - Home Page for the Triangle chapter of ...€¦ · DEMAND CONTROL VENTILATION ... Triangle ASHRAE 2015 Created Date: 20150313134249Z](https://reader033.vdocuments.site/reader033/viewer/2022050521/5fa4a077102cc20964272684/html5/thumbnails/51.jpg)
CLEARANCE TO COMBUSTIBLES
• New UL 710 version allows for hoods to have a reduced clearance to combustible rating
• Intended for use adjacent to combustible construction of less than 18” clearance
• Temperatures on adjacent surfaces are measured and limited for rating
• 2 Tests: limited to max 117° F above ambient• 4 Tests: limited to max 175° F above ambient
• Labels include appliance duty classifications
Exhaust Hoods
![Page 52: TION STEMS DESIGN - Home Page for the Triangle chapter of ...€¦ · DEMAND CONTROL VENTILATION ... Triangle ASHRAE 2015 Created Date: 20150313134249Z](https://reader033.vdocuments.site/reader033/viewer/2022050521/5fa4a077102cc20964272684/html5/thumbnails/52.jpg)
FACTORY-BUILT GREASE DUCT
• Listed to UL1978 (Single)• Listed to UL2221 (Double)• 100% Dye Tested at Factory• Improved Fire Safety• No Field Welding• Zero & Reduced Clearance
to Combustible for Double Wall Duct
![Page 53: TION STEMS DESIGN - Home Page for the Triangle chapter of ...€¦ · DEMAND CONTROL VENTILATION ... Triangle ASHRAE 2015 Created Date: 20150313134249Z](https://reader033.vdocuments.site/reader033/viewer/2022050521/5fa4a077102cc20964272684/html5/thumbnails/53.jpg)
ROBUST DUCTWORK DESIGN
• Correct size and velocity• 1500-2000 FPM
• Static pressure drop estimated accurately
• Minimize number of tees and elbows, radius not mitered elbows
• Improved access for cleaning
![Page 54: TION STEMS DESIGN - Home Page for the Triangle chapter of ...€¦ · DEMAND CONTROL VENTILATION ... Triangle ASHRAE 2015 Created Date: 20150313134249Z](https://reader033.vdocuments.site/reader033/viewer/2022050521/5fa4a077102cc20964272684/html5/thumbnails/54.jpg)
WATER-BASED FIRE SUPPRESSION
![Page 55: TION STEMS DESIGN - Home Page for the Triangle chapter of ...€¦ · DEMAND CONTROL VENTILATION ... Triangle ASHRAE 2015 Created Date: 20150313134249Z](https://reader033.vdocuments.site/reader033/viewer/2022050521/5fa4a077102cc20964272684/html5/thumbnails/55.jpg)
RECENT FIRE
![Page 56: TION STEMS DESIGN - Home Page for the Triangle chapter of ...€¦ · DEMAND CONTROL VENTILATION ... Triangle ASHRAE 2015 Created Date: 20150313134249Z](https://reader033.vdocuments.site/reader033/viewer/2022050521/5fa4a077102cc20964272684/html5/thumbnails/56.jpg)
RESTAURANT FIRES
• 5,900 reported restaurant structure fires annually
• $172 million property loss • 75 civilian fire injuries • Cooking is the leading cause
of restaurant fires (41%)• Cooking materials (grease,
oil) were the most frequent items first ignited
US Fire Administration, April 2011
![Page 57: TION STEMS DESIGN - Home Page for the Triangle chapter of ...€¦ · DEMAND CONTROL VENTILATION ... Triangle ASHRAE 2015 Created Date: 20150313134249Z](https://reader033.vdocuments.site/reader033/viewer/2022050521/5fa4a077102cc20964272684/html5/thumbnails/57.jpg)
FIRE SUPPRESSION60 Years of Commercial Kitchen Fire Suppression ASHRAE Journal, June 2014• Proper application and maintenance of suppression
systems is an ongoing challenge• Fires in commercial kitchens most often start in or near
appliances• Fires are often related to inoperative appliance safety
devices
![Page 58: TION STEMS DESIGN - Home Page for the Triangle chapter of ...€¦ · DEMAND CONTROL VENTILATION ... Triangle ASHRAE 2015 Created Date: 20150313134249Z](https://reader033.vdocuments.site/reader033/viewer/2022050521/5fa4a077102cc20964272684/html5/thumbnails/58.jpg)
FIRE SUPPRESSIONSection 509 - Fire Protection System509.1 Where Required: Commercial cooking appliances
required by section 507.2.1 to have a Type I hood shall be provided with an approved automatic fire suppression system complying with the building code.
System Requirements:• Tested and Listed to UL300 Standard • Automatic activation • Means of manual operation • Appliance surface protection • Hood plenum and duct collar
![Page 59: TION STEMS DESIGN - Home Page for the Triangle chapter of ...€¦ · DEMAND CONTROL VENTILATION ... Triangle ASHRAE 2015 Created Date: 20150313134249Z](https://reader033.vdocuments.site/reader033/viewer/2022050521/5fa4a077102cc20964272684/html5/thumbnails/59.jpg)
SYSTEM TYPES
• Wet Chemical Systems• Discharge chemical agent• Appliance-specific protection and/or
overlapping protection• Water-Based Systems
• Discharge water and surfactant• Total flooding of hazard area
• Combination Systems• Discharge water and chemical agent
![Page 60: TION STEMS DESIGN - Home Page for the Triangle chapter of ...€¦ · DEMAND CONTROL VENTILATION ... Triangle ASHRAE 2015 Created Date: 20150313134249Z](https://reader033.vdocuments.site/reader033/viewer/2022050521/5fa4a077102cc20964272684/html5/thumbnails/60.jpg)
WATER-BASED FIRE SUPPRESSION
• Temperature detection with electronic activation
• Sprays appliances, hood plenum, exhaust duct
• Reliable: Continuous flow until fire is completely extinguished
• Meets UL300, IMC, and NFPA96
• Electronic monitoring and communication
![Page 61: TION STEMS DESIGN - Home Page for the Triangle chapter of ...€¦ · DEMAND CONTROL VENTILATION ... Triangle ASHRAE 2015 Created Date: 20150313134249Z](https://reader033.vdocuments.site/reader033/viewer/2022050521/5fa4a077102cc20964272684/html5/thumbnails/61.jpg)
UL300 TESTING FOR HOOD FIRE SUPPRESSION SYSTEM
![Page 62: TION STEMS DESIGN - Home Page for the Triangle chapter of ...€¦ · DEMAND CONTROL VENTILATION ... Triangle ASHRAE 2015 Created Date: 20150313134249Z](https://reader033.vdocuments.site/reader033/viewer/2022050521/5fa4a077102cc20964272684/html5/thumbnails/62.jpg)
SUMMARY
• Exhaust Flow Rates are critical: Find balance between low exhaust rate and peak performance
• Robust Filtration reduces greasy effluent, improves IAQ
• Dedicated MUA results in peak efficiency • Demand Control Ventilation allows for greatest fan
energy savings• Factory-Welded Ductwork results in best
performance, fewest leaks and fires• Water-Based Fire Suppression ensures highest
safety, significantly reduced fire risk
![Page 63: TION STEMS DESIGN - Home Page for the Triangle chapter of ...€¦ · DEMAND CONTROL VENTILATION ... Triangle ASHRAE 2015 Created Date: 20150313134249Z](https://reader033.vdocuments.site/reader033/viewer/2022050521/5fa4a077102cc20964272684/html5/thumbnails/63.jpg)
RESULT: INTEGRATED KITCHEN DESIGN
Streamlined KVS Design, from Hood to Fan