PERIMETER INSULATION FROM RISING WALL TO UNDERSIDE OF EXTERNAL INSULATION TO REDUCE THE IMPACT OF THERMAL BRIDGING AIRTIGHT LAYER SEALED AT FLOOR SLAB EXISTING CONCRETE WINDOW CILLS REMOVED AND REPLACED WITH PRESSED METAL CILLS WITH EXTERNAL INSULATION RETURNED TO UNDERSIDE OF CILL 150MM KINGSPAN KOOLTHERM K7 EXTERNAL INSULATION AIRTIGHT LAYER PLASTERED INTO WINDOW REVEAL & TAPED TO WINDOW FRAME EXISTING 215MM MASS CONCRETE WALL EXISTING 18MM PEBBLEDASH FINISH 10MM POLYMER RENDER FINISH 18MM PLASTER INTERNALLY 200MM REINFORCED CONCRETE SLAB VISQUEEN RADON MEMBRANE 200MM KINGSPAN KOOLTHERM K3 FLOORBOARD 75MM CONCRETE SCREED WITH UNDERFLOOR HEATING PIPES 18MM ENGINEERED SEMI-SOLID TIMBER FLOORING LAID ON SIKABOND LIQUID BATTEN SYSTEM 150MM KINGSPAN K5 EXTERNAL WALL INSULATION 10MM POLYMER RENDER FINISH EXISTING DOUBLE GLAZED WINDOWS REMOVED & REPLACED WITH NEW TRIPLE GLAZED THERMALLY BROKEN MUNSTER JOINERY PASSI V ALUCLAD WINDOWS AIRTIGHT LAYER PLASTERED INTO WINDOW REVEAL & TAPED TO WINDOW FRAME EXTERNAL INSULATION FIXED TO EXISTING PEBBLEDASH RENDER & RETURNED TO MEET THE NEW WINDOW FRAME uPVC FASCIA GRILLE UNIT FIXED WITH THERMALLY BROKEN FIXINGS TO FASCIA BOARD EAVES VENTILATOR TRAY SKIRT DRESSED INTO GUTTER CRYOGEL Z FLEXIBLE AEROGEL BLANKET INSULATION uPVC EAVES VENTILATOR TRAY 100MM KNAUF EARTHWOOL RAFTER ROLL 32 TYVEK SUPRO BREATHER MEMBRANE KINGSPAN KOOLTHERM K7 PITCHED ROOF BOARD 100MM KNAUF EARTHWOOL RAFTER ROLL 32 BETWEEN CEILING JOISTS WITH 200MM KNAUF EARTHWOOL RAFTER ROLL 32 LAID DRESSED OVER TYVEK SD2 VCL VAPOUR BARRIER STUDY DINING LIVING FAMILY AREA WC BEDROOM BEDROOM LANDING BATHROOM STAIRS STORE STORE EXTERNAL INSULATION FIXED TO EXISTING RENDERED WALLS EXISTING DOUBLE GLAZED WINDOWS REMOVED & REPLACED WITH NEW TRIPLE GLAZED THERMALLY BROKEN WINDOWS ADDITIONAL INSULATION INSTALLED IN ATTIC SPACE & ALONG SLOPED CEILING & EAVES VENTILATION ADDED BUILDING EXTENDED TO THE REAR TO CREATE A MORE FEXIBLE LAYOUT & MAXIMISE THE RETURN ON THE INVESTMENT EXISTING FLOOR REMOVED & REPLACED WITH NEW CONRETE FLOOR WITH INSULATION & UNDERFLOOR HEATING WINDOWS 0.6 W/m2K FLAT ROOF 0.15 W/m2K ROOFLIGHT 1.24W/m2K SLOPED CEILING 0.13 W/m2K FLAT CEILING 0.12W/m2K FLOOR 0.09 W/m2K WINDOWS 0.6 W/m2K WALLS 0.14 W/m2K HEAT PUMP MANIFOLD FLOOR STANDING UNIT SOLAR COLLECTORS EXPANSION VESSEL WALLS U VALUE & CONDENSATION DIAGRAM FLAT CEILING U VALUE & CONDENSATION DIAGRAM SLOPED CEILING U VALUE & CONDENSATION DIAGRAM FLAT ROOF U VALUE & CONDENSATION DIAGRAM GROUND FLOOR U VALUE & CONDENSATION DIAGRAM nZEB GROUND FLOOR RETROFIT LAYOUT nZEB FIRST FLOOR RETROFIT LAYOUT CUTAWAY VIEW OF RETROFIT LAYOUT MODEL VIEW OF RETROFIT FABRIC MEASURES AXO VIEW OF FIRST FLOOR AXO VIEW OF EXTENDED GROUND FLOOR EXISTING BASELINE BER END OF TERRACE EXISTING BASELINE BER MID & GABLE TERRACE nZEB RETROFIT BER DETAIL SECTION THROUGH RETROFIT WALL AT GROUND FLOOR LEVEL DETAIL SECTION THROUGH RETROFIT WALL AT FIRST FLOOR LEVEL DETAIL SECTION THROUGH RETROFIT WALL AT CEILING/ROOF LEVEL VIEW FROM KITCHEN TO NEW FAMILY AREA VIEW OF KITCHEN / DINING AREA VIEW FROM FAMILY AREA OF KITCHEN / DINING AREA VIEW FROM LIVING STUDY AREA CALCULATED U VALUES THROUGH RETROFITTED FABRIC ELEMENTS VIEW OF EXTENSION TO THE REAR OF THE CRUMLIN COTTAGE HEATING SCHEMATIC THROUGH RETROFITTED CRUMLIN COTTAGE PRIMARY ENERGY USAGE COMPARISION FOR BASELINE & RETROFIT HEAD & EAVES HEAD ONLY GROUND FLOOR CORNER OPE - LINTEL OPE - JAMB END OF TERRACE BASELINE FABRIC HEAT LOSS END OF TERRACE RETROFIT FABRIC HEAT LOSS END OF TERRACE BASELINE HEAT USAGE END OF TERRACE RETROFIT HEAT USAGE CILL

Upload: others

Post on 12-Aug-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: TIM LAVIN D14124545 - PROJECT NO.6 - YEAR 2015 · cutaway view of retrofit layout model view of retrofit fabric measures axo view of first floor axo view of extended ground floor

PERIMETER INSULATION FROM RISING WALL TOUNDERSIDE OF EXTERNAL INSULATION TO REDUCETHE IMPACT OF THERMAL BRIDGING

AIRTIGHT LAYER SEALED AT FLOOR SLAB

EXISTING CONCRETE WINDOW CILLS REMOVED ANDREPLACED WITH PRESSED METAL CILLS WITHEXTERNAL INSULATION RETURNED TO UNDERSIDEOF CILL

150MM KINGSPAN KOOLTHERM K7EXTERNAL INSULATION

AIRTIGHT LAYER PLASTERED INTO WINDOWREVEAL & TAPED TO WINDOW FRAME

EXISTING 215MM MASS CONCRETE WALL

EXISTING 18MM PEBBLEDASH FINISH

10MM POLYMER RENDER FINISH

18MM PLASTER INTERNALLY

200MM REINFORCED CONCRETE SLAB

VISQUEEN RADON MEMBRANE

200MM KINGSPAN KOOLTHERM K3 FLOORBOARD

75MM CONCRETE SCREED WITH UNDERFLOOR HEATINGPIPES

18MM ENGINEERED SEMI-SOLID TIMBER FLOORING LAID ONSIKABOND LIQUID BATTEN SYSTEM

150MM KINGSPAN K5 EXTERNAL WALLINSULATION

10MM POLYMER RENDER FINISH

EXISTING DOUBLE GLAZED WINDOWS REMOVED &REPLACED WITH NEW TRIPLE GLAZEDTHERMALLY BROKEN MUNSTER JOINERY PASSI VALUCLAD WINDOWS

AIRTIGHT LAYER PLASTERED INTO WINDOWREVEAL & TAPED TO WINDOW FRAME

EXTERNAL INSULATION FIXED TO EXISTINGPEBBLEDASH RENDER & RETURNED TO MEET THENEW WINDOW FRAME

uPVC FASCIA GRILLE UNIT FIXED WITHTHERMALLY BROKEN FIXINGS TO FASCIA BOARD

EAVES VENTILATOR TRAY SKIRT DRESSED INTOGUTTER

CRYOGEL Z FLEXIBLE AEROGEL BLANKETINSULATION

uPVC EAVES VENTILATOR TRAY

100MM KNAUF EARTHWOOL RAFTER ROLL 32

TYVEK SUPRO BREATHER MEMBRANE

KINGSPAN KOOLTHERM K7 PITCHEDROOF BOARD

100MM KNAUF EARTHWOOL RAFTER ROLL 32BETWEEN CEILING JOISTS WITH 200MM KNAUFEARTHWOOL RAFTER ROLL 32 LAID DRESSEDOVER

TYVEK SD2 VCL VAPOUR BARRIER

STUDY

DINING

LIVING

FAMILYAREA

WC

BEDROOM

BEDROOM

LANDING

BATHROOM

STAIRS

STORE

STORE

EXTERNAL INSULATION FIXED TOEXISTING RENDERED WALLS

EXISTING DOUBLE GLAZEDWINDOWS REMOVED & REPLACEDWITH NEW TRIPLE GLAZEDTHERMALLY BROKEN WINDOWS

ADDITIONAL INSULATION INSTALLEDIN ATTIC SPACE & ALONG SLOPEDCEILING & EAVES VENTILATION ADDED

BUILDING EXTENDED TO THE REAR TOCREATE A MORE FEXIBLE LAYOUT &MAXIMISE THE RETURN ON THE INVESTMENT

EXISTING FLOOR REMOVED & REPLACEDWITH NEW CONRETE FLOOR WITH INSULATION& UNDERFLOOR HEATING

WINDOWS 0.6 W/m2K

FLAT ROOF 0.15 W/m2K

ROOFLIGHT 1.24W/m2K

SLOPED CEILING 0.13 W/m2K

FLAT CEILING 0.12W/m2K

FLOOR 0.09 W/m2K

WINDOWS 0.6 W/m2K

WALLS 0.14 W/m2K

HEAT PUMP

MANIFOLD

FLOORSTANDINGUNIT

SOLARCOLLECTORS

EXPANSIONVESSEL

WALLS U VALUE & CONDENSATION DIAGRAM FLAT CEILING U VALUE & CONDENSATION DIAGRAM SLOPED CEILING U VALUE & CONDENSATION DIAGRAM FLAT ROOF U VALUE & CONDENSATION DIAGRAM GROUND FLOOR U VALUE & CONDENSATION DIAGRAM

nZEB GROUND FLOOR RETROFIT LAYOUT nZEB FIRST FLOOR RETROFIT LAYOUT

CUTAWAY VIEW OF RETROFIT LAYOUT MODEL VIEW OF RETROFIT FABRICMEASURES

AXO VIEW OF FIRST FLOOR AXO VIEW OF EXTENDED GROUND FLOOR

EXISTING BASELINE BEREND OF TERRACE

EXISTING BASELINE BERMID & GABLE TERRACE

nZEB RETROFIT BER

DETAIL SECTION THROUGH RETROFITWALL AT GROUND FLOOR LEVEL

DETAIL SECTION THROUGH RETROFIT WALLAT FIRST FLOOR LEVEL

DETAIL SECTION THROUGH RETROFITWALL AT CEILING/ROOF LEVEL

VIEW FROM KITCHEN TO NEW FAMILY AREA

VIEW OF KITCHEN / DINING AREA

VIEW FROM FAMILY AREA OF KITCHEN / DINING AREA

VIEW FROM LIVING STUDY AREA

CALCULATED U VALUES THROUGH RETROFITTED FABRIC ELEMENTS

VIEW OF EXTENSION TO THE REAR OF THE CRUMLIN COTTAGE

HEATING SCHEMATIC THROUGH RETROFITTED CRUMLIN COTTAGEPRIMARY ENERGY USAGE COMPARISION FOR BASELINE & RETROFIT

HEAD & EAVESHEAD ONLY

GROUND FLOOR

CORNER

OPE - LINTEL

OPE - JAMB

DT 774 - RETROFIT TECHNOLOGY MODULE ARCH - 1280TIM LAVIN D14124545 - PROJECT NO.6 - YEAR 2015

END OF TERRACE BASELINE FABRIC HEAT LOSS END OF TERRACE RETROFIT FABRIC HEAT LOSS

END OF TERRACE BASELINE HEAT USAGE END OF TERRACE RETROFIT HEAT USAGE

CILL