thermal and daylighting performance of automated...

94
1 THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED SPLIT-CONTROLLED BLINDS By DEEPAK V. GOLASANGIMATH A THESIS PRESENTED TO THE GRADUATE SCHOOL OF THE UNIVERSITY OF FLORIDA IN PARTIAL FULFILLMENT OF THE REQUIREMENTS FOR THE DEGREE OF MASTER OF SCIENCE IN BUILDING CONSTRUCTION UNIVERSITY OF FLORIDA 2009

Upload: others

Post on 08-Jul-2020

30 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

1

THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED SPLIT-CONTROLLED BLINDS

By

DEEPAK V. GOLASANGIMATH

A THESIS PRESENTED TO THE GRADUATE SCHOOL OF THE UNIVERSITY OF FLORIDA IN PARTIAL FULFILLMENT

OF THE REQUIREMENTS FOR THE DEGREE OF MASTER OF SCIENCE IN BUILDING CONSTRUCTION

UNIVERSITY OF FLORIDA

2009

Page 2: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

2

© 2009 Deepak V. Golasangimath

Page 3: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

3

To my family and friends, for all the support and guidance they provided throughout my

student life

Page 4: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

4

ACKNOWLEDGMENTS

I would like to thank Dr. Svetlana Olbina for her constant support and motivation

throughout my course work and research. I would also like to thank Dr. Raymond R.

Issa for all his valuable inputs into this research, without his support this research could

not have been completed. I express my gratitude to Mr. Richard Kelley, Senior Systems

Programmer, for his tireless effort to make this research possible by running the

simulations in the computer lab. Also, I would like to thank committee member Dr.

Robert J. Ries for his valuable inputs on the research. I would also like to thank my

parents and my sister for supporting me throughout my education life and to all my

friends for all the ways in which they supported me throughout my research.

Page 5: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

5

TABLE OF CONTENTS page

ACKNOWLEDGMENTS .................................................................................................. 4

LIST OF TABLES ............................................................................................................ 7

LIST OF FIGURES .......................................................................................................... 8

ABSTRACT ................................................................................................................... 10

CHAPTER

1 INTRODUCTION .................................................................................................... 12

Problem Statement ................................................................................................. 12 Research Objectives ............................................................................................... 13 Limitations of Research .......................................................................................... 14

2 LITERATURE REVIEW .......................................................................................... 16

Manually Controlled Blinds ..................................................................................... 16 Automated blinds .................................................................................................... 17 Energy Analysis ...................................................................................................... 18 Blinds Control Strategies ........................................................................................ 19 EnergyPlus and Radiance ...................................................................................... 21

EnergyPlus (EP) ............................................................................................... 21 Radiance .......................................................................................................... 22

3 METHODOLOGY ................................................................................................... 24

Introduction ............................................................................................................. 24 Description of Case Study ...................................................................................... 24

Location and Weather Data: ............................................................................. 26 HVAC ............................................................................................................... 26

Simulations ............................................................................................................. 26 EnergyPlus Inputs ............................................................................................ 28

Selecting the walls and windows ................................................................ 28 Material Regular ......................................................................................... 29 Design Day ................................................................................................ 29 Construction ............................................................................................... 29 Material: Blinds .......................................................................................... 30 Surface(s) .................................................................................................. 30 Lights ......................................................................................................... 30 Schedule .................................................................................................... 31 Daylighting: Detailed .................................................................................. 31 Lighting Control Type ................................................................................. 32

Page 6: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

6

Selecting Input and Weather Files ............................................................. 33 Radiance .......................................................................................................... 34 Quality settings ................................................................................................. 37

Ambient bounces (-ab): .............................................................................. 38 Ambient value (-av): ................................................................................... 38 Ambient Divisions (-ad) .............................................................................. 38

4 RESULTS AND ANALYSIS .................................................................................... 40

Introduction ............................................................................................................. 40 EnergyPlus Results Analysis .................................................................................. 40 Daylighting Analysis ................................................................................................ 42

Choosing Blind Angle ....................................................................................... 48 Radiance Results Analysis ............................................................................... 49

Automation Model ................................................................................................... 65

5 CONCLUSIONS AND RECOMMENDATIONS ....................................................... 67

Conclusions ............................................................................................................ 67 Recommendations .................................................................................................. 68

APPENDIX

A ENERGYPLUS SPECIFICATIONS ........................................................................ 69

B RADIANCE GENERATORS ................................................................................... 72

C RADIANCE SCRIPT ............................................................................................... 73

D ENERGYPLUS INPUTS ......................................................................................... 75

LIST OF REFERENCES ............................................................................................... 92

BIOGRAPHICAL SKETCH ............................................................................................ 94

Page 7: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

7

LIST OF TABLES

Table page 3-1 Example of a Stepped Lighting Control System with Three Steps ...................... 33

4-1 Energy consumption for lighting (W), HVAC (W) and Total Electric Demand (W) for March 21, June 21 and December 21 .................................................... 43

4-2 EnergyPlus Comparison Results ........................................................................ 44

4-3 UDI values for Sensor Point 1 ............................................................................ 50

4-4 UDI values for Sensor Point 2 ............................................................................ 51

4-5 UDI values for Sensor Point 3 ............................................................................ 52

4-6 UDI values for Sensor Point 4 ............................................................................ 53

Page 8: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

8

LIST OF FIGURES

Figure page 1-1 A three-dimensional view of a Google SketchUp image for the proposed split

controlled blind system. The split blinds system is divided into three sections: Top section, Middle section, and Bottom section................................................ 14

3-1 Three-dimensional Google SketchUp view of the office room. ........................... 25

3-2 Top view the office building with the two sensor points positioned on two office desks......................................................................................................... 26

3-3 The input for EnergyPlus was done through the IDF-Editor interface. ................ 28

3-4 The IDF interface for Design Day Input. ............................................................. 29

3-5 Screen shot showing all the necessary variables for the object surface heat transfer. .............................................................................................................. 31

3-6 The first drop-down menu is used for selecting the input file (IDF editor file) created using IDF Editor. .................................................................................... 33

3-7 The second drop-down menu is used for selecting the weather file. .................. 34

3-8 Fish-eye view of a Radiance-rendered image of the office room. ....................... 36

3-9 Close-up view of the office room. ....................................................................... 37

4-1 Energy consumption differences between split-controlled blinds and conventional blinds for March 21st ..................................................................... 45

4-2 Energy consumption differences between split-controlled blinds and conventional blinds for June 21st. ...................................................................... 46

4-3 Energy consumption differences between split-controlled blinds and conventional blinds for December 21 ................................................................. 47

4-4 UDI comparison for Sensor Point 1(SP1). .......................................................... 55

4-5 UDI comparison for Sensor Point 2 (SP2). ......................................................... 56

4-6 UDI comparison for Sensor Point 3 (SP3). ......................................................... 57

4-7 UDI comparison for Sensor Point 4 (SP4). ......................................................... 58

4-8 Frequency distribution of illuminance values from split-controlled blinds for sensor point 1. .................................................................................................... 61

Page 9: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

9

4-9 Frequency distribution of illuminance values from conventional blinds for the first sensor point. ................................................................................................ 61

4-10 Illuminance values for all the split blind angles, at the first sensor point for January 1 at 8 a.m. ............................................................................................. 62

4-11 Average illuminance distribution at the four sensor points. ................................. 62

4-12 Yearly illuminance values at the first sensor point. ............................................. 63

4-13 Yearly illuminance values at the second sensor point. ....................................... 63

4-14 Yearly illuminance values at the first sensor point. ............................................. 64

4-15 Yearly illuminance values at the first sensor point. ............................................. 64

4-16 Automation algorithm for split-controlled blinds. ................................................. 66

Page 10: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

10

Abstract of Thesis Presented to the Graduate School of the University of Florida in Partial Fulfillment of the

Requirements for the Degree of Master of Science in Building Construction

THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED SPLIT-CONTROLLED BLINDS

By

Deepak V. Golasangimath

December 2009

Chair: Svetlana Olbina Cochair: R Raymond Issa Major: Building Construction

This research dealt with the study of thermal and daylighting performance of the

proposed split-controlled blind system, as compared to a conventional Venetian blind

system commonly used in commercial offices. Conventional blinds are most commonly

used for the purpose of blocking direct sunlight and preventing glare to the occupants.

Conventional blinds are not efficiently used to maximize daylight once the direct light is

no longer available. Also, keeping the blinds open for longer periods with direct light

coming inside the building increases the cooling loads for the building. The proposed

split-controlled blinds consist of multiple sections of blinds, each section with a separate

blind angle to allow sufficient daylight inside the building, prevent glare to the occupants

and reduce cooling loads for the office building. The case study for this research

comprised of a simple office room with a south facing window and interior blinds system

installed. EnergyPlus, thermal and energy simulation software and Radiance,

daylighting analysis software were used as tools to simulate the office room. Seven

static blind angle settings in conventional blinds as a base case and 29 split blind angle

settings as a prototype case were simulated by EnergyPlus (EP) and Radiance, to study

Page 11: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

11

the thermal and daylighting performance of the proposed split-controlled blind system.

Conservative energy savings were observed for the split-blinds system for the three

days of energy simulations. Within the comfort range between 500 lux and 2000 lux,

higher average illuminance values with less daylighting fluctuation were observed

during the course of the entire year as a result of using the split-blinds system. No

observable difference in Useful Daylight Illuminances (UDI) performance was observed

between the split-controlled blind system and conventional blind system.

Page 12: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

12

CHAPTER 1 INTRODUCTION

Blinds are the most commonly used shading devices in commercial and residential

buildings. Blinds consist of slats of wood, fabric, or metal which are made to overlap one

another to cover the window. They are operated by rotating the slats from an open

position to a closed position by making them overlap each other.

Venetian blinds consist of horizontal slats connected by cloth stripes called tapes

or chords which help in rotating all the slats in unison from 0 to 180 degrees. In general,

split blinds were defined as conventional Venetian blinds divided into multiple sections.

Each section of the split-controlled blinds would perform a specific function. In this

research, split blinds were divided into three sections. Each section of the split-

controlled blind system had different slat angle covering different sections of the

window.

Figure 1-1 shows split-controlled blind system in which each section performs

different functions:

• The top section performs the function of transmission of low angled daylight so that light penetrates into the remote part of the room.

• The middle section performs the function of allowing all the daylight to come in, and at the same time preventing direct sunlight, which causes glare, thus creating discomfort for occupants.

• The lower section performs the function of not allowing too much heat to come inside and thus prevents overheating of the room.

Problem Statement

Buildings in United States account for 40% of the total energy consumption.

Substantial research has been carried out in the field of sustainable construction to

reduce the amount of energy consumed in buildings. “Research studies related to

Page 13: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

13

advanced glazings and daylighting systems have been made to maximize daylighting

and reduce glare inside the buildings” (Tzempelikos et al.2007). Venetian blinds are one

of the most common shading devices used in most commercial and residential

buildings. Conventional Venetian blinds are most commonly used to block direct

sunlight and prevent glare. Conventional Venetian blinds are rarely used to maximize

daylight penetration into the building. Significant electric lighting energy savings can be

obtained by proper use of daylighting in buildings (Lee et al.1998a). In regions

dominated by warm weather, keeping blinds open for longer periods allows excess heat

inside the building and thus increases the cooling load. A more efficient blind system,

which prevents glare to the occupants and reduces energy consumption in buildings, is

a necessity. The proposed split-controlled blind system performs the function of

providing better daylighting into the building. Split-controlled blind system also reduces

the Heating Ventilation and Air Conditioning (HVAC) load by preventing excess heat

entering the room and allowing sufficient daylighting, which, in turn, reduces the use of

electric lighting.

Research Objectives

The objective of this research was to study thermal and daylighting performance of

a new shading device system, the split-controlled blind system. The thermal and

daylighting performances of split-controlled blinds were compared to the performance of

conventional blinds. This research determined energy savings and useful daylight

illuminance as a result of using the split-controlled blinds.

Thus this research tried to answer the following questions:

• Does split-controlled blind system give higher energy savings and perform better thermally as compared to the conventional blind system?

Page 14: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

14

• Does split-controlled blind system provide higher daylighting levels?

Figure 1-1. A three-dimensional view of a Google SketchUp image for the proposed

split controlled blind system. The split blinds system is divided into three sections: Top section, Middle section, and Bottom section

Limitations of Research

The test facility for this experiment was a small office room 3 m x 3.5 m x 5 m in

size located in Gainesville, Florida. This research was validated by testing the proposed

split-controlled blind system by using two simulation software tools: EnergyPlus and

Radiance. However, it should be noted that this experiment did not take into

consideration other possible external conditions such as a presence of trees and other

sources of shade. The performance of proposed split-controlled blinds is yet to be

tested in complex building systems.

Page 15: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

15

The ability of the software tools used to accurately simulate the desired conditions

is a factor to be considered while validating these theoretical results. Radiance is

considered a highly accurate software program for simulating lighting conditions for

three-dimensional models of buildings, but Radiance requires a high amount of

computing power, as well as a thorough knowledge of daylighting and optics.

EnergyPlus (EP) is considered to be one of the best software engines for energy

simulations of buildings, but it is not the best software to be considered for daylighting

analysis.

Page 16: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

16

CHAPTER 2 LITERATURE REVIEW

The function of a shading device is to prevent glare caused by direct sunlight, as

well as to prevent excess heat entering into the building. Venetian blinds are one of the

most commonly used shading devices in office buildings. Heating/cooling energy

consumption, along with the thermal and visual comfort, is highly affected by the type of

shading device used (Tzempelikos et al. 2007).

Manually Controlled Blinds

Manually controlled blinds perform the function of blocking excess direct light

coming into the building and preventing glare. Excess heat entering through the

fenestration leads to an increase in cooling load for the building (Tzempelikos et al.

2007). The process of manually operating blinds by the occupant is often found to be

cumbersome. Most of the time the user tends to leave the blinds open all day, which

leads to excessive heat coming into the building, thus increasing the cooling load for the

building.

Just the presence of blinds can affect the illuminance level inside the room, when

compared with blinds totally retracted. The horizontal blind slats reduced the illuminance

at a photosensor on the ceiling by 30% to 50% for about eight hours between 6 a.m. to

6 p.m. in September and May, which increased the lighting consumption of the test

room by approximately 30% (Galasiu et al. 2004).

Positioning the blinds with the slats at a 45° upward angle reduced the total

illuminance at the ceiling on average by 45% to 60% in both September and May for

about 8 to 10 hours a day. Results showed that blinds positioned with their slats at a 45°

Page 17: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

17

downward angle reduced the total illuminance at the ceiling photosensor by 40% to 45%

for 7 hours in the spring, and 10 hours in the fall (Galasiu et al. 2004).

Automated blinds

In the case of automated blinds, the slat angle of the blinds is controlled by a

computer program. Dynamic blinds are controlled automatically with the help of a motor

or mechanized system to make the blinds system perform a particular task, such as

block direct sunlight or to maintain a particular illuminance level inside the room.

The category of ‘dynamic’ window technologies encompasses numerous conventional components, such as motorized louvers, venetian blinds, and shades, as well as more advanced glazing systems, such as switchable electrochromics, photochromics, thermochromics, polymer-dispersed liquid crystal glazings, and electrically-heated glazings (Lee et al. 1998b).

However, the potential for a dynamic operation of shading devices through a

building automation system is generally neglected. The impact of shading design and

control on building performance is not taken into account at the design stage, although

an optimum cooling and lighting energy balance between fenestration and lighting may

be identified and utilized (Tzempelikos et al. 2006).

As a result of the dynamic systems control over solar heat gain, reductions in

cooling load were observed. Also lighting energy savings were observed as a result of

dynamic systems ability to control the illuminance levels inside the room. Dynamic

blinds were found to perform better than the static blind system in terms of cooling load

reductions and peak load reduction (Lee et al. 1998b). “Total annual energy savings of

16-26% were attained with the automated blind compared to an unshaded low-E

spectrally-selective window system with the same daylighting controls in Los Angeles,

California” (Lee et al.1998a).

Page 18: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

18

Field data indicated that an automated interior blind with spectrally selective glazing and a less than optimal control algorithm was more than twice as effective at reducing peak solar gains under clear sky conditions as a static unshaded bronze glazing with the same daylighting control system, while providing the same level of useful daylight (Lee et al. 1998b).

Energy Analysis

One of the main purposes of using Venetian blinds as a shading device is to avoid

the flow of excess heat coming into the room, thus increasing the cooling load for the

building.

Even in heating-dominated climates, cooling is important for perimeter spaces with high solar gains. Shading provision is necessary; the properties and control of shading have to be taken into account from the early design stage, since they have a significant impact on peak thermal loads, energy consumption for heating, cooling and lighting, as well as on human comfort (Tzempelikos et al. 2006).

One quarter of total energy usage in the commercial sector is accounted by

lighting energy consumption in buildings, followed by heating, cooling, office equipment

and water heating (Koomey et al. 2001). In one comparative study by Lee et al. (1998a)

the base case was defined as automated blinds with static positions, divided into two

cases, one with daylighting control and one without daylighting control. The prototype

case consisted of automated blinds activated every 30 seconds to maintain illuminance

of 540-700 lux. The same ballast system was used for lighting control in both cases.

Average cooling reductions of 6% to 15% (for 45˚ blind angle) and 17% to 32%

(for 0˚ blind angle) were achieved by the dynamic blinds compared to the static blinds.

Average peak load reductions were 6% to 15% by dynamic blinds as compared to static

blinds (for 45˚blind angle) and 18% to 32% by dynamic blinds as compared to static

blinds (for 0˚ static angle). For the base case without daylighting controls, daily lighting

energy savings by dynamic blinds were 22% to 86% for any static blind angle. Cooling

Page 19: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

19

load reductions for dynamic blinds were on the order of 28 ± 5% as compared to the

static blinds for 0˚ blind angle for clear days in July.

In the case of the static system, an imbalance occurred between cooling load

reductions and lighting energy savings for closed and horizontal position of the blinds.

This balance was achieved in case of the dynamic system. The dynamic system always

blocked direct sunlight and provided view for a maximum of 50% of the day throughout

the year, thus reducing the occupant’s discomfort considerably (Lee et al. 1998a).

Blinds Control Strategies

For climates with moderate daylight availability and for a building type that is

cooling-load dominated, dynamic window technologies can be coupled with daylighting

controls to actively optimize daylight and its respective solar heat gains at the perimeter

zone of commercial buildings (Lee et al. 1998). If automated blinds were interconnected

to a lighting system, such that the amount of electric lighting used was linked with the

daylight available inside the building, sufficient energy savings could be observed. A

variety of control alternatives have been suggested to reduce lighting energy

consumption. Daylight dimming control systems save lighting energy most effectively

since they use daylight as an alternative light source (Kim and Kim, 2007). “The

dimming system had the potential to save between 50% and 60% lighting energy over

the 12-hour period considered (6 a.m. to 6 p.m.) compared to the electric lights being

fully on during the same time interval” (Galasiu et al. 2004). Approximately 20% to 40%

of lighting energy consumption in buildings can be reduced by using daylight dimming

control systems (Kim et al. 2007). However, daylight dimming systems have not been

widely applied to buildings due to the visual problems associated with fluctuating electric

light outputs under varying sky and cloud conditions.

Page 20: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

20

Use of off-the-shelf technology can be made to promote efficient window systems.

For example, (Lee et al. 2004) attempted to develop a low cost networking system for

dynamic window, lighting and sensors devices. Lawrence Berkeley National Laboratory

(LBNL) developed a building communication network, known as the Integral Building

Environment Communication System (IBECS). This system was found to be cheaper

due to a low per point networking cost. This cost-effective network interface for AC/DC

motorized shading and a switchable electrochromic window system was developed by

using a microlan bridge to couple the various devices and sensors in a building with the

existing Ethernet Network. The IBECS achieved significant reductions in per point

networking costs. By making some modifications to the interface between the motor and

the shading devices, such a system can also be applied to all types of motorized

window shading systems (Lee et al. 2004).

In another experiment by Galasiu et al. (2004), 15 photometric sensors were

positioned for measuring exterior as well as interior illuminance levels; three of them

were at the center of the ceiling. These three sensors were set to have partially

shielded, fully shielded and no shielded conditions. The sky conditions were classified

into clear sky conditions and partly cloudy sky conditions. Three blind conditions: no

blind condition, horizontal blinds, and blinds at a 35˚ angle were used in the study. The

shielding conditions used in the photo sensors significantly controlled the daylight

fluctuations caused by the partly cloudy sky conditions. The slat angle of the Venetian

blind used was not a significant factor in controlling or determining the interior

illuminance level. The altitude and azimuth angles were important factors under partly

cloudy sky conditions for causing the change in fluctuations (Galasiu et al. 2004).

Page 21: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

21

EnergyPlus and Radiance

EnergyPlus (EP)

EnergyPlus is a building energy simulation program. Various components of

building dynamics such as heating, cooling, lighting, ventilation, and energy flows, can

be modeled in EnergyPlus. EnergyPlus is a standalone simulation program without a

graphical user interface (GUI). A number of GUIs are being developed to make the

software user friendly. Some of the commonly used GUIs are Open Studio,

EnergyPlugged, DesignBuilder, and ECOTECT.

Building Loads Analysis and System Thermodynamics (BLAST) and DOE-2 are

computer programs used to perform the heating and cooling load calculations for

buildings. Their origins date from the early 1970s. They are primarily used to investigate

the energy performance of new as well as retrofit building design options. They possess

different capabilities, such as peak load calculation and annual energy performance of

building facilities of any size and type.

EnergyPlus was built on the platform of BLAST and DOE-2. EnergyPlus

possesses many of their capabilities with many innovative simulation capabilities, such

as time-step less than an hour, modular systems, and plant integration with heat

balance-based simulation, Multizone airflow, thermal comfort, water use, and natural

ventilation.

The disadvantages of EnergyPlus include:

• EnergyPlus does not have a Graphical User Interface (GUI). Though a number of third party interfaces are being developed, EP is a simulation engine.

• EP is not a life cycle assessment program. EP cannot be used as a Life Cycle Costing (LCC) tool.

Page 22: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

22

• EnergyPlus also cannot be considered as a replacement for an architect or a design engineer. EP inputs and outputs have to be monitored by an engineer or an architect to correctly interpret the results (EnergyPlus Documentation 2008).

Radiance

Radiance is software tool to simulate various lighting conditions. Radiance makes

visualization of lighting effortless in a virtual environment because of the endless

possibilities that arise from its 50 or so tools. These tools can be used to produce

realistic and natural renderings of complex building systems with complex lightings.

Radiance synthesizes images from three-dimensional geometric models. The

model consists of the description of the surface’s shape, size, location, and

composition. Generally, simple surfaces, such as polygons, spheres, and cones, can be

directly modeled in Radiance. A number of other generator programs can be used to

produce more complex shapes, such as boxes, prisms, and surfaces of revolution. More

complex structures, consisting of thousands of surfaces, can be produced separately by

Computer Aided Design (CAD) programs (Larson 1991).

Radiance is UNIX-based software, thus familiarity with the UNIX operating system

is necessary in order to use Radiance.

Radiance performs five main functions:

• Produces shapes of objects in an environment by entering and compiling information by various methods described in Larson and Shakespeare’s book Rendering with Radiance.

• Characterizes the light’s interaction with the surfaces using various mathematical models described in the book.

• Simulates and renders lighting, certain techniques can calculate the propagation of light in an environment, as well as the nature of the values computed.

• Analyzes and manipulates images, the image processing and conversion.

Page 23: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

23

• Creates interactions between automation of rendering and analysis processes and facilitates links to other systems and computing environments (Larson and Shakespeare 1998).

Page 24: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

24

CHAPTER 3 METHODOLOGY

Introduction

This research evaluated the performance of split-controlled blind system by

comparing its thermal and daylighting performance with conventional Venetian blind

system. Two building simulation tools, EnergyPlus (EP) and Radiance, were used to

validate the proposed split-controlled blind system. In EnergyPlus, simulations were

performed for three days: March 21, June 21, and December 21.

Daylighting assessment was done using the software, Radiance. Simulations were

performed for every occupied hour for the entire year to obtain illuminance values for

four sensor points placed one meter from each other. The first sensor point was placed

one meter from the window.

Description of Case Study

The case study involved a small 3 m x 3.5 m x 5 m office room in Gainesville,

Florida. The office room was fitted with a 1.83 m x 1.83 m (6’ x 6’) window (U-

factor=2.69, visible transmittance=0.744) on the south side. The window was glazed

with double insulated glass that consisted of: a 6 mm interior glass (Low emittance

glass (Low-E), conductivity=0.6 W/m-K, thickness=0.006 m, solar transmittance=0.6,

solar reflectance on front side=0.22, solar reflectance on back side=0.17), 13 mm air

space, and a 6 mm Low-E exterior glass. No frame was used for the window.

The wall surface consisted of three layers: concrete with steel connectors on the

outside (thickness=0.15 m, conductivity=1.078 W/m-k, density=2185.44 kg/m3, specific

heat=1173 J/kg-K), an insulation in the middle (thickness=0.1 m, conductivity=0.499

W/m-K, density=1552 kg/ m3, specific heat=880 J/kg-k), and concrete with steel

Page 25: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

25

connectors on the inside (thickness=0.1 m, conductivity=1.329 W/m-k, density=2213 kg/

m3, specific heat=964 J/kg-K). Blinds with high reflective slats were used. Slat width was

0.025 m; slat separation was 0.0187 m and slat conductivity of 0.9 W/m-K.

EnergyPlus simulations were performed for three days of the year, March 21

(maximum dry-bulb temperature equal to 31.7˚ C, barometric pressure equal to 101217,

wind speed equal to 12.9 m/s), June 21 (maximum dry-bulb temperature equal to 34.4˚

C, barometric pressure equal to 101217, wind speed equal to 9.3 m/s) and December

21 (maximum dry-bulb temperature equal to 27.2˚ C, barometric pressure equal to

101217, wind speed equal to 8.8 m/s).

Figure 3-1 shows the three-dimensional model of the office room described in the

case study. This Google SketchUp model was imported into EP using the Plug-in,

OpenStudio.

Figure 3-1. Three-dimensional Google SketchUp view of the office room.

Figure 3-2 shows the top view of the office room. The two sensor points used in

EP were collinearly placed at distance of 0.75 m and 3.5 m with the window’s midpoint

at a height of 0.76 m above the ground level.

Page 26: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

26

Figure 3-2. Top view the office building with the two sensor points positioned on two

office desks.

Location and Weather Data:

The weather file for the Gainesville region was obtained from the U.S Department

of Energy (DOE) Building Technologies (BT) Program website. Elevation of the building

is 41 m above sea level and standard pressure was 100833 Pa. (EnergyPlus Weather

file, 2008).

HVAC

The HVAC system used for the EnergyPlus simulation was Packaged Terminal:

Air Conditioner (PTAC). The PTAC consists of an outside air mixer, direct Expansion

(DX) cooling coil, and a heating coil, which may be run by gas, electricity, hot water,

steam and a supply air fan (EnergyPlus Documentation, 2008).

Simulations

Simulations were conducted for seven different static slat angles (0˚, 15˚, 30˚, 45˚,

60˚, 75˚, and 90˚) in the case of conventional blinds. In the case of split blinds, the

Page 27: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

27

following 29 sets of split angles were tested: 0˚-0˚-0˚, 0˚-0˚-80˚, 0˚-0˚-45˚, 10˚-0˚-0˚, 10˚-

0˚-45˚, 10˚-0˚-80˚, -37˚-45˚-45˚, -37˚-45˚-80˚, -37˚-45˚-0˚, -37˚-45˚-10˚, -37˚-0˚-0˚, -37˚-

0˚-80˚, -37˚-0˚-45˚, 0˚-45˚-0˚, 0˚-45˚-0˚, 0˚-45˚-45˚, 0˚-45˚-80˚, 0˚-80˚-0˚, 0˚-80˚-45˚, 0˚-

80˚-80˚, 10˚-45˚-0˚, 10˚-45˚-45˚, 10˚-45˚-80˚, 10˚-80˚-0˚, 10˚-80˚-45˚, 10˚-80˚-80˚, -37˚-

80˚-80˚, -37˚-80˚-45˚, and -37˚-80˚-0˚. For split blinds, the angles are specified in the

order from the top section to the bottom section. For example, 10˚-0˚-45˚ means, the top

blinds would be 10˚ closed downwards, the middle angle would be totally open at 0˚

angles, and the bottom section would have an angle of 45˚ closed downwards. The -37˚

slat angle indicated the slat angle rotation of 37˚ inwards facing the room allowing for

more daylight penetration at the backend of the room.

The office room had two sensor points, each placed at a height of 0.76 m above

the ground level. The first sensor point was placed 0.75 m from the window, and the

second sensor point was placed 3.5 m from the window. The following variables were

measured at the two sensor points: Average Illuminance (lux), Glare Index, Average

hourly lighting load (W), Average hourly HVAC load (W), Average Total Energy

Consumption (W) for three days of the year: March 21, June 21, and December 21 for

every occupied hour, from 8 a.m. to 5 p.m.

June 21 is one of two solstices. On this day, the rays of the sun directly strike the

Tropic of Cancer at 23°30' north latitude. On June 21 the summer solstice marks the

beginning of summer in the Northern Hemisphere and subsequently marks winter in the

Southern Hemisphere. On December 21, the winter solstice marks the beginning of

winter in the Northern Hemisphere and marks summer in the Southern Hemisphere.

Page 28: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

28

Therefore March 21, June 21, and December 21 become important days for performing

simulations.

EnergyPlus Inputs

The IDF editor is the interface used by the user to define all the parameters

required to run the simulation. The three-dimentional model created in Google

SketchUp was imported in EnergyPlus using IDF Editor. The graphical interface for IDF

Editor is shown in Figure 3-3. The IDF Editor lists all the input parameters as objects to

be defined by the user. The value to be inputted is defined briefly in the box named

“comments section” on the right side of the checklist. The important parameters that

need to be defined before running the simulations are as follows:

Figure 3-3. The input for EnergyPlus was done through the IDF-Editor interface.

Selecting the walls and windows

The parameter surface construction was used to describe the physical properties

and the configuration for the building envelope and the interior elements.

Page 29: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

29

Material Regular

This parameter was used to define the four main thermal properties of the

material: thickness, conductivity, density, and specific heat. Appendix A contains all the

values assigned for each of the required variables for the definition of the parameter.

Design Day

Figure 3-4 shows the object Design day, this parameter defines all the variables

for the day required to run the simulation. The day of the month and month of the year

for which the simulations are to be run are defined here. Others prominent variables,

such as maximum Drybulb temperature and Windspeed, are defined here.

Figure 3-4. The IDF interface for Design Day Input.

Construction

Once all the materials are defined in the parameter Material Regular, all the

elements of the building such as walls, floors, windows, and doors are “built” in this

Page 30: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

30

parameter from the materials defined. From the most exterior layers, up to 10 layers can

be specified.

Material: Blinds

This parameter defines all the dimensions of the blinds, as well as material

properties of the blinds. Blinds can be placed either inside of the window, on the outside

of the window, or between two layers of glass. For this case study, the blinds are placed

inside the window. The blinds are assumed to cover all the glazed part of the window.

Surface(s)

The parameter Surface heat transfer was used to define all the geometric

specifications for all the building elements, walls, window, slab, and roof. This

parameter not only defines the important elements of the building but also the

interaction between all the building surfaces.

Figure 3-5 shows the parameter surface heat transfer selected in the Thermal

Zone Description Geometry section. This parameter consists of the variables, Surface

Type, Sun Exposure, Wind Exposure, and the coordinates for each surface vertex of the

surface selected.

Lights

The parameter Lights gives the option to define the type and intensity of the

interior lights used. This case study used 256 W of interior lighting for the office building.

Page 31: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

31

Figure 3-5. Screen shot showing all the necessary variables for the object surface heat transfer.

Schedule

Electrical equipment, such as Heating Ventilation and Air Conditioning (HVAC),

and lights can be set on schedule by using the parameter schedule compact. The

parameter schedule compact defines the time period of the day for which the electric

appliance was in use.

Daylighting: Detailed

The parameter Daylighting: Detailed defines all the necessary variables required

to calculate illuminance levels at the required sensor points. Many variables, such as

sky condition, sun position, calculation point (sensor point), location of the sensor point,

and transmittance value of the windows, were defined here. The dimming strategy used

to control lighting depended on the illuminance set point that was chosen, the fraction of

Page 32: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

32

the zone that the set point controls, and the type of lighting control used (EnergyPlus

Documentation, Version 2.2, 2008).

Lighting Control Type

EnergyPlus has two types of lighting control mechanisms. In the first mechanism,

the overhead lights dim continuously and linearly from maximum electric power and

maximum light output to minimum electric power and minimum light output as the

daylight illuminance increases inside the room. The lights stay on at the minimum point

with further increase in the daylight illuminance. In the second mechanism, known as

stepped control of lighting, the electric power input and light output vary in discrete,

equally spaced steps (EnergyPlus Documentation, 2008). For this case study, the

stepped control of lighting was used. For the two sensor points in the model, the

illuminance setpoint was 500 lux. The stepped control of light works in the following

manner:

For an illuminance value of less than one-third of the set point value (i.e,

500/3=167 lux), the fraction of light to be switched ON is equal to one. For illuminance

values between one-third and two-thirds of 500 (i.e., 167-333 lux), the fraction of light to

be switched ON is equal to two-thirds. This means if the light level in the room was

between 167 and 333 lux, two-thirds of the lights were be switched ON. If the

illuminance value in the room was between 333 and 500 lux, then one-thirds of the

lighting was switched ON. Finally, if the illuminance value in the room is more than 500

lux, all the lights were switched OFF. Table 3-1 describes the fractional distribution of

electric lighting used, depending on the illuminance values in the room.

Page 33: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

33

Selecting Input and Weather Files

As shown in Figure 3-6, the input file and weather files can be selected from the

“Single Simulation” tab from the two pull-down lists. The "Browse…" option can be used

to locate an input or weather file that was created or downloaded from the website.

Table 3-1. Example of a Stepped Lighting Control System with Three Steps Daylight illuminance (lux) Fraction of lights that are ON 0-167 1.0 167-233 2/3 233-500 1/3 500 0.0

Figure 3-6. The first drop-down menu is used for selecting the input file (IDF editor file) created using IDF Editor.

Page 34: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

34

Figure 3-7 shows the drop-down menu to select the weather file for the city for

which the simulation was run. The weather files can be downloaded from the website for

the Building Technologies Program of the U.S Department of Energy: Energy Efficiency

and Renewable Energy. The simulate option at the bottom of the interface is used to run

the simulations.

Figure 3-7. The second drop-down menu is used for selecting the weather file.

Radiance

The Radiance program was developed as a research tool for predicting the

distribution of visible radiation in illuminated spaces. Radiance takes as input a three-

dimensional geometric model of the physical environment and produces a map of

Page 35: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

35

spectral radiance values in a color image. The technique of ray tracing follows light

backwards from the image plane to the source(s). Because Radiance can produce

realistic images from a simple description, it has a wide range of applications in graphic

arts, lighting design, Computer-Aided Design (CAD), and architecture (Larson and

Shakespeare 1998).

The simulation tool Radiance uses a light-backwards ray tracing method with

extensions to efficiently solve the rendering equation for specular, diffuse and

directional-diffuse reflection, and transmission in any combination to any level in any

environment, including complicated, curved geometries. The simulation blends

deterministic and stochastic ray tracing techniques to achieve the best balance between

speed and accuracy in its local and global illumination methods (Larson 1991).

The building blocks for any Radiance input file are the primitives. All the materials

that were used, along with all the surfaces that described the objects in the scene, need

to be described as primitives.

The scene description for Radiance is in three-dimensional Cartesian (X, Y, Z

rectilinear) coordinates, which lists all the materials and surfaces used to create the

scene. The scene description file is stored in American Standard Code for Information

Interchange (ASCII) text.

Modifiers are either the word "void," which indicates no modifier, or some

previously defined primitive identifier. The type can be the material type (e.g., plastic,

metal or glass) or surface type (e.g., sphere, polygon, cone, or cylinder), as well as one

of a few other type categories (pattern, texture, or mixture), and the identifier is the

name of the primitive being described.

Page 36: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

36

Figure 3-8 shows a fish-eye image of the office room used in this case study. This

image was generated by the software Radiance. This is a high resolution fish-eye image

of the office room used in the case study. This image was rendered in Radiance using

the command Rpict (Appendix B). The walls of the office room are gray, the floor was

green, and the two furniture tables shown are made of wood.

Figure 3-8. Fish-eye view of a Radiance-rendered image of the office room.

Page 37: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

37

Figure 3-9 shows a closer view of the office room. The Venetian blinds covering

the window can be observed in the image.

Figure 3-9. Close-up view of the office room.

Quality settings

To obtain meaningful quantitative results and maintain the photometric accuracy,

the Radiance quality setting needs to be configured correctly. The following three main

Page 38: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

38

ambient parameters were considered for this research to calculate the illuminance

values at the four sensor points.

1) Ambient bounces (-ab) 2) Ambient value (-av) 3) Ambient divisions (-ad) Ambient bounces (-ab):

This parameter sets the number of inter-reflections between the surfaces that the

program should calculate before reverting to the ambient value. For example, if the

ambient bounce (–ab) was set to 4, then the sampling of the ray occurs on four different

surfaces after leaving the source. Thus, as the -ab value increases, the ambient bounce

increases and the accuracy of the quantitative results increases. Concurrently, the time

taken to run the simulations also increases. Due to the large quantity of the data desired

a low value of ambient bounce (-ab) was assumed for this research.

Ambient value (-av):

The ambient value is the average radiance in all directions of the visible scene,

and it is to be defined by the user as an RGB value. Setting an ambient value may be

useful for visualization, where adding a constant radiance to a scene may save on

computational effort by maybe achieving a similar appearance using less ambient

bounces. Where “absolute” quantitative accuracy is required, the ambient value should

be set at zero, and all simulated lighting should be a result of the indirect calculation.

Ambient Divisions (-ad)

Monte Carlo sampling takes place in cosine-weighted hemispheres at selected

points within the model, with interpolation occurring between these points. The number

of ambient divisions sets the number of samples sent out from each sample

hemisphere. The error in the Monte Carlo calculation of indirect illuminance is inversely

Page 39: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

39

proportional to the square root of this number. In other words, the higher the value for -

ad, more accurate the results are. The –ad value of 4096 was used in this research.

Conventionally, -ad value is expressed as a factor of 2 (2n).

In conclusion, an appropriate setting of the ambient parameters was one of the

challenging aspects of using Radiance. The need for realistic and meaningful results

necessitates higher settings of ambient parameters. Higher ambient parameters

demand for high computer a processing capability, which means higher investments in

computer infrastructure. It was important to maintain a balance between the research

costs and time required for running the simulations. Time constraints, as well as low

computer processing capabilities, meant a compromise with the ambient settings of the

software (Larson and Shakespeare 1998).

Page 40: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

40

CHAPTER 4 RESULTS AND ANALYSIS

Introduction

Simulations were performed by EnergyPlus (EP) and Radiance to assess the

thermal and daylighting performance of the proposed split-controlled blind system. The

simulations were carried out for seven different static slat angles (0˚, 15˚, 30˚, 45˚, 60˚,

75˚, and 90˚) in the case of conventional blinds. In the case of split-controlled blinds 29

sets of split angles were tested. The parameters average hourly lighting load (W),

average hourly HVAC load (W), and average total energy consumption (W) were

obtained from EnergyPlus for three days of the year: March 21, June 21, and December

21. A comparative study was conducted for the results obtained from EnergyPlus and

Radiance to assess the performance of the two blind systems. Illuminance values were

obtained at the four sensor points by from the Radiance simulations conducted for the

entire year. The four sensor points were placed one meter from each other with the first

sensor point placed one meter from the window.

EnergyPlus Results Analysis

Energy consumption results were obtained from the software EnergyPlus.

Simulations were performed for the three days of the year, March 21, June 21 and

December 21 for each occupied hour from 8 a.m. to 5 p.m. The results obtained are

tabulated in Table 4-1. The hourly lighting energy consumption, HVAC consumption,

and as the total energy consumption were used as criteria for selection of the best blind

angle for that hour (refer to “choosing angle” for best angle).

Table 4-1 gives the energy consumption for lighting, HVAC, and the total electric

demand for the three days March 21, June 21, and December 21 for each occupied

Page 41: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

41

hour from 8 a.m. to 5 p.m. The results are shown for the best possible angle for each

hour. For example, if 30˚ is the best angle for conventional blinds at 9 a.m. on March 21

and 10˚-0˚-45˚ is the best angle for split blinds for the same hour and day, then the

Lighting consumption, HVAC and Total electric demand for that hour for that day were

chosen.

Table 4-2 shows the comparative study of split-controlled blinds and conventional

blinds. The three columns give the difference in percentage for the lighting energy

consumption, HVAC and total electric consumption between the split-controlled blinds

and conventional blinds. A positive difference would mean split-controlled blinds work

better than conventional blinds, and a negative difference would infer otherwise.

Figures 4-1 through 4-3 show the percentage of energy savings as a result of

using split-controlled blinds. The x axis represents the office hours from 9 a.m. to 5 p.m.

The y axis represents the percentage values. A positive difference indicates energy

savings as a result of using split-controlled blinds. A negative difference indicates

energy savings as a result of using conventional blind system blind system.

On March 21 (Figure 4-1), 11 a.m. lighting energy consumption for the split-

controlled blinds angle was 50% more than for conventional blinds, and the HVAC

consumption was 2.83% more than that of conventional blinds. The total energy

consumption for that hour was 14.81% more in the case of split-controlled blinds as

compared to conventional blinds. At 1 p.m., the split-controlled blind system was 50%

more efficient in terms of lighting energy consumption and 1.44% more efficient in terms

of HVAC consumption. Overall, at 1 p.m., the split-controlled blinds were 13.22% more

efficient than conventional blinds. Considering the results for the entire day, a marginal

Page 42: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

42

difference of 1% occurred between the two systems with split-controlled blinds being

more efficient.

For June 21 at noon (Figure 4-2), the split-controlled blinds had 33.33% lower

electric lighting energy consumption and 20.81% lower HVAC consumption, thus total

energy consumption for split controlled blinds was 24.41% lower as compared to

conventional blinds. On average for the entire day, split-controlled blinds caused 3.10%

less energy consumption, as compared to conventional blinds.

For December 21 (Figure 4-3), the average energy consumption in the case of the

split-controlled blind system was 1.85% less than the conventional blinds. Thus, on

average the split-controlled blind system worked slightly better than the conventional

blind system in terms of lighting and HVAC electric energy consumption.

Daylighting Analysis

Evaluating the performance of blinds was one of the important tasks of this

research. Dynamic daylighting performance parameter such as Useful Daylight

Illuminance (UDI) was recommended by Mardaljevic et al. (2006). The UDI may be

defined as the percentage of time per year when useful daylight (i.e., between 100 lux

and 2000 lux) is available to the occupant. If illuminance value in the room is less than

100 lux, the room becomes too dark and when greater than 2000 lux, the excess

daylight can cause glare and thus discomfort to the occupant (Mardaljevic et al. 2006).

Once the illuminance values on a work plane are obtained, the next challenge was to

quantify these results for comparative study. The Daylight Autonomy (DA) is the

percentage of time per year when the minimum required illuminance at the sensor point

is met by daylight alone (Mardaljevic et al. 2006).

Page 43: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

43

Table 4-1. Energy consumption for lighting (W), HVAC (W) and Total Electric Demand (W) for March 21, June 21 and December 21

Conventional Blinds Split blinds21-Mar Angle Hour Lighting Demand HVAC Demand Total Electric Demand Angle Hour Lighting Demand HVAC Demand Total Electric Demand

30 9 162 263 425 10-0-45 9 162 263 42530 10 115 282 398 10-45-45 10 128 284 41230 11 102 301 403 80-80-80 11 154 309 46330 12 102 312 415 80-80-80 12 102 317 41930 13 102 320 422 37-45-45 13 51 315 36630 14 102 318 420 37-45-45 14 77 315 39230 15 102 309 411 10-45-45 15 102 308 411

0 16 102 294 397 10-0-0 16 102 294 3970 17 141 279 420 0-0-0 17 141 246 387

21-Jun Angle Hour Lighting Demand HVAC Demand Total Electric Demand Angle Hour Lighting Demand HVAC Demand Total Electric Demand15 9 188 390 578 10-0-0 9 188 390 57815 10 188 393 581 10-0-0 10 188 393 58115 11 162 394 557 10-0-0 11 154 394 54730 12 154 395 549 10-45-0 12 102 313 41515 13 154 397 551 10-0-0 13 154 397 55115 14 154 397 551 10-0-0 14 154 397 55115 15 162 397 559 10-0-0 15 154 396 55015 16 188 399 587 10-0-0 16 188 399 58715 17 188 400 588 10-0-0 17 188 399 587

21-Dec Angle Hour Lighting Demand HVAC Demand Total Electric Demand Angle Hour Lighting Demand HVAC Demand Total Electric Demand60 9 162 1455 1618 0-80-80 9 196 1452 164860 10 115 1342 1457 37-80-0 10 64 1361 142560 11 102 1261 1363 0-80-80 11 102 1244 134660 12 102 1212 1314 0-80-80 12 51 1209 126060 13 102 1186 1288 37-45-80 13 51 1228 127960 14 102 1194 1296 0-80-80 14 0 1195 119560 15 102 1230 1333 0-80-45 15 51 1232 1283

0 16 13 1286 1299 0-0-45 16 26 1286 13110 17 85 1352 1437 0-0-45 17 90 1353 1442

Page 44: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

44

Table 4-2. EnergyPlus Comparison Results

Simulation day Hours Lighting energy consumption (Difference in percentage) HVAC electric demand (Difference in percentage) Total Electric Demand (Difference in percentage)21-Mar 9 0.00 0.04 0.02

10 -11.11 -0.47 -3.5611 -50.00 -2.83 -14.8112 0.00 -1.38 -1.0413 50.00 1.44 13.2214 25.00 0.94 6.8015 0.00 0.08 0.0616 0.00 0.08 0.0617 0.00 11.67 7.76

Average 1.54 1.06 0.95

21-Jun9 0.00 0.05 0.03

10 0.00 0.02 0.0211 5.26 0.20 1.6812 33.33 20.81 24.3113 0.00 0.00 0.0014 0.00 0.02 0.0215 5.26 0.22 1.6816 0.00 0.10 0.0717 0.00 0.11 0.07

Average 4.87 2.39 3.10

21-Dec 9 -21.05 0.27 -1.8710 44.44 -1.39 2.2411 0.00 1.34 1.2412 50.00 0.28 4.1613 50.00 -3.60 0.6614 100.00 -0.12 7.7915 50.00 -0.11 3.7416 -100.00 0.01 -0.9717 -5.00 -0.08 -0.37

Average 18.71 -0.38 1.85

Page 45: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

45

Figure 4-1. Energy consumption differences between split-controlled blinds and conventional blinds for March 21st

Page 46: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

46

Figure 4-2. Energy consumption differences between split-controlled blinds and conventional blinds for June 21st.

Page 47: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

47

Figure 4-3. Energy consumption differences between split-controlled blinds and conventional blinds for December 21

Page 48: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

48

Mardaljevic et al. (2006) suggested that the useful daylight illuminance can be

divided into two ranges, UDI between 100 lux and 500 lux can be considered as

supplementary daylight, which meant, depending on user preference, electric lighting

could be used to supplement daylight required in the room. The second range was

named as autonomous UDI for illuminance values between 500 lux and 2000 lux. This

range of daylighting would not require any artificial electric lighting.

Choosing Blind Angle

One of the objectives of choosing the blinds’ best possible slat angle was to make

sure sufficient useful daylight was available at each sensor point. The angle of the

blinds’ setting, which gave maximum illuminance levels on all four sensor points was

considered the best angle for the blinds’ setting. Thus, the basic algorithm for selecting

the best angle was as follows:

• Select all the angles at the first sensor point, which have illuminance levels in the autonomous UDI range (500-2000 lux).

• Then select the same angles for the fourth sensor point.

• Choose the angle that gives maximum illuminance value for the fourth sensor point.

• Then select the angle among the points chosen from the first sensor point which has given the highest illuminance value for the fourth sensor point.

This way the blind angle for each hour was chosen. Then the UDI was classified

for each sensor point, depending on the value of illuminance at each sensor point. For

example, if the first sensor point gave an illuminance value between 500 lux and 2000

lux; it was classified into the 500 lux to 2000 lux UDI range. Similarly, if a sensor point

gave an illuminance value between 100 lux and 500 lux, then it was classified as the

UDI in the 100 lux to 500 lux range. For an illuminance value between 100 lux and 500

Page 49: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

49

lux, the value 100% was assigned to the corresponding UDI range, and a value of zero

was assigned to the remaining UDI ranges. For each hour, the UDI was defined and the

average for each day was calculated. Similarly, the average for each month was

calculated and tabulated into the following results.

Tables 4-3 through 4-7 show the UDI results for each month of the year, and are

tabulated for each of the four sensor points. The UDI is divided into four sections:

UDI<100 lx, UDI-100-500lx, UDI-500-2000lx, and UDI>2000 lx. The values in Tables 4-

3 through 4-7 show the average UDI values for each month.

Radiance Results Analysis

Figures 4-4 through 4-7 show UDI distribution for the four sensor points in the form

of stacked column charts. The x axis represents the months and the y axis represents

the percentages (i.e. values of UDI). Different UDI ranges are represented by different

colors.

At the first sensor point (Figure 4-4), for the month of February, the UDI (500-2000

lux) decreases to 92% and for the month of March, it decreases to 84% in the case of

split-controlled blinds. In the case of conventional blinds, the UDI remains almost

constant throughout the year except for the month of October, when the UDI (500-2000

lux) decreases to 93% Thus, in this case for the first sensor point, the conventional

blinds have an upper edge over the blinds in terms of daylighting performance.

At the second sensor point (Figure 4-5), for the month of March, the UDI (500-

2000 lux) decreases to 77% and for the month of October, it decreases to 80% while

maintaining a constant value between 90% to 96% for the rest of the year in the case of

split-controlled blinds. In the case of conventional blinds, the UDI remains almost

Page 50: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

50

Table 4-3. UDI values for Sensor Point 1

SPLIT-CONTROLLED BLINDSSENSOR POINT 1UDI <100lx UDI =100lx-50 UDI =500-200UDI >2000lx

jan 0.00 0.32 99.68 0.00feb 0.00 7.24 92.76 0.00mar 0.00 15.31 84.69 0.00apr 0.00 0.00 100.00 0.00may 0.00 0.00 100.00 0.00jun 0.00 0.00 100.00 0.00jul 0.00 0.00 100.00 0.00aug 0.00 0.00 100.00 0.00sep 0.00 3.33 96.67 0.00oct 0.00 9.35 90.65 0.00nov 0.00 0.33 99.67 0.00dec 0.00 0.32 99.68 0.00Average 0.00 3.02 96.98 0.00

CONVENTIONAL BLINDSSENSOR POINT 1UDI <100lx UDI =100lx-50 UDI =500-200UDI >2000lx

jan 0.00 0.00 98.39 1.61feb 0.00 0.00 100.00 0.00mar 0.00 0.00 100.00 0.00apr 0.00 0.00 100.00 0.00may 0.00 0.00 100.00 0.00jun 0.00 0.00 100.00 0.00jul 0.00 0.00 100.00 0.00aug 0.00 0.00 100.00 0.00sep 0.00 0.00 100.00 0.00oct 0.00 6.77 93.23 0.00nov 0.00 0.00 100.00 0.00dec 0.00 0.00 98.39 1.61Average 0.00 0.56 99.17 0.27

Page 51: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

51

Table 4-4. UDI values for Sensor Point 2

SPLIT-CONTROLLED BLINDSSENSOR POINT 2

UDI <100lx UDI =100lx-50 UDI =500-200UDI >2000lxjan 0 3.55 96.45 0feb 0 10.00 90.00 0mar 0 22.81 77.19 0apr 0 10.00 90.00 0may 0 10.00 90.00 0jun 0 10.00 90.00 0jul 0 10.00 90.00 0aug 0 10.00 90.00 0sep 0 13.33 86.67 0oct 0 19.35 80.65 0nov 0 9.00 91.00 0dec 0 6.45 93.55 0Average 0.00 11.21 88.79 0.00

CONVENTIONAL BLINDSSENSOR POINT 2

UDI <100lx UDI =100lx-50 UDI =500-200UDI >2000lxjan 0.00 15.16 84.84 0.00feb 0.00 3.10 96.90 0.00mar 0.00 8.13 91.88 0.00apr 0.00 10.00 90.00 0.00may 0.00 10.00 90.00 0.00jun 0.00 10.00 90.00 0.00jul 0.00 8.71 91.29 0.00aug 0.00 10.00 90.00 0.00sep 0.00 10.00 90.00 0.00oct 0.00 10.00 90.00 0.00nov 0.00 10.33 89.67 0.00dec 0.00 23.23 76.77 0.00Average 0.00 10.72 89.28 0.00

Page 52: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

52

Table 4-5. UDI values for Sensor Point 3

SPLIT-CONTROLLED BLINDSSENSOR POINT 3

UDI <100lx UDI =100lx-500 UDI =500-2000UDI >2000lxjan 0.32 14.52 85.16 0.00feb 7.24 17.24 75.52 0.00mar 15.31 22.19 59.69 2.81apr 0.00 30.00 70.00 0.00may 0.00 48.06 51.94 0.00jun 0.00 49.00 51.00 0.00jul 0.00 40.00 60.00 0.00aug 0.00 36.45 63.55 0.00sep 3.33 29.00 64.67 3.00oct 9.35 20.00 70.65 0.00nov 0.33 14.33 85.33 0.00dec 0.32 17.74 81.94 0.00Average 3.02 28.21 68.29 0.48

CONVENTIONAL BLINDSSENSOR POINT 3

UDI <100lx UDI =100lx-500 UDI =500-2000UDI >2000lxjan 0.00 50.00 50.00 0.00feb 0.00 20.34 79.66 0.00mar 0.00 25.63 74.38 0.00apr 0.00 31.00 69.00 0.00may 0.00 43.23 56.77 0.00jun 0.00 40.33 59.67 0.00jul 0.00 40.00 60.00 0.00aug 0.00 38.06 61.94 0.00sep 0.00 29.67 70.33 0.00oct 0.00 20.00 80.00 0.00nov 0.00 29.33 70.67 0.00dec 0.00 71.94 28.06 0.00Average 0.00 36.63 63.37 0.00

Page 53: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

53

Table 4-6. UDI values for Sensor Point 4 SPLIT-CONTROLLED BLINDS

SENSOR POINT 4UDI <100lx UDI =100lx-500 UDI =500-2000UDI >2000lx

jan 0.32 94.52 5.16 0.00feb 7.24 92.76 0.00 0.00mar 15.31 71.25 10.94 2.50apr 0.00 77.67 22.33 0.00may 0.00 86.13 13.87 0.00jun 0.00 90.00 10.00 0.00jul 0.00 87.42 12.58 0.00aug 0.00 84.19 15.81 0.00sep 3.33 79.00 14.67 3.00oct 9.35 81.94 8.71 0.00nov 0.33 97.67 2.00 0.00dec 0.32 86.13 13.55 0.00Average 3.02 85.72 10.80 0.46

CONVENTIONAL BLINDSSENSOR POINT 4

UDI <100lx UDI =100lx-500 UDI =500-2000UDI >2000lxjan 0.32 74.52 25.16 0.00feb 0.00 67.59 32.41 0.00mar 0.00 63.75 36.25 0.00apr 0.00 73.00 27.00 0.00may 0.00 89.68 10.32 0.00jun 0.00 90.00 10.00 0.00jul 0.00 90.00 10.00 0.00aug 0.00 82.26 17.74 0.00sep 0.00 62.00 38.00 0.00oct 0.32 70.65 29.03 0.00nov 0.00 62.33 37.67 0.00dec 0.00 94.84 5.16 0.00Average 0.05 76.72 23.23 0.00

Page 54: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

54

constant throughout the year except for the month of December, where it falls to 76%.

Thus, in this case for the second sensor point, both blind systems perform equally well.

For the third sensor point (Figure 4-6), the UDI (500-2000 lux) for split-controlled

blinds for the month of January was 85%, as compared to 50% for conventional blinds.

For the month of November, the UDI for split-controlled blinds was 85%, as compared

to 70% for conventional blinds. Similarly for the month of December, the UDI for split-

controlled blinds was 81%, as compared to 28% in the case of conventional blind

system. Overall, for 68% time of the year, useful daylight was available at the third

sensor point in the case of split-controlled blinds, as compared to 63% of time for

conventional blinds.

Figure 4-7 shows, at the fourth sensor point, that split-controlled blind have a lower

annual average UDI (500-2000 lux) with the value of 10%, as compared to 23% for

conventional blinds. Supplementary UDI (100-500 lux) was 88% for split blinds, as

compared to 76% for conventional blinds, which means that the need for supplementary

electric lighting would be required at the fourth sensor point for most of the year.

By analyzing the UDI for both split and conventional blind systems, it can be

concluded that both blind systems seem to perform equally well. It was proposed that

split-controlled blinds would perform better than conventional blinds due to the different

functions that the split sections would tend to perform. It cannot be determined why the

proposed hypothesis was not true. It can be concluded that for the given set of split

angles discussed in this research, both split-controlled blinds and conventional blinds

would perform equally well. Simulations performed with more varied set of angles can

Page 55: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

55

Figure 4-4. UDI comparison for Sensor Point 1(SP1).

Page 56: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

56

Figure 4-5. UDI comparison for Sensor Point 2 (SP2).

Page 57: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

57

Figure 4-6. UDI comparison for Sensor Point 3 (SP3).

Page 58: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

58

Figure 4-7. UDI comparison for Sensor Point 4 (SP4).

Page 59: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

59

perhaps shed more light on the performance of these split-controlled blinds, as

compared to conventional blinds.

Figures 4-8 and 4-9 show the frequency distribution in percentage of total

illuminance values for the entire year at the first sensor point for split-controlled blinds

and conventional blinds. X axis represents the illuminance values in range intervals of

100 lux and the y axis represents percentages of total illuminance values.

For histograms shown in Figures 4-8 and 4-9, the illuminance values at the first

sensor point are plotted for the entire year. In the case of conventional blinds a wide

distribution of values falls in the range between 500 lux and 2000 lux. The illuminance

values obtained for split-controlled blinds vary in a range of 600 lux to 2000 lux with

almost 70% values falling in the range between 1400 lux and 2000 lux, thus showing

less variation in illuminance values for split-controlled blinds.

Figure 4-10 shows the illuminance values at the first sensor point on January 1st at

8 a.m. The x axis represents the 29 split blind angles simulated, and the y axis

represents the illuminance values obtained at the first sensor point for each of the split

blind angles.

For split blind angles -37˚-80˚-80˚, -37˚-80˚-45˚, where the top blinds are tilted

downwards towards the interior at -37˚,illuminance values of 574 lux and 858 lux were

obtained at the first sensor point respectively. This demonstrates the ability of the top

blinds to deflect daylight into the room, even when the middle and bottom blinds are

almost closed. For the angles 0˚-80˚-0˚, 0˚-80˚-45˚, 0˚-80˚-80˚, illuminance values of

851 lux, 849 lux, and 599 lux were obtained at the first sensor point respectively.

Page 60: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

60

With the middle blinds almost closed at 80˚, there is still sufficient daylight inside

the room, which demonstrated the ability of the split blinds to prevent glare causing

direct sunlight entering into the room at the eye level and concurrently have good

daylighting inside the room.

Figure 4-11 shows the average illuminance values at all four sensor points in the

office room. The x axis represents the four sensor points, and y axis represents the

illuminance values in lux.

Average illuminance value for split-controlled blinds at the first sensor point is

1542 lux as compared to 1251 lux for conventional blinds. Average illuminance value for

spilt-controlled blinds at the first sensor point is 19% higher than the average

illuminance value for conventional blinds. Similarly, at the second sensor point, the

illuminance value for split-controlled blinds is 924 lux, as compared to 857 lux, for

conventional blinds. Considering the comfort zone between 500 lux and 2000 lux,

higher illuminance values were obtained at all four sensor points as a result of using

split-controlled blinds.

Figures 4-12 through 4-15 show yearly illuminance (lux) distribution at the four

sensor points respectively. The x axis represents months and y axis represents the

illuminance values in lux. Figures 4-12 and 4-13 show that, from May 1st to September

1st, split-controlled blinds consistently gave higher illuminance values at the first sensor

point as compared to illuminance values at the first sensor point for conventional blinds.

Figures 4-14 and 4-15 show higher illuminance values for conventional blinds as

compared to split-controlled blinds at the third and the fourth sensor point between April

and September.

Page 61: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

61

Figure 4-8. Frequency distribution of illuminance values from split-controlled blinds for sensor point 1.

Figure 4-9. Frequency distribution of illuminance values from conventional blinds for the first sensor point.

Page 62: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

62

Figure 4-10. Illuminance values for all the split blind angles, at the first sensor point for January 1 at 8 a.m.

Figure 4-11. Average illuminance distribution at the four sensor points.

Page 63: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

63

Figure 4-12. Yearly illuminance values at the first sensor point.

Figure 4-13. Yearly illuminance values at the second sensor point

Page 64: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

64

Figure 4-14. Yearly illuminance values at the first sensor point.

Figure 4-15. Yearly illuminance values at the first sensor point.

Page 65: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

65

Automation Model

One of the aims of this research was to formulate a possible algorithm for the

working of the split-controlled blind system in real time. Figure 4-16 shows a possible

algorithm for real-time control of an automated split-controlled blind system. The

automation model describes the functioning of each section of the split-control blind

system with response to variation in illuminance levels inside the office room, as well as

temperature variation.

In the first possible condition, if the illuminance level inside the room was greater than

the maximum allowed illuminance of 2000 lux, the bottom blinds would be completely

closed to prevent any excess heat coming into the building. Simultaneously, the middle

section of the blinds would be closed by an angle β, and the top blind would be closed

by an angle γ. This would naturally decrease the illuminance levels inside the room. The

next step is to perform the illuminance check. In the second condition, if the illuminance

level was less than 2000 lux, then the next illuminance check would be performed. Here

the illuminance must be checked if it lies in the range between 500 lux and 2000 lux. If

yes, no change in the blinds’ angle is suggested. If no, proceed to the temperature

check.

In the temperature check, if the temperature value is between the comfort ranges

defined by the user, the bottom blinds are opened to allow light to come into the building

until the illuminance value reaches the desired level. If the temperature is above the

maximum allowed, the bottom blinds are closed, the middle section is closed by an

angel β, and the top section is closed by an angle γ. If the temperature is below the

minimum allowed, the top blinds are opened by γ, the middle blinds are opened by β,

and the bottom blinds are opened by α.

Page 66: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

66

Figure 4-16. Automation algorithm for split-controlled blinds.

Page 67: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

67

CHAPTER 6 CONCLUSIONS AND RECOMMENDATIONS

Conclusions

The main purpose of this research was to determine the ability of split-controlled

blinds to provide better daylighting, as compared to the conventional Venetian blind

system, and, as a result, to provide comfort to the occupants.

Energy Plus results showed lighting energy savings for the three days: March 21,

June 21 and December 21. For certain periods of the day, lighting energy savings up to

50% were achieved by application of split controlled blind system. This results from the

ability of split controlled blinds to provide better daylighting than the conventional blinds

for the three days simulated.

Daylighting analysis showed that on average the split-controlled blind system

provided higher illuminance at the sensor points compared to conventional blind

system. Comparison of the UDI values for the two blind systems shows no significant

difference among for the values for the four sensor points. It was observed that the

average of all the illuminance values for the entire year at the four sensor points for the

split controlled blinds were higher than those for the conventional blind system. From

March to September, consistently higher illuminance values were obtained at the first

and second sensor point in the case of split-controlled blind system. In the case of the

split-controlled blinds, with the middle section of the blinds closed, sufficient daylight

was obtained inside the room as a result of the ability of top section of the blinds to

deflect light into the room. Thus, split-controlled blind system can provide sufficient level

of daylight inside the room. For split-controlled blind system, 70% of the illuminance

values obtained for the entire year at the first sensor point were within the range of

Page 68: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

68

1400-2000 lux. Conventional blinds showed a wide distribution of illuminance values at

the first sensor point with values ranging from 500 lux to 2000 lux.

Because of the constraints faced with running Radiance simulations, compromises

were made on the quality settings that were chosen for running the simulation. Higher

quality settings would provide more realistic results. For daylighting analysis involving

complex fenestration systems, the ambient bounces (-ab) value to be chosen is on the

order of 6 to 7. Running simulations with such high quality settings is not feasible with

traditional personal computers.

Recommendations

It was observed that the proposed split-controlled blind system can be used to

provide energy savings to the building. A wide range of split angles can be tested, which

can verify the validity of split-control blinds. The best possible angles can then be

chosen and an experimental setup can be tested to verify the validity of Radiance and

EnergyPlus results. The results obtained from the simulation carried out for this

research provide the benchmark for further research in this area, and they also provide

an insight into the use of advanced daylighting and energy simulation tools, such as

Radiance and EnergyPlus. This research can be extended by performing glare studies.

Glare index values can be computed for the four sensor points using Radiance to

analyze and assess the performance of split-controlled blinds in terms of occupancy

comfort. This field of research contributes to the field of sustainable construction and

can provide a valuable source of information for further research in this field. With an

increased emphasis on “green” buildings, the need for more efficient building systems

with advanced fenestration systems becomes a necessity.

Page 69: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

69

APPENDIX A ENERGYPLUS SPECIFICATIONS

Table A-1 shows the area distribution for each of the four walls along with their

cardinal directions. The building envelope mainly comprises of concrete walls with

insulation.

Table A-1. Window-Wall Ratio

Total North (315 to 45 deg)

East (45 to 135 deg)

South (135 to 225 deg)

West (225 to 315 deg)

Gross Wall Area (m2) 52.80 11.15 15.25 11.15 15.25

Window Opening Area (m2) 3.34 0.00 0.00 3.34 0.00

Window-Wall Ratio (%) 6.33 0.00 0.00 30.00 0.00

The rate of heat loss is indicated in terms of the U-factor (U-value) of a window

assembly. The Insulating value is indicated by the R-value which is the inverse of the U-

value. The lower the U-value, the greater a window's resistance to heat flow and the

better its insulating value. Table A-2 gives the reflectance value, U-factor, gross area,

azimuth angle, and the tilt angle for each of the surface elements of the office room.

Table A-2. The exterior of the room

Construction Reflectance

U-Factor with Film (W/m2-K)

U-Factor no Film (W/m2-K)

Gross Area (m2)

Azimuth (deg)

Tilt (deg)

CardinalDirection

WALL1

COMPOSITE CONCRETE/FOAM/CONCRETE WITH STEEL CONNECTORS

0.30 1.751 2.37 15.25 270.00 90.00 W

WALL2

COMPOSITE CONCRETE/FOAM/CONCRETE WITH STEEL CONNECTORS

0.30 1.751 2.37 11.15 0.00 90.00 N

WALL3

COMPOSITE CONCRETE/FOAM/CONCRETE WITH STEEL CONNECTORS

0.30 1.751 2.37 15.25 90.00 90.00 E

Page 70: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

70

WALL4

COMPOSITE CONCRETE/FOAM/CONCRETE WITH STEEL CONNECTORS

0.30 1.751 2.37 11.15 180.00 90.00 S

SLAB

COMPOSITE CONCRETE/FOAM/CONCRETE WITH STEEL CONNECTORS

0.30 1.505 2.37 18.30 0.00 180.00

ROOF

COMPOSITE CONCRETE/FOAM/CONCRETE WITH STEEL CONNECTORS

0.30 1.640 2.37 18.30 180.00 0.00

Table A-3 shows the area, U-factor, and Visible transmittance value for the fenestration

used in the EnergyPlus Model simulation model.

Construction Area of Opening (m2)

U-Factor SHGC Visible

Transmittance Shade Control

Parent Surface

WINDOW DBL LOE (E2=.1) CLR 6MM/13MM AIR 3.34 2.69 0.567 0.744 Yes WALL4

Table A-4 shows the various Air flow rates used for the HVAC system.

Table A-4. ( PTAC) PACKAGED TERMINAL: AIRCONDITIONER

maximum cooling air flow rate [m3/s]

maximum heating air flow rate [m3/s]

maximum air flow rate when compressor is off [m3/s]

maximum outside air flow rate in cooling [m3/s]

maximum outside air flow rate in heating [m3/s]

maximum outside air flow rate when compressor is off [m3/s]

RINKER BUILDING OFFICE PTAC

0.090848 0.090848 0.090848 0.000000 0.000000 0.000000

Tables A-5 and A-6 show the Rated Air Volume Flow, Rated Total Cooling Capacity,

Rated Sensible Heating Ratio (SHR) value for the cooling coil and Nominal Capacity of

the heating coil.

Page 71: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

71

Table A-5. COIL: DX: COOLING BYPASS FACTOREMPIRICAL

Rated Air Volume Flow Rate [m3/s]

Rated Total Cooling Capacity (gross) [W]

Rated SHR

RINKER BUILDING OFFICE PTAC COOLING COIL 0.090848 1503.86 0.798655

Table A-6. COIL: ELECTRIC: HEATING

Nominal Capacity of the Coil [W]

RINKER BUILDING OFFICE PTAC HEATING COIL 1666.43

Table A-7 shows the Design load, Design air flow, Temperature at peak, Date

/Time of the peak used for the cooling load.

Table A-7. HVAC Sizing Summary

Zone Cooling

Design Load (W)

Calculated Design Air Flow (m3/s)

User Design Air Flow (m3/s)

Design Day Name

Date/Time Of Peak

Temperature at Peak (C)

Humidity Ratio at Peak (kgWater/kgAir)

RINKER BUILDING OFFICE

1108.53 0.091 0.091 SIMULATION DAY 1

6/21 13:30:00 33.00 0.00001

Table A-8 show the Design load, Design Air Flow, Temperature at peak, Date

/Time of the peak used for the heating load.

Table A-8. Zone Heating

Design Load (W)

Calculated Design Air Flow (m3/s)

User Design Air Flow (m3/s)

Design Day Name

Date/Time Of Peak

Temperature at Peak (C)

Humidity Ratio at Peak (kgWater/kgAir)

RINKER BUILDING OFFICE

1666.43 0.046 0.046 SIMULATION DAY 3

12/21 07:30:00 -0.33 0.00368

Page 72: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

72

APPENDIX B: RADIANCE GENERATORS

Generators

A generator is any program that produces a scene description as its output. They

usually appear as commands in a scene description file. An example of a simple

generator is genbox.

• Genbox takes the arguments of width, height and depth to produce a parallelepiped description.

• Genprism takes a list of 2-dimensional coordinates and extrudes them along a vector to produce a 3-dimensional prism.

• Genrev is a more sophisticated generator that produces an object of rotation from parametric functions for radius and axis position.

• Gensurf tessellates a surface defined by the parametric functions x(s, t), y(s, t), and z(s, t).

• Genworm links cylinders and spheres along a curve.

• Gensky produces a sun and sky distribution corresponding to a given time and date.

• Xform is a program that transforms a scene description from one coordinate space to another. Xform does rotation, translation, scaling, and mirroring. ry can be easily produced in RADIANCE, without the help of any CAD program.

• Rview is ray-tracing program for viewing a scene interactively. When the user specifies a new perspective, rview quickly displays a rough image on the terminal, and then progressively increases the resolution as the user looks on. The user can select a particular section of the image to improve, or move to a different view and start over. This mode of interaction is useful for debugging scenes as well as determining the best view for a final image.

• Rpict produces a high-resolution picture of a scene from a particular perspective. This program features adaptive sampling, crash recovery and progress reporting, all of which are important for time-consuming images.

Page 73: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

73

APPENDIX C RADIANCE SCRIPT

Appendix C shows the script used to run hourly simulations for each occupied

hour from 8 a.m. to 5 p.m. for the 365 days of the year. Illuminance values were

obtained at the four sensor points placed at a distance of 1 meter from each other with

the first sensor point placed at a distance of 1 meter from the window at a height of 0.76

m from the floor level.

#!/bin/csh -f set hr=$1 set day=$2 set mon=$3 #set filename="conv15" if ($mon < 10) then set monname="0""$mon" else set monname=$mon endif if ($#argv > 3) then set anglename=$4 else set anglename="" endif if ($#argv > 4) then set angle1=$5 else set angle1="" endif if ($#argv > 5) then set angle2=$6 else set angle2="" endif if ($#argv > 6) then set angle3=$7 else set angle3="" endif

Page 74: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

74

set month="$anglename""_""$monname""-""$day""-""$hr" echo $month set coord=(-a 30.00 -o 82.35 -m 84) rm $month.out echo "hr=$hr" set skypar=($mon $day $hr $coord +s) echo "$month/$day/$hr">>$month.out gensky $mon $day $hr -a 29.69 -o -82.65 -m -84 +s>sky1.rad oconv sky1.rad outside.rad room.rad window2.rad conv-45.rad>hr.oct mkillum -ab 1 -ad 256 -as 128 -av 0 0 0 hr.oct "<" windowillum1.rad>illumination.rad oconv -i hr.oct illumination.rad>hour.oct rtrace -h -I -ab 1 -ad 4096 -as 128 -av 0 0 0 hour.oct<mainsamplesup1.inp|rcalc -e '$1=47.4*$1+120*$2+11.6*$3'>>$month.out echo " ">>$month.out rm hr.oct rm hour.oct end @ day++ echo "day=$day" end

Page 75: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

75

APPENDIX D ENERGYPLUS INPUTS

Appendix D shows all the necessary inputs for running simulations inon

EnergyPlus. All the data is obtained from .audit file, obtained as an output of

EnergyPlus simulations. All the parameters and their assigned values, necessary to run

the simulations can be seen here.

14 !- =========== ALL OBJECTS IN CLASS: BUILDING =========== 15 16 BUILDING, 17 rinker building, !- Building Name 18 0, !- North Axis {deg} 19 Urban, !- Terrain 20 0.04, !- Loads Convergence Tolerance Value 21 0.4, !- Temperature Convergence Tolerance Value {deltaC} 22 FullInteriorAndExteriorWithReflections, !- Solar Distribution 23 25; !- Maximum Number of Warmup Days 24 25 26 !- =========== ALL OBJECTS IN CLASS: TIMESTEP IN HOUR =========== 27 28 TIMESTEP IN HOUR, 29 4; !- Time Step in Hour 30 31 32 !- =========== ALL OBJECTS IN CLASS: INSIDE CONVECTION ALGORITHM =========== 33 34 INSIDE CONVECTION ALGORITHM, 35 Detailed; !- Algorithm 36 37 38 !- =========== ALL OBJECTS IN CLASS: OUTSIDE CONVECTION ALGORITHM =========== 39 40 OUTSIDE CONVECTION ALGORITHM, 41 Detailed; !- Algorithm 42 43 44 !- =========== ALL OBJECTS IN CLASS: SOLUTION ALGORITHM =========== 45 46 SOLUTION ALGORITHM, 47 CTF, !- SolutionAlgo 48 200; !- Max Surface Temperature Limit 49 50 51 !- =========== ALL OBJECTS IN CLASS: DIAGNOSTICS =========== 52

Page 76: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

76

53 DIAGNOSTICS, 54 DisplayExtraWarnings; !- key1 55 56 57 !- =========== ALL OBJECTS IN CLASS: RUN CONTROL =========== 58 59 RUN CONTROL, 60 Yes, !- Do the zone sizing calculation 61 No, !- Do the system sizing calculation 62 No, !- Do the plant sizing calculation 63 Yes, !- Do the design day simulations 64 Yes; !- Do the weather file simulation 65 66 67 !- =========== ALL OBJECTS IN CLASS: LOCATION =========== 68 69 Location, 70 Gainesville, !- LocationName 71 30, !- Latitude {deg} 72 -81.65, !- Longitude {deg} 73 -5, !- TimeZone {hr} 74 54; !- Elevation {m} 75 76 77 !- =========== ALL OBJECTS IN CLASS: WEATHER STATION =========== 78 79 WEATHER STATION, 80 10.0, !- Wind Sensor Height Above Ground {m} 81 0.14, !- Wind Speed Profile Exponent 82 270.0, !- Wind Speed Profile Boundary Layer Thickness {m} 83 1.5; !- Air Temperature Sensor Height Above Ground {m} 84 85 86 !- =========== ALL OBJECTS IN CLASS: DESIGNDAY =========== 87 88 DesignDay, 89 Simulation day 1, !- DesignDayName 90 33, !- Maximum Dry-Bulb Temperature {C} 91 , !- Daily Temperature Range {deltaC} 92 , !- Humidity Indicating Conditions at Max Dry-Bulb 93 101217, !- Barometric Pressure {Pa} 94 8.8, !- Wind Speed {m/s} 95 10, !- Wind Direction {deg} 96 0.9, !- Sky Clearness 97 , !- Rain Indicator 98 , !- Snow Indicator 99 21, !- Day Of Month 100 6, !- Month 101 Thursday, !- Day Type 102 , !- Daylight Saving Time Indicator 103 ; !- Humidity Indicating Type 104 105 DesignDay, 106 Simulation day 2, !- DesignDayName

Page 77: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

77

107 29, !- Maximum Dry-Bulb Temperature {C} 108 , !- Daily Temperature Range {deltaC} 109 , !- Humidity Indicating Conditions at Max Dry-Bulb 110 101217, !- Barometric Pressure {Pa} 111 8.8, !- Wind Speed {m/s} 112 10, !- Wind Direction {deg} 113 0.9, !- Sky Clearness 114 , !- Rain Indicator 115 , !- Snow Indicator 116 21, !- Day Of Month 117 3, !- Month 118 Tuesday, !- Day Type 119 , !- Daylight Saving Time Indicator 120 ; !- Humidity Indicating Type 121 122 DesignDay, 123 Simulation day 3, !- DesignDayName 124 -.33, !- Maximum Dry-Bulb Temperature {C} 125 , !- Daily Temperature Range {deltaC} 126 , !- Humidity Indicating Conditions at Max Dry-Bulb 127 101217, !- Barometric Pressure {Pa} 128 8.8, !- Wind Speed {m/s} 129 10, !- Wind Direction {deg} 130 0.9, !- Sky Clearness 131 , !- Rain Indicator 132 , !- Snow Indicator 133 21, !- Day Of Month 134 12, !- Month 135 Friday, !- Day Type 136 , !- Daylight Saving Time Indicator 137 ; !- Humidity Indicating Type 138 139 140 !- =========== ALL OBJECTS IN CLASS: MATERIAL:REGULAR =========== 141 142 MATERIAL:REGULAR, 143 Composite Concrete/Foam/Concrete With Steel Connectors #3, !- Name 144 Rough, !- Roughness 145 0.15240030480061, !- Thickness {m} 146 1.078, !- Conductivity {W/m-K} 147 2185.44, !- Density {kg/m3} 148 1173, !- Specific Heat {J/kg-K} 149 0.9, !- Absorptance:Thermal 150 0.7, !- Absorptance:Solar 151 0.7; !- Absorptance:Visible 152 153 MATERIAL:REGULAR, 154 Composite Insulated Concrete Form Wall With Steel Ties #2, !- Name 155 Smooth, !- Roughness 156 0.101600203200406, !- Thickness {m} 157 0.499, !- Conductivity {W/m-K} 158 1552.01, !- Density {kg/m3} 159 880, !- Specific Heat {J/kg-K}

Page 78: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

78

160 0.9, !- Absorptance:Thermal 161 0.7, !- Absorptance:Solar 162 0.7; !- Absorptance:Visible 163 164 MATERIAL:REGULAR, 165 Composite Concrete/Foam/Concrete With Steel Connectors #1, !- Name 166 Rough, !- Roughness 167 0.101600203200406, !- Thickness {m} 168 1.329, !- Conductivity {W/m-K} 169 2213.25, !- Density {kg/m3} 170 964, !- Specific Heat {J/kg-K} 171 0.9, !- Absorptance:Thermal 172 0.7, !- Absorptance:Solar 173 0.7; !- Absorptance:Visible 174 175 176 !- =========== ALL OBJECTS IN CLASS: MATERIAL:WINDOWGLASS =========== 177 178 MATERIAL:WINDOWGLASS, 179 LoE CLEAR 6MM Rev, !- Name 180 SpectralAverage, !- Optical Data Type 181 , !- Name of Window Glass Spectral Data Set 182 0.006, !- Thickness {m} 183 0.600, !- Solar Transmittance at Normal Incidence 184 0.220, !- Solar Reflectance at Normal Incidence: Front Side 185 0.170, !- Solar Reflectance at Normal Incidence: Back Side 186 0.840, !- Visible Transmittance at Normal Incidence 187 0.078, !- Visible Reflectance at Normal Incidence: Front Side 188 0.055, !- Visible Reflectance at Normal Incidence: Back Side 189 0.0, !- IR Transmittance at Normal Incidence 190 0.10, !- IR Hemispherical Emissivity: Front Side 191 0.84, !- IR Hemispherical Emissivity: Back Side 192 0.9; !- Conductivity {W/m-K} 193 194 MATERIAL:WINDOWGLASS, 195 CLEAR 6MM, !- Name 196 SpectralAverage, !- Optical Data Type 197 , !- Name of Window Glass Spectral Data Set 198 0.006, !- Thickness {m} 199 0.775, !- Solar Transmittance at Normal Incidence 200 0.071, !- Solar Reflectance at Normal Incidence: Front Side 201 0.071, !- Solar Reflectance at Normal Incidence: Back Side

Page 79: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

79

202 0.881, !- Visible Transmittance at Normal Incidence 203 0.080, !- Visible Reflectance at Normal Incidence: Front Side 204 0.080, !- Visible Reflectance at Normal Incidence: Back Side 205 0.0, !- IR Transmittance at Normal Incidence 206 0.84, !- IR Hemispherical Emissivity: Front Side 207 0.84, !- IR Hemispherical Emissivity: Back Side 208 0.9; !- Conductivity {W/m-K} 209 210 211 !- =========== ALL OBJECTS IN CLASS: MATERIAL:WINDOWGAS =========== 212 213 MATERIAL:WINDOWGAS, 214 AIR 13MM, !- Name 215 Air, !- Gas Type 216 0.0127; !- Thickness {m} 217 218 219 !- =========== ALL OBJECTS IN CLASS: MATERIAL:WINDOWBLIND =========== 220 221 MATERIAL:WINDOWBLIND, 222 BLIND WITH HIGH REFLECTIVITY SLATS 1, !- Name 223 HORIZONTAL, !- Slat orientation 224 0.025, !- Slat width {m} 225 0.01875, !- Slat separation {m} 226 0.001, !- Slat thickness {m} 227 90, !- Slat angle {deg} 228 0.9, !- Slat conductivity {W/m-K} 229 0.0, !- Slat beam solar transmittance 230 0.8, !- Slat beam solar reflectance, front side 231 0.8, !- Slat beam solar reflectance, back side 232 0.0, !- Slat diffuse solar transmittance 233 0.8, !- Slat diffuse solar reflectance, front side 234 0.8, !- Slat diffuse solar reflectance, back side 235 0.0, !- Slat beam visible transmittance 236 0.8, !- Slat beam visible reflectance, front side 237 0.8, !- Slat beam visible reflectance, back side 238 0.0, !- Slat diffuse visible transmittance 239 0.8, !- Slat diffuse visible reflectance, front side 240 0.8, !- Slat diffuse visible reflectance, back side 241 0.0, !- Slat IR (thermal) hemispherical transmittance

Page 80: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

80

242 0.9, !- Slat IR (thermal) hemispherical emissivity, front side 243 0.9, !- Slat IR (thermal) hemispherical emissivity, back side 244 0.050, !- Blind-to-glass distance {m} 245 0.5, !- Blind top opening multiplier 246 0.5, !- Blind bottom opening multiplier 247 0.5, !- Blind left-side opening multiplier 248 0.5, !- Blind right-side opening multiplier 249 , !- Minimum Slat Angle {deg} 250 ; !- Maximum Slat Angle {deg} 251 252 MATERIAL:WINDOWBLIND, 253 BLIND WITH HIGH REFLECTIVITY SLATS 2, !- Name 254 HORIZONTAL, !- Slat orientation 255 0.025, !- Slat width {m} 256 0.01875, !- Slat separation {m} 257 0.001, !- Slat thickness {m} 258 90, !- Slat angle {deg} 259 0.9, !- Slat conductivity {W/m-K} 260 0.0, !- Slat beam solar transmittance 261 0.8, !- Slat beam solar reflectance, front side 262 0.8, !- Slat beam solar reflectance, back side 263 0.0, !- Slat diffuse solar transmittance 264 0.8, !- Slat diffuse solar reflectance, front side 265 0.8, !- Slat diffuse solar reflectance, back side 266 0.0, !- Slat beam visible transmittance 267 0.8, !- Slat beam visible reflectance, front side 268 0.8, !- Slat beam visible reflectance, back side 269 0.0, !- Slat diffuse visible transmittance 270 0.8, !- Slat diffuse visible reflectance, front side 271 0.8, !- Slat diffuse visible reflectance, back side 272 0.0, !- Slat IR (thermal) hemispherical transmittance 273 0.9, !- Slat IR (thermal) hemispherical emissivity, front side 274 0.9, !- Slat IR (thermal) hemispherical emissivity, back side 275 0.050, !- Blind-to-glass distance {m} 276 0.5, !- Blind top opening multiplier 277 0.5, !- Blind bottom opening multiplier 278 0.5, !- Blind left-side opening multiplier 279 0.5, !- Blind right-side opening multiplier 280 , !- Minimum Slat Angle {deg} 281 ; !- Maximum Slat Angle {deg} 282 283 MATERIAL:WINDOWBLIND, 284 BLIND WITH HIGH REFLECTIVITY SLATS 3, !- Name 285 HORIZONTAL, !- Slat orientation

Page 81: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

81

286 0.025, !- Slat width {m} 287 0.01875, !- Slat separation {m} 288 0.001, !- Slat thickness {m} 289 90, !- Slat angle {deg} 290 0.9, !- Slat conductivity {W/m-K} 291 0.0, !- Slat beam solar transmittance 292 0.8, !- Slat beam solar reflectance, front side 293 0.8, !- Slat beam solar reflectance, back side 294 0.0, !- Slat diffuse solar transmittance 295 0.8, !- Slat diffuse solar reflectance, front side 296 0.8, !- Slat diffuse solar reflectance, back side 297 0.0, !- Slat beam visible transmittance 298 0.8, !- Slat beam visible reflectance, front side 299 0.8, !- Slat beam visible reflectance, back side 300 0.0, !- Slat diffuse visible transmittance 301 0.8, !- Slat diffuse visible reflectance, front side 302 0.8, !- Slat diffuse visible reflectance, back side 303 0.0, !- Slat IR (thermal) hemispherical transmittance 304 0.9, !- Slat IR (thermal) hemispherical emissivity, front side 305 0.9, !- Slat IR (thermal) hemispherical emissivity, back side 306 0.050, !- Blind-to-glass distance {m} 307 0.5, !- Blind top opening multiplier 308 0.5, !- Blind bottom opening multiplier 309 0.5, !- Blind left-side opening multiplier 310 0.5, !- Blind right-side opening multiplier 311 , !- Minimum Slat Angle {deg} 312 ; !- Maximum Slat Angle {deg} 313 314 315 !- =========== ALL OBJECTS IN CLASS: CONSTRUCTION =========== 316 317 CONSTRUCTION, 318 Composite Concrete/Foam/Concrete With Steel Connectors, !- Name 319 Composite Concrete/Foam/Concrete With Steel Connectors #3, !- Outside Layer 320 Composite Insulated Concrete Form Wall With Steel Ties #2, !- Layer #2 321 Composite Concrete/Foam/Concrete With Steel Connectors #1; !- Layer #3 322 323 CONSTRUCTION, 324 Dbl LoE (e2=.1) Clr 6mm/13mm Air 1, !- Name 325 LoE CLEAR 6MM Rev, !- Outside Layer 326 AIR 13MM, !- Layer #2 327 CLEAR 6MM, !- Layer #3 328 BLIND WITH HIGH REFLECTIVITY SLATS 1; !- Layer #4

Page 82: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

82

329 330 CONSTRUCTION, 331 Dbl LoE (e2=.1) Clr 6mm/13mm Air 2, !- Name 332 LoE CLEAR 6MM Rev, !- Outside Layer 333 AIR 13MM, !- Layer #2 334 CLEAR 6MM, !- Layer #3 335 BLIND WITH HIGH REFLECTIVITY SLATS 2; !- Layer #4 336 337 CONSTRUCTION, 338 Dbl LoE (e2=.1) Clr 6mm/13mm Air 3, !- Name 339 LoE CLEAR 6MM Rev, !- Outside Layer 340 AIR 13MM, !- Layer #2 341 CLEAR 6MM, !- Layer #3 342 BLIND WITH HIGH REFLECTIVITY SLATS 3; !- Layer #4 343 344 CONSTRUCTION, 345 Dbl LoE (e2=.1) Clr 6mm/13mm Air , !- Name 346 LoE CLEAR 6MM Rev, !- Outside Layer 347 AIR 13MM, !- Layer #2 348 CLEAR 6MM; !- Layer #3 349 350 351 !- =========== ALL OBJECTS IN CLASS: ZONE =========== 352 353 ZONE, 354 Rinker building office, !- Zone Name 355 0, !- Relative North (to building) {deg} 356 -0.203200406400813, !- X Origin {m} 357 0, !- Y Origin {m} 358 0, !- Z Origin {m} 359 1, !- Type 360 1, !- Multiplier 361 3.04785126485828, !- Ceiling Height {m} 362 autocalculate, !- Volume {m3} 363 Simple, !- Zone Inside Convection Algorithm 364 Simple, !- Zone Outside Convection Algorithm 365 Yes; !- Part of Total Floor Area 366 367 368 !- =========== ALL OBJECTS IN CLASS: SURFACEGEOMETRY =========== 369 370 SurfaceGeometry, 371 LowerLeftCorner, !- SurfaceStartingPosition 372 ClockWise, !- VertexEntry 373 world; !- CoordinateSystem 374 375 597 598 !- =========== ALL OBJECTS IN CLASS: WINDOWSHADINGCONTROL =========== 599 600 WindowShadingControl, 601 Normal 1, !- User Supplied Shading Control Name 602 InteriorBlind, !- Shading Type 603 Dbl LoE (e2=.1) Clr 6mm/13mm Air 1, !- Name of construction with shading 604 AlwaysOn, !- Shading Control Type

Page 83: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

83

605 , !- Schedule Name 606 , !- SetPoint {W/m2, W or deg C} 607 Yes, !- Shading Control Is Scheduled 608 Yes, !- Glare Control Is Active 609 BLIND WITH HIGH REFLECTIVITY SLATS 1, !- Material Name of Shading Device 610 FixedSlatAngle, !- Type of Slat Angle Control for Blinds 611 ; !- Slat Angle Schedule Name 612 613 WindowShadingControl, 614 Normal 2, !- User Supplied Shading Control Name 615 InteriorBlind, !- Shading Type 616 Dbl LoE (e2=.1) Clr 6mm/13mm Air 2, !- Name of construction with shading 617 AlwaysOn, !- Shading Control Type 618 , !- Schedule Name 619 , !- SetPoint {W/m2, W or deg C} 620 Yes, !- Shading Control Is Scheduled 621 Yes, !- Glare Control Is Active 622 BLIND WITH HIGH REFLECTIVITY SLATS 2, !- Material Name of Shading Device 623 FixedSlatAngle, !- Type of Slat Angle Control for Blinds 624 ; !- Slat Angle Schedule Name 625 626 WindowShadingControl, 627 Normal 3, !- User Supplied Shading Control Name 628 InteriorBlind, !- Shading Type 629 Dbl LoE (e2=.1) Clr 6mm/13mm Air 3, !- Name of construction with shading 630 AlwaysOn, !- Shading Control Type 631 , !- Schedule Name 632 , !- SetPoint {W/m2, W or deg C} 633 Yes, !- Shading Control Is Scheduled 634 Yes, !- Glare Control Is Active 635 BLIND WITH HIGH REFLECTIVITY SLATS 3, !- Material Name of Shading Device 636 FixedSlatAngle, !- Type of Slat Angle Control for Blinds 637 ; !- Slat Angle Schedule Name 638 639 640 !- =========== ALL OBJECTS IN CLASS: SCHEDULETYPE =========== 641 642 ScheduleType, 643 Fraction, !- ScheduleType Name 644 0.0 : 1.0, !- range 645 CONTINUOUS; !- Numeric Type 646 647 ScheduleType, 648 Any number; !- ScheduleType Name 649 650 651 !- =========== ALL OBJECTS IN CLASS: SCHEDULE:COMPACT =========== 652 653 SCHEDULE:COMPACT, 654 Office Lighting 2, !- Name 655 Fraction, !- ScheduleType 656 Through: 12/31, !- Complex Field #1

Page 84: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

84

657 For: Weekdays SummerDesignDay, !- Complex Field #2 658 Until: 05:00, !- Complex Field #3 659 0, !- Complex Field #4 660 Until: 07:00, !- Complex Field #5 661 0, !- Complex Field #6 662 Until: 08:00, !- Complex Field #7 663 0, !- Complex Field #8 664 Until: 17:00, !- Complex Field #9 665 1, !- Complex Field #10 666 Until: 18:00, !- Complex Field #11 667 0, !- Complex Field #12 668 Until: 20:00, !- Complex Field #13 669 0, !- Complex Field #14 670 Until: 22:00, !- Complex Field #15 671 0, !- Complex Field #16 672 Until: 23:00, !- Complex Field #17 673 0, !- Complex Field #18 674 Until: 24:00, !- Complex Field #19 675 0, !- Complex Field #20 676 For: Saturday, !- Complex Field #21 677 Until: 06:00, !- Complex Field #22 678 0.05, !- Complex Field #23 679 Until: 08:00, !- Complex Field #24 680 0.1, !- Complex Field #25 681 Until: 12:00, !- Complex Field #26 682 0.3, !- Complex Field #27 683 Until: 17:00, !- Complex Field #28 684 0.15, !- Complex Field #29 685 Until: 24:00, !- Complex Field #30 686 0.05, !- Complex Field #31 687 For: WinterDesignDay, !- Complex Field #32 688 Until: 24:00, !- Complex Field #33 689 0.0, !- Complex Field #34 690 For: Sunday Holidays AllOtherDays, !- Complex Field #35 691 Until: 24:00, !- Complex Field #36 692 0.05; !- Complex Field #37 693 694 SCHEDULE:COMPACT, 695 Office HVAC, !- Name 696 on/off, !- ScheduleType 697 Through: 12/31, !- Complex Field #1 698 For: Weekdays SummerDesignDay, !- Complex Field #2 699 Until: 06:00, !- Complex Field #3 700 0.0, !- Complex Field #4 701 Until: 22:00, !- Complex Field #5 702 1.0, !- Complex Field #6 703 Until: 24:00, !- Complex Field #7 704 0.0, !- Complex Field #8 705 For: Saturday WinterDesignDay, !- Complex Field #9 706 Until: 06:00, !- Complex Field #10 707 0.0, !- Complex Field #11 708 Until: 18:00, !- Complex Field #12 709 1.0, !- Complex Field #13 710 Until: 24:00, !- Complex Field #14 711 0.0, !- Complex Field #15 712 For: Sunday Holidays AllOtherDays, !- Complex Field #16 713 Until: 24:00, !- Complex Field #17

Page 85: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

85

714 0.0; !- Complex Field #18 715 716 SCHEDULE:COMPACT, 717 ALWAYS 4, !- Name 718 Any number, !- ScheduleType 719 Through: 12/31, !- Complex Field #1 720 For: AllDays, !- Complex Field #2 721 Until: 24:00, !- Complex Field #3 722 4; !- Complex Field #4 723 724 SCHEDULE:COMPACT, 725 ALWAYS 20, !- Name 726 Any number, !- ScheduleType 727 Through: 12/31, !- Complex Field #1 728 For: AllDays, !- Complex Field #2 729 Until: 24:00, !- Complex Field #3 730 20; !- Complex Field #4 731 732 SCHEDULE:COMPACT, 733 ALWAYS 24, !- Name 734 Any number, !- ScheduleType 735 Through: 12/31, !- Complex Field #1 736 For: AllDays, !- Complex Field #2 737 Until: 24:00, !- Complex Field #3 738 24; !- Complex Field #4 739 740 SCHEDULE:COMPACT, 741 OCCUPY-1, !- Name 742 Fraction, !- ScheduleType 743 Through: 12/31, !- Complex Field #1 744 For: WeekDays SummerDesignDay CustomDay1 CustomDay2, !- Complex Field #2 745 Until: 8:00, !- Complex Field #3 746 0.0, !- Complex Field #4 747 Until: 11:00, !- Complex Field #5 748 1.00, !- Complex Field #6 749 Until: 12:00, !- Complex Field #7 750 0.80, !- Complex Field #8 751 Until: 13:00, !- Complex Field #9 752 1, !- Complex Field #10 753 Until: 14:00, !- Complex Field #11 754 1, !- Complex Field #12 755 Until: 18:00, !- Complex Field #13 756 1.00, !- Complex Field #14 757 Until: 19:00, !- Complex Field #15 758 0.50, !- Complex Field #16 759 Until: 21:00, !- Complex Field #17 760 0.10, !- Complex Field #18 761 Until: 24:00, !- Complex Field #19 762 0.0, !- Complex Field #20 763 For: Weekends WinterDesignDay Holiday, !- Complex Field #21 764 Until: 24:00, !- Complex Field #22 765 0.0; !- Complex Field #23 766 767 SCHEDULE:COMPACT, 768 ActSchd, !- Name 769 Any number, !- ScheduleType

Page 86: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

86

770 Through: 12/31, !- Complex Field #1 771 For: AllDays, !- Complex Field #2 772 Until: 24:00, !- Complex Field #3 773 50; !- Complex Field #4 774 775 776 !- =========== ALL OBJECTS IN CLASS: PEOPLE =========== 777 778 PEOPLE, 779 Occupancy, !- Name 780 Rinker building office, !- Zone Name 781 OCCUPY-1, !- Number of People SCHEDULE Name 782 people, !- Number of People calculation method 783 2, !- Number of People 784 , !- People per Zone Area {person/m2} 785 , !- Zone area per person {m2/person} 786 0.8, !- Fraction Radiant 787 autocalculate, !- user specified sensible fraction 788 ActSchd, !- Activity level SCHEDULE Name 789 No, !- Enable ASHRAE 55 comfort warnings 790 ZoneAveraged; !- MRT Calculation Type 791 792 793 !- =========== ALL OBJECTS IN CLASS: LIGHTS =========== 794 795 LIGHTS, 796 PERIMETER Lights 1, !- Name 797 Rinker building office, !- Zone Name 798 Office Lighting 2, !- SCHEDULE Name 799 lighting level, !- Design Level calculation method 800 256, !- Lighting Level {W} 801 20, !- Watts per Zone Area {W/m2} 802 , !- Watts per Person {W/person} 803 0.2, !- Return Air Fraction 804 0.59, !- Fraction Radiant 805 0.2, !- Fraction Visible 806 1, !- Fraction Replaceable 807 GeneralLights; !- End-Use Subcategory 808 809 810 !- =========== ALL OBJECTS IN CLASS: DAYLIGHTING:DETAILED =========== 811 812 DAYLIGHTING:DETAILED, 813 Rinker building office, !- Zone Name 814 2, !- Total Daylighting Reference Points 815 1.524, !- X-coordinate of first reference point {m} 816 0.75, !- Y-coordinate of first reference point {m} 817 0.762, !- Z-coordinate of first reference point {m} 818 1.524, !- X-coordinate of second reference point {m} 819 3.5, !- Y-coordinate of second reference point {m}

Page 87: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

87

820 0.762, !- Z-coordinate of second reference point {m} 821 0.4, !- Fraction of zone controlled by first reference point 822 0.6, !- Fraction of zone controlled by second reference point 823 500, !- Illuminance setpoint at first reference point {lux} 824 500, !- Illuminance setpoint at second reference point {lux} 825 2, !- Lighting control type 826 75, !- Azimuth angle of view direction clockwise from zone y-axis (for glare calculation) {deg} 827 16, !- Maximum allowable discomfort glare index 828 0.3, !- Minimum input power fraction for continuous dimming control 829 0.3, !- Minimum light output fraction for continuous dimming control 830 3, !- Number of steps (excluding off) for stepped control 831 1; !- Probability lighting will be reset when needed in manual stepped control 832 833 834 !- =========== ALL OBJECTS IN CLASS: NODE LIST =========== 835 836 NODE LIST, 837 zone node, !- Node List Name 838 one, !- Node_ID_1 839 two; !- Node_ID_2 840 841 842 !- =========== ALL OBJECTS IN CLASS: SET POINT MANAGER:SINGLE ZONE HEATING =========== 843 844 SET POINT MANAGER:SINGLE ZONE HEATING, 845 heat, !- Name 846 TEMP, !- Control variable 847 -99, !- minimum supply air temperature {C} 848 99, !- maximum supply air temperature {C} 849 Rinker building office, !- zone name of the control zone 850 one, !- node name of zone node 851 two, !- node name of zone inlet node 852 zone node; !- Name of the set point Node or Node List 853 854 855 !- =========== ALL OBJECTS IN CLASS: SET POINT MANAGER:SINGLE ZONE COOLING =========== 856 857 SET POINT MANAGER:SINGLE ZONE COOLING, 858 cooling, !- Name 859 TEMP, !- Control variable 860 -99, !- minimum supply air temperature {C} 861 99, !- maximum supply air temperature {C} 862 Rinker building office, !- zone name of the control zone

Page 88: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

88

863 one, !- node name of zone node 864 two, !- node name of zone inlet node 865 zone node; !- Name of the set point Node or Node List 866 867 868 !- =========== ALL OBJECTS IN CLASS: ZONE CONTROL:THERMOSTATIC =========== 869 870 ZONE CONTROL:THERMOSTATIC, 871 ZONE ONE Thermostat, !- Thermostat Name 872 Rinker building office, !- Zone Name 873 ALWAYS 4, !- Control Type SCHEDULE Name 874 Dual Setpoint with Deadband, !- Control Type #1 875 Office Thermostat Dual SP Control; !- Control Type Name #1 876 877 878 !- =========== ALL OBJECTS IN CLASS: DUAL SETPOINT WITH DEADBAND =========== 879 880 DUAL SETPOINT WITH DEADBAND, 881 Office Thermostat Dual SP Control, !- Name 882 ALWAYS 20, !- Heating Setpoint Temperature SCHEDULE Name 883 ALWAYS 24; !- Cooling Setpoint Temperature SCHEDULE Name 884 ! 885 ! 886 !- =========== ALL OBJECTS IN CLASS: COMPACT HVAC:THERMOSTAT =========== 887 ! 888 ! COMPACT HVAC:THERMOSTAT, 889 ! Rinker thermostat, !- Thermostat Name 890 ! ALWAYS 20, !- Thermostat Heating Setpoint Schedule 891 ! 24, !- Thermostat Constant Heating Setpoint {C} 892 ! ALWAYS 24, !- Thermostat Cooling Setpoint Schedule 893 ! 20; !- Thermostat Constant Cooling Setpoint {C} 894 ! 895 ! 896 !- =========== ALL OBJECTS IN CLASS: COMPACT HVAC:ZONE:PTAC =========== 897 ! 898 ! COMPACT HVAC:ZONE:PTAC, 899 ! Rinker building office, !- Zone Name 900 ! Rinker thermostat, !- Thermostat Name 901 ! autosize, !- Zone Supply Air Cooling Flow Rate {m3/s} 902 ! autosize, !- Zone Supply Air Heating Flow Rate {m3/s} 903 ! autosize, !- Zone Supply Air No-Load Flow Rate {m3/s} 904 ! , !- Zone Supply Air Sizing Factor 905 ! flow/zone, !- Zone Outside Air Method

Page 89: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

89

906 ! 0.00944, !- Zone Outside Air Flow Rate per Person {m3/s} 907 ! , !- Zone Outside Air Flow per Zone Area {m3/s-m2} 908 ! , !- Zone Outside Air Flow per Zone {m3/s} 909 ! , !- System Availability Schedule 910 ! Office HVAC, !- Supply Fan Operating Mode Schedule Name 911 ! Draw Through, !- Supply Fan Placement 912 ! 0.7, !- Supply Fan Total Efficiency 913 ! 75, !- Supply Fan Delta Pressure {Pa} 914 ! 0.9, !- Supply Fan Motor Efficiency 915 ! Single-speed DX, !- Cooling Coil Type 916 ! , !- Cooling Coil Availability Schedule 917 ! autosize, !- Cooling Coil Rated Capacity {W} 918 ! autosize, !- Cooling Coil Rated SHR 919 ! 3, !- Cooling Coil Rated COP 920 ! Electric, !- Heating Coil Type 921 ! , !- Heating Coil Availability Schedule 922 ! autosize, !- Heating Coil Capacity {W} 923 ! 0.8, !- Gas Heating Coil Efficiency 924 ! ; !- Gas Heating Coil Parasitic Electric Load {W} 925 926 927 !- =========== ALL OBJECTS IN CLASS: REPORT VARIABLE =========== 928 929 Report Variable, 930 *, !- Key_Value 931 Window Blind Slat Angle ,!- Variable_Name 932 hourly; !- Reporting_Frequency 933 934 Report Variable, 935 *, !- Key_Value 936 Lights Electric Power, !- Variable_Name 937 hourly, !- Reporting_Frequency 938 Office Lighting 2; !- Schedule_Name 939 940 Report Variable, 941 *, !- Key_Value 942 Daylight Illum at Ref Point 1, !- Variable_Name 943 hourly; !- Reporting_Frequency 944 945 Report Variable, 946 *, !- Key_Value 947 Glare Index at Ref Point 1, !- Variable_Name 948 hourly; !- Reporting_Frequency 949 950 Report Variable, 951 *, !- Key_Value 952 Total Electric Power Purchased, !- Variable_Name 953 hourly; !- Reporting_Frequency 954 955 Report Variable, 956 *, !- Key_Value 957 Total Building Electric Demand, !- Variable_Name

Page 90: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

90

958 hourly; !- Reporting_Frequency 959 960 Report Variable, 961 *, !- Key_Value 962 Total HVAC Electric Demand, !- Variable_Name 963 hourly; !- Reporting_Frequency 964 965 Report Variable, 966 *, !- Key_Value 967 Total Electric Demand, !- Variable_Name 968 hourly; !- Reporting_Frequency 969 970 Report Variable, 971 *, !- Key_Value 972 Daylight Illum at Ref Point 2, !- Variable_Name 973 hourly; !- Reporting_Frequency 974 975 Report Variable, 976 *, !- Key_Value 977 Glare Index at Ref Point 2, !- Variable_Name 978 hourly; !- Reporting_Frequency 979 980 981 !- =========== ALL OBJECTS IN CLASS: REPORT METER =========== 982 983 Report Meter, 984 PurchasedHeating:Facility, !- Meter_Name 985 hourly; !- Reporting_Frequency 986 987 Report Meter, 988 PurchasedCooling:Facility, !- Meter_Name 989 hourly; !- Reporting_Frequency 990 991 992 !- =========== ALL OBJECTS IN CLASS: REPORT CUMULATIVE METERFILEONLY =========== 993 994 Report Cumulative MeterFileOnly, 995 Electricity:Zone:RINKER BUILDING OFFICE, !- Meter_Name 996 hourly; !- Reporting_Frequency 997 998 Report Cumulative MeterFileOnly, 999 InteriorLights:Electricity, !- Meter_Name 1000 hourly; !- Reporting_Frequency 1001 1002 Report Cumulative MeterFileOnly, 1003 EnergyTransfer:Zone:RINKER BUILDING OFFICE, !- Meter_Name 1004 hourly; !- Reporting_Frequency 1005 1006 Report Cumulative MeterFileOnly, 1007 Heating:EnergyTransfer, !- Meter_Name 1008 hourly; !- Reporting_Frequency 1009 1010 Report Cumulative MeterFileOnly, 1011 Heating:EnergyTransfer:Zone:RINKER BUILDING OFFICE, !- Meter_Name 1012 hourly; !- Reporting_Frequency

Page 91: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

91

1013 1014 Report Cumulative MeterFileOnly, 1015 EnergyTransfer:Zone:RINKER BUILDING OFFICE, !- Meter_Name 1016 hourly; !- Reporting_Frequency 1017 1018 1019 !- =========== ALL OBJECTS IN CLASS: REPORT =========== 1020 1021 Report, 1022 Variable Dictionary, !- Type_of_Report 1023 DETAILS, !- Name_of_Report 1024 Lines; !- Specifications1_for_Report 1025 1026 Report, 1027 Construction; !- Type_of_Report 1028 1029 Report, 1030 Surfaces, !- Type_of_Report 1031 Details; !- Name_of_Report

Page 92: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

92

LIST OF REFERENCES

EnergyPlus Documentation (2008) Version 2-2.

Galasiu, A. D., Atif, M. R., and Macdonald, R. A. (2004). “Impact of window blinds on daylight-linked dimming and automatic on/off lighting controls.” Solar Energy, 76, 523-544.

Guillemin, A., and Molteni, S. (2002). “An energy-efficient controller for shading devices self-adapting to the user wishes.” Building and environment, 1091-1097.

Kim, S. Y., and Kim, J. J. (2007). “The impact of daylight fluctuations on a daylight dimming control system in a small office.” Energy and buildings, 39, 935-944.

Koomey, J. G., Webber, C. A., Celina, S., Atkinson, C. D., and Nicholls, A. (2001). “Addressing energy-related challenges for the US buildings sector: results from the clean energy futures study.” Energy Policy 29, 1209–1221.

Larson, C. (1991). Radiance User Manual.

Larson, G. W., and Shakespeare, R. (1998). “Rendering with Radiance and Radiance Reference Material.” Morgan Kaufmann Publishers.

Lawrence, G. W. (1993). Radiance Tutorial. University of California. <http://radsite.lbl.gov/radiance/refer/tutorial.html> (15th November 1993).

Lee, E. S., and Selkowitz, S. E. (2006). “The New York Times headquarters daylighting Mockup: Monitored performance of daylighting control system.” Energy and Buildings, 38, 914-929.

Lee, E. S., DiBartolomeo, D. L., and Selkowitz, S. E. (1998)a. “Thermal and daylighting performance of an automated venetian blind and lighting system in a full-scale private office.” Energy and Buildings, 29, 47-63.

Lee, E. S., DiBartolomeo, D. L., Joseph, H. K., Mehry, Y., and Selkowiz, S. E. (2006). “Monitored Energy Performance of Electrochromic windows Controlled for Daylight and Visual Comfort.” Presented at the ASHRAE 2006 Summer Meeting, Quebec City, Canada, June 24-28, 2006, and published in ASHRAE Transactions.

Lee, E. S., DiBartolomeo, D. L., Rubinstein, F. M., and Selkowitz, S. E. (2004). “Low-cost networking for dynamic window systems.” Energy and Buildings, 36, 503–513.

Lee, E. S., DiBartolomeo, D. L., Vine, E. L., and Selkowitz, S. E. (1998)b. “Integrated Performance of an Automated Venetian Blind/Electric Lighting System in a Full-Scale Private Office.” Proceedings of the Thermal Performance of the Exterior Envelopes of Buildings VII, 1998 in Clearwater Beach, FL.

Page 93: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

93

Mardaljevic., J. and Nabil, A. (2006)“Useful daylight illuminances: A replacement for daylight factors.” Energy and Buildings, 38, 905–913.

Reinhart, C. F. (2004). “Lightswitch-2002: A model for manual and automated control of electric lighting and blinds.” Solar Energy, 77, 15-28.

Selkowitz, S. E., and Lee, E. S. (2004) “Integrating Automated Shading and Smart Glazings with Daylight Controls.” International symposium on Daylight Buildings. 1-9.

Tzempeliko, A., Athienitis, A. K., and Karava, P. (2006). “Simulation of façade and envelope design options for a new institutional building.” Solar Energy, 81, 1088–1103.

Tzempelikos, A., and Athienitis, A. K., (2007). “The impact of shading design and control on building cooling & lighting demand.” Solar Energy 81 (3), 369–382.

Page 94: THERMAL AND DAYLIGHTING PERFORMANCE OF AUTOMATED …ufdcimages.uflib.ufl.edu/UF/E0/04/12/61/00001/golasangimath_d.pdf · thermal and daylighting performance of automated split-controlled

94

BIOGRAPHICAL SKETCH

Deepak V. Golasangimath was born in Bijapur, India. As a child, he excelled in

mathematics and physics. This encouraged him to pursue an engineering career.

Deepak earned his Master of Science (MS) degree in Building Construction from the

M.E. Rinker, Sr. School of Building Construction at the University of Florida in

Gainesville. While pursuing his master’s degree in building construction, he worked as a

research assistant with Dr. Svetlana Olbina. Prior to earning his M.S degree, he

attended the National Institute of Technology in Warangal, India, to earn his Bachelor of

Technology (B-Tech) degree in Civil Engineering. Deepak’s research interests are in the

field of sustainable construction, with emphasis on building technologies. He is also

interested in Building Information Management (BIM) and implementation of BIM in the

building industry. After graduation in December 2009, Deepak plans to work for a

construction management firm in the United States to pursue a successful career in the

field of construction.