The New Georgia Energy Code:The New Georgia Energy Code:2006 IECC2006 IECC
![Page 2: The New GA Energy Code-2006 IECC · 2018-01-04 · The New Georgia Energy Code: 2006 IECC. 2 Sponsors and Resources Pacific Northwest Laboratory: 1-800-270-CODE . 3 About Southface](https://reader034.vdocuments.site/reader034/viewer/2022042220/5ec5fe6a1ef0f36d12360fa3/html5/thumbnails/2.jpg)
2
Sponsors and Sponsors and ResourcesResources
Pacific Northwest Laboratory: 1-800-270-CODEwww.dca.state.ga.us www.energycodes.gov
www.bcap-energy.orgwww.southface.org
![Page 3: The New GA Energy Code-2006 IECC · 2018-01-04 · The New Georgia Energy Code: 2006 IECC. 2 Sponsors and Resources Pacific Northwest Laboratory: 1-800-270-CODE . 3 About Southface](https://reader034.vdocuments.site/reader034/viewer/2022042220/5ec5fe6a1ef0f36d12360fa3/html5/thumbnails/3.jpg)
3
About Southface
Non-profit 501-C3 founded in 1978Pragmatic environmental organization with focus on the built environment
Mission: Southface promotes sustainable homes, workplaces and communities through education, research, advocacy and technical assistance
![Page 4: The New GA Energy Code-2006 IECC · 2018-01-04 · The New Georgia Energy Code: 2006 IECC. 2 Sponsors and Resources Pacific Northwest Laboratory: 1-800-270-CODE . 3 About Southface](https://reader034.vdocuments.site/reader034/viewer/2022042220/5ec5fe6a1ef0f36d12360fa3/html5/thumbnails/4.jpg)
4
Training for residential stakeholders on green building issues from pre-design through constructionExisting home servicesLEED for Homes ProviderEnergy performance modeling and building optimizationEnergy code training and compliance documentationProject energy design reviewsBuilding energy assessmentsHERS Rater trainers and providerEarthCraft House programCommunity and Developmentplanning & charrettes
Residential Green Building Services
![Page 5: The New GA Energy Code-2006 IECC · 2018-01-04 · The New Georgia Energy Code: 2006 IECC. 2 Sponsors and Resources Pacific Northwest Laboratory: 1-800-270-CODE . 3 About Southface](https://reader034.vdocuments.site/reader034/viewer/2022042220/5ec5fe6a1ef0f36d12360fa3/html5/thumbnails/5.jpg)
6
Southface Energy and Environmental Resource Center
Demonstration facility built in 1996Reduces air and water pollutionConserves natural resourcesProvides a healthy indoor environment
![Page 6: The New GA Energy Code-2006 IECC · 2018-01-04 · The New Georgia Energy Code: 2006 IECC. 2 Sponsors and Resources Pacific Northwest Laboratory: 1-800-270-CODE . 3 About Southface](https://reader034.vdocuments.site/reader034/viewer/2022042220/5ec5fe6a1ef0f36d12360fa3/html5/thumbnails/6.jpg)
7
EarthCraft Housea Southface partnership with the Greater Atlanta HBA
Healthy and quietLow maintenance and durableReduced energy andwater billsWise use of materialsAdded resale valueRegional – GA, AL, TN, SC, NC, VASingle-family, Multifamily, Renovation, Communities, Light Commercial (pilot)
![Page 7: The New GA Energy Code-2006 IECC · 2018-01-04 · The New Georgia Energy Code: 2006 IECC. 2 Sponsors and Resources Pacific Northwest Laboratory: 1-800-270-CODE . 3 About Southface](https://reader034.vdocuments.site/reader034/viewer/2022042220/5ec5fe6a1ef0f36d12360fa3/html5/thumbnails/7.jpg)
9
Ch. 1 - Administration and EnforcementCh. 2 - DefinitionsCh. 3 - Design ConditionsCh. 4 - “Systems Analysis”Ch. 5 - “Component Performance”Ch. 6 - “Design by Acceptable Practice”Ch. 7,8 - Design for non-Residential Buildings
(Chapter 7 – ASHRAE 90.1)
Structure: 2000 vs. 2006 IECC
Ch. 1 - AdministrationCh. 2 - DefinitionsCh. 3 - Climate ZonesCh. 4 - Residential Code
401 General402 Building Thermal Envelope403 Fenestration404 Simulated Performance Alternative
Ch. 5 - Commercial Buildings(still references ASHRAE 90.1 – version 2004 is cited for GA)
![Page 8: The New GA Energy Code-2006 IECC · 2018-01-04 · The New Georgia Energy Code: 2006 IECC. 2 Sponsors and Resources Pacific Northwest Laboratory: 1-800-270-CODE . 3 About Southface](https://reader034.vdocuments.site/reader034/viewer/2022042220/5ec5fe6a1ef0f36d12360fa3/html5/thumbnails/8.jpg)
10
What Residential Buildings Must Comply?Chapter 1
New construction1 and 2 familyMulti-family, 3 stories and less
Exempt BuildingsNo conditioningHistoricalLow peak energy for space conditioning
< 3.4 Btu/hr/ft2 of floor area< 1.0 W/ft2 of floor area
![Page 9: The New GA Energy Code-2006 IECC · 2018-01-04 · The New Georgia Energy Code: 2006 IECC. 2 Sponsors and Resources Pacific Northwest Laboratory: 1-800-270-CODE . 3 About Southface](https://reader034.vdocuments.site/reader034/viewer/2022042220/5ec5fe6a1ef0f36d12360fa3/html5/thumbnails/9.jpg)
11
A few definitions…Chapter 2
Air BarrierAny material that blocks air flow between a conditioned space and an unconditioned space, including necessary sealing to block excessive air flow at edges and seams. (Information on proper air sealing may be found in Appendix A, ‘AIR SEALING KEY POINTS’, on the U.S. Department of Energy’s Building America website [www.eere.energy .gov/buildings/building_america], and in the Energy and Environmental Building Association’s [EEBA’s] Builders Guides [www.eeba.org]. These references include guidance on identifying and sealing air barriers.)
Attic KneewallAny vertical or near-vertical wall in the building envelope that has conditioned space on one side and unconditioned attic space on the other side. If the envelope features the insulation installed along the sloped ceiling, the vertical wall is considered an interior wall and thus does not require insulation.
R-value…All R-values shall be stabilized (aged 2 minimum years) R-values.
![Page 10: The New GA Energy Code-2006 IECC · 2018-01-04 · The New Georgia Energy Code: 2006 IECC. 2 Sponsors and Resources Pacific Northwest Laboratory: 1-800-270-CODE . 3 About Southface](https://reader034.vdocuments.site/reader034/viewer/2022042220/5ec5fe6a1ef0f36d12360fa3/html5/thumbnails/10.jpg)
12
IECC 2006 Climate Zones Chapter 3
Note: All GA is CZ 2A, 3A, or 4A
![Page 11: The New GA Energy Code-2006 IECC · 2018-01-04 · The New Georgia Energy Code: 2006 IECC. 2 Sponsors and Resources Pacific Northwest Laboratory: 1-800-270-CODE . 3 About Southface](https://reader034.vdocuments.site/reader034/viewer/2022042220/5ec5fe6a1ef0f36d12360fa3/html5/thumbnails/11.jpg)
1313
4
3
2
GA Climate Zones
![Page 12: The New GA Energy Code-2006 IECC · 2018-01-04 · The New Georgia Energy Code: 2006 IECC. 2 Sponsors and Resources Pacific Northwest Laboratory: 1-800-270-CODE . 3 About Southface](https://reader034.vdocuments.site/reader034/viewer/2022042220/5ec5fe6a1ef0f36d12360fa3/html5/thumbnails/12.jpg)
14
IECC 2006 – Section 401Defines residential (lots of cross referencing to other I-codes)
R3 (1 and 2 family)R2 and R4 (Multifamily 3 stories or less)
Certificate on panel box shows major component R-values, U-factors, efficiencies, etc.
![Page 13: The New GA Energy Code-2006 IECC · 2018-01-04 · The New Georgia Energy Code: 2006 IECC. 2 Sponsors and Resources Pacific Northwest Laboratory: 1-800-270-CODE . 3 About Southface](https://reader034.vdocuments.site/reader034/viewer/2022042220/5ec5fe6a1ef0f36d12360fa3/html5/thumbnails/13.jpg)
15
IECC 2006 – Section 401
Amended language:“A permanent certificate shall be readily accessible and shall be posted on or near the electrical distribution panel or air handler.The certificate shall be completed by the builder or registered design professional. The certificate shall list the predominant R-values of insulation installed in or on ceiling/roof, walls, foundation (slab, basement wall, crawlspace wall and/or floor) and ducts outside conditioned spaces; U-factors for fenestration; and the solar heat gain coefficient (SHGC) of fenestration. Where there is more than one value for each component, the certificate shall list the value covering the largest area. The certificate shall list the type and efficiency of heating, cooling and service water heating equipment. The certificate shall also list the calculated heating load, sensible cooling load, latent cooling load and cfm for space conditioning.”
•See Appendix E for example certificate
![Page 14: The New GA Energy Code-2006 IECC · 2018-01-04 · The New Georgia Energy Code: 2006 IECC. 2 Sponsors and Resources Pacific Northwest Laboratory: 1-800-270-CODE . 3 About Southface](https://reader034.vdocuments.site/reader034/viewer/2022042220/5ec5fe6a1ef0f36d12360fa3/html5/thumbnails/14.jpg)
16
HeatConductionConvectionRadiation
AirWindStack EffectMechanical Fans
Building Science Fundamentals
MoistureBulk CapillarityDiffusionInfiltration
![Page 15: The New GA Energy Code-2006 IECC · 2018-01-04 · The New Georgia Energy Code: 2006 IECC. 2 Sponsors and Resources Pacific Northwest Laboratory: 1-800-270-CODE . 3 About Southface](https://reader034.vdocuments.site/reader034/viewer/2022042220/5ec5fe6a1ef0f36d12360fa3/html5/thumbnails/15.jpg)
17
House as a System
Building EnvelopeContinuous air barrierComplete insulation coverage
Proper Heating and Cooling SystemsControlled Ventilation
The building envelope separates conditioned space from unconditioned (or outside) and consists of two elements: an air barrier & insulation that must be continuous and touching
outside
• Deal with Moisture!
![Page 16: The New GA Energy Code-2006 IECC · 2018-01-04 · The New Georgia Energy Code: 2006 IECC. 2 Sponsors and Resources Pacific Northwest Laboratory: 1-800-270-CODE . 3 About Southface](https://reader034.vdocuments.site/reader034/viewer/2022042220/5ec5fe6a1ef0f36d12360fa3/html5/thumbnails/16.jpg)
18
Blower Door
Duct Blaster
![Page 17: The New GA Energy Code-2006 IECC · 2018-01-04 · The New Georgia Energy Code: 2006 IECC. 2 Sponsors and Resources Pacific Northwest Laboratory: 1-800-270-CODE . 3 About Southface](https://reader034.vdocuments.site/reader034/viewer/2022042220/5ec5fe6a1ef0f36d12360fa3/html5/thumbnails/17.jpg)
19
Positive Ventilation Supplied via O.A. Ducted to Return
![Page 18: The New GA Energy Code-2006 IECC · 2018-01-04 · The New Georgia Energy Code: 2006 IECC. 2 Sponsors and Resources Pacific Northwest Laboratory: 1-800-270-CODE . 3 About Southface](https://reader034.vdocuments.site/reader034/viewer/2022042220/5ec5fe6a1ef0f36d12360fa3/html5/thumbnails/18.jpg)
20
Heat Flow
Conduction is heat flowing through a solid materialConvection is the transfer of heat by the movement of gases or liquids (air)Radiation is the movement of heat energy through space from a hot surfaceto a cold surface, and requires no transfer medium (air, water, etc.)
![Page 19: The New GA Energy Code-2006 IECC · 2018-01-04 · The New Georgia Energy Code: 2006 IECC. 2 Sponsors and Resources Pacific Northwest Laboratory: 1-800-270-CODE . 3 About Southface](https://reader034.vdocuments.site/reader034/viewer/2022042220/5ec5fe6a1ef0f36d12360fa3/html5/thumbnails/19.jpg)
21
ConductionConduction is heat flowing through a solid material (insulation slows conduction)
![Page 20: The New GA Energy Code-2006 IECC · 2018-01-04 · The New Georgia Energy Code: 2006 IECC. 2 Sponsors and Resources Pacific Northwest Laboratory: 1-800-270-CODE . 3 About Southface](https://reader034.vdocuments.site/reader034/viewer/2022042220/5ec5fe6a1ef0f36d12360fa3/html5/thumbnails/20.jpg)
22
Convection• Convection is the transfer of heat
through air (air barriers slow convection)
![Page 21: The New GA Energy Code-2006 IECC · 2018-01-04 · The New Georgia Energy Code: 2006 IECC. 2 Sponsors and Resources Pacific Northwest Laboratory: 1-800-270-CODE . 3 About Southface](https://reader034.vdocuments.site/reader034/viewer/2022042220/5ec5fe6a1ef0f36d12360fa3/html5/thumbnails/21.jpg)
23
RadiationRadiation is the movement of heat from a hot surface to a cold surface with nothing solid or opaque in between (low-emitting surfaces slow radiation)
![Page 22: The New GA Energy Code-2006 IECC · 2018-01-04 · The New Georgia Energy Code: 2006 IECC. 2 Sponsors and Resources Pacific Northwest Laboratory: 1-800-270-CODE . 3 About Southface](https://reader034.vdocuments.site/reader034/viewer/2022042220/5ec5fe6a1ef0f36d12360fa3/html5/thumbnails/22.jpg)
24
H
Air handler & ductwork
________________ heat transfer 1-2
1
23
4
5
6
7
_______________ heat transfer 2-3
________________ heat transfer 3-4
________________ heat transfer 5-6-7
![Page 23: The New GA Energy Code-2006 IECC · 2018-01-04 · The New Georgia Energy Code: 2006 IECC. 2 Sponsors and Resources Pacific Northwest Laboratory: 1-800-270-CODE . 3 About Southface](https://reader034.vdocuments.site/reader034/viewer/2022042220/5ec5fe6a1ef0f36d12360fa3/html5/thumbnails/23.jpg)
25
Air Leakage Requirements
Conditions for Air InfiltrationPressure difference (high to low)Penetrations in building envelope (holes)
Driving ForcesTemperature difference (stack effect)WindMechanical systems
![Page 24: The New GA Energy Code-2006 IECC · 2018-01-04 · The New Georgia Energy Code: 2006 IECC. 2 Sponsors and Resources Pacific Northwest Laboratory: 1-800-270-CODE . 3 About Southface](https://reader034.vdocuments.site/reader034/viewer/2022042220/5ec5fe6a1ef0f36d12360fa3/html5/thumbnails/24.jpg)
26
Wind
Mechanical Systems
Driving Forces for Air Movement
Stack Effect
![Page 25: The New GA Energy Code-2006 IECC · 2018-01-04 · The New Georgia Energy Code: 2006 IECC. 2 Sponsors and Resources Pacific Northwest Laboratory: 1-800-270-CODE . 3 About Southface](https://reader034.vdocuments.site/reader034/viewer/2022042220/5ec5fe6a1ef0f36d12360fa3/html5/thumbnails/25.jpg)
27
2006 IECC (prescriptive chart)
Section 404(annual simulation)
Plan Reviewand Field Inspection
Basic Requirements
Insulation & WindowRequirements
RESCheck(free software)
Energy Code Compliance Pathways
![Page 26: The New GA Energy Code-2006 IECC · 2018-01-04 · The New Georgia Energy Code: 2006 IECC. 2 Sponsors and Resources Pacific Northwest Laboratory: 1-800-270-CODE . 3 About Southface](https://reader034.vdocuments.site/reader034/viewer/2022042220/5ec5fe6a1ef0f36d12360fa3/html5/thumbnails/26.jpg)
28
402-Building Thermal Envelope
40°
30°
55°
72°Conditioned
Space
Outdoors
Unconditioned Space
Unconditioned Space
![Page 27: The New GA Energy Code-2006 IECC · 2018-01-04 · The New Georgia Energy Code: 2006 IECC. 2 Sponsors and Resources Pacific Northwest Laboratory: 1-800-270-CODE . 3 About Southface](https://reader034.vdocuments.site/reader034/viewer/2022042220/5ec5fe6a1ef0f36d12360fa3/html5/thumbnails/27.jpg)
29
Building Envelope - Appendix B
![Page 28: The New GA Energy Code-2006 IECC · 2018-01-04 · The New Georgia Energy Code: 2006 IECC. 2 Sponsors and Resources Pacific Northwest Laboratory: 1-800-270-CODE . 3 About Southface](https://reader034.vdocuments.site/reader034/viewer/2022042220/5ec5fe6a1ef0f36d12360fa3/html5/thumbnails/28.jpg)
30
2006 IECC (prescriptive chart)
Section 404(annual simulation)
Plan Reviewand Field Inspection
Basic Requirements
Insulation & WindowRequirements
RESCheck(free software)
Energy Code Compliance Pathways
![Page 29: The New GA Energy Code-2006 IECC · 2018-01-04 · The New Georgia Energy Code: 2006 IECC. 2 Sponsors and Resources Pacific Northwest Laboratory: 1-800-270-CODE . 3 About Southface](https://reader034.vdocuments.site/reader034/viewer/2022042220/5ec5fe6a1ef0f36d12360fa3/html5/thumbnails/29.jpg)
31
IECC 2006 - Section 402.1Biggest change is simplicity – one prescriptive “answer” for how to build in each climate zoneOption for hourly energy simulation pathway (section 404)
Mandatory provisions spelled out but similar (to IECC 2000)“Meat” of the code is only 4 pages (19-22)!
![Page 30: The New GA Energy Code-2006 IECC · 2018-01-04 · The New Georgia Energy Code: 2006 IECC. 2 Sponsors and Resources Pacific Northwest Laboratory: 1-800-270-CODE . 3 About Southface](https://reader034.vdocuments.site/reader034/viewer/2022042220/5ec5fe6a1ef0f36d12360fa3/html5/thumbnails/30.jpg)
32
IECC 2006 - Section 402.1Revised table for GA – lots of footnotes
![Page 31: The New GA Energy Code-2006 IECC · 2018-01-04 · The New Georgia Energy Code: 2006 IECC. 2 Sponsors and Resources Pacific Northwest Laboratory: 1-800-270-CODE . 3 About Southface](https://reader034.vdocuments.site/reader034/viewer/2022042220/5ec5fe6a1ef0f36d12360fa3/html5/thumbnails/31.jpg)
33
402.1 Footnotes
![Page 32: The New GA Energy Code-2006 IECC · 2018-01-04 · The New Georgia Energy Code: 2006 IECC. 2 Sponsors and Resources Pacific Northwest Laboratory: 1-800-270-CODE . 3 About Southface](https://reader034.vdocuments.site/reader034/viewer/2022042220/5ec5fe6a1ef0f36d12360fa3/html5/thumbnails/32.jpg)
34
IECC 2006 – Section 402.1.4Equivalency using UA approach (REScheck)
South GA
North GA
Middle GA
![Page 33: The New GA Energy Code-2006 IECC · 2018-01-04 · The New Georgia Energy Code: 2006 IECC. 2 Sponsors and Resources Pacific Northwest Laboratory: 1-800-270-CODE . 3 About Southface](https://reader034.vdocuments.site/reader034/viewer/2022042220/5ec5fe6a1ef0f36d12360fa3/html5/thumbnails/33.jpg)
35
Compliance Paths for Insulation and Windows
2006 IECC (prescriptive chart)
Section 404(annual simulation)
Plan Reviewand Field Inspection
Basic Requirements
Insulation & WindowRequirements
RESCheck(free software)
![Page 34: The New GA Energy Code-2006 IECC · 2018-01-04 · The New Georgia Energy Code: 2006 IECC. 2 Sponsors and Resources Pacific Northwest Laboratory: 1-800-270-CODE . 3 About Southface](https://reader034.vdocuments.site/reader034/viewer/2022042220/5ec5fe6a1ef0f36d12360fa3/html5/thumbnails/34.jpg)
36
REScheckTM Softwarewww.energycodes.gov
Software evaluates specific designs quicklyDemonstrates SHGC complianceAllows trade-offs
Building envelope componentsHeating and cooling equipment efficiencies
![Page 35: The New GA Energy Code-2006 IECC · 2018-01-04 · The New Georgia Energy Code: 2006 IECC. 2 Sponsors and Resources Pacific Northwest Laboratory: 1-800-270-CODE . 3 About Southface](https://reader034.vdocuments.site/reader034/viewer/2022042220/5ec5fe6a1ef0f36d12360fa3/html5/thumbnails/35.jpg)
37
Section 402.2 Specific Insulation
RequirementsDetails for insulating various aspects of the building envelope
Ceilings with Attic – 402.2.1Ceilings without Attic – 402.2.2Mass Walls – 402.2.3Steel Framing – 402.2.4Floors – 402.2.5Basement Walls – 402.2.6Slab-on-grade – 402.2.7Crawlspace Walls – 402.2.8Masonry Veneer – 402.2.9Sunrooms – 402.2.10
![Page 36: The New GA Energy Code-2006 IECC · 2018-01-04 · The New Georgia Energy Code: 2006 IECC. 2 Sponsors and Resources Pacific Northwest Laboratory: 1-800-270-CODE . 3 About Southface](https://reader034.vdocuments.site/reader034/viewer/2022042220/5ec5fe6a1ef0f36d12360fa3/html5/thumbnails/36.jpg)
38
402.2.1 - Ceilings with AtticsIn CZ4, the R-38 may be reduced to R-30 if full-height over the top plate
![Page 37: The New GA Energy Code-2006 IECC · 2018-01-04 · The New Georgia Energy Code: 2006 IECC. 2 Sponsors and Resources Pacific Northwest Laboratory: 1-800-270-CODE . 3 About Southface](https://reader034.vdocuments.site/reader034/viewer/2022042220/5ec5fe6a1ef0f36d12360fa3/html5/thumbnails/37.jpg)
39
402.2.2 - Ceilings without AtticsIn CZ4, the R-38 may be reduced to R-30 if there is not sufficient room for R-38 (up to 500 s.f. 25% of the ceiling area may be exempt)
Vaulted ceilings and foam sprayed rooflines would need to perform an R-value trade-off
![Page 38: The New GA Energy Code-2006 IECC · 2018-01-04 · The New Georgia Energy Code: 2006 IECC. 2 Sponsors and Resources Pacific Northwest Laboratory: 1-800-270-CODE . 3 About Southface](https://reader034.vdocuments.site/reader034/viewer/2022042220/5ec5fe6a1ef0f36d12360fa3/html5/thumbnails/38.jpg)
40
402.2.3 – Mass WallsMass walls (concrete block, concrete, insulated concrete forms, masonry cavity, brick (other than veneer), earth (adobe, compressed block, rammed earth) and solid timber/logsR-value must be either exterior or integral and meet requirements of table (adding R-6 in CZ2 or R-8 in CZ3) or else meet frame wall requirements
![Page 39: The New GA Energy Code-2006 IECC · 2018-01-04 · The New Georgia Energy Code: 2006 IECC. 2 Sponsors and Resources Pacific Northwest Laboratory: 1-800-270-CODE . 3 About Southface](https://reader034.vdocuments.site/reader034/viewer/2022042220/5ec5fe6a1ef0f36d12360fa3/html5/thumbnails/39.jpg)
41
402.2.4 – Steel FramingSteel framing – equivalency charts adjust for thermal bridging (see Table 402.2.4)
402.2.5 – FloorsFloors – insulation must be permanently installed against subfloor
![Page 40: The New GA Energy Code-2006 IECC · 2018-01-04 · The New Georgia Energy Code: 2006 IECC. 2 Sponsors and Resources Pacific Northwest Laboratory: 1-800-270-CODE . 3 About Southface](https://reader034.vdocuments.site/reader034/viewer/2022042220/5ec5fe6a1ef0f36d12360fa3/html5/thumbnails/40.jpg)
42
Basement Wall –Average gross wall must be at least 50% below grade and enclose conditioned spaceCZ 3 & 4 requires R-5 continuous or R-13 in cavity
Grade Line
4’
4’
4’
4’
402.2.6 Basement Walls Min. R-5/13
![Page 41: The New GA Energy Code-2006 IECC · 2018-01-04 · The New Georgia Energy Code: 2006 IECC. 2 Sponsors and Resources Pacific Northwest Laboratory: 1-800-270-CODE . 3 About Southface](https://reader034.vdocuments.site/reader034/viewer/2022042220/5ec5fe6a1ef0f36d12360fa3/html5/thumbnails/41.jpg)
43
402.2.6 – Basement WallsBasement walls – top ten feet insulated, CZ3 & 4
Slabs – only CZ4 required insulation, but termite exemption includes all of GAR-5 added to R-valuefor heated slab
402.2.7 – Slab-on-grade
![Page 42: The New GA Energy Code-2006 IECC · 2018-01-04 · The New Georgia Energy Code: 2006 IECC. 2 Sponsors and Resources Pacific Northwest Laboratory: 1-800-270-CODE . 3 About Southface](https://reader034.vdocuments.site/reader034/viewer/2022042220/5ec5fe6a1ef0f36d12360fa3/html5/thumbnails/42.jpg)
44
3 Crawlspace Options in GA
Standard vented crawlspace -underfloorinsulation
Closed crawlspace -underfloorinsulationClosed
crawlspace with wall insulation
Note: all crawspaces must meet vapor retarderrequirements, as per IRC
![Page 43: The New GA Energy Code-2006 IECC · 2018-01-04 · The New Georgia Energy Code: 2006 IECC. 2 Sponsors and Resources Pacific Northwest Laboratory: 1-800-270-CODE . 3 About Southface](https://reader034.vdocuments.site/reader034/viewer/2022042220/5ec5fe6a1ef0f36d12360fa3/html5/thumbnails/43.jpg)
45
IECC 2006 – Section 402.2.8Crawlspace Walls
• 3” inspection view strip
• 9” to finished grade
(optional removable insulation “plugs”, with approval)
• Complete plastic sealed to walls
![Page 44: The New GA Energy Code-2006 IECC · 2018-01-04 · The New Georgia Energy Code: 2006 IECC. 2 Sponsors and Resources Pacific Northwest Laboratory: 1-800-270-CODE . 3 About Southface](https://reader034.vdocuments.site/reader034/viewer/2022042220/5ec5fe6a1ef0f36d12360fa3/html5/thumbnails/44.jpg)
46
Crawlspace Moisture Levels Summer 2002
50
60
70
80
90
100
6/3 6/13 6/23 7/3 7/13 7/23 8/2 8/12 8/22 9/1Da t e
Rel
ativ
e H
umid
ity (%
)
Wall Vented Closed Outside
![Page 45: The New GA Energy Code-2006 IECC · 2018-01-04 · The New Georgia Energy Code: 2006 IECC. 2 Sponsors and Resources Pacific Northwest Laboratory: 1-800-270-CODE . 3 About Southface](https://reader034.vdocuments.site/reader034/viewer/2022042220/5ec5fe6a1ef0f36d12360fa3/html5/thumbnails/45.jpg)
47
IECC 2006 – Section 402.2.9Masonry veneer – horizontal insulation not required (insulation exception for brick ledge)
Sunrooms (thermally isolated insulation) - details
Section 402.2.10
![Page 46: The New GA Energy Code-2006 IECC · 2018-01-04 · The New Georgia Energy Code: 2006 IECC. 2 Sponsors and Resources Pacific Northwest Laboratory: 1-800-270-CODE . 3 About Southface](https://reader034.vdocuments.site/reader034/viewer/2022042220/5ec5fe6a1ef0f36d12360fa3/html5/thumbnails/46.jpg)
48
IECC 2006 – Sections 402.3Fenestration (windows and doors)
U-factors and SHGC from table – low-e effectively requiredExempt - 15 sq. feet from U & SHGC plus one opaque door402.6 - Area weighted average SHGC is 0.5 when modeling (Section 404)Replacement glazing must comply
![Page 47: The New GA Energy Code-2006 IECC · 2018-01-04 · The New Georgia Energy Code: 2006 IECC. 2 Sponsors and Resources Pacific Northwest Laboratory: 1-800-270-CODE . 3 About Southface](https://reader034.vdocuments.site/reader034/viewer/2022042220/5ec5fe6a1ef0f36d12360fa3/html5/thumbnails/47.jpg)
49
Fenestration U-factorsLower U-factor means better insulated (U = 1/R)U-factor applies towindows, skylights, doors
Single Pane
Double Pane
U = 1.05
U = 0.55
Triple Pane
U = 0.35
DP clear glassSHGC: ~ 0.6
DP low-e (low solar gain)SHGC: < 0.4
Solar Heat Gain Coefficient
![Page 48: The New GA Energy Code-2006 IECC · 2018-01-04 · The New Georgia Energy Code: 2006 IECC. 2 Sponsors and Resources Pacific Northwest Laboratory: 1-800-270-CODE . 3 About Southface](https://reader034.vdocuments.site/reader034/viewer/2022042220/5ec5fe6a1ef0f36d12360fa3/html5/thumbnails/48.jpg)
50
ENERGY STAR CriteriaAlmost all
windows sold in GA meet ENERGY STAR
![Page 49: The New GA Energy Code-2006 IECC · 2018-01-04 · The New Georgia Energy Code: 2006 IECC. 2 Sponsors and Resources Pacific Northwest Laboratory: 1-800-270-CODE . 3 About Southface](https://reader034.vdocuments.site/reader034/viewer/2022042220/5ec5fe6a1ef0f36d12360fa3/html5/thumbnails/49.jpg)
51
402.3 Fenestration RequirementsMaximum fenestration U-factor = 0.65
Area weighted average of fenestrationMaximum SHGC = 0.40 for all glazing
1. Show compliance by having all glazing be <= 0.402. Perform REScheck weighted average trade-off 3. Use REScheck to take credit for large overhangs and/or solar shade screens with clear glazing
15 square feet exemption for decorative glazing Permits modest amount of stained glass, transom windows, etc.
Opaque door exemptionOne opaque door is exempt from U-factor requirements
SunroomsReplacement fenestration –must meet codeWeather-stripped access doors –includes hatches/scuttle hole covers
![Page 50: The New GA Energy Code-2006 IECC · 2018-01-04 · The New Georgia Energy Code: 2006 IECC. 2 Sponsors and Resources Pacific Northwest Laboratory: 1-800-270-CODE . 3 About Southface](https://reader034.vdocuments.site/reader034/viewer/2022042220/5ec5fe6a1ef0f36d12360fa3/html5/thumbnails/50.jpg)
52
Access to AtticsWeather-stripped access doors –includes kneewall doors, pull-down stairs, and hatches/scuttle hole coversR-values for hatches R-19Kneewall doors R-3Pull-down stairs R-3
![Page 51: The New GA Energy Code-2006 IECC · 2018-01-04 · The New Georgia Energy Code: 2006 IECC. 2 Sponsors and Resources Pacific Northwest Laboratory: 1-800-270-CODE . 3 About Southface](https://reader034.vdocuments.site/reader034/viewer/2022042220/5ec5fe6a1ef0f36d12360fa3/html5/thumbnails/51.jpg)
53
IECC 2006 – Section 402.4
Air SealingDetailed listFenestrationIC-rated fixtures (option 3 is eliminated)Air barrier leakage criteria in Section 402.4.4
Appendix A for details on techniques for air sealing –now in flip book format
![Page 52: The New GA Energy Code-2006 IECC · 2018-01-04 · The New Georgia Energy Code: 2006 IECC. 2 Sponsors and Resources Pacific Northwest Laboratory: 1-800-270-CODE . 3 About Southface](https://reader034.vdocuments.site/reader034/viewer/2022042220/5ec5fe6a1ef0f36d12360fa3/html5/thumbnails/52.jpg)
54Airtight, IC-rated After drywall
402.4.1 Recessed LightsOption 1 & 2 only: Must be airtight, IC-rated
Standard Can Light
![Page 53: The New GA Energy Code-2006 IECC · 2018-01-04 · The New Georgia Energy Code: 2006 IECC. 2 Sponsors and Resources Pacific Northwest Laboratory: 1-800-270-CODE . 3 About Southface](https://reader034.vdocuments.site/reader034/viewer/2022042220/5ec5fe6a1ef0f36d12360fa3/html5/thumbnails/53.jpg)
Old Code – Appendix B
![Page 54: The New GA Energy Code-2006 IECC · 2018-01-04 · The New Georgia Energy Code: 2006 IECC. 2 Sponsors and Resources Pacific Northwest Laboratory: 1-800-270-CODE . 3 About Southface](https://reader034.vdocuments.site/reader034/viewer/2022042220/5ec5fe6a1ef0f36d12360fa3/html5/thumbnails/54.jpg)
56
No BIG Holes!
• Cover with sheet material and seal
![Page 55: The New GA Energy Code-2006 IECC · 2018-01-04 · The New Georgia Energy Code: 2006 IECC. 2 Sponsors and Resources Pacific Northwest Laboratory: 1-800-270-CODE . 3 About Southface](https://reader034.vdocuments.site/reader034/viewer/2022042220/5ec5fe6a1ef0f36d12360fa3/html5/thumbnails/55.jpg)
57
New Code –Appendix A
(page 1)
![Page 56: The New GA Energy Code-2006 IECC · 2018-01-04 · The New Georgia Energy Code: 2006 IECC. 2 Sponsors and Resources Pacific Northwest Laboratory: 1-800-270-CODE . 3 About Southface](https://reader034.vdocuments.site/reader034/viewer/2022042220/5ec5fe6a1ef0f36d12360fa3/html5/thumbnails/56.jpg)
59
New Code –Appendix A
(page 2)
![Page 57: The New GA Energy Code-2006 IECC · 2018-01-04 · The New Georgia Energy Code: 2006 IECC. 2 Sponsors and Resources Pacific Northwest Laboratory: 1-800-270-CODE . 3 About Southface](https://reader034.vdocuments.site/reader034/viewer/2022042220/5ec5fe6a1ef0f36d12360fa3/html5/thumbnails/57.jpg)
60
Air Sealing Blocking & SheathingSolid sheet behind tubs & showers on insulated walls
•Callback waiting to occur
•Call back prevention
![Page 58: The New GA Energy Code-2006 IECC · 2018-01-04 · The New Georgia Energy Code: 2006 IECC. 2 Sponsors and Resources Pacific Northwest Laboratory: 1-800-270-CODE . 3 About Southface](https://reader034.vdocuments.site/reader034/viewer/2022042220/5ec5fe6a1ef0f36d12360fa3/html5/thumbnails/58.jpg)
61
New Code –Appendix A
(page 3)
![Page 59: The New GA Energy Code-2006 IECC · 2018-01-04 · The New Georgia Energy Code: 2006 IECC. 2 Sponsors and Resources Pacific Northwest Laboratory: 1-800-270-CODE . 3 About Southface](https://reader034.vdocuments.site/reader034/viewer/2022042220/5ec5fe6a1ef0f36d12360fa3/html5/thumbnails/59.jpg)
62
New Code –Appendix A
(page 4)
![Page 60: The New GA Energy Code-2006 IECC · 2018-01-04 · The New Georgia Energy Code: 2006 IECC. 2 Sponsors and Resources Pacific Northwest Laboratory: 1-800-270-CODE . 3 About Southface](https://reader034.vdocuments.site/reader034/viewer/2022042220/5ec5fe6a1ef0f36d12360fa3/html5/thumbnails/60.jpg)
63
New Code –Appendix A
(page 5)Attic Kneewalls
(min. R-18 with attic-side air barrier required)
(required)
![Page 61: The New GA Energy Code-2006 IECC · 2018-01-04 · The New Georgia Energy Code: 2006 IECC. 2 Sponsors and Resources Pacific Northwest Laboratory: 1-800-270-CODE . 3 About Southface](https://reader034.vdocuments.site/reader034/viewer/2022042220/5ec5fe6a1ef0f36d12360fa3/html5/thumbnails/61.jpg)
65
New Code –Appendix A
(page 6)
![Page 62: The New GA Energy Code-2006 IECC · 2018-01-04 · The New Georgia Energy Code: 2006 IECC. 2 Sponsors and Resources Pacific Northwest Laboratory: 1-800-270-CODE . 3 About Southface](https://reader034.vdocuments.site/reader034/viewer/2022042220/5ec5fe6a1ef0f36d12360fa3/html5/thumbnails/62.jpg)
66
New Code –Appendix A
(page 7)
![Page 63: The New GA Energy Code-2006 IECC · 2018-01-04 · The New Georgia Energy Code: 2006 IECC. 2 Sponsors and Resources Pacific Northwest Laboratory: 1-800-270-CODE . 3 About Southface](https://reader034.vdocuments.site/reader034/viewer/2022042220/5ec5fe6a1ef0f36d12360fa3/html5/thumbnails/63.jpg)
67
IECC 2006 – Section 402.5Moisture Control
No wall or ceiling Vapor Diffusion Retarder required in GACrawlspace floor requires 100% plastic sealed to walls and with seams sealed (IRC)
![Page 64: The New GA Energy Code-2006 IECC · 2018-01-04 · The New Georgia Energy Code: 2006 IECC. 2 Sponsors and Resources Pacific Northwest Laboratory: 1-800-270-CODE . 3 About Southface](https://reader034.vdocuments.site/reader034/viewer/2022042220/5ec5fe6a1ef0f36d12360fa3/html5/thumbnails/64.jpg)
68
IECC 2006 – Section 402.6Fenestration U-factor and SHGC
Maximum values permitted based on trade-off approach
IECC 2006 – Section 402.7Minimum R-values for trade-offs with REScheck
![Page 65: The New GA Energy Code-2006 IECC · 2018-01-04 · The New Georgia Energy Code: 2006 IECC. 2 Sponsors and Resources Pacific Northwest Laboratory: 1-800-270-CODE . 3 About Southface](https://reader034.vdocuments.site/reader034/viewer/2022042220/5ec5fe6a1ef0f36d12360fa3/html5/thumbnails/65.jpg)
69
Load Calculations
FURNACE
A/C UNIT
Ductwork
Heating and Cooling Efficiency
Temperature &Humidity Controls
Duct Installationand Insulation
Pipe Insulation
Section 403 - Systems
![Page 66: The New GA Energy Code-2006 IECC · 2018-01-04 · The New Georgia Energy Code: 2006 IECC. 2 Sponsors and Resources Pacific Northwest Laboratory: 1-800-270-CODE . 3 About Southface](https://reader034.vdocuments.site/reader034/viewer/2022042220/5ec5fe6a1ef0f36d12360fa3/html5/thumbnails/66.jpg)
70
IECC 2006 – Section 403.1HVAC Controls
Thermostat requiredHeat Pump requires smart thermostat to prevent unnecessary strip heat
![Page 67: The New GA Energy Code-2006 IECC · 2018-01-04 · The New Georgia Energy Code: 2006 IECC. 2 Sponsors and Resources Pacific Northwest Laboratory: 1-800-270-CODE . 3 About Southface](https://reader034.vdocuments.site/reader034/viewer/2022042220/5ec5fe6a1ef0f36d12360fa3/html5/thumbnails/67.jpg)
71
IECC 2006 – Section 403.2Ducts
R-8 Insulation (R-6 ducts in floor trusses)No Insulation required when inside envelopeSealing required as per IRC Mech section (UL 181 approved sealants)Allowed to used building cavities for returns
![Page 68: The New GA Energy Code-2006 IECC · 2018-01-04 · The New Georgia Energy Code: 2006 IECC. 2 Sponsors and Resources Pacific Northwest Laboratory: 1-800-270-CODE . 3 About Southface](https://reader034.vdocuments.site/reader034/viewer/2022042220/5ec5fe6a1ef0f36d12360fa3/html5/thumbnails/68.jpg)
72
IECC 2006 – Section 403.3Pipe Insulation – Min. R-2
mechanical systems - fluids > 105 F or < 55 Ffor plumbing circulating systems (plus controls)
Mechanical Vents require dampers
Load Calcs & Sizingas per Mechanical section of IRC (ACCA Manual J or approved equivalent, i.e., ASHRAE Fundamentals) summary info required on certificate
![Page 69: The New GA Energy Code-2006 IECC · 2018-01-04 · The New Georgia Energy Code: 2006 IECC. 2 Sponsors and Resources Pacific Northwest Laboratory: 1-800-270-CODE . 3 About Southface](https://reader034.vdocuments.site/reader034/viewer/2022042220/5ec5fe6a1ef0f36d12360fa3/html5/thumbnails/69.jpg)
73
IRC references
![Page 70: The New GA Energy Code-2006 IECC · 2018-01-04 · The New Georgia Energy Code: 2006 IECC. 2 Sponsors and Resources Pacific Northwest Laboratory: 1-800-270-CODE . 3 About Southface](https://reader034.vdocuments.site/reader034/viewer/2022042220/5ec5fe6a1ef0f36d12360fa3/html5/thumbnails/70.jpg)
74
Compliance Paths for Insulation and Windows
2006 IECC (prescriptive chart)
Section 404(annual simulation)
Plan Reviewand Field Inspection
Basic Requirements
Insulation & WindowRequirements
RESCheck(free software)
![Page 71: The New GA Energy Code-2006 IECC · 2018-01-04 · The New Georgia Energy Code: 2006 IECC. 2 Sponsors and Resources Pacific Northwest Laboratory: 1-800-270-CODE . 3 About Southface](https://reader034.vdocuments.site/reader034/viewer/2022042220/5ec5fe6a1ef0f36d12360fa3/html5/thumbnails/71.jpg)
75
IECC 2006 – Section 404Simulated Performance Alternative
Annual energy usage simulation demonstrates that the proposed building’s energy costs are <“standard code” buildingLikely to involve a HERS raterREMrate & Energy Gauge are acceptable
www.resnet.us
![Page 72: The New GA Energy Code-2006 IECC · 2018-01-04 · The New Georgia Energy Code: 2006 IECC. 2 Sponsors and Resources Pacific Northwest Laboratory: 1-800-270-CODE . 3 About Southface](https://reader034.vdocuments.site/reader034/viewer/2022042220/5ec5fe6a1ef0f36d12360fa3/html5/thumbnails/72.jpg)
76
Energy Code “on a Stick”Revised table for GA – lots of footnotesCreated by RECA
South GA
North GA
Middle GA