the israel electric corporation ltd...4.4.3 - iec publication 60230 "impulse test on cables...
TRANSCRIPT
Israel Electric Corporation Ltd. - Customer Division - National Network Unit Edition No.: 5 Specification NPS – 75
for Single Core XLPE Insulated Power
Cable U0/U = 26/45 kV
Issued date: February, 2018
THE ISRAEL ELECTRIC CORPORATION LTD.
National Network Unit
Specification No. NPS - 75
for
Single Core
Extruded Cross - Linked
Polyethylene (XLPE) Insulated
Power Cable
of
Rated Voltage U0/U = 26/45 kV
This issue supersedes specification NPS - 75/4
Haifa, Israel
February, 2018
Israel Electric Corporation Ltd. - Marketing Division - National Network Unit Edition No.: 5 Specification NPS – 75
for Single Core XLPE Insulated Power
Cable U0/U = 26/45 kV
Issued date: February, 2018
Page No. 1 of 22
Contents
1 - General
2 - The IECo. catalogue Numbers
3 - Documents to be supplied with the Proposal
4 - Standards
5 - Technical Requirements
6 - Tests
7 - Marking
8 - Packing
9 - Quality Requirements
10 - Prototype approval
11- Questionnaire
Appendix “A” - Test requirements for cables manufactured according to
I.E.C .
Appendix “B” - Acceptance Test requirements
Appendix "C" - Quality Requirements for Contracts Execution
Appendix "D" - Schedule up to prototype approval
APPENDIX "E" – Statement of manufacturer experience
Prepared by : A. Lavian (- signed )
Approved by: N. Grinberg (- signed )
Israel Electric Corporation Ltd. - Marketing Division - National Network Unit Edition No.: 5 Specification NPS – 75
for Single Core XLPE Insulated Power
Cable U0/U = 26/45 kV
Issued date: February, 2018
Page No. 2 of 22
1 - General
Scope
This specification defines the technical requirements of power cables with single core
copper/aluminum conductor, extruded solid cross-linked polyethylene insulation (XLPE) of
rated voltage Uo/U=26/45 kV (henceforth referred to as “Cables”).
The cables are designate to be installed in outdoor and underground networks with neutral point
earthed via Peterson Coil but operation with solidly earthed neutral point is also possible.
2 - The IECo catalogue Numbers
The IECo. catalogue Numbers and the relevant conductor cross-section:
Table 1
Type of Cable Conductor Cross Section (mm2) IECo Cat. No.
N2XS (F) 2Y 95 Cu 570754
N2XS (F) 2Y 240 Cu 329060
NA2XS (F) 2Y 240 Al 5228282
NA2XS (F) 2Y 300 Al 5254360
3 - Documents to be supplied with the Proposal
The Proposer shall submit all the following documents to the IECo. with the bid documents.
3.1 Complete and fill in “Questionnaire”;
3.2 A complete Type Test Reports, according to Israeli standard IS 1516-2, issued within the
last 7 years preceding the date of the bid, for the proposed cable or for a similar* cable.
3.3 Certificate issued by the Standards Institution of Israel (SII) or any agreed accredited
institution, attesting that the Manufacturer meets the requirements of the Israeli Standard
IS 1516-2 for MV power cables (identical to IEC standard 60502 part 2)
3.4 Cross-section drawings including dimensions;
3.5 Approval of conformance with ISO 9001 requirements shall be in a form of a certificate
issued by a Certification Body (CB) which is accredited by an Accreditation Body (AB).
Israel Electric Corporation Ltd. - Marketing Division - National Network Unit Edition No.: 5 Specification NPS – 75
for Single Core XLPE Insulated Power
Cable U0/U = 26/45 kV
Issued date: February, 2018
Page No. 3 of 22
The certificate should bare the logo of the CB and of its AB and/or the logo of the IAF.
The certificate shall be valid on the date set for submission of the proposal.
The certificate shall be valid for the scope of activities requested in the request for
proposal.
3.6 Document approving experience: the manufacturer actively produced and supplied at
least 150 km of the proposed cable or similar* cable during a period of at least 3 years
during the last 7 years preceding the date of the bid. Additionally, The Proposer shall
submit reference list indicating the quantities of the cables manufactured and sold during
these years;
* Similar cable: Same construction, same conductor cross-section or bigger, the conductor
may be either copper or aluminum.
** All the above documents shall be in English.
4 - Standards
4.1 Standards referenced in this specification, and in supplements to this specification, form
an integral part of this specification.
4.2 All the standards referred to the most current issue, including all amendments, and
supplements, as of the date of the bid.
4.3 The cables that are provided under this specification, shall be designed, manufactured
inspected, tested and preserved in compliance with the standards as specified herein.
4.4 Relevant standards:
4.4.1 - Israeli Standard SI 60228 (IEC Publication 60228) "Conductors of Insulated
Cables";
4.4.2 - IEC Publication 60229 "Test on Cable Oversheaths"
4.4.3 - IEC Publication 60230 "Impulse Test on Cables & their Accessories"
4.4.4 - IEC Publication 60840 "Tests for Power cables with Extruded Insulation for
Rated Voltages Above 30 kV and up to 150 kV"
Israel Electric Corporation Ltd. - Marketing Division - National Network Unit Edition No.: 5 Specification NPS – 75
for Single Core XLPE Insulated Power
Cable U0/U = 26/45 kV
Issued date: February, 2018
Page No. 4 of 22
4.4.5 - DIN VDE 0276- 620 part 5c Distribution Cables (3.6/6kV up to and including
20.8/36 kV): XLPE Insulated Single Core Cables with PE
or PVC sheath.
In case of differences between the present specification and the said standards, the
present specification is mandatory.
Israel Electric Corporation Ltd. - Marketing Division - National Network Unit Edition No.: 5 Specification NPS – 75
for Single Core XLPE Insulated Power
Cable U0/U = 26/45 kV
Issued date: February, 2018
Page No. 5 of 22
5 - Technical Requirements
5.1 Operating Temperatures
5.1.1 Maximum rated conductor temperature: 90C
5.1.2 Short circuit maximum conductor temperature (for duration up to 5 sec): 250C
5.1.3 The conductor temperature under emergency condition: 130C for duration of 8 hours
continuously. The total duration of such overloads may exceed 100 hours per annual.
5.2 Construction
5.2.1 Conductor
5.2.1.1 Material: The conductor shall consist of plane annealed copper wires or aluminum
alloy.
5.2.1.2 Form: The conductor shall be class 2 stranded circular compacted.
5.2.1.3 Dimensions: Table 1 hereafter sets out the cross-sectional areas and characteristics of the
conductors covered by this specification.
Table 2
Nominal Cross-
Section
(mm2)
Diameter
Range
(mm)
Minimum
Number of Wires
Max. DC Resistance at
200C
(/km)
95 Cu 11.0 12.0 15 0.193
240 Cu 17.6 19.2 34 0.0754
240 Al 17.6 19.2 30 0.125
300 Al 19.7 21.6 30 0.100
5.2.2 Conductor Screen
5.2.2.1 The conductor screen shall consist of an extruded cross-linked semi-conducting compound
layer (HD 620, part 5-c sub-clause 2.2).
Israel Electric Corporation Ltd. - Marketing Division - National Network Unit Edition No.: 5 Specification NPS – 75
for Single Core XLPE Insulated Power
Cable U0/U = 26/45 kV
Issued date: February, 2018
Page No. 6 of 22
This inner-semi-conducting layer shall not penetrate into the inner wire layers of the
conductor and shall be easily removable during installation. The wall thickness of the inner
semi-conducting layer shall be at least 0.3 mm.
5.2.2.2 Tapes are permitted under the inner-conducting layer if an electrical contact is guaranteed
between the conductor and the inner-conducting layer.
5.2.2.3 The irregularities in the conductor screen, shall be of sizes specified in sub-clause 2.5 of the
standard HD 620, part 5-c.
5.2.2.4 The Resistance, both before and after aging, shall not exceed 1000 m.
5.2.3 Insulation
5.2.3.1 The insulation shall be of extruded cross-linked polyethylene (XLPE).
5.2.3.2 The process of cross-linking or vulcanization may be achieved by any method except
"Curing in Steam" process.
5.2.3.3 The nominal thickness, not including the thickness of any separator or semiconducting
screen on the conductor and over the insulation, shall be 10.5 mm for all the cross-sectional
areas specified in Table 2 of this specification.
5.2.3.4 The average thickness of the insulation shall not be less than the specified nominal value.
5.2.3.5 The thickness at any place may however be less than the specified nominal value
provided that the difference does not exceed 0.1 mm +10% of the specified nominal value
(IEC 60840, sub-clause 4.6.2.a).
5.2.3.6 Wall thickness difference of the insulation between the lowest and the highest values in
one measured plane shall not exceed 1.1 mm.
5.2.3.7 Max. and min. diameter values over the insulation shall be as specified in Table 3:
Nominal
Cross-Section
(mm2)
Minimum
Insulation Diameter
(mm)
Maximum
Insulation
Diameter
(mm)
95 Cu 33.5 35.0
240 Cu 40.6 42.6
240 Al 40.6 42.6
300 Al 42.5 44.8
Table 3
Israel Electric Corporation Ltd. - Marketing Division - National Network Unit Edition No.: 5 Specification NPS – 75
for Single Core XLPE Insulated Power
Cable U0/U = 26/45 kV
Issued date: February, 2018
Page No. 7 of 22
5.2.3.8 The irregularities (voids, impurities) in the insulation shall not exceed 0.2 mm as specified
in sub-clause 3.3 of standard HD 620 part 5-C.
.
5.2.4 Non-Metallic Insulation Screen
5.2.4.1 The semi-conducting screen shall be applied directly over the insulation and shall consist
of an extruded cross linked polyethylene. The semi-conducting screen shall be non-
peelable (bonded).
5.2.4.2 The maximum thickness of the semi-conducting screen shall be of 0.6 mm for all the
cables covered by this specification.
5.2.4.3 The minimum thickness of the semi-conducting screen shall be of 0.3 mm.
5.2.4.4 The diameter difference over the non-metallic insulation screen between the lowest and
the highest value shall be maximum 0.5 mm.
5.2.4.5 The inner and the outer semi-conducting layers shall not present any surface roughness,
shall be smooth, and shall adhere perfectly to the insulation all along its periphery.
5.2.4.6 The electric Resistivity of the layers, both before and after aging, shall not exceed
500 m at 200C .
5.2.4.7 Conductor screen, insulation and insulation screen shall be laid by triple extrusion
process.
5.2.5 Semi-Conductive Bedding Tape
A swelling semi-conductive Bedding tape shall be applied lapped all over the non-
metallic insulation screen.
5.2.6 Metallic Screen
5.2.6.1 A metallic screen shall be applied helical over the bedding semi-conductive tape. The
screen shall consist a concentric layer of copper wires, bounded together with one or
two copper tapes, having thickness of at least 0.1 mm and a minimum cross-sectional
area of l mm2.
Israel Electric Corporation Ltd. - Marketing Division - National Network Unit Edition No.: 5 Specification NPS – 75
for Single Core XLPE Insulated Power
Cable U0/U = 26/45 kV
Issued date: February, 2018
Page No. 8 of 22
The copper tape shall be applied helical so that the helix lay will not be greater than the
cable diameter underneath the concentric layer of copper wires times 4.
5.2.6.2 The metallic screen dimensions and resistance shall be as specified in Table 4:
Table 4
Total Cross-Sectional Area
of the Screen Wires
[mm2]
Wires’ Minimum
Diameter
[mm]
Max DC Resistance of
the Screen at 200C
[/km]
25 0.5 0.727
5.2.7 Watertight Measures
5.2.7.1 The cables shall be longitudinally watertight protected on the screen area.
5.2.7.2 The watertight layer shall be made of special swelling tape.
5.2.8 Outer Sheath
5.2.8.1 The outer sheath shall be made of HDPE polyethylene compound, ST7 type (IEC
publication 60502-2 table 4).
5.2.8.2 The color of the outer sheath shall be black.
5.2.8.3 The nominal thickness shall be 2.5 mm and the minimum thickness shall be not less than
2.03 mm for all the cables covered by this specification.
5.2.8.4 The diameter over the outer sheath shall be within the range specified in Table 5:
Table 5
Conductor Cross Section
Area
[mm2]
Min. outer sheath
Diameter
[mm]
Max. outer sheath
Diameter
[mm]
95 Cu 41 47
240 Cu 48 54
240 Al 48 54
300 Al 50 57
Israel Electric Corporation Ltd. - Marketing Division - National Network Unit Edition No.: 5 Specification NPS – 75
for Single Core XLPE Insulated Power
Cable U0/U = 26/45 kV
Issued date: February, 2018
Page No. 9 of 22
6 - Tests
6.1 General
Tests shall be performed in accordance with the requirements of Annex “A” of this
specification and will meet the latest published recommendations of the standards prescribed
under clause 4 of this specification, by and at the expense of the Contractor. In case that the
Proposer has a type test of one of the said standards, he will complete the tests according to
Annex “A”.
6.2 Type Tests
6.1 Type Test
Within 3 months after from the date on which a binding contractual obligation has been created,
the Contractor shall submit type test report that was performed on the first manufactured batch
of the cable to be supply to the IECo.
The type test shall be performed according to Annex "A" in an independent authorized laboratory
(ISO/IEC 17025 or EN 45011 approved).;
The IECo. reserves the right to attend during the performance of the Type Test
Exemption: If the Contractor had supplied identical cable to the IECo. during the last 7 years
preceding the date of the present bid, and if the manufacturing method was not changed, the
Contractor can introduce type test report if it was approved by the IECo. in the former supply.
6.2 Routine Tests
The Contractor shall perform and submit test reports for all routine tests for each cable that is
wrapped on each drum.
The Contractor shall submit to IE Co. the routine test reports for approval prior to delivery of
the cable
The cable shall be delivered only after approval of the routine test report of the cable.
Israel Electric Corporation Ltd. - Marketing Division - National Network Unit Edition No.: 5 Specification NPS – 75
for Single Core XLPE Insulated Power
Cable U0/U = 26/45 kV
Issued date: February, 2018
Page No. 10 of 22
6.3 Acceptance Test
Acceptance tests shall be performed according to the standards in para. 3 and shall include tests
required in Appendix "B"
In case that the cable under test will not fulfill all requirements specified in Appendix "B" the
IECo. has the right to reject the consignment.
6.4 The tests shall be performed by and at the expense of the Contractor. The contractor shall make
all the necessary arrangements to enable the IECo.’s inspectors to be present at the tests.
6.5 The following data shall be indicated on each test certificate:
Manufacturer's name;
Name and address of the testing laboratory;
Serial number of the test certificate;
The certificate issue date;
Test report of special test shall specify the pertained batch number of the cables;
A signature of the person responsible for tests and his position.
6.6 The test certificate should contain results for each test according to the test requirements with
reference to appropriate Clauses and Sub-clauses of standards and this specification.
Israel Electric Corporation Ltd. - Marketing Division - National Network Unit Edition No.: 5 Specification NPS – 75
for Single Core XLPE Insulated Power
Cable U0/U = 26/45 kV
Issued date: February, 2018
Page No. 11 of 22
7 - Marking
Throughout whole cable length, at intervals not exceeding 100 cm, the following identification
marks shall be indelibly imprinted in white color, embossed or by reproduction in relief on the outer
sheath.
a) Manufacturer’s name or trade mark (logo)
b) The structure: " N2XS (F) 2Y - l x (cross-sectional area in mm2), 18/30 kV "
c) Year of production
d) "Property of the Israel Electric Corp."
e) Running length (in meters) No. marked on each one of the cable ends (the first and the
last No.)
8 - Packing
8.1 The following data shall be printed legibly on a tag strongly attached on each drum:
f) Manufacturer's Name g) The IECo. Order No.
h) Drum Serial No. i) Manufacturing Date
j) Cable Type k) Cross Sectional Area in mm2
l) Cable Length m) Gross Weight
n) Cable Standard o) The IECo. Catalog No.
p) The IECo. Specification No. (NPS-75) l) Manufacturer's Plant address
8.2 The cables shall be furnished in lengths of 500÷650 (±5) meters wound on seaworthy metal or
metal framed wooden drums. The accurate length and type of drum should be coordinated
according to the tender requirements.
The cable on the drum shall be protected against damage by a suitable cover easy to be
removed, mounted around the drum flanges, so that the drum shall be closed from all sides.
8.3 The supplied drums shall be with max. flange diameter 2240 mm and max. width 1200 mm.
8.4 The supplied cable's ends shall be hermetically sealed with watertight caps that shall prevent
the ingress of humidity and fine dust into the cable's ends.
Israel Electric Corporation Ltd. - Marketing Division - National Network Unit Edition No.: 5 Specification NPS – 75
for Single Core XLPE Insulated Power
Cable U0/U = 26/45 kV
Issued date: February, 2018
Page No. 12 of 22
8.5 COT of the conductor material should be attached to each consignment;
9- Quality Requirements
For quality system and other specific quality requirements, see Appendix A: Q-APP-02.
Bidder shall submit with his proposal the following (In English):
Quality system Certificate;
Quality manual;
Certificates that demonstrate the Bidder's compliance with the requirements specified
or implied in this specification;
Example of an inspection & test plan and/or Quality plan which pertain to the cable to
be supplied;
Formal confirmation that he will conform to the requirements of Q-APP-02.
Israel Electric Corporation Ltd. - Marketing Division - National Network Unit Edition No.: 5 Specification NPS – 75
for Single Core XLPE Insulated Power
Cable U0/U = 26/45 kV
Issued date: February, 2018
Page No. 13 of 22
10 PROTOTYPE APPROVAL
10.1 Prototype approval for new suppliers.
New supplier – Supplier that didn’t supply the ordered item to the IECorp. in the last five (5) years.
10.1.1 In a period of max three (3) months from the date on which a binding contractual obligation
has been created, and before production for IEC of all ordered items, the Contractor shall perform
Prototype Approval
10.1.2 For purposes of the Prototype approval, the manufacturer shall perform the complete type
tests as required in this specification.
10.1.3 The contractor shall be responsible to conduct successfully all the necessary tests, and to
deliver to the Israel Electric Corp. all the necessary required reports, in a manner, which will not
interfere with or delay any of the time schedules, pertaining to any action or undertaking, required of
the winning bidder, including, but not limited to delivery schedule. Such responsibility shall include
proper and reasonable advance notifications to the Israel Electric Corp., prior to any action, required
of it.
If type and special tests have already been conducted with reference to the identical cable which is
offered by the proposed and the Israel Electric Corp. approves the reports, pertaining to such tests,
the Israel Electric Corp. shall have a right (but not a duty) to waive all or part of the required tests.
10.1.4 The Israel Electric Corp. reserves the right to cancel the order for the supply of equipment if
the prototype will not be approved by the Israel Electric Corp. In any case, the contractor shall not
resume manufacture of the rest of the ordered equipment before receiving the Israel Electric
final approval of the prototype.
10.1.5 Required schedule up to prototype approval (after notification of award) is attached in
APPENDIX: "D".
Israel Electric Corporation Ltd. - Marketing Division - National Network Unit Edition No.: 5 Specification NPS – 75
for Single Core XLPE Insulated Power
Cable U0/U = 26/45 kV
Issued date: February, 2018
Page No. 14 of 22
11 – Questionnaire
Tender No.: __________________ Name of Proposer : ________________
Subject Insert all data in this column
Manufacturer’s name and address
Specify the standards that the cable will comply:
1 – Cable
1.1 Coding
1.2 Rating voltage (U0/U) (kV)
1.3 Current rating (in soil having 1 km/W at 300C, at a load
factor of 1.0, laying depth 0.7 m) (A)
1.4 Short circuit rating current for 5 sec duration (A)
1.5 Corona level (pC/kV)
1.6 Inductive resistance at 50 Hz (Ω/km)
1.7 AC effective resistance at 900C (Ω/km)
1.8 Capacitance (F/km)
2 – Conductor
2.1 Material:
2.2 Nominal cross-sectional area (mm2)
2.3 Number and nominal diameter of wires (mm)
2.4 Designed diameter (mm)
2.5 Max DC resistance at 200C (Ω/km)
2.6 Max permissible continuous temp. (0C)
2.7 Max permissible Short circuit temp. (0C)
Israel Electric Corporation Ltd. - Marketing Division - National Network Unit Edition No.: 5 Specification NPS – 75
for Single Core XLPE Insulated Power
Cable U0/U = 26/45 kV
Issued date: February, 2018
Page No. 15 of 22
3 – Conductor Screen
3.1 Material:
3.2 Min thickness (mm)
3.3 Max electrical resistivity at operating temp. (Ω/km)
3.4 The irregularities sizes (mm)
4 - Insulation
4.1 Material:
4.2 Nominal thickness (mm)
4.3 Nominal diameter (mm)
4.4 Difference between lowest and highest value of wall
thickness in one measured plane (mm)
4.5 Dielectric permeability
5 - Non-Metallic Insulation Screen
5.1 Material:
5.2 Extruded layer peelabe / non-peelable
5.3 Thickness (min – max) (mm)
5.4 Max electrical resistivity at operating temp. (Ω/km)
5.5 Difference between lowest and highest value of wall
thickness in one measured plane (mm)
6 - Bedding semi-conductive tape is applied on the
nonmetallic insulation screen Yes/No
7 - Metallic Screen
7.1 Number and diameter of wires (mm)
7.2 Number, thickness and width of tapes (mm)
7.3 Nominal cross-sectional area (mm2)
7.4 Electrical resistance at 200C (Ω/km)
Israel Electric Corporation Ltd. - Marketing Division - National Network Unit Edition No.: 5 Specification NPS – 75
for Single Core XLPE Insulated Power
Cable U0/U = 26/45 kV
Issued date: February, 2018
Page No. 16 of 22
8 - A swelling tape shall be applied over the metallic screen (yes/no)
9 - Outer Sheath
9.1 Material:
9.2 Nominal thickness (mm)
9.3 Nominal diameter (mm)
9.4 Difference between lowest and highest value of wall
thickness in one measured plane (mm)
9.5 Color:
9.6 Marking embossed according sub-clause 7
10 - General Data
10.1 Cable Weight (kg/km)
10.2 Permissible bending radius (m)
10.3 Permissible pulling force (kg)
11 - Drum
11.1 Type:
11.2 Material:
11.3 Weight of empty drum (kg)
11.4 Flange diameter (cm)
11.5 Barrel diameter (cm)
11.6 Overall Width (cm)
11.7 Gross weight (drum with cable) (kg)
11.8 Length of cable per drum (kg)
12- Packing
12.1 A tag with all details as required in sub-clause 8.1 shall be
attached
Yes/No
12.2 The cable shall have sealing caps Yes/No
12.3 The drum shall be protected as required in sub-clause 8.2 (Yes/No)
Israel Electric Corporation Ltd. - Marketing Division - National Network Unit Edition No.: 5 Specification NPS – 75
for Single Core XLPE Insulated Power
Cable U0/U = 26/45 kV
Issued date: February, 2018
Page No. 17 of 22
13 - Attached Documents
13.1 The IEC certification of being in the list of approved
suppliers (Yes/No)
13.2 ISO 9001:2000 certificate (valid in the questionnaire date)
(Yes/No)
13.3 Catalogue (Yes/No)
13.4 Inspection and test plan, QA manual (Yes/No)
Proposer’s address: Email address:
Fax. No. : Tel. No. :
Contact: Cellular:
Date: Signature:
Israel Electric Corporation Ltd. - Marketing Division - National Network Unit Edition No.: 5 Specification NPS – 75
for Single Core XLPE Insulated Power
Cable U0/U = 26/45 kV
Issued date: February, 2018
Page No. 18 of 22
Annex "A"
TEST REQUIREMENTS
for
CABLES MANUFACTURED
ACCORDING TO
The IECo SPECIFICATION NPS - 75
Israel Electric Corporation Ltd. - Marketing Division - National Network Unit Edition No.: 5 Specification NPS – 75
for Single Core XLPE Insulated Power
Cable U0/U = 26/45 kV
Issued date: February, 2018
Page No. 19 of 22
Annex "B"
SPECIFICATION
for
ACCEPTANCE TESTS
of
CABLES MANUFACTURED
ACCORDING TO
The IECo. SPECIFICATION NPS - 75
–
Israel Electric Corporation Ltd. - Marketing Division - National Network Unit Edition No.: 5 Specification NPS – 75
for Single Core XLPE Insulated Power
Cable U0/U = 26/45 kV
Issued date: February, 2018
Page No. 20 of 22
QUALITY SPECIFICATIONS
THE ISRAEL ELECTRIC CORPORATION LTD.
ORGANIZATION AND QUALITY DIVISION QUALITY CONTROL UNIT
Q - APP - 02 3
03/2005
Spec. No. Rev.
Status Volume
APPENDICES FOR CONTRACTS / ORDERS TITLE
QUALITY REQUIREMENTS FOR CONTRACTS EXECUTION
SUB TITLE
ANNEX "C"
ORGANIZATION, QUALITY AND SAFETY DIVISION
QUALITY CONTROL UNIT
APPENDIX FOR CONTRACTS / ORDERS
REV. 4
Volume 03/ 2011
Spec. No. Q - APP - 02
QUALITY REQUIREMENTS
Israel Electric Corporation Ltd. - Marketing Division - National Network Unit Edition No.: 5 Specification NPS – 75
for Single Core XLPE Insulated Power
Cable U0/U = 26/45 kV
Issued date: February, 2018
Page No. 21 of 22
Appendix. D – Schedule for prototype approval
Israel Electric Corporation Ltd. - Marketing Division - National Network Unit Edition No.: 5 Specification NPS – 75
for Single Core XLPE Insulated Power
Cable U0/U = 26/45 kV
Issued date: February, 2018
Page No. 22 of 22
APPENDIX "E" - STATEMENT OF MANUFACTURING EXPERIENCE
I, ______________________________ (Enter name), do hereby state the following:
1. I am a position holder at ________________________ ("The factory") occupying the position of
____________________________ (Enter job title and description, i.e. partner, production
manager, sales manager, etc.)
2. I have been occupying this position since ___________________ (Enter date).
3. I give this statement in regards to I.E.C Tender number __________________ ("The Tender").
4. The facts/details given in this statement have been checked and verified by me.
5. _________________ (The factory) has actively produced and supplied at least 150 km of the
proposed cable or similar* cable during a period of at least 3 years during the last 7
years prior to submission.
* Similar cable: Same construction, same conductor cross-section or bigger, the conductor
may be either copper or aluminum.
6. I hereby undertake to provide, upon IEC's request and at its sole discretion, any other documents
(reference list, quantity ,dates of supply, letter of recommendations etc ) or other information
requested for this Tender for purposes of proving said experience.
_______________
Signature
_______________
Date