the highest energy recovery available. rg · pdf filethe company building on over 20 years of...
TRANSCRIPT
The Company
Building on over 20 years of European
innovation Tempeff North America is
pleased to offer Dual Core energy recovery
ventilation equipment with the highest
efficiency available. In these times of
escalating energy costs, and concern over
environmental impact, Tempeff Dual Core
Technology is an ideal solution for your
building ventilation needs.
Ventilation
Any building owner or operator knows
that due to the extreme North American
climate, conditioning ventilation air is
very expensive. However, that ventilation
air is extremely important to ensure good
building health, and in turn health of
occupants, leading to increased comfort
and productivity. Thanks to Tempeff Dual
Core’s high efficiencies, owners can meet
or exceed minimum legislated ventilation
requirements, without the usual high
operating costs of traditional ventilation
heating and cooling equipment.
Dual Core Energy RecoveryTemperature Efficiency
Tempeff North America products employ Dual Core regenerative technology
that offers up to 95% temperature efficiency. Other available technologies offer a
maximum of approximately 50% to 75% efficiency under ideal circumstances, and
much lower real effectiveness in colder temperatures due to frost. The Dual Core design is
significantly more energy efficient in all conditions, thus payback periods are extremely attractive.
Latent Recovery
In winter modes condensation will form on the exhausting heat exchanger. When the cycle changes the outdoor
air is passed over the heat exchanger, and that moisture is added back to the airstream. This reduces the need for
adding humidity to the conditioned space. In many cases up to 70% latent recovery can be obtained.
Frost Resistant Most heat recovery technologies suffer from the same basic drawback. In cold temperatures frost will form on the
exhaust side of the heat exchanger, dramatically reducing the heat recovery effectiveness. If a defrost cycle is not
employed, frost will build up until the entire heat recovery device becomes inoperable. During the defrost cycle the
heat recovery device is usually bypassed, or put into a mode where effectiveness is significantly reduced so that
the frost can melt. Thus in times where heat recovery is needed the most (ambient temperatures are coldest) the
effectiveness of the device is the lowest. As a result, most technologies require additional heat capacity for these
times, usually sized as if there is no heat recovery device at all to ensure the building does not experience periods
where cold air is being introduced (during defrost cycles). In turn real effectiveness is greatly reduced, increasing
operating costs, equipment costs, and life cycle costs.
With the Dual Core design frost will never build up in a typical application. With the cycling heat exchanger, frost
doesn’t have a chance to form, and one heat exchanger is always delivering conditioned air to the space. In many
cases additional heat is not necessary for the ventilation air, due to the real effectiveness of the system! As a result
operating costs, equipment cost, installation cost and overall life cycle costs are significantly reduced compared to
traditional heat recovery technology.
Low Maintenance
With few moving parts, maintenance of the system is very low. Due to cycling nature of the heat exchangers dust
rarely builds up on the heat exchangers, thus frequent cleaning is not required. If cleaning is required, cores are
easily removable for cleaning as necessary.
Long Term performance
In a third party audit of a 17 year old installation, performed by CIT Energy Management AB, it was found that
the efficiency of the equipment was the same as the day it was installed (90% measured temperature efficiency).
The product has also been rigorously tested in one of the coldest climates in North America, Winnipeg, Manitoba,
where temperatures reach below -40 0F (-40 0C). Thus owners of Tempeff equipment can rest assured that they
will enjoy the high performance of their system for a long time.
Applications, Standard and Optional Features, Design considerations 1
Sequence Diagrams 3 – 4
Selection Guide 5 – 6
Performance Data (IMPErIAl) 7 – 8
Performance Data (METrIC) 9 – 10
rG 1800 - 2700 with blowers 11
rG 9000 - 25000 with blowers 12
rG 33000 - 56000 with blowers 13
rG 1800 - 2700 blowers by others 14
rG 9000 - 25000 blowers by others 15
rG 33000 - 56000 blowers by others 16
rG 1800 - 2700 with blowers and heating coil 17
rG 9000 - 25000 with blowers and heating coil 18
rG 33000 - 56000 with blowers and heating coil 19
rG 1800 - 2700 with blowers, heating coil and cooling coil 20
rG 9000 - 25000 with blowers, heating coil and cooling coil 21
rG 33000 - 56000 with blowers, heating coil and cooling coil 22
Sample Specification 24 – 26
90%Temperature Efficiency +/- 5%
21
Typical Applications
Dual Core units can be applied wherever
ventilation air is required. Dual Core units meet
or exceed ASHrAE 62 – 2004 acceptable cross
leakage rates, and are an excellent solution for
energy recovery in ventilation applications.
Some common applications:
• Schools
• Apartment/condocomplexes
• Factories
• Parkades
• Swimmingpools
• Paintshops
And so many more….
Design Considerations
Due to the Dual Core’s innovative damper design, outside air dampers are not necessary to isolate the atmosphere
from the building when the unit is off.
Due to the Dual Core’s fast acting damper design, cross leakage rates are less than 1-3% which is well under
ASHrAE 62 -2004 prescribed acceptable cross leakage rates for energy recovery applications. Consult your local
approval agency to ensure they will allow ASHrAE’s recommendation.
When choosing a location for the unit, ensure that the duct length for outside/exhaust air is as short as possible.
When the cycles switch, the exhaust air in the duct will be drawn back into the outside air. Cross leakage is less
than 1-3%, but will increase with longer outside air duct runs.
If the unit is located indoors, ensure ducting for outside/exhaust air is designed to handle the switching positive
and negative pressures. These ducts will experience alternating positive and negative pressures every 60 seconds.
The supply air and exhaust air duct work (to the unit) must be well insulated to assure maximum heat recovery is
attained. Insulating outside air ducts located in non-heated areas is not necessary.
Standard Features
• Extruded aluminum post and corner construction
• 18 ga galvanized exterior panels
• 22 ga galvanized liner
• 2” Mineral Wool insulation
• All sections come with hinged access doors
• locking latches on controls section
• Multi-Damper switchover section
complete with actuators
• Internal damper section closes completely to
isolate outdoor air from building when unit is disabled.
Eliminates the need for external shut-off dampers
• Galvanized damper blades, damper rods and axles
• Indoor or Outdoor construction
• Supply and Exhaust temperature sensors
• All controls to perform damper sequencing
• Dry contacts to allow damper control by BMS system
• Electric actuators standard up to rG 25000 size,
pneumatic actuators on larger units.
• line voltage to control voltage transformer
Optional Features
• Supply and exhaust blower sections with spring isolation.
• Backward inclined and Airfoil Blowers
• Filter sections
• High efficiency filters
• Heating coil plenums
• Heating coils
• Cooling coil plenums
• Cooling coils
• Special coatings (epoxy, heresite)
• Storm louvers
• Pneumatic Actuators on units up to rG 25000 size
• Drain connection in heat exchanger sections
for high humidity applications
• re-circulating mode contacts to allow air to bypass damper section.
Used in off peak (unoccupied) modes, when outdoor air is not required,
but system is being used to provide heating or cooling for building.
Ancillary outdoor and exhaust air dampers recommended with this option.
• Contact your local Tempeff representative for more available options.
An ideal solution.
CyclingforRecoveryPHASE1
When energy recovery is called for, the dampers position so that Energy Core A will add energy to the supply air stream, heating up the air. Simultaneously Energy Core B is absorbing energy from the exhaust air stream.
2
Recovery OperationTempeffDualCoreEnergy
SimplestForm
A typical Tempeff Dual Core unit contains 2 energy cores (A & B), special change over damper section, an exhaust fan, and a supply fan.
Exhaust Fan
atmosphErE
atmosphErE
supply Fan
ChangE ovErdampEr sECtion
EnErgy CorE A
EnErgy CorE B
ShutOffShutDownStandby
When unit is shut down, the dampers close, isolating the building from the atmosphere.
1
Exhaust Fan
atmosphErE
atmosphErE
EnErgy CorE A
EnErgy CorE B
INERT
INERT
supply Fan
ABSORBING
EMITTING
CyclingforRecoveryPHASE23
After 60 seconds, the dampers reposition. Now Energy Core B is adding the energy it reclaimed in Phase 1 to the supply air stream, heating it up. Simultaneously Energy Core A is “recharging” by absorbing energy from the exhaust air stream. Phase 1 and Phase 2 will alternate every 60 seconds, constantly delivering extremely high energy recovery regardless of outdoor air temperatures. Because the cores switch cycles every 60 seconds, frost does not have a chance to build up, thus energy recovery is constant day in and day out, unlike other traditional types of energy recovery devices.
EMITTING
ABSORBING
Exhaust air
Exhaust air
supply air
outdoor air
EnErgy CorE B
EnErgy CorE A
COLD
CHARGED
FreeCooling4Exhaust air
Exhaust air
supply air
outdoor air
EnErgy CorE B
EnErgy CorE A
If exhaust air and supply air are above set point, unit will revert to Free Cooling Mode. No energy recovery is taking place. Damper will switch every 3 hours to clean core faces.
OptionalRecirculatingMode
In off peak or unoccupied mode, internal dampers can be bypassed so that 100% re-circulated air can be used to heat or cool the building through ancillary heating or cooling devices. External shut off dampers recommended for this option.
5
INERT
INERT
supply air
rEturn air
EnErgy CorE B
EnErgy CorE A
atmosphErE
atmosphErE
43
EnErgy CorE A
EnErgy CorE B
Exhaust air
Exhaust air
outdoor air
supply air
65
How to select a Tempeff Dual Core unit Before starting, establish the required airflow for the
space this unit will be applied to. The selection guide and
performance charts in this manual assume a balanced
airflow system, where supply and exhaust air volumes are
equal. If an unbalanced system is desired, contact your local
Tempeff representative for design assistance.
Step 1
Consult the performance chart on page 7 & 8 and select a
model that is suitable for the air volume desired. Dual Core
models are sized based on required airflow. The models
listed are in cost effective order, the first unit is the lowest
cost, but will typically have a lower temperature efficiency.
The other model options listed will progressively grow in
initial cost, but will have a higher temperature efficiency.
If the air volume needed is larger than the chart reflects,
contact your local Tempeff representative for design
assistance. larger air volumes than catalogued are available.
Step 2
Calculate the leaving air temperature. First determine the
outdoor (entering) air temperature and the exhaust air
temperature. For winter mode calculation the temperature
efficiency of the unit can be obtained from the performance
chart on page 7 & 8. For summer mode the temperature
efficiency can also be obtained from the performance chart
on page 7 & 8.
Temperature Efficiency is calculated by:
Et = ________________T2 - T3
T1 - T3
Et = Temperature efficiency
T1 = Temperature of Exhaust air (Dry Bulb)
T2 = Temperature of Supply air (Dry Bulb)
T3 = Temperature of Outdoor air (Dry Bulb)
Isolating for T2 (supply air) we find:
T2 = Et(T1-T3) + T3
This formula can be used for both winter and summer
modes.
Using the calculated supply air temperature, we can now
determine whether supplementary heat or cooling is required
to meet space conditions.
Determine:
1. Desired Tempeff Dual Core model
2. Supply air temperature in both Summer and Winter modes
3. Regained sensible heating and cooling in BTUH
4. HP requirements for supply and exhaust fans
1. Consulting the performance charts on page 7 & 8 the
following 3 options are available at 10,000 CFM.
1. RG 16000
2. RG 20000
3. RG 25000
The rG 20000 has a temperature efficiency of 89.6%, thus is
very close to the target efficiency. The summer efficiency for
the rG 20000 is 79.6%.
2. Supply air temperature is determined by:
T2 = Et(T1-T3) + T3
Where:
Et = Temperature efficiency
T1 = Temperature of Exhaust air (Dry Bulb)
T2 = Temperature of Supply air (Dry Bulb)
T3 = Temperature of Outdoor air (Dry Bulb)
Winter:
T2 = 0.896 (70 – (-4)) + (-4)
T2 = 62.3 deg F
Summer:
T2 = 0.796 (75-85) + 85
T2 = 77.0 deg F
Using these numbers we can now determine whether
additional heating or cooling is required. Since the desired
winter supply temp is 72 deg F, a heating device is required
to raise the supply temperature by 9.7 deg F. Cooling supply
temperatures match desired, thus no additional cooling is
required. Selecting a heating coil to accomplish the
9.7 deg F adds 0.1” W.C to the system.
Step 3
Calculate regained sensible heating and cooling. Now
that the supply air temperature has been calculated, it
can be used to determine how much sensible heating
and cooling has been regained.
The formula to accomplish this is:
BTUH = (T2-T3) x Airflow x 1.08
This can be used for both winter and summer, if
the number is a negative, that is the sensible BTUH
cooling regained by the unit.
Step 4
Calculate the HP required for both supply and
exhaust. If the supply and exhaust fans are existing
or supplied by others, the static pressure drop added
to the system can be obtained from the performance
chart (Core Pressure Drop). This pressure drop will be
added to both supply and exhaust air streams, thus
the motors must be sized to account for this added
pressure.
If the fans are to be included in the Tempeff unit,
simply add the external static pressure (ESP), any
additional heating or cooling coil pressure drops, and
special filter pressure drops, to get your total ESP.
Using the performance chart, find the column that
corresponds to your total ESP, and select the BHP that
matches the model selected. This value will be used
for both supply and exhaust HP requirements.
ExaMpLE: A space requires 10,000 CFM of
ventilation (outside) air to meet code requirements.
A corresponding 10,000 CFM of exhaust air will be
removed from the space. Both air streams have a
static pressure loss or 0.75 “W.C. A Tempeff Dual
Core unit complete with fans has been selected to
assure maximum energy recovery from the space.
The winter outside design air temperature is -4
deg F, and exhaust temperature is 70 deg F. The
summer outside design air temperature is 85 deg F,
and exhaust temperature is 75 deg F. Desired winter
supply temperature is 72 deg F, and desired summer
leaving temperature is 77 deg F. The target winter
temperature efficiency is 90%
3. Sensible Heating and cooling
recovered determined by:
BTUH = (T2-T3) x Airflow x 1.08
Winter:
BTUH = (62.3 – (-4)) x 10,000 CFM x 1.08
BTUH = 716, 040
Thus at -4 deg F the system will recover
716,040 BTU per hour.
Summer:
BTUH = (77-85) x 10,000 CFM x 1.08
BTUH = - 86,400 BTUH
Thus at 85 deg F the system will regain
86,400 BTU per hour of cooling, or 7.2 tons.
4. Determine HP required for supply
and exhaust fans.
We have been given that the ESP for both supply and
exhaust is 0.75” W.C. Since a heating coil has been
added to the supply air stream, the pressure drop
of the coil must be added. Thus the total ESP for
the supply is 0.85” W.C, and total for the exhaust is
0.75” W.C. To be conservative on the supply air side,
1.0” W.C will be used.
Consulting the performance chart at 10,000 CFM
and 1.0 “W.C ESP = 6.27 bhp
Consulting the performance chart at 10,000 CFM
and 0.75 “W.C ESP = 5.71 bhp
Thus a 7.5 hp motor is the minimum allowable motor
size for both supply and exhaust air fans.
Selection Guide
87
Larger sizes are available, contact your local Tempeff representative for more information
All winter efficiencies are calculated using -4 deg F (-20 deg C).
All efficiencies are +/- 5% depending on site conditions
All efficiencies are across entire base unit, including supply fan and motor
HP values shown include core pressure drop, standard 30% (MERV 7) filter and basic cabinet losses.
Add all ancillary coil, filter and other pressure drops to the ESP to use chart.
For unbalanced air streams, contact your local Tempeff representative
For larger ESP values, contact your local Tempeff representative
PERFORMAnCEDATA IMPERIAL
Available configurations
SF
EF
Type 1
SF
EF
Type 2
Type 3
SF
EF
Type 4
SF
EF
Available configurations
SF
EF
Type 1
SF
EF
Type 2
Type 3
SF
EF
Type 4
SF
EF
available Configurations • Theconfigurationsdifferbasedonlocationsofthefans.• Supplyandexhaustairconnectionmaybeonthebackside.
CFM ModelWinter
Efficiency%Summer
Efficiency%VelocityFPM
CorePressureDrop“WC
BHP@ESP(“W.C)
0.5" 0.75" 1.0" 1.5" 2.0"
750 RG 1800 92.9 82.6 230 0.18 0.33 0.39 0.46 0.53 0.64
1000RG 1800 90.6 80.5 329 0.38 0.54 0.61 0.67 0.79 1.00
RG 2700 92.4 82.1 244 0.20 0.48 0.56 0.63 0.74 0.89
1250
RG 1800 89.1 79.2 396 0.51 0.78 0.87 0.95 1.11 1.29
RG 2700 91.2 81.1 293 0.30 0.60 0.79 0.88 1.04 1.21
RG 3600 93.1 82.8 216 0.15 0.55 0.63 0.82 0.99 1.15
1500
RG 1800 87.8 78.0 461 0.64 0.89 0.99 1.08 1.44 1.68
RG 2700 90.2 80.2 342 0.39 0.80 0.89 0.99 1.38 1.58
RG 3600 92.3 82.0 252 0.22 0.64 0.82 0.92 1.32 1.51
1750
RG 2700 89.2 79.3 392 0.49 0.89 1.00 1.27 1.48 1.71
RG 3600 91.5 81.3 287 0.29 0.81 0.91 1.02 1.39 1.62
RG 5400 92.9 82.6 224 0.16 0.76 0.85 0.96 1.34 1.56
2000
RG 2700 87.6 77.9 464 0.63 1.14 1.26 1.37 1.62 2.10
RG 3600 90.2 80.2 342 0.40 1.04 1.15 1.27 1.50 1.99
RG 5400 91.9 81.7 266 0.24 0.81 1.08 1.19 1.42 1.92
2500
RG 3600 88.3 78.5 431 0.57 1.30 1.43 1.57 2.14 2.43
RG 5400 90.4 80.4 337 0.38 1.21 1.33 1.46 2.04 2.32
RG 7200 92.0 81.8 260 0.23 1.12 1.26 1.38 1.65 2.24
3000RG 5400 88.8 78.9 405 0.51 1.38 1.68 2.01 2.32 2.62
RG 7200 90.8 80.7 313 0.34 1.39 1.56 1.73 2.20 2.52
3500
RG 5400 87.6 77.9 462 0.62 1.98 2.16 2.36 3.02 3.39
RG 7200 89.8 79.8 356 0.42 1.82 2.02 2.20 2.60 3.23
RG 9000 92.8 82.5 220 0.16 1.64 1.82 2.01 2.39 3.05
4000
RG 7200 88.7 78.8 407 0.53 2.38 2.59 2.79 3.22 3.68
RG 9000 92.0 81.8 252 0.23 2.13 2.34 2.54 2.97 3.40
RG 11000 92.2 82.0 240 0.21 2.11 2.32 2.52 2.96 3.39
4500
RG 7200 87.6 77.9 459 0.62 2.33 2.59 2.85 3.96 4.44
RG 9000 91.3 81.2 281 0.29 2.01 2.25 2.50 3.65 4.11
RG 11000 91.6 81.4 270 0.26 1.98 2.21 2.47 3.62 4.09
5000
RG 9000 90.5 80.4 315 0.35 2.43 2.69 2.96 3.51 4.95
RG 11000 90.8 80.7 299 0.33 2.40 2.66 2.94 3.49 4.93
RG 13000 91.2 81.1 281 0.29 2.36 2.62 2.88 3.44 4.04
5500
RG 9000 89.9 79.9 346 0.41 2.90 3.18 3.47 4.07 4.68
RG 11000 90.2 80.2 331 0.39 2.88 3.16 3.45 4.04 4.65
RG 13000 90.5 80.4 309 0.35 2.84 3.11 3.41 3.99 4.60
6000
RG 9000 89.2 79.3 376 0.48 3.45 3.75 4.06 4.68 5.35
RG 11000 89.5 79.6 360 0.44 3.40 3.72 4.01 4.64 5.30
RG 13000 89.9 79.9 337 0.40 3.01 3.37 3.72 4.26 4.90
7000
RG 11000 88.3 78.5 419 0.56 4.71 5.05 5.40 6.10 6.83
RG 13000 88.5 78.7 394 0.51 3.97 4.36 4.77 5.60 6.47
RG 16000 90.7 80.6 295 0.32 3.65 4.05 4.46 5.29 6.14
7500
RG 13000 87.9 78.1 421 0.57 4.51 4.94 5.38 6.26 7.15
RG 16000 90.2 80.2 317 0.37 4.17 4.59 5.03 5.89 6.80
RG 20000 91.7 81.5 256 0.24 3.94 4.38 4.79 5.68 6.56
8000
RG 13000 87.2 77.5 449 0.63 5.12 5.56 6.03 6.96 7.91
RG 16000 89.8 79.8 337 0.41 3.74 4.23 5.61 6.55 7.49
RG 20000 91.3 81.2 272 0.28 4.48 4.92 5.40 6.30 7.24
8500
RG 13000 86.6 77.0 476 0.68 4.59 5.13 6.72 7.69 8.68
RG 16000 89.3 79.4 358 0.45 4.12 4.62 5.15 7.24 8.24
RG 20000 90.9 80.8 289 0.31 3.86 4.35 4.86 6.97 7.96
9000
RG 16000 88.9 79.0 380 0.49 4.54 5.06 5.60 7.99 9.03
RG 20000 90.4 80.4 307 0.35 4.27 4.78 5.29 7.69 8.72
RG 25000 91.9 81.7 246 0.22 4.02 4.51 5.02 6.11 8.47
9500
RG 16000 88.4 78.6 401 0.53 5.00 5.54 6.07 7.24 8.90
RG 20000 90.0 80.0 325 0.38 4.69 5.21 5.75 6.90 8.59
RG 25000 91.7 81.5 260 0.25 4.43 4.95 5.47 6.58 7.62
10000
RG 16000 87.8 78.0 423 0.58 5.53 6.06 6.61 7.81 8.89
RG 20000 89.6 79.6 342 0.42 5.18 5.71 6.27 7.42 8.52
RG 25000 91.4 81.2 274 0.28 4.89 5.29 5.94 7.10 8.31
10500
RG 16000 87.4 77.7 445 0.62 6.07 6.61 7.22 8.39 9.67
RG 20000 89.3 79.4 358 0.45 5.42 6.08 6.75 7.96 9.23
RG 25000 91.1 81.0 287 0.31 5.07 5.70 6.36 7.64 8.87
11000
RG 16000 87.0 77.3 466 0.66 6.34 7.03 7.71 9.03 10.34
RG 20000 88.9 79.0 376 0.49 5.88 6.56 7.24 8.60 9.87
RG 25000 90.8 80.7 301 0.33 5.48 6.13 6.80 8.22 9.46
CFM ModelWinter
Efficiency%Summer
Efficiency%VelocityFPM
CorePressureDrop“WC
BHP@ESP(“W.C)
0.5" 0.75" 1.0" 1.5" 2.0"
11500
RG 16000 86.5 76.9 486 0.71 6.87 7.58 8.31 9.70 11.04
RG 20000 88.5 78.7 394 0.52 6.34 7.05 7.74 9.21 10.54
RG 25000 90.4 80.4 315 0.36 5.95 6.61 7.30 8.74 10.12
12000RG 20000 88.1 78.3 409 0.55 6.87 7.55 8.29 9.77 11.25
RG 25000 90.2 80.2 329 0.39 6.44 7.12 7.83 9.32 10.88
12500RG 20000 87.7 78.0 427 0.59 7.43 8.13 8.88 10.42 12.04
RG 25000 89.9 79.9 342 0.42 6.95 7.64 8.36 9.88 11.47
13000RG 20000 87.3 77.6 445 0.63 8.00 8.76 9.53 11.08 12.75
RG 25000 89.6 79.6 356 0.45 7.48 8.23 8.96 10.53 12.12
13500RG 20000 87.0 77.3 461 0.66 8.60 9.36 10.14 11.74 13.45
RG 25000 89.4 79.5 370 0.47 8.05 8.78 9.56 11.13 12.77
14000RG 20000 86.6 77.0 478 0.70 9.27 10.04 10.83 12.49 14.19
RG 25000 89.1 79.2 384 0.50 8.67 9.45 10.19 11.82 13.50
14500RG 20000 86.2 76.6 496 0.73 9.95 10.74 11.53 13.24 14.99
RG 25000 88.8 78.9 398 0.53 7.24 10.09 10.90 12.52 14.26
15000RG 25000 88.5 78.7 411 0.56 10.02 10.83 11.62 13.31 15.03
RG 33000 91.7 81.5 263 0.25 6.63 7.47 8.37 10.27 13.98
16000RG 25000 87.9 78.1 439 0.62 11.49 12.35 13.20 14.95 16.96
RG 33000 91.3 81.1 280 0.30 7.50 8.35 9.27 11.21 15.60
17000RG 25000 87.4 77.7 466 0.67 13.12 13.97 14.87 16.70 18.56
RG 33000 90.8 80.7 298 0.33 8.39 9.28 10.20 12.15 14.31
18000RG 25000 87.0 77.3 494 0.72 14.47 15.84 16.71 18.56 20.54
RG 33000 90.4 80.4 316 0.36 9.38 10.27 11.22 13.18 15.39
20000RG 33000 89.7 79.7 351 0.44 11.61 12.64 13.59 15.67 17.90
RG 46000 91.1 81.0 290 0.31 9.06 9.98 10.97 13.09 17.31
22000RG 33000 89.3 79.4 365 0.45 14.05 15.02 16.13 18.24 20.59
RG 46000 90.2 80.2 320 0.37 10.97 11.92 12.95 15.08 17.52
24000RG 33000 88.8 78.9 398 0.53 13.57 14.56 15.64 17.90 20.34
RG 46000 89.8 79.8 349 0.43 13.15 14.21 15.25 17.46 19.86
26000RG 33000 87.8 78.1 431 0.60 16.11 17.29 18.36 20.68 23.26
RG 46000 88.9 79.0 377 0.49 15.67 16.73 17.85 20.22 22.63
28000RG 33000 87.0 77.3 465 0.66 16.54 17.89 19.22 22.13 25.26
RG 46000 88.2 78.4 407 0.54 15.92 17.23 18.63 21.47 24.51
30000RG 46000 87.9 78.1 436 0.61 18.49 19.89 21.24 24.19 27.34
RG 56000 89.6 79.6 357 0.45 15.53 16.90 18.36 21.47 26.32
32000RG 46000 87.0 77.3 465 0.66 18.66 20.16 21.61 24.91 28.42
RG 56000 88.9 79.0 381 0.49 17.61 19.17 20.56 23.74 27.12
34000RG 46000 87.0 77.3 494 0.72 21.19 22.73 24.37 27.59 31.16
RG 56000 88.3 78.5 405 0.54 20.05 21.53 23.09 26.35 29.95
36000 RG 56000 87.7 78.0 429 0.59 22.69 24.35 25.95 29.25 32.89
38000 RG 56000 87.1 77.4 453 0.65 24.05 25.70 27.44 31.03 35.00
40000 RG 56000 86.6 77.0 477 0.70 26.84 28.66 30.41 34.17 38.09
41000 RG 56000 86.6 77.0 488 0.71 28.21 30.13 31.95 35.68 39.77
109
Larger sizes are available, contact your local Tempeff representative for more information
All winter efficiencies are calculated using -4 deg F (-20 deg C).
All efficiencies are +/- 5% depending on site conditions
All efficiencies are across entire base unit, including supply fan and motor
HP values shown include core pressure drop, standard 30% (MERV 7) filter and basic cabinet losses.
Add all ancillary coil, filter and other pressure drops to the ESP to use chart.
For unbalanced air streams, contact your local Tempeff representative
For larger ESP values, contact your local Tempeff representative
Available configurations
SF
EF
Type 1
SF
EF
Type 2
Type 3
SF
EF
Type 4
SF
EF
Available configurations
SF
EF
Type 1
SF
EF
Type 2
Type 3
SF
EF
Type 4
SF
EF
available Configurations • Theconfigurationsdifferbasedonlocationsofthefans.• Supplyandexhaustairconnectionmaybeonthebackside.
AirVolumel/s
AirVolumem3/s Model
WinterEfficiency%
SummerEfficiency%
Velocitym/s
CorePressureDropPa
MotorkWrequired@ESP(Pa)
125 186 250 375 500
355 0.36 RG 1800 92.9 82.6 1.17 45 0.25 0.29 0.35 0.39 0.48
475 0.48RG 1800 90.6 80.5 1.67 94 0.40 0.45 0.50 0.59 0.75
RG 2700 92.4 82.1 1.24 50 0.36 0.42 0.47 0.55 0.66
590 0.59
RG 1800 89.1 79.2 2.01 127 0.58 0.65 0.71 0.83 0.96
RG 2700 91.2 81.1 1.49 74 0.45 0.59 0.65 0.78 0.90
RG 3600 93.1 82.8 1.10 37 0.41 0.47 0.61 0.74 0.86
710 0.71
RG 1800 87.8 78.0 2.34 159 0.66 0.74 0.81 1.08 1.25
RG 2700 90.2 80.2 1.74 98 0.60 0.66 0.74 1.03 1.18
RG 3600 92.3 82.0 1.28 55 0.48 0.61 0.68 0.98 1.13
825 0.83
RG 2700 89.2 79.3 1.99 122 0.66 0.75 0.95 1.11 1.28
RG 3600 91.5 81.3 1.46 72 0.61 0.68 0.76 1.04 1.21
RG 5400 92.9 82.6 1.14 40 0.57 0.64 0.71 1.00 1.16
945 0.95
RG 2700 87.6 77.9 2.36 157 0.85 0.94 1.02 1.21 1.57
RG 3600 90.2 80.2 1.74 99 0.78 0.86 0.95 1.12 1.48
RG 5400 91.9 81.7 1.35 60 0.61 0.81 0.89 1.06 1.43
1180 1.18
RG 3600 88.3 78.5 2.19 143 0.97 1.07 1.17 1.60 1.81
RG 5400 90.4 80.4 1.71 94 0.90 0.99 1.09 1.52 1.73
RG 7200 92.0 81.8 1.32 58 0.84 0.94 1.03 1.23 1.67
1415 1.42RG 5400 88.8 78.9 2.06 128 1.03 1.25 1.50 1.73 1.95
RG 7200 90.8 80.7 1.59 84 1.04 1.16 1.29 1.64 1.88
1650 1.65
RG 5400 87.6 77.9 2.35 155 1.48 1.61 1.76 2.25 2.53
RG 7200 89.8 79.8 1.81 105 1.36 1.51 1.64 1.94 2.41
RG 9000 92.8 82.5 1.12 40 1.22 1.36 1.50 1.78 2.28
1890 1.89
RG 7200 88.7 78.8 2.07 131 1.78 1.93 2.08 2.41 2.74
RG 9000 92.0 81.8 1.28 56 1.59 1.74 1.90 2.21 2.54
RG 11000 92.2 82.0 1.22 51 1.58 1.73 1.88 2.21 2.53
2125 2.13
RG 7200 87.6 77.9 2.33 155 1.74 1.93 2.13 2.95 3.31
RG 9000 91.3 81.2 1.43 72 1.50 1.68 1.87 2.72 3.07
RG 11000 91.6 81.4 1.37 65 1.48 1.65 1.84 2.70 3.05
2360 2.36
RG 9000 90.5 80.4 1.60 88 1.81 2.01 2.21 2.62 3.70
RG 11000 90.8 80.7 1.52 81 1.79 1.98 2.19 2.61 3.68
RG 13000 91.2 81.1 1.43 72 1.76 1.95 2.15 2.57 3.01
2600 2.60
RG 9000 89.9 79.9 1.76 103 2.17 2.38 2.59 3.04 3.49
RG 11000 90.2 80.2 1.68 96 2.15 2.36 2.58 3.01 3.47
RG 13000 90.5 80.4 1.57 86 2.12 2.32 2.54 2.97 3.44
2830 2.83
RG 9000 89.2 79.3 1.91 119 2.57 2.80 3.03 3.49 3.99
RG 11000 89.5 79.6 1.83 110 2.54 2.78 2.99 3.46 3.96
RG 13000 89.9 79.9 1.71 100 2.24 2.51 2.77 3.18 3.66
3300 3.30
RG 11000 88.3 78.5 2.13 140 3.51 3.77 4.03 4.55 5.10
RG 13000 88.5 78.7 2.00 128 2.96 3.25 3.56 4.18 4.83
RG 16000 90.7 80.6 1.50 80 2.72 3.02 3.33 3.95 4.58
3540 3.54
RG 13000 87.9 78.1 2.14 142 3.37 3.69 4.01 4.67 5.33
RG 16000 90.2 80.2 1.61 91 3.11 3.43 3.75 4.40 5.07
RG 20000 91.7 81.5 1.30 60 2.94 3.27 3.57 4.24 4.90
3775 3.78
RG 13000 87.2 77.5 2.28 156 3.82 4.15 4.50 5.20 5.90
RG 16000 89.8 79.8 1.71 101 2.79 3.16 4.19 4.89 5.59
RG 20000 91.3 81.2 1.38 69 3.34 3.67 4.03 4.70 5.40
4010 4.01
RG 13000 86.6 77.0 2.42 170 3.43 3.83 5.01 5.74 6.48
RG 16000 89.3 79.4 1.82 111 3.07 3.45 3.84 5.40 6.15
RG 20000 90.9 80.8 1.47 77 2.88 3.24 3.63 5.20 5.94
4250 4.25
RG 16000 88.9 79.0 1.93 122 3.39 3.77 4.18 5.96 6.74
RG 20000 90.4 80.4 1.56 86 3.19 3.57 3.95 5.74 6.51
RG 25000 91.9 81.7 1.25 55 3.00 3.37 3.74 4.56 6.32
4485 4.49
RG 16000 88.4 78.6 2.04 133 3.73 4.14 4.53 5.40 6.64
RG 20000 90.0 80.0 1.65 95 3.50 3.89 4.29 5.15 6.41
RG 25000 91.7 81.5 1.32 62 3.31 3.70 4.08 4.91 5.69
4720 4.72
RG 16000 87.8 78.0 2.15 144 4.13 4.52 4.93 5.83 6.63
RG 20000 89.6 79.6 1.74 104 3.87 4.26 4.68 5.53 6.36
RG 25000 91.4 81.2 1.39 69 3.65 3.95 4.44 5.30 6.20
4955 4.96
RG 16000 87.4 77.7 2.26 155 4.53 4.93 5.39 6.26 7.22
RG 20000 89.3 79.4 1.82 112 4.04 4.54 5.03 5.94 6.89
RG 25000 91.1 81.0 1.46 76 3.78 4.25 4.74 5.70 6.62
5190 5.19
RG 16000 87.0 77.3 2.37 165 4.73 5.25 5.76 6.74 7.72
RG 20000 88.9 79.0 1.91 121 4.39 4.90 5.40 6.42 7.36
RG 25000 90.8 80.7 1.53 83 4.09 4.57 5.07 6.13 7.06
AirVolumel/s
AirVolumem3/s Model
WinterEfficiency%
SummerEfficiency%
VelocityFPM
CorePressureDropPa
MotorkWrequired@ESP(Pa)
125 186 250 375 500
5425 5.43
RG 16000 86.5 76.9 2.47 176 5.13 5.66 6.20 7.24 8.24
RG 20000 88.5 78.7 2.00 130 4.73 5.26 5.77 6.87 7.86
RG 25000 90.4 80.4 1.60 90 4.44 4.93 5.45 6.53 7.56
5660 5.66RG 20000 88.1 78.3 2.08 138 5.13 5.63 6.19 7.29 8.39
RG 25000 90.2 80.2 1.67 97 4.80 5.31 5.84 6.96 8.12
5900 5.90RG 20000 87.7 78.0 2.17 147 5.54 6.06 6.63 7.78 8.99
RG 25000 89.9 79.9 1.74 104 5.19 5.70 6.24 7.37 8.56
6135 6.14RG 20000 87.3 77.6 2.26 156 5.97 6.53 7.11 8.27 9.52
RG 25000 89.6 79.6 1.81 111 5.58 6.14 6.69 7.86 9.05
6370 6.37RG 20000 87.0 77.3 2.34 164 6.42 6.99 7.56 8.76 10.04
RG 25000 89.4 79.5 1.88 118 6.01 6.55 7.13 8.31 9.53
6600 6.60RG 20000 86.6 77.0 2.43 173 6.92 7.49 8.08 9.32 10.59
RG 25000 89.1 79.2 1.95 125 6.47 7.05 7.60 8.82 10.08
6845 6.85RG 20000 86.2 76.6 2.52 181 7.43 8.02 8.60 9.88 11.18
RG 25000 88.8 78.9 2.02 132 5.40 7.53 8.13 9.35 10.64
7080 7.08RG 25000 88.5 78.7 2.09 139 7.48 8.08 8.67 9.93 11.21
RG 33000 91.7 81.5 1.36 62 4.95 5.57 6.25 7.66 10.43
7550 7.55RG 25000 87.9 78.1 2.23 153 8.58 9.22 9.85 11.15 12.66
RG 33000 91.3 81.1 1.45 75 5.60 6.23 6.92 8.36 11.65
8025 8.03RG 25000 87.4 77.7 2.37 166 9.79 10.43 11.10 12.46 13.85
RG 33000 90.8 80.7 1.54 82 6.26 6.93 7.61 9.07 10.68
8500 8.50RG 25000 87.0 77.3 2.51 180 10.80 11.82 12.47 13.85 15.33
RG 33000 90.4 80.4 1.52 90 7.00 7.66 8.37 9.84 11.48
9440 9.44RG 33000 89.7 79.7 1.69 109 8.66 9.43 10.14 11.69 13.36
RG 46000 91.1 81.0 1.48 77 6.76 7.45 8.19 9.77 12.92
10385 10.39RG 33000 89.3 79.4 1.85 112 10.48 11.21 12.04 13.61 15.37
RG 46000 90.2 80.2 1.62 92 8.19 8.89 9.66 11.25 13.07
11330 11.33RG 33000 88.8 78.9 2.02 132 10.12 10.87 11.67 13.36 15.18
RG 46000 89.8 79.8 1.77 107 9.82 10.61 11.38 13.03 14.82
12270 12.27RG 33000 87.8 78.1 2.19 149 12.02 12.91 13.71 15.43 17.36
RG 46000 88.9 79.0 1.92 122 11.69 12.48 13.32 15.09 16.89
13215 13.22RG 33000 87.0 77.3 2.36 164 12.34 13.35 14.34 16.52 18.85
RG 46000 88.2 78.4 2.06 134 11.88 12.86 13.91 16.02 18.29
14160 14.16RG 46000 87.9 78.1 2.21 152 13.80 14.84 15.85 18.06 20.40
RG 56000 89.6 79.6 1.82 112 11.59 12.61 13.71 16.02 19.64
15100 15.10RG 46000 87.0 77.3 2.36 164 13.93 15.04 16.13 18.59 21.21
RG 56000 88.9 79.0 1.94 122 13.14 14.30 15.34 17.72 20.24
16045 16.05RG 46000 87.0 77.3 2.51 179 15.81 16.96 18.19 20.59 23.25
RG 56000 88.3 78.5 2.06 134 14.97 16.06 17.23 19.66 22.35
16990 16.99 RG 56000 87.7 78.0 2.18 147 16.93 18.17 19.36 21.83 24.54
17934 17.93 RG 56000 87.1 77.4 2.30 162 17.95 19.18 20.48 23.16 26.12
18878 18.88 RG 56000 86.6 77.0 2.42 174 20.03 21.39 22.69 25.50 28.42
19350 19.35 RG 56000 86.6 77.0 2.48 177 21.05 22.48 23.84 26.63 29.68
PERFORMAnCEDATA METRIC
1211
+/-
+/-
A B
1265 [49 3/4] 940 [37] 1265 [49 3/4]3470 [136 5/8]
H4
H4
H1
D2D1 D1
D2
H1
H4
H4
Exhaust airExhaust/outdoor - air
Section A Section B
Change over damper section
Heat Exchanger section
Heat Exchanger section Duct connection
Duct connection
Supply airExhaust/outdoor - air
Exhaust air
Supply air
Exhaust fan
Supply fan
F1
F1F3
F2
Notes:1) Also available with optional double doors2) All units in this series have the same length, only height and width differ between the different sizes3) RG 1800-7200 are also available in special compact sizes, with length of 89.4 inches (2270 mm)4) Connections for Exhaust and Outside air = D2 x H45) Connections for supply air = F1 x F16) For reference use only, all information subject to change without notice
BA
+/-
D2D1 D1
D2
+/-
H4
H4
H4
H2
H4
H2
H1
H1
L4
L2 L3 L4
L5 L2
L1
F1
F1 F2
Exhaust air Exhaust/outdoor - air
Section A Section B
Change over dampersection
Heat Exchangersection
Duct connection
Duct connection
L5
F3
H2
H2
Exhaust air
Exhaust fan
Supply fan
Supply air
Supply air
Heat Exchangersection
Exhaust/outdoor - air
Notes:1) Connections for Exhaust and Outside air = D2 x H42) Connections for supply air = F1 x F13) For reference use only, all informationsubject to change without notice
Notes:
1) Connections for Exhaust and Outside air = D2 x H4
2) Connections for supply air = F1 x F1
3) For reference use only, all information subject to change without notice
approxWeight (lbs)model l1 l2 l3 l4 l5 d1 d2 h1 h2 h4 F1 F2 F3
rg 9000 195 2/3 49 4/5 37 48 29 1/2 71 2/3 67 5/7 78 3/4 39 3/8 35 3/7 22 4/9 12 3/5 24 5/8 4730
rg 11000 195 2/3 49 4/5 37 48 29 1/2 74 4/5 70 6/7 78 3/4 39 3/8 35 3/7 22 4/9 12 3/5 24 5/8 5060
rg 13000 210 1/4 49 4/5 51 4/7 48 29 1/2 71 2/3 67 5/7 86 3/5 43 1/3 39 3/8 25 1/5 13 2/5 23 1/4 5720
rg 16000 228 3/4 59 51 4/7 51 4/7 29 1/2 85 3/7 81 1/2 94 1/2 47 1/4 43 1/3 28 1/7 15 1/6 28 2/3 6820
rg 20000 232 2/3 61 51 4/7 51 4/7 29 1/2 92 1/3 88 2/5 106 2/7 53 1/7 49 1/5 31 1/2 17 30 2/5 8140
rg 25000 232 2/3 61 51 4/7 51 4/7 29 1/2 114 1/6 110 1/4 106 2/7 53 1/7 49 1/5 31 1/2 17 41 1/3 9240
approxWeight (kg)model l1 l2 l3 l4 l5 d1 d2 h1 h2 h4 F1 F2 F3
rg 9000 4970 1265 940 1220 750 1820 1720 2000 1000 900 570 320 625.5 2150
rg 11000 4970 1265 940 1220 750 1900 1800 2000 1000 900 570 320 625.5 2300
rg 13000 5340 1265 1310 1220 750 1820 1720 2200 1100 1000 640 340 591 2600
rg 16000 5810 1500 1310 1310 750 2170 2070 2400 1200 1100 715 385.5 727.5 3100
rg 20000 5910 1550 1310 1310 750 2345 2245 2700 1350 1250 800 431.8 772.5 3700
rg 25000 5910 1550 1310 1310 750 2900 2800 2700 1350 1250 800 431.8 1049.5 4200
approxWeight (lbs)model d1 d2 h1 h4 F1 F2 F3
rg 1800 30 1/3 26 3/8 43 18 1/2 11 1/3 7 1/6 9 1/2 1298
rg 2700 37 1/5 33 1/4 46 20 12 2/3 7 5/6 12 1/4 1540
rg 3600 44 40 1/6 50 4/5 22 4/9 14 1/5 9 15 1870
rg 5400 51 1/6 47 1/4 55 1/2 24 4/5 16 10 17 2/3 2376
rg 7200 57 7/8 54 61 4/5 28 17 5/6 10 2/7 20 3058
approxWeight (kg)model d1 d2 h1 h4 F1 F2 F3
rg 1800 770 670 1090 470 288 182 241 590
rg 2700 945 845 1170 510 322 199 311.5 700
rg 3600 1120 1020 1290 570 361 230 379.5 850
rg 5400 1300 1200 1410 630 404 252.4 448 1080
rg 7200 1470 1370 1570 710 453 261.5 508.5 1390
RG1800-2700with blowers RG9000-25000 with blowers
Notes:1) Also available with optional double doors2) All units in this series have the same length, only height and width differ between the different sizes3) rG 1800-7200 are also available in special compact sizes, with length of 89.4 inches (2270 mm)4) Connections for Exhaust and Outside air = D2 x H45) Connections for supply air = F1 x F16) For reference use only, all information subject to change without notice
IMPERIAL (inches)
IMPERIAL (inches)
METRIC (mm)METRIC (mm)
1413
Supply air
Change over damper section
Height = H5
Exhaust duct connection
Supplyductconnection
Exhaust/outdoor - air
Exhaust air
D1 x H1D2 x H2
Exhaust/outdoor - air
+/-
+/-
Heat Exchangersection
L1
L4 x
H4
L3 x
H3
L2L2
Duct Transition: From (D2 x H2) to (L4 x H5), minimum L5 long
Duct Transition: From (D2 x H2) to (L4 x H5), minimum L5 long
Filter and Supply Fan Section
Filter and Exhaust Fan Section
L3 x
H3
L4 x
H4
D4
D1 x H1D2 x H2
D3 D3
Heat Exchangersection
+/-
+/-
A B
1265 [49 3/4] 940 [37] 1265 [49 3/4]3470 [136 5/8]
H4
H4
H1
D2D1 D1
D2
H1
H4
H4
Exhaust air Exhaust/outdoor - air
Section A Section B
Change over damper section
Heat Exchanger section Duct connection
Duct connection
Supply airExhaust/outdoor - air
Exhaust air
Supply air
Heat Exchanger section
Notes:1) Also available with optional double doors2) All units in this series have the same length, only height and width differ between the different sizes3) RG 1800-7200 are also available in special compact sizes, with length of 89.4 inches (2270 mm)4) Connections for Exhaust, Supply and Outside air = D2 x H45) For reference use only, all information subject to change without notice
approxWeight (lbs)model d1 d2 h1 h4
rg 1800 30 1/3 26 3/8 43 18 1/2 1144
rg 2700 37 1/5 33 1/4 46 20 1364
rg 3600 44 40 1/6 50 4/5 22 4/9 1694
rg 5400 51 1/6 47 1/4 55 1/2 24 4/5 2200
rg 7200 57 7/8 54 61 4/5 28 2838
approxWeight (kg)model d1 d2 h1 h4
rg 1800 770 670 1090 470 520
rg 2700 945 845 1170 510 620
rg 3600 1120 1020 1290 570 770
rg 5400 1300 1200 1410 630 1000
rg 7200 1470 1370 1570 710 1290
approxWeight (lbs)model l1 l2 l3 l4 l5 d1 d2 d3 d4 h1 h2 h3 h4 h5
rg 33000 212 3/5 53 1/7 82 2/3 78 3/4 11 4/5 106 2/7 102 1/3 112 1/5 307 82 2/3 78 3/4 82 2/3 78 3/4 82 2/3 19160
rg 46000 212 3/5 53 1/7 82 2/3 78 3/4 11 4/5 130 126 141 3/4 366 1/7 82 2/3 78 3/4 82 2/3 78 3/4 106 2/7 23090
rg 56000 212 3/5 53 1/7 82 2/3 78 3/4 11 4/5 157 1/2 153 1/2 159 4/9 401 4/7 82 2/3 78 3/4 82 2/3 78 3/4 124 28560
approxWeight (kg)model l1 l2 l3 l4 l5 d1 d2 d3 d4 h1 h2 h3 h4 h5
rg 33000 5400 1350 2100 2000 300 2700 2600 2850 7800 2100 2000 2100 2000 2100 8709
rg 46000 5400 1350 2100 2000 300 3300 3200 3600 9300 2100 2000 2100 2000 2700 10495
rg 56000 5400 1350 2100 2000 300 4000 3900 4050 10200 2100 2000 2100 2000 3150 12982
RG33000-56000 with blowers RG1800-2700 blowers by others
IMPERIAL (inches)
IMPERIAL (inches)
METRIC (mm)
METRIC (mm)
Notes:1) Also available with optional double doors2) All units in this series have the same length, only height and width differ between the different sizes3) rG 1800-7200 are also available in special compact sizes, with length of 89.4 inches (2270 mm)4) Connections for Exhaust, Supply and Outside air = D2 x H45) For reference use only, all information subject to change without notice
Notes:1) Plan view shown2) For reference use only, subject to change without notice. Contact your local TEMPEFF representative for job specific data.
1615
BA
+/-
D2D1 D1
D2
+/-
H4
H2
H4
H2
H4
H2
H4
H2
H1
H1
L4
L3 L4L1
Exhaust air Exhaust/outdoor - air
Section A Section B
Duct connection
Duct connection
Supply airExhaust/outdoor - air
Exhaust air
Supply air
Recommendedsupport(not included)
S
S
Change over dampersection
Heat Exchangersection
Heat Exchangersection
Notes:1) Connections for Exhaust, Supply and Outside air = D2 x H42) For reference use only, all information subject to change without notice
Supply air
Change over damper section
Heat Exchanger
section
Exhaust duct connection
Supplyductconnection
Exhaust/outdoor - air
Exhaust air
FOR REFERENCE USE ONLY, SUBJECT TO CHANGE WITHOUT NOTICE
D1 x H1D2 x H2
Exhaust/outdoor - air
+/-
+/-
Heat Exchanger
section
L1
L4 x
H4
L3 x
H3
L2L2
Duct Transition: From (D2 x H2) to (L4 x H4), minimum L5 long
Duct Transition: From (D2 x H2) to (L4 x H4), minimum L5 long
D1 x H1D2 x H2
L3 x
H3
L4 x
H4
CONTACT YOUR LOCAL TEMPEFF REPRESENTATIVE FOR JOB SPECIFIC DATA
RG9000-25000 blowers by others RG33000-56000 blowers by others
approxWeight (lbs)model l1 l3 l4 d1 d2 h1 h2 h4
rg 9000 133 37 48 71 2/3 67 5/7 78 3/4 39 3/8 35 3/7 3800
rg 11000 133 37 48 74 4/5 70 6/7 78 3/4 39 3/8 35 3/7 4070
rg 13000 147 2/3 51 4/7 48 71 2/3 67 5/7 86 3/5 43 1/3 39 3/8 4620
rg 16000 154 5/7 51 4/7 51 4/7 85 3/7 81 1/2 94 1/2 47 1/4 43 1/3 5720
rg 20000 154 5/7 51 4/7 51 4/7 92 1/3 88 2/5 106 2/7 53 1/7 49 1/5 6600
rg 25000 154 5/7 51 4/7 51 4/7 114 1/6 110 1/4 106 2/7 53 1/7 49 1/5 8250
IMPERIAL (inches)
approxWeight (kg)model l1 l3 l4 d1 d2 h1 h2 h4
rg 9000 3380 940 1220 1820 1720 2000 1000 900 1730
rg 11000 3380 940 1220 1900 1800 2000 1000 900 1850
rg 13000 3750 1310 1220 1820 1720 2200 1100 1000 2100
rg 16000 3930 1310 1310 2170 2070 2400 1200 1100 2600
rg 20000 3930 1310 1310 2345 2245 2700 1350 1250 3000
rg 25000 3930 1310 1310 2900 2800 2700 1350 1250 3750
METRIC (mm)
approxWeight (kg)model l1 l2 l3 l4 l5 d1 d2 h1 h2 h3 h4 h5
rg 33000 5400 1350 2100 2000 300 2700 2600 2100 2000 2100 2000 2100 5300
rg 46000 5400 1350 2100 2000 300 3300 3200 2100 2000 2100 2000 2700 7200
rg 56000 5400 1350 2100 2000 300 4000 3900 2100 2000 2100 2000 3150 8800
approxWeight (lbs)model l1 l2 l3 l4 l5 d1 d2 h1 h2 h3 h4 h5
rg 33000 212 3/5 53 1/7 82 2/3 78 3/4 11 4/5 106 2/7 102 1/3 82 2/3 78 3/4 82 2/3 78 3/4 82 2/3 11660
rg 46000 212 3/5 53 1/7 82 2/3 78 3/4 11 4/5 130 126 82 2/3 78 3/4 82 2/3 78 3/4 106 2/7 15840
rg 56000 212 3/5 53 1/7 82 2/3 78 3/4 11 4/5 157 1/2 153 1/2 82 2/3 78 3/4 82 2/3 78 3/4 124 19360
IMPERIAL (inches)
METRIC (mm)
Notes:1) Connections for Exhaust, Supply and Outside air = D2 x H42) For reference use only, all information subject to change without notice
Notes:1) Plan view shown2) For reference use only, subject to
change without notice. Contact your local TEMPEFF representative for job specific data.
1817
+/-
+/-
A B
1265 [49 3/4] 940 [37] 1265 [49 3/4]3470 [136 5/8]
H4
H4
H1
D2D1 D1
D2
H1
H4
H4
Exhaust air Exhaust/outdoor - air
Section A Section B
Change over damper section
Heat Exchanger section
Heat Exchanger section Duct connection
Duct connection
Supply airExhaust/outdoor - air
Exhaust air
Supply air
Exhaust fan
Supply fan
F1
F1F3
F2
HeatingCoil
Coil connectionsthis side
Notes:1) Also available with optional double doors2) All units in this series have the same length, only height and width differ between the different sizes3) Connections for Exhaust and Outside air = D2 x H44) Connections for supply air = F1 x F15) With heating coil option in this configuration only 2" flat filters are available.6) For reference use only, all information subject to change without notice
BA
+/-
D2D1 D1
D2
+/-
H4
H4
H4
H2
H4
H2
H1
H1
L4
L2 L3 L4
L5 L2
L1
F1
F1 F2
Exhaust airExhaust/outdoor - air
Section A Section B
Duct connection
Duct connection
Supply airExhaust/outdoor - air
Exhaust air
Supply air
Exhaust fan
Supply fan
L5
F3
H2
H2
HeatingCoil
Coil connectionsthis side
Change over dampersection
Notes:1) Connections for Exhaust and Outside air = D2 x H42) Connections for supply air = F1 x F13) With heating coil option in this configuration only 2" flat filters are available.4) For reference use only, all information subject to change without notice
Heat Exchangersection
Heat Exchangersection
Heating Coil
max Finheight
max Finlength
approxWeight (lbs)model l1 l2 l3 l4 l5 d1 d2 h1 h2 h4 F1 F2 F3
rg 9000 195 2/3 49 4/5 37 48 29 1/2 71 2/3 67 5/7 78 3/4 39 3/8 35 3/7 22 4/9 12 3/5 24 5/8 30 56 4930
rg 11000 195 2/3 49 4/5 37 48 29 1/2 74 4/5 70 6/7 78 3/4 39 3/8 35 3/7 22 4/9 12 3/5 24 5/8 30 59 5310
rg 13000 210 1/4 49 4/5 51 4/7 48 29 1/2 71 2/3 67 5/7 86 3/5 43 1/3 39 3/8 25 1/5 13 2/5 23 1/4 33 3/4 56 6020
rg 16000 228 3/4 59 51 4/7 51 4/7 29 1/2 85 3/7 81 1/2 94 1/2 47 1/4 43 1/3 28 1/7 15 1/6 28 2/3 37 1/2 70 7170
rg 20000 232 2/3 61 51 4/7 51 4/7 29 1/2 92 1/3 88 2/5 106 2/7 53 1/7 49 1/5 31 1/2 17 30 2/5 43 1/2 77 8540
rg 25000 232 2/3 61 51 4/7 51 4/7 29 1/2 114 1/6 110 1/4 106 2/7 53 1/7 49 1/5 31 1/2 17 41 1/3 43 1/2 99 9690
Heating Coil
max Finheight
max Finlength
approxWeight (lbs)model d1 d2 h1 h4 F1 F2 F3
rg 1800 30 1/3 26 3/8 43 18 1/2 11 1/3 7 1/6 9 1/2 10 15 1518
rg 2700 37 1/5 33 1/4 46 20 12 2/3 7 5/6 12 1/4 11 1/4 22 1815
rg 3600 44 40 1/6 50 4/5 22 4/9 14 1/5 9 15 13 3/4 29 1980
rg 5400 51 1/6 47 1/4 55 1/2 24 4/5 16 10 17 2/3 16 1/4 36 2728
rg 7200 57 7/8 54 61 4/5 28 17 5/6 10 2/7 20 20 42 3432
Heating Coil
max Finheight
max Finlength
approxWeight (kg)model d1 d2 h1 h4 F1 F2 F3
rg 1800 770 670 1090 470 288 182 241 254 381 690
rg 2700 945 845 1170 510 322 199 311.5 286 559 825
rg 3600 1120 1020 1290 570 361 230 379.5 349 737 900
rg 5400 1300 1200 1410 630 404 252.4 448 413 914 1240
rg 7200 1470 1370 1570 710 453 261.5 508.5 508 1067 1560
Heating Coil
max Finheight
max Finlength
approxWeight (kg)model l1 l2 l3 l4 l5 d1 d2 h1 h2 h4 F1 F2 F3
rg 9000 4970 1265 940 1220 750 1820 1720 2000 1000 900 570 320 625.5 762 1422 2240
rg 11000 4970 1265 940 1220 750 1900 1800 2000 1000 900 570 320 625.5 762 1499 2415
rg 13000 5340 1265 1310 1220 750 1820 1720 2200 1100 1000 640 340 591 857 1422 2735
rg 16000 5810 1500 1310 1310 750 2170 2070 2400 1200 1100 715 385.5 727.5 953 1778 3250
rg 20000 5910 1550 1310 1310 750 2345 2245 2700 1350 1250 800 431.8 772.5 1105 1956 3885
rg 25000 5910 1550 1310 1310 750 2900 2800 2700 1350 1250 800 431.8 1049.5 1105 2515 4405
RG1800-2700 with blowers and heating coil RG9000-25000 with blowers and heating coil
IMPERIAL (inches)
METRIC (mm)
IMPERIAL (inches)
METRIC (mm)
Notes:1) Connections for Exhaust and
Outside air = D2 x H42) Connections for supply air = F1 x F13) With heating coil option in this configuration only 2” flat filters are available.4) For reference use only, all
information subject to change without notice
Notes:1) Also available with optional double doors2) All units in this series have the same length, only height and width
differ between the different sizes3) Connections for Exhaust and Outside air = D2 x H44) Connections for supply air = F1 x F15) With heating coil option in this configuration only 2” flat filters are available.6) For reference use only, all information subject to change without notice
2019
Supply air
Change over damper section
Height = H5
Heat Exchanger
section
Exhaust duct connection
Supplyductconnection
Exhaust/outdoor - air
Exhaust air
FOR REFERENCE USE ONLY, SUBJECT TO CHANGE WITHOUT NOTICE
D1 x H1D2 x H2
Exhaust/outdoor - air
+/-
+/-
Heat Exchanger
section
L1
L4 x
H4
L3 x
H3
L2L2
Duct Transition: From (D2 x H2) to (L4 x H5), minimum L5 long
Duct Transition: From (D2 x H2) to (L4 x H5), minimum L5 long
Filter and Supply Fan Section
Filter and Exhaust Fan Section
L3 x
H3
L4 x
H4
D4
D1 x H1D2 x H2
D3 D3D5
HeatingCoil
CONTACT YOUR LOCAL TEMPEFF REPRESENTATIVE FOR JOB SPECIFIC DATANotes:1) Also available with optional double doors2) All units in this series have the same length, only height and width differ between the different sizes3) Connections for Exhaust and Outside air = D2 x H44) Connections for supply air = F1 x F15) With heating coil option in this configuration only 2" flatfilters are available.6) For reference use only, all information subject to change without notice
+/-
+/-
AB
1265 [49 3/4] 940 [37] 1265 [49 3/4]4220 [166 1/8]
H4
H4
H1
D2D1 D1
D2
H1
H4
H4
Exhaust air Exhaust/outdoor - air
Section A Section B
Change over damper section
Heat Exchanger section
Heat Exchanger sectionDuct connection
Duct connection
Supply airExhaust/outdoor - air
Exhaust air
Supply air
Exhaust fan
Supply fan
HeatingCoil
L5
CoolingCoil
Coil connectionsthis side
Heating Coil Cooling Coil
max Finheight
max Finlength
max Finheight
max Finlength
approxWeight (lbs)model d1 d2 h1 h4 l5
rg 1800 30 1/3 26 3/8 43 18 1/2 29 1/2 10 15 10 15 1838
rg 2700 37 1/5 33 1/4 46 20 29 1/2 11 1/4 22 11 1/4 22 2175
rg 3600 44 40 1/6 50 4/5 22 4/9 29 1/2 13 3/4 29 13 3/4 29 2430
rg 5400 51 1/6 47 1/4 55 1/2 24 4/5 29 1/2 16 1/4 36 16 1/4 36 3228
rg 7200 57 7/8 54 61 4/5 28 29 1/2 20 42 20 42 4032
Heating Coil Cooling Coil
max Finheight
max Finlength
max Finheight
max Finlength
approxWeight (kg)model d1 d2 h1 h4 l5
rg 1800 770 670 1090 470 750 254 381 254 381 835
rg 2700 945 845 1170 510 750 286 559 286 559 990
rg 3600 1120 1020 1290 570 750 349 737 349 737 1105
rg 5400 1300 1200 1410 630 750 413 914 413 914 1465
rg 7200 1470 1370 1570 710 750 508 1067 508 1067 1830
Heating Coil
max Finheight
max Finlength
approxWeight (lbs)model l1 l2 l3 l4 l5 d1 d2 d3 d4 d5 h1 h2 h3 h4 h5
rg 33000 212 3/5 53 1/7 82 2/3 78 3/4 11 4/5 106 2/7 102 1/3 112 1/5 336 3/5 29 1/2 82 2/3 78 3/4 82 2/3 78 3/4 82 2/3 72 67 20260
rg 46000 212 3/5 53 1/7 82 2/3 78 3/4 11 4/5 130 126 141 3/4 401 4/7 35 3/7 82 2/3 78 3/4 82 2/3 78 3/4 106 2/7 72 67 24330
rg 56000 212 3/5 53 1/7 82 2/3 78 3/4 11 4/5 157 1/2 153 1/2 159 4/9 437 35 3/7 82 2/3 78 3/4 82 2/3 78 3/4 124 72 67 29900
Heating Coil
max Finheight
max Finlength
approxWeight (kg)model l1 l2 l3 l4 l5 d1 d2 d3 d4 d5 h1 h2 h3 h4 h5
rg 33000 5400 1350 2100 2000 300 2700 2600 2850 8550 750 2100 2000 2100 2000 2100 1829 1702 9209
rg 46000 5400 1350 2100 2000 300 3300 3200 3600 10200 900 2100 2000 2100 2000 2700 1829 1702 11059
rg 56000 5400 1350 2100 2000 300 4000 3900 4050 11100 900 2100 2000 2100 2000 3150 1829 1702 13591
RG33000-56000 with blowers and heating coil RG1800-2700 with blowers, heating coil and cooling coil
IMPERIAL (inches)
IMPERIAL (inches)
METRIC (mm)
METRIC (mm)
Notes:1) Also available with optional double doors2) All units in this series have the same
length, only height and width differ between the different sizes
3) Connections for Exhaust, Supply and Outside air = D2 x H4
4) With heating coil option in this configura-tion only 2” flat filters are available.
5) For reference use only, all information subject to change without notice
Notes:1) Plan view shown2) For reference use only, subject to change without notice. Contact your local TEMPEFF representative for job specific data.
2221
BA
+/-
D2D1 D1
D2
+/-
H4
H4
H4
H2
H4
H2
H1
H1
L4
L2 L3 L4
L5 L2
L1
F1F1 F2
Exhaust air Exhaust/outdoor - air
Section A Section B
Duct connection
Duct connection
Supply airExhaust/outdoor - air
Exhaust air
Supply air
Exhaust fan
Supply fan
L5
F3
H2
H2
HeatingCoil
L5
CoolingCoil
Coil connectionsthis side
Change over dampersection
Notes:1) Connections for Exhaust and Outside air = D2 x H42) Connections for supply air = F1 x F13) With heating coil option in this configuration only 2" flat filters are available.4) For reference use only, all information subject to change without notice
Heat Exchangersection
Heat Exchangersection
Supply air
Change over damper section
Height = H5
Exhaust duct connection
Supplyductconnection
Exhaust air
FOR REFERENCE USE ONLY, SUBJECT TO CHANGE WITHOUT NOTICECONTACT YOUR LOCAL TEMPEFF REPRESENTATIVE FOR JOB SPECIFIC DATA
D1 x H1D2 x H2
Exhaust/outdoor - air
+/-
+/-
Heat Exchangersection
Heat Exchangersection
L1
L4 x
H4
L3 x
H3
L2L2
Duct Transition: From (D2 x H2) to (L4 x H5), minimum L5 long
Duct Transition: From (D2 x H2) to (L4 x H5), minimum L5 long
Filter and Supply Fan Section
Filter and Exhaust Fan Section
L3 x
H3
L4 x
H4
D4
D1 x H1D2 x H2
D3 D3D5
HeatingCoil
CoolingCoil
Exhaust/outdoor - air
Recommended maximum single coil height = 51", coils
taller than 51" should be ordered as dual coils
RG9000-25000 with blowers, heating coil and cooling coil RG33000-56000 with blowers, heating coil and cooling coil
Heating Coil Cooling Coil
max Finheight
max Finlength
max Finheight
max Finlength
approxWeight (lbs)model l1 l2 l3 l4 l5 d1 d2 d3 d4 d5 h1 h2 h3 h4 h5
rg 33000 212 3/5 53 1/7 82 2/3 78 3/4 11 4/5 106 2/7 102 1/3 112 1/5 366 1/7 59 82 2/3 78 3/4 82 2/3 78 3/4 82 2/3 72 67 72 67 21360
rg 46000 212 3/5 53 1/7 82 2/3 78 3/4 11 4/5 130 126 141 3/4 437 70 6/7 82 2/3 78 3/4 82 2/3 78 3/4 106 2/7 72 67 72 67 25570
rg 56000 212 3/5 53 1/7 82 2/3 78 3/4 11 4/5 157 1/2 153 1/2 159 4/9 472 4/9 70 6/7 82 2/3 78 3/4 82 2/3 78 3/4 124 72 67 72 67 31240
Heating Coil Cooling Coil
max Finheight
max Finlength
max Finheight
max Finlength
approxWeight (kg)model l1 l2 l3 l4 l5 d1 d2 d3 d4 d5 h1 h2 h3 h4 h5
rg 33000 5400 1350 2100 2000 300 2700 2600 2850 9300 1500 2100 2000 2100 2000 2100 1829 1702 1829 1702 9709
rg 46000 5400 1350 2100 2000 300 3300 3200 3600 11100 1800 2100 2000 2100 2000 2700 1829 1702 1829 1702 11623
rg 56000 5400 1350 2100 2000 300 4000 3900 4050 12000 1800 2100 2000 2100 2000 3150 1829 1702 1829 1702 14200
Heating Coil Cooling Coil
max Finheight
max Finlength
max Finheight
max Finlength
approxWeight (lbs)model l1 l2 l3 l4 l5 d1 d2 h1 h2 h4 F1 F2 F3
rg 9000 225 1/5 49 4/5 37 48 29 1/2 71 2/3 67 5/7 78 3/4 39 3/8 35 3/7 22 4/9 12 3/5 24 5/8 30 56 30 56 5400
rg 11000 225 1/5 49 4/5 37 48 29 1/2 74 4/5 70 6/7 78 3/4 39 3/8 35 3/7 22 4/9 12 3/5 24 5/8 30 59 30 59 5830
rg 13000 239 3/4 49 4/5 51 4/7 48 29 1/2 71 2/3 67 5/7 86 3/5 43 1/3 39 3/8 25 1/5 13 2/5 23 1/4 33 3/4 56 33 3/4 56 6600
rg 16000 258 1/4 59 51 4/7 51 4/7 29 1/2 85 3/7 81 1/2 94 1/2 47 1/4 43 1/3 28 1/7 15 1/6 28 2/3 37 1/2 70 37 1/2 70 7830
rg 20000 262 1/5 61 51 4/7 51 4/7 29 1/2 92 1/3 88 2/5 106 2/7 53 1/7 49 1/5 31 1/2 17 30 2/5 43 1/2 77 43 1/2 77 9290
rg 25000 262 1/5 61 51 4/7 51 4/7 29 1/2 114 1/6 110 1/4 106 2/7 53 1/7 49 1/5 31 1/2 17 41 1/3 43 1/2 99 43 1/2 99 10540
Heating Coil Cooling Coil
max Finheight
max Finlength
max Finheight
max Finlength
approxWeight (kg)model l1 l2 l3 l4 l5 d1 d2 h1 h2 h4 F1 F2 F3
rg 9000 5720 1265 940 1220 750 1820 1720 2000 1000 900 570 320 625.5 762 1422 762 1422 2455
rg 11000 5720 1265 940 1220 750 1900 1800 2000 1000 900 570 320 625.5 762 1499 762 1499 2650
rg 13000 6090 1265 1310 1220 750 1820 1720 2200 1100 1000 640 340 591 857 1422 857 1422 3000
rg 16000 6560 1500 1310 1310 750 2170 2070 2400 1200 1100 715 385.5 727.5 953 1778 953 1778 3560
rg 20000 6660 1550 1310 1310 750 2345 2245 2700 1350 1250 800 431.8 772.5 1105 1956 1105 1956 4225
rg 25000 6660 1550 1310 1310 750 2900 2800 2700 1350 1250 800 431.8 1049.5 1105 2515 1105 2515 4790
IMPERIAL (inches)
IMPERIAL (inches)
METRIC (mm)
METRIC (mm)
Notes:1) Connections for Exhaust and Outside air = D2 x H42) Connections for supply air = F1 x F13) With heating coil option in this configuration only 2” flat filters are available.4) For reference use only, all information subject to change without notice Notes:
1) Plan view shown2) For reference use only, subject to change without notice. Contact your local TEMPEFF representative for job specific data.
2423
SAMPLE SPECIFICATIOnPRODUCTS1.01 MaNUFaCTURERS
A. The following manufacturers are approved for use. No substitutions will be permitted.
1. Tempeff as basis of design
1.02 GENERaL DESCRIpTION
A. Configuration: Fabricate as detailed on drawings.
B. Performance: See schedules on prints.
1.03 UNIT CONSTRUCTION
A. Fabricate unit with extruded aluminum channel posts and galvanized panels secured with mechanical fasteners. Unit shall be capable
of having all wall panels removed simultaneously without affecting the structural integrity of the unit. All access doors shall be sealed with
permanently applied bulb-type gasket.
1. Panels and access doors shall be constructed as a 2-inch (50-mm) nominal thick; thermal broke double wall assembly, with 4.0 lb/ft3
mineral wool insulation. The outer panel shall be constructed of G90 galvanized 18-gauge steel. The inner liner shall be constructed of
22 gauge G90 galvanized steel. Module to module assembly shall be accomplished with self adhering foam gaskets.
2. Entire unit shall be placed on a [4] [6] [8] [10] [12]-inch full perimeter base rail if condensate trapping is required. The following
calculation shall determine the required height of the baserail to allow for adequate drainage. Use the largest pressure to determine base
rail height. [(Negative)(Positive) static pressure (in)] (2) + 4” = required baserail height. Should the unit baserail not be factory supplied
at this height, the contractor is required to supply a frame to make up the difference.]
B. Access Doors shall be flush mounted to cabinetry, with minimum of two hinges, locking latch and full size handle assembly.
1.04 SUppLY / RETURN FaNS
A. Provide [DWDI forward-curved] [DWDI airfoil] [belt-drive airfoil plenum] [direct-drive airfoil plenum] supply [return] fan(s). Fan assemblies
including fan, motor and sheaves shall be dynamically balanced by the manufacturer on all three planes and at all bearing supports.
Manufacturer must ensure maximum fan rPM is below the first critical speed.
B. Bearings shall be self-aligning, grease lubricated, ball or roller bearings.
C. Fan and motor shall be mounted internally on a steel base. Provide access to motor, drive, and bearings through hinged access door. Fan
and motor assembly shall be mounted on spring vibration type isolators inside cabinetry
1.05 BEaRINGS aND DRIVES
A. Bearings: Basic load rating computed in accordance with AFBMA - ANSI Standards, [l-50 life at 200,000 hours – all DWDI fans] [l-50 life
at 500,000 hours – DWDI fans on unit sizes 003 - 035], [l-50 life at 400,000 hours all belt-drive airfoil plenum fans and DWDI fans on unit
sizes greater than 035] [l-50 life 1,000,000 hours – DWDI fans on unit sizes 003 – 035] [l-50 life at 600,000 hours – all inline fans], heavy
duty pillow block type, self-aligning, grease-lubricated ball bearings.
B. Shafts shall be solid, hot rolled steel, ground and polished, keyed to shaft, and protectively coated with lubricating oil. Hollow shafts are not
acceptable.
C. V-Belt drives shall be cast iron or steel sheaves, dynamically balanced, bored to fit shafts and keyed. [Fixed sheaves, matched belts, and
drive rated based on motor horsepower] [Variable and adjustable pitch sheaves selected so required rPM is obtained with sheaves set at mid-
position and rated based on motor horsepower]. Minimum of 2 belts shall be provided on all fans with 10 HP motors and above. Standard drive
service factor shall be [1.1 S.F. (for 1/4 HP – 7.5 HP)] [1.3 S.F. (for 10HP and larger)], calculated based on fan brake horsepower.
90%Temperature Efficiency +/- 5%
2625
1.10 UNIT CONTROL FUNCTION
A. Testing Damper Actuators
1. Damper motors can be tested by using the changeover switch S1 in the damper control panel.
2. The normal position of the S1 switch is 0 where the actuators follow the signals from a central control system (BMS)
3. If S1 is in position 1 the damper actuator M7 runs continuously, and in position 2 actuator M6 runs continuously
B. Sequence with the unit controlled by central control system (BMS)
1. When the S2 switch is in position A (automatic) the damper is controlled by the central control system (BMS)
a. Contact1(seefieldwiringdiagram)controlsthewhetherthedamperoperatesornot(contactclosed=operating,opennotoperating)
b. Contact2(seefieldwiringdiagram)controlsthedamperoperatingmode(contactclosed=heatrecovery,open=freecooling)
2. Contact 1 closed and contact 2 open = damper changes position every 3 hours (free cooling)
3. Contact 1 closed and contact 2 closed = damper changes position every 60 seconds (field adjustable) heat recovery
4. Contact 1 open and contact 2 open = the damper is closed
C. Operation of the changeover damper if central control system is not used
1. Set the changeover switch S2 in the M position (manual)
2. Damper is now controlled by the 2 internal thermostats GT1 in the supply air and GT2 in the exhaust air.
GT1 is set to 59 oF (15 oC) and GT2 is set to 68 oF (20 oF).
3. The sequence will now be:
a. If exhaust air < 68 oF (20 oC)=heatrecovery(cyclingevery60seconds)
b. If exhaust air > 68 oF (20 oC)andsupplyair>59oF (15 oC)=freecooling(cyclingevery3hours)
c. If exhaust air > 68 oF (20 oC)andsupplyair<59oF (15 oC)=heatrecoveryuntilsupplyair>59oF (15 oC)
thenitwillreverttofreecoolingmode.
4. When the S2 switch is in position 0 = shut off = all dampers closed.
D. Fans, heating and cooling
1. Starting and stopping of supply and exhaust fans will be by others (central control system)
2. Any type of supplemental heating or cooling of the supply air will be controlled by others (central control system)
Note: In all cases ensure that damper section is first on and last off, (after supply and exhaust blower section) to prevent damage
to internal damper section.
EXECUTIOn2.01 INSTaLLaTION
A. Install in accordance with manufacturer’s Installation & Maintenance instructions.
2.02 ENVIRONMENTaL REQUIREMENTS
A. Do not operate units for any purpose, temporary or permanent, until ductwork is clean,
filters are in place, bearings lubricated, and fan has been test run under observation.
1.06 ELECTRICaL
A. The air handler(s) components shall be CSA, Ul or CE listed as applicable.
B. On rG sizes 1800 through 25000 all controls shall be located on the side of the unit for ease of servicing. Units within this size range which will
come with controls on roof shall be provided with a permanently installed ladder to access controls, meeting all applicable OSHA standards.
C. Wiring Termination: Provide terminal lugs to match branch circuit conductor quantities, sizes, and materials indicated. All wires shall be
number tagged and cross-referenced to the wiring diagram for ease of troubleshooting.
D. Fan motors shall be [1800 rpm, open drip-proof (ODP)] [1800 rpm, totally enclosed fan-cooled (TEFC)] [1800/1200 rpm, 2 Speed/2
Winding (ODP) (TEFC)] [1800/900 rpm, 2 Speed/1 Winding (ODP)(TEFC)] type. Motors shall be [standard efficiency.] [high efficiency to
meet EPAct requirements.] [premium efficiency.] Electrical characteristics shall be as shown in schedule.
E. [Supplier shall provide and mount variable speed drive with electrical characteristics as shown on project schedule. [A two-contactor type
bypass switch shall be provided.] [A line reactor shall be provided.]
F. Air handler manufacturer shall provide and mount a damper hand-off-auto (HOA) switch.
1.07 paRTICULaTE FILTERS
A. [Filter section with filter racks and guides with hinged and latching access doors on either, or both sides, for side loading and removal of
filters] [Filter section with front loading frames and clips].
B. Filter media shall be Ul 900 listed, Class I or Class II.
C. [Flat] [Angle] arrangement with [2”, 50mm] [4”, 100mm] deep [pleated] [disposable] panel filters.
D. [Bag] [Cartridge] type arrangement with holding frames suitable for [2” (50 mm)], [4” (100 mm)] prefilter and final filter media and blank-off
sheets, extended surface [bag] [cartridge] media filters with [60-65] [80-85] [90-95] percent dust spot efficiency. Bag filter media [12” (305
mm )] [15” (381 mm)] [19” (483 mm)] [22” (559 mm)] [30” (762 mm)] [36” (914 mm)] deep. Cartridge filter media is [4” (50 mm)] [12”
(305 mm)] deep. [Provide microbial resistant Intersept® coating on all filters.] Designed for side loading of filters.
1.08 ENERGY RECOVERY
A. Dual Core Energy recovery
1. Unit shall be equipped with Tempeff Dual Core energy recovery technology. The unit shall be 90% temperature efficient (+-5%) in winter
and up to 80% in summer. It shall also provide up to 70% latent recovery. Unit shall accomplish this recovery without a defrost cycle that will
reduce the effectiveness of the device. Devices employing defrost cycles that bypass the heat recovery device, or reduce the effectiveness
are not acceptable. Heat recovery device shall not require frost protection in applications down to -40 degrees. Cores shall be Generation 3,
comprised of precisely corrugated high grade aluminum.
2. Switchover damper section shall be comprised of multi section low leakage dampers operated by electric damper motors complete with
DC braking (pneumatic on sizes rG 33000 and larger). Each damper shall control one of the 4 airways, upper-horizontal, lower-horizontal,
forward-vertical and rear-vertical. Dampers shall be capable of orienting to close off outside air to the building without needing external shut
off dampers. Units employing single blade dampers must include external shut-off dampers. Dampers shall also be capable of orienting
to allow 100% recirculation of air without using heat recovery device for off peak or unoccupied heating modes. Units incapable of these
operations are not acceptable. Damper blades, rods and axles shall be galvanized for long life expectancy.
3. recovery cycles shall be controlled by internal programmed thermostats measuring both supply and exhaust air, and optimizing
performance of both heat recovery and free cooling modes.
1.09 ExTERNaL DaMpERS
[Damper leakage: leakage rate shall be less than two tenths of one percent leakage at 2 inches static pressure differential.
leakage rate tested in accordance with AMCA Standard 500.]