Sepam Offer EN 2007_01.ppt 1 THE "GUIDING SYSTEM"

Upload: audi

Post on 19-Jan-2016

59 views

Category:

Documents


0 download

DESCRIPTION

THE "GUIDING SYSTEM". Sepam series 80: intelligent solutions for personalized applications. Sepam series 40: high-performing solutions for demanding applications. Sepam series 20: simple solutions for common applications. Sepam protection relays. - PowerPoint PPT Presentation

TRANSCRIPT

Page 1: THE "GUIDING SYSTEM"

Sepam Offer EN 2007_01.ppt1

THE "GUIDING SYSTEM"

Page 2: THE "GUIDING SYSTEM"

Sepam Offer EN 2007_01.ppt2

Sepam series 20:simple solutions for common applications

Sepam series 40:high-performing solutions for demanding applications

Sepam series 80:intelligent solutions for personalized applications

Sepam protection relays

A range of solutions for all applications

Sepam series 10:designed for building and Utilities

Page 3: THE "GUIDING SYSTEM"

Sepam Offer EN 2007_01.ppt3

Sepam Series 10 selection guide

Sepam series 10 N: earth fault protection

-Sepam series 10 B: 3 phases overcurrent and earth fault protection

- Sepam series 10 A: communication, logic input and signalling relays

Page 4: THE "GUIDING SYSTEM"

Sepam Offer EN 2007_01.ppt4

Sepam series 20 40 80 selection guide

3V + V0

3I + I0

42 I / 23 O2 com. portLogical equationsLOGIPAM

Series 80

10 I / 8 O1 com. port

Series 20

capacitorBus bargeneratortransformer motorSubstation

10 I / 8 O1 com. portLogical equations

Series 40

sensors

3 V + V0

Specificprotection

2x3I + 2xI03 V + V0

87 T

87 M

3I + 2xI02x3V + V0

3I + I0

67N

3I + I0 S 20 T 20 M 20

B 21

B 22

S 40 T 40 G 40S 41 M 41S 42 T 42

3I + 2xI0

3V + V0 67N

67et 67N

37P et 81R

S 80

S 81

S 82S 84

T 81 M 81

B 80

T 82 G 82

T 87

M 87

M 88 G 88

G 87

B 83

C 864unbalance I

81R

3V

S 23 T 2350BF

67et 67N

Page 5: THE "GUIDING SYSTEM"

? Situate SEPAM protection relays

Sepam Offer EN 2007_01.ppt5

Software

General introduction

Protection for each type of application

B

C

D

ToolsA

Tools

Get to know the Sepam range

Tools

Page 6: THE "GUIDING SYSTEM"

Sepam Offer EN 2007_01.ppt6

Data sheets

To be included with quotes

Description of the main characteristics:

– Selection table– Wiring diagrams– Modularity principle

Series 20Series 40Series 80

Project managers

Page 7: THE "GUIDING SYSTEM"

Sepam Offer EN 2007_01.ppt7

Commercial catalogue

Series 10Used to choose and order the right Sepam

Page 8: THE "GUIDING SYSTEM"

Sepam Offer EN 2007_01.ppt8

Commercial catalogue

1 Selection guide

2 & 3 for each series– General presentation and

selection table– Concise description of metering,

protection, control logic and communication functions.

– Wiring diagram and general characteristics

4 Add-on modules andaccessories

– Characteristics – Connection

5 Order forms

Used to choose and order the right Sepam

Series 20Series 40Series 80

Sales engineers

Page 9: THE "GUIDING SYSTEM"

Sepam Offer EN 2007_01.ppt9

User manuals

Series 10Provide the information required to use Sepam Series 20 and 40

Page 10: THE "GUIDING SYSTEM"

Sepam Offer EN 2007_01.ppt10

User manuals

Describe function characteristics in detail

– metering– protection– control and monitoring

Present Modbus communication tables

Present characteristics and wiring rules for Sepam and remote modules

Provide the information required to use Sepam Series 20 and 40

Series 20Series 40

Design offices and users

Page 11: THE "GUIDING SYSTEM"

Sepam Offer EN 2007_01.ppt11

User manuals

Manual 1

Describes characteristics and wiring rules for Sepam and remote modules

Manual 2

Describes function characteristics in detail– metering– protection– control and monitoring

Manual 3

Presents Modbus communication tables

Provide the information required to use Sepam Series 80

Series 80Design offices and users

Page 12: THE "GUIDING SYSTEM"

Sepam Offer EN 2007_01.ppt12

DNP3 communication

Presentation of the protocol

List of data

Configuration of interfaces

Provides the information required to implement the DNP3 protocol

Design offices and usersSeries 20Series 40Series 80

Page 13: THE "GUIDING SYSTEM"

Sepam Offer EN 2007_01.ppt13

IEC 60870-5-103 communication

Presentation of the protocol

List of data

Configuration of interfaces

Provides the information required to implement the IEC 60870-5-103 protocol

Design offices and usersSeries 20Series 40Series 80

Page 14: THE "GUIDING SYSTEM"

? Situate SEPAM protection relays

Sepam Offer EN 2007_01.ppt14

Software

General introduction

Protection for each type of application

B

C

D

ToolsA

General introduction

Get to know the Sepam range

General introduction

Page 15: THE "GUIDING SYSTEM"

Sepam Offer EN 2007_01.ppt15

Basic earth-fault relay and / or overcurrent

Series 10

Standard input (for conventional CTs)

Sensitive input (for conventional CTs)

Very sensitive (for G0110 CSH 120/200)

Different type of supply

Page 16: THE "GUIDING SYSTEM"

Sepam Offer EN 2007_01.ppt16

No modularity choose the right reference

model number

of CTs

input

earth fault sensitivity

24-125 VDC

100-120 VAC

110-250 VDC

100- 240 VAC

220-250 VDC

Sepam series 10 N 1Io standard REL 59817 REL 59819 -

very sensitive REL 59818 REL 59820 -

Sepam series 10 B 3 (2+1Io)

standard REL 59800 REL 59801 -

standard REL 59802 REL 59805 -

4 (3+1Io)

sensitive REL 59803 REL 59806 -

very sensitive REL 59804 REL 59807 -

Sepam series 10 A 4 (3+1Io)

standard REL 59808 REL 59811 REL 59814

sensitive REL 59809 REL 59812 REL 59815

very sensitive REL 59810 REL 59813 REL 59816

Series 10

Page 17: THE "GUIDING SYSTEM"

Sepam Offer EN 2007_01.ppt17

How to built the reference

Series 10

Page 18: THE "GUIDING SYSTEM"

Sepam Offer EN 2007_01.ppt18

Choose the base

SEPAM is provided with different types of base :Series 20Series 40

Series 80

Page 19: THE "GUIDING SYSTEM"

Sepam Offer EN 2007_01.ppt19

Ready to use configuration

Build your SEPAM configuration :

–Choose the base unit e.g. :

Then add–connectors :

–Application :

–Working language :

–Manuals :

Series 20Series 40Series 80

Page 20: THE "GUIDING SYSTEM"

Sepam Offer EN 2007_01.ppt20

Current sensor inputs

CCA630 connector

The CCA630 connector is used to connect 3 phase current transformers to Sepam

contain interposing ring CTs with through primaries

Can be disconnected with the power on since disconnection does not open the CT secondary circuit.

Series 20Series 40Series 80

Page 21: THE "GUIDING SYSTEM"

Sepam Offer EN 2007_01.ppt21

Current sensor inputs

CCA634 connector

The CCA634 adds an input for a residual current transformer :

do not connect a core balance ct

do not use base’s Io input

contain interposing ring CTs with through primaries

can be disconnected with the power on since disconnection does not open the CT secondary circuit.

Series 20Series 40Series 80

Page 22: THE "GUIDING SYSTEM"

Sepam Offer EN 2007_01.ppt22

Evolve with the installation

Upgrading of functions by optional modules– possible at any time– easy to connect– implementation by simple parameter setting

Series 20Series 40Series 80

Page 23: THE "GUIDING SYSTEM"

Sepam Offer EN 2007_01.ppt23

Increase input/output capacity

Addition of a module with – 10 logic inputs– 4 output relays

3 models of modules– MES 114

voltage on inputs– 24 to 250 V DC

– MES 114 Evoltage on inputs

– 110 to 250 V DC– 110 V AC

– MES 114 F voltage on inputs

– 220 to 250 V DC– 220 to 240 V AC

Series 20Series 40

Module MES 114

How to choice : - general case, without immunity constraint Vcc: MES114- auxiliary supply : 100 or 110V Vcc ou Vca MES114E- auxiliary supply >200V Vcc ou Vca MES114F

Page 24: THE "GUIDING SYSTEM"

Sepam Offer EN 2007_01.ppt24

Increase input/output capacity

Addition of modules with – 14 logic inputs– 6 output relays

3 models of modules– MES 120

voltage on inputs– 24 to 250 V DC

– MES 120 Gvoltage on inputs

– 220 to 250 V DC– MES 120 H

voltage on inputs– 110 to 250 V DC

3 modules maximum– Maximum configuration:

– 42 inputs (3 x 14)– 23 outputs (3 x 6 + 5)

Module MES 120Series 80

How to choice : - general case, without immunity constraint Vcc MES120- auxiliary supply 100 or 110V Vcc MES120H- auxiliary supply >200V Vcc MES120G

Page 25: THE "GUIDING SYSTEM"

Sepam Offer EN 2007_01.ppt25

Improve ergonomics and the installation

Remote advanced UMI module

Module flush-mounted "wherever you want"

May only be connected to a base unit without advanced UMI

Series 20Series 40Series 80

Page 26: THE "GUIDING SYSTEM"

Sepam Offer EN 2007_01.ppt26

Acquire temperature data

Remote MET148-2 module

Measurement of 8 temperatures

By Pt100, Ni100 or Ni120 RTD

To protect transformers, motors and generators

Number of modules per Sepam

– Series 20: 1– Series 40: 2– Series 80: 2

Series 20Series 40Series 80

Page 27: THE "GUIDING SYSTEM"

Sepam Offer EN 2007_01.ppt27

Remote measurement available

Remote MSA141 module

Choice of measurement via SFT2841

Transmission format– 0-10mA– 0-20mA– 4-20mA

1 module per Sepam

Series 20Series 40Series 80

Page 28: THE "GUIDING SYSTEM"

Sepam Offer EN 2007_01.ppt28

Enable the coupling of 2 networks

For substation, transformer, generator and busbar applications

Measurement of 2 phase-to-neutral or phase-to-phase voltages

Checking for voltage, frequency and phase differences between 2 different networks

Configuration via base unit

3 output relays to enable coupling used by Sepam to control the closing of breaking devices

Series 80 Remote MCS025 module

Page 29: THE "GUIDING SYSTEM"

Sepam Offer EN 2007_01.ppt29

Connect optional modules

Inter-module connection cables– CCA770, 0.6 m long– CCA772, 2 m long– CCA774, 4 m long

1 single chain of modules

Base unit Cable 1st module Cable 2nd module Cable 3rd mod.

Series 20 CCA772 MSA141 CCA770 MET148-2 CCA774 DSM303

Series 40 CCA772 MSA141 CA770 MET148-2 CCA774 DSM303

Series 40 CCA772 MSA141 CCA770 MET148-2 CCA772 MET148-2

Series 40 CCA772 MET148-2 CCA770 MET148-2 CCA774 DSM303

Series 20Series 40

Page 30: THE "GUIDING SYSTEM"

Sepam Offer EN 2007_01.ppt30

Connect optional modules

Inter-module connection cables– same as for Series 20 & 40– CCA785 must be used to connect the MCS025 module (cable supplied

with the module)

2 chains of modules

Base unit Cable 1st module Cable 2nd module Cable 3rd mod.

Chain 1 D1 CCA772 MET148-2 CCA770 MET148-2 CCA774 DSM303

Chain 2 D2 CCA772 MSA141 CCA785 MCS025

Series 80

Page 31: THE "GUIDING SYSTEM"

Sepam Offer EN 2007_01.ppt31

Communicate: no interface needed

Sepam series 10 can be daisy chained to a RTU (with Modbus or IEC 60870-5-103 protocols

Several functions available for easy remote operation

– control of the CB– dated events and trip currents– reading of the currents– reset of the protections

to scada system

Series 10

Page 32: THE "GUIDING SYSTEM"

Sepam Offer EN 2007_01.ppt32

Communicate: interfaces forconnection to one network

Modbus interfaces – ACE949-2:

2-wire RS 485– ACE959:

4-wire RS 485– ACE937: Fiber optic

Number of interfaces that can be connected:

– Series 20: 1– Series 40: 1– Series 80: 2

Series 20Series 40Series 80

Page 33: THE "GUIDING SYSTEM"

Sepam Offer EN 2007_01.ppt33

Communicate: interfaces forconnection to two networks

ACE969-TP

Number of interfaces– Series 20: 1

– Series 40: 1

– Series 80: 2

network linked to the supervisory system

network linked to a PC for Sepam parameter setting

ACE969-FO

S-LAN2-wire RS 485 Fiber optic

Interfaces:

E-LAN

MODBUS, DNP3, IEC 60870-5-103

2-wire RS 485 MODBUS

Series 20Series 40Series 80

Page 34: THE "GUIDING SYSTEM"

Sepam Offer EN 2007_01.ppt34

S-LAN E-LAN

S20 >V0526 S40 >V3.00 S80 : all versions

Series 20Series 40Series 80

Page 35: THE "GUIDING SYSTEM"

? Situate SEPAM protection relays

Sepam Offer EN 2007_01.ppt35

Software

General introduction

Protection for each type of application

B

C

D

ToolsA

Software

Get to know the Sepam range

Software

Page 36: THE "GUIDING SYSTEM"

Sepam Offer EN 2007_01.ppt36

Definition and quoting of Sepam

Selection guide

Selection of protection functions Selection of remote modules Basic configuration Creation of the quote

Series 20Series 40Series 80

Page 37: THE "GUIDING SYSTEM"

Sepam Offer EN 2007_01.ppt37

SFT2841

2 operating modes– not connected– connected to Sepam

Windows environment On-line help available Comes in 3 languages,

and may also be customized

For commissioning, the SFT2841 tool is

– useful for Series 20– recommended for Series

40– essential for Series 80

Sepam parameter settingSeries 20Series 40Series 80

Page 38: THE "GUIDING SYSTEM"

Sepam Offer EN 2007_01.ppt38

SFT2826

Selection of analog channels displayed

Selection of logic data displayed

2 cursors to measure differences

Possibility of zooming on a zone of the graph

Display of disturbance recording filesSeries 20Series 40Series 80

Page 39: THE "GUIDING SYSTEM"

Sepam Offer EN 2007_01.ppt39

SFTSAV

Display of current and cumulative faults

Display of passwords

This software is not diffused yet.

Provided by the help desk where necessary

Diagnosis of Sepam operating problemsSeries 20Series 40Series 80

Internal PMC use only

Page 40: THE "GUIDING SYSTEM"

Sepam Offer EN 2007_01.ppt40

SFT2840

Conversion of language files

Conversion of all text displayed on front panel

Creation of a language file

Series 20Series 40Series 80

Page 41: THE "GUIDING SYSTEM"

Sepam Offer EN 2007_01.ppt41

SFT2842

Adaptation of Sepam units in local adaptation centers

Loading of the application in Sepam

Loading of language files in Sepam

Series 20Series 40Series 80

For local adaptation center

Page 42: THE "GUIDING SYSTEM"

Sepam Offer EN 2007_01.ppt42

SFT2885

Creation of control logic schemes

Entry of the control logic scheme

Simulation of operation

Series 80

Page 43: THE "GUIDING SYSTEM"

Sepam Offer EN 2007_01.ppt43

SFT2887

Conversion of Sepam 2000 control logic into Sepam Series 80 control logic

Definition of I/O equivalence tables

Conversion of control logic

Generation of a report

Series 80

Page 44: THE "GUIDING SYSTEM"

Sepam Offer EN 2007_01.ppt44

No software

Series 10

Sepam series 10 is easy to configure:no need for a PC software

Page 45: THE "GUIDING SYSTEM"

? Situate SEPAM protection relays

Sepam Offer EN 2007_01.ppt45

Software

General introduction

Protection for each type of application

B

C

D

ToolsA

Protection for each type of application

Get to know the Sepam range

Protection for each type of application

Page 46: THE "GUIDING SYSTEM"

Sepam Offer EN 2007_01.ppt46

Incomer protection

Detection of short-circuits and overloads on busbars

Without voltage monitoring50/51 : maxi I 50N/51N : maxi I0

46 : unbalance

(50BF : breaker failure)

With voltage monitoring50/51 : maxi I 50N/51N : maxi I0

46 : unbalance

50BF : breaker failure

27 (+D+R) : Under voltage (–positive seq – remanent)

59 +N : Over voltage – neutral displacement

47 : negative sequence over voltage

81L+H : under – over frequency

thermal overload for cables49RMS with a single time constant

S81/82/84

Page 47: THE "GUIDING SYSTEM"

Sepam Offer EN 2007_01.ppt47

Incomer protection

Detection of short-circuits and overloads on busbars

Additional bus bar voltage monitoringA single L-L or L-N voltage on the second measuring point for

27+R / 59 / 81 L+H protections

Load-shedding by ROCOF (rate-of-change of frequency) function (81R)

– for faster action

Page 48: THE "GUIDING SYSTEM"

Sepam Offer EN 2007_01.ppt48

Parallel Incomer protection

Isolate the faulty section and resupply when required

Directional phase 67 and earth fault 67N/67NC

Directional discrimination

Underpower disconnection function 37P

– disconnection of the network if the power drawn by the load can be supplied by the generator

Automatic transfer (AT) Synchro-check 25

Page 49: THE "GUIDING SYSTEM"

Sepam Offer EN 2007_01.ppt49

Bus bar protection

Monitoring of voltages and frequency

Monitoring of bus bar voltages27 +D+R : Under voltage –positive seq - remanent59 +N : Over voltage – neutral displacement47 : negative sequence over voltage81L+H : under – over frequency

Load-shedding by ROCOF (rate-of-change of frequency) function (81R)

– for faster action

Page 50: THE "GUIDING SYSTEM"

Sepam Offer EN 2007_01.ppt50

Coupling circuit breaker protection

Detection of short-circuits on bus bars Monitoring of voltages and frequency

Monitoring of the voltages and frequency of two bus bars50/51 : maxi I 50N/51N : maxi I050BF : Breaker failure46 : unbalance27 +D+R : Under voltage –positive seq - remanent59 +N : Over voltage – neutral displacement47 : negative sequence over voltage81L+H : under – over frequency

Page 51: THE "GUIDING SYSTEM"

Sepam Offer EN 2007_01.ppt51

Feeder protection

Detection of short-circuits and overloads on the line

Highly capacitive feeder or isolated neutral directional earth fault 67N/67NC

With voltage monitoring50/51 : maxi I 50N/51N : maxi I050BF : Breaker failure27 (+D+R) : Under voltage ( –positive seq – remanent)59 +N : Over voltage – neutral displacement47 : negative sequence over voltage81L+H : under – over frequency

Without voltage monitoring50/51 : maxi I 50N/51N : maxi I0

(50BF : breaker failure)

79 : re-closer

Page 52: THE "GUIDING SYSTEM"

Sepam Offer EN 2007_01.ppt52

Transformer protection

Detection of short-circuits and overloadsDetection of internal faults, Thermostat or BuchholzTemperature monitoring by RTD

Without voltage monitoring50/51 : maxi I 50N/51N : maxi I0(50BF : Breaker failure)46 : unbalance49RMS : thermal overload 38/49T : temp monitoring26/63 : thermostat / bucholz ( DGPT2 – DMCR)

With voltage monitoring27 (+D+R) : Under voltage ( –positive seq – remanent)59 +N : Over voltage – neutral displacement47 : negative sequence over voltage81L+H : under – over frequency

Page 53: THE "GUIDING SYSTEM"

Sepam Offer EN 2007_01.ppt53

Transformer protection

Fast detection of short-circuits in the transformer

Transformer rating higher than 5MVA

Transformer differential 87T

Several possible combinations of earth fault protection functions

– restricted earth fault differential 64REF on the primary and/or secondary circuit

– sensitive earth fault 50G/51G on the primary and/or secondary circuit

Page 54: THE "GUIDING SYSTEM"

Sepam Offer EN 2007_01.ppt54

Transformer protection

Isolation of faulty section and different sources in parallel when applicable

Restricted earth fault differential 64REF

Synchro-check 25

Differentsources

Directional phase overcurrent 67 and earth fault 67N/67NC

Directional logic discrimination

Same source

Page 55: THE "GUIDING SYSTEM"

Sepam Offer EN 2007_01.ppt55

Motor protection

Detection of internal faultsDetection of power supply faultsDetection of load-related faultsTemperature monitoring by RTD

Without voltage monitoring50/51 : maxi I 50N/51N : maxi I0 37 : undercurrent46 : unbalance49RMS : thermal overload 38/49T : temp monitoring48 / 51LR / 14 : excessive starting time / locked rotor66 : starts per hour

With voltage monitoring32 P+Q : directional active/reactive power

(40 : field loss 78PS :pole slip)

(12/14 : over under speed)

Possibility of control logic scheme– starting by autotransformer– two operating directions

Page 56: THE "GUIDING SYSTEM"

Sepam Offer EN 2007_01.ppt56

Motor protection

Fast detection of short-circuits in the motor

Motor rating higher than 2MVA

Machine differential 87M

Page 57: THE "GUIDING SYSTEM"

Sepam Offer EN 2007_01.ppt57

Motor-transformer unit protection

Detection of internal faults in the motor and transformerDetection of power supply faultsDetection of load-related faultsTemperature monitoring by RTD

If the transformer is not monitored by the Sepam, a M41 may be suitable

Page 58: THE "GUIDING SYSTEM"

Sepam Offer EN 2007_01.ppt58

Motor-transformer unit protection

Fast detection of short-circuits in the transformer and motor

Motor rating higher than 2MVA

Transformer differential 87T

Page 59: THE "GUIDING SYSTEM"

Sepam Offer EN 2007_01.ppt59

Generator protection

Detection of internal faultsDetection of network faultsDetection of driving machine-related faultsTemperature monitoring by RTDMonitoring of voltages and frequency

Isolated generator

Coupled generator Detection of short-circuits on generator side by

directional protection 67 Restricted earth fault differential 64REF

Page 60: THE "GUIDING SYSTEM"

Sepam Offer EN 2007_01.ppt60

Generator protection

Fast detection of short-circuits in the generator

Machine differential 87M

Generator rating higher than 5MVA

Page 61: THE "GUIDING SYSTEM"

Sepam Offer EN 2007_01.ppt61

Generator-transformer unit protection

Detection of internal faults in the generator and transformerDetection of network faultsDetection of driving machine-related faultsTemperature monitoring by RTDMonitoring of voltages and frequency

If the generator is isolated, a G40 may be suitable

Page 62: THE "GUIDING SYSTEM"

Sepam Offer EN 2007_01.ppt62

Generator-transformer unit protection

Fast detection of short-circuits in the generator and transformer

Generator rating higher than 5MVA

Transformer differential 87T

Page 63: THE "GUIDING SYSTEM"

Sepam Offer EN 2007_01.ppt63

Capacitor bank (delta connection) protection

Detection of short-circuits in the capacitor bank

Without voltage monitoring

With voltage monitoring Detection of overloads by thermal overload

protection 49RMS (Sepam C86 only)

Page 64: THE "GUIDING SYSTEM"

Sepam Offer EN 2007_01.ppt64

Protection of capacitor banks with 1 to 4 steps (double star connection)Detection of short-circuits and overloads in the capacitor bankMonitoring of voltages and frequencyDetection of unbalance in each step

Detection of capacitor bank unbalance 51C

Detection of overloads by thermal overload protection 49RMS, with automatic adaptation of the number of steps in service

(steps must have the same size)