Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #50 Compressor Calorimeter Test of Refrigerant Blend DR-3 in a R-404A Reciprocating Compressor Jozef Sedliak Embraco Slovakia Odorinska cesta 2, 052 01 Spisska Nova Ves, Slovakia September 23, 2015 This report has been made available to the public as part of the author company’s participation in the AHRI’s Low-GWP AREP.

Upload: hoangdung

Post on 24-Apr-2018

222 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: TEST REPORT #50 Compressor Calorimeter Test of ... - Compressor shell TC "T", Agilent 34970A ± 0.5 C Temperature - Return gas TC "T", Agilent 34970A ± 0.5 C Table 2-2, List of instruments

Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP)

TEST REPORT #50 Compressor Calorimeter Test of Refrigerant Blend DR-3 in a R-404A Reciprocating Compressor Jozef Sedliak Embraco Slovakia Odorinska cesta 2, 052 01 Spisska Nova Ves, Slovakia September 23, 2015 This report has been made available to the public as part of the author company’s participation in the AHRI’s Low-GWP AREP.

 

Page 2: TEST REPORT #50 Compressor Calorimeter Test of ... - Compressor shell TC "T", Agilent 34970A ± 0.5 C Temperature - Return gas TC "T", Agilent 34970A ± 0.5 C Table 2-2, List of instruments

2

1. Introduction:

Scope of the work is evaluation of the compressor performance with new low GWP

refrigerant DR3 in compressor NEK2134GK primarily used for R404A refrigerant.

2. Details of Test Setup:

a. Description of Test Refrigerant-Lubricant and Charge

Refrigerant or refrigerant blend tested

o R404A by supplier LINDE

o New mixture refrigerant named DR3 delivered by DuPont

Lubricant

o Compressor lubricant is POE oil Emkarate RL 22HB by Lubrizol.

b. Description of Compressors and test conditions/methodology

The evaluation was done by testing of 2 compressors model NEK2134GK, 958AG71

made by Embraco, type hermetic reciprocating one piston compressor. Compressors are

primarily used for R404A refrigerant. First test was done with R404A for purpose of

reference values and then they were tested with new refrigerant DR3. Average from 2

compressors was considered in the final results.

Model NEK2134GK NEK2134GK

BOM 958AG71 958AG71

Application LBP-HST LBP-HST

S/N P12RLC52 P12RPA8D

Oil POE 22 POE 22

Motor CSIR, monophase CSIR, monophase

Power supply 115V/60Hz 115V/60Hz

Ambient temperature 35°C 35°C

Subcooling 0°C 0°C

Fan cooling 270 m3/h 270 m

3/h

Temperature determination Dewpoint Dewpoint

Table 2-1, Compressor configuration and test description

Thermodynamic properties of R404A determined from Refprop 6.0 (by NIST USA),

thermodynamic properties of DR3 determined from files received from DuPont.

Page 3: TEST REPORT #50 Compressor Calorimeter Test of ... - Compressor shell TC "T", Agilent 34970A ± 0.5 C Temperature - Return gas TC "T", Agilent 34970A ± 0.5 C Table 2-2, List of instruments

3

c. Test facilities

The performance tests were performed on a calorimeter using Calorimetric method A

Secondary fluid calorimeter on the suction side, see EN13771. Before the measurements

were done, the calorimeter was cleaned from potential residues of previous tests,

evacuated and subsequently charged with the correct refrigerant R404A and DR3.

Calorimeter charge with R404A: 0.7 kg

Calorimeter charge with DR3: 1.1 kg

Figure 2-1, Schematic diagram of the calorimeter

Page 4: TEST REPORT #50 Compressor Calorimeter Test of ... - Compressor shell TC "T", Agilent 34970A ± 0.5 C Temperature - Return gas TC "T", Agilent 34970A ± 0.5 C Table 2-2, List of instruments

4

Parameter Instrument Accuracy

Compressor power input Yokogawa WT230 ± (0.1% of reading + 0.1% of range),

Compressor voltage Yokogawa WT230 ± (0.1% of reading + 0.1% of range), 300 V

Compressor current Yokogawa WT230 ± (0.1% of reading + 0.1% of range), 10 A

Heat exchanger DC power input Yokogawa WT230 ± (0.3% of reading + 0.2% of range)

Heat exchanger DC voltage Yokogawa WT230 ± (0.2% of reading + 0.2% of range), 300 V

Heat exchanger DC current Yokogawa WT230 ± (0.2% of reading + 0.2% of range), 20 A

Suction pressure transducer BD sensor 10 bar ± 0.1% of range

Discharge pressure transducer BD sensor 40 bar ± 1% of range

Temperature - Heat exchanger input TC "T", Agilent 34970A ± 0.5°C

Temperature - Heat exchanger output TC "T", Agilent 34970A ± 0.5°C

Temperature - Heat exchanger internal TC "T", Agilent 34970A ± 0.3°C

Temperature - Calorimeter ambient TC "T", Agilent 34970A ± 0.5°C

Temperature - Compressor shell TC "T", Agilent 34970A ± 0.5°C

Temperature - Return gas TC "T", Agilent 34970A ± 0.5°C

Table 2-2, List of instruments with their accuracy

d. Coefficients equation format

Coefficients equation format:

X = C1 +C2 • (S) + C3 • D +C4 • (S2) + C5 • (S•D) + C6 • (D

2) + C7 • (S

3) + C8 • (D•S

2) +C9 •

(S•D2) + C10 • (D

3)

where:

C = Equation coefficient, represents compressor performance

S = Suction dew point temperature, °F [°C]

D = Discharge dew point temperature, °F [°C]

X = compressor performance (mass flow rate, capacity, power and COP)

e. Uncertainties

Uncertainty for cooling capacity: ± 47.29 BTU/h (valid for all points)

Power input uncertainty: ± 3.46 W (valid for all points)

Page 5: TEST REPORT #50 Compressor Calorimeter Test of ... - Compressor shell TC "T", Agilent 34970A ± 0.5 C Temperature - Return gas TC "T", Agilent 34970A ± 0.5 C Table 2-2, List of instruments

5

3. Results

All compressor tests are performed at a refrigerant’s dew point temperature for suction and

discharge pressure conditions, per AHRI Standard 540 requirements. This does not have an

impact on comparing compressor performance between two or more refrigerants that do not

exhibit temperature glide. However, when refrigerants exhibit temperature glide, it is important

to note that actual systems operate closer to the mid-point condition. When comparing

compressor performance of one refrigerant with glide to another refrigerant without glide, or

comparing two refrigerants with significantly different glides, comparison at pressures

corresponding to the mid-point of the temperature glide rather than the dew point will yield

results that are more representative of actual operation in a system.

R404A is near azeotropic blend with small temperature glide less than 1K and from practical

purposes can be neglected.

DR3 is a zeotropic blend with temperature glides between 12°F and 6°F over operating

application range.

3.1. Return gas temperature 18.3 °C

3.1.1. Reference measurement with R404A (dew point based)

AVERAGE T cond T evap T return gas T Superheat Cool. Capacity Power input Current EER Mass flow

REFRIGERANT (°C) (°C) (°C) (°C) BTU/h W A (BTU/Wh) kg/h

R404A 30 -12 18.3 30.3 3399.9 458.4 5.80 7.42 25.01

R404A 30 -20 18.3 38.3 2399.7 398.1 5.39 6.03 17.40

R404A 30 -30 18.3 48.3 1477.2 324.4 4.97 4.56 10.59

R404A 30 -40 18.3 58.3 897.4 263.0 4.71 3.41 6.39

R404A 45 -12 18.3 30.3 2635.8 521.8 6.22 5.05 23.39

R404A 45 -20 18.3 38.3 1864.1 443.9 5.68 4.20 16.33

R404A 45 -30 18.3 48.3 1177.3 349.5 5.11 3.37 10.15

R404A 45 -40 18.3 58.3 653.6 261.9 4.67 2.50 5.58

R404A 60 -12 18.3 30.3 1841.5 587.0 6.69 3.14 21.49

R404A 60 -20 18.3 38.3 1301.3 483.6 5.93 2.69 14.88

R404A 60 -30 18.3 48.3 782.9 360.5 5.15 2.17 8.79

R404A 60 -40 18.3 58.3 396.5 247.4 4.62 1.60 4.41

Table 3-1a., Measured data of NEK2134GK, refrigerant R404A,

return gas temperature 18.3 °C (dew point based)

Page 6: TEST REPORT #50 Compressor Calorimeter Test of ... - Compressor shell TC "T", Agilent 34970A ± 0.5 C Temperature - Return gas TC "T", Agilent 34970A ± 0.5 C Table 2-2, List of instruments

6

AVERAGE T cond T evap T return

gas T Superheat Cool. Capacity Power input Current EER Mass flow

REFRIGERANT (°C) (°C) (°C) (°C) % % % % %

R404A 30 -12 18.3 30.3 2.6 0.6 0.9 1.9 2.8

R404A 30 -20 18.3 38.3 2.0 0.6 1.1 1.4 2.1

R404A 30 -30 18.3 48.3 2.2 1.7 1.4 3.8 2.1

R404A 30 -40 18.3 58.3 1.4 2.9 1.3 1.5 1.8

R404A 45 -12 18.3 30.3 1.6 1.7 1.3 0.0 1.4

R404A 45 -20 18.3 38.3 1.2 1.4 1.2 0.2 1.2

R404A 45 -30 18.3 48.3 0.5 3.0 2.0 3.4 0.2

R404A 45 -40 18.3 58.3 2.1 2.7 1.5 0.6 2.0

R404A 60 -12 18.3 30.3 2.2 3.0 2.1 0.7 2.3

R404A 60 -20 18.3 38.3 2.4 2.8 2.0 0.3 2.1

R404A 60 -30 18.3 48.3 4.0 3.6 2.4 0.4 4.1

R404A 60 -40 18.3 58.3 4.2 3.6 2.0 0.6 3.9

Table 3-1b., Difference (abs %) between 2 measured pieces of NEK2134GK, refrigerant R404A,

return gas temperature 18.3 °C (dew point based)

Coefficients Capacity (BTU/h, °C) Mass flow (kg/h, °C) Power input (W, °C)

C1 8.633E+03 5.039E+01 3.710E+02

C2 2.922E+02 1.919E+00 3.588E+00

C3 -1.360E+02 -4.483E-01 5.509E+00

C4 3.689E+00 2.900E-02 -6.073E-02

C5 -3.030E+00 -9.549E-03 6.228E-02

C6 1.310E+00 6.495E-03 6.398E-03

C7 1.238E-02 1.532E-04 -1.175E-03

C8 -3.356E-02 -1.197E-04 1.103E-04

C9 2.412E-04 1.556E-05 1.282E-03

C10 -1.034E-02 -5.299E-05 5.070E-05

Table 3-2., Coefficients C1 – C10 for NEK2134GK, refrigerant R404A,

return gas temperature 18.3 °C (dew point based)

Page 7: TEST REPORT #50 Compressor Calorimeter Test of ... - Compressor shell TC "T", Agilent 34970A ± 0.5 C Temperature - Return gas TC "T", Agilent 34970A ± 0.5 C Table 2-2, List of instruments

7

CURVE-FITTED CHARTS

Figure 3-1, Cooling capacity of NEK2134GK, refrigerant R404A,

return gas temperature 18.3 °C, (dew point based)

Figure 3-2, Mass flow of NEK2134GK, refrigerant R404A,

return gas temperature 18.3 °C, (dew point based)

0

250

500

750

1000

1250

1500

1750

2000

2250

2500

2750

3000

3250

3500

3750

4000

-45 -40 -35 -30 -25 -20 -15 -10 -5

Cap

acit

y (B

TU

/h)

Evaporating Temp (°C)

COMPRESSOR CHART - CAPACITY (BTU/h); R404A, return 18.3 °C

60

55

50

45

40

35

30

0.0

5.0

10.0

15.0

20.0

25.0

30.0

-45 -40 -35 -30 -25 -20 -15 -10 -5

Mass flo

w (kg

/h)

Evaporating Temp (°C)

COMPRESSOR CHART - MASS FLOW (kg/h); R404A, return 18.3 °C

60

55

50

45

40

35

30

Page 8: TEST REPORT #50 Compressor Calorimeter Test of ... - Compressor shell TC "T", Agilent 34970A ± 0.5 C Temperature - Return gas TC "T", Agilent 34970A ± 0.5 C Table 2-2, List of instruments

8

Figure 3-3, Power input of NEK2134GK, refrigerant R404A,

return gas temperature 18.3 °C, (dew point based)

Figure 3-4, EER of NEK2134GK, refrigerant R404A,

return gas temperature 18.3 °C, (dew point based)

200

250

300

350

400

450

500

550

600

650

-45 -40 -35 -30 -25 -20 -15 -10 -5

Po

wer in

pu

t (W

)

Evaporating Temp (°C)

COMPRESSOR CHART - POWER INPUT(W); R404A, return 18.3 °C

60

55

50

45

40

35

30

1.00

2.00

3.00

4.00

5.00

6.00

7.00

8.00

-45 -40 -35 -30 -25 -20 -15 -10 -5

EE

R (B

TU

/Wh

)

Evaporating Temp (°C)

COMPRESSOR CHART - EER(BTU/Wh); R404A, return 18.3 °C

60

55

50

45

40

35

30

Page 9: TEST REPORT #50 Compressor Calorimeter Test of ... - Compressor shell TC "T", Agilent 34970A ± 0.5 C Temperature - Return gas TC "T", Agilent 34970A ± 0.5 C Table 2-2, List of instruments

9

3.1.2. Measurement with new refrigerant DR3

AVERAGE T cond T evap T return gas T Superheat Cool. Capacity Power input Current EER Mass flow

REFRIGERANT (°C) (°C) (°C) (°C) BTU/h W A (BTU/Wh) kg/h

DR3 30 -12 18.3 30.3 2701.6 374.5 5.52 7.22 16.39

DR3 30 -20 18.3 38.3 1909.9 319.3 5.22 5.98 11.47

DR3 30 -30 18.3 48.3 1123.9 262.9 5.01 4.28 6.71

DR3 30 -40 18.3 58.3 611.1 213.9 4.85 2.86 3.62

DR3 45 -12 18.3 30.3 2210.3 413.6 5.71 5.34 15.60

DR3 45 -20 18.3 38.3 1530.3 354.2 5.38 4.32 10.70

DR3 45 -30 18.3 48.3 921.6 283.3 5.05 3.25 6.39

DR3 45 -40 18.3 58.3 485.6 214.2 4.78 2.27 3.34

DR3 60 -12 18.3 30.3 1655.0 456.6 5.97 3.62 14.31

DR3 60 -20 18.3 38.3 1127.7 378.3 5.49 2.98 9.64

DR3 60 -30 18.3 48.3 633.1 282.9 5.04 2.24 5.35

DR3 60 -40 18.3 58.3 286.8 197.3 4.78 1.45 2.41

Table 3-3a., Measured data of NEK2134GK, refrigerant DR3,

return gas temperature 18.3 °C, (dew point based)

AVERAGE T cond T evap T return gas T Superheat Cool. Capacity Power input Current EER Mass flow

REFRIGERANT (°C) (°C) (°C) (°C) % % % % %

DR3 30 -12 18.3 30.3 2.8% 4.0% 2.2% 4.0% 2.6%

DR3 30 -20 18.3 38.3 1.3% 0.8% 0.8% 2.1% 1.4%

DR3 30 -30 18.3 48.3 0.2% 1.6% 1.4% 1.5% 0.4%

DR3 30 -40 18.3 58.3 1.4% 1.7% 1.4% 0.3% 2.3%

DR3 45 -12 18.3 30.3 2.3% 0.0% 0.4% 2.4% 2.1%

DR3 45 -20 18.3 38.3 1.7% 0.6% 0.7% 1.1% 1.7%

DR3 45 -30 18.3 48.3 1.8% 0.7% 1.2% 1.1% 2.1%

DR3 45 -40 18.3 58.3 0.6% 0.3% 0.0% 0.2% 0.6%

DR3 60 -12 18.3 30.3 0.1% 0.0% 0.3% 0.1% 0.3%

DR3 60 -20 18.3 38.3 1.3% 0.8% 0.4% 0.5% 1.3%

DR3 60 -30 18.3 48.3 0.2% 0.4% 0.4% 0.5% 0.0%

DR3 60 -40 18.3 58.3 3.5% 0.9% 0.8% 2.6% 3.4%

Table 3-3b., Difference (abs %) between 2 measured pieces of NEK2134GK,

refrigerant DR3, return gas temperature 18.3 °C, (dew point based)

Page 10: TEST REPORT #50 Compressor Calorimeter Test of ... - Compressor shell TC "T", Agilent 34970A ± 0.5 C Temperature - Return gas TC "T", Agilent 34970A ± 0.5 C Table 2-2, List of instruments

10

Coefficients Capacity (BTU/h) Mass flow (kg) Power input (W)

C1 6.125E+03 3.167E+01 4.049E+02

C2 2.037E+02 1.088E+00 8.393E+00

C3 -7.507E+01 -2.889E-01 3.381E-01

C4 2.108E+00 1.329E-02 6.552E-02

C5 -1.852E+00 -3.948E-03 -6.288E-02

C6 6.024E-01 5.249E-03 6.304E-02

C7 4.947E-03 5.958E-05 8.550E-05

C8 -1.495E-02 -1.770E-05 -5.808E-04

C9 2.279E-03 2.150E-05 1.686E-03

C10 -5.046E-03 -4.371E-05 -3.333E-04

Table 3-4, Coefficients C1 – C10 for NEK2134GK, refrigerant DR3,

return gas temperature 18.3 °C, (dew point based)

CURVE-FITTED CHARTS

Figure 3-5, Cooling capacity of NEK2134GK, refrigerant DR3,

return gas temperature 18.3 °C, (dew point based)

0

250

500

750

1000

1250

1500

1750

2000

2250

2500

2750

3000

3250

-45 -40 -35 -30 -25 -20 -15 -10 -5

Cap

acit

y (B

TU

/h)

Evaporating Temp (°C)

COMPRESSOR CHART - CAPACITY (BTU/h); DR3, return 18.3 °C

60

55

50

45

40

35

30

T cond (°C)

Page 11: TEST REPORT #50 Compressor Calorimeter Test of ... - Compressor shell TC "T", Agilent 34970A ± 0.5 C Temperature - Return gas TC "T", Agilent 34970A ± 0.5 C Table 2-2, List of instruments

11

Figure 3-6, Mass flow of NEK2134GK, refrigerant DR3,

return gas temperature 18.3 °C, (dew point based)

Figure 3-7, Power input of NEK2134GK, refrigerant DR3,

return gas temperature 18.3 °C, (dew point based)

0.0

2.0

4.0

6.0

8.0

10.0

12.0

14.0

16.0

18.0

20.0

-45 -40 -35 -30 -25 -20 -15 -10 -5

Mass flo

w (kg

/h)

Evaporating Temp (°C)

COMPRESSOR CHART - MASS FLOW (kg/h); DR3, return 18.3 °C

60

55

50

45

40

35

30

T cond (°C)

150

200

250

300

350

400

450

500

550

-45 -40 -35 -30 -25 -20 -15 -10 -5

Po

wer in

pu

t (W

)

Evaporating Temp (°C)

COMPRESSOR CHART - POWER INPUT(W); DR3; return 18.3 °C

60

55

50

45

40

35

30

T cond (°C)

Page 12: TEST REPORT #50 Compressor Calorimeter Test of ... - Compressor shell TC "T", Agilent 34970A ± 0.5 C Temperature - Return gas TC "T", Agilent 34970A ± 0.5 C Table 2-2, List of instruments

12

Figure 3-8, EER of NEK2134GK, refrigerant DR3,

return gas temperature 18.3 °C, (dew point based)

1.00

2.00

3.00

4.00

5.00

6.00

7.00

8.00

-45 -40 -35 -30 -25 -20 -15 -10 -5

EE

R (B

TU

/Wh

)

Evaporating Temp (°C)

COMPRESSOR CHART - EER(BTU/Wh); DR3, return 18.3 °C

60

55

50

45

40

35

30

T cond (°C)

Page 13: TEST REPORT #50 Compressor Calorimeter Test of ... - Compressor shell TC "T", Agilent 34970A ± 0.5 C Temperature - Return gas TC "T", Agilent 34970A ± 0.5 C Table 2-2, List of instruments

13

3.1.3. Comparison of the results

Capacity (BTU/h) DR3 Mass Flow (kg/h) DR3

°C 60 55 50 45 40 35 30 °C 60 55 50 45 40 35 30

-40 288 369 434 487 531 570 609 -40 2.41 2.86 3.16 3.35 3.47 3.54 3.60

-37 377 464 536 596 648 695 742 -37 3.17 3.61 3.92 4.12 4.25 4.34 4.42

-34 477 573 653 722 782 839 895 -34 4.03 4.47 4.79 5.00 5.14 5.24 5.34

-31 591 695 785 864 935 1002 1070 -31 4.99 5.44 5.77 5.99 6.14 6.27 6.39

-28 717 833 934 1023 1106 1185 1265 -28 6.08 6.54 6.87 7.10 7.28 7.42 7.56

-25 859 986 1099 1202 1297 1390 1483 -25 7.30 7.76 8.11 8.35 8.54 8.71 8.88

-22 1015 1156 1282 1399 1509 1616 1725 -22 8.65 9.13 9.48 9.75 9.96 10.14 10.34

-19 1187 1343 1484 1616 1742 1865 1990 -19 10.16 10.65 11.02 11.30 11.53 11.74 11.96

-16 1376 1547 1705 1854 1997 2137 2280 -16 11.83 12.33 12.71 13.01 13.27 13.50 13.75

-13 1583 1771 1947 2113 2275 2434 2596 -13 13.66 14.18 14.58 14.90 15.18 15.44 15.72

-10 1807 2015 2209 2395 2576 2756 2938 -10 15.67 16.20 16.63 16.97 17.27 17.56 17.88

Capacity (BTU/h) R404A Mass Flow (kg/h) R404A

°C 60 55 50 45 40 35 30 °C 60 55 50 45 40 35 30

-40 393 501 588 664 734 808 892 -40 4.46 5.00 5.40 5.69 5.92 6.13 6.35

-37 505 619 713 795 871 951 1042 -37 5.67 6.19 6.57 6.84 7.06 7.25 7.46

-34 622 746 849 940 1026 1115 1215 -34 6.96 7.47 7.84 8.11 8.33 8.52 8.73

-31 747 883 998 1102 1200 1302 1415 -31 8.37 8.88 9.25 9.53 9.75 9.95 10.17

-28 881 1032 1163 1282 1396 1513 1641 -28 9.92 10.44 10.82 11.11 11.35 11.57 11.81

-25 1027 1196 1346 1483 1615 1751 1898 -25 11.62 12.16 12.57 12.89 13.15 13.40 13.68

-22 1186 1377 1548 1706 1860 2017 2186 -22 13.51 14.09 14.53 14.88 15.19 15.48 15.80

-19 1360 1576 1771 1954 2133 2314 2507 -19 15.62 16.23 16.72 17.12 17.47 17.82 18.19

-16 1552 1795 2018 2228 2435 2644 2864 -16 17.95 18.62 19.17 19.63 20.04 20.45 20.89

-13 1764 2037 2290 2531 2768 3008 3259 -13 20.55 21.29 21.90 22.42 22.91 23.39 23.91

-10 1997 2303 2590 2865 3135 3408 3693 -10 23.44 24.25 24.93 25.54 26.11 26.67 27.28

Capacity: (DR3 - R404A)/R404A (%) Mass flow: (DR3 - R404A)/R404A (%)

°C 60 55 50 45 40 35 30 °C 60 55 50 45 40 35 30

-40 -26.7 -26.3 -26.3 -26.7 -27.7 -29.4 -31.7 -40 -45.8 -42.9 -41.5 -41.1 -41.5 -42.2 -43.2

-37 -25.4 -25.0 -24.8 -25.0 -25.6 -26.9 -28.8 -37 -44.1 -41.6 -40.3 -39.8 -39.8 -40.2 -40.8

-34 -23.3 -23.2 -23.1 -23.2 -23.8 -24.8 -26.3 -34 -42.2 -40.1 -39.0 -38.4 -38.3 -38.5 -38.8

-31 -20.9 -21.2 -21.4 -21.6 -22.1 -23.0 -24.4 -31 -40.4 -38.7 -37.7 -37.2 -37.0 -37.0 -37.2

-28 -18.6 -19.3 -19.7 -20.2 -20.8 -21.7 -22.9 -28 -38.7 -37.3 -36.5 -36.1 -35.9 -35.9 -36.0

-25 -16.4 -17.6 -18.3 -19.0 -19.7 -20.6 -21.8 -25 -37.2 -36.2 -35.5 -35.2 -35.0 -35.0 -35.1

-22 -14.4 -16.1 -17.1 -18.0 -18.9 -19.9 -21.1 -22 -36.0 -35.2 -34.7 -34.5 -34.4 -34.5 -34.6

-19 -12.7 -14.8 -16.2 -17.3 -18.3 -19.4 -20.6 -19 -34.9 -34.4 -34.1 -34.0 -34.0 -34.1 -34.3

-16 -11.3 -13.8 -15.5 -16.8 -18.0 -19.2 -20.4 -16 -34.1 -33.8 -33.7 -33.7 -33.8 -34.0 -34.2

-13 -10.3 -13.0 -15.0 -16.5 -17.8 -19.1 -20.4 -13 -33.5 -33.4 -33.4 -33.6 -33.8 -34.0 -34.2

-10 -9.5 -12.5 -14.7 -16.4 -17.8 -19.2 -20.5 -10 -33.1 -33.2 -33.3 -33.6 -33.8 -34.2 -34.5

Page 14: TEST REPORT #50 Compressor Calorimeter Test of ... - Compressor shell TC "T", Agilent 34970A ± 0.5 C Temperature - Return gas TC "T", Agilent 34970A ± 0.5 C Table 2-2, List of instruments

14

Table 3-5, Comparison of the results, return gas temperature 18.3 °C, (dew point based)

Power Input (W) DR3 EER (BTU/Wh) DR3

°C 60 55 50 45 40 35 30 °C 60 55 50 45 40 35 30

-40 196 206 212 216 217 216 213 -40 1.47 1.79 2.05 2.25 2.44 2.64 2.85

-37 222 229 233 235 234 232 227 -37 1.69 2.03 2.30 2.54 2.77 3.00 3.26

-34 249 253 255 254 252 248 242 -34 1.92 2.26 2.56 2.84 3.10 3.39 3.70

-31 276 277 277 274 270 265 258 -31 2.14 2.51 2.84 3.15 3.46 3.79 4.15

-28 303 302 300 295 289 282 274 -28 2.37 2.76 3.12 3.47 3.83 4.20 4.62

-25 331 328 323 316 309 300 291 -25 2.60 3.01 3.41 3.80 4.20 4.63 5.10

-22 359 353 346 338 329 319 309 -22 2.83 3.27 3.70 4.14 4.59 5.07 5.59

-19 388 380 371 360 350 339 327 -19 3.06 3.54 4.01 4.48 4.98 5.51 6.08

-16 417 406 395 384 371 359 346 -16 3.30 3.81 4.31 4.83 5.38 5.96 6.58

-13 446 434 421 407 393 380 366 -13 3.55 4.08 4.63 5.19 5.78 6.41 7.08

-10 476 462 447 432 416 402 387 -10 3.79 4.36 4.95 5.55 6.19 6.86 7.58

Power Input (W) R404A EER (BTU/Wh) R404A

°C 60 55 50 45 40 35 30 °C 60 55 50 45 40 35 30

-40 247 254 259 263 265 265 262 -40 1.59 1.97 2.27 2.52 2.77 3.05 3.40

-37 279 284 286 287 286 284 280 -37 1.81 2.18 2.49 2.77 3.04 3.35 3.72

-34 313 315 314 313 310 305 298 -34 1.99 2.37 2.70 3.01 3.32 3.66 4.07

-31 348 347 344 339 334 327 318 -31 2.14 2.55 2.91 3.25 3.60 3.99 4.44

-28 385 380 374 367 359 350 339 -28 2.29 2.72 3.11 3.49 3.89 4.33 4.84

-25 422 414 405 395 385 373 361 -25 2.43 2.89 3.32 3.75 4.20 4.69 5.26

-22 459 448 437 424 411 397 383 -22 2.58 3.07 3.54 4.02 4.52 5.08 5.71

-19 497 483 469 454 438 422 405 -19 2.74 3.26 3.78 4.31 4.87 5.49 6.19

-16 535 518 501 483 465 447 428 -16 2.90 3.46 4.03 4.61 5.23 5.92 6.70

-13 574 554 533 513 492 471 450 -13 3.07 3.68 4.29 4.94 5.62 6.38 7.24

-10 612 589 565 542 519 496 473 -10 3.26 3.91 4.58 5.28 6.04 6.87 7.81

Power input: (DR3 - R404A)/R404A (%) EER: (DR3 - R404A)/R404A (%)

°C 60 55 50 45 40 35 30 °C 60 55 50 45 40 35 30

-40 -20.4 -19.0 -18.2 -17.9 -18.0 -18.3 -18.7 -40 -7.8 -9.0 -9.8 -10.7 -11.8 -13.6 -16.0

-37 -20.4 -19.2 -18.5 -18.2 -18.2 -18.4 -18.7 -37 -6.2 -7.2 -7.7 -8.3 -9.1 -10.4 -12.4

-34 -20.6 -19.5 -18.9 -18.7 -18.6 -18.7 -18.8 -34 -3.4 -4.5 -5.1 -5.6 -6.3 -7.5 -9.2

-31 -20.9 -20.0 -19.4 -19.1 -19.0 -19.0 -19.0 -31 0.0 -1.5 -2.4 -3.1 -3.8 -5.0 -6.6

-28 -21.2 -20.4 -19.9 -19.6 -19.4 -19.3 -19.2 -28 3.4 1.4 0.2 -0.7 -1.7 -2.9 -4.6

-25 -21.5 -20.8 -20.3 -20.0 -19.8 -19.6 -19.3 -25 6.6 4.1 2.5 1.3 0.1 -1.3 -3.1

-22 -21.8 -21.2 -20.7 -20.3 -20.0 -19.7 -19.3 -22 9.5 6.5 4.5 2.9 1.4 -0.2 -2.2

-19 -22.1 -21.4 -20.9 -20.5 -20.2 -19.8 -19.3 -19 12.0 8.4 6.0 4.1 2.3 0.4 -1.7

-16 -22.2 -21.6 -21.1 -20.6 -20.2 -19.7 -19.0 -16 13.9 9.9 7.1 4.8 2.8 0.6 -1.7

-13 -22.2 -21.6 -21.1 -20.6 -20.1 -19.4 -18.6 -13 15.4 11.0 7.7 5.1 2.8 0.4 -2.1

-10 -22.2 -21.6 -21.0 -20.4 -19.8 -19.0 -18.1 -10 16.3 11.5 8.0 5.1 2.4 -0.2 -2.9

Page 15: TEST REPORT #50 Compressor Calorimeter Test of ... - Compressor shell TC "T", Agilent 34970A ± 0.5 C Temperature - Return gas TC "T", Agilent 34970A ± 0.5 C Table 2-2, List of instruments

15

3.2. Superheating 11.1 °C

3.2.1. Reference measurement with R404A (dew point based)

AVERAGE T cond T evap T return gas T Superheat Cool. Capacity Power input Current EER Mass flow

REFRIGERANT (°C) (°C) (°C) (°C) BTU/h W A (BTU/Wh) kg/h

R404A 30 -12 -0.9 11.1 3112.8 464.0 5.84 6.71 26.02

R404A 30 -20 -8.9 11.1 2094.8 406.5 5.45 5.15 18.26

R404A 30 -30 -18.9 11.1 1238.6 330.5 5.01 3.75 11.32

R404A 30 -40 -28.9 11.1 690.1 264.2 4.69 2.61 6.69

R404A 45 -12 -0.9 11.1 2335.4 525.8 6.27 4.44 24.29

R404A 45 -20 -8.9 11.1 1552.6 447.3 5.71 3.47 16.96

R404A 45 -30 -18.9 11.1 894.8 351.9 5.12 2.54 10.45

R404A 45 -40 -28.9 11.1 462.0 264.8 4.69 1.75 5.82

R404A 60 -12 -0.9 11.1 1526.7 583.5 6.68 2.62 22.13

R404A 60 -20 -8.9 11.1 992.6 481.1 5.93 2.06 15.39

R404A 60 -30 -18.9 11.1 528.5 364.9 5.20 1.45 9.03

R404A 60 -40 -28.9 11.1 238.2 252.5 4.67 0.94 4.54

Table 3-6a, Measured data of NEK2134GK, refrigerant R404A,

superheating 11.1°C, (dew point based)

AVERAGE T cond T evap T return gas T Superheat Cool. Capacity Power input Current EER Mass flow

REFRIGERANT (°C) (°C) (°C) (°C) % % % % %

R404A 30 -12 -0.9 11.1 2.6 1.0 1.0 1.6 2.7

R404A 30 -20 -8.9 11.1 1.6 0.0 0.7 1.5 1.3

R404A 30 -30 -18.9 11.1 1.8 2.6 1.6 0.7 1.8

R404A 30 -40 -28.9 11.1 0.0 3.3 1.9 3.2 0.1

R404A 45 -12 -0.9 11.1 2.2 1.6 1.4 0.6 2.4

R404A 45 -20 -8.9 11.1 1.2 1.6 1.4 0.4 1.4

R404A 45 -30 -18.9 11.1 0.9 2.1 1.6 2.9 1.0

R404A 45 -40 -28.9 11.1 0.0 2.6 1.3 2.5 0.9

R404A 60 -12 -0.9 11.1 3.2 2.3 2.0 2.6 3.1

R404A 60 -20 -8.9 11.1 3.5 3.1 2.0 0.4 3.3

R404A 60 -30 -18.9 11.1 1.4 3.4 2.3 1.9 1.7

R404A 60 -40 -28.9 11.1 2.7 4.3 4.2 1.6 2.6

Table 3-6b, Difference (abs %) between 2 measured pieces of NEK2134GK, refrigerant R404A,

superheating 11.1 °C, (dew point based)

Page 16: TEST REPORT #50 Compressor Calorimeter Test of ... - Compressor shell TC "T", Agilent 34970A ± 0.5 C Temperature - Return gas TC "T", Agilent 34970A ± 0.5 C Table 2-2, List of instruments

16

Coefficients Capacity (BTU/h, °C) Mass flow (kg/h, °C) Power input (W, °C)

C1 8.298E+03 4.921E+01 3.491E+02

C2 3.025E+02 1.761E+00 2.883E+00

C3 -1.241E+02 -3.407E-01 7.655E+00

C4 4.329E+00 2.364E-02 -2.829E-02

C5 -2.670E+00 -6.993E-03 1.374E-01

C6 1.054E+00 4.286E-03 -3.252E-02

C7 2.020E-02 9.636E-05 -2.655E-04

C8 -2.970E-02 -9.929E-05 8.385E-04

C9 -2.365E-03 -1.872E-06 6.640E-04

C10 -8.525E-03 -3.910E-05 2.346E-04

Table 3-7, Coefficients C1 – C10 for NEK2134GK, refrigerant R404A,

superheating 11.1°C, (dew point based)

CURVE-FITTED CHARTS

Figure 3-9, Cooling capacity of NEK2134GK, refrigerant R404A,

superheating 11.1 °C, (dew point based)

0

250

500

750

1000

1250

1500

1750

2000

2250

2500

2750

3000

3250

3500

3750

-45 -40 -35 -30 -25 -20 -15 -10 -5

Cap

acit

y (B

TU

/h)

Evaporating Temp (°C)

COMPRESSOR CHART - CAPACITY (BTU/h); R404A, SH 11.1 °C

60

55

50

45

40

35

30

Page 17: TEST REPORT #50 Compressor Calorimeter Test of ... - Compressor shell TC "T", Agilent 34970A ± 0.5 C Temperature - Return gas TC "T", Agilent 34970A ± 0.5 C Table 2-2, List of instruments

17

Figure 3-10, Mass flow of NEK2134GK, refrigerant R404A,

superheating 11.1 °C, (dew point based)

Figure 3-11, Power input of NEK2134GK, refrigerant R404A,

superheating 11.1 °C, (dew point based)

0.0

5.0

10.0

15.0

20.0

25.0

30.0

-45 -40 -35 -30 -25 -20 -15 -10 -5

Mass flo

w (kg

/h)

Evaporating Temp (°C)

COMPRESSOR CHART - MASS FLOW (kg/h); R404A, SH 11.1 °C

60

55

50

45

40

35

30

200

250

300

350

400

450

500

550

600

650

-45 -40 -35 -30 -25 -20 -15 -10 -5

Po

wer in

pu

t (W

)

Evaporating Temp (°C)

COMPRESSOR CHART - POWER INPUT(W); R404A, SH 11.1 °C

60

55

50

45

40

35

30

Page 18: TEST REPORT #50 Compressor Calorimeter Test of ... - Compressor shell TC "T", Agilent 34970A ± 0.5 C Temperature - Return gas TC "T", Agilent 34970A ± 0.5 C Table 2-2, List of instruments

18

Figure 3-12, EER of NEK2134GK, refrigerant R404A,

superheating 11.1 °C, (dew point based)

3.2.2. Measurement with new refrigerant DR3 (dew point based)

AVERAGE T cond T evap T return gas T Superheat Cool. Capacity Power input Current EER Mass flow

REFRIGERANT (°C) (°C) (°C) (°C) BTU/h W A (BTU/Wh) kg/h

DR3 30 -12 -0.9 11.1 2534.3 376.0 5.55 6.74 17.13

DR3 30 -20 -8.9 11.1 1704.7 322.8 5.27 5.28 11.89

DR3 30 -30 -18.9 11.1 956.9 268.9 5.03 3.56 6.98

DR3 30 -40 -28.9 11.1 509.0 220.4 4.79 2.31 3.77

DR3 45 -12 -0.9 11.1 2019.1 415.1 5.73 4.86 16.18

DR3 45 -20 -8.9 11.1 1342.8 357.9 5.42 3.75 11.20

DR3 45 -30 -18.9 11.1 747.1 285.8 5.08 2.61 6.57

DR3 45 -40 -28.9 11.1 385.1 221.5 4.75 1.74 3.42

DR3 60 -12 -0.9 11.1 1465.1 457.7 5.98 3.20 14.81

DR3 60 -20 -8.9 11.1 926.5 379.0 5.50 2.44 9.88

DR3 60 -30 -18.9 11.1 478.7 284.0 5.04 1.69 5.46

DR3 60 -40 -28.9 11.1 222.7 207.3 4.67 1.07 2.53

Table 3-8a, Measured data of NEK2134GK, refrigerant DR3,

superheating 11.1°C, (dew point based)

0.00

1.00

2.00

3.00

4.00

5.00

6.00

7.00

8.00

-45 -40 -35 -30 -25 -20 -15 -10 -5

EE

R (B

TU

/Wh

)

Evaporating Temp (°C)

COMPRESSOR CHART - EER(BTU/Wh); R404A, SH 11.1 °C

60

55

50

45

40

35

30

Page 19: TEST REPORT #50 Compressor Calorimeter Test of ... - Compressor shell TC "T", Agilent 34970A ± 0.5 C Temperature - Return gas TC "T", Agilent 34970A ± 0.5 C Table 2-2, List of instruments

19

AVERAGE T cond T evap T return gas T Superheat Cool. Capacity Power input Current EER Mass flow

REFRIGERANT (°C) (°C) (°C) (°C) % % % % %

DR3 30 -12 -0.9 11.1 1.0% 2.3% 1.3% 3.2% 1.2%

DR3 30 -20 -8.9 11.1 0.9% 2.0% 0.2% 1.1% 0.7%

DR3 30 -30 -18.9 11.1 0.2% 0.2% 0.0% 0.0% 0.1%

DR3 30 -40 -28.9 11.1 3.3% 1.9% 1.1% 1.5% 3.4%

DR3 45 -12 -0.9 11.1 2.0% 0.6% 0.2% 2.6% 2.2%

DR3 45 -20 -8.9 11.1 3.9% 1.2% 1.5% 2.6% 3.7%

DR3 45 -30 -18.9 11.1 2.5% 0.8% 1.2% 1.6% 2.9%

DR3 45 -40 -28.9 11.1 1.5% 0.9% 0.1% 0.6% 1.5%

DR3 60 -12 -0.9 11.1 0.7% 0.2% 0.3% 0.5% 0.6%

DR3 60 -20 -8.9 11.1 1.7% 1.0% 0.0% 0.8% 1.7%

DR3 60 -30 -18.9 11.1 0.7% 0.1% 0.4% 0.6% 0.7%

DR3 60 -40 -28.9 11.1 1.2% 2.0% 1.0% 0.8% 1.2%

Table 3-8b., Difference (abs %) between 2 measured pieces of NEK2134GK,

refrigerant DR3, superheating 11.1 °C, (dew point based)

Coefficients Capacity (BTU/h) Mass flow (kg) Power input (W)

C1 6.130E+03 3.081E+01 3.459E+02

C2 2.173E+02 1.092E+00 1.889E+00

C3 -7.830E+01 -1.565E-01 1.633E+00

C4 2.563E+00 1.292E-02 -5.417E-02

C5 -1.730E+00 -2.761E-03 1.090E-01

C6 6.687E-01 2.434E-03 7.183E-02

C7 7.381E-03 5.124E-05 -6.417E-04

C8 -1.533E-02 -1.173E-05 9.510E-04

C9 -4.039E-05 9.204E-06 5.636E-04

C10 -5.744E-03 -2.571E-05 -5.622E-04

Table 3-9, Coefficients C1 – C10 for NEK2134GK,

refrigerant DR3, superheating 11.1°C, (dew point based)

Page 20: TEST REPORT #50 Compressor Calorimeter Test of ... - Compressor shell TC "T", Agilent 34970A ± 0.5 C Temperature - Return gas TC "T", Agilent 34970A ± 0.5 C Table 2-2, List of instruments

20

CURVE-FITTED CHARTS

Figure 3-13, Cooling capacity of NEK2134GK, refrigerant DR3,

superheating 11.1 °C, (dew point based)

Figure 3-14, Mass flow of NEK2134GK, refrigerant DR3,

superheating 11.1 °C, (dew point based)

0

250

500

750

1000

1250

1500

1750

2000

2250

2500

2750

3000

-45 -40 -35 -30 -25 -20 -15 -10 -5

Cap

acit

y (B

TU

/h)

Evaporating Temp (°C)

COMPRESSOR CHART - CAPACITY (BTU/h); DR3; SH 11,1 °C

60

55

50

45

40

35

30

T cond (°C)

0.00

2.00

4.00

6.00

8.00

10.00

12.00

14.00

16.00

18.00

20.00

-45 -40 -35 -30 -25 -20 -15 -10 -5

Mass flo

w (kg

/h)

Evaporating Temp (°C)

COMPRESSOR CHART - MASS FLOW (kg/h); DR3; SH 11.1 °C

60

55

50

45

40

35

30

T cond (°C)

Page 21: TEST REPORT #50 Compressor Calorimeter Test of ... - Compressor shell TC "T", Agilent 34970A ± 0.5 C Temperature - Return gas TC "T", Agilent 34970A ± 0.5 C Table 2-2, List of instruments

21

Figure 3-15, Power input of NEK2134GK, refrigerant DR3,

superheating 11.1 °C, (dew point based)

Figure 3-16, EER of NEK2134GK, refrigerant DR3,

superheating 11.1 °C, (dew point based)

150

200

250

300

350

400

450

500

550

-45 -40 -35 -30 -25 -20 -15 -10 -5

Po

wer in

pu

t (W

)

Evaporating Temp (°C)

COMPRESSOR CHART - POWER INPUT(W); DR3; SH 11.1 °C

60

55

50

45

40

35

30

T cond (°C)

0.70

1.70

2.70

3.70

4.70

5.70

6.70

7.70

-45 -40 -35 -30 -25 -20 -15 -10 -5

EE

R (B

TU

/Wh

)

Evaporating Temp (°C)

COMPRESSOR CHART - EER(BTU/Wh); DR3, SH 11.1 °C

60

55

50

45

40

35

30

T cond (°C)

Page 22: TEST REPORT #50 Compressor Calorimeter Test of ... - Compressor shell TC "T", Agilent 34970A ± 0.5 C Temperature - Return gas TC "T", Agilent 34970A ± 0.5 C Table 2-2, List of instruments

22

3.2.3. Comparison of the results

Capacity (BTU/h) DR3 Mass Flow (kg/h) DR3

°C 60 55 50 45 40 35 30 °C 60 55 50 45 40 35 30

-40 222 290 344 388 427 465 507 -40 2.52 2.93 3.24 3.45 3.59 3.69 3.75

-37 281 357 419 472 519 566 615 -37 3.26 3.68 4.00 4.23 4.39 4.50 4.58

-34 355 440 512 575 632 688 747 -34 4.12 4.56 4.89 5.13 5.31 5.44 5.54

-31 445 541 624 698 766 833 903 -31 5.10 5.55 5.90 6.16 6.36 6.50 6.62

-28 552 661 756 842 923 1002 1085 -28 6.22 6.68 7.05 7.33 7.54 7.71 7.85

-25 677 800 909 1009 1103 1197 1293 -25 7.48 7.96 8.34 8.64 8.87 9.07 9.23

-22 822 960 1085 1200 1309 1418 1530 -22 8.89 9.39 9.79 10.11 10.36 10.58 10.77

-19 988 1143 1284 1415 1541 1667 1795 -19 10.46 10.98 11.40 11.73 12.01 12.25 12.47

-16 1176 1349 1508 1657 1801 1944 2091 -16 12.19 12.73 13.17 13.53 13.84 14.10 14.34

-13 1387 1579 1757 1926 2090 2252 2418 -13 14.11 14.67 15.13 15.51 15.84 16.13 16.40

-10 1622 1835 2034 2224 2408 2591 2777 -10 16.20 16.78 17.27 17.68 18.03 18.34 18.64

Capacity (BTU/h) R404A Mass Flow (kg/h) R404A

°C 60 55 50 45 40 35 30 °C 60 55 50 45 40 35 30

-40 235 322 396 464 531 605 691 -40 4.49 5.03 5.45 5.80 6.11 6.40 6.70

-37 318 414 498 575 651 733 827 -37 5.70 6.22 6.64 6.99 7.29 7.57 7.86

-34 406 515 611 699 787 880 985 -34 7.03 7.56 7.98 8.33 8.63 8.91 9.21

-31 502 627 737 840 942 1049 1167 -31 8.50 9.04 9.47 9.83 10.14 10.44 10.74

-28 611 753 881 1001 1120 1243 1378 -28 10.13 10.69 11.14 11.52 11.85 12.16 12.49

-25 735 898 1046 1186 1324 1466 1620 -25 11.93 12.52 13.00 13.41 13.77 14.11 14.46

-22 878 1064 1235 1397 1557 1722 1896 -22 13.92 14.55 15.07 15.51 15.91 16.29 16.68

-19 1042 1254 1451 1638 1823 2012 2211 -19 16.12 16.79 17.36 17.85 18.29 18.71 19.15

-16 1232 1473 1697 1912 2125 2341 2566 -16 18.53 19.26 19.88 20.43 20.93 21.40 21.89

-13 1450 1722 1977 2223 2466 2711 2966 -13 21.18 21.97 22.66 23.27 23.83 24.37 24.93

-10 1700 2005 2294 2573 2849 3127 3414 -10 24.08 24.95 25.71 26.39 27.02 27.64 28.26

Capacity: (DR3 - R404A)/R404A (%) Mass flow: (DR3 - R404A)/R404A (%)

°C 60 55 50 45 40 35 30 °C 60 55 50 45 40 35 30

-40 -5.6 -10.0 -13.2 -16.3 -19.6 -23.1 -26.7 -40 -43.9 -41.6 -40.6 -40.5 -41.2 -42.4 -44.1

-37 -11.5 -13.8 -15.8 -17.9 -20.2 -22.8 -25.6 -37 -42.8 -40.8 -39.8 -39.5 -39.8 -40.5 -41.8

-34 -12.5 -14.4 -16.1 -17.8 -19.7 -21.8 -24.1 -34 -41.4 -39.7 -38.8 -38.4 -38.5 -39.0 -39.9

-31 -11.5 -13.6 -15.3 -17.0 -18.7 -20.6 -22.6 -31 -40.0 -38.6 -37.7 -37.3 -37.3 -37.7 -38.3

-28 -9.8 -12.3 -14.2 -15.9 -17.6 -19.4 -21.3 -28 -38.6 -37.5 -36.8 -36.4 -36.4 -36.6 -37.1

-25 -7.9 -10.9 -13.1 -14.9 -16.7 -18.4 -20.2 -25 -37.3 -36.4 -35.9 -35.6 -35.5 -35.7 -36.2

-22 -6.4 -9.7 -12.2 -14.1 -15.9 -17.6 -19.3 -22 -36.2 -35.5 -35.1 -34.9 -34.9 -35.1 -35.4

-19 -5.2 -8.9 -11.5 -13.6 -15.5 -17.2 -18.8 -19 -35.1 -34.6 -34.4 -34.3 -34.3 -34.5 -34.9

-16 -4.6 -8.4 -11.2 -13.4 -15.2 -16.9 -18.5 -16 -34.2 -33.9 -33.8 -33.7 -33.9 -34.1 -34.5

-13 -4.4 -8.3 -11.1 -13.4 -15.3 -16.9 -18.5 -13 -33.4 -33.3 -33.2 -33.3 -33.5 -33.8 -34.2

-10 -4.6 -8.5 -11.3 -13.6 -15.5 -17.1 -18.6 -10 -32.7 -32.7 -32.8 -33.0 -33.3 -33.6 -34.0

Page 23: TEST REPORT #50 Compressor Calorimeter Test of ... - Compressor shell TC "T", Agilent 34970A ± 0.5 C Temperature - Return gas TC "T", Agilent 34970A ± 0.5 C Table 2-2, List of instruments

23

Table 3-10, Comparison of the results, superheating 11.1 °C, (dew point based)

Power Input (W) DR3 EER (BTU/Wh) DR3

°C 60 55 50 45 40 35 30 °C 60 55 50 45 40 35 30

-40 209 214 218 219 219 219 218 -40 1.06 1.35 1.58 1.77 1.95 2.13 2.33

-37 231 235 237 237 236 234 232 -37 1.22 1.52 1.77 1.99 2.20 2.41 2.65

-34 254 257 257 256 254 251 247 -34 1.40 1.72 1.99 2.25 2.49 2.74 3.02

-31 279 280 278 276 272 268 263 -31 1.59 1.94 2.24 2.53 2.81 3.11 3.43

-28 305 304 301 297 291 286 280 -28 1.81 2.18 2.51 2.84 3.17 3.51 3.88

-25 331 329 324 318 311 304 297 -25 2.04 2.43 2.81 3.17 3.54 3.94 4.36

-22 359 354 348 340 332 323 314 -22 2.29 2.71 3.12 3.52 3.94 4.39 4.87

-19 388 381 373 363 353 342 332 -19 2.55 3.00 3.44 3.90 4.37 4.87 5.41

-16 417 408 398 386 374 362 350 -16 2.82 3.30 3.79 4.29 4.81 5.37 5.98

-13 447 436 423 410 396 382 368 -13 3.10 3.62 4.15 4.70 5.28 5.90 6.57

-10 477 464 449 434 418 402 386 -10 3.40 3.95 4.53 5.13 5.76 6.45 7.20

Power Input (W) R404A EER (BTU/Wh) R404A

°C 60 55 50 45 40 35 30 °C 60 55 50 45 40 35 30

-40 254 258 262 265 266 266 264 -40 0.93 1.25 1.51 1.75 2.00 2.28 2.62

-37 285 288 290 290 290 287 284 -37 1.11 1.44 1.72 1.98 2.25 2.55 2.92

-34 318 319 318 316 314 310 304 -34 1.27 1.62 1.92 2.21 2.51 2.84 3.24

-31 352 350 347 343 339 333 325 -31 1.43 1.79 2.12 2.45 2.78 3.15 3.59

-28 387 382 377 371 364 356 346 -28 1.58 1.97 2.34 2.70 3.08 3.49 3.98

-25 422 415 407 399 390 379 368 -25 1.74 2.16 2.57 2.97 3.40 3.87 4.40

-22 458 448 438 427 416 403 390 -22 1.92 2.37 2.82 3.27 3.74 4.27 4.86

-19 495 483 470 457 443 428 412 -19 2.11 2.60 3.09 3.59 4.12 4.70 5.37

-16 532 517 502 486 470 453 434 -16 2.31 2.85 3.38 3.93 4.52 5.17 5.91

-13 571 553 534 516 497 477 457 -13 2.54 3.12 3.70 4.31 4.96 5.68 6.49

-10 609 588 567 546 525 503 480 -10 2.79 3.41 4.04 4.71 5.43 6.22 7.12

Power input: (DR3 - R404A)/R404A (%) EER: (DR3 - R404A)/R404A (%)

°C 60 55 50 45 40 35 30 °C 60 55 50 45 40 35 30

-40 -17.8 -17.1 -17.0 -17.2 -17.5 -17.6 -17.4 -40 14.8 8.6 4.6 1.1 -2.5 -6.6 -11.2

-37 -19.2 -18.5 -18.3 -18.3 -18.5 -18.5 -18.2 -37 9.5 5.7 3.1 0.6 -2.1 -5.3 -9.1

-34 -20.2 -19.5 -19.2 -19.1 -19.1 -19.1 -18.7 -34 9.5 6.2 3.8 1.7 -0.7 -3.4 -6.7

-31 -20.8 -20.1 -19.8 -19.7 -19.6 -19.5 -19.0 -31 11.7 8.1 5.5 3.4 1.1 -1.4 -4.4

-28 -21.2 -20.5 -20.2 -20.0 -19.9 -19.7 -19.2 -28 14.5 10.3 7.5 5.1 2.8 0.4 -2.5

-25 -21.4 -20.8 -20.4 -20.2 -20.1 -19.8 -19.3 -25 17.2 12.5 9.2 6.6 4.3 1.8 -1.0

-22 -21.6 -20.9 -20.6 -20.4 -20.2 -19.9 -19.4 -22 19.4 14.2 10.6 7.8 5.3 2.9 0.1

-19 -21.6 -21.0 -20.7 -20.4 -20.3 -20.0 -19.5 -19 20.9 15.4 11.5 8.6 6.0 3.5 0.8

-16 -21.7 -21.1 -20.7 -20.5 -20.3 -20.0 -19.5 -16 21.8 16.0 12.1 9.0 6.4 3.8 1.2

-13 -21.7 -21.1 -20.8 -20.5 -20.3 -20.0 -19.5 -13 22.1 16.2 12.2 9.0 6.4 3.9 1.3

-10 -21.6 -21.1 -20.8 -20.6 -20.4 -20.1 -19.6 -10 21.8 16.0 11.9 8.8 6.2 3.7 1.2

Page 24: TEST REPORT #50 Compressor Calorimeter Test of ... - Compressor shell TC "T", Agilent 34970A ± 0.5 C Temperature - Return gas TC "T", Agilent 34970A ± 0.5 C Table 2-2, List of instruments

24

3.3. Superheating 22.2 °C

3.3.1. Reference measurement with R404A (dew point based)

AVERAGE T cond T evap T return gas T Superheat Cool. Capacity Power input Current EER Mass flow

REFRIGERANT (°C) (°C) (°C) (°C) BTU/h W A (BTU/Wh) kg/h

R404A 30 -12 10.2 22.2 3299.6 463.0 5.83 7.13 25.61

R404A 30 -20 2.2 22.2 2223.8 403.1 5.44 5.52 17.90

R404A 30 -30 -7.8 22.2 1286.5 328.2 5.00 3.92 10.91

R404A 30 -40 -17.8 22.2 724.6 262.9 4.68 2.76 6.49

R404A 45 -12 10.2 22.2 2511.8 523.6 6.24 4.80 24.09

R404A 45 -20 2.2 22.2 1679.2 445.4 5.69 3.77 16.69

R404A 45 -30 -7.8 22.2 980.3 351.2 5.12 2.79 10.36

R404A 45 -40 -17.8 22.2 510.8 262.8 4.67 1.94 5.81

R404A 60 -12 10.2 22.2 1716.3 584.8 6.68 2.93 21.84

R404A 60 -20 2.2 22.2 1118.3 480.5 5.93 2.33 15.18

R404A 60 -30 -7.8 22.2 596.3 358.7 5.15 1.66 8.84

R404A 60 -40 -17.8 22.2 273.1 246.8 4.62 1.11 4.46

Table 3-11a, Measured data of NEK2134GK, refrigerant R404A,

superheating 22.2 °C, (dew point based)

AVERAGE T cond T evap T return gas T Superheat Cool. Capacity Power input Current EER Mass flow

REFRIGERANT (°C) (°C) (°C) (°C) % % % % %

R404A 30 -12 10.2 22.2 2.4 0.3 0.9 2.1 2.5

R404A 30 -20 2.2 22.2 1.5 0.0 0.9 1.4 1.4

R404A 30 -30 -7.8 22.2 2.0 2.2 1.4 4.1 2.0

R404A 30 -40 -17.8 22.2 1.7 1.8 1.5 0.2 1.2

R404A 45 -12 10.2 22.2 1.9 1.6 1.3 0.3 2.6

R404A 45 -20 2.2 22.2 1.9 1.9 1.8 0.1 2.0

R404A 45 -30 -7.8 22.2 0.9 2.8 1.8 3.6 0.7

R404A 45 -40 -17.8 22.2 1.3 2.3 1.3 3.5 1.5

R404A 60 -12 10.2 22.2 3.1 2.4 1.7 0.7 3.1

R404A 60 -20 2.2 22.2 2.7 2.6 1.9 0.1 2.8

R404A 60 -30 -7.8 22.2 2.5 3.8 2.2 1.3 2.5

R404A 60 -40 -17.8 22.2 1.6 3.7 2.2 3.0 1.6

Table 3-11b., Difference (abs %) between 2 measured pieces of NEK2134GK, refrigerant

R404A, superheating 22.2 °C, (dew point based)

Page 25: TEST REPORT #50 Compressor Calorimeter Test of ... - Compressor shell TC "T", Agilent 34970A ± 0.5 C Temperature - Return gas TC "T", Agilent 34970A ± 0.5 C Table 2-2, List of instruments

25

Coefficients Capacity (BTU/h, °C) Mass flow (kg, °C) Power input (W, °C)

C1 8.572E+03 4.858E+01 3.868E+02

C2 3.206E+02 1.838E+00 3.480E+00

C3 -1.189E+02 -3.140E-01 5.000E+00

C4 4.249E+00 2.550E-02 -5.375E-02

C5 -3.191E+00 -8.308E-03 7.891E-02

C6 8.157E-01 4.060E-03 1.670E-02

C7 1.671E-02 1.102E-04 -7.084E-04

C8 -3.125E-02 -1.092E-04 7.155E-04

C9 2.459E-03 5.844E-06 1.349E-03

C10 -6.092E-03 -4.050E-05 -2.527E-05

Table 3-12, Coefficients C1 – C10 for NEK2134GK, refrigerant R404A,

superheating 22.2 °C, (dew point based)

CURVE-FITTED CHARTS

Figure 3-17, Cooling capacity of NEK2134GK, refrigerant R404A,

superheating 22.2 °C, (dew point based)

0

250

500

750

1000

1250

1500

1750

2000

2250

2500

2750

3000

3250

3500

3750

4000

-45 -40 -35 -30 -25 -20 -15 -10 -5

Cap

acit

y (B

TU

/h)

Evaporating Temp (°C)

COMPRESSOR CHART - CAPACITY (BTU/h); R404A, SH 22.2°C

60

55

50

45

40

35

30

Page 26: TEST REPORT #50 Compressor Calorimeter Test of ... - Compressor shell TC "T", Agilent 34970A ± 0.5 C Temperature - Return gas TC "T", Agilent 34970A ± 0.5 C Table 2-2, List of instruments

26

Figure 3-18, Mass flow of NEK2134GK, refrigerant R404A,

superheating 22.2 °C, (dew point based)

Figure 3-19, Power input of NEK2134GK, refrigerant R404A,

superheating 22.2 °C, (dew point based)

0.0

5.0

10.0

15.0

20.0

25.0

30.0

-45 -40 -35 -30 -25 -20 -15 -10 -5

Mass flo

w (kg

/h)

Evaporating Temp (°C)

COMPRESSOR CHART - MASS FLOW (kg/h); R404A, SH 22.2 °C

60

55

50

45

40

35

30

200

250

300

350

400

450

500

550

600

650

-45 -40 -35 -30 -25 -20 -15 -10 -5

Po

wer in

pu

t (W

)

Evaporating Temp (°C)

COMPRESSOR CHART - POWER INPUT(W); R404A, SH 22.2°C

60

55

50

45

40

35

30

Page 27: TEST REPORT #50 Compressor Calorimeter Test of ... - Compressor shell TC "T", Agilent 34970A ± 0.5 C Temperature - Return gas TC "T", Agilent 34970A ± 0.5 C Table 2-2, List of instruments

27

Figure 3-20, EER of NEK2134GK, refrigerant R404A,

superheating 22.2 °C, (dew point based)

3.3.2. Measurement with new refrigerant DR3 (dew point based)

AVERAGE T cond T evap T return gas T Superheat Cool. Capacity Power input Current EER Mass flow

REFRIGERANT (°C) (°C) (°C) (°C) BTU/h W A (BTU/Wh) kg/h

DR3 30 -12 10.2 22.2 2642.0 375.2 5.53 7.05 16.77

DR3 30 -20 2.2 22.2 1792.4 320.6 5.23 5.59 11.75

DR3 30 -30 -7.8 22.2 1004.5 266.6 5.01 3.77 6.87

DR3 30 -40 -17.8 22.2 534.3 218.5 4.91 2.45 3.71

DR3 45 -12 10.2 22.2 2133.9 413.1 5.72 5.17 15.85

DR3 45 -20 2.2 22.2 1409.2 355.0 5.38 3.97 10.91

DR3 45 -30 -7.8 22.2 796.4 285.5 5.06 2.79 6.49

DR3 45 -40 -17.8 22.2 410.5 216.3 4.77 1.90 3.38

DR3 60 -12 10.2 22.2 1571.9 456.1 5.96 3.45 14.50

DR3 60 -20 2.2 22.2 1014.6 378.9 5.50 2.68 9.81

DR3 60 -30 -7.8 22.2 527.7 284.6 5.04 1.85 5.46

DR3 60 -40 -17.8 22.2 245.4 206.2 4.71 1.19 2.53

Table 3-13a, Measured data of NEK2134GK, refrigerant DR3,

superheating 22.2 °C, (dew point based)

0.50

1.50

2.50

3.50

4.50

5.50

6.50

7.50

-45 -40 -35 -30 -25 -20 -15 -10 -5

EE

R (B

TU

/Wh

)

Evaporating Temp (°C)

COMPRESSOR CHART - EER(BTU/Wh); R404A, SH 22.2°C

60

55

50

45

40

35

30

Page 28: TEST REPORT #50 Compressor Calorimeter Test of ... - Compressor shell TC "T", Agilent 34970A ± 0.5 C Temperature - Return gas TC "T", Agilent 34970A ± 0.5 C Table 2-2, List of instruments

28

AVERAGE T cond T evap T return gas T Superheat Cool. Capacity Power input Current EER Mass flow

REFRIGERANT (°C) (°C) (°C) (°C) % % % % %

DR3 30 -12 10.2 22.2 2.9% 3.6% 1.6% 4.3% 2.9%

DR3 30 -20 2.2 22.2 1.4% 0.3% 1.3% 1.8% 1.5%

DR3 30 -30 -7.8 22.2 0.1% 1.8% 0.4% 1.8% 0.1%

DR3 30 -40 -17.8 22.2 2.9% 3.7% 2.2% 0.8% 2.7%

DR3 45 -12 10.2 22.2 1.8% 0.1% 0.9% 1.9% 1.9%

DR3 45 -20 2.2 22.2 2.8% 1.2% 0.7% 1.6% 3.1%

DR3 45 -30 -7.8 22.2 2.9% 1.3% 0.2% 1.5% 2.5%

DR3 45 -40 -17.8 22.2 2.5% 1.3% 2.2% 1.2% 2.7%

DR3 60 -12 10.2 22.2 0.6% 0.2% 0.2% 0.5% 0.2%

DR3 60 -20 2.2 22.2 0.7% 0.7% 0.2% 0.0% 0.7%

DR3 60 -30 -7.8 22.2 1.4% 0.9% 0.0% 0.4% 1.5%

DR3 60 -40 -17.8 22.2 1.9% 1.4% 2.0% 0.5% 1.7%

Table 3-13b., Difference (abs %) between 2 measured pieces of NEK2134GK, refrigerant DR3,

superheating 22.2 °C, (dew point based)

Coefficients Capacity (BTU/h) Mass flow (kg) Power input (W)

C1 6.260E+03 3.147E+01 3.514E+02

C2 2.229E+02 1.074E+00 5.997E+00

C3 -7.483E+01 -2.363E-01 3.244E+00

C4 2.574E+00 1.219E-02 3.655E-02

C5 -1.794E+00 -3.788E-03 1.665E-02

C6 5.570E-01 3.775E-03 1.020E-02

C7 6.799E-03 4.356E-05 -9.526E-06

C8 -1.586E-02 -1.906E-05 -1.394E-05

C9 3.816E-04 1.611E-05 1.069E-03

C10 -4.742E-03 -3.258E-05 -1.037E-05

Table 3-14, Coefficients C1 – C10 for NEK2134GK, refrigerant DR3,

superheating 22.2 °C, (dew point based)

Page 29: TEST REPORT #50 Compressor Calorimeter Test of ... - Compressor shell TC "T", Agilent 34970A ± 0.5 C Temperature - Return gas TC "T", Agilent 34970A ± 0.5 C Table 2-2, List of instruments

29

CURVE-FITTED CHARTS

Figure 3-21, Cooling capacity of NEK2134GK, refrigerant DR3,

superheating 22.2 °C, (dew point based)

Figure 3-22, Mass flow of NEK2134GK, refrigerant DR3,

superheating 22.2 °C, (dew point based)

0

250

500

750

1000

1250

1500

1750

2000

2250

2500

2750

3000

3250

-45 -40 -35 -30 -25 -20 -15 -10 -5

Cap

acit

y (B

TU

/h)

Evaporating Temp (°C)

COMPRESSOR CHART - CAPACITY (BTU/h); DR3; SH 22.2 °C

60

55

50

45

40

35

30

T cond (°C)

0.00

2.00

4.00

6.00

8.00

10.00

12.00

14.00

16.00

18.00

20.00

-45 -40 -35 -30 -25 -20 -15 -10 -5

Mass flo

w (kg

/h)

Evaporating Temp (°C)

COMPRESSOR CHART - MASS FLOW (kg/h); DR3; SH 22.2 °C

60

55

50

45

40

35

30

T cond (°C)

Page 30: TEST REPORT #50 Compressor Calorimeter Test of ... - Compressor shell TC "T", Agilent 34970A ± 0.5 C Temperature - Return gas TC "T", Agilent 34970A ± 0.5 C Table 2-2, List of instruments

30

Figure 3-23, Power input of NEK2134GK, refrigerant DR3,

superheating 22.2 °C, (dew point based)

Figure 3-24, EER of NEK2134GK, refrigerant DR3,

superheating 22.2 °C, (dew point based)

150

200

250

300

350

400

450

500

550

-45 -40 -35 -30 -25 -20 -15 -10 -5

Po

wer in

pu

t (W

)

Evaporating Temp (°C)

COMPRESSOR CHART - POWER INPUT(W); DR3; SH 22.2 °C

60

55

50

45

40

35

30

T cond (°C)

1.00

2.00

3.00

4.00

5.00

6.00

7.00

8.00

-45 -40 -35 -30 -25 -20 -15 -10 -5

EE

R (B

TU

/Wh

)

Evaporating Temp (°C)

COMPRESSOR CHART - EER(BTU/Wh); DR3, return 22.2 °C

60

55

50

45

40

35

30

T cond (°C)

Page 31: TEST REPORT #50 Compressor Calorimeter Test of ... - Compressor shell TC "T", Agilent 34970A ± 0.5 C Temperature - Return gas TC "T", Agilent 34970A ± 0.5 C Table 2-2, List of instruments

31

3.3.3. Comparison of the results

Capacity (BTU/h) DR3 Mass Flow (kg/h) DR3

°C 60 55 50 45 40 35 30 °C 60 55 50 45 40 35 30

-40 246 312 366 411 452 491 533 -40 2.53 2.92 3.20 3.40 3.53 3.62 3.69

-37 312 386 448 501 550 598 647 -37 3.27 3.67 3.96 4.17 4.31 4.42 4.52

-34 393 477 548 611 669 727 786 -34 4.13 4.54 4.84 5.06 5.22 5.34 5.46

-31 491 586 668 742 811 879 950 -31 5.11 5.52 5.84 6.07 6.25 6.40 6.53

-28 608 714 809 895 976 1057 1140 -28 6.21 6.64 6.97 7.22 7.41 7.58 7.74

-25 743 863 971 1071 1166 1261 1358 -25 7.44 7.89 8.23 8.50 8.72 8.91 9.10

-22 898 1033 1156 1271 1382 1492 1604 -22 8.82 9.28 9.64 9.93 10.17 10.39 10.60

-19 1074 1225 1365 1497 1625 1751 1880 -19 10.34 10.81 11.20 11.51 11.77 12.02 12.26

-16 1272 1442 1600 1750 1895 2040 2187 -16 12.01 12.51 12.91 13.25 13.54 13.81 14.09

-13 1494 1683 1860 2029 2194 2359 2525 -13 13.85 14.37 14.79 15.16 15.48 15.78 16.09

-10 1740 1950 2148 2338 2524 2709 2897 -10 15.85 16.39 16.85 17.24 17.58 17.92 18.26

Capacity (BTU/h) R404A Mass Flow (kg/h) R404A

°C 60 55 50 45 40 35 30 °C 60 55 50 45 40 35 30

-40 269 365 447 519 586 652 722 -40 4.47 5.06 5.51 5.85 6.10 6.30 6.48

-37 357 461 551 631 706 781 861 -37 5.64 6.22 6.66 6.99 7.23 7.43 7.60

-34 455 569 669 761 848 935 1026 -34 6.94 7.52 7.96 8.28 8.53 8.72 8.90

-31 565 692 806 911 1012 1114 1220 -31 8.38 8.96 9.41 9.74 10.00 10.21 10.40

-28 689 833 963 1085 1203 1322 1446 -28 9.97 10.57 11.03 11.39 11.67 11.90 12.11

-25 831 994 1143 1284 1423 1562 1707 -25 11.73 12.36 12.86 13.24 13.55 13.81 14.05

-22 994 1177 1349 1513 1673 1836 2004 -22 13.69 14.36 14.89 15.31 15.66 15.96 16.25

-19 1179 1387 1583 1772 1958 2147 2341 -19 15.86 16.57 17.15 17.63 18.02 18.38 18.71

-16 1390 1625 1849 2066 2280 2497 2721 -16 18.25 19.03 19.66 20.20 20.65 21.07 21.47

-13 1629 1894 2148 2396 2642 2890 3146 -13 20.89 21.74 22.44 23.04 23.57 24.05 24.52

-10 1899 2197 2485 2766 3045 3328 3618 -10 23.80 24.72 25.50 26.18 26.79 27.35 27.90

Capacity: (DR3 - R404A)/R404A (%) Mass flow: (DR3 - R404A)/R404A (%)

°C 60 55 50 45 40 35 30 °C 60 55 50 45 40 35 30

-40 -8.5 -14.5 -18.1 -20.7 -22.8 -24.6 -26.1 -40 -43.4 -42.2 -41.9 -41.9 -42.2 -42.6 -43.0

-37 -12.7 -16.3 -18.7 -20.5 -22.1 -23.5 -24.8 -37 -42.0 -41.0 -40.5 -40.3 -40.4 -40.5 -40.6

-34 -13.6 -16.2 -18.1 -19.7 -21.0 -22.3 -23.4 -34 -40.5 -39.6 -39.2 -38.9 -38.8 -38.7 -38.7

-31 -13.0 -15.4 -17.1 -18.6 -19.9 -21.1 -22.2 -31 -39.0 -38.3 -37.9 -37.7 -37.5 -37.3 -37.1

-28 -11.9 -14.3 -16.0 -17.5 -18.8 -20.1 -21.2 -28 -37.7 -37.2 -36.9 -36.6 -36.5 -36.3 -36.0

-25 -10.7 -13.2 -15.1 -16.6 -18.0 -19.3 -20.5 -25 -36.6 -36.2 -36.0 -35.8 -35.7 -35.5 -35.3

-22 -9.7 -12.3 -14.3 -16.0 -17.4 -18.7 -20.0 -22 -35.6 -35.4 -35.3 -35.2 -35.1 -34.9 -34.7

-19 -8.9 -11.7 -13.8 -15.5 -17.1 -18.4 -19.7 -19 -34.8 -34.7 -34.7 -34.7 -34.7 -34.6 -34.5

-16 -8.5 -11.3 -13.5 -15.3 -16.9 -18.3 -19.6 -16 -34.2 -34.3 -34.3 -34.4 -34.4 -34.4 -34.4

-13 -8.3 -11.2 -13.4 -15.3 -16.9 -18.4 -19.7 -13 -33.7 -33.9 -34.1 -34.2 -34.3 -34.4 -34.4

-10 -8.4 -11.3 -13.6 -15.5 -17.1 -18.6 -19.9 -10 -33.4 -33.7 -33.9 -34.2 -34.4 -34.5 -34.5

Page 32: TEST REPORT #50 Compressor Calorimeter Test of ... - Compressor shell TC "T", Agilent 34970A ± 0.5 C Temperature - Return gas TC "T", Agilent 34970A ± 0.5 C Table 2-2, List of instruments

32

Table 3-15, Comparison of the results, superheating 22.2 °C, (dew point based)

Power Input (W) DR3 EER (BTU/Wh) DR3

°C 60 55 50 45 40 35 30 °C 60 55 50 45 40 35 30

-40 205 211 216 219 220 220 218 -40 1.20 1.48 1.70 1.88 2.05 2.24 2.45

-37 229 233 236 237 237 235 232 -37 1.36 1.66 1.90 2.11 2.32 2.54 2.79

-34 254 256 257 256 254 251 246 -34 1.55 1.86 2.14 2.39 2.63 2.90 3.19

-31 279 279 278 276 272 267 261 -31 1.76 2.10 2.40 2.69 2.98 3.29 3.63

-28 305 303 300 296 291 285 277 -28 1.99 2.36 2.69 3.02 3.36 3.71 4.11

-25 332 328 323 317 310 302 294 -25 2.24 2.63 3.01 3.38 3.76 4.17 4.62

-22 359 353 346 339 330 321 311 -22 2.50 2.92 3.34 3.76 4.19 4.65 5.15

-19 387 379 370 361 351 340 329 -19 2.77 3.23 3.69 4.15 4.63 5.15 5.71

-16 416 406 395 384 372 360 348 -16 3.06 3.55 4.05 4.56 5.09 5.66 6.29

-13 446 433 420 407 394 381 367 -13 3.35 3.89 4.42 4.98 5.57 6.20 6.88

-10 476 461 446 432 417 402 387 -10 3.66 4.23 4.81 5.42 6.06 6.74 7.49

Power Input (W) R404A EER (BTU/Wh) R404A

°C 60 55 50 45 40 35 30 °C 60 55 50 45 40 35 30

-40 247 254 260 264 265 265 262 -40 1.09 1.43 1.72 1.97 2.21 2.46 2.75

-37 279 284 287 288 288 286 282 -37 1.28 1.62 1.92 2.19 2.45 2.74 3.06

-34 312 315 315 314 312 307 302 -34 1.46 1.81 2.12 2.42 2.72 3.04 3.40

-31 347 346 344 341 336 330 322 -31 1.63 2.00 2.34 2.67 3.01 3.38 3.79

-28 382 379 374 369 361 353 344 -28 1.80 2.20 2.57 2.94 3.33 3.74 4.21

-25 419 413 405 397 387 377 365 -25 1.98 2.41 2.82 3.24 3.67 4.14 4.67

-22 456 447 437 426 414 401 388 -22 2.18 2.64 3.09 3.55 4.04 4.58 5.17

-19 494 482 469 455 441 426 410 -19 2.39 2.88 3.38 3.90 4.45 5.04 5.71

-16 532 517 501 484 468 450 433 -16 2.61 3.14 3.69 4.26 4.88 5.54 6.29

-13 571 552 533 514 495 475 455 -13 2.85 3.43 4.03 4.66 5.34 6.08 6.91

-10 610 588 566 544 522 500 478 -10 3.11 3.73 4.39 5.08 5.83 6.66 7.57

Power input: (DR3 - R404A)/R404A (%) EER: (DR3 - R404A)/R404A (%)

°C 60 55 50 45 40 35 30 °C 60 55 50 45 40 35 30

-40 -17.1 -17.0 -17.0 -17.0 -17.0 -17.0 -17.0 -40 10.3 3.0 -1.3 -4.4 -7.0 -9.1 -11.0

-37 -18.0 -17.9 -17.9 -17.8 -17.8 -17.7 -17.7 -37 6.4 2.0 -1.0 -3.3 -5.3 -7.0 -8.6

-34 -18.8 -18.7 -18.6 -18.5 -18.4 -18.4 -18.4 -34 6.5 3.1 0.6 -1.4 -3.2 -4.7 -6.2

-31 -19.6 -19.4 -19.3 -19.2 -19.0 -19.0 -18.9 -31 8.2 5.0 2.7 0.7 -1.0 -2.6 -4.1

-28 -20.2 -20.0 -19.9 -19.7 -19.5 -19.4 -19.3 -28 10.5 7.2 4.8 2.7 0.9 -0.8 -2.4

-25 -20.8 -20.5 -20.3 -20.1 -19.9 -19.7 -19.6 -25 12.7 9.3 6.6 4.4 2.4 0.6 -1.1

-22 -21.2 -21.0 -20.7 -20.5 -20.2 -20.0 -19.7 -22 14.6 11.0 8.1 5.7 3.5 1.5 -0.3

-19 -21.6 -21.3 -21.0 -20.7 -20.4 -20.1 -19.8 -19 16.1 12.2 9.1 6.5 4.2 2.0 0.1

-16 -21.8 -21.5 -21.1 -20.8 -20.4 -20.1 -19.7 -16 17.1 13.0 9.7 6.9 4.4 2.2 0.1

-13 -22.0 -21.6 -21.2 -20.8 -20.4 -19.9 -19.5 -13 17.6 13.3 9.9 6.9 4.3 1.9 -0.3

-10 -22.1 -21.6 -21.2 -20.7 -20.2 -19.7 -19.1 -10 17.6 13.2 9.7 6.6 3.8 1.3 -1.0

Page 33: TEST REPORT #50 Compressor Calorimeter Test of ... - Compressor shell TC "T", Agilent 34970A ± 0.5 C Temperature - Return gas TC "T", Agilent 34970A ± 0.5 C Table 2-2, List of instruments

33

4. Summary

4.1. Return gas temperature 18.3 °C (dew point based)

100% 100% 100%

84%

82%

79%

70%

75%

80%

85%

90%

95%

100%

105%

-10/45 -20/45 -30/45

Rela

tive c

han

ge

Evap/cond (°C)

CAPACITY EVALUATION (%), return temp. 18.3 °C, dew point basedR404A

DR3

100% 100% 100%

105%104%

98%

70%

75%

80%

85%

90%

95%

100%

105%

110%

115%

-10/45 -20/45 -30/45

Rela

tive c

han

ge

Evap/cond (°C)

EFFICIENCY EVALUATION (%), return temp. 18.3 °C, dew point based R404A

DR3

49.4

57.0

59.3

56.2

62.866.2

30

35

40

45

50

55

60

65

70

-12/45 -20/45 -30/45

°C

Evap/cond (°C)

Shell temperature (°C), return temp. 18.3 °C, dew point basedR404A

DR3

Page 34: TEST REPORT #50 Compressor Calorimeter Test of ... - Compressor shell TC "T", Agilent 34970A ± 0.5 C Temperature - Return gas TC "T", Agilent 34970A ± 0.5 C Table 2-2, List of instruments

34

4.2. Superheating 11.1 °C (dew point based)

93.0 93.7 93.2

99.2 100.2

95.2

70

75

80

85

90

95

100

105

110

-12/45 -20/45 -30/45

°C

Evap/cond (°C)

Discharge temperature (°C), return temp. 18.3 °C, dew point based R404A

DR3

100% 100% 100%

86% 86%83%

70%

75%

80%

85%

90%

95%

100%

105%

-10/45 -20/45 -30/45

Rela

tive c

han

ge

Evap/cond (°C)

CAPACITY EVALUATION (%), superheating 11.1 °C, dew point basedR404A

DR3

100% 100% 100%

109% 108%

104%

90%

95%

100%

105%

110%

115%

-10/45 -20/45 -30/45

Rela

tive c

han

ge

Evap/cond (°C)

EFFICIENCY EVALUATION (%), superheating 11.1 °C, dew point based R404A

DR3

Page 35: TEST REPORT #50 Compressor Calorimeter Test of ... - Compressor shell TC "T", Agilent 34970A ± 0.5 C Temperature - Return gas TC "T", Agilent 34970A ± 0.5 C Table 2-2, List of instruments

35

4.3. Superheating 22.2 °C (dew point based)

41.7

48.0 51.048.3 50.3

58.4

30

35

40

45

50

55

60

65

70

-12/45 -20/45 -30/45

°C

Evap/cond (°C)

Shell temperature (°C), superheating 11.1 °C, dew point basedR404A

DR3

84.1 86.3 84.7

91.5

93.2

87.2

70

75

80

85

90

95

100

105

110

-12/45 -20/45 -30/45

°C

Evap/cond (°C)

Discharge temperature (°C), superheating 11.1 °C, dew point based R404A

DR3

100% 100% 100%

85% 84%

82%

70%

75%

80%

85%

90%

95%

100%

105%

-10/45 -20/45 -30/45

Rela

tive c

han

ge

Evap/cond (°C)

CAPACITY EVALUATION (%), superheating 22.2 °C, dew point basedR404A

DR3

Page 36: TEST REPORT #50 Compressor Calorimeter Test of ... - Compressor shell TC "T", Agilent 34970A ± 0.5 C Temperature - Return gas TC "T", Agilent 34970A ± 0.5 C Table 2-2, List of instruments

36

End of the report

100% 100% 100%

107%106%

101%

90%

95%

100%

105%

110%

115%

-10/45 -20/45 -30/45

Rela

tive c

han

ge

Evap/cond (°C)

EFFICIENCY EVALUATION (%), superheating 22.2 °C, dew point based R404A

DR3

46.2

51.5

54.4

52.1

56.7

60.8

30

35

40

45

50

55

60

65

-12/45 -20/45 -30/45

°C

Evap/cond (°C)

Shell temperature (°C), superheating 22.2 °C, dew point basedR404A

DR3

89.4 89.4 87.5

95.6

91.7 90.2

70

75

80

85

90

95

100

105

110

-12/45 -20/45 -30/45

°C

Evap/cond (°C)

Discharge temperature (°C), superheating 22.2 °C, dew point based R404A

DR3