Page 1: Tenmat Fire Rated Light Covers

FIRE RATED ENCLOSURES Reliable, easy-to-install, code compliant covers for

recessed lights, troffers and in-ceiling loudspeakers.

Page 2: Tenmat Fire Rated Light Covers

Fire Rated Recessed Fixture Covers TENMAT offers a wide choice of fire rated covers

for recessed lights, fluorescents and in-ceiling

speakers. The covers have been developed to meet

the code requirements of NFPA, IBC and UBC.

Other Passive Fire Protection TENMAT’s FIREFLY® range of intumescent

materials is a family of technically advanced passive

fire protection materials with outstanding

performance that have proved effective in a wide

variety of passive fire protection applications.

For over 100 years, TENMAT has been a

leader in the development, engineering and

manufacturing of specialist non-metallic

materials that offer advanced passive fire

protection capabilities.

TENMAT stands for innovation, safety

products, commitment to our customers and

the latest quality standards worldwide.

Page 3: Tenmat Fire Rated Light Covers

FF109-350 1 Hour Fire Rated Light Cover Inside height 11" diameter 15" Packaged 10 per carton

1 Hour Fire Rated Enclosure for Recessed Lights up to 8”.

FF109-300 1 Hour UL Fire Rated Light Cover Inside height 8" diameter 13" Packaged 6 per carton

1 Hour Fire Rated Enclosure for Recessed Lights up to 6”.

FF130-2'x2' Troffer Cover Inside height 5" length 2' width 2' Packaged 6 per carton

1 Hour Fire Rated Enclosure for 2’x2’ Troffers.

FF130-2'x4' Troffer Cover Inside height 5" length 4' width 2' Packaged 6 per carton more details for FF130-2x4

1 Hour Fire Rated Enclosure for 2’x4’ Troffers.

FF109X 2 Hour UL Fire Rated Light Cover Inside height 8" diameter 15" Packaged 8 per carton

The only 2 Hour UL Fire Rated Recessed Light Enclosure on the market.

FF109-FRSC Fire Rated Speaker Cover Inside height 8" diameter 13"

FF109-FRSCXL Fire Rated Speaker Cover Large Inside height 11" diameter 15"

1 Hour Fire Rated Enclosure for In-ceiling Loudspeakers.

Other Passive Fire Protection - Fire Barriers for Ventilated Cavities

- Fire Stop Blocks

- Fire Barriers for Linear Gaps & Joints

- Fire Rated Pipe Sleeves

Passive Fire Protection Solutions for the Construction Industry

Page 4: Tenmat Fire Rated Light Covers

FF109X 2 Hour Fire Rated Light Cover

Technical Product Specification

Model

Number

Inside

Height

Outside

Diameter

FF109X 8” 17”

Performance Data

For Use:

UL Classified to maintain fire ratings of up to two hours

for the following fire-rated floor/ceiling assemblies:

L500, D500, G500, D200, G200, J200 and

L200 series

UL Classified to maintain

fire ratings of up to one hour

for the following roof/ceiling

assemblies (attics):

P200 and P500 series

General Information

Benefits:

120 minute protection.

Fits most popular IC rated fixtures.

For use with recessed incandescent, fluorescent or LED

light fixtures.

For Joist Spacing up to 24" on center.

Suitable for 2"x10", 2"x12", 2"x14" and 2"x16" joists.

Can be used in floor/ceiling, as well as roof/ceiling as-

semblies (attic).

Flexible and lightweight (approx. 2.5 lbs).

Easy Installation - can be fitted in seconds - no screws,

drilling or additional sealant required.

Maintenance free.

The FF109X is the only two hour UL

classified fire barrier that can be used

with a wide range of recessed lights to

effectively prevent the spread of flames

through a ceiling opening.

The flexible and lightweight enclosures

are made out of an intumescent

material which will be activated in case

of a fire, stopping both, flame spread

and heat transmission for up to 2 hours.

CLASSIFIED FOR FIRE RESISTANCE FIRE RESISTANCE CLASSIFICATION

SEE UL FIRE RESISTANCE DIRECTORY

Page 5: Tenmat Fire Rated Light Covers

FF109-300 1 Hour Fire Rated Light Cover

Technical Product Specification

Model

Number

Inside

Height

Outside

Diameter

FF109-300 7 3/8” 14 1/4”

Performance Data

For Use:

UL Classified to maintain the fire rating (1 hour) for the

following fire-rated floor/ceiling assemblies:

L500 series

General Information

Benefits:

60 minute protection.

Fits most popular IC rated fixtures.

For use with recessed incandescent, fluorescent or LED

light fixtures.

Can be used in L500 floor/ceiling assemblies.

Lightweight (approx. 1.5 lbs).

Easy Installation - can be fitted in seconds - no screws,

drilling or additional sealant required.

Flexible material enables the cover to be fitted around

obstacles or retro-fitted.

Enhances the acoustic protection of the ceiling.

Maintenance free.

CLASSIFIED FOR FIRE RESISTANCE FIRE RESISTANCE CLASSIFICATION

SEE UL FIRE RESISTANCE DIRECTORY

The FF109-300 UL Fire Rated cover is

a dome-shaped cover which has been

designed to help maintain the integrity

of fire rated ceilings for one hour when

using recessed light fixtures.

The unique design gives the architect,

specifier and installer more freedom in

fixture selection as the covers are suited

to a wide range of recessed lights.

Page 6: Tenmat Fire Rated Light Covers

FF109-350 1 Hour Fire Rated Light Cover

Technical Product Specification

Model

Number

Inside

Height

Outside

Diameter

FF109-350 10 3/8” 17”

Performance Data

For Use:

Warnock Hersey - Intertek certified to maintain the fire

rating (1 hour) of fire-rated floor/ceiling assemblies.

General Information

Benefits:

60 minute protection.

Fits most popular recessed light fixtures.

For use with recessed incandescent, fluorescent or LED

light fixtures.

Can be used in L500 floor/ceiling assemblies.

Lightweight (approx. 2.5 lbs).

Easy Installation - can be fitted in seconds - no screws,

drilling or additional sealant required.

Flexible material enables the cover to be fitted around

obstacles or retro-fitted.

Enhances the acoustic protection of the ceiling.

Maintenance free.

The FF109-350 is the larger version of

the FF109-300 and suitable for lights up

to 8”.

Both covers are made out of the same

intumescent material and exhibit

excellent thermal and acoustical

insulating properties.

The FF109-350 has an inside height of

10 3/8” and a diameter of 15” to fit the

most common recessed light housings.

Tested to ASTM E119 UBC 7 1

NFPA 251 ASI A2.1

Page 7: Tenmat Fire Rated Light Covers

FF130 1 Hour Fire Rated Troffer Cover

Technical Product Specification

FF130-2’x2’ FF130-2’x4’

Model

Number

Inside

Height

Outside

Length

Outside

Width

FF130-2’x2’ 5” 29” 27”

FF130-2’x4’ 5” 52” 28”

Performance Data

For Use:

UL Classified to maintain the fire rating (1 hour) for the following fire-rated assemblies: A202, D203, D216, D219, G205, G208, G218, G252, G255, G256, G262,G264, J201, J202, L006, L201, L202, L206, L209, L210, P202, P204, P206, P207, P210, P211, P213, P214,P216, P225, P227, P228, P229, P230, P231, P235, P238, P242, P246, P250, P251, P254, P255, P259, P260, P261, P264, P265, P267, P268, P269

General Information

Benefits:

60 minute protection.

Fits most popular fluorescent fixtures.

Suitable for lay-in tile ceilings.

Lightweight (approx. 5 and 10 lbs).

Easy Installation - can be fitted in seconds - no screws,

drilling or additional sealant required.

Enhances the acoustic protection of the ceiling.

Reduces heat loss through the fixture.

Maintenance free.

Cable entry points can be made anywhere on the top

and sides for ease of wiring of the fixture.

The FF130 Luminaire Covers are UL

fire rated enclosures designed to protect

recessed luminaires, troffers and flu-

orescent fixtures.

The covers are ready to install with no

assembly required and can even be

retrofitted into position due to their flex-

ible and durable design.

The FF130 Cover can be folded to ease

installation in restricted spaces.

2’

5”

CLASSIFIED FOR FIRE RESISTANCE FIRE RESISTANCE CLASSIFICATION

SEE UL FIRE RESISTANCE DIRECTORY

Page 8: Tenmat Fire Rated Light Covers

FF109-FRSC 1 Hour Fire Rated Speaker Cover

The FF109-FRSC sizes have been

designed to help maintain the integrity

of fire rated ceilings when penetrated by

in-ceiling loudspeakers.

Two convenient cover sizes give the

architect, audio professional or installer

more freedom in loudspeaker selection.

The sound absorbing properties of the

FF109 enhance the acoustic rating of

the structure for crisp and clear sound.

Technical Product Specification

FF109-FRSC FF109-FRSCXL

Model

Number

Inside

Height

Outside

Diameter

FF109-FRSC 7 3/8” 14 1/4”

FF109-FRSCXL 10 3/8” 17”

Performance Data

For Use:

Intertek/OPL certified to maintain the fire rating (1 hour)

of fire-rated floor/ceiling assemblies.

Suitable for a wide range of in-ceiling loudspeakers.

General Information

Benefits:

60 minute protection.

Enhances the acoustic protection of the ceiling.

Can be used in floor/ceiling assemblies.

Lightweight (approx. 1.5 lbs and 2.5 lbs).

Easy Installation - can be fitted in seconds - no screws,

drilling or additional sealant required.

Flexible material enables the cover to be fitted around

obstacles or retro-fitted.

Reduces heat loss through the fixture.

Significant energy cost savings.

Maintenance free.

Tested to ASTM E119 UBC 7 1

NFPA 251 ASI A2.1

Page 9: Tenmat Fire Rated Light Covers

Advanced Fire Protection Other Passive Fire Protection Products

Fire Barriers for Ventilated Cladding Cladding systems are designed with an air cavity

that acts like an open chimney to provide back

ventilation. However, in a fire situation this chim-

ney effect creates an open path for the spread of

fire. The FF109 VFB maintains the back

ventilation in normal conditions, but, in the event

of fire, quickly expand to seal off the cavity.

Fire Stop Blocks TENMAT's FF108 Fire Stop Block is a unique,

compressible and fully intumescent alternative to

traditional fire stop pillows.

The Fire Stop Block can be supplied in up to

1 meter lengths and then be cut to size on site,

to ensure maximum flexibility and minimum

wastage.

Fire Barriers for Linear Gaps & Joints TENMAT's fully intumescent and compressible

FF108 materials are supplied as linear gap or

expansion joint seals.

The seals are available in a range of thicknesses

and widths to suit a wide variety of gap sizes.

The materials offer excellent compression and

movement characteristics and are easy to fit.

Fire Rated Pipe Sleeves TENMAT FF 109 Pipe Fire Sleeves are an

intumescent solution providing fire and acoustic

protection to combustible and non-combustible

pipes, ventilation ducting and cable bunches

when penetrating fire rated walls or floors.

The FF109 Fire Rated Pipe Sleeves are ready to

install providing a quick and easy solution

without the need for foams, mastic or sealant.

Page 10: Tenmat Fire Rated Light Covers
Page 11: Tenmat Fire Rated Light Covers

Recessed lights in ceilings are widely used in residential and commercial buildings.

Each ceiling is subject to fire regulations and where applicable the ceiling

construction needs to be fire rated. However, once a hole is made in the ceiling for

recessed lighting, the integrity of the construction and its ability to perform in a fire

is reduced significantly. Code Officials and lawmakers have recognized this fire

hazard and the potential risks it poses to life and property. The Building Code

therefore requires recessed fixtures to be enclosed with a fire barrier.

TENMAT covers are made from intumescent and fire resistant materials which

meet and exceed the building code requirements. TENMAT materials have

outstanding firestopping capabilities and provide a one or two hour fire protection.

Multiple independent third party laboratories have tested and approved TENMAT

materials as outlined by the most stringent standards and codes.

Page 12: Tenmat Fire Rated Light Covers
Page 13: Tenmat Fire Rated Light Covers

TENMAT has changed the way how many builders, contractors and architects deal

with the problem of fire rating recessed lights. TENMAT offers the only flexible,

lightweight and fully fire tested enclosures on the market to securely fire rate your

recessed lights. The covers can be used in conjunction with a vast majority of

recessed lights, regardless of manufacturer or model.

TENMAT Fire Rated Light Covers do not require any assembly and are simply put

on top of the light without the need for any sealant, fastener or specialty tool.

TENMAT recessed light and troffer covers are used in various applications

throughout the United States and Canada; from multi-story apartment buildings,

over single-family homes to college dormitories, hotels and assisted living facilities.

TENMAT is the market leader in the production of Fire Rated Recessed Light

Covers which meet the International Building Code, NFPA, as well as the Uniform

Building Code.

Page 14: Tenmat Fire Rated Light Covers

How do TENMAT Fire Rated Light Covers work?

TENMAT covers prevent the passage of

flames and insulate against excessive heat

build up. Without the covers, the fire could

quickly spread and the building structure

could be weakened.

The FF109 Fixture Protection Covers have

intumescent characteristics so that in case

of a fire the covers expand internally to form

a highly insulative char to seal off any gaps

and prevent the fire and heat from spreading

further.

Are TENMAT Fire Rated Light Covers suitable for a range of fixtures?

Yes! TENMAT Fixture Protection Covers have been designed to fit over a wide range of

recessed light fixtures and troffers. TENMAT Fire Rated Light Covers come in different

sizes with different heights and diameters and are suitable for a broad range of recessed

light models from various manufacturers.

The covers can be used for new construction as well as remodel projects, giving the

architect and specifier finally the freedom to select the right light and fixture of their choice.

My light is IC rated. Doesn’t that mean it is already fire rated?

No! IC–rated fixtures are designed and tested for direct contact with

insulation, but are by themselves poor flame barriers. Most IC

fixtures are made either from light sheet metal or aluminum that

breaks down rapidly when in direct contact with fire. While IC-rated

lights are just constructed to be used in insulated ceilings, fire rated

lights and covers are required by the code and serve as a fire -

barrier in the event of a fire. TENMAT Fire Rated Light Covers

are also approved for use in conjunction with IC-rated lights and will maintain the fire rating

of the ceiling.

Are TENMAT Fire Rated Light Covers easy to install?

Yes! TENMAT covers are supplied ready to install. There is no additional assembly, fixing

or sealing required. The covers can be installed with a single trip up the ladder without

screws and nails! The flexible nature of the covers makes installation extremely easy in

places with limited space. The FF109 covers are extremely lightweight (about 2 lbs.) and

can be easily handled by one person. The covers are simply placed over the light fixture.

Page 15: Tenmat Fire Rated Light Covers

What are the benefits of TENMAT Covers over the drywall box method?

TENMAT Fire Barriers are ready-to-use and require NO additional assembly.

Contractors and Builders using TENMAT Fire Rated Enclosures experience significant

time and cost savings as they are able to install the covers much faster than building bulky

drywall boxes.

Light fixtures are often installed in ceilings where pipes, conduits, wiring and joists are in

close proximity. The flexible nature of the cover enables it to be fitted around these

obstructions or retro-fitted.

TENMAT covers are manufactured to the highest quality control standards, are fully fire

tested and are readily available in stock.

Yes. TENMAT covers form a barrier

over the fixtures which helps to prevent

heat loss from the room below and

contributes to improved heating and

cooling efficiencies.

TENMAT users experience significant

energy savings.

Can TENMAT Covers reduce noise transmission through the fixture?

Yes. TENMAT covers are designed to completely cover the

fixtures and exhibit excellent acoustic insulating properties.

The covers have been tested for their soundproofing capabilities

and found to significantly reduce the noise traveling through the

holes made in the ceiling for the fixtures.

How fast can I get TENMAT Fire Rated Light Covers?

TENMAT has a broad network of stocking distributors throughout

the entire United States. Material is usually in stock and can be

shipped within 24 hours.

When time is at a premium, TENMAT is your fastest and most

reliable source for code compliant fire protection solutions.

Can TENMAT Covers reduce heat loss through the fixture?

Page 16: Tenmat Fire Rated Light Covers

The information contained in this brochure is presented in good faith. It is based on data and knowledge considered to be true and accurate and is offered for the customer’s consideration, investigation and verification, but Tenmat does not warrant the results to be obtained. Please read all statements, recommendations and suggestions in conjunction with our Conditions of Sale which apply to all Tenmat goods and services. For further information please contact our Customer Service Department on 1-800-821-3436.

TENMAT consists of four divisions Passive Fire Protection, Composite Wear Parts,

High Temperature Materials, and Engineering Ceramics.

The TENMAT group is a multinational manufacturer of advanced materials with

representation in the USA, France, Italy, Germany, Sweden, the Czech Republic and

the United Kingdom, as well as a global network of resellers and distributors.

Part of

1-800-821-3436

NORTH AMERICA CUSTOMER SERVICE CENTER

Visit us on the web at www.TENMATUSA.com

NORTH AMERICA

TENMAT Inc.

23 Copper Drive

Newport, DE 19804

USA

Tel.: +1 302-633-6600

Fax: +1 302-633-6838

Email: [email protected]

Web: www.tenmatusa.com

TENMAT is committed to the highest standards in customer service and

our international staff is looking forward to assist you.

UNITED KINGDOM

TENMAT Ltd.

Ashburton Rd West

Trafford Park

Manchester M17 1TD

England

Tel.: +44(0)161 872 2181