tender specification for hvac matreial

Upload: sushil-chauhan

Post on 08-Apr-2018

218 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/7/2019 Tender Specification for HVAC matreial.

    1/17

    Table of Contents

    Sr. Description Page

    No. NoTable of Contents.......................................................................................................................................1

    1. BASIS OF DESIGN.............................................................................................................................. 1

    2. AIR COOLED SPLIT AIR CONDITIONING UNITS.........................................................................1

    3. FANS..................................................................................................................................................... 3

    4. REFRIGERANT PIPING .....................................................................................................................6

    5. PIPING INSTALLATION ....................................................................................................................7

    6. AIR DISTRIBUTION ...........................................................................................................................8

    7. INSULATION ....................................................................................................................................11

    PPENDIX - II...........................................................................................................................................15

    LIST OF APPROVED MAKES FOR EQUIPMENT & MATERIALS ............................................15

  • 8/7/2019 Tender Specification for HVAC matreial.

    2/17

    TECHNICAL SPECIFICATIONS

    1. BASIS OF DESIGN

    1.1 Site location. : Pune Maharashtra

    1.2 Geographic location. : 18.53 Deg N 73.85 Deg E

    1.3 Altitude. : 559 Mtrs. above mean sea level

    1.4 OUTDOOR DESIGN CONDITIONS

    The outdoor design conditions for various months for Pune have been considered as

    follows :

    Summer : 38.4 C ( 101.12 F) DB 20.5 C (68.9F)

    WB (mean coincidental)

    Monsoon : 30.9 C ( 87.62 F) DB (mean coincidental)

    24.8 C ( 76.64 F) WB

    Winter : 9.2 C ( 48.56 F) DB 8.0 C ( 46.4 F)

    WB (mean coincidental)

    Outdoor conditions are based on 0.4% cumulative frequency distribution (ISHRAE

    weather data book).

    1.5 INDOOR DESIGN CONDITIONS :

    Indoor design conditions for Air Conditioned spaces shall be as follows :

    a. Office areas, Cafeteria, Meeting Rooms

    DB : 23 1 Deg C (74 2 Deg F)

    RH : Less than 60%

    1.6 ASSUMPTIONS FOR HVAC LOADS :

    Glass ( Single Glass with control films) : Solar-0.56

    Transmission 1.13 Btu/hr/Ft2. 0F

    Wall U Value : 0.34 Btu/Hr. Ft2.OF (Exposed)

    0.30 Btu/Hr. Ft2.OF (Partition)

    Roof U Value considering 65mm thick

    extruded polystyrene.

    : 0.12 Btu/Hr. Ft2.OF (Exposed)

    Outside air quantity : As per ASHARE 62.1 - 2004

    2. AIR COOLED SPLIT AIR CONDITIONING UNITS

    2.1 SCOPE

  • 8/7/2019 Tender Specification for HVAC matreial.

    3/17

    The scope of this section comprise the supply, erection, testing and commissioning of

    Air Cooled Split Units conforming to these specifications and in accordance with the

    requirements of Drawings and Schedule of Quantities.

    2.2 TYPE

    The Split Units shall consist of hermetically sealed reciprocating / Scroll compressor,

    motor, air cooled condenser, integral refrigerant piping and wiring, all mounted on a

    steel frame.

    Indoor unit to be installed for Split Unit within building, shall be housed in insulated

    cabinet consisting of cooling coil, blower with motor, filter & insulated drain pan.

    The Air cooled condenser with fan and compressor duly mounted on a common

    frame shall be installed at suitable places as per drawing with suitable angle iron /

    channel frame to be provided by contractor. The suitable starters, switches, power

    control cabling between Air Indoor Unit and Outdoor Unit shall be included by the

    contractor.

    2.3 CAPACITY

    The refrigeration capacity of Split unit shall be as shown on Drawings and in

    Schedule of Quantities.

    2.4 COMPRESSOR AND MOTOR

    Compressor shall be hermetic reciprocating / Scroll, serviceable type and shall have

    dual pressure stat, and an operating oil charge. The motor shall be suction gas cooled

    and shall be sealed against dirt and moisture. The motor shall be suitable for

    41510% / volts or 23010 % volts, 50 Hz, A.C. supply.

    2.5 REFRIGERANT PIPING AND CONTROLS

    Refrigerant piping and fittings interconnecting compressor condenser shall be all

    copper and valves shall be brass / gunmetal construction.

    2.6 CASING

    The indoor & outdoor units shall be sectionalised / cabinet construction. Indoor units

    shall be consisting of fan section, coil section, filter section, and drain pan. Outdoor

    unit shall consist of condenser coil, fan & compressor. In case of split unit, the

    compressor shall be mounted with the outdoor units. Each section shall be

    constructed of thick sheet steel all welded / bolted construction, adequately reinforcedwith structural members and provided with sufficient access panels for proper

    lubrication and maintenance. Base panel shall be constructed of fabricated steel

    structure provided with an under frame suitably braced. Each unit shall include one

    piece drain pan constructed of 20 gauge galvanised sheet steel plate. Drain pan shall

    extend under coil and fan sections with drain connections. Removable panels in fan

    and coil sections shall provide access to all internal parts. Panels shall be internally

    lined with 2.5 cm thick fibreglass as per section Insulation for the thermal

    insulation and acoustic lining.

    2.7 FAN MOTOR AND DRIVE

    Fan motor shall be suitable for 415 10% volts or 23010% volts, 50 Hz,

    A.C.Supply, Single phase, motors shall be provided with permanent capacitor.

    Motors shall be especially designed for quite operation and motor speed shall not

    exceed 1440 rpm.

  • 8/7/2019 Tender Specification for HVAC matreial.

    4/17

    2.8 FAN

    Fan wheels and housing shall be fabricated from heavy gauge steel. Fan wheels shall

    be of double-width, double inlet forward-curve, multi-blade type enclosed in a

    housing and mounted on a common shaft. Fan housing shall be made of die-formed

    steel sheets with stream-lined inlets to ensure smooth air flow into the fans, fan shaft

    bearing shall be oil/grease lubricated. All rotating parts shall be dynamically

    balanced individually, and the complete assembly shall be statically and hydraulically

    balanced. Fan speed shall not exceed 1000 rpm and maximum fan outlet velocity

    shall be 550 meters per minute.

    2.9 COOLING COIL

    Cooling coils shall be of fin and tube type having aluminium fins firmly bonded to

    copper tubes assembled in zinc coated steel frame. Face and surface areas shall be

    such as to ensure rated capacity from each unit and air velocity across each coil shall

    not exceed 100 meters per minute. The coil shall be pitched in the unit casing for

    proper drainage. Each coil shall be factory-tested at 21 Kg. per sq.cm air pressure

    under water. Tube shall be mechanically / hydraulically expanded for minimumthermal contract resistance with fins. The number of fins per cm. shall be 4 to 5.

    2.10 VIBRATION ISOLATORS

    The indoor and outdoor units shall be provided with ribbed rubber pad vibration

    isolators.

    2.11 PAINTING

    Split units shall be factory finished with durable alkyd spray enamel. Shop coats of

    paint that have become marred during shipment or erection shall be cleaned off with

    mineral spirits, then coated with enamel paint to match the finish over the adjoiningshop-painted surface.

    2.12 PERFORMANCE RATING

    The unit shall be selected for the lowest operating noise level. Capacity rating and

    power consumption with operating points clearly indicated shall be submitted with

    the tenders and verified at the time of testing and commissioning of the installation.

    3. FANS

    3.1 SCOPE

    The scope of this section comprises the supply, erection, testing and

    commissioning of centrifugal, in-line and propeller type fans conforming to

    these Specifications and in accordance with the requirement of Drawings and

    Schedule of Quantities.

    3.2 TYPE

  • 8/7/2019 Tender Specification for HVAC matreial.

    5/17

    Centrifugal, in-line propeller fans shall be of the type as indicated on Drawings and

    identified in Schedule of Quantities.

    3.3 CAPACITY

    The air-moving capacity of fans shall be as shown on Drawings and in Schedule of

    Quantities.

    3.4 CENTRIFUGAL FAN

    Centrifugal fan shall be DWDI / SWSI Class I construction arrangement 3 (i.e.

    bearings on both the sides) for DWDI fans complete with access door, squirrel-cage

    induction motor, V-belt drive, belt guard and vibration isolators, direction of

    discharge / rotation, and motor position shall be as per the Approved-for-

    Construction shop drawings.

    a. Housing shall be constructed of 14 gage sheet steel welded construction.

    It shall be rigidly reinforced and supported by structural angles. Split casing

    shall be provided on larger sizes of fans, however neoprene / asbestospacking should be provided throughout split joints to make it air-tight.

    18 gauge galvanized wire mesh inlet guards of 5 cm sieves shall be

    provided on both inlets. Housing shall be provided with standard cleanout

    door with handles and neoprene gasket. Rotation arrow shall be clearly

    marked on the housing.

    b. Fan Wheel shall be backward-curved non-over loading type. Fan wheel and

    housing shall be statically and dynamically balanced. For fans upto 450 mm

    dia, fan outlet velocity shall not exceed 550 meter/minute and maximum fan

    speed shall not exceed 1450 rpm. For fans above 450 mm dia, the outlet

    velocity shall be within 700 meter/minute and maximum fan speed shall notexceed 1000 RPM. High static pressure fan speed shall be as per

    manufacturer.

    c. Shaft shall be constructed of steel, turned, ground and polished.

    d. Bearings : shall be of the sleeve / ball-bearing type mounted directly on

    the fan housing. Bearings shall be designed especially for quiet operation

    and shall be of the self-aligning, oil / grease pack pillow block type.

    e. Motor : Fan motor shall be energy efficient and suitable for 41510% volts,

    50 cycles, 3 phase AC power supply, squirrel-cage, totally enclosed, fan-

    cooled motor, provided with class F insulation, and of approved make.Motor name plate horsepower shall exceed brake horsepower by a minimum

    of 10%. Motor shall be designed specially for quiet operation and motor

    speed shall not exceed 1440 rpm. The fan and motor combination selected

    for the particular required performance shall be of the most efficient

    (smallest horse power), so that sound level is lowest.

    f. Drive to fan shall be provided through belt with adjustable motor

    sheave and a standard belt guard. Belts shall be of the oil-resistant type.

    g. Vibration Isolation : MS base shall be provided for both fan and motor, built

    as an integral part, and shall be mounted on a concrete foundation

    through resistoflex vibration isolators. The concrete foundation shall be

    atleast 15 cm above the finished floor level, or as shown in approved-for-

    construction shop drawings.

    3.5 AXIAL FLOW FAN

  • 8/7/2019 Tender Specification for HVAC matreial.

    6/17

    Fan shall be complete with motor, motor mount, belt driven (or direct driven) and

    vibration isolation type, suspension arrangement as per approved for construction

    shop drawings.

    a. Casing : shall be constructed of heavy gage sheet steel. Fan casing, motor

    mount and straightening vane shall be of welded steel construction. Motor

    mounting plate shall be minimum 15 mm thick and machined to receive

    motor flange.

    An inspection door with handle and neoprene gasket shall be provided.

    Casing shall have flanged connection on both ends for ducted applications.

    Support brackets for ceiling suspension shall be welded to the casing for

    connection to hanger bolts. Straightening vanes shall be aerodynamically

    designed for maximum efficiency by converting velocity pressure to

    static pressure potential and minimizing turbulence. Casing shall be

    bonderized, primed and finish coated with enamel paint.

    b. Rotor : hub and blades shall be cast aluminium or cast steel construction.

    Blades shall be die-formed aerofoil shaped for maximum efficiency and shall

    vary in twist and width from hub to tip to effect equal air distribution alongthe blade length. Fan blades mounting on the hub shall be statically and

    dynamically balanced. Extended grease leads for external lubrication shall

    be provided. The fan pitch control may be manually readjusted at site upon

    installation, for obtaining actual air flow values, as specified and quoted.

    c. Motor: shall be energy efficient squirrel-cage, totally-enclosed, fan

    cooled, standard frame, constant speed, continuous duty, single

    winding, suitable for 41510% volts, 50 cycles, 3 phase AC power

    supply, provided with class `F insulation. Motor shall be specially

    designed for quiet operation. The speed of the fans shall not exceed

    1000 RPM for fans with impeller diameter above 450 mm, and 1440

    RPM for fans with impeller diameter 450 mm and less. For lowestsound level, fan shall be selected for maximum efficiency or

    minimum horsepower. Motor conduit box shall be mounted on exterior

    of fan casing, and lead wires from the motor to the conduit box shall be

    protected from the air stream by enclosing in a flexible metal conduit.

    d. Drive : to fan shall be provided through belt drive with adjustable motor

    sheave and standard sheet steel belt guard with vented front for heat

    dissipation. Belts shall be of oil-resistant type.

    e. Vibration Isolation : The assembly of fan and motor shall be suspended

    from the slab by vibration isolation suspension of rubber-in-shear type.

    f. Accessories : The following accessories shall be provided with all fans :

    i. Outlet cone for static pressure regain.

    ii. Inlet cone.

    Fan silencers may be provided where specifically called for in Schedule of

    Quantities. Fans shall be factory assembled and shipped with all

    accessories factory-mounted.

    3.6 PROPELLER FAN

    Propeller fan shall be direct-driven, three or four blade type, mounted on a steel

    mounting plate with orifice ring.

    a. Mounting Plate shall be of steel construction, square with streamlined

    venturi inlet (reversed for supply applications) coated with baked enamel

  • 8/7/2019 Tender Specification for HVAC matreial.

    7/17

    paint. Mounting plate shall be of standard size, constructed of 12 to 16

    gauge sheet steel depending upon the fan size. Orifice ring shall be

    correctly formed by spinning or stamping to provide easy passage of air

    without turbulence and to direct the air stream.

    b. Fan Blades shall be constructed of aluminium or steel. Fan hub shall be of

    heavy welded steel construction with blades bolted to the hub. Fan blades

    and hub assembly shall be statically and dynamically balanced at the

    manufacturers works.

    c. Shaft shall be of steel, accurately ground and shall be of ample size for the

    load transmitted and shall not pass through first critical speed thru the full

    range of specified fan speeds.

    d. Motor shall be standard (easily replaceable) permanent split capacitor or

    shaded pole for small sizes, totally enclosed with prelubricated sleeve or

    ball bearings, designed for quiet operation with a maximum speed of 1000

    rpm for fans 60 cm dia or larger and 1440 rpm for fans 45 cm dia and

    smaller. Motors for larger fans shall be suitable for 4156% volts, 50

    cycles 3 phase power supply, and for smaller fans shall be suitable for 220 6% volts, 50 cycles single phase power supply. Motors shall be suitable

    for either horizontal or vertical service as indicated on Drawings and in

    Schedule of Quantities.

    e. Accessories : The following accessories shall be provided with propeller

    fans :

    i. Wire guard on inlet side and bird screen at the outlet.

    ii. Fixed or gravity louvers built into a steel frame at the outlet.

    iii. Regulator for controlling fan speed for single phase fan motor.

    iv. Single phase preventers for 3 phase fans.

    3.7 PERFORMANCE DATA

    All fans shall be selected for the lowest operating noise level. Capacity ratings,

    power consumption, with operating points clearly indicated, shall be submitted and

    verified at the time of testing and commissioning of the installation.

    3.8 TESTING

    Capacity of all fans shall be measured by an anemometer. Measured air flow

    capacities shall conform to the specified capacities and quoted ratings. Power

    consumption shall be computed from measurements of incoming voltage and

    input current.

    4. REFRIGERANT PIPING

    a. All refrigerant pipes and fittings shall be hard drawn copper tubes and

    wrought copper / brass fittings suitable for connection with silver solder /

    phos-copper.

    b. All joints in copper piping shall be sweat joints using low temperature

    brazing and / or silver solder. Before joining any copper pipe or fittings, its

    interiors shall be thoroughly cleaned by passing a clean cloth via wire or

    cable through its entire length. The piping shall be continuously kept clean

  • 8/7/2019 Tender Specification for HVAC matreial.

    8/17

    of dirt etc. while constructing the joints. Subsequently, it shall be

    thoroughly blown out using carbon dioxide / nitrogen.

    c. Refrigerant lines shall be sized to limit pressure drop between the

    evaporator and condensing unit to less than 0.2 kg per sq.cm.

    d. Sight glass with moisture indicator and removable type combination dryer

    cum filter with MS housing and brass wire mesh / punched brass sheet

    shall be installed in liquid line of the refrigeration system incorporating a

    three valve by pass. After ninety days of operation, liquid line drier cartridges

    shall be replaced.

    e. Horizontal suction line shall be pitched towards the compressor and no

    reducers shall be provided for proper oil return.

    f. After the refrigerant piping installation has been completed, the

    refrigerant piping system shall be pressure tested using Freon mixed

    with nitrogen / carbon dioxide at a pressure of 20 kg per sq. cm (high

    side) and 10 kg per sq. cm (low side). Pressure shall be maintained in the

    system for a minimum of 12 hours. The system shall then be evacuated to aminimum vacuum of 70 cm of mercury and held for 24 hours. Vacuum shall

    be checked with a vacuum gage.

    g. All refrigeration piping shall be installed strictly as per the instructions

    and recommendations of air conditioning equipment manufacturer.

    5. PIPING INSTALLATION

    a. Design Drawings indicate schematically the location of pipes. The

    Contractor, on award of the work, shall prepare detailed shop drawings,

    showing the cross-section, longitudinal sections, details of fittings,

    locations of isolating and control valves, drain and air valves, and all pipe

    supports. He must keep in view the specific openings in the building

    through which pipes are designed to pass.

    Pipe shall be cut only with hack saw blades and welding rods shall not beused for this purpose. All the pipes shall be cleaned and applied with one coat

    of Zinc chromate primer.

    b. Piping shall be properly supported on, or suspended from, stands, clamps,

    hangers as specified and as required. The Contractor shall adequately design

    all the brackets, saddles, anchors, clamps and hangers and be responsible

    for their structural sufficiency.

    c. Pipe supports shall be of steel, adjustable for height and Zinc chromate

    primer coated and finish coated black. Where pipe and clamps are of

    dissimilar materials, a gasket shall be provided in between. Spacing of pipe

    supports shall not exceed the following :

    ___________________________________________________________

    Pipe size Spacing between supports

    Rod Size

    ___________________________________________________________

    Upto 12 mm 1.5 Meter 8 mm

  • 8/7/2019 Tender Specification for HVAC matreial.

    9/17

    15 to 25 mm 2.0 meter 8 mm

    d. Bull heading in water/refrigerant piping shall be avoided.

    e. Pipe sleeves at least 3 mm thick, 50 mm / 100 mm larger in diameter than

    condenser / ref. (with insulation) pipes respectively shall be provided

    wherever pipes pass through retaining wall and slab. Annular space shall

    be filled with fiberglass and finished with retainer rings welded on the ends

    of the sleeve.

    f. Wherever pipes pass through the brick or masonry / slab openings, the gaps

    shall be sealed with fire sealant such as fire barrier caulks.

    g. All piping work shall be carried out in a workmen like manner, causing

    minimum disturbance to the existing services, buildings and structure.

    The entire piping work shall be organized, in consultation with other

    agencies work, so that laying of pipes, supports, and pressure testing for

    each area shall be carried out in one stretch.

    h. Cut-outs in the floor slabs for installing the various pipes are indicated in

    the Drawings. Contractor shall carefully examine the cut-outs provided and

    clearly point out where the cut-outs shown in the Drawings do not meet with

    the requirements.

    i. The Contractor shall make sure that the clamps, brackets, clamp saddles

    and hangers provided for pipe supports are adequate.

    j. All pipes shall be accurately cut to the required size in accordance with

    relevant BIS Codes, edges beveled and burrs removed before laying.

    6. AIR DISTRIBUTION

    (FOR DUCTS FABRICATED AT SITE

    AS PER BIS STANDARD)

    6.1 SCOPE

    The scope of this section comprises supply fabrication installation and testing

    of all sheet metal / flexible ducts, supply installation testing and balancing of all

    dampers, and registers, in accordance with these specifications and the general

    arrangement shown on the Drawings.

    6.2 DUCT MATERIALS

    All ducts shall be fabricated from galvanized steel sheets / aluminium sheets of the

    following thickness as indicated in Schedule of Quantities.

    G S S ALUMINIUM

    Rectangular ducts upto 75 cm 24 gage 22 gage

    Rectangular ducts 76 to 150 cm

    and all round ducts. 22 gage 20 gage

    Rectangular ducts 151 to 225 cm 20 gage 18 gage

    Rectangular ducts greater than 225 cm 18 gage 16 gage

    Sheet metal ducts shall be fabricated out of galvanized steel sheets. Fabrication of

    ducts shall be through well conditioned Triplex lock former or multiple lock

  • 8/7/2019 Tender Specification for HVAC matreial.

    10/17

    formers, conforming to relevant BIS Codes. Sheets used shall be produced by Hot

    Dip Process .

    6.3 All ducts shall be fabricated and installed in workmanlike manner, generally

    conforming to relevant BIS Codes. Round exposed ducts shall be die-formed for

    achieving perfect circle configuration.

    6.3.1 a. Ducts shall be straight and smooth on the inside with neatly finished

    joints. All joints shall be made air tight.

    b. Changes in dimensions and shape of ducts shall be gradual. Air-turns

    (Vanes) shall be installed in all bends and duct collars designed to permit

    the air to make the turn without appreciable turbulence.

    c. Ducts shall be fabricated as per details shown on Drawings. All ducts

    shall be rigid and shall be adequately supported and braced where

    required with standing seams, tees, or angles, of ample size to keep the

    ducts true to shape and to prevent buckling, vibration or breathing.

    d. Self adhesive rubber lining minimum 5 mm thick instead of felt, shall beused between duct flanges and between duct and duct supports in all

    ducting installation.

    6.4 All ducts shall be installed generally as per tender Drawings, and in strict

    accordance with approved shop drawings to be prepared by the Contractor.

    a. The Contractor shall provide and neatly erect all sheet metal work as may

    be required to carry out the intent of these Specifications and Drawings . The

    work shall meet with the approval of Owners site representative in all its

    parts and details.

    b. All necessary allowances and provisions shall be made by the Contractor forbeams, pipes, or other obstructions in the building, whether or not the same

    are shown on the Drawings. Where necessary to avoid beams or other

    structural work, plumbing or other pipes, and conduits, the ducts shall be

    transformed, divided or curved to one side (the required area being

    maintained) all as per the site requirements.

    c. If a duct cannot be run as shown on the Drawings, the Contractor shall

    install the duct between the required points by any path available, in

    accordance with other services and as per approval of Owners site

    representative.

    d. All duct work shall be independently supported from buildingconstruction. All horizontal ducts shall be rigidly and securely supported,

    in an approved manner, with trapeze hangers formed of galvanized steel

    rods and galvanized steel angle/channel under ducts at no greater than 2

    meter centre.

    e. Ducting over furred ceiling shall be supported from the slab above, or from

    trusses, after obtaining approval of Owners site representative. In no case

    shall any duct be supported from false ceiling hangers or be permitted to

    rest on false ceiling. All metal work in dead or furred down spaces shall be

    erected in time to occasion no delay to other Contractors work in the

    building.

    f. Where ducts pass through brick or masonry openings, it shall be provided

    with 25 mm thickTF quality expanded polystyrene around the duct and

    totally covered with fire sealant such as fire barrier mortar for complete

    sealing.

  • 8/7/2019 Tender Specification for HVAC matreial.

    11/17

    g. All ducts shall be totally free from vibration under all conditions of

    operation. Whenever duct work is connected to fans, air handling units or

    blower coil units that may cause vibration in the ducts, ducts shall be

    provided with a flexible connection, located at the unit discharge. Flexible

    connections shall be constructed of flame retardant, water proof, silicon

    rubber impregnated flexible connection atleast 10 cm long securely bonded

    and flange bolted on both sides. Sleeve shall be made smooth and the

    connecting duct work rigidly held by independent supports on both sides

    of the flexible connection. The flexible connection shall be suitable for

    pressure at the point of installation.

    6.5 DAMPERS

    a. Dampers : All duct dampers shall be opposed blade louver dampers of

    robust 16 G GSS construction and tight fitting. The design, method of

    handling and control shall be suitable for the location and service

    required.

    b. Dampers shall be provided with suitable links levers and quadrants as

    required for their proper operation. Control or setting device shall be maderobust, easily operable and accessible through suitable access door in the

    duct. Every damper shall have an indicating device clearly showing the

    damper position at all times.

    c. Dampers shall be placed in ducts at every branch supply or return air duct

    connection, whether or not indicated on the Drawings, for the proper

    volume control and balancing of the air distribution system.

    6.6 MEASUREMENTS FOR DUCTING

    Unless otherwise specified, measurements for ducting for the project shall be on the

    basis of centre-line measurements described herewith :

    a. Duct Work shall be measured on the basis of external surface area of

    ducts. Duct measurements shall be taken before application of the

    insulation. The external surface area shall be calculated by

    measuring the perimeter comprising overall width and depth, including the

    corner joints, in the centre of each duct section, multiplying with the overall

    length from flange face to flange face of each duct section and adding up

    areas of all duct sections. Plenums shall also be measured in similar manner.

    For tapered rectangular ducts, the average width and depth shall be considered

    for perimeter, whereas for tapered circular ducts, the diameter of the

    section midway between large and small diameter shall be adopted, thelength of tapered duct section shall be the centre line distance between the

    flanges of the duct section.

    For special pieces like bends, tees, reducers, branches and collars, mode of

    measurement shall be identical to that described above using the length

    along the centre line.

    The quoted unit rate for external surface of ducts shall include all wastage

    allowances, flanges and gaskets for joints, nuts and bolts, hangers and

    angles with double nuts for supports, rubber strip 3 mm thick between duct

    and support, vibration isolator suspension where specified or required,

    inspection chamber / access panel, splitter damper with quadrant and lever

    for position indication, turning vanes, straightening vanes, and all other

    accessories required to complete the duct installation as per the

    Specifications. These accessories shall NOT be separately measured nor paid

    for.

  • 8/7/2019 Tender Specification for HVAC matreial.

    12/17

    b. Special Items for Air Distribution shall be measured by the cross-section

    area perpendicular to air flow, as identified herewith :

    i. Fire dampers - shall be measured by their cross sectional area

    perpendicular to the direction of air flow. Quoted rates shall include

    the necessary collars and flanges for mounting, inspection pieces

    with access door, electrical actuators and panel. No special

    allowance shall be payable for extension of cross section outside the

    air stream.

    ii. Flexible connection - shall be measured by their cross sectional

    area perpendicular to the direction of air flow. Quoted rates shall

    include the necessary mounting arrangement, flanges, nuts and

    bolts and treated-for-fire requisite length of canvas cloth.

    6.7 TESTING AND BALANCING

    After the installation of the entire air distribution system is completed in all respects,

    all ducts shall be tested for air leaks by visual inspection.

    The entire air distribution system shall be balanced using an anemometer. Measured

    air quantities at fan discharge and at various outlets shall be identical to or

    less/excess than 5 percent in excess of those specified and quoted. Branch duct

    adjustments shall be permanently marked after air balancing is completed so that

    these can be restored to their correct position if disturbed at any time. Complete

    air balance report shall be submitted for scrutiny and approval, and four copies of theapproved balance report shall be provided with completion documents.

    7. INSULATION

    7.1 SCOPE

    The scope of this section comprises the supply and application of insulation

    conforming to these specifications.

    7.2 MATERIAL

    Thermal insulation material for Duct & Pipe insulation shall be closed cell

    Elastomeric Nitrile Rubber of Thermal conductivity of the insulation material shall

    not exceed 0.038 W/moK or 0.212 BTU / (Hr-ft2-oF/inch) at an average temperature

    of 30oC. Density of the nitrile rubber shall be 40-60 Kg/m3. The product shall have

    temperature range of 40 oC to 105oC. The insulation material shall be fire rated for

    Class 0 as per BS 476 Part 6 : 1989 for fire propagation test and for Class 1 as per BS

    476 Part 7, 1987 for surface spread of flame test. Water vapour permeability shall be

    not less than 0.024 perm inch (2.48 x 10-14 Kg/m.s.Pa i.e. >7000: Water vapour

    diffusion resistance).

    7.3 PIPING INSULATION

    All refrigerant, and condensate drain piping shall be insulated in the manner

    specified herein. Split units refrigerant piping insulation thickness shall be strictly as

    per manufacturers recommendations. Before applying insulation, all pipe shall be

    brushed and cleaned. Insulating material in tube form shall be sleeved on the pipes.

    On piping, slit opened tube from insulating material shall be placed over the pipe and

    adhesive shall be applied as suggested by the manufacturer. Adhesive must be

  • 8/7/2019 Tender Specification for HVAC matreial.

    13/17

    allowed to tack dry and then press surface firmly together starting from butt end and

    working towards centre. Wherever flat sheets shall be used it shall be cut out in

    correct dimension using correct tools. Scissors or Hacksaw-blade shall not be

    allowed. All longitudinal and transverse joints shall be sealed as per manufacturer

    recommendations. The adhesive shall be strictly as recommended by the

    manufacturer. The insulation shall be continuous over the entire run of piping, fittings

    and valves. Manufacturers installation manual shall be submitted and followed for

    full compliance. All insulation work shall be carried out by skilled workmen

    specially trained in this kind of work. .

    7.4 PROTECTIVE COATING OVER INSULATION

    To provide mechanical strength and protection from damage all pipe / duct insulated

    with nitrile rubber as indicated in BOQ shall be covered with fibreglass fabric of 7

    mil minimum thickness or self adhesive fibre glass cloth of 7 mil. thickness.

    7.5 UNDERDECK INSULATION

    Underdeck insulation shall be 50mm thick TF Quality expanded polystyrene (32

    Kg/m

    3

    ) or 30mm thick phenotherm. Underdeck surface of ceiling shall be cleanedand made dirt free. Insulation panels shall be pasted on this surface with black CPRX

    compound. 28g wire net shall be tightened around insulation so as to avoid any kind

    of sagging. Ends of net shall be overlapping by at least 25mm. Overlaps shall be

    screwed with galvanized screws to avoid rusting.

  • 8/7/2019 Tender Specification for HVAC matreial.

    14/17

    COOLING TEST REPORT (SPLIT UNITS)

    PROJECT

    __________________________________________________________________________________

    COIL DATA COIL NO. COIL NO. COIL NO. COIL NO.

    System Number

    Location

    Coil Type

    No. Rows Fins/In

    Manufacturer

    Model Number

    Face Area, Sq.Ft.

    TEST DATA DESIG

    N

    ACTUA

    L

    DESIG

    N

    ACTUA

    L

    DESIG

    N

    ACTU

    AL

    DESIG

    N

    ACTUA

    L

    Air Qty. CFM

    Air Vel.FPM

    Press.Drop In.

    Out.Air DB/WB

    Ret. Air DB/WB

    Ent.Air DB/WB

    Lvg.Air DB/WB

    Air AT

    Waer flow.

    GPM

    Press.Drop.PSI

    Ent.Water Temp

    Lvg .Water

    Temp

    REF. AT

    Exp.Valve/Refrig

    Refrig.Suction

    Pr.

    Refrig.Suct.Tem

    p

    Inlet Steam

    press.

    REMARKS.

    TEST DATE ________________________________ READINGS BY

    ___________________________

  • 8/7/2019 Tender Specification for HVAC matreial.

    15/17

    FAN TEST REPORT

    PROJECT_________________________________________________________________________

    FAN DATA FAN NO. FAN NO. FAN NO.

    Location

    Service

    Manufacturer

    Model No.

    Serial No.

    Type / Class

    Motor Make / Style

    Motor H.P/RPM/ Frame

    Volts/Phase/Cycles

    F.L Amps.

    Motor pully Diam./Bore

    Fan pully Diam./Bore

    No. Belts/ Make/Size

    Pully Distance.

    TEST DATA DESIG

    N

    ACTUA

    L

    DESIG

    N

    ACTUA

    L

    DESIG

    N

    ACTUA

    L

    CFM

    FAN RPM

    S.P IN/OUT

    TOTAL S.P

    Voltage T1T

    2T

    2T

    3T

    3T

    1

    Amperage T1 T2 T3

    REMARKS:

    TEST DATE:_________________________________ READINGS BY

    _____________________

  • 8/7/2019 Tender Specification for HVAC matreial.

    16/17

    PPENDIX - II

    LIST OF APPROVED MAKES FOR EQUIPMENT & MATERIALS

    (As Listed Alphabetically)

    S.No. Details of Materials / EquipmentManufacturers Name

    1. Split Units / Package Unit Blue Star

    Carrier (only Split AC unit)

    ETA

    Voltas

    2. Centrifugal Fan Chaysol

    Comefri

    Kruger

    ebm-Nadi

    Nicotra

    3. Axial Flow Fan Kruger

    Nuaire

    Systemair

    ebm-Nadi

    Nicotra

    4.. Inline / Propeller Fan / Roof extractor

    Fan

    Chaysol

    Nuaire

    Systemair

    Alstom

    ebm-Nadi

    5. GI Sheet ESSAR

    Jindal

    SAIL

    TATA

    Lloyd

    6. Smoke / Fire/ Volume

    control Damper

    Gryfit

    Ruskin

    Airmaster

    Caryaire

    Conaire

    George RaoRavistar

    7. Anchor Fastener Fischer

    Hilti

    SHAKTI

    8 Thermal Insulation:

    Closed Cell Elastomeric nitrile rubber

    along with adhesive

    Armacell - Armaflex

    K-Flex

    A-Flex

    S.No. Details of Materials / EquipmentManufacturers Name

    9. Acoustic insulation:

    Fibre glass

    Owens Corning

    UP Twiga

  • 8/7/2019 Tender Specification for HVAC matreial.

    17/17

    10. Expanded Polystyrene (TF Quality) Beardsell

    Coolite

    DEBS Products

    Styrene Packaging

    Tosiba

    11. Protective Coating over Closed Cell

    Elastomeric Fibreglass Woven Cloth

    Armacell Armachek

    Paramount

    UP Twiga

    12. Fire Sealant BTHM Engineering

    Birla 3 M

    Hilti

    Promat