TECHNICAL SUBMITTAL

FOR

LIGHTING FIXTURES

Page 3: Technical Submittal for Lighting Fixtures

8/12/2019 Technical Submittal for Lighting Fixtures

http://slidepdf.com/reader/full/technical-submittal-for-lighting-fixtures 3/15

 

L IST OF MATERIALS

Sn DESCRIPTION AREA USED CAT. NO. MAKE

1. Fluorescent battenfitting of slim cross-section, T8 - 2 x36W, switch start,with clip-on coverplate and adjustableend cap system withreflector.

Substation,Indoor GeneralLighting

PP236 +PPRE24

 Thorn-UK

2. Fluorescent battenemergency fitting ofslim cross-section, T8 - 2 x 36W, switchstart, with 3 hoursback-up power from

self containedbattery with charger.Clip-on cover plateand adjustable endcap system withreflector.

Substation,IndoorEmergencyLighting

E3PP236+ PPRE24

 Thorn-UK

3. Fluorescent battenfitting of slim cross-section, T8 - 2 x18W, switch start,with clip-on coverplate and adjustableend cap system.

Substation,Indoor GeneralLighting (AirLock area)

PP218 Thorn-UK

4. Fluorescent battenfitting of slim cross-section, T8 - 1 x36W, switch start,

with clip-on coverplate and adjustable

Fire Fighting GasCylinder Room

PP136 +PPRE24

 Thorn-UK

Page 4: Technical Submittal for Lighting Fixtures

8/12/2019 Technical Submittal for Lighting Fixtures

http://slidepdf.com/reader/full/technical-submittal-for-lighting-fixtures 4/15

 

end cap system withreflector.

5. EEX ed, ATEX Cat 2Gas group IICcertified,polycarbonate L alloybodied fluorescentfitting withpolycarbonate coverand rapid fix flexible

installation channel. T8 – 2 x 36W, HFElectroniccontrolgear.

Battery Room P9236/HF

 Thorn-UK

6. Cast Aluminumbulkhead lampfitting with mouldedglass cover fordischarge lamps.IP65 protection.

HPS-E 70W HighPressure SodiumLamp with IntegralGear.

SubstationExternal Lighting(Mounted onexterior walls ofSubstation)

DB70 Thorn-UK

7. Enclosed Floodlightwith black aluminumbody and frame,housing flat glass.Integral controlgear

and assymetricalreflector for 100WHPS-T lamp.

SubstationExternal Lighting – TransformerArea (Mountedon exterior walls

of Substation)

SONPAK7/15OT100T.4

 Thorn-UK

8. Self contained singlesided exit sign with8W fluorescent lampfor non-maintainedemergency lightingfor 3 hour duration.

Substation ExitSign on Doors.

EFX3-NM Thorn-UK

Page 5: Technical Submittal for Lighting Fixtures

8/12/2019 Technical Submittal for Lighting Fixtures

http://slidepdf.com/reader/full/technical-submittal-for-lighting-fixtures 5/15

 

INDOOR

LIGHTING FIXTURES

Page 6: Technical Submittal for Lighting Fixtures

8/12/2019 Technical Submittal for Lighting Fixtures

http://slidepdf.com/reader/full/technical-submittal-for-lighting-fixtures 6/15

 www.thornlighting.co.uk 90

Popular Range Battens1:10

The only one called ‘Pop Pack’,the original fluorescent batten.

• 5 year guarantee* on‘Super Pack’ versions

• ‘Super Pack’ versions suppliedwith HF ballast and Tri-Phosphorlamp for maximum economicoperation and minimummaintenance

• No conversions - standardrange includes maintainedemergency versions. Battens,louvre and reflector

attachments are suitable foremergency lighting.

• Adjustable twin lampholderprovides uniform light inlow ceiling installations ordownward light in highmounting positions

• Tool-less clip-on cover platefor quick installation

• Dimmable Digital Controliteversions allow dimming downto 1% lamp power

• Single and Twin body in 5lengths from 600mm to2400mm (2ft – 8ft)

• High frequency electronic orswitch start wire wound gear

• A range of diffusers andreflectors covering everyapplication requirement

• Can be surface orsuspension mounted

•Twist-lock lampholders forreliable electrical contact

• Slim spine with durable,corrosion resistant finish

* Conditions apply

Materials/FinishBatten: Rolled steel section inpre-coated high reflectivitywhite paint.Lampholder assembly:Tough white polycarbonate.

Twin ( lampholder narrow posit ion) Twin ( lampholder wide posi tion)

81

82 125

64

Single 

82

60

42

18W, 36W, 58W, 70W, 100W Standard T8 (3500K) G13 Super Pack T8 835 (3500K) G13

EN 60598, (Emergency EN 60598 2.22) SLL LG3 65°, 500cd/m2 for VDT insert louvres (1000cd/m2 for single Architectural Up/Downlight louvre - 2 x 36W is 1500cd/m2)

Page 7: Technical Submittal for Lighting Fixtures

8/12/2019 Technical Submittal for Lighting Fixtures

http://slidepdf.com/reader/full/technical-submittal-for-lighting-fixtures 7/15

 www.thornlighting.co.uk  91

Ordering Guide Supplied complete with lamp(s), (switchstart 3500Kstandard white, high frequency 835), unless otherwise stated. To ordera complete luminaire quote required batten and correspondingattachment catalogue number(s).

Lamp type Overall Weight Cat. No. Emergency version Cat. No.& rating Length (kg) Weight (kg)

(mm)

Super Pack - High Frequency Electronic BallastT8 1 x 36W 1223 1.90 PPZXL136* 2.75 E3 PZXL136*T8 2 x 36W 1223 2.10 PPZXL236* 2.95 E3 PZXL236*T8 1 x 58W 1523 2.05 PPZXL158* 3.05 E3 PZXL158*T8 2 x 58W 1523 2.25 PPZXL258* 3.30 E3 PZXL258*T8 1 x 70W 1787 2.30 PPZXL170* 3.45 E3 PZXL170*T8 2 x 70W 1787 2.50 PPZXL270* 3.65 E3 PZXL270*

SwitchstartT8 1 x 18W 613 1.80 PP118T8 2 x 18W 613 2.16 PP218T8 1 x 36W 1223 2.60 PP136 3.45 E3 PP136T8 2 x 36W 1223 4.10 PP236 4.85 E3 PP236T8 1 x 58W 1523 3.40 PP158 4.40 E3 PP158T8 2 x 58W 1523 5.45 PP258 6.25 E3 PP258T8 1 x 70W 1787 3.70 PP170 4.85 E3 PP170T8 2 x 70W 1787 6.12 PP270 7.25 E3 PP270T8 1 x 100W 2398 5.23 PP1100T8 2 x 100W 2398 7.95 PP2100

Controlite Digital Dimming Versions (Lamps to be ordered separately).T8 1 x 36W 1223 2.10 PP136CLDLL 2.95 E3PP136CLDLLT8 2 x 36W 1223 2.30 PP236CLDLL 3.15 E3PP236CLDLLT8 1 x 58W 1523 2.35 PP158CLDLL 3.35 E3PP158CLDLLT8 2 x 58W 1523 2.55 PP258CLDLL 3.55 E3PP258CLDLL

* With 835 (3500K) lamp.

100

50

150

30°

60°

90°

30°

90°

120° 180°

120°

60°

cd/1000 lm

TA

Cat. No. PP258 (Narrow Position)ULOR: 0.30 DLOR: 0.64 LOR: 0.94 LMC: A

Utilisation factors UF (F)

Mounting: Ceiling

Reflectances Room IndexC W F 1.0 2.0 3.0 4.0 5.0

0.8 0.6 0.2 0.61 0.78 0.85 0.89 0.920.5 0.56 0.73 0.82 0.86 0.890.3 0.48 0.67 0.76 0.81 0.85

0.7 0.6 0.2 0.57 0.73 0.80 0.84 0.860.5 0.53 0.69 0.77 0.81 0.840.3 0.46 0.63 0.72 0.77 0.80

0.5 0.6 0.2 0.51 0.65 0.71 0.74 0.760.5 0.48 0.62 0.69 0.72 0.750.3 0.42 0.57 0.64 0.69 0.72

Cat. No. E3PPZXL258 (Narrow Position)

2m Escape route

Min illum M ounting Max spacing (m)

( lux ) he ig ht (m) ce nt re to en d b et wee n c en tr es

2.5 3.25 9.101.0 trans 3.0 3.25 9.20

3.5 3.15 9.30

2.5 2.70 7.001.0 axial 3.0 2.70 7.40

3.5 2.65 7.60

Open area

Min Mounting Max spacing (m)

illum height centre to end between centres

(lux) (m) Trans Axial Trans Axial

2.5 2.95 2.95 9.80 8.800.5 3.0 3.05 3.05 10.30 9.503.5 3.10 3.10 10.80 10.00

Installation/MountingFour-way terminal block withcapacity for 2 x 2.5mm2 cables.Angled terminal block foreasy wiring.Ambient temperature: Switchstart-5°C to 25°C, High frequencyelectronic -15°C to 25°C.Normal, dry, indoor atmospheres.Fixings via three BESA piercings,one central and two at fixingcentres: 600mm - 500mm,1200/1500/1800mm - 600mm,2400mm - 1200mm (HF electronicversions have no central fixing.)Bare battens can be mountedend-to-end (except emergencyversions - recommended minimumspace between luminaires 50mm).Emergency fixing centres:E3PP158/E3PP170 - 600mm,E3PP136/E3PP236/E3PPZXL13/E3PPZXL236 - 1110mmE3PP258/E3PP270/E3PPZXL15/E3PPZXL258/E3PPZXL170/E3PPZXL270 - 1410mm.

SpecificationTo specify state:Fluorescent batten fitting of slim

cross-section with clip-on coverplate and adjustable endcap system.As Thorn Popular Pack Batten.

Popular Range Batten with Architectural Up/Downlight Attachment 

I   ND  O OR  C  O M ME R  C I  A L  

F L   U  OR E  S  C E  N

T B A T T E  N S  & 

 S Y  S T E  M S 

Page 8: Technical Submittal for Lighting Fixtures

8/12/2019 Technical Submittal for Lighting Fixtures

http://slidepdf.com/reader/full/technical-submittal-for-lighting-fixtures 8/15

 www.thornlighting.co.uk  93

Popular Range Reflectors 4:10

Choice of Economy, Asymmetricand Rack reflectors for use withPopular Battens.

Economy Reflectors

• For cost conscious schemes

• Narrow reflector for lowest cost

• Wide reflector for highestlight output

• Wire guard available• Continuous end to end

mounting possible (exceptemergency versions and wireguard) 50mm spacingminimum recommended

Materials/FinishReflectors: Steel with precoathigh reflectivity white finishWire guards: Steel, brightZinc plated

Specification

To specify state:Open-ended, trough reflector inwhite stove enamelled steel withoptional wire guard (PP/PT GE).As Thorn Popular Range MetalReflector (PPR).

Ordering Guide

Description Cat. No. Optional wire guardfor reflector Cat. No.

Economy reflector - nar row - for 1 & 2 x 36W PPRE 4 PP/PT GE 4Economy reflector - nar row - for 1 & 2 x 58W PPRE 5 PP/PT GE 5Economy reflector - nar row - for 1 & 2 x 70W PPRE 6 PP/PT GE 6Economy reflector - narrow - for 1 x 100W PPRE 8 PP/PT GE 8Economy reflector - wide - for 1 & 2 x 36W PPRE 24 PP/PT GE 24Economy reflector - wide - for 1 & 2 x 58W PPRE 25 PP/PT GE 25Economy reflector - wide - for 1 & 2 x 70W PPRE 26 PP/PT GE 26

Economy reflector - wide - for 1 & 2 x 100W PPRE 28 PP/PT GE 28Rack reflector for 1 & 2 x 58W PPRL 5Rack reflector for 1 & 2 x 70W PPRL 6Asymmetrical reflector for 1 & 2 x 36W PPA 4Asymmetrical reflector for 1 & 2 x 58W PPA 5Asymmetrical reflector for 1 & 2 x 70W PPA 6

Narrow economy reflector Wide economy reflector with wire guard  

121

92.5 92.5

167.5

51

287

199

121

92.5

Narrow reflector (lampholder narrow position)

Narrow reflector 

Wide reflector (lampholder narrow position) Rack lighting

79

133

Asymmetrical metal reflector single 

133

110

Asymmetrical metal reflector twin

Rack Lighting Reflector

• For use where verticalillumination is required innarrow aisle racking

• Continuous end to endmounting possible (except

emergency versions)

SpecificationTo specify state:Rack lighting reflector in highreflectivity polished aluminium.As Thorn Popular Range RackLighting Reflector (PPRL).

 Asymmetrical MetalReflector

• For use where wall washinglight is required

• Twin batten offers alternativelumen distribution with

adjustable lampholder

SpecificationTo specify state:Single side angled reflector inwhite stove enamelled steel.As Thorn Popular Range AngledMetal Reflector (PPA).

Rack lighting reflector Asymmetrical metal reflector  

I   ND  O OR  C  O M ME R  C I  A L  

F L   U  OR E  S  C E  N

T B A T T E  N S  & 

 S Y  S T E  M S 

Page 9: Technical Submittal for Lighting Fixtures

8/12/2019 Technical Submittal for Lighting Fixtures

http://slidepdf.com/reader/full/technical-submittal-for-lighting-fixtures 9/15

 

EXPLOSION PROOF

LIGHTING FIXTURES

Page 10: Technical Submittal for Lighting Fixtures

8/12/2019 Technical Submittal for Lighting Fixtures

http://slidepdf.com/reader/full/technical-submittal-for-lighting-fixtures 10/15

 www.thornlighting.co.uk  307

18W, 36W, 58W T8 G13 For Standards see below

Petrelux 9 1:1

Standards

Zone: ATEX Cat 2 (can also be used in Cat 3)

Zone 1 (can also be used in Zone 2)

Gas Groups: 11C

T Rating: T4

Voltage: 220/240V, 50/60Hz

IP Rating: IP66

Certification Code: EEx ed 11C T4 - T5

Certification Standard: EN50014, 50018 and 50019

Approval Authority: SIRA

Certification Number: 00 ATEX 3071

Certification Detail: T4 @ Ta = 40°C 11C

T5 @ Ta = 25°C 11C

A Zone 1, ATEX Category 2certified increased safety EEx edlinear fluorescent luminaire forsurface or suspended mounting.

• High light output ratio

• Simple lamp changemechanism

• Fast fix installation via flexiblefixing channel with T bolts

• Integral high frequencyelectronic ballast

• Lightweight

• Integral emergency lighting(3hr duration of one lamp)versions available as standard

Materials/FinishBody: AA 25 anodised corrosionresistant alloy andpolycarbonate, finished inPetrelux Green.Enclosure: High output, U.V.stabilised and shock resistantpolycarbonate.

Installation/MountingUnique quick fixing T bolts onadjustable centres with optional

mounting accessory kits.Cable entry: 2 x M20 eachend as standard.Terminals: 3 wire and earthfor 4mm2 suitable for looping.

SpecificationTo specify state:EEx ed, ATEX Cat 2 certifiedpolycarbonate /alloy bodied/emergency/ fluorescent fittingwith polycarbonate cover andrapid-fix flexible installationchannel. IP66 sealing via multi-point locking mechanism. As Thorn

Petrelux 9/ Petrelux 9 Emergency.

Ordering Guide Lamps to be ordered separately.

Lamp type Control Weight Cat. No. Weight Emergency  and rating gear (kg) (kg) Cat. No.

T8 600mm 2 x 18W HF Electronic 5.7 P9218/HF 6.9 P9218/HF/EMT8 1200mm 2 x 36W HF Electronic 9.2 P9236/HF 10.4 P9236/HF/EMT8 1500mm 2 x 58W HF Electronic 10.5 P9258/HF 12.0 P9258/HF/EM

 Attachments

Description Cat. No.Fixing bracket (wall/ceiling) P9/GWPole Clamp mounting - for 40mm Ø pole P9/PC40Eye bolt suspension P9/PMFixing bracket - adjustable P9/ADJ

B 192A

142

Dim A max Dim B o/afixing centres length

2 x 18W 450 7652 x 36W 1060 13752 x 58W 1260 1675

50

100

150

60°60°

30° 30°0°

120° 120°

90° 90°

cd/1000 lm

T

A

Cat. No. P9218/HFLamp: 2 x 600 18W 26øULOR: 0.04 DLOR: 0.56 LOR: 0.60 SHR max: 1.67 LMC: E

Utilisation factors UF (F)

Reflectances Room IndexC W F 1.0 2.0 3.0 4.0 5.0

0.8 0.6 0.2 0.42 0.54 0.58 0.61 0.630.5 0.39 0.51 0.56 0.59 0.610.3 0.34 0.47 0.53 0.56 0.59

0.7 0.6 0.2 0.41 0.52 0.57 0.59 0.610.5 0.38 0.50 0.55 0.58 0.590.3 0.33 0.46 0.52 0.55 0.57

0.5 0.6 0.2 0.39 0.49 0.53 0.56 0.570.5 0.36 0.47 0.52 0.55 0.560.3 0.32 0.44 0.49 0.52 0.54

I   ND  U  S T R I  A L  

P R  O OF | 

H A 

Z A R D  O U  S A R E A 

L   U  MI   NA I  R E  S 

Page 11: Technical Submittal for Lighting Fixtures

8/12/2019 Technical Submittal for Lighting Fixtures

http://slidepdf.com/reader/full/technical-submittal-for-lighting-fixtures 11/15

 

OUTDOOR

LIGHTING FIXTURES

Page 12: Technical Submittal for Lighting Fixtures

8/12/2019 Technical Submittal for Lighting Fixtures

http://slidepdf.com/reader/full/technical-submittal-for-lighting-fixtures 12/15

 www.thornlighting.co.uk 300

DB Bulkhead1:1

70W HPS-E E27 150W, 200W GLS E27 220/240V, 50Hz IP65 EN 60598

A tough bulkhead fordischarge or tungsten lampsfor use in non-hazardous areas.

• Ideal for localised lighting

• Robust cast aluminium bodyand glass bowl resist impactand corrosion

• Wire guard option foradded protection

Materials/FinishBody: Pressure die castLM6 aluminium finishedhammer grey.Bowl: Moulded borosilicateprismatic glass in hingedaluminium frame retained byfour stainless steel Allen screws.

Reflector/gear tray: Whitepainted steel.

Installation/Mounting

Direct ceiling or wall mounting.M20 cable entry at each end,one with removable plug forthrough wiring. Suitable for40°C maximum ambientdepending on orientation.

SpecificationTo specify state:Cast aluminium bulkhead withmoulded glass cover fordischarge/tungsten lamps.IP65 protection.As Thorn DB Bulkhead.

296 fxg crs

314

192

170105

fxg crs

Cat. No. DB70Lamp: 70W HPS-EULOR: 0.10 DLOR: 0.69 LOR: 0.79 SHR max: 1.92 LMC: E

50

100

150

90°

30°30° 0°

60°60°

90°

cd/1000 lm

AT

Utilisation factors UF (F)

Reflectances Room IndexC W F 1.0 2.0 3.0 4.0 5.0

0.8 0.6 0.2 0.49 0.64 0.71 0.75 0.780.5 0.44 0.60 0.68 0.72 0.750.3 0.37 0.53 0.62 0.67 0.70

0.7 0.6 0.2 0.47 0.61 0.68 0.72 0.750.5 0.43 0.58 0.65 0.69 0.720.3 0.36 0.51 0.59 0.65 0.68

0.5 0.6 0.2 0.44 0.57 0.63 0.66 0.690.5 0.40 0.53 0.60 0.64 0.670.3 0.34 0.48 0.56 0.60 0.63

Ordering Guide HPS-E versions supplied complete with lamp,

GLS less lamp.Lamp type Description Weight Cat. No.& rating (kg)

HPS-E 70W Integral gear 6.0 DB70GLS 150/200W ES lamp not supplied 4.3 DB200

Spares and Attachments

Description Cat. No.Glass bowl DBGWire guard DBW

Page 13: Technical Submittal for Lighting Fixtures

8/12/2019 Technical Submittal for Lighting Fixtures

http://slidepdf.com/reader/full/technical-submittal-for-lighting-fixtures 13/15

 www.thornlighting.co.uk  373

Ordering Guide Supplied complete with lamp.

Lamp type Windage Weight Cat. No.& rating (m2) (kg)

HPS-T (external ignitor) 70W 0.105 9.0 OT70T.4HPS-T 100W 0.105 9.0 OT100T.4HPS-T 150W 0.105 9.0 OT150T.4HIT-DE 150W 0.105 9.0 OTMH150D.4

Export voltages available, refer to page 553 for details.

 Attachments

Description Cat. No.Wire guard OTWGBLouvre* OTLBSpill shield for environmentally sensitive areas* OTSSB

Pole clamp for use with 48-89mm Ø poles OHA4613Sonpak single mounting bracket (76mm Ø shaft) QCB F1Sonpak twin stirrup version mounting bracket (76mm Ø shaft) QCB F2Sonpak triple stirrup version mounting bracket (76mm Ø shaft) QCB F3 DELTASonpak 4-way stirrup version mounting bracket (76mm Ø shaft) QCB F4 CROSS

Note that brackets above are suitable for use with QC-TC and QCZR (76mm Ø shaft) columns.*Supplied with 4 screws and washers. These attachments cannot be mounted together,one on the other. See page 372 for attachments.

 O U T D  O OR 

A R E A 

F L   O OD 

L  I   GH T I   N G

Sonpak 7/151:1

Discharge floodlight forgeneral area lighting.

• Choice of high pressure sodiumor double-ended metal halidelamps in a variety of wattages

• Robust die-cast aluminium

body and front frame• Asymmetrical reflector

• Toughened glass front

• Integral control gear

• Spill shield available forreduced glare (see page 372)

• Easy installation with drop downfront glass and cable entry

• Adjustable streamlined stirrupfor flexibility in mounting

• Sealed to IP65

Materials/FinishBody and front frame: Die-castaluminium, painted black,RAL 9005.Reflector: Dimpled anodisedaluminium.Lens: Tempered 4mm flat glasswith stainless steel bolts andsilicone rubber gasket.Stirrup: 3mm mild steel, polyesterpainted black, RAL 9005.

Installation/MountingOne glanded cable entry for9-13mm o/d cable with 3 poleterminal block for up to 10mm2

cables.21mm Ø knockout at rear forthrough wiring.Stirrup fixed by single boltthrough 21mm Ø hole. Twoadditional 11mm  Ø fixing holesat 102mm centres, with a furthertwo 13mm Ø fixing holes at250mm centres.Aiming angle of floodlight aidedby goniometer.

SpecificationTo specify state:Enclosed floodlight with blackaluminium body and frame,housing flat glass. Integral controlgear and asymmetrical reflectorfor 70W/100W/150W HPS-Tor 150W HIT-DE lamp.Sealed to IP65.As Thorn Sonpak 7/15.

127

256

335

115

400 365

192

-90° -60° -30° 0° 30° 60° 90°

900

750

600

450

300

250

0

cd/1000 lm

horizontalvertical

Cat. No. OT150T.4Lamp: 150W HPS-T

70W HPS-T E27 (external ignitor) 100W, 150W HPS-T E40 150W HIT-DE Rx7s

IP65 EN 60598 5 joules 960˚ Hotwire Ta Max: +25˚C

Page 14: Technical Submittal for Lighting Fixtures

8/12/2019 Technical Submittal for Lighting Fixtures

http://slidepdf.com/reader/full/technical-submittal-for-lighting-fixtures 14/15

 

EMERGENCY

LIGHTING FIXTURES

Page 15: Technical Submittal for Lighting Fixtures

8/12/2019 Technical Submittal for Lighting Fixtures

http://slidepdf.com/reader/full/technical-submittal-for-lighting-fixtures 15/15

E  ME R  GE  N  C Y 

L  I   GH T  I   N  G

1:1

 Voyager 8W Single Sided Exit

 C  O M ME R  C I  A L  L  I   GH T  I   N  G

 A simple cei ling or wallmounted emergency exitsign luminaire for generalinterior use.

Key Features

Ceiling or wall mounting options

Choice of white or brass finish

Strong, durable construction

Non-maintained, maintained andsustained options to matchapplication needs

Extensive choice of legend panelsto match scheme style

Lamp Type

8W, T5, white fluorescent,cap: G5

Materials/Finish

Body: Folded steel construction withwhite stove enamelled or brass finish

Electrical Characteristics

Supply voltage: 220/240V

Input current: 50mAFrequency: 50Hz

Ordering GuideSupplied complete with lamp. Legends to be ordered separately.

Lamp type Description Duration Weight Cat. No.& rating (hrs) (kg)

Non-Maintained

T5 8W White 3 2.8 EFX3 NM

T5 8W Brass 3 2.8 EFX3 NM/BR

Maintained

T5 8W White 3 2.8 EFX3

T5 8W Brass 3 2.8 EFX3/BR

Sustained

T5 8W White 3 2.8 EFXS3

T5 8W Brass 3 2.8 EFXS3/BR

 Attachments

Euro Legends Cat. No. Pictograms Cat. No.

EFXF EFXF 7

EFXE 1 EFXF 8

EFXE 2 EFXF 9

EFXE 3 EFXF 10

EFXE 4 EFXF 11

320mmfixingcentres

515mm

60mm

150mm fixing centres

191mm

Installation/Mounting

Ceiling or wall mounting, 20mmBESA provision in back plate or20mm Ø conduit knockout on eitherend. Screw fixings in back face.4 way terminal block,2 x 2.5mm2 capacity.

Standards

Designed and manufactured tocomply with EN 60598 2.22

Ta: -5°C to +25°C

Photometric Data

For signage only.

Specification

To specify state:Self contained single sided exit signwith 8W fluorescent lamp formaintained/non-maintained/sustainedemergency lighting for 3 hourduration. Steel construction.As Thorn EFX3.