CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.566 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11 TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD 1.0 SCOPE The scope of this specification cover design, manufacture, assembly, testing at manufacturer’s works, packing & forwarding to site indoor type 415V, 3 phase 4 wire AC Distribution boards for power distribution to sub-station. 2.0 STANDARDS : The AC Distribution boards offered under this specification shall conform to latest revision of relevant Indian Standard Specification. 3.0 PRINCIPAAL PARAMETERS 3.1 The AC distribution boards shall be sheet steel enclosed self standing suitable for mounting indoors. 3.2 The AC distribution boards covered in this specification shall meet the general technical requirements furnished below, the makes of various components listed at Annexure-I. 4.0 GENERAL TECHNICAL REQUIREMENTS 4.1 Constructional Features 4.1.1 The board shall be sheet steel enclosed, indoor, floor mounted modular, self supporting type made up of the requisite vertical sections. 4.1.2 It shall be dust & vermin proof with a degree of protection of IP-52. 4.1.3 It shall be possible to extend the board on both sides by addition of vertical sections after removing the end covers.

Upload: dangmien

Post on 06-Feb-2018

228 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.566 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

TECHNICAL SPECIFICATIONS FOR

AC DISTRIBUTION BOARD

1.0 SCOPE

The scope of this specification cover design, manufacture, assembly, testing at

manufacturer’s works, packing & forwarding to site indoor type 415V, 3 phase

4 wire AC Distribution boards for power distribution to sub-station.

2.0 STANDARDS :

The AC Distribution boards offered under this specification shall conform to

latest revision of relevant Indian Standard Specification.

3.0 PRINCIPAAL PARAMETERS

3.1 The AC distribution boards shall be sheet steel enclosed self standing suitable

for mounting indoors.

3.2 The AC distribution boards covered in this specification shall meet the general

technical requirements furnished below, the makes of various components

listed at Annexure-I.

4.0 GENERAL TECHNICAL REQUIREMENTS

4.1 Constructional Features

4.1.1 The board shall be sheet steel enclosed, indoor, floor mounted modular, self

supporting type made up of the requisite vertical sections.

4.1.2 It shall be dust & vermin proof with a degree of protection of IP-52.

4.1.3 It shall be possible to extend the board on both sides by addition of vertical

sections after removing the end covers.

Page 2: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.567 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

4.1.4 A metal sill frame made of M.S. channel of 100 x 50 mm ISMC shall be

provided as base frame, properly drilled for mounting the board. Necessary

hardware shall also be provided for the same.

4.1.5 It shall be provided with cable entry at bottom with 3 mm removable gland

plate.

4.1.6 The board shall be of uniform height of not more than 2450 mm and it shall

be of single front execution. It shall be provided with busbars running at top

along the length of the board in separate sheet steel enclosure. The board

shall be provided with gasket all round including removable covers & doors.

All the operating devices shall be provided only on the front of the board.

4.1.7 The height of the top most operating handle shall not be more than 1800 mm

and that of the bottom most operating handle shall not be less than 300mm.

4.1.8 The board shall be divided into distinct sections comprising of

a) metal enclosed busbar compartment running horizontally

b) Individual feeder modules arranged in multitier formation.

c) Enclosed vertical busbars serving all modules.

d) Vertical cable alley covering entire height.

Metal sheet shall be provided between two adjacent vertical sections running

to full height of the board.

4.1.9 All equipment associated with a single circuit shall be housed in a separate

module compartment. The compartment shall be sheet steel enclosed on all

sides and rear. A plate cover with a slot to permit wiring connections shall be

Page 3: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.568 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

provided on the side corresponding to the cable alley. The front of the

compartment shall be provided with hinged door.

4.1.10 Only the handles of switches, push buttons knobs and cutouts for lamps &

meters shall be arranged on front of the respective compartment to permit

operation without opening the door. All cutouts shall be gasketed for dust

proofing.

4.1.11 Cable alley shall be provided with suitable hinged door. Vertical bus bar

compartments shall be provided with adequate shrouding & bolted covers.

4.1.12 Rear of the board shall be provided with removable panels.

4.1.13 All doors shall be provided with concealed type hinges and captive screws.

4.1.14 All identical equipment and corresponding parts of similar ratings shall be

fully interchangeable.

4.2 Sheet Metal Work:

4.2.1 The board frame shall be fabricated using pressed & shaped CRCA sheet

steel of minimum 2.5mm thickness.

4.2.2 The Board shall be enclosed by sheet steel of minimum 2.0 mm thickness

smoothly finished & leveled. Doors & covers shall be made of 1.6 mm thick

sheet steel. Adequate stiffeners shall be provided wherever necessary.

4.2.3 All panel edges and door edges shall be reinforced against distortion. Cut

outs shall be true in shape and devoid of sharp edges.

Page 4: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.569 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

4.2.4 The complete structure shall be rigid, self supporting free from vibration,

twists & bends.

4.3 Painting :

All sheet steel work shall be phosphated in accordance with the following

procedure.

4.3.1 Oil, grease, dirt and swan shall be thoroughly removed by emulsion cleaning.

4.3.2 Rust and scale shall be removed by pickling with dilute acid followed by

washing with running water, rinsing with slightly alkaline hot water and

drying.

4.3.3 After phosphating, through rinsing shall be carried out with clean water,

followed by final rinsing with dilute dichromate solution and over drying.

4.3.4 The panel then powder coated with an approved colour shade as per IS.

4.3.5 The final finished thickness of paint film on steel shall not be less than 50

microns, and shall not be more than 80 microns.

4.3.6 Finished painted appearance of equipment shall present an aesthetically,

pleasing appearance, free from dents and uneven surfaces.

4.4 Main Bus & Taps:

4.4.1 The board shall be provided with three phase and neutral busbars.

4.4.2 Busbars shall be of uniform cross section throughout the length of the board

and up to the incoming terminals of feeder circuit breaker/switch.

Page 5: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.570 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

4.4.3 The busbars shall be made of high conductivity aluminium alloy of E91E

grade.

4.4.4 Busbars shall be adequately supported and braced to withstand the stresses

due to the specified short circuit currents. Busbar supports shall be made of

hylum sheets, glass reinforced moulded plastic material or cast resin.

4.4.5 Separate supports shall be provided for each phase of the busbars. If a

common support is provided for all three phase, antitracking barriers shall be

incorporated.

4.4.6 Busbar joints shall be complete with high tensile steel bolt and washers and

nuts. Busbars shall be thoroughly cleaned at the joint locations and a suitable

contact grease shall be applied just before making a joint.

4.5 Mounted case Circuit Breakers :

4.5.1 Wherever specified moulded case Circuit Breakers shall be provided for

circuit protection. They shall be suitable for over load and short circuit

protection of the feeders.

4.5.2 The circuit breaker shall have switching mechanism, contact system, arc

extinguishing device and a tripping unit contained in a compact moulded case

and cover.

4.5.3 The insulating case and cover shall be made of high strength, heat resistant,

flame retardant material.

Page 6: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.571 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

4.5.4 The MCCB shall be provided with a quick make- quick break type of

switching mechanism which a definite speed of travel of moving contacts is

ensured.

4.5.5 The MCCB shall employ a maintenance free contact system designed to

minimize the let through energies while handing abnormal currents.

4.5.6 An indicator showing ON, OFF and TRIPPED positions shall be provided.

4.6 Air Break Switches :

4.6.1 Air break switches shall be of the heavy duty, group operated load-break,

fault-make type, complying with the requirements of applicable standards.

4.6.2 The switches shall be capable of withstanding the thermal stresses caused by

overloads, and short circuit currents of values associated with protective

relays settings and the let through current of the associated fuse.

4.6.3 The switches shall be capable of withstanding the mechanism stress caused

by the peak short circuit current of value equal to the cut-off current of the

associated fuse.

4.6.4 Whenever solid links are used for the connections between switches and

fuses, such links shall be fitted with insulated sleeves.

4.6.5 All live parts of the switch shall be shrouded.

4.6.6 Switch operating handles shall be suitable for padlocking in `OFF’ position.

4.7 Fuses :

Page 7: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.572 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

4.7.1 Fuses shall be of the HRC cartridge fuse-link type having a certified

rupturing capacity of not less than 80kA at 440V. Fuses up to 630A for

distribution systems of medium short circuit levels may be of HRC cartridge

screw-cap type, having a certified rupturing capacity of not less than 46KA at

440 V and 16KA at 250V DC.

4.7.2 Fuses shall be provided with visible indication to show that they have

operated.

4.7.3 Fuses shall preferably be mounted in moulded plastic carries and shall be

complete with fuse bases.

4.8 Current Transformers :

4.8.1 Current transformers shall be dry type.

4.8.2 Current transformers shall have a short time withstand rating equal to the

short time withstand rating of the associated board for one second.

4.8.3 Rated burden shall be as specified in the single line diagram.

4.8.4 All current transformers shall be earthed through a separate earth link on the

terminal block to permit easy measurement of the current transformers

insulation resistance.

4.9 Indicating Instruments and Meters :

4.9.1 Electrical indicating instruments shall be of minimum 144 sq.mm. size for

incoming feeder and 96 mm size for out going suitable for flush mounting.

Page 8: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.573 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

4.9.2 Indicating instruments shall have provision for zero adjustment outside the

cover.

4.9.3 Instrument dials shall be parallax free with black numerals on a white dial.

4.10 Indicating Lamps

The indicating lamps shall be Cluster LED type having low watt consumption

and shall be provided, translucent lamp cover of appropriate colour. The bulb

& lens shall be easily replaceable from the front.

4.11 Control & Selector Switches :

4.11.1 The control & selector switches shall be adequately rated for the purpose

intended and shall be rotary type. They shall be provided with ascutcheon

plates clearly marked to show the position.

4.11.2 The selector switches shall be maintained contact stayput type. Further

switches in ammeter circuit shall have make before break type contact &

shall be provided with oval handles.

4.12 Push Buttons :

The push buttons shall be of momentary contact push to actuate type rated to

carry 10A at 240V A.C. It shall be fitted with self reset, 2 No. & 2 NC

contacts. It shall be provided with integrate plate marked with its function.

Start, open, close, push buttons shall be green in colour & stop push button

shall be red in colour. All other push buttons shall be black.

4.13 Internal Wiring :

Page 9: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.574 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

4.13.1 Wiring inside the board shall be carried out with 1100/650V grade. PVC

insulated, stranded conductor wires. Minimum size of conductor for power

circuits shall be 4 sq.mm. copper or stranded wires. Control circuits shall be

wired with copper conductor of at least 2.5 sq.mm. for CT circuits & 1.5

sq.mm. for other circuits, the number and size of strands shall be 7 of 0.67

mm and 0.5 mm diameter respectively.

4.13.2 Engraved identification ferrules, marked to correspond with the wiring

diagrams shall be fitted to each wire. Ferrules shall be of yellow colour with

black lettering.

4.13.3 Spare auxiliary contacts of all equipment forming part of the board shall be

wired up to the terminal blocks.

4.13.4 Wiring shall be terminated on preferably stud type terminal blocks such that

the wires are connected by cable-lugs with nuts & washers/lock nuts.

4.14 Terminal Blocks

4.14.1 Terminal blocks (both for power and control circuits) shall be of reputed

make specially for CT and PT circuits. It shall comprise finely threaded pairs

of brass studs of at least 6 mm diameter, links between each pair of studs,

washers, nuts and lock nuts. The studs, shall be accurately locked within the

mounting base to prevent their turning. Insulated barriers shall be provided

between adjacent terminals.

4.14.2 Terminal blocks shall be adequately rated to carry the current of the

associated circuit Minimum rating of the terminal block shall be 10A.

Page 10: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.575 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

4.14.3 Terminals shall be numbered for identification, Engraved white-on-black

labels shall be provided on the terminal blocks, describing the function of the

circuit.

4.14.4 Where duplication of a terminal block is necessary, it shall be achieved by

solid bonding links.

4.14.5 Terminal blocks for CT secondary lead wires shall be provided with shorting

and disconnecting/earthing facilities.

4.15 Labels..

4.15.1 All labels shall comprise white letters on a black background.

4.15.2 Labels shall be made of non-rusting metal or 3 ply lamicoid, or engraved

PVC.

4.15.3 Labels shall be properly fixed, with provision to prevent distortion due to

expansion.

4.15.4 Size of lettering shall be 6 mm., unless otherwise specified for incoming

outgoing feeders.

4.16 Earthing :

4.16.1 Each Board, shall be provided with an earth busbar running along the entire

length of the board. Material and size of the earth busbar shall be as

specified. At either end of the earth bus, one (1) clamp type terminal with

nuts, bolts and earthing conductor shall be provided for bolting Purchaser’s

earthing conductor. In case the earth bus is provided near top of the Board,

Page 11: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.576 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

one down comer at either end shall be provided for connection to the

Owner’s earthing conductor.

4.16.2 Earth busbars shall be supported at suitable intervals.

4.16.3 Positive connection between all the frames of equipment mounted in the

switchboard and earth busbar shall be provided by using insulated copper

wires/bare busbars of cross section equal to that of the busbar.

4.16.4 All instrument and relay cases shall be connected to the earth busbar using

1100/650V grade, 2.5 sq.mm. stranded copper earthing conductor.

__________________ ________________________________ Signature of Tenderer Chief Engineer & General Manager (T)

Date : Date :

Page 12: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.577 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

SPECIFICATIONS FOR EARTHING INSTALLATION

1.0 SCOPE

The intent of this specification is to define the requirements for the supply,

installation, testing and commissioning of the Earthing System.

Note : The bidder shall have to design the earthing system required for the

installation after measuring the soil resistivity & approvals.

2.0 EARTHING CONDUCTOR/ELECTRODE :

The main grid conductor shall be hot dip galvanized G.I. flat or PVC insulated

aluminium conductor/copper conductor. Sizes for main conductors shall be

marked on the drawings. Earth electrodes shall be as per IS standard.

Thickness of hot dip galvanizing shall not be less than 75 microns.

3.0 EARTHING NETWORK:

3.1 The entire earthing installation shall be done in accordance with the earthing

drawings, specifications and the standard drawings of reference attached with

this document. The entire earthing system shall fully comply with the Indian

Electricity Act and rules framed thereunder. The contractor shall carry out any

changes desired by the Electrical Inspector or the owner, in order to make the

installation confirm to the Indian Electricity Rules at no extra cost. The exact

location of earth conductors, earth electrodes and earthing points on the

equipment shall be determined in field, in consultation with the Engineer or his

authorized representative. Any changes in the methods, routing, size of

conductors etc. shall be subject to approval of the Owner/ Engineer before

execution.

Page 13: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.578 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

3.2 Excavation and refilling of earth, necessary for laying underground earth bus

loops shall be the responsibility of the contractor.

3.3 The resistance between the earthing system and the general mass of earth shall

be as per IS code of practice. The earth loop impendence to any point in the

electrical system shall not be in excess of 5.0 ohm, in order to ensure

satisfactory operation of protective devices.

3.4 The main earth loop shall be laid at a depth of 300 mm below grade level.

Wherever cable trenches are available, the earth lead shall be laid in the

trenches and shall be firmly cleated to the walls or run of trays when run in

concrete lines trenches. The earthing strip shall be protected against

mechanical damage.

3.5 In process unit areas, the earthing cable shall be run along cable trays wherever

specified in the layout drawings. The earthing cable shall be suitably cleated

and electrically bonded to the cable tray at regular intervals.

3.6 Joints and tappings in the main earth loop shall be made in such a way that

reliable and good electrical connections are permanently ensured. All joints

below grade shall be welded and suitably protected by giving two coats of

bitumen and covering with hessian tape. All joints above ground shall be by

means of connectors/lugs as far as practicable. Tee connectors shall be used

for tapping, earth leads from the main earth loop wherever it is installed above

ground. Where aluminium cable risers are to be connected to the underground

GI earth bus, the aluminium cable riser shall be taken to the nearest earth pit

and terminated through a bolted joint. If this is not practicable then a G.I. risers

shall be brought above grade and a bolted joint shall be made between this GI

Page 14: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.579 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

riser shall be protected applying two coats of bituminous paint/bitumen on the

exposed portion.

3.7 Conduits in which cables have been installed shall be effectively bonded and

earthed. Cable armoured shall be earthed at both ends.

4.0 EARTHING ELECTRODES:

4.1 Earth pipe electrodes shall be installed as shown in the earthing layout

drawings and in accordance with the standard drawings of reference and

IS:3043. Their location shall be marked to enable accurate location by

permanent markers.

4.2 All earth electrodes shall preferably be driven to a sufficient depth to reach

permanently moist soil. Electrodes shall preferably be situated in a soil which

has a fine texture and which is packed by watering and ramming as lightly as

possible. Wherever practicable, the soil shall be dug up, all lumps broken and

stones removed from the immediate vicinity of the electrode.

4.3 All earth electrodes shall be tested for earth resistance by means of standard

earth test meter. The tests shall take place in dry months, preferably after a

protracted dry spell. If necessary, a number of electrodes shall be connected in

parallel to reduce the earth resistance. In such a case the distance between two

electrodes shall not be less than twice the length of electrode.

4.4 The electrodes shall have a clean surface, not covered by paint, enamel, grease

or other materials of poor conductivity.

4.5 The exact location and number of earth electrodes required at each location

shall be determined in the field in consultation with the owner/Engineer,

Page 15: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.580 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

depending on the soil strata and resistivity, to meet the ohmic values prescribed

in clause 4.3.

4.6 The disconnect facility shall be provided for the individual earth pits to check

their earth resistance periodically.

5.0 CONNECTION :

5.1 All electrical equipment is to be doubly earthed by connecting two points on

equipment to main earthing ring. The earthing ring will be connected via links

to several earth electrodes. The cable armour will be earthed through the cable

glands.

5.2 The following shall be earthed.

1. Transformer neutrals (Double Earthing).

2. Transformer Housing.

3. All switchgear and their earth buses.

4. Motor Frames.

5. Non-current carrying metallic parts of electrical equipment such as

switchgear, switch rocks, panel boards, motor control centers, lighting,

power and instrument panels, push button stations, cable trays, pipes

conduits, terminal boxes etc.

6. All fences/enclosures housing electrical equipment.

7. All still structures, rails etc. including bonding between sections.

8. Shield Wire.

9. Structural steel Columns of building etc.

10. Loading racks.

5.3 System shall be earthed by two distint conductors directly connected to

independent earth electrodes which in turn, shall be connected to the earth

Page 16: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.581 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

loop. The earth connection shall be properly made. A small flexible

aluminium cable loops to bridge the top cover of the transformer and the tank

shall be provided to avoid earth fault current passing through fastening bolts

when there is lightning surge, high voltage surge or failure of the bushings.

5.4 Each Lightening Arrestor shall be connected to a separate electrode located as

close as possible to it and within he fenced area for each set of arrestors shall

be spaced such that they are all within the enclosing fence. Each of these

electrodes shall be connected to the main earth grid.

5.5 The shield wire shall be connected with the main grid solidly and net through

supporting steel structures.

5.6 All paint, scale and enamel shall be removed from the contact surface before

the earthing connections are made.

5.7 All hardware used for earthing installation shall be hot dip galvanized for zinc

passivated. Spring washers shall be used for all earthing connections of

equipment having moving parts and for all the connections subject to vibrations

etc.

5.8 Lighting fixtures shall be earthes through the extra core provided in the lighting

cable this purpose.

6.0 TESTING

Earthing system/connections shall be tested as follows:

6.1 Resistance of individual electrodes shall be measured after disconnecting it

from the grid.

Page 17: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.582 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

6.2 Earthing resistance of the grid shall be measured after connecting all the

electrodes to the grid and generally the test value shall conform to IS:3043

code of practice unless otherwise specified.

6.3 The resistance to earth shall be measured at the following:

a) At each electrical system earth or system at the following.

b) At each earth provided for structure lightning protections.

c) At one point on each earthing system used to earth electrical equipment

enclosures.

d) At one point on each earthing system used to earth wiring system

enclosures such as metal conduits and cable sheaths or armour.

e) At one point on each fence enclosing electrical equipment.

Measurement shall be made before connection is made between the

ground and the object to be grounded.

__________________ ________________________________ Signature of Tenderer Chief Engineer & General Manager (T)

Date : Date :

Page 18: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.583 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

TECHNICAL SPECIFICATION FOR

G.I. PERFORATED TRAYS/ CABLE SUPPORTS

1.0 SCOPE

The scope of this specification covers design, manufacture, inspection and

testing at manufacturer’s works packing & dispatch of M.S. galvanized

perforated trays for use in sub-station for cable laying in trenches, on

structures, on walls etc.

2.0 STANDARDS

The cable trays fittings and accessories including all bolts nuts screws shall be

hot dip galvanized as per IS:2629. The G.I. sheet used for fabrication shall

conform to IS:226.

3.0 PRINCIPAL PARAMETERS

The perforated trays shall be 100 mm , 150 mm and 300mm wide and 75 mm

deep. The trays shall meet the general technical requirement furnished below.

4.0 GENERAL TECHNICAL REQUIREMENT

4.1 The perforated trays shall be fabricated out of 2.0 mm thick G.I. formed into a

trough 75mm deep and shall be 100mm, 150mm & 300 mm wide.

4.2 Each section of tray shall be 2.5 m long & shall be provided with two side

coupler plates & associated nut bolts & washers.

4.3 The side coupler shall be fabricated out of 3 mm thick G.I. plate with four

circular & four elliptical holes.

Page 19: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.584 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

4.4 All trays & coupler plates, bolts, nuts & washers shall be hot dip galvanized

after fabrication. The galvanizing shall be uniform. The amount of zinc

deposit shall not be less than 615 gram per square metre of surface area. The

thickness of zinc deposit at any spot shall not be less than 75 microns. The

amount of zinc deposit over threaded portion of bolts, nuts shall not be less

than 300 grams per square meter.

4.5 The cable trays shall be generally as per enclosed drawing.

5.0 INSTRUCTION MANUAL, TECHNICAL INFORMATION, SHOP

DRAWINGS AND GUARANTEE:

The contractor shall submit immediately after the work is awarded, three copies

of the complete instructions for installation, operation, maintenance and

repairs, circuit diagrams, foundation and trench details for the transformer

proposed to be purchased.

The contractor shall also furnish the information regarding complete

dimensions and total weight of the transformer, minimum room height required

to house and transformer and no load and load losses of the transformer.

The contractor shall furnish shop drawings for the approval of the Engineer

before commencing manufacturing/fabrication of the equipments. Shop

drawings shall be based on the specifications as laid down. The manufacturing

shall be taken up only after approval of the shop drawings by EE(Electrical),

CIDCO.

Page 20: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.585 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

The equipments supplied shall be guaranteed against bad design or

workmanship, improper transport, handing, storage, erection and

commissioning, for a period of 18 months form the date of receipt of materials

at site or 12 months from the date of commissioning whichever is earlier. The

contractor shall replace/repair the damaged equipments without any extra cost.

__________________ ________________________________ Signature of Tenderer Chief Engineer & General Manager (T)

Date : Date :

Page 21: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.586 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

SPECIFICATIONS FOR L.V./M.V. DISTRIBUTION PILLARS

The intent of these specification is to give general guidelines for the

equipments/materials proposed to be used and best efforts are made to

cover all requirements and specifications. However, if any changes,

modifications or additions are to be done as indicated by CIDCO, the

same shall be done without any extra cost or financial implications.

1.0 SCOPE

This specification covers design, manufacture, testing at works, transportations

to site including transit insurance, complete supply, testing and commissioning

at site.

2.0 SYSTEM

Distribution pillars are to be used in underground distribution system with

normal system voltage of 415V. 50 Hz, 3 phase, 4 wire system.

3.0 6 WAY ACB L.T. FEEDER PILLAR/4 WAY L.T. FEEDER PILLAR:

3.1 Indoor type 6 way distribution pillar with 1000 Amp Air Curcuit Breaker pillar

shall be suitable for 3 phase neutral, 50 Hz, 415V AC system and shall confirm

to IS:5039.

3.2 The feeder pillar shall be fabricated out of Galvanised angle iron 35 x 35 x 5

mm frame and 10 SWG sheet steel with slanting roof top and adequately

ventilated by providing louvers with stainless steel wire mesh from inside. The

feeder pillar shall be provided with degree of protection as per IS:2417. The

overall arrangement shall be vermin proof and also water proof.

3.3 The bottom skirt of the pillar shall be fabricated out of 10 SWG G.I. sheet steel

with the louvers on front and back with stainless steel wire mesh from inside as

per the drawings. After carrying out necessary anticorrosive treatment the

Page 22: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.587 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

feeder pillar shall be painted with synthetic enamel paint with post office red

colour and bottom skirt shall be painted with black colour.

3.4 The front and back doors shall be provided with double heavy duty brass

hinged with stainless steel pin and sleeves and galvanized handle for opening

the door. Each door should open by minimum 135 degrees. Latch type

locking arrangement with centrally operated three position locking shall be

provided for doors. The doors shall have self latch locking arrangement with

Godrej type lock and with duplicate keys shall be provided with each pillar.

3.5 Asbestos sheet lining shall be provided on inner side of the door. Inside the

pillar two compartments shall be formed by used of 4/6mm thick asbestos sheet

separators. Rear part will be used for cable entry and cable connections. Front

portion will be used for future replacement.

3.6 Electrolytic Aluminium busbars suitable for 1000 Amps & 630 Amp (4

way)/(6 Way) 1 No. per phase and duly painted with expoxy paint red, yellow,

blue for R, Y, B phases shall be used. For neutral one electrolytic Aluminium

busbar of size 30 x 5 mm shall be used with black epoxy paint. The busbars

shall be mounted on porcelain insulators fixed to the main body/frame.

3.7 For incoming 630 Amp porcelain fuse bases (3 Nos.) with solid links of

removable type and of electrolytic copper shall be used. For outgoing 400

Amps. Porcelain fuse bases with silver plated, copper contacts suitable for

standard HRC fuses shall be used. The rating of the HRC fuses shall be 400A

or as directed. For 4 way distribution pillar the No. of outgoing shall be 3 Nos.

per phase i.e. total of 9 Nos.

3.8 Fuse bases will be mounted on G.I. channels of size 60 x 20 x 3.15 mm fixed

horizontally and which in turn will be supported on angle iron 40 x 20 x 3.15

Page 23: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.588 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

fixed vertically. The pillars shall be provided with HRC fuses of various

rating.

3.9 Split phase busbars shall be connected through solid links removable type on

incoming side of the porcelain fuse bases. Electrolytic Aluminium strips 2

Nos. of 40 x 5 mm size, shall be used as jumpers between outgoing of fuse

bases and cable terminal for each outgoing circuit. These jumpers shall be

supported on 12 mm thick backlite strips which in turn will be supported on

necessary angles. The jumper ends on the cable terminal side shall have 2 Nos.

of holes suitable for connecting outgoing cables by means of 2 Nos. of nutbolts

for each crimping type copper lugs.

3.10 G.I. base plate 3 mm thick and detachable type shall be provided with 4/6 Nos.

knockouts of suitable size for cable entry. Flanged type brass cables glands as

required shall be provided. The base plate shall have the louvers with wire

mesh fitted to them to provide proper ventilation. One illuminating lamp shall

be provided inside the pillar and the lamp shall be provided inside the pillar

and the lamp shall be switched ON when the panel door is opened. The pillar

shall display danger board on front and back doors.

3.11 Two Nos. of earthing terminals with G.I. threaded stud welded to the body on

opposite sides, shall be provided on inner side of the pillar for connecting

earthing strips from earthing stations.

3.12 All nutbolts, washers and fastners used for electrical connections shall be

stainless steel and all other nutbolts shall be G.I.

3.13 For fixing the foundation bolts (of size 12.5mm x 25 mm long) the pillar

bottom frame shall be provided with 4 Nos. of 18 mm dia. holes. The

foundations bolts shall be provided with spring and plain washers and locknuts

Page 24: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.589 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

and the bolts shall be grouted in the foundation concrete block 600mm above

ground level all as per IS specifications and requirements.

3.14 The overall arrangements shall be in line with the drawings and before

manufacturing the pillar it is mandatory for the contractor to submit the

detailed shop/floor drawing of manufacturer for approval of CIDCO.

3.15 Two Nos. of pipe type earthing has to be provided with 25 x mm GI earth

strips.

3.16 The feeder pillars has to be erected on the `C’ type cement concrete foundation

plinth.

4.0 MINIPILLAR

4.1 Outdoor type minipillar shall be suitable for 3 phase & neutral, 50 Hz, 415V,

C.D. system and shall confirm to IS 5039 and shall have a Aluminium busbars

of size 50 x 10 mm and 50 x 5 mm for neutral and 3 Nos. 400 A HRC fuses on

incoming side. The aluminium busbars shall be adequately supported by

porcelain insulators.

4.2 The pillar shall be fabricated out of 14 SWG sheet steel and shall have a

pedestal made out of G.I. angle of size 50 x 50 x 6 mm. The bottom shirt of

the panel shall be with 10 SWG G.I. sheet with louvers on all sides. After

carrying out anticorrosive treatment the pillar shall be painted with synthetic

enamel paint or red colour for the top and bottom skirt shall be with black

colour.

4.3 For fixing the foundation bolts (of size 12.5 mm x 250 mm long) the pillar

bottom frame shall be provided with 4 Nos. of 18 mm dia. holes. The

foundations bolts shall be provided with spring washers and locknuts and the

Page 25: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.590 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

bolts shall be grouted in the foundation concrete block 600 mm above ground

level all as per specifications and requirements.

4.4 Two Nos. of earthing terminals shall be provided on inner side of the pillar for

earthing & pipe type earthing has to be provided for earthing with 2 Nos. 25 x

3 mm GI earth strips.

4.5 The front door shall be provided with double G.I. hinges with panel type

locking arrangement and duplicate keys shall be provided with each pillar. The

pillar shall be provided with a detachable back door, bolted to the main frame.

The pillar shall be provided with slanting roof top and shall be adequately

ventilated by providing gap between pillar body and main body as well as

pedestal.

4.6 Detachable 10 SWG thick gland plate shall be provided at the bottom with

required number of knockouts of suitable size for cable entry.

4.7 Brass cable glands suitable for required number of incoming and outgoing

cables shall be provided. One number extra gland and future use shall be

provided. The pillar shall display danger board.

4.8 The overall arrangement shall be in line with the drawings and before

manufacturing the pillar it is mandatory for the contractor to submit the

detailed shop floor drawing of manufacture for approval of CIDCO.

4.9 The minipillar has to be erected on cement concrete foundation `C’ type plinth.

5.0 GUIDELINES FOR WELDING, ASSEMBLY & POWDER COATING

OF PANELS:

Following procedures have to be adopted:

Page 26: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.591 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

5.1 Components are punched as per drawing & after punching dimensional check

is done, tolerance 10.1 mm as sample from the set for every new setting.

5.2 Before bending all the components, 10% of components from the sets are

checked & tolerance is 10.1 mm to 10.5 degree.

5.3 The parts which are to be welded will be sent for pre-treatment (7 tank process)

to remove the seales & getting coat of phosphating to avoid the possibility of

corrosions at joints.

5.4 After getting phosphated parts, they are welded as per the requirement & then

final inspection of components is done before given to power coating.

5.5 a) Before doing powder coating process, again phosphating is done to

get the phosphating coat wherever phosphating is damaged because of

welding, grinding & in handling.

b) After phosphating, it is immediately followed by a hot run before

powder to avoid the corrosion.

c) Powder coating thickness to measure before giving the components for

assembly & which should be 50 microns. Tolerance + 10 microns

unless otherwise specified.

__________________ ________________________________ Signature of Tenderer Chief Engineer & General Manager (T)

Date : Date :

Page 27: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.592 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

TECHNICAL SPECIFICATIONS FOR

LT CONTROL CABLES

1.0 SCOPE

The scope of this specification covers design, manufacture, inspection, testing

at works, packing and forwarding of 1100 V grade control cables.

2.0 STANDARDS

The cables offered shall conform to the latest revision of relevant Indian

Standard Specifications. Come of these standards are listed below.

Sr.

No.

Indian Standard

Spec. No.

Title

1. 1554 PVC insulated heavy duty electrical cables

for working voltages upto 1100 V.

2. 8130 Conductors for insulated electric cables and

flexible cords

3. 5831 PVC insulation & sheath of electric cables.

4. 3975 Mild steel wires, strips and tapes for

armouring of cables.

5. 2633 Methods of testing weight, uniformity of

coating, thickness on hot dip galvanized

articles.

6. 209 Specification for zinc.

7. 3961 Recommended current ratings for cables –

PVC insulated & PVC sheathed.

8. 1753 Aluminium conductors for insulators cables.

9. 7098 (Part-I) L.T. XLPE Power Cable.

3.0 PRINCIPAL PARAMETERS

Page 28: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.593 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

3.1 The Control cables shall be used indoors/outdoors, directly buried or in open

racks in the plant premises.

3.2 They shall meet the requirements of IS specifications listed above and the

general technical requirement detailed below.

4.0 GENERAL TECHNICAL REQUIREMENT :

4.1 The cables shall be brand new. They shall be suitable for laying on trays, in

trenches, ducts, conduits.

4.2 All the control cables shall be 1100 V grade with aluminium conductor, PVC

insulated, inner sheathed, over all PVC sheathed.

4.3 The construction of the conductors shall be stranded for aluminium cables.

Conductors of nominal area of 25 sq.mm. shall be circular. Those above may

be circular or oval shaped.

4.4 The core insulation shall be with PVC compound applied over the conductor

by extrusion only & shall conform to the type a compound of IS 5831. Control

cables having 6 cores or above shall be identified with prominent and indelible

white coloured Arabic numerical on the outer surface of the insulation at every

500 mm.

4.5 The inner sheath shall be applied over the laid up cores by extrusion and shall

be of PVC confirming to the requirements of type ST1 PVC compound. The

extruded inner sheath shall be of uniform thickness of 0.5 mm upto 16 sq.mm.

0.8 mm upto 120 sq.mm. & 1.0 mm above 120 sq.mm. conductor size.

Page 29: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.594 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

4.6 The outer sheath of the cables shall be applied by extrusion and shall be PVC

compound. Suitable chemicals shall be added to the PVC compound of the

outer sheath to protect the cable against rodent and termite attack.

4.7 The dimensions of the insulation outer sheath materials shall be governed by IS

1554.

__________________ ________________________________ Signature of Tenderer Chief Engineer & General Manager (T)

Date : Date :

Page 30: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.595 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

TECHNICAL SPECIFICATIONS FOR

L.T. XLPE POWER CABLE

1.0 GENERAL

The cables shall be suitable for laying in racks, ducts, trenched, conduits and

underground buried installation with uncontrolled back fill and chances of

flooding by water.

They shall be designed to withstand all mechanical electrical and thermal

stresses under steady state and transient operating conditions. The XLPE

cables shall withstand without damage a three-phase fault current of at least

26.2 kA for at least 0.5 second. The armour for these power cables shall be

capable of carrying 26.2 kA for at least 0.5 second without exceeding the

maximum allowable temperature of outer sheath.

The XLPE insulated cables shall be capable of withstanding a conductor

temperature of 250 degree C during a short circuit without any damage.

The aluminium wires unsed for manufacturing the cables shall be true circular

in shape before stranding and shall be uniformly good quality, free from

defects. All aluminium used in the cables shall be of H2 grade.

The fillers and inner sheath shall be of non- hygroscopic, fire retardant

material, shall be softer then insulation and outer sheath shall be suitable for the

operating temperatures of the cable.

Progressive sequential marking of the length of cable in meters at every one

meter shall be provided on the outer sheath of all cables.

The cable shall have outer sheath of a material with an oxygen index of not less

than 29 and a temperature index of not less than 250 degree C.

Page 31: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.596 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

All the cables shall pass fire resistance test as per IS:1554 (part-1)

Repaired cables shall not be accepted.

Allowable tolerance on the overall diameter of the cables shall be plus or minus

2 mm.

2.0 XLPE POWER CABLES

The XLPE insulated cables shall be of FR type, C1 category conforming to

IS:7098 (part-1) and its amendments read along with this specification. The

conductor shall be stranded aluminium circular/sector shaped and compacted.

In multicore cables, the core shall be identified by red, yellow, blue and black

coloured strips or colouring of insulation. A distinct inner sheath shall be

provided in all multicore cables. For XLPE cables, the inner sheath shall be of

extruded PVC to type ST-2 of IS:5831. When armouring is specified for single

core cables, the same shall consist of aluminium wires/strips. The outer sheath

shall be extruded PVC to Type ST-2 of IS:5831 for all XLPE cables.

3.0 CABLE DRUMS :

Cable shall be supplied non-returnable wooden or steel drums of heavy

construction. Wooden drum shall be properly seasoned, sound and free from

defects. Wood preservative shall be applied to the entire drum.

Standard lengths for each size of power and control cables shall be 500/1000

metres. The cable length per drum shall be subject to a tolerance of plus or

minus 5% of the standard drum length. The owner shall have the option of

rejecting cable drums with shorter lengths. However, the total quantity of

cables after taking into consideration of all cable drums for each size shall be

within the tolerance of plus or minus 2%.

Page 32: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.597 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

A layer of water proof paper shall be applied to the surface of the drums and

over the outermost cable layer.

A clear space of at least 40 mm shall be left between the cables and the

lagging.

Each drum shall carry the manufacturer’s name, the purchaser’s name, address

and contact number and type, size and length of the cable, net and gross weight

stenciled on the both sides of drum. A tag containing the same information

shall be attached to the leading end of the cable. An arrow and suitable

accompanying wording shall be marked on one end of the reel indicating the

direction in which is should be rolled.

Packing shall be sturdy and adequate to protect the cables, from any injury due

to mishandling or other conditions encountered during transportation, handling

and storage. Both cable ends shall be sealed with PVC/Rubber caps so as to

eliminate ingress of water during transportation and erection.

4.0 TESTS

All cables shall conform to all type, routine and acceptance tests listed in the

relevant IS.

All power cables shall meet the requirements of the following additional test

and type test may be conducted to prove their capabilities.

1. Short time current test of conductors.

2. Short time current test on armours.

__________________ ________________________________ Signature of Tenderer Chief Engineer & General Manager (T)

Page 33: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.598 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

Date : Date :

SPECIFICATIONS FOR CABLE LAYING

1.0 SCOPE

This is to define the requirements for the installation, testing and

commissioning of the cabling system.

2.0 CABLE SPECIFICATIONS

2.1 Power Cables

Power cables for use on 415V system shall be of 1100 Volts grade, aluminium

conductor, XLPE insulated, PVC sheathed single wire armoured and overall

PVC sheathed. Power cables for HV system shall be aluminium conductor,

XLPE insulted screened, PVC bedded galvanized steel flat armoured and PVC

sheathed cable.

All L.T. cables conform to the relevant sections of IS:1554 Part-I and H.T.

cables shall conform to IS:7098 (Part-II).

Unarmoured cables will be used wherever specified on the cable schedule.

2.2 Control Cables

Control cables shall be 1100 Volt Grade, 2.5 sq.mm. copper conductor, PVC

insulated, PVC sheathed with an overall PVC sheath as per IS:1554 (Part-I).

2.3 Communication Cables

Communication cable shall comprise 1 pair unarmoured, 2 pair, 5 pair and

multipair armoured cables of sizes as specified in the cable schedule. Minmum

size shall be 0.5 mm dia for telephone system and 1 for plant communication

system.

Page 34: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.599 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

3.0 MISCELLANEOUS MATERIALS

3.1 Connectors

Cable terminations shall be made with aluminium crimped type solderless lugs

of M/s Dowells make or approved equivalent for all aluminium conductors and

stud type terminals.

3.2 Cable Identification

Cable tags shall be of 2 mm thick aluminium strap of suitable size to contain

cable number, equipment number etc.

3.3 Ferrules

Ferrules shall be of self sticking type and shall be employher to designate the

various cores of control cable by the terminal numbers to which the cores are

connected for ease in identification and maintenance.

3.4 Cable Glands

Cable glands to be supplied shall be brass single/double compression type as

per the directions of Engineer. Generally single compression type cable glands

shall be used for indoor protected locations and double compression type shall

be used for outdoor locations.

3.5 Cable Trays

Prefabricated hot dip galvanized sheet steel cable trays shall be used for

maximum support span of 2000 mm unless design is approved for larger span.

For requirements of larger than 750 mm width two trays shall be run side by

side. Cable trays shall be suitable for a cable weight of 50 kg/m running length

of tray. Minimum thickness of sheet steel/galvanized shall be 3 mm/86

Page 35: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.600 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

micorns. Cable trays fabricated from standard rolled sections shall used 50 x

50 x 6 /ISMC 100 sections for runners for supporting spans limited to 2000

mm/more than 2000 mm respectively. Cross support shall be 32 x 6 mm flat

25 x 25 x 6 mm angle for widths upt o500 mm/ more than 500 mm

respectively. If unit rate not included in schedule of rates then cable trays if

required shall be fabricated/installed at site as per the per tonne rate for

electrical structural supports etc.

4.0 CABLE LAYING

4.1 Cable network shall include power, control lighting cables, which shall be laid

in trenches, cable trays or conduits as detailed in the relevant drawings and

cable schedules. Erection of cable trays as required shall be the responsibility

of the contractor. Cable routing shall be checked in the filed to avoid

interference with structures, piping or air-conditioning duct and minor

adjustments shall be done to suit the filed conditions wherever deemed

necessary without any extra cost.

4.2 High voltage, medium voltage and other control and communication cables

shall be separated from each other by adequate spacing or running through

independent pipes, trenches or cable trays, as applicable.

4.3 All cable routes shall be carefully measured and cables cut to the required

lengths, leaving sufficient lengths for the final connection of the cable to the

terminal of the equipment. The various cable lengths cut form the cable reels

shall be carefully selected to prevent undue wastage of cables. The quantity

indicated in the cable schedule is only approximate. The contractor shall

ascertain the exact requirement of cable for a particular feeder by measuring at

site and avoiding interference with structure, foundation, pipelines or any other

works.

Page 36: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.601 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

4.4 Cables as far as possible shall be laid in complete, uncut lengths from one

termination to the other.

4.5 Cables shall be neatly arranged in the trenches/trays in such manner so that

criss-crossing is avoided and final take off to the motor/switchgear is

facilitated. Arrangement of cables within the trench/trays shall be the

responsibility of the contractor.

4.6 All cables will be identified close to their termination point by cable numbers

as per cable schedule. Cable numbers will be punched on aluminium straps (2

mm thick) securely fastened to the cable and srapped around it. Alternatively

cable tags shall be circular in construction to which cable numbers can be

conveniently punched. Each underground cable shall be provided with

identify tags of lead securely fastened every 30 m of its underground length

with atleast one tag at each end before the cable enters the ground. In unpaved

areas, cable trenches shall be identified by means of markers as per standard

drawing. These posts shall be placed at location of changers in the direction of

cables and at intervals of not more than 30 m and at cable joint locations.

4.7 All temporary ends of cables must be protected against dirt and moisture to

prevent damage to the insulation. For this purpose, ends of all PVC insulated

cables shall be taped with an approved PVC or rubber insulating tape. Use of

friction type or other fabric type tape is not permitted. Lead sheathed cables

shall be plumbed with lead olloy.

4.8 RCC cable trenches with insert plates shall be provided by the contractor.

Cable shall be laid in 3 to 4 tiers in these trenches.

Page 37: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.602 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

4.9 Directly buried cables shall be laid underground in excavated cable trenches

where specified and layout drawings. Trenches shall be of minimum 0.9 mtr.

depth and suitable width for accommodation of all cables correctly spaced and

arranged with a view of heat dissipation and economy of design. Depth of

burying shall allow minimum 900 mm soil cover for low voltage and 1000 mm

for 11KV cables.

L.T. cables shall be laid in trenches as above stated depth. Before cables are

placed, the trenches bottom shall be filled with layer of sand. This sand shall

be leveled and the cables laid over it. The cables shall be covered with 150

mm of sand on top of the largest diameter cable and sand shall be lightly

pressed. A protective covering of 75 mm thick second class red bricks shall

then be laid flat. The remainder of the trench shall then be back-filled with

soil, rammed and leveled.

As each row of cables is laid in place and before covering with sand every

cables shall be given an insulation test in the presence of Engineer/Owner.

Any cable which proves defective shall be replaced before the next group of

cables are laid.

All wall openings shall be effectively sealed after installation of cables to avoid

leakage of water.

4.10 Where cables rise from trenches to motor, control, station, lighting panels etc.,

they shall be taken in G.I. pipes for mechanical protection upto a minimum of

300 mm acboe grade or as shown in the standard drawings.

Cable ends shall be carefully pulled through the conduits to prevent damge to

the cable. Where required, approved cable lubricant shall be used for this

Page 38: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.603 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

purpose. Where cable enters conduit the cable should be bent in large radius.

Radius shall not be less than the recommended bending radius of the cables

specified by the manufacturer.

Following guide of the pipe fill shall be used for sizing the pipe size:-

a) 1 Cable in pipe : 53% full

b) 2 Cables in pipe : 31% full

c) 3 or more cables : 43% full

d) Multiple cables : 40 % full.

After the cables are installed and all testing is complete, conduit ends above

grade shall be plugged with a suitable weatherproof plastic compound/PUTTI

for sealing purpose. Alternatively G.I. Lids or PVC bushes shall be employed

for sealing purposes. The cost for the same shall be deemed to have been

included in the installation of G.I. pipe and no separate payment shall be done.

4.11 Where cables pass through foundation wall or other underground structures, the

necessary ducts or openings will be provided in advance for the same.

However, should it become necessary to cut holes in existing foundations or

structures the electrical contractor shall etermine their location and obtain

approval of the Engineer before cutting is done.

4.12 At road crossing and other places where cable enter pipe sleeves adequate bed

of sand shall be given so that the cables do not slack and get damaged by pipe

ends after back filling.

4.13 Drum number of each cable from which it is taken shall be recorded alongwith

the cable number in the cable schedule.

Page 39: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.604 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

4.14 Cables installed above grade shall be run in trays, exposed on walls, ceilings or

structures and shall be run parallel or at right angles to beams, walls or

columns.

Cables shall be so routed that they will not be subjected to heat from adjacent

hot piping or vessels.

4.15 Individual cables or small groups which run along structures/walls etc. will be

clamped by meas of 16 SWG GI saddles on 25 x 6 mm saddle bars. The cost

of saddle and saddle bars shall be deemed to have been included in the

installation of cables and no separate payment shall be made on this account.

They shall be rightly supported on structural steel masonry, individual or in

groups as required, if drilling of steel must be resorted to, approval must be

secured and steel must be drilled where the minimum weakening of the

structure will result.

Cables shall be supported so as to prevent unsightly sagging, in general

distance between supports shall be approximately 300 mm for cables upto 25

mm diameter and maximum 450 mm for cables larger than 25 mm dia.

4.16 All G.I. pipes shall be laid as per site requirements. Before fabrication of

various profiles of pipe by hydraulically operated, bending machine (which is

to be arranged by the contractor), all the bars from the pipes shall be removed.

G.I. pipes buries in soil, bitumen coating shall be applied on the buried lengths.

Installation of G.I. pipes shall be undertaken well before paving is completed

and necessary co-ordination will paving agency shall be the responsibility of

Electrical contractor. The open ends of pipes shall be suitably plugged with

Page 40: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.605 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

G.I. plugs after they are laid in final position G.I. plugs shall be supplied by the

contractor at no extra cost.

4.17 Cable laid on supporting angle in cable trenches, structures, columns and

vertical run of cable trays shall be suitably clamped by means of G.I.

saddles/clamps, whereas cable in horizontal run of cable trays shall be tied by

means of nylon cords.

4.18 Supporting steel shall be painted before laying of cables. The painting shall be

done with one coat of red lead paint and two coats of approved bituminous

alluminium paint.

5.0 TERMINATION:

5.1 All PVC cables upto 1.1KV grade shall be terminated at the equipments by

means of compression type cable lugs of aluminium. They shall have a gland

of screwed nipple with conduit electrical threads and check nut.

5.2 Power cables shall be identified with red, yellow and blus PVC tapes. Where

copper to aluminium connections are made, necessary bimetallic washers shall

be used. For trip circuit identification additional red ferrules shall be used only

in the particular cores of control cables at the termination points in the

switchgear/control panels and control switches.

5.3 In case of control cables all cores shall be identified at both ends by their

terminal numbers by means of PVC ferrules, or self sticking cable markers.

Wire numbers shall be as per schematic/wiring/inter-connection diagram.

Bidders shall have the samples of PVC ferrules/cable markers approved before

starting the work.

Page 41: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.606 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

5.4 Where threaded cable gland is screwed into threaded opening of different size,

suitable galvanized threaded reducing bushing shall be used of approved type,

at no extra cost.

5.5 The cable shall be through glands inside the panels or any other electrical

equipment such as motors. The individual cores shall then be dressed and

taken along the cable ways (if provided) or shall be fixed to the panels with

polyethylene straps. Only control cables of single strand and lighting cables

may be directly terminated on the terminals.

In case of termination of cables at the bottom of a panel over a cable trench

having no access from the bottom close fit hole should be drilled in the bottom

plate for all the cables in one line, then bottom plate should be split in two

parts along the center line of holes. After installation of bottom plate and

cables it should be sealed with cold setting compound. Cables shall be

clamped over the open armouring to connect it to earth bus.

5.6 Cable leads shall be terminated at the equipment terminals, by means of

crimped type solderless connectors as manufactured by M/s. Dowell Electro

Works or approved equivalent.

Crimping shall be done by hand crimping/hydraulically operated tool and

conducting jelly shall be applied on the conductor. Insulation of the leads

should be removed immediately before the crimping. Conductor surface shall

be cleaned and shall not be left open.

5.7 11, 6.6 and 3.3 KV cables terminations/joints shall be done byu skilled and

experienced jointers duly approved by the owner, if included in the contract.

Page 42: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.607 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

6.0 TESTING

6.1 Before energizing, the insulation resistance of every circuit shall be measured

from phase to phase and from phase to ground, This requires 3 measurements

if one side is grounded and 6 measurements for 3 phase circuits.

Where splices or terminations are required in circuits rated above 600 Volts,

measure insulation resistance of each length of cable before splicing and

or/terminating. Repeat measurement after splices and/ or terminations are

completed.

6.2 Measure the insulation resistance of directly buried cable circuits before cable

trenches are back-filled. Repeat measurement after back filling.

7.1 CABLE TRENCHES (EXCAVATED):

7.3.1 The cable trenches shall be excavated 1000 mm below the finished ground

level and shall have a minimum width of 300 mm. for laying of single cable.

When more than one cables are laid in the same trench, the width of the

trench shall be increased such that the spacing between the cables is 25 cms.

and the end cables are at minimum 15 cms. from the side of the trenches. At

the turning of the cable route the trench shall be dug with radius equal to 15

times the cable diameter.

7.3.2 The trenches shall be cut square with vertical side walls and with uniform

depth. Suitable shoring and propping may be done to avoid caving in of

trench walls. The floor of the trench shall be rammed and leveled. The

bottom of the cable trench shall be prepared with 100mm. sand bed for

laying the cables.

Page 43: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.608 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

7.3.3 The cables shall be laid in trenches over the rollers. After the cable is laid

and straightened it shall be covered with sand, and RCC half round/semi

circular pipe of appropriate strength & size.

7.3.4 The cable trench then shall be refilled with excavated materials after

removing the stones and other sharp materials and the refilled materials shall

be compacted with light ramming.

7.3.5 Approved cable markers made of G.I. with 15 cms crown shall be provided

along the route of cables at a spacing of 40 – 50 meters and also at both ends

of road crossings or at the cable turning points. The class, type and No. of

cables shall be indicated on the markers.

7.3.6 Cable shall be laid in hume pipes at all road crossings and in GI pipes at the

wall entries.

7.4 CABLE JOINTING :

7.4.1 Cable jointing shall be done as per the recommendations of the cable

manufacturer. Jointing shall be done by qualified cable jointer. The location

of the cable joint shall not be where the cable takes a bend also where the soil

is loose and shows signs of subsidence.

7.5 TESTING OF CABLE BEFORE LAYING AND COMMISSIONING :

7.5.1 All tests shall be carried out in accordance with relevant IS codes of practice,

IE rules.

7.5.2 100% cable drums shall be checked for continuity and cross continuity tests

to ensure that there is no internal damage to the cable during transportation.

Page 44: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.609 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

7.5.3 Installation resistance shall be measured with 1000 V megger between the

cores and all the cores to earth (armour) and results shall be recorded.

7.5.4 Before cable jointing is done, cable shall be tested for presence of moisture

by dipping a piece of insulation of cable in hot compound of paraffin was at

temperature between 120 –140 degree centigrade. The presence of moisture

is indicated by the formation of bubbles. Only a single strip of insulation

gripped by a pair of tweezers should be used.

7.5.5 After the cables are installed before commissioning it shall be tested for high

DC voltage test. The recommended volts and duration of the test shall be as

per I.E. rules & regulations. However the test voltage and duration shall be

in conformity with standards of local supply authorities. During high voltage

tests all electrical equipments related to the cable installation must be earthed

and adequate clearance shall be maintained from the other equipments and

from work to prevent flash over.

__________________ ________________________________ Signature of Tenderer Chief Engineer & General Manager (T)

Date : Date :

Page 45: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.610 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

TECHNICAL SPECIFICATIONS FOR LIGHTING FIXTURES

1.0 SCOPE:

The scope of this specification covers providing, testing at works, inspection

before dispatch, packing and forwarding of industrial lighting fittings and

accessories.

2.0 STANDARDS:

It is not the intent to specify herein all the details of the design and construction

of the equipment. However, the equipment shall conform in all respects to

standards, engineering, deign and workmanship.

3.0 PRINCIPAL PARAMETERS:

The lighting fixtures shall conform to the General Technical requirement

furnished below:-

4.0 GENERAL TECHNICAL REQUIREMENT:

4.1 Constructional Features

4.1.1 The lighting fittings shall be supplied with lamps and all other accessories to

make the fittings complete in all respects.

4.1.2 The fittings comprising reflectors, housing shall be made of single piece

alluminium die cast.

4.1.3 The fittings shall be suitable for ambient condition of dusty and humid

atmosphere. Outdoor fittings such as street light fitting & floor light fitting

shall have IP 55 enclosure.

Page 46: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.611 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

4.1.4 The fittings shall be provided with sufficient space inside to permit repair and

reassembly of replaceable components with ease and without impairing

safety.

4.1.5 The street light fitting shall have a cut off or semi cut off, lighting distribution

by adjusting the position of lamp holder by adjusting the position of lamp

holder.

4.1.6 The control gears of the flood light fittings shall be suitable for mounting at

the base of the lighting tower on which the flood light fitting is mounted.

4.1.7 Lighting fittings with discharge lamps shall be provided with power factor

improving capacitors.

4.1.8 All the components of the lighting fittings shall be duly wired with PVC

insulted flexible copper conductor wires of adequate size not less than 0.5

sq.mm. The insulation thickness shall not be less than 0.6 mm. The

conductor insulation shall be capable of withstanding the maximum

temperature to which it will be subjected to in normal use. The internal

wiring shall be terminated on tough, non-hygroscopic, non-inflamable & non

tracking terminal block suitable for accepting 2 cores of 4 sq.mm. aluminium

conductor for power supply to the fitting.

4.1.9 The fitting shall be provided with suitable cable entry arrangement for 3 core

aluminium conductor PVC insulated cable.

4.1.10 All the lighting fittings shall be provided with suitable mounting

arrangement.

Page 47: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.612 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

4.1.11 The lighting fitting shall be provided with an earthing terminal of adequate

size. The earthing terminal shall be marked with the symbol on or adjacent to

this terminal.

4.1.12 All hardware material used in the fitting shall be corrosion resistant zinc

passivated or cadmium plated bolts nuts & washers only shall be used.

4.2 Components

4.2.1 Holders for Lamps & Starters

The holder shall be so designated and constructed so as to be mechanically

robust and free from any operational difficulties. It shall be designed to ensure

safe & easy functioning under normal condition. It shall be so constructed as

to be capable of withstanding shock during normal transportation, installation

& in use. It shall be adequately resistant to heat. All metal parts likely to be

affected by atmospheric condition shall be adequately protected to prevent

corrosion.

4.2.2 Lamps

a) High pressure sodium vapour lamp shall be tubular shaped with

diffusing powder coating. The lamp shall have external ignitor.

b) The fluorescent tube light shall be 1200mm long 36 W rating cool day

light type.

4.2.3 Ballasts Ignitor & Starter

a) The ballast shall be copper wound polyster filled & shall be

mechanically robust and so designed & constructed as to minimize

effect of atmospheric moisture & of temperature changes during use.

b) HPSV lamp ballasts shall be provided with necessary tappings for the

specified voltage range.

Page 48: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.613 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

c) The ballast, ignitor & the discharge lamp shall be designed to be on

perfect matching with each other.

d) The fluorescent lamp starter capsule shall be made of aluminium with

brass pins.

4.2.4 Capacitors

a) Every fitting shall be provided with a power factor improving capacitor.

The power factor shall be least be 0.9.

b) The capacitor shall be provided with discharge resistor for safety.

4.3 Painting

a) All the fitting housing, reflectors, gear trays etc. shall be thoroughly

cleaned & shall undergo 7 tank process & then two coats of eposy base

primer shall be applied.

b) After the preparation of surfaces, the fitting shall be powder coated.

c) Sheet steel reflector shall be store enameled & aluminium reflector shall

be anodized.

4.4 Following Types of Lighting Fixtures are envisaged.

4.4.1 1 x 40 W Industrial Type Fluorescent Fitting

The luminaire shall be fabricated from CRCA sheet steel with white powder

coating. The CRCA sheet shall not be less than 0.7 mm thick. The reflector

shall be stove enameled light dove grey outside & reflecting white inside. A

channel cover shall be provided. The luminaire shall be prewired & shall be

provided with power factor improvement capacitor, vacuum pressure

impregnated copper holders and main connector. An elegant acrylic

transparent cover damped to the fixture shall also be provided. The fixture

shall be provided with light source also. The lighting fixture shall be TKC

24/136 Philips make or equivalent.

Page 49: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.614 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

4.4.2 2 x 40 W Mirror Optic Fitting

The luminaire shall be fabricated from CRCA sheet steel with epoxy powder

white coating from inside & outside. The CRCA sheet shall not be less than

0.7 mm thick. The reflector shall be stove enameled light dove grey outside &

reflecting white inside. The luminaire shall be wired & provided with power

factor improvement capacitor, vacuum pressure impregnated copper wound

ballast, bipin pushfit type lamp holders & mains connector. The fixture shall

be provided with light source also. The lighting fixture shall be similar to TBS

50/136 of Philips make or equivalent.

4.4.3 1 x 40 W Corrosion Proof Industrial Fixtures

The luminaire shall be fabricated from CRCA sheet steel with white powder

coating and corrosion proof. The CRCA sheet shall not be less than 0.7 mm

thick. The reflector shall be stove enameled light dove grey outside &

reflecting white inside and corrosion proof. A channel cover shall be provided.

The luminaire shall be prewired & shall be provided with power factor

improvement capacitor, vacuum pressure impregnated copper holders and main

connector. An elegant acrylic transparent cover clamped to the fixture shall

also be provided. The fixture shall be provided with light source also. The

lighting fixture shall be similar to TDC 10 Philips make or equivalent.

__________________ ________________________________ Signature of Tenderer Chief Engineer & General Manager (T)

Date : Date :

Page 50: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.615 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

SPECIFICATION FOR ELECTRICAL WORK

MEDIUM VOLTAGE DISTRIBUTION SYSTEM

1. Internal Wiring for lighting and power

This specification covers, system and method of wiring, definition of point

wiring, and supply, installation, connection, testing and commissioning of point

wiring for light points, fan points, convenience socket outlet points, power

socket outlet points, bell outlet points, etc. Wiring shall be with copper

conductor PVC insulated wires drawn in PVC conduits, concealed in or surface

erected on wall, ceiling etc. or in surface erected PVC casing and caping.

Wiring shall be from meter rooms to distribution boards, from D.B. to switch

boards and from switch board to outlet points. The method of wiring for this

particular work shall be as mentioned under paras of work and Bill of

Quantities.

2. System of wiring

Medium voltage distribution system shall be applicable for wiring three phase,

4 wire, 415 V, 50 Hz, AC supply and single phase, 2 wire, 230 V, 50 Hz, AC

supply.

3. Applicable Standards

1. IS:732 Code of Practice for Electrical wiring installation (System

voltage not exceeding 650 V).

2. IS:1646 Code of Practice for fire safety of buildings (General)

Electrical Installation.

3. IS:9537 Rigid steel conduits for electrical wiring.

Part II

Page 51: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.616 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

4. IS:2667 Fittings for rigid steel conduits for electrical wiring.

5. IS:3480 Flexible steel conduits for electrical wiring.

6. IS:3837 Accessories for rigid steel conduit for electrical wiring.

7. IS:694 PVC insulated cables.

8. IS:2509 Rigid non-metallic conduits for Electrical wiring.

9. IS:3419 Specifications for fittings for rigid PVC non-metallic

conduits.

10. IS:6946 Flexible (Pliable) non-metallic conduits for electrical

installation.

11. IS:12S3 3 pin plugs and sockets.

12. IS:8130 Conductors for insulated electric cables and flexible cord.

13. IS:9537 Specification for conduits for Electrical Installation.

14. IE : Rules Indian Electricity Act

15. IS:5133 Boxes for enclosure of electrical accessories.

Part-I : Steel and CI boxes.

16. IS:371 Ceiling roses (Second revision)

17. IS:4615 Switch socket outlets (Non interlocking type)

18. IS:3854 Switches for domestic and similar purposes.

4. General Requirements :

4.1 Drawings

a. Prior to laying of conduits, the contractor shall submit the shop drawing

for layout of conduits for approval. The drawing shall indicate the route

and the no. and sizes of the conduits, location of junction inspection / pull

/ outlet boxes, size and location of switch boxes, number and size of wires

pulled through each conduit and all other necessary relevant details.

b. Only after the drawings are approved, the contractor shall proceed with

the work of laying of conduits and/or erection of PCVC casing caping.

The owner reserves the right to modify or alter or reject the shop drawings

Page 52: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.617 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

and the contractor is responsible to resubmit the revised / modified

drawing for approval.

4.2 Site Layout

Before the conduits are installed, the exact route shall be marked at the site for

approval and the actual work shall be undertaken only after approval.

4.3 Load Balancing

Balancing of circuits in three phase installation shall be planed before the

commencement of wiring and shall be strictly adhered to.

4.4 Definition of Point Wiring

A point shall consist of the branch wiring from the switch board together with a

switch and point control boxes as required, as far as and including the wiring

accessories such as ceiling fan box or socket outlet point or suitable

termination. A point shall include, in addition, the earth continuity

conductor/wire form the switch board to the earth pin/stud of the outlet/switch

box.

5 Scope of Work

The medium voltage distribution system wiring shall be carried out in the

under mentioned manner.

a. Supply, installation, fixing of conduits and PVC casing/caping with

necessary accessories, switch boxes, outlet boxes and pull/junction boxes.

b. Supplying and drawing of wires of required size including earth

continuity wire.

c. Supply, installation and connection of switches; sockets, cover plates,

switch plates, concealed fan hook boxes / fan hooks as specified etc.

Page 53: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.618 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

d. The point shall be complete with the branch wiring form the switch

boards to the outlet point, PVC casing caping with accessories, control

switch, socket outlet boxes, ceiling roses, batten/angle holder, connector

etc.

6. Wiring System with PVC Casing Caping

6.1 This wiring system shall not be used in location which are exposed to sun and

rain.

6.2 The PVC casing and caping and its accessories shall be push fit type with fine

polished surface both inside and outside. The standard accessories from the

same manufacturer as that of casing shall be used for jointing. For reducing the

size of a casing a standard reducer junction box shall be used.

6.3 The size of the casing shall be selected as per manufacturers recommendation

and in the absence of which selection shall be based on criteria of

accommodating required number of wires without over crowding.

6.4 Ceiling and outside walls shall be totally avoided. Also it shall not be buried

under plaster or fixed in proximately to gas, steam or water pipes or below the

same. For typical locations as indicated above the casting shall be terminated

and the wiring extended as directed either in PVC/MS conduits.

6.5 Casing shall be fixed to wall or ceiling by means of suitable flat head screws to

plugs at both ends of the casing and at an interval not exceeding 50 cms. Screw

heads shall be countersunk type within the casing thickness and shall not

protrude out to damage the wires laid inside.

Page 54: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.619 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

6.6 The casing shall be fixed flat to wall and shall not sag out of the wall surface or

there shall be no visible gap between wall and casing at nay point.

6.7 All joints shall be made through standard PVC casing coupler to avoid any

gaps and to firmly connected two casing caping ends in straight lines.

6.8 Layout of casing wiring shall be such as to avoid corners as far as possible and

avoid crossing of conductors inside casing. Where casing and caping have to

cross comers and take ends, accessories such as standard elbow caps, right

angle comers, external angles, internal angle, three or four way box shall be

used. The jointing accessories shall be of same width as that of casing.

6.9 Casing and caping shall be run in lengths as long as possible. All joints shall

be cut diagonally in longitudinal section and smoothened down by filing to

make a smooth and very close fit. Both ends of the joints shall be screwed and

joints in casing shall not be over the joints casing and shall be staggered.

6.10 Casing shall be press fit type and attached to the caping, after all wiring are laid

inside the casing. The wires shall be held with wire clips at suitable spacing.

7. Surface conduit wiring system with rigid steel conduits

7.1 All conduit pipes shall confirm to IS:1653 and shall have finishing with over

baked enamel painting as directed and specified. All conduit accessories shall

be of threaded type and minimum dia of the conduits used shall be 25 mm.

The wall thickness of conduits shall be 16 SWG for 25 mm dia conduits and 14

SWG for 32 mm and above dia unless specified otherwise.

7.2 The conduit shall have uniform wall thickness and uniform cros section

throughout. The welding (ERW) shall be uniform and good such that welded

Page 55: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.620 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

joints do not yield when subjected to a flattening wt. The conduits shall be free

from welding burr. Welded joints shall not break when threaded or bend at an

angle. Conduits shall bear the name and trade mark of the manufacturer on

earth length. The conduits shall be delivered to the site in original bundles.

7.3 Conduit accessories such as bends, inspection bends, inspection tees, elbows,

draw boxes, junction boxes etc. shall confirm in all respects to IS:3837. Boxes

shall have internally tapped spouts. Junction boxes and inspection boxes shall

be provided with suitable covers.

7.4 Insulated conductors of AC supply and DC supply shall not be bunched in the

same conduit. All conduits shall be installed so as to avoid steam and hot water

pipes. A separation of 200 mm shall be maintained between electrical conduits

and hot water lines in the building.

7.5 Conduit pipes shall be joined by means of screwed couplers and screwed

accessories only. In long distance strength runs of conduit, inspection type

couplers or draw-in points/boxes at maximum 8 M interval shall be provided.

Threads on conduits pipes shall a between 11 mm to 27 mm long and sufficient

accommodate pipes in to full threaded portion of couplers or accessories. In

case of screwed coupler joints the threads of conduit and coupler shall be free

from grease and oil and shall be thoroughly cleaned before making the joints.

7.6 Cut ends of conduits pipes shall have no sharp edges nor any burr left, so as to

avoid damage to the installation of conductors while pulling them through such

pipes. All conduits ends shall be bushed with wooden bushes.

7.7 The outer surface of conduit pipes including all bends, tees, junction boxes,

unions etc. which form part of the conduit system shall be adequately protected

Page 56: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.621 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

against rust. No bare threaded portion of the conduit shall be allowed unless

such are threaded portion is treated with anti corrosive preservative or covered

with plastic compound. After the wires are drawn in caudate it shall be painted

with enamel paint of shade as directed.

7.8 Conduit pipe shall be fixed by heavy gauge. GI saddles fixed on MS spacers

(Galvanized) secured to wall, ceiling with wood plugs or any other approved

plugs with screws and all in an approved manner. The spacers and saddles

shall be provided at a distance of not more than one meter. However, saddles

shall be fixed on either side of couplers or bends or similar fittings at a distance

of not more than 300 mm from the center of such fittings.

7.9 All necessary bends in the system including diversions sall be done by bending

conduits by pipe bending machine or any other suitable device as far as

possible. Bends which cannot be negotiated by pipe bend shall be achieved by

inserting suitable solid or inspection type normal bends, elbows or similar

fittings or by fixing cast iron inspection boxes which ever is suitable.

Conduit fittings shall be avoided as far as possible on conduits system exposed

to weather, however, where necessary, solid type fittings shall be useful.

Radius of bend in conduit pipes shall be not less than 75 mm. No length of

conduit shall have more than two right angle bends nor deviation from the

straight run.

7.10 All outlet for fittings, switches, etc. shall be boxes of suitable metal or ay other

approved outlet boxes for either surface mounting or flush mounting system.

Page 57: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.622 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

7.11 In order to minimize condensation or sweating inside the conduits, all outlets of

conduit system shall be properly drained and ventilated, but in such a manner

as to prevent the entry of insects, etc.

7.12 Fixing between conduit and boxes, outlet boxes, switch boxes and the like must

be provided with entry spouts and smooth PVC bushes. Joints between conduit

and any type of boxes shall be effected by means of conduit couplers in to each

of which shall be coupled smooth PVC bush from inside the box. Conduits

shall be rigidly connected to the box/boards with check nuts on either side of

the entry to ensure proper electrical and mechanical continuity. In any case all

the joints shall be fully water tight.

7.13 All screwed and socket connections shall be adequately made fully water tight

by the use of proper jointing materials.

7.14 Conduits shall be so arranged as to facilitate easy drawing of wires through

them. Entire conduit layout shall be done in such a way as to avoid additional

junction boxes other than light points. The wiring shall be done in a looping

manner. All the looping shall be done in either switch boxes or outlet box.

Looping in junction or pull boxes is strictly not allowed. Where conduits cross

building expansion joints, adequate expansion fittings or other approved

devices shall be used to take care of any relative movement.

7.15 The conduit layout of each circuit or section shall be completed before

conductors are drawn in. The entire system of conduit after erection shall be

tested for mechanical and electrical continuity throughout and permanently

connected to earth, conforming to the requirement specified, by means of

special approved type earthing clamp efficiently fastened to conduit pipe for a

perfect continuity between earth wire and conduit. Gas or water pipes shall not

Page 58: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.623 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

be used as earth medium. If conduit pipes are liable to mechanical damage

they shall be adequately protected.

7.16 The entire conduit system including boxes shall be thoroughly cleaned after

completion of escalations and before drawing of wires. Conduit system shall

be erect and straight as far as possible. The where water may accumulate from

condensation are to be avoided and if unavoidable, suitable provision for

draining the water shall be made.

7.17 Conduits shall be installed in such a way that the junction deviation and pull

boxes shall always be accessible for repairs and maintenance work. The

location of junction/pull boxes shall be marked on the shop drawings.

8. Concealed/recessed conduit wiring system with rigid steel conduit

8.1 In addition to the requirements as specified for surface conduits wiring system,

the recessed conduit wiring system shall conform to the following

requirements.

8.2 All the conduits including bends, unions, junction boxes etc. shall be cleaned

and painted with two coats of bitumen pant, if specifically called for, before

they fixed in position.

8.3 Conduits embedded in concrete shall be installed on the prepared shuttering

work before pouring concrete. The conduits shall be installed above the

bottom reinforcing bars, and shall provide positive wire fastening of the

conduit to reinforcing rods at an interval of not more than one meter. But on

either side of couplers or bends or outlet/pull/junction boxes or similar fittings,

proper hold fast shall be fixed at a distance of 30 cm from the center of such

fittings.

Page 59: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.624 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

8.4 Before conduits are laid in the ceiling the positions of outlet points, point

control, junction boxes shall be set out dearly so as to minimize off-sets and

bends. The conduit shall be properly threaded and screwed into sockets, bends,

junction boxes, outlet boxes and shall be made watertight by using bituminous

hemp yam at the screwed ends.

8.5 Conduits embedded in the wall shall be fixed inside the chase. The chase in

the wall shall be neatly made and be of ample dimensions to permit the conduit

to be fixed in the manner desired. In the case of buildings under constriction,

chases shall be provided in the wal, ceiling, etc. at the time of their construction

and shall be filled up neatly with cement mortar after erection of conduit and

brought to the original finish of the wall. Cutting of horizontal chases in walls

is not recommended.

8.6 The conduit pipe shall be fixed inside the chase by means of staples or by

means of saddles not more than 60 cm apart. Fixing of standard bends or

elbows shall be avoided as far as practicable and all curves maintained by

bending the conduit pipe itself with along radius which will permit easy

drawing-in of conductors. Al the threaded joints of rigid steel conduit shall be

treated with some approved preservative compound to secure protective against

rust. The ends of pipes shall be bushed and sealed with compound after the

wires are drawn-in to prevent ingress of moisture.

8.7 The outlet boxes, point control boxes, inspection and draw-in boxes shall be

fixed as and when conduit is being laid. The recessing of conduits in wall shall

be so arranged as to allow atleast 12 mm plaster cover on the same.

Page 60: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.625 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

8.8 Suitable cast iron or mild steel inspection boxes as specified shall be provided

to permit periodical inspection and to facilitate removal of wires, if necessary.

These shall be mounted flush with the wall. Suitable ventilating holes shall be

provided in the inspection box covers.

8.9 All outlets, such as boxes for fixing switches and wall sockets, may be either of

flush mounting type or of surface mounting type as specified.

a. Flush mounting type : All flush mounting outlets shall be of cast iron or

mild steel boxes with a cover of approved insulating materials or shall be

a box made of a suitable insulating material. The switches and other

accessories shall be mounted on such boxes as would be approved. The

metal box shall be efficiently earthed with conduit by an approved means

of earth attachment.

b. Surface mounting type : If surface mounting type outlet box is specified, it

shall be of any approved insulating material and all accessories mounted

in approved manner.

8.10 Where conduits pass through expansion joints in the building, adequate

expansion fittings or other approved devices shall be used to take case of any

relative movement.

9. Surface and/or recessed/concealed conduit wiring system with rigid PVC

conduit

9.1 All non metallic PVC conduits used shall conform to IS:2509. The conduit

may be either threaded type or plain type as specified in IS:2509 and shall be

used with corresponding accessories as per IS:3419. PVC conduits shall be

rigid, unplasticised, heavy gauge having wall thickness as per IS. The

accessories shall be of same make as that of the conduit. Standard circular

boxes shall be used at junctions, lighting points, draw in points etc.

Page 61: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.626 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

9.2 All boxes shall have tapped brass inserts within the pillars. In damp or exposed

situations box cover shall be fitted with neoprene rubber gaskets. All box

covers shall be fitted to boxes with greased brass cheese head screws.

9.3 Caution shall be exercised in using the PVC conduits in location where

ambient temperature is 50 degree Celsius or above. Use of PVC conduits in

places where ambient temperature is more than 60 degree C. is prohibited.

9.4 Conduits shall be joined by means of screwed or plain couplers depending on

whether the conduits are screwed or plain. Where there are long runs of

straight conduit, inspection type couplers/pull boxes shall be provided at

intervals. In case of screwed coupler joints, the threads of conduit and coupler

shall be free from grease and oil and shall be thoroughly cleaned before making

the joints. In case of plain coupler joints, proper jointing material like a vinyl

solvent cement (gray in colour) or any material as recommended by the

manufacturer shall be used.

9.5 Conduit pipes shall be fixed by heavy gauge GI saddles fixed on MS spacers

(galvanized) secured to wall, ceiling with wood plugs or any other approved

plugs with screws and all in al approved manner. The spacers and saddles shall

be provided at a distance of not more that 60 cms. However, saddles shall be

fixed on either side of couplers or bends or similar fittings at a distance of not

more than 30D mm from the center of such fittings. PVC spacers and saddles

shall be used if specified.

9.6 Wherever necessary, bends or diversions may be achieved by bending the

conduits or by employing normal bends. No bends shall have radius less than

2.5 times outside diameter of the conduit. Bending spring of the correct size

Page 62: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.627 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

shall be used to form all bends in conduits. All bends in conduits shall be slow

hand made bends. Factory made bends, elbows, tees, and other fittings shall be

avoided as far as possible.

9.7 Conduit fittings shall be avoided as far as possible in outdoor installation.

9.8 The other requirement shall be as specified for conduit wiring system with rigid

steel conduits.

9.9 Sockets or couplings shall be of heavy duty type and shall not in any

circumstances be cut. Female bushes shall be of the smooth bore type

externally threaded.

9.10 No draw wires shall be left in conduit during erection of conduit. Conduits

shall be arranged for the drawing system and wiring shall not commence until

all ceiling and walls are plastered.

9.11 Concealed conduits shall be run in chase cut in block work or brickwork, fixed

by crampets or saddles at intervals of not more than 1.0 metre and deep enough

to allow for at least 12 mm of plaster or other rendering cover.

9.12 Conduit in in-situ concrete shall be installed in the center of the slab thickness

and fixed to the shuttering and reinforcing bars before the concrete is poured.

Conduit boxes for in-situ concrete slab shall be of the deep type to allow the

box to fit hard onto the shuttering. Conduit boxes shall be packed with an

easily removable materials prior to fixing to the shuttering to prevent ingress of

concrete during pouring. Extension rings shall be fitted to boxes after

shuttering is struck to allow for the finished face of the ring to be flush with the

Page 63: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.628 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

plaster surface. At expansion joints in the structure a suitable expansion

coupling shall be provided.

Conduit boxes shall normally be fitted at light points only. The approved shall

be obtained if the contractor require additional conduit boxes to be fitted in the

ceiling. Fan hook boxes shall be used for the fan points. Positions of all

lighting points shall harmonize with ceiling pattern. The contractor shall

ensure that all light points fit in with the architectural ceiling pattern prior to

fixing any points. All conduits boxes under boarded floors shall be readily

accessible for maintenance purposes.

Where a surface mounted accessory such as an isolating switch, bell etc. is

fixed to a concealed conduit, a flush fitting conduit box shall be fitted behind

the accessory to obviate conduit bending out of plaster wall surface, the surface

having a bushed or grommeted entry in the back for this purpose.

All the concealed conduits shall be cleaned and proved by drawing a mandrel

of slightly les diameter than the conduit immediately after de-shuttering. A

draw wire shall be laid in the conduit for pulling the cable in the conduit at

later stage.

All the conduits, junction boxes, switch boxes, pull boxes etc. shall be cleaned

immediately before pulling in the cables.

10. Boxes

10.1 Junction Boxes

All the boxes for junction boxes, pull boxes used in conduit wiring system shall

be fabricated from 1.5 mm thick mild sheet steel with two coats of enamel

paint of approved shade. The boxes shall have smooth external and internal

Page 64: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.629 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

finished surface. Separate screwed earth terminal shall be provided in the box

for earthing purpose. AH boxes shall have adequate no. of knock out holes of

required diameter for conduit entry.

The boxes shall be provided with a minimum of four fixing lugs located at the

corners for fixing the covers. All fixing lugs shall have tapped holes to take

machined brass screws. The boxes shall be sufficiently strong to resist

mechanical damage under normal service conditions. Wherever different phase

conductors are brought into the same enclosure, phase barriers shall be

provided. The boxes shall have removable covers at the top and bottom if

specified.

10.2 Switch boxes and outlet boxes

Switch boxes to receive switches, socket outlets, power cutlets, Telephone

outlets and fan regulators etc. shall be GI boxes as manufactured by the switch

manufacturer for erection of plate type switches.

The depth of the switch board boxes shall be 50 mm and the size shall be

selected so as to accommodate required number of switches, sockets and fan

regulators without overcrowding the box.

10.3 Fan Regulator

Fan regulators shall be incorporated in the front plate of switchboard and shall

form a single unit under one front plate in case of plate type switches erected

on GI boxes.

11. Cables

Page 65: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.630 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

11.1 All cables wires used for internal wiring shall be PVC isolated single core,

stranded conductor as specified and of 1100 volts grade and with copper

conductors.

11.2 The conductors shall be plain annealed circular copper conductor. The

minimum number and diameter of wires for circular stranded conductor shall

be as per relevant IS specifications. The insulation shall be PVC compound

complying with the requirements of IS specifications and the thickness of PVC

insulation shall be as set out in the relevant standards.

11.3 All wires shall be colour coded as follows :

Single Phase - Red

Three Phase - Red, Yellow, Blue

Neutral - Black

Earth - Green or Green/Yellow

(insulated)

Control (if any) - Grey

11.4 The wires shall be supplied in sealed coils of 100 mtrs. length and bear the

manufacturers name, trade mark, ISI mark, voltage grade etc.

11.5 Bunching of Cables

1. Wires carrying current shall be so bunched in the conduit that the

outgoing and return wires are drawn into the same conduit. Wires

originating from two different phases shall not be run in the same conduit.

2. The number of insulated wires/cables that may be drawn into the conduits

shall be as per the following table. In any case conduits having less than

20 mm diameter shall not be used.

3. Bunching of cables is rigid PVC conduits

Page 66: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.631 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

Maximum permissible number of single core cables that may be drawn in

to rigid PVC conduits.

Size of conduits (MM) Cable size in

sq.mm. 20 25 32 40

1.5

2.5

4.0

6.0

10.0

16.0

7

5

4

3

2

-

15

11

8

6

4

3

24

17

13

10

6

4

-

-

-

-

7

6

4. Bunching of cables in rigid steel conduits

Maximum permissible number of single core cables that can be drawn

into rigid steel conduits.

Size of conduits (MM) Cable size in

sq.mm. 20 25 32 40

1.5

2.5

4.0

6.0

10.0

16.0

6

5

4

3

2

2

11

9

7

5

4

2

-

-

-

8

6

4

-

-

-

-

-

6

12. Drawing of conductor

Page 67: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.632 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

12.1 No wire shall be drawn in to any conduit, until all work of any nature that may

cause injury 4o wire is complete. Care shall be taken in pulling the wires so

that no damage occurs to the insulation of the wire. Before the wires are drawn

into the conduits the conduits shall be thoroughly cleaned of moisture, dust,

and dirt or any other obstruction by forcing compressed air through the

conduits. The drawing and joining of copper conductor or wires shall be

executed with due regard to the following precautions.

12.2 While drawing insulated wires into the conduits, care shall be taken to avoid

scratches and kinks which may cause breakage of conductors. There shall be

no sharp bends in the conduit system.

12.3 Insulation shall be shaved off for a length of 15 mm at the end of wire like

sharpening of a pencil and it shall not be removed by cutting it square or

ringing.

12.4 Wire ends before connection shall be properly soldered (atleast 15 m length)

with special ALCAP soldering flux/copper solder, for copper conductor as the

case may be. All strands of wires shall be soldered at the end before

connection. The connecting brass-screws shall have flat ends.

12.5 Strands of wires shall not be cut for connecting to the terminals. The terminals

shall have adequate cross section to take all the strands.

12.6 All looped joints shall be soldered and connected through terminal block /

connectors. The pressure applied to tighten terminal screws shall be just

adequate, neither too much nor too less.

Page 68: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.633 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

12.7 Conductors having nominal cross section area exceeding 4 sq.mm. shall always

be provided with crimping type cable sockets.

12.8 At all bolted terminals, brass flat washer of large area and approved steel spring

washers shall be used. Brass nuts and bolts shall be used for all connections.

12.9 Only certified wiremen and cable jointers shall be employed to do jointing

work.

12.10 For all internal wiring PVC insulated wires of 650/1100 volts grade shall be

used. The sub-circuit wiring for point shall be carried out in looping system

and no joint shall be allowed in the length of the conductors.

12.11 Circuit wiring shall be provided with printed PVC identification ferrules at

either end bearing the circuit number and designation.

12.12 General wiring installation shall be as under.

a. Sub-main wiring

Wring from meter room to the distribution boards in individual tenements

shall be in concealed rigid PVC conduits.

b. Circuit wiring

Wiring from DB’s to point control boxes for lighting, fan, 5 A sockets call

bells etc. and from DS to the power sockets in the case of power wiring.

12.13 The sub-main wiring shall be either three phase, four wire or single phase, two

wire system. Each sub-main wiring circuit shall also have its own earth

continuity wire. The no. and size of earth continuity wire shall be as per

detailed drawings.

Page 69: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.634 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

12.14 The circuit wiring shall generally be in single phase system. However, a

maximum of 3 to 4 single phase circuits belonging to the same pole/phase

could be installed in the same conduit or raceway. Each circuit wiring shall be

provided with suitable earth continuity conductor as per standard

specifications.

12.15 No more than 10 light point/fan points shall be grouped on the one lighting

circuit. The load per circuit shall not exceed 800 watts. The minimum size of

conductor for wiring of lighting circuit shall not be less than 1.5 sq.mm. power

circuit wiring shall not have more than two sockets connected to one circuit.

13. Joints in the Wiring

The wiring shall be by looping system, and hence all joints shall be made at

main switches, distribution boards, socket outlets, lighting outlets and switch

boxes only. No joints shall be made inside conduits and junction boxes.

Conductors shall be continuous from outlet to outlet. For unavoidable joints

due to any reason prior permission shall be obtained before making such

connections. Joints by twisting conductors are prohibited.

14. Switches, socket and accessories

14.1 Switches

a. Switches shall confirm to IS:3854, IS:1293 and IS:4615. Switches shall be

single pole, single or two way as shown on the drawings. .

b. The switches shall be rocker operated with a quite operating mechanism

with bounce free snap action mechanism endorsed in an arc resistant

chamber. The switches shall have coated silver and silver cadmium

contacts. The switches installed in outdoor area shall be industrial, metal

clad type and shall be provided in weather proof enclosures, complete

with weath3er proof gasketed covers.

Page 70: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.635 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

c. Switches at the same location shall be ganged to form a single unit under

cover plate. Where fan regulators are to be provided with the

switchboards the same shall be incorporated.

14.2 Socket

a. The sockets shall conform to IS:1293. Each sockets shall be provided

with control switch of appropriate rating. The socket shall be molded

type, rated for 250 volts, and either of full 6 Amp or 16 Amp capacity as

mentioned.

b. Sockets shall be of three pin type, the third pin being connected to earth

continuity conductor. The socket shall be flush modular type. The

sockets installed in machine room, plant room or wet/damp areas shall be

metal or weather proof type. The socket shall have fully spring socket

contacts and solid brass shrouded terminal to ensure positive electrical

connections.

c. If specified, the sockets shall be provided with automatic shutters, which

opens only when earth pin of the plug inserts in the sockets and provided

with three pin plug top suitable to the socket and of the same make as

socket.

d. All 6 A sockets, 16 A switched sockets, DP switches, connector boxes etc.

shall be as specified and with the finishing and make same as fighting

switches. These shall be erected on the boxes as specified in drawings.

14.3 Industrial type sockets

Industrial type sockets shall be provided wherever specifically called for,

industrial sockets shall be totally metal dad with porcelain base incorporating

the pins. Sockets shall have 3 pins for single phase applications and 4 pins and

Page 71: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.636 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

scrapping earth for 3 phase applications. The sockets shall be provided with

suitable metal clad plug top suitable for cable entry. Sockets shall have metal

covers with chain. Industrial type sockets shall be provided with a suitable

sheet steel housing made of 16 gauge with the socket mounted in flush with

cover of the housing.

14.4 Lamp holder, ceiling roses etc.

Accessories for light outlets such as lamp holders, ceiling roses, etc. shall be

white in colour and in conformity with requirements of relevant IS

specification. Ceiling roses shall be 3 plate type wherever specified. Angle

holder and batten holder shall be erected on the junction boxes erected on wall

/ ceiling.

14.5 Installation of switch, socket and accessories

a. Connection tol be made only after testing the wires for continuity, cross

phase etc. with the help of a megger.

b. The switch controlling the light point or fan shall be connected on to the

phase wire of the circuit and neutral shall be continuous, having no fuse or

switch installed in the line except at the D.B. the third pin of the socket

shall be connected to the earth continuity conductor of the circuit.

c. Outlets shall be terminated into ceiling rose for ceiling mounted points.

For other wall light points the outlets shall be connected in to a angle

holder. For wall plug sockets the conductors may be terminated directly

into the switches and sockets.

d. The position of all outlets, point control boxes etc. shall be set out as

shown on the drawing but before fixing these, the contractor shall obtain

the prior clearance from the engineer with regard to their proper location.

e. The switch boxes, installed back to back in the same wall shall be offset

from each other, 150 mm horizontally.

Page 72: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.637 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

15. Earthing

15.1 All earthing systems shall be in accordance with IS: 3043 code of practice for

earthing. The type and size of earthing wire shall be as specified separately

and in Schedule ‘A’ and drawings.

15.2 The earth continuity conductor shall be similar to circuit cables and shall be

drawn through conduit along with other circuit cables. Separate circuit shall

run for each water heater, kitchen equipment, window air conditioner and

similar outlets at location as shown on drawings.

16. Testing and Commissioning of installation

Before a completed installation is put into service, the testing of the installation

shall be done as per IS:732.

16.1 Insulation Resistance

1. The insulation resistance shall be measured by applying 500 volt megger

with all fuses in places, circuit breaker and all switches dosed.

2. The insulation resistance in mega ohms of an installation, measured shall

not be less than 50 mega ohms divided by the number of points on the

circuits provided that the whole installation shall be required to have an

insulation resistance grater than one mega ohms.

3. The insulation resistance shall be measured between

a. Earth to Phase

b. Earth to Neutral

c. Phase to Neutral

16.2 Earth continuity path

Page 73: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.638 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

The earth continuity conductors shall be tested for electrical continuity and the

electrical resistance of the same along with the earth lead but excluding any

added resistance or earth leakage circuit breaker, measured from the

connection, with the earth electrode to any point in the earth continuity

conductor in the completed installation and shall not exceed on ohm.

16.3 Polarity of single pole switches

1. A test shall be made to verify that every non linked, single pole switch is

connected to one of the phase of the supply system.

2. In a two wire installation a test shall be made to verify that al non linked

single pole switches have been fitted in the same conductor throughout

and such conductor shall be labeled or marked for connection to an outer

or phase conductor or to the non earthed conductor of the supply.

3. In a three wire or four wire installation a test shall be made to verify that

every non linked single pole switch is fitted in a conductor and which

shall be labeled or marked for connection to one of the outer or phase

conductor of the supply.

16.4 Completion certificates

1. All the above tests shall be carried out in presence of the Engineer in

charge and the results shall be recorded in the prescribed forms. Any

default during the testing shall be immediately rectified and that section of

the installation shall be re tested. The completed test result forms shall be

submitted to the Engineer in charge for approval.

2. On completion of an electric installation a certificate shall be furnished by

the contractor, countersigned by the certified supervisor under whose

direct supervision the installation was carried out. This certificate shall be

in a prescribed form as required by the local electric supply authorities.

Page 74: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.639 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

__________________ ________________________________ Signature of Tenderer Chief Engineer & General Manager (T)

Date : Date :

Page 75: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.640 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

MCB DB, MCB & RCCB

1. Miniature Circuit Breaker Distribution Boards

1.1 Miniature Circuit Breaker Distribution Boards shall conform to IS:2675,

IS:8623 and shall be suitable for operation on three phase, 4 wire, 415 V, 50

Hz, AC supply or single phase, 2 wire, 230 V, 50 Hz, AC supply.

1.2 The MCB distribution board shall be in sheet steel endorses with removable

type cover with additional acrylic door for procting accidental operation. All

the MCB type distribution boards shall be similar to MDS sleek model series

3000 with 100 A busbar capacity.

1.3 Endorser and door shall be made out of 2 mm thick CRCA sheet steel and two

tone power coated and of approved shade. The interior shall be of white finish.

The DB shall be totally enclosed with dust and vermin proof construction and

shall be of domestic pattern.

1.4 Where distribution boards are specified to be complete with an isolator as

incomer, the isolator shall be double pole for SP and N distribution boards and

4 pole for TP and N distribution boards.

1.5 Where distribution boards are specified to be complete with MCB+ELCB as

incomer, the MCB + ELCB shall be double pole for SP and N distribution

boards and 4 pole for TP and N distribution boards.

1.6 Bus bars shall be tinned copper rated 100 Amp. The internal connections in the

DB shall be by using stranded copper conductor, PVC insulated wire with

copper lugs crimped at both ends. Neutral busbar and earth busbars shall also

Page 76: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.641 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

be provided in the enclosure. Neutral busbar shall have equal rating of phase

busbars.

1.7 Distribution boards shall be provided with circuit identification by means of

directory on the front cover. Upon completion of the works, the contractor shall

provide and fix accurate framed circuit lists for all distribution boards. These

shall consist of Perspex envelopes, fixed securely by an approved method on

the inside face of each distribution board front cover into which shall be

inserted a neatly typed list of circuits, indicating the number of circuits, phase,

cable, size, number of points connected, circuit rating and the loading.

The contractor, shall also provide and fix by means of brass screws tapped into

the DB cover, labels, with black letter on a white background with black letter

on a white background for all distribution boards, MCB + ELCB, isolators etc.

The engraving on the labels and the inscription on the circuit lists shall be

approved by the Consultants before the work is carried out.

1.8 All incoming terminals shall be fully shrouded.

1.9 The conduit entry plates shall be removable type and shall be provided at top

and bottom. All the conduits shall be properly terminated using Glands, grips,

check nuts, female adapters with bush etc.

1.10 Wiring shall be terminated properly using crimping type copper lugs / sockets,

identification ferrules shall be provided on all wires.

1.11 2 no. earth terminals shall be provided on each Distribution Board.

Page 77: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.642 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

1.12 Distribution boards shall be installed surface mounted or recessed mounted as

specified and erected at the locations shown.

Surface mounted DB shall be mounted on a suitable size frame made out of

angle iron. The hole fasts of the angle iron frame shall be grouted in the wall

with cement mortar and the frame shall be painted with two coats of red oxide

and two coats of enamel paint of approved shade. The DB shall be mounted on

this frame with proper size nut bolts.

Recessed molded DB shall be erected in the chase/cut portion of the wall. The

cutting of the walls shall be done while constructing the wall and shall be of

adequate size to comfortably accommodate the DB. The cut portion shall be

smoothened and made plain and shall be of fine finished. The DB shall be

fixed in this chased portion with suitable damps and bolts. The top cover of the

DB cabinet shall be projecting out of the wall surface and free from any

obstruction so as to open the same smoothly.

2. Miniature Circuit Breakers

2.1 MCB’s shall be manufactured in accordance with IS:8828 having a short

circuit breaking capacity category M9-9000 Amps at both 240 volts 50 Hz and

240/415 V, 50 Hz and complying with the test requirements for both reference

calibration temperatures of 20 degree C and 40 degree C.

2.2 All miniature circuit breakers shall be rated to withstand the fault currents of

the circuits they protect without causing any interference in any other

protective device associated with the distribution system. At the same time the

design of Ca circuit breakers shall be such that, it will protect the circuit for

which it is intended and not cause or allow other protective devices to operate

when fault conditions apply.

Page 78: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.643 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

2.3 Miniature circuit breakers shall be capable of carrying its full rated current

continuously without tripping out.

2.4 All the miniature circuit breakers shall be fitted with a magnetic undelayed

tripping mechanism.

3. Residual Current Operated Circuit Breakers (RCCB)

3.1 RCCB’s shall be manufactured in accordance with IS : 12640 and IS : 8828

having a short circuit breaking and earth fault protection up to 9 KA at both

240 Volts 50 Hz and 240/415 V, 50 Hz and complying with the test

requirements as per IS : 2640.

3.2 RCCB shall be designed to interrupt the circuit during and earth fault, overload

or short circuit. Al RCCB shall be high sensitive and calibrated to trip the

power supply when the residual current is more than 50% of its calibrated

rating. This means that a 30 MA sensitivity RCCB should trip when the

residual current is in the range of 15 to 30 mA and a 300 mA RCCB should trip

open the residual current is in the range of 150 to 300 mA.

3.3 The RCCB’s shall be truly current operated, which means that it shall be totally

independent of the mains voltage for tripping. RCCB must operate for nominal

voltage well below the maximum safe value of 10 volts. RCCB shall interrupts

the circuit within 30 mS at a leakage current of 30 mA.

3.4 RCCB shall be provided with a neutral advance mechanism. RCCB shall be

functioning even in the event of failure of neutral and/or any one or two of

phase supply conductor. RCCB shall be provided with trip free mechanism

ensuring that the device cannot be reclosed/reset if the fault persists. RCCB

Page 79: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.644 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

shall be functioning even in the case interchange of load and supply side

connections.

3.5 Test button shall be provided to check the correct operation of the unit.

3.6 RCCB shall be designed for a very long life of a minimum of 20,000

operations and shall be capable of withstanding inrush current of 4 to 8 times

the rates current. For the proper functioning the RCCB should not require any

connection of earthing on the device.

3.7 The device should have high tripping accuracy of less than 5% of rated tripping

current. The RCCB shall be provided with dear indication to show whether the

tripping is due to current leakage or overload/short circuit.

3.8 The MCB section of RCCB shall be provided with arc chambers and vents are

also to be provided to release the arcing products in the atmosphere, so as to

increase contact lift and to prevent damage to the insulation. The self

extinguishing thermo set plastic material shall be used for body and shall have

a modular construction. The device should be vibration proof.

__________________ ________________________________ Signature of Tenderer Chief Engineer & General Manager (T)

Date : Date :

Page 80: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.645 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

EARTHING

1. Scope

This specification covers supply of necessary materials, and erection at site, of

complete earthing system including earth pits at the locations indicated, earth

conductors from earth pit to the respective equipments, switchgears, pillars etc.

and making connections, testing at site, commissioning and handing over.

2. Applicable standards

The entire work of earthing system, shall conform to IS: 3043, Indian

Electricity Act and Rules and relevant regulations.

3. General requirements

3.1 The earthing shall generally be carried out in accordance with the requirements

of Indian Electricity Rules 1956 as amended from time to time and relevant

regulations. The following IE rules are particularly applicable I.E. Rule Nos.

32, 51, 61, 62, 67, 69, 88(2) and 90.

3.2 All earth connections shall be carefully made, visible for inspection, and the

testing of individual earth electrode shall be possible.

3.3 All materials, fittings etc. used in earthing shall conform to IS specifications

and in the absence of which the approval of competent authority shall be

obtained.

3.4 The earthing electrode shall be at a minimum distance of 2 meters away from

the outer face of the building wall. A minimum durance of twice the depth of

the electrode shall be maintained between two earthing station.

Page 81: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.646 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

3.5 A brick masonry chamber to facilitate easy identification and for carrying out

periodical tests and inspection shall be constructed on top of the earth pit.

3.6 All metal conduits, trucking, cable sheets, HT and MV switchgears,

Transformers, distribution boards, meters, light fixtures, fans, and all other

metal parts forming part of the work shall be bonded together and connected to

earthing network as specified.

3.7 Earthing system shall be mechanically robust and the joints shall be capable of

retaining low resistance even after passege of fault currents.

3.8 Joints shall be soldered, tinned and double riveted. All the joints shall be

mechanically, electrically continuous and effective. Joints shall be provided

against corrosion.

4. Earth Electrodes

4.1 The materials of earth electrode and earth conductors shall be galvanized iron

unless specified otherwise in Schedule ‘A’, specifications or drawings.

4.2 The earth electrodes shall be free from paint, enamel, grease etc.

4.3 The earth electrode shall be embedded as far as practicable in a moist soil and

below permanent moist level.

4.4 The earth electrode shall not be installed in the proximity of a metal fence.

5. Types of Earth Electrodes

The earth electrodes shall be either a pipe electrode or plate electrode, the

details of which are as given in the following sections of specifications,

drawings and Schedule ‘A’

Page 82: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.647 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

6. Pipe Electrodes

6.1 Pipe electrodes shall consist of 2.5 meter long single piece G.I. pipe of min. 40

mm dia as specified and shall be cut tapered at the bottom. 12 mm dia holes

shall be drilled with 75 mm spacing between the holes and in a staggered

manner as indicated in IS:3043.

6.2 The electrode shall be buried vertically in a specially prepared earth pit of size

35 cm x 35 cm and the earth pit shall be filled with ultimate layers of charcoal,

salt and fine washed sand for a minimum thickness of 150 mm. A funnel with

wire mesh inside shall be fixed to the top of the GI pipe for watering purpose.

6.3 The earth conductor of 25 x 3 mm GI strip shall be connected to the electrode

just below the funnel with proper terminal Lugs and check nuts and the other

end of earth conductor shall be connected to the equipotential bus of the

equipment.

6.4 A masonry chamber with with a cast iron cover hinged to the cast iron frame

embedded in the top portion of the masonry shall be constructed on the top of

the G.I. pipe to house the funnel and the earth connection. The approximate

size of the chamber shall be 300 mm x 300 mm and 300 mm deep.

6.5 The earth conductor from electrode shall be taken out of the masonry chamber

through a protecting pipe embedded in masonry.

6.6 The top of the masonry chamber shall be 50 mm above the finished ground

level.

Page 83: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.648 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

7.0 Plate Electrode

7.1 The plate electrode shall consist of either copper plate of size 60 cm x 60 cm x

3.15 mm or G.I plate of size 60 cm x 60 cm x 6.3 mm , and as specified in the

schedule ‘A’ of drawing.

7.2 The electrode shall be buried vertically in a specially prepared earth pit which

shall be dug upto 2.5 m depth, from the ground level. The earth plate shall be

laced in the earth pit with its faces vertical and embedded in the alternate layers

of coal and salt for a minimum thickness of 15 cms.

7.3 The earth conductor shall of same material as of the earth electrode. For

copper earth electrode copper strips shall be provide as conductor and for GI

earth electrode GI strips shall be used as earth conductor.

The size and material of the earth conductor shall be as specified separately in

the Schedule ‘A’ or drawings. The earth conductors shall be connected to the

earth electrode (Plate) with G.I. nut bolts, check nuts and washers and welded

at the edges and shall be brought up in the masonry chamber at the ground

level.

7.4 The earth conductor shall be extended via the earth link provided in the

masonry chamber. This link shall be corrected to earth conductors from the

earth plate and earth conductor going to equipment with two nos. of nut-bolts,

check nut and washers (all of G.I.) make secured connections. This link can be

removed in the chamber for testing the earthing.

7.5 A 20 mm dia GI pipe shall be provided from the masonry chamber to the top of

the earth plate for watering purpose. The GI pipe shall be provided with a

funnel at the top with wire mesh inside.

Page 84: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.649 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

7.6 A masonry chamber with a cast iron cover hinged to the cast iron frame

embedded in the top portion of the masonry shall be constructed on top of the

GI pipe to house the funnel and the earth connection. The approximate size of

the chamber shall be 300 mm x 300 mm and 300 mm dep.

7.7 The earth conductor from electrode shall be taken out of the masonry chamber

through a protecting pipe embedded in the masonry.

7.8 The top of the masonry chamber shall be 50 mm above the finished ground

level.

8. Earth Conductor

All earthing conductors shall be high conductivity copper and or GI as

specified and shall be protected against mechanical injury or corrosion. The

connection of earth continuity conductors of earth bus and earth electrodes

shall be strong and sound and shall be rigidly fixed to the walls, cable trenches,

cable trays or conduits and cables by using suitable damps made of non ferrous

metals.

8.1 The cross-sectional area of earthing conductor shall not be smaller than half

that of the largest current carrying conductor, subject to the minimum size

being not less 1.5 sq.mm. for copper and 2.5 sq.mm. for aluminum conductors

and the upper limit being 10 sq.mm. for copper and 120 sq.mm. for aluminum.

The size of the galvanized iron earth continuity conductors may be equal to the

size of the current carrying conductors with which they are to be used.

8.2 As a guide line the following sizes of earth continuity conductors shall be used

for earthing installation.

Page 85: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.650 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

8.2.1 Size of earth conductors for lighting and power circuits.

Cross sectional area of current

carrying conductor copper

Cross sectional area of earth

continuity conductor Copper

Size in Sq.mm. Size in Sq.mm.

1.5

2.5

4.0

6.0

1.5

1.5

2.5

4.0

8.2.2 Size of earth conductors from main switch board to sub-main switches or

distribution boards.

Cross sectional area of current

carrying conductor copper/Alum.

Cross sectional area of earth

continuity conductor Copper

Size in Sq.mm. Size in Sq.mm.

4

6

10

16

25

35

50

70

95

120

2.5

4

6

10

16

16

25

35

50

70

Page 86: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.651 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

8.2.3 The size of an earth continuity conductor contained in a flexible cable or

flexible cord shall be equal to that of the current carrying conductor.

9. Earth Connection

9.1 All metal clad switches and other equipment carrying single phase current

shall be connected to earth by a single connection. All metal dad switches

carrying three phase medium voltage and high voltage shall be connected with

earth by two separate and distinct connections.

9.2 The earthing conductors inside the building, wherever exposed shall be

properly protected from mechanical injury by running the same in G.I. pipe of

adequate size. Earthing conductors outside the building shall be laid 600 mm

below the finished ground level.

9.3 The over lapping of strips at joints where required shall be minimum 75 mm.

The joints shall be reverted in an approved manner. Lugs of adequate capacity

and size shall be used for all termination of wires above 6 sq.mm. size and bare

copper wire above 2.5 mm dia lugs shall be bolted to the equipment body to be

earthed after the metal body is cleaned of paint and other oily substance and

properly tinned.

10. Connection of Earthing Conductor

The earthing conductors are broadly divided in the following categories.

10.1 Main earthing conductor shall be taken from the earth electrode to the earth

bus/connection at the main switch board.

10.2 Sub-main earthing conductor shall run from the main switch board to the sub-

distribution boards.

Page 87: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.652 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

10.3 Final earthing conductor shall run from the sub-distribution boards to the final

distribution boards.

10.4 Circuit earthing conductor shall run from the final distribution board to the

exposed metal of the equipment to be earthed. This may run directly from final

distribution boards or through earth leakage circuit breaker.

10.5 Metal conduits, cable sheathing and armoring shall be earthed at the ends

adjacent to switch boards at which they originate or at the commencement of

the run by the earthing conductor.

10.6 Earthing conductor endorsed with the current carrying conductors within the

flexible cord shall be used only incase of equipments connected by flexible

cord.

10.7 Lighting fittings, switches and accessories shall also be provided with an

earthing conductor even though they may be rigidly secured/fixed with metallic

conduit.

10.8 The electrical resistance of earthing conductors shall be low enough to permit

passage of fault current necessary to operate a fuse, protective device or a

circuit breaker.

11. Prohibited Connection

Use of following as earth conductor is not recommended, and strictly

prohibited for earthing an installation or even as a link in an earthing system.

Neutral conductor, sprinkler pipes or pipes conveying gas, water or

inflammable liquid, structural steel work, metallic enclosures or armour of

Page 88: TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD …cidco.maharashtra.etenders.in/tnduploads/cidco/tndheader/TND... · TECHNICAL SPECIFICATIONS FOR AC DISTRIBUTION BOARD ... latest

CIDCO OF MAHARASHTRA LIMITED Sl.Pg.No.653 C.A.NO.10/CIDCO/SE(ULWE)/EE(B&U-I)/2010-11

cables and conductors, metallic conduits and lighting protection system

conductors are all prohibited to be used as earth conductor.

12. Earth Resistance

The earth resistively of the soil where the earthing stations are located shall be

submitted to the owner before the earthing work starts and the approval of the

owner shall be taken. If the earth resistance is to high and multiple electrode

earthing does not give adequate low resistance to earth, then the soil resistively

immediately surrounding the earth electrodes shall be reduced by adding

sodium chloride, calcium chloride, sodium carbonate.

13. Testing

On completion of the entire installation, the earthing network shall be tested for

their resistance to earth in accordance with IS:3043. All meters, instruments

and labour required for the tests shall be provided by the contractor. The test

results shall be submitted in triplicate to the owners for approval. The

following tests shall be conducted.

1. Earth resistance of electrodes

2. Independence of earth continuity conductors.

3. Effectiveness of earthing

__________________ ________________________________ Signature of Tenderer Chief Engineer & General Manager (T)

Date : Date :