technical specifications · ecg2 mecc-alte ecp 34-2s / 4 100 kva 110 kva (400 / 230 v) 415/240 50 3...
TRANSCRIPT
TECHNICAL SPECIFICATIONS
Image for guidance purposes.
Model:
VOLTAGE HZ PHASE COS Ø PRP KVA/KW LTP KVA/KW AMPERAGE
Amperes in the different voltages:
STAND-BY POWER:(LTP “Limited Time Power” norma ISO 8528-1)
CONTINUOUS POWER:(PRP “Prime Power” norma ISO 8528-1)
ENGINE
ALTERNATOR
MAKE MODEL
MODEL
These details shown on this datasheet are intended for guidance only. Inmesol reserves the right to change the details without prior notice. The present documents will not be part of any sales contract.
DEUTZ BF4M 1013ECG2
MECC-ALTE ECP 34-2S / 4
100 kVA
110 kVA
(400 / 230 V)
415/240 50 3 0,8 105,0/84,0 110,8/88,6 154,27
400/230 50 3 0,8 105,0/84,0 110,8/88,6 160,05
380/220 50 3 0,8 105,0/84,0 110,8/88,6 168,47
240/139 50 3 0,8 105,0/84,0 110,8/88,6 266,75
230/133 50 3 0,8 105,0/84,0 110,8/88,6 278,35
220/127 50 3 0,8 105,0/84,0 110,8/88,6 291
IDT100S - DEUTZ - BF4M 1013 ECG2 1.500 R.P.M. | 50 Hz
IDT100SGenerator set with manualor automatic control panel.
INMESOL, S.L.
Power PRP (kWm)
Power LTP (kWm)
No. cylinders
Cylinder capacity (L)
Diameter per stroke (mm)
Compression ratio
Cooling system
Injection
Suction
Series regulator
Steering wheel coupling
Oil capacity (L)
Oil consumption (%)
Min. alarm oil pressure (bar)
Aircoolingflow(m3/h)
Combustionairflow(m3/h)
Max. back pressure for fan (mbar)
Exhaustgasflow(m3/h)
Exhaust back pressure (mbar)
Temp. exhaust gases (ºC))
VDC (V)
Battery (Ah)
Engine start-up (kW)
Lubrication system
Ventilation system
Exhaust system
Electrical system
GENERAL DATA
ENGINE CHARACTERISTICS
MAKE MODEL
These details shown on this datasheet are intended for guidance only. Inmesol reserves the right to change the details without prior notice. The present documents will not be part of any sales contract.
DEUTZ BF4M 1013 ECG2
91.10
96.10
4
4.76
108 x 130
19
LIQUID
DIRECT
TURBO-INTERC.
MECHANICAL
-
11
0.30
2.70
6100
365
0
1102
30
560
12
96
3
IDT100S - DEUTZ - BF4M 1013 ECG2 1.500 R.P.M. | 50 Hz
INMESOL, S.L.
GENERAL DATA
ALTERNATOR CHARACTERISTICS
MODEL
%POWERUSED LITRES/HOUR
DIMENSIONS, CAPACITIES AND APPROXIMATE WEIGHT
GENERATOR SET CONSUMPTION
FUEL TANK (LITRES)
WEIGHT(KG)
DIMENSIONS (MM) LENGTH WIDTH HEIGHT
Power PRP (kVA)
Power LTP (kVA)
EfficiencyAlt.3/4%
EfficiencyAlt.4/4%
No. Poles
Voltage regulator
No. wires
Insulation
Xd (%)
X’d (%)
X
Degree of protection
These details shown on this datasheet are intended for guidance only. Inmesol reserves the right to change the details without prior notice. The present documents will not be part of any sales contract.
MECC-ALTE ECP 34-2S / 4 (400 / 230 V)
105
115.50
92.50
92.20
4
DSR
12
H
230
17.60
7.40
IP21
50%
75%
100%
13.10
19.30
25.80
3000 1200 1614
220.00
1900.00
IDT100S - DEUTZ - BF4M 1013 ECG2 1.500 R.P.M. | 50 Hz
INMESOL, S.L.
GENERAL DESCRIPTION
The “INMESOL” generator set is an electrical energy generating machine which is used in places where there is no mains supply or when there is a MAINS failure.
The mobile elements, distribution belt, fan, etc., and those parts which reach high temperatures during operation, exhaust manifold, etc, include their corresponding protections, in compliance with the requirements of the Machinery Directive 2006/42.
REGULATIONS
The machine holds the “CE” marking, and the corresponding Declaration of Conformity isissuedwitheachofthem,inwhichitspecifiesthatthemachinecomplieswithR.D 842/2002 Low Voltage Regulations and with the European Directives:
2006/42onSafetyinMachinery. ▪
2006/95/CEonElectricalSafety. ▪
2004/108/CEonElectromagneticCompatibility. ▪
2005/88/CE on NOISE EMISSIONS by equipment for outdoor use (for ▪SOUNDPROOF GENERATOR SETS).
INMESOL GENERATOR SET
These details shown on this datasheet are intended for guidance only. Inmesol reserves the right to change the details without prior notice. The present documents will not be part of any sales contract.
IDT100S - DEUTZ - BF4M 1013 ECG2 1.500 R.P.M. | 50 Hz
INMESOL, S.L.
INDUSTRIAL RANGE / SCOPE OF SUPPLYIN
Engine/alternator monobloc directly connected and installed via silent blocks on a frame made from high tensile electro welded steel profiles that are treated with degreasing liquids and aplicated with a phosphate coat and epoxi paint.
Canopy of steel sheet sound proofed with fireproof rockwool, and treated with degreasing liquids and aplicated with a phosphate coat and epoxi paint.
Fuel tank integrated in the base frame provided with fuel level jauge and fuel connections to the engine.
Engine with mechanical engine driven pusher fan.
Industrial silencer with -15 db(A) noise reduction and exhaust outlet tube.
Residencial silencer with -35 db(A) noise reduction with exhaust tube and protection cap.
Electric control cubicle with control module including protection and reading of electrical meassures engine instrumentation fuel level and engine running hours, etc.
Termal and magnetic circuit breaker and termal and magnetic circuit breaker and earth fault relay.
Battery charge alternator.
Starter battery complete with cables to the engine and pole protection.
Installation prepared for earthing spike (spike not included).
Security protection for heat and moving parts as well as live electrical components.
External emergency stop push button.
Manual engine oil extraction pump.
Self excited and auto regulated alternator.
Integrated lifting hook for single point lifting with crane, gensets up to 450 kVA.
4 Lifting points for gen sets from 250 kVA and bigger.
Preparate for extended fuel tank, fully bomded for leakage protection.
Base frame is prepared for trailer kit installation.
Standard electronic speed governor on engines from 220 kVA (LTP) and up.
These details shown on this datasheet are intended for guidance only. Inmesol reserves the right to change the details without prior notice. The present documents will not be part of any sales contract.
IDT100S - DEUTZ - BF4M 1013 ECG2 1.500 R.P.M. | 50 Hz
DSE 3110 MANUAL CONTROL PANEL
MANUAL CONTROL, PROTECTION AND DISTRIBUTION panel, assembled on the generator set in metal cabinet with a DSE 3110 engine protection unit.
DSE 3110 MANUAL CONTROL PANEL
Image for guidance purposes.
These details shown on this datasheet are intended for guidance only. Inmesol reserves the right to change the details without prior notice. The present documents will not be part of any sales contract.
CONTACT US FOR DETAILED DATA SHEETS AND OTHER CONTROL PANEL OPTIONS
SOUNDPROOFED GENERATOR SETS
DSE 6020 AUTOMATIC CONTROL PANEL
PROTECTION, DISTRIBUTION AND AUTOMATIC CONTROL panel which starts the generator set when it detects a mains failure and stops it when the mains is restored with the control unit DSE 6020. It also starts and stops the group manually via a pushbutton or remote start-up by contact
DSE 6020 AUTOMATIC CONTROL PANEL
These details shown on this datasheet are intended for guidance only. Inmesol reserves the right to change the details without prior notice. The present documents will not be part of any sales contract.
Image for guidance purposes.
CONTACT US FOR DETAILED DATA SHEETS AND OTHER CONTROL PANEL OPTIONS
SOUNDPROOFED GENERATOR SETS