Technical Note
ILX69-PBM with Siemens DP/PA
Coupler Setup PROFIBUS DPV1 Master for CompactLogix Document Code: TN01-ILX69PBM-17
Author: Jose Carrillo
Date: April 24, 2017
(replace with correct product logo)
Technical Note Document Code: TN01-ILX69PBM-17
ProSoft Technology, Inc. ILX69-PBM with Siemens DP/PA Coupler Setup December 18, 2018 Page 2 of 9
Document Information
Author Jose Carrillo
Description ILX69-PBM setup using a Siemens DP/PA coupler
Date April 24, 2017
Revision 1.0
Product Name ILX69-PBM
Document Code TN01-ILX69PBM-17
ProSoft Technology 9201 Camino Media Suite 200
Bakersfield, CA 93311
+1 (661) 716-5100
+1 (661) 716-5101 (Fax) www.prosoft-technology.com
Copyright © ProSoft Technology, Inc. 2009. All Rights Reserved.
November 05, 2009
ProSoft Technology ® ProLinx ®, inRAx ®, ProTalk®, and RadioLinx ® are Registered Trademarks of ProSoft Technology,
Inc. All other brand or product names are or may be trademarks of, and are used to identify products and services of, their respective owners.
How to contact us: Sales & Support All ProSoft Technology® products are backed with unlimited technical support. Contact our worldwide Technical Support team directly by phone or email:
Asia Pacific +603.7724.2080, [email protected] Languages spoken include: Chinese, Japanese, English
Europe – Middle East – Africa +33 (0) 5.34.36.87.20, [email protected]
Languages spoken include: French, English
[email protected], fax to +33 (0) 5.61.78.40.52
North America +1.661.716.5100, [email protected]
Languages spoken include: English, Spanish
fax to +1 661.716.5101
Latin America (Sales only) +1.281.298.9109, [email protected]
Languages spoken include: Spanish, English
Brasil +55-11.5084.5178, [email protected] Languages spoken include: Portuguese, English
Technical Note Document Code: TN01-ILX69PBM-17
ProSoft Technology, Inc. ILX69-PBM with Siemens DP/PA Coupler Setup December 18, 2018 Page 3 of 9
Contents
Document Information .............................................................................................................................2
ILX69-PBM USING SIEMENS DP/PA COUPLER ..................................................................................4
Overview ..................................................................................................................................................4 Test Setup .................................................................................................................................................4 Procedure ..................................................................................................................................................4
Technical Note Document Code: TN01-ILX69PBM-17
ProSoft Technology, Inc. ILX69-PBM with Siemens DP/PA Coupler Setup December 18, 2018 Page 4 of 9
ILX69-PBM using SIEMENS DP/PA Coupler
Overview This document was created to detail the setup process when using the ILX69-PBM with a SIEMENS DP/PA Coupler that allows our PROFIBUS DP master device to communicate with a PROFIBUS PA network.
Test Setup
Procedure Open ProSoft fdt Configuration and start a new Project, follow the prompt to begin configuring your PBM device.
Technical Note Document Code: TN01-ILX69PBM-17
ProSoft Technology, Inc. ILX69-PBM with Siemens DP/PA Coupler Setup December 18, 2018 Page 5 of 9
After setting the IP address and selecting the device, configure your slave within the project by installing necessary GSD files (if required).
*Note that the SIEMENS DP/PA Coupler is a transparent device when setting up the network. This means that there is no
configuration necessary for the coupler and does not have to be added to the bus network. The default baud rate instructed by SIEMENS for their coupler is 45.45 kBits/s [set the PBM to this baud rate under the bus parameters].
Technical Note Document Code: TN01-ILX69PBM-17
ProSoft Technology, Inc. ILX69-PBM with Siemens DP/PA Coupler Setup December 18, 2018 Page 6 of 9
Download project to PBM. Connect to device and open diagnostics. Double-clicking on the master, user can determine if PBM is communicating with PA Slave device. Notice that the PBM is not communicating with the PA Slave.
After testing this set up, it was determined that the value of the Slot time was not high enough to allow communication between
the PBM and target slave device. The initial default of 100 tBit was not enough time for the DP to wait for a response from the slave.
Increase the Slot time to a higher value (tested time of 640 tBit on the 1 slave network) and download to PBM.
Technical Note Document Code: TN01-ILX69PBM-17
ProSoft Technology, Inc. ILX69-PBM with Siemens DP/PA Coupler Setup December 18, 2018 Page 7 of 9
After downloading the new Slot Time, the PBM and PA slave start communicating.
[PBM Diagnosis window]
[PA Slave Diagnosis window]
Technical Note Document Code: TN01-ILX69PBM-17
ProSoft Technology, Inc. ILX69-PBM with Siemens DP/PA Coupler Setup December 18, 2018 Page 8 of 9
Reference If user has a large network to configure (multiple PA Slaves) and the slot time is unknown for the project or if user is unsure of
the Slot time value, user can use ProSoft Configuration Builder (PCB) to configure their network and have the program calculate
the bus parameters is communication issue occur.
Start PCB and add the MVI69-PDPMV1 module to the project.
Launch the PROFIBUS DP Master Setup tool [highlighted in blue above] and click ‘Configure PROFIBUS’
In this window, install the GSD files for the slaves to be used and configure your Bus network.
Technical Note Document Code: TN01-ILX69PBM-17
ProSoft Technology, Inc. ILX69-PBM with Siemens DP/PA Coupler Setup December 18, 2018 Page 9 of 9
After installing your slaves, double-click on the PROFIBUS Master and look under the PROFIBUS tab and select the Baud Rate
of 45.45 kBit/s [as detailed for the SIEMENS DP/PA Coupler] and the DP Profile.
Finally, look under the Bus Parameter tab and note the values predefined in this section. Using these values, manually configure the Bus parameters in the ProSoft fdt Configuration Manager and follow the download instructions.