Technical Cleaning
�������������� ��������
JUSTIFICATION
Cleaning of Data Centers and Communications Rooms should be performed by
qualified personnel who will use techniques and equipment designed to clean
without re-contaminating environment or disrupt the Data Center and
Communications Rooms.
Surface cleaning of racks and above pipes is done by using a damp cloth and Surface cleaning of racks and above pipes is done by using a damp cloth and
vacuum, then the gap between the soil and subsoil (most important area of the
Data Center for cleanliness), as it is the plenum generally where the cold air is
distributed. It is also the most critical site because dust and dirt accumulates.
It is very important to properly clean the floor tiles of the Data Center that are
designed to dissipate static electricity. Dirt reduces electrostatic dissipating
property of these tiles. Should be cleaned one by one all those to which access is
outside the room and install again and level.
BENEFITS OF TECHNICAL CLEANING
- Extend the life of the new equipment in the rooms, avoiding contamination
thereof.
- Minimize the risk of fire due to the accumulated dust on the hardware.
- Avoid electro static discharge causing transmission failure between
computers.
- Avoid the existence of ferrous material (oxides).
- To minimize mechanical wear and hardware failures. - To minimize mechanical wear and hardware failures.
- Minimize air pollution
- Remove contaminants alive
- Avoid cleaning by unqualified staff that may cause damage and downtime
- Keep the environment free of contaminating particles.
- Extend the life of air conditioning filters.
- Avoid using harsh cleaning agents that can attack the hardware and pollute the
environment
CONTENT SERVICE
Raised Floor:
- Removing large waste
- Vacuum Waste
- Vacuum micro-particles
- Thorough cleaning with special products of data cables, power cables, cable
trays, rosettes, raised floor structure
Floor Tiles:Floor Tiles:
- Removal of tile
- Cleaning the outside of the Data Center with no aggressive products
- Positioning and Leveling
- Cleaning of the top of the tile.
Data Cabling and Power:
- Aspiration of micro-particles
- Clean the surface of the wires.
Racks and Hardware (exterior):
- Aspiration of external racks.
- Dry cleaning of critical parts.
- Clean Rack and glass door access.
USED EQUIPMENT
- Vacuum with HEPA filter (filtering particles
down to 0.3 microns) and accessories
- Industrial Vacuum Cleaner
- Special Products (non-corrosive, non-toxic,
non-harmful to the environment and Anti-
Static)
- Special brushes for all types of surfaces
and corners.
- General Cleaning.
- Other accessories for the development of
the technical cleaning
PURITY ANALYSIS OF AIR
Should carry out an analysis of the amount of suspended particles containing air
with an optical particle analyzer. This analysis follows the International Standard
ISO 14644, with several measures over the entire surface of the Data Center
(according to standard depends on the size), with the limits of that legislation the
values indicated in the table:
Clase Número de Partículas por Metro Cúbico de cada tamañoClase Número de Partículas por Metro Cúbico de cada tamaño
0.1 um 0.2 um 0.3 um 0.5 um 1 um 5 um
ISO 1 10 2
ISO 2 100 24 10 4
ISO 3 1,000 237 102 35 8
ISO 4 10,000 2,370 1,020 352 83
ISO 5 100,000 23,700 10,200 3,520 832 29
ISO 6 1,000,000 237,000 102,000 35,200 8,320 293
ISO 7 352,000 83,200 2,930
ISO 8 3,520,000 832,000 29,300
ISO 9 35,200,000 8,320,000 293,000
Particle Counter
Channel 0.3, 0.5, 1.0, 2.5, 5.0, 10µm
Flow Rate (/min) controlled by internal pump
Count Modes Totalize, Concentration, Audio
Coincidence Loss 5%, 2000000 particles per ft3
IR Temperature Measure
Specifications:
MEASUREMENT EQUIPMENT: Particle Counter
Portable particle counter to measure the amount of suspended particles.
It has channels for 0.3, 0.5 and 5 microns.
IR Temperature Measure
IR Temp. Range -20.0ºC to 500.0ºC/-4.0ºF to 916ºF ;
Basic Accuracy: ±1.5% of reading
Optical Resolution 8:1 Distance to Spot size
Emissivity Adjustable 0.10~1.0 Adjustable
Response Time 500mS
Air Temperature Measure
0 to 50ºC/32 to 122ºF; Basic Accuracy:±0.5ºC/1ºF
0 to 100%RH; Basic Accuracy:±2.5%RH(20%~80%RH)
Range -30~100ºC/ -22~199ºF
Wet Bulb Temp. Range 0~80ºC/ 32~176ºF
GAS Detectors
HCHO (methanal) Range 0.01~5.00ppm; Basic Accuracy: ±5%± 0.01ppm
CO (carbon monoxide) Range 0~1000ppm; Basic Accuracy:±5% ± 10ppm
IT TILES
A good Technical Cleaning should last over time.
Data Centers should be kept clean according to ISO 14644 Class 8.
80% of dust and dirt in the critical area occurs in the feet (Source: 3M).
IT Tiles located at the entrance of the technical rooms avoid more than 99% of IT Tiles located at the entrance of the technical rooms avoid more than 99% of
the dust and dirt from entering the room and near the ground level.
IT TILES
IT tiles provide important benefits:
- Longer equipment life
- Reduced loss of data and read / write errors
- Reduced maintenance cost itself
- Improved reliability of its facilities
Dust may cause irreversible damage to computer systems to obstruct heat sinks
and cooling systems leading to overheating and cause an increased risk of fire
hazard. No protection against dust, there is great risk of data loss and hardware
failures in Data Centers.