table 2.1-1: electrical receptacles for patient care areas
TRANSCRIPT
Chapter 2.1 tables
DRAFT 2022 FGI Guidelines for Design and Construction of Outpatient Facilities 1
Table 2.1-1: Electrical Receptacles for Patient Care Areas in Outpatient Facilities1
Section Room Type Number of Single Receptacles12
Receptacle Locations23
PATIENT BED LOCATIONS
2.15-2.2 Extended stay patient room 12 2 at each side of the head of the bed 2 on all other walls 1 for a television, where provided 1 for each motorized bed, where provided
2.15-2.2.4.1
Extended stay airborne infection isolation (AII) room
12 2 at each side of the head of the bed 2 on all other walls 1 for a television, where provided 1 for each motorized bed, where provided
PATIENT CARE AND DIAGNOSTIC AREAS
2.1-3.2.1
Examination room/observation room
8 4 convenient to head of exam table or gurney or on each lateral side of the imaging gantry
Table 2.1-4
Class 1 imaging room 8 4 convenient to head of exam table or gurney or on each lateral side of the imaging gantry
2.1-3.2.2
Procedure room (including endoscopy)
1234 8 convenient to table placement At least 1 on each wall
Table 2.1-4
Class 2 imaging room 1234 8 convenient to table placement At least 1 on each wall
2.1-3.2.3
Operating room
3634
12 convenient to table placement 2 on each wall
Table 2.1-4
Class 3 imaging room 3634
12 convenient to table placement 2 on each wall
2.1-3.7.3 Pre-procedure patient care station
4 Convenient to gurney, lounge chair, or bed
2.1-3.7.5 Phase II recovery patient care station
4 Convenient to gurney, lounge chair, or bed
2.1-3.7.4 Phase I post-anesthesia recovery (PACU) patient care station
8 Convenient to head of gurney or bed
2.4-2.2 Birthing room 8 4 convenient to head of the mother’s bed 2.8-3.4.2 Emergency facility
treatment room 12 4 convenient to head of exam table or
gurney
2.8-3.4.4 Trauma/resuscitation room 16 Convenient to head of gurney or bed
2.8-3.4.8.2
Human decontamination room 4 —
Chapter 2.1 tables
DRAFT 2022 FGI Guidelines for Design and Construction of Outpatient Facilities 2
2.8-3.4.10.2
Low-acuity patient treatment station
4 Convenient to patient chair
2.8-6.2.2 Emergency facility triage area
6 Convenient to head of gurney or bed (at least 3 outlets connected to emergency system power and so labeled)
2.10-3.2.2 Hemodialysis patient care station
8 4 on each side of a patient bed or lounge chair (2 on each side of the bed connected to emergency power)
1Receptable numbers reflect the total number of receptacles from normal power, emergency power, or any combination thereof. See Section 2.1-8.3.3.1 (Essential electrical system or emergency electrical power) to determine if an essential electrical system or emergency electrical power is required.
21Permanently installed single, duplex, or fourplex receptacles or a combination of these shall be permitted. Receptacles in relocatable power taps or mounted on portable equipment shall not be counted as part of the total minimum requirement.
32In this table, “convenient” means the cords from the equipment to be used in the room can reach the receptacles without causing a trip hazard.
43The number of receptacles for these spaces is intended to agree with the number required in the governing edition of NFPA 99: Health Care Facilities Code.
Notes 1. Consideration shall be given to providing some outlets on essential electrical power and some on normal
power in operating rooms and post-anesthesia recovery areas in case of transfer switch failure. 2. Each room in the table shall meet the requirements for connection to the essential electrical system in the
governing edition of NFPA 99: Health Care Facilities Code. 3. Branch circuits serving only special purpose receptacles shall be permitted to be served by other
panelboards.
Chapter 2.1 tables
DRAFT 2022 FGI Guidelines for Design and Construction of Outpatient Facilities 3
Table 2.1-2: Station Outlets for Oxygen, Vacuum, Medical Air, and Instrument Air Systems in Outpatient Facilities
Section Location Oxygen Vacuum Nitrous Oxide Medical Air Instrument Air PATIENT CARE AND DIAGNOSTIC AREAS 2.1-3.2.2 Procedure room 11 11 — — —
Table 2.1-4 Class 2 imaging room 2 2 — 11 —
2.1-3.2.3.2 (1)(a)
Operating room (255-square-foot OR)
11 11 01, 2 — —
2.1-3.2.3.2 (1)(b)-(c)
Operating rooms2 22 32 01, 2 11,2 —
Table 2.1-4 Class 3 imaging room2 22 32 01, 2 11,2 —
2.1-3.2.4.4 Hyperbaric pre-procedure patient care area
21 21 — — —3
2.1-3.3.2 Airborne infection isolation room 01 01 — — —
2.1-3.5.5.2 Magnetic resonance imaging scanner room
01, 2 01, 2 01, 2 — —
2.1- 3.7.4 Phase I post-anesthesia recovery (PACU) patient care station
01 01 — — —
2.1-3.7.5 Phase II recovery patient care station
01 01 — — —
— Cast room 01 01 01, 2 — —
2.4-2.2 Birthing room 11 11 01, 2 — —
2.8-3.4.2 Emergency facility treatment room
1 1 — — —
2.8-3.4.4 Trauma/resuscitation room—per gurney
2 2 — 1 —
2.8-3.4.8.2 Human decontamination room 11 01 — — —
2.8-3.4.10.2 Low-acuity patient treatment station
—1 —1 — — —
2.8-6.2.2 Emergency facility triage area—per station
1 1 — — —
2.9-3.2.2 Endoscopy procedure room 1 3 — — —
2.11-3.2.9.2 (2)
Electroconvulsive therapy treatment room
11 11 — — —
2.14-3.3 Dental operatory room — — 01, 2 — — PATIENT SUPPORT FACILITIES 2.1-4.3.2.2 (2) Sterile processing
decontamination room — — — — 11, 4, 5
2.1-4.3.2.2 (3) Sterile processing clean workroom
— — — — —1, 4, 5
2.1-4.3.2.3 One-room sterile processing room — — — — —1, 4, 5
2.9-4.3.2 Endoscope processing room—decontamination area
— —3 — — —1, 3, 5
2.9-4.3.3 Endoscope processing room—clean work area
— —3 — — —1, 3, 5
Chapter 2.1 tables
DRAFT 2022 FGI Guidelines for Design and Construction of Outpatient Facilities 4
1Use of portable equipment in lieu of a piped gas system shall be permitted. 2If Where inhalation anesthesia, including nitrous oxide, will be used, in an operating room or Class 3 imaging
room, installation of a waste anesthetic gas disposal (WAGD) system should shall be provided considered. Use of portable delivery and scavenging equipment shall be permitted in lieu of a permanently installed WAGD system.
3Vacuum and/or instrument air shall be provided if needed for cleaning methods used. 4In the one-room sterile processing facility and the clean workroom of the two-room sterile processing facility,
an instrument air outlet or portable compressed air shall be provided as required by the equipment used. In the decontamination room of the two-room sterile processing facility, an instrument air outlet or portable compressed air is required.
5NFPA 99 permits the use of portable medical compressed air for single applications. Where cylinders are used for non-respiratory purposes, such as air for blowing down scopes and/or running decontamination equipment, NFPA 99 should be consulted for cylinder air quality, placement, and handling.
Note The provision of medical gases shall also comply with NFPA 99: Health Care Facilities Code. The clinical risk assessment in NFPA 99 may result in more stringent requirements for locations where this table permits use of portable gases.
Chapter 2.1 tables
DRAFT 2022 FGI Guidelines for Design and Construction of Outpatient Facilities 5
Table 2.1-3: Locations for Nurse Call Devices in Outpatient Facilities1, 2
Section Location Patient Station
Staff Assistance Station
Emergency Call Station
Toilet Room Call Station
Notes
PATIENT CARE AND DIAGNOSTIC AREAS
2.1-3.2.2 Table 2.1-4
Procedure room (including endoscopy)
Class 2 imaging room l l
2, 3
2.1-3.2.3 Operating room l l 2 Table 2.1-4 Class 3 imaging room l l 2 2.1-3.7.3 Pre-procedure patient care station l l l 1, 2 2.1-3.7.4 Phase I post-anesthesia recovery
(PACU) patient care station l l l 2, 3
2.1-3.7.5 Phase II recovery patient care station l l l 1, 2 2.8-3.4.2 Emergency facility treatment room l l 1, 2, 3 2.8-3.4.8.2 Human decontamination room l 2.8-3.4.10.2 Low-acuity treatment patient care
station l
2.8-6.2.2 Emergency facility triage area l l 1, 2, 3 2.10-3.2.2 Hemodialysis patient care station l l 1 2.10-3.3 Dialysis facility home training room l l 1, 4 2.10-3.10.2 Dialysis facility patient toilet room l l 1 2.11-3.2.9.2 (2)
Electroconvulsive therapy (ECT) room l l 2
2.11-3.2.9.3 (2)
ECT recovery patient care station l l 2
1It is recognized that staff other than nurses may respond to these devices, but the term “nurse call” is used here as it is an industry-accepted term.
2A Where patient toilet room call stations are optional, a safety risk assessment shall be performed. identify patient toilet rooms where a patient station is required.
Notes 1. One device shall be permitted to accommodate patient station, staff assistance station, and emergency call
station functionality. 2. A visible signal shall be activated in the corridor at the door to the room from which the signal was initiated
and at the nurse/control station where one is provided. 3. One device shall be permitted to accommodate both staff assistance and emergency call station
functionality. 4. Provision of toilet room call stations shall be predicated on the fall prevention assessment portion of the
safety risk assessment.
Chapter 2.1 tables
DRAFT 2022 FGI Guidelines for Design and Construction of Outpatient Facilities 6
Table 2.1-4: Examination/Treatment, Procedure, and Operating Room Classification1
[no changes; not in draft Table 2.1-5: Classification of Room Types for Imaging Services1 [no changes; not in draft] Appendix Table A2.1-a: Waiting Area Seating Capacity1 Chapter Facility Type Seating Calculation2 Wheelchair
Waiting Spaces3 2.2 General and specialty medical
facilities Primary care center and small neighborhood clinic
1.5 per patient care room 1
2.3 Outpatient imaging facility 1.5 per patient care room 1 2.4 Birth center 2 per birthing room 1 2.5 Urgent care center 2 per patient care room 1 2.6 Infusion and cancer treatment
center 2 per bay, cubicle or bed 1
2.7 Outpatient surgery facility 1.5 per procedure/operating room 1 2.9 Endoscopy facility 1.5 per endoscopy room 1 2.10 Dialysis center 2 .75 per patient care station 2 2.11 Psychiatric center 1.5 per patient care room 1 2.12 Rehab therapy facility 1.5 per simultaneous patient visits 5% total seats 2.14 Dental facility 1.5 per patient care room/station 1
1The total seating capacity should include 10 percent seating to accommodate individuals of size (patients and those who accompany them). See Section 2.1-2 (Accommodations for Care of Individuals of Size) for more information.
2Seating capacity should be rounded up to the next whole number when calculating the total number of seats required.
3Open spaces should be included for patients in wheelchairs who are waiting for care; these spaces may be counted as part of the total number of seats provided.
Chapter 2.1 tables
DRAFT 2022 FGI Guidelines for Design and Construction of Outpatient Facilities 7
Appendix Table A2.1-b: Maximum Length of Hot Water System Pipe or Tube [no changes; not in draft] Appendix Table A2.1-c: Resources for Grab Bar Configurations
Accessibility Standards
(ANSI/ADAAG) Georgia Tech Study*
Preferred alternative configuration for one-person, two-person, or
equipment-assisted transfer Wall Partition Location Behind and adjacent Behind and adjacent, where
provided Grab Bar Dimensions Centerline of toilet from side wall or permanent fixture
16 to 18 inches (40.64 to 45.72 centimeters)
24 inches (60.96 centimeters) for independent resident transfer
Side wall partition grab bar length
42 inches (1.07 meters) long 12 inches (30.48 centimeters)
maximum from rear wall 54 inches (1.37 meters) minimum
from rear wall
Not addressed
Rear wall partition grab bar length
36 inches (91.44 centimeters) long minimum
12 inches (30.48 centimeters) from centerline of toilet on one side and 24 inches (60.96 centimeters) on the other side
Eliminate in favor of installing swing-up grab bars
Fixed horizontal grab bar height
33 to 36 inches (83.82 to 91.44 centimeters) above finished floor to top of gripping surface
Not addressed
Swing-up grab bar height Not applicable 31 to 33 inches (78.74 to 83.82 centimeters) above finished floor to top of gripping service
Swing-up grab bar length Not applicable Extend 6 to 9 inches (15.24 to 22.86 centimeters) in front of toilet
Swing-up grab bar from centerline of toilet
Not applicable 13 to 15 inches (33.02 to 38.1 centimeters)
*This data is based on the Mayer-Rothschild Foundation report “Determination of Grab Bar Specifications for Independent and Assisted Transfers in Residential Care Settings.” A related article on the research appeared in the HERD Journal September 2017 under the title “Beyond ADA Accessibility Requirements: Meeting Seniors’ Needs for Toilet Transfers.”