systemredundancy fw v40 en
DESCRIPTION
systemredundancy fw v40_enTRANSCRIPT
© Siemens AG 2011. All Rights Reserved.
SIMATIC ET 200MSystemredundancy
© Siemens AG 2011. All Rights Reserved.
Industry SectorPage 2
Redundancy with PROFINET
Possible Configurations
PNSync
Sync
PN
PN
DP/MPI
Sync
Sync
PN
PN
DP
ET 200M
IM 153-4 PN IO High Feature
DP/MPI
DP
System redundancy with S7-400H
PNSync
Sync
PN
PN
ET 200M
IM153-4 PN IO Standard
DP/MPI
DP
Ring struktur with standard-CPU (MRP)
ET 200M ET 200M
Standard-CPU (IO Controller) S7-400H
ET 200MET 200M
© Siemens AG 2011. All Rights Reserved.
Industry SectorPage 3
Redundancy with PROFINET
Control of possible errors
1. Wire break of the ring2. Power off / failure of a single station3. Switch over time appr. 200ms
1
2
1. Wire break of the ring2. Power off / failure of a single station3. CPU failure4. Switch over time appr. 30ms
autom. synchronisation at CPU change
1
2
3
© Siemens AG 2011. All Rights Reserved.
Industry SectorPage 4
References
Applications
Safety & High
availibility
High-available
communication
PROFIBUS I/O
PROFINET I/O
Overview
Periphery
Redundant
Periphery
Innovations
Overview
Goals
High-available automation system SIMATIC S7-400H with PROFINET I/O System Redundancy (SR)
Automatic switchover in the event of a fault Event-controlled synchronization of both stations makes for fast and bumpless switchover Redundant CPU picks up processing at the interruption point without loss of information and alarms. All components can be replaced during running operation (hot swapping). When replacing a CPU, it is automatically loaded with the latest programs and data.
PROFINET
Open ring architecture
SR-Support through H-CPUs and ET 200M
Automatic synchronization after replacement of faulty component
Failure of an IO device (ET 200M) is limited to the damaged ring node
Guarantee of functionality in the case of an error in a CPU or a ring node or a bus error
ET 200M E 200M
Cable break between two devices does not affect functionality of the system
Failure of a CPU does not affect functionalityof the redundant system
ET 200MET 200M
Data synchronization
Switch SwitchSwitch
CPU 41x-5H CPU 41x-5H
Sync wiring
© Siemens AG 2011. All Rights Reserved.
SIMATIC ET 200M