Page 1: SYSTEM EQUIPMENT · 2018. 7. 27. · Model RFC43 (SIN RA0612) Model RFC49 (SIN RA0616) Flat Concealed Residential Sprinklers A Concealed Residential Sprinkler engineered for a minimum

SYSTEM EQUIPMENT

952 Arapahoe 952 Arapahoe Ave

Boulder, CO 80301

Page 2: SYSTEM EQUIPMENT · 2018. 7. 27. · Model RFC43 (SIN RA0612) Model RFC49 (SIN RA0616) Flat Concealed Residential Sprinklers A Concealed Residential Sprinkler engineered for a minimum
Page 3: SYSTEM EQUIPMENT · 2018. 7. 27. · Model RFC43 (SIN RA0612) Model RFC49 (SIN RA0616) Flat Concealed Residential Sprinklers A Concealed Residential Sprinkler engineered for a minimum

Model RFC43 (SIN RA0612)Model RFC49 (SIN RA0616)Flat ConcealedResidential Sprinklers

A Concealed ResidentialSprinkler engineered for aminimum design densityof 0.05 gpm/ft2 with low GPMrequirements.

Features1. Very low water flow requirements.

2. ½� (13mm) Total adjustment.

3. Thread-On/Thread-Off orPush-On/Thread Offcover attachment option.

4. Smooth aesthetic ceiling profile.

5. Available in brass, chrome andblack plated or painted finishes.

Product DescriptionModel RFC43 and RFC49 Concealed Residential Sprinklers

are fast response residential fusible solder link automaticsprinklers. Residential sprinklers differ from standardsprinklers primarily in their response time and waterdistribution patterns.

Model RFC43 and RFC49 sprinklers discharge water in ahemispherical pattern below the sprinkler deflector.Residential distribution patterns are higher and generallycontain a finer droplet size than standard sprinkler patterns.

The combination of speed of operation and high dischargepattern required for residential sprinklers has demonstrated,in fire testing, an ability for controlling residential fires, andthereby providing significant evacuation time for occupants.

The RFC43 and RFC49 Sprinklers provide the best form offire protection by combining an attractive appearance and½� (13mm) of cover adjustment for ease of installation. Thesmall diameter cover plate is easily and positively attachedand blends into the ceiling, concealing the most dependablefire protection available, an automatic sprinkler system.

The RFC43 and RFC49 are UL Listed Residential Sprinklersto be installed in the residential portions of any occupancy inaccordance with NFPA 13, 13R, & 13D.

The RFC43 and RFC49 can reduce the need for precisecutting of drop nipples. The threaded cover plate assemblycan be adjusted without tools to fit accurately against theceiling. The fire protection system need not be shut down toadjust or remove the cover plate assembly.

Application and InstallationThe RFC43 and RFC49, for residential installations, use a

165�F (74�C) fusible solder link in a tuning fork style sprinklerframe with a drop-down deflector. This assembly is recessedinto the ceiling and concealed by a flat cover plate. The coverplate is attached to the skirt, using 135�F (57�C) ordinarytemperature classification solder. When the ceilingtemperature rises, the solder holding the cover plate releasesthe cover allowing the deflector to drop into position and

The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523

Bulletin 006 Rev.D

Listings & Approval1. Listed by Underwriters Laboratories,

and certified by UL for Canada (cULus)

2. NYC MEA 258-93-E

UL Listing CategoriesResidential Automatic Sprinklers

UL Guide NumberVKKW

Bulle

tin006

Rev.D

Page 4: SYSTEM EQUIPMENT · 2018. 7. 27. · Model RFC43 (SIN RA0612) Model RFC49 (SIN RA0616) Flat Concealed Residential Sprinklers A Concealed Residential Sprinkler engineered for a minimum

exposing the sprinkler inside to ceiling temperature. Thesubsequent operation of the solder link opens the waterwayand causes the deflector to drop into position to distribute thedischarging water in a hemispherical pattern below thesprinkler deflector. Any adjustment of thread engagementbetween the cover plate and cup will assure that thedrop-down deflector is properly located below the ceiling.The residential distribution pattern contains a finer droplet sizethan a standard sprinkler, and the pattern producessignificantly higher wall wetting.

After a 2 5/8 inch diameter hole is cut in the ceiling, thesprinkler is to be installed with the Model FC Wrench. Wheninstalling a sprinkler, the wrench is first positioned into thesprinkler/cup assembly and around the hexagonal body ofthe sprinkler frame. The Wrench must bottom out against thecup in order to ensure proper, safe installation. The sprinkleris then tightened into the pipe fitting. When inserting orremoving the wrench from the sprinkler/cup assembly, care

should be taken to prevent damage to the sprinkler. DO NOTWRENCH ON ANY OTHER PART OF THE SPRINKLER/CUPASSEMBLY. MODEL RFC43 AND RFC49 CONCEALEDSPRINKLERS MUST BE INSTALLED ONLY WITH 135°FRATED COVERS.

Cover assemblies provide up to 12� (13mm) of

adjustment. Turn the cover clockwise until the flange is incontact with the ceiling. For the push-on/thread-off option,the cover assembly is pushed onto the cup and finaladjustment is made by turning the cover clockwise until theskirt flange makes full contact with the ceiling. Coverremoval requires turning in the counter-clockwise direction.

In ceilings that have a plenum space above the sprinkler,the plenum space may have neutral or negativepressurization but must not be positively pressurized. Inspectall sprinklers after installation to ensure that the gap betweenthe cover plate and ceiling and the 4 slots in the cup are allopen and free from any air flow impediment.

Sprinkler Cover Plate Max. AmbientTemp.

165oF/74

oC 135

oF/57

oC 100

oF/38

oC

Temperature Rating

Thread Sizeinch (mm)

KFactor

SprinklerSpacing

ft. (m)

MaximumDistance

to Wall ft. (m)

MinimumDistance betweensprinklers, ft. (m)

Minimum RequiredSprinkler Discharge

Flowgpm (Lpm)

Press.psi (bar)

½� (15mm)½� (15mm)½� (15mm)½� (15mm)½� (15mm)

4.34.34.34.34.3

12 x 12 (3.6x3.6)14 x 14 (4.3x4.3)16 x 16 (4.9x4.9)18 x 18 (5.5x5.5)20 x 20 (6.0x6.0)

6 (1.83)7 (2.13)8 (2.43)9 (2.74)

10 (3.05)

8 (2.43)8 (2.43)8 (2.43)8 (2.43)8 (2.43)

12 (45)13 (49)13 (49)18 (68)21 (79)

7.8 (0.54)9.1 (0.63)9.1 (0.63)

17.5 (1.21)23.8 (1.64)

Installation Data: RFC43 (SIN RA0612)

Note: 1 bar = 100 Kpa

2.

Thread Sizeinch (mm)

KFactor

SprinklerSpacing

ft. (m)

MaximumDistance

to Wall ft. (m)

MinimumDistance betweensprinklers, ft. (m)

Minimum RequiredSprinkler Discharge

Flowgpm (Lpm)

Press.psi (bar)

½� (15mm)½� (15mm)½� (15mm)½� (15mm)½� (15mm)

4.94.94.94.94.9

12 x 12 (3.6x3.6)14 x 14 (4.3x4.3)16 x 16 (4.9x4.9)18 x 18 (5.5x5.5)20 x 20 (6.0x6.0)

6 (1.83)7 (2.13)8 (2.43)9 (2.74)

10 (3.05)

8 (2.43)8 (2.43)8 (2.43)8 (2.43)8 (2.43)

13 (49)13 (49)13 (49)

17 (64.3)20 (75.7)

7.0 (0.48)7.0 (0.48)7.0 (0.48)

12.0 (0.83)16.7 (1.14)

Installation Data: RFC49 (RA0616)

Note: 1 bar = 100 Kpa

FOR SLOPED CEILING APPLICATIONS SEE RASCO BULLETIN 035.

jkobobel
Highlight
jkobobel
Highlight
jkobobel
Highlight
jkobobel
Highlight
jkobobel
Highlight
jkobobel
Highlight
jkobobel
Highlight
jkobobel
Highlight
jkobobel
Highlight
Page 5: SYSTEM EQUIPMENT · 2018. 7. 27. · Model RFC43 (SIN RA0612) Model RFC49 (SIN RA0616) Flat Concealed Residential Sprinklers A Concealed Residential Sprinkler engineered for a minimum

MaintenanceModel RFC43 and RFC49 Concealed Sprinklers should be

inspected quarterly and the sprinkler system maintained inaccordance with NFPA 25. Do not clean sprinklers with soapand water, ammonia or any other cleaning fluids. Removedust by using a soft brush or gentle vacuuming. Remove anysprinkler cover plate assembly which has been painted (otherthan factory applied) or damaged in any way. A stock ofspare sprinklers should be maintained to allow quickreplacement of damaged or operated sprinklers. Prior toinstallation, sprinklers should be maintained in the originalcartons and packaging until used to minimize the potential fordamage to sprinklers that would cause improper operation ornon-operation.

Ordering InformationSpecify:1. Sprinkler Model

2. Cover Plate Finish

3. Thread-On or

Push-On Feature

Standard Finishes

Chrome

White

Special ApplicationFinishes

Bright Brass

Black Plating

Black Paint

Off White

Satin Chrome

Cover Plate Finishes (1)

(1)Other colors and finishes

available. Consult factoryfor details.Note: Paint or any othercoatings applied over thefactory finish will void allapprovals and warranties.

3.

Model RFC43 and RFC49 ResidentialConcealed Sprinkler Specification

Sprinklers shall be cULus Listed low flow residentialconcealed sprinklers with drop-down deflector andadjustable flat cover plate engineered for a minimum designdensity of 0.05 gpm/ft

2. Sprinkler frame and deflector shall be

of bronze frame construction having a ½” NPT thread.Thermal element shall consist of an approved black-paintedberyllium-nickel fusible solder link with symmetric levermechanism, maintaining a Teflon-coated Belleville springwasher and machined brass cap water seal assemblycontainingnoplasticparts. SprinklerK-factor shall benominal4.3 (62.4), having a 7/16” orifice. Temperature rating shall beOrdinary 165�F (74�C); cover plate temperature rating to be

135�F (57�C). Cover plate assembly shall consist of a brasscover plate and copper alloy retainer flange allowing a ½”cover plate adjustment. Any secure engagement betweenthe cover plate and the cup will assure that the drop-downdeflector is properly located below the ceiling. A plasticprotective cap shall be provided and factory installed insidethe sprinkler cup to protect the drop-down sprinkler deflectorfrom damage, which could occur during construction beforethe cover plate is installed. Standard cover finish: [Chrome][White] [Specialty – specify]. Residential concealedsprinklersshall be Reliable Model RFC43, SIN RA0612 (Bulletin 006) orModel RFC49, SIN RA0616 (Bulletin 006).

Page 6: SYSTEM EQUIPMENT · 2018. 7. 27. · Model RFC43 (SIN RA0612) Model RFC49 (SIN RA0616) Flat Concealed Residential Sprinklers A Concealed Residential Sprinkler engineered for a minimum

1.

The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523

Bulletin 135 Rev.G Bulle

tin135

Rev.G

Model F1 Res Sprinklers engineered for the lowest flowsto meet the minimum design density of .05 gpm/ft2

Types:1. F1 Res 30 Pendent2. F1 Res 30 Recessed Pendent/F23. F1 Res 30 Recessed Pendent/FP4. F1 Res 49 Pendent5. F1 Res 49 Recessed Pendent/F16. F1 Res 49 Recessed Pendent/FP7. F1 Res 58 Pendent8. F1 Res 58 Recessed Pendent/F19. F1 Res 58 Recessed Pendent/FP

10. F1 Res 76 Pendent11. F1 Res 76 Recessed Pendent/F112. F1 Res 76 Recessed Pendent/FP13. F1 Res 30 CCP Pendent14. F1 Res 49 CCP Pendent15. F1 Res 58 CCP Pendent16. F1 Res 76 CCP Pendent17. F1 Res 44 HSW18. F1 Res 44 Recessed HSW/F219. F1 Res 58 HSW20. F1 Res 58 HSW Recessed HSW/F221. F1 Res 44 SWC22. F1 Res 40 HSW23. F1 Res 40 Recessed HSW/F2

Listings & Approvals1. Listed by Underwriters Laboratories Inc. and

UL Certified for Canada (cULus)2. NYC MEA 258-93-E

Slope Ceiling Approvals:Sprinklers for .10 Density:

Product DescriptionModel F1 Res Pendent sprinklers (Figs. 1, 2, 3, & 4) are

fast response sprinklers combining excellent durability,high sensitivity glass-bulb and low profile decorativedesign. The F1 Res Horizontal Sidewall sprinklers (Figs.5, 6 & 7) are equally attractive when above ceiling pipingcannot be used.

The 3mm glass-bulb pendent sprinklers permit theefficient use of residential water supplies for sprinklercoverage in residential fire protection design.

ApplicationModel F1 Res Sprinklers are used for Residential Fire

Protection according to UL 1626 Standard*. Be surethat orifice size, temperature rating, deflector style andsprinkler type are in accordance with the latestpublished standards of The National Fire ProtectionAssociation or the approving authority havingjurisdiction.

F1Res30,49,58&76RecessedPendent /F1

F1Res30,49,58&76RecessedPendent /FP

F1 Res 30, 49, 58 & 76CCP Pendent

F1 Res 40 RecessedHSW/F2

UL Listing CategoryResidential Automatic Sprinkler

UL Guide NumberVKKW

PatentsUS Patent No. 6,516,893 applies to theModel F1 Res 49 & 58 Pendent Sprinklers

The low flow F1 Res sprinklers are speciallyengineered for fast thermal response to meet thesensitive fire protection application needs of the latestresidential market standards (UL 1626 Standard). Uponfire conditions, rising heat causes a sprinkler’sheat-sensitive glass-bulb to shatter, releasing thewaterway for water flow onto the deflector, evenlydistributing the discharged water to control a fire.

Technical Data:• Thermal Sensor: Nominal 3mm glass-bulb• Sprinkler Frame : Brass Casting• Sprinklers’ Pressure Rating : 175 psi

Factory Hydrostatically Tested to 500 psi• Thread Size: ½” NPT (R½)• K-Factor: 3.0 (Actual) - F1 Res 30 Pendent Sprinkler

4.9 (Actual) - F1 Res 49 Pendent Sprinkler5.8 (Actual) - F1Res58Pendent&HSWSprinkler7.6 (Actual) - F1 Res 76 Pendent Sprinkler4.4 (Actual) - F1 Res 44 HSW Sprinkler4.0 (Actual) - F1 Res 40 HSW Sprinkler

• Density: Minimum 0.05 gpm/ft2

F1 Res 44 & 58Recessed HSW/F2

F1 Res 44 SWC

Model F1Residential Sprinklers forDesign Density of .05 gpm/ft2

jkobobel
Rectangle
jkobobel
Accepted
Page 7: SYSTEM EQUIPMENT · 2018. 7. 27. · Model RFC43 (SIN RA0612) Model RFC49 (SIN RA0616) Flat Concealed Residential Sprinklers A Concealed Residential Sprinkler engineered for a minimum

Model F1 Res 30, 49, 58 & 76 Pendent

Model F1 Res 30 RecessedPendent / F2

Model F1 Res 49, 58 & 76Recessed Pendent / F1

Fig. 1 Fig. 2

F1 escutcheon, 34� (19mm) adjustment

2.

InstallationModels F1 Res sprinklers are to be installed as

shown. Model F1, F2 and FP Escutcheons, illustratedherewith, are the only recessed escutcheons to be usedwith Model F1 Res sprinklers. Use of any otherrecessed escutcheon will void all approvals andwarranties. For installing Model F1 Res Pendentsprinklers use only the Model D sprinkler Wrench; forinstalling Models F1 Res Recessed Pendent, CCP &

SWC sprinklers use only the Model GFR2 sprinklerwrench; for installing Model F1 Res Recessed HSWsprinklers use only the Model GFR2 Sprinkler Wrench.Use of wrenches other than those specified maydamage these sprinklers. Install F1 Res 44 and 40 HSWwith a ceiling to deflector distance of 4� - 12�. Flow arrowon deflector must point away from near wall and “Top”marking must face ceiling.

Type AdjustmentInch (mm)

“A”Inch (mm)

Face of fitting toceiling

Inch (mm)

F1 34 (19.0) Min.= 3

4� (19.1)Max.=11

2� (38.1)3

16 - 1516 (4.7 - 24.0)

F2 12 (12.7) Min.= 15

16� (23.8)Max.=11

2� (38.1)3

16 - 1116 (4.7 - 17.4)

Escutcheon*, F1 or F2, Data:

* Note:

Page 8: SYSTEM EQUIPMENT · 2018. 7. 27. · Model RFC43 (SIN RA0612) Model RFC49 (SIN RA0616) Flat Concealed Residential Sprinklers A Concealed Residential Sprinkler engineered for a minimum

ThreadSize

NominalOrificeInch(mm)

SprinklerTemp.Rating

Max.Pressure

psi(bar)

Max.AmbientTemp.

ActualK

Factor

SprinklerLength

Inch(mm)

�F �C �F �C1

2� NPT(R1

2)716" (11) 155

1756879

175 (12)100150

3866

4.9 2.25 (57)

Max. SprinklerSpacing

ft (m)

Flowgpm (Lpm)

Pressurepsi (bar)

SprinklerIdentificationNumber (SIN)

12 x 12 (3.6x3.6) 13 (49) 7.0 (0.48)

R3516

14 x 14 (4.3x4.3) 13 (49) 7.0 (0.48)

16 x 16 (4.9x4.9) 13 (49) 7.0 (0.48)

18 x 18 (5.5x5.5) 17 (64.3) 12.0 (0.83)

20 x 20 (6.1x6.1) 20 (75.7) 16.7 (1.14)

Deflector - to - ceilingMaximum 1� (25mm) to 4� (100mm)

3.

Max. SprinklerSpacing

ft (m)

Flowgpm (Lpm)

Pressurepsi (bar)

SprinklerIdentificationNumber (SIN)

12 x 12 (3.6x3.6) 15 (57) 9.4 (0.65)

R3516

14 x 14 (4.3x4.3) 16 (60.5) 10.6 (0.73)

16 x 16 (4.9x4.9) 17 (64.3) 12.0 (0.83)

18 x 18 (5.5x5.5) 19 (72) 15.0 (1.0)

20 x 20 (6.1x6.1) 22 (83.2) 20.2 (1.4)

*Deflector - to - ceilingMaximum 4� (100mm) to 8� (203mm)

*Note: The F1 Res 49 pendent and recessed pendentresidential sprinklers can be installed per NFPA 13 inbeamed ceilings meeting the following criteria:1. Maximum beam depth = 7� (178mm)2. Beam spacing at or greater than 7.5 ft. (2.3m) on center.

Technical Data: F1 Res 49 Pendent and Recessed Pendent

ThreadSize

NominalOrificeInch(mm)

SprinklerTemp.Rating

Max.Pressure

psi(bar)

Max.AmbientTemp.

KFactor

SprinklerLength

Inch(mm)

�F �C �F �C

½� NPT(R½)

12" (13) 155

1756879

175 (12)100150

3866

5.8 2.25 (57)

Max. SprinklerSpacing

ft (m)

Flowgpm (Lpm)

Pressurepsi (bar)

Ceiling -to-DeflectorInch (mm)

SprinklerIdentificationNumber (SIN)

12 x 12 (3.6x3.6) 16 (61) 7.6 (0.53)

1-4(25-100)

R3513

14 x 14 (4.3x4.3) 16 (61) 7.6 (0.53)

16 x 16 (4.9x4.9) 16 (61) 7.6 (0.53)

18 x 18 (5.5x5.5) 19 (72) 10.8 (0.75)

20 x 20 (6.1x6.1) 22 (83.3) 14.4 (1.0)

Technical Data: F1 Res 58 Pendent and Recessed Pendent

Technical Data: F1 Res 30 Pendent and Recessed Pendent

ThreadSize

NominalOrificeInch(mm)

SprinklerTemp.Rating

Max.Pressure

psi(bar)

Max.AmbientTemp.

ActualK

Factor

SprinklerLength

Inch(mm)

�F �C �F �C1

2� NPT(R1

2)21

64" (8.2) 155175

6879

175 (12) 100 38 3.0 2.25 (57)

Max. SprinklerSpacing

ft (m)

Flowgpm (Lpm)

Pressurepsi (bar)

SprinklerIdentificationNumber (SIN)

12 x 12 (3.6x3.6) 8 (30.3) 7.0 (0.48)R3511

14 x 14 (4.3x4.3) 10 (37.8) 11 (0.76)

Deflector - to - ceilingMaximum 1� (25mm) to 4� (100mm)

Page 9: SYSTEM EQUIPMENT · 2018. 7. 27. · Model RFC43 (SIN RA0612) Model RFC49 (SIN RA0616) Flat Concealed Residential Sprinklers A Concealed Residential Sprinkler engineered for a minimum

4.

Technical Data: F1 Res 76 Pendent and Recessed Pendent

ThreadSize

NominalOrificeInch(mm)

SprinklerTemp.Rating

Max.Pressure

psi(bar)

Max.AmbientTemp.

KFactor

SprinklerLengthInch

(mm)�F �C �F �C

34� NPT(R3

4)

1732"

(13.5)155175

6879

175 (12)100150

3866

7.6 2.25 (57)

Max. SprinklerSpacing

ft (m)

Flowgpm (Lpm)

Pressurepsi (bar)

SprinklerIdentificationNumber (SIN)

12 x 12 (3.6x3.6) 21 7.6 (0.53)

R7618

14 x 14 (4.3x4.3) 21 7.6 (0.53)

16 x 16 (4.9x4.9) 21 7.6 (0.53)

18 x 18 (5.5x5.5) 21 7.6 (0.53)

20 x 20 (6.1x6.1) 23 9.2 (0.63)

Model F1 Res 30, 49, 58 & 76CCP Pendent

Model F1 Res 30, 49, 58 & 76Recessed Pendent / FP

FP push-on/thread-offescutcheon

Fig. 4Fig. 3

NOTE: The F1 Res 76 will use a 1" x ¾" reducer.

Page 10: SYSTEM EQUIPMENT · 2018. 7. 27. · Model RFC43 (SIN RA0612) Model RFC49 (SIN RA0616) Flat Concealed Residential Sprinklers A Concealed Residential Sprinkler engineered for a minimum

ThreadSize

NominalOrificeInch(mm)

SprinklerTemp.Rating

CCPAssembly

Temp.Rating

Max.Pressurepsi(bar)

Max.AmbientTemp.

KFactor

SprinklerLengthInch(mm)

�F �C �F °C �F �C½�

NPT(R½)

2164" (8.2) 155 68 135 57 175 (12) 100 38 3.0

2.25(57)

Max. SprinklerSpacing

ft (m)

Flowgpm (Lpm)

Pressurepsi (bar)

SprinklerIdentificationNumber (SIN)

12 x 12 (3.6x3.6) 8 (30.3) 7.0 (0.48)R3511

14 x 14 (4.3x4.3) 11 (41.6) 13.4 (0.92)

Technical Data: F1 Res 30 CCP Pendent and Recessed Pendent / FP

ThreadSize

NominalOrificeInch(mm)

SprinklerTemp.Rating

CCPAssembly

Temp.Rating

Max.Pressure

psi(bar)

Max.AmbientTemp.

KFactor

SprinklerLengthInch(mm)

�F �C �F °C �F �C½� NPT

(R½)1

2" (13) 155 68 135 57 175 (12) 100 38 5.8 2.25 (57)

Max. SprinklerSpacing

ft (m)

Flowgpm (Lpm)

Pressurepsi (bar)

SprinklerIdentificationNumber (SIN)

12 x 12 (3.6x3.6) 16 (61) 7.6 (0.53)

R351314 x 14 (4.3x4.3) 16 (61) 7.6 (0.53)16 x 16 (4.9x4.9) 16 (61) 7.6 (0.53)18 x 18 (5.5x5.5) 19 (72) 10.8 (0.75)20 x 20 (6.1x6.1) 22 (83.3) 14.4 (1.0)

Technical Data: F1 Res 58 CCP Pendent and Recessed Pendent/FP

5.

ThreadSize

NominalOrificeInch(mm)

SprinklerTemp.Rating

CCPAssembly

Temp.Rating

Max.Pressure

psi(bar)

Max.AmbientTemp.

KFactor

SprinklerLength

Inch(mm)�F �C �F °C �F �C

¾� NPT(R3/4)

1732"

(13.5)155175

6879

135 57 175 (12)100150

3866

7.6 2.25 (57)

Max. SprinklerSpacing

ft (m)

Flowgpm (Lpm)

Pressurepsi (bar)

SprinklerIdentificationNumber (SIN)

12 x 12 (3.6x3.6) 21 7.6 (0.53)

R761814 x 14 (4.3x4.3) 21 7.6 (0.53)16 x 16 (4.9x4.9) 21 7.6 (0.53)18 x 18 (5.5x5.5) 22 8.4 (0.58)20 x 20 (6.1x6.1) 25 10.8 (0.74)

Technical Data: F1 Res 76 CCP Pendent and Recessed Pendent/FP

ThreadSize

NominalOrificeInch(mm)

SprinklerTemp.Rating

CCPAssembly

Temp.Rating

Max.Pressurepsi(bar)

Max.AmbientTemp.

KFactor

SprinklerLengthInch(mm)

�F �C �F °C �F �C½�

NPT(R½)

716" (11) 155 68 135 57 175 (12) 100 38 4.9

2.25(57)

Max. SprinklerSpacing

ft (m)

Flowgpm (Lpm)

Pressurepsi (bar)

SprinklerIdentificationNumber (SIN)

12 x 12 (3.6x3.6) 13 (49) 7.0 (0.48)

R351614 x 14 (4.3x4.3) 13 (49) 7.0 (0.48)16 x 16 (4.9x4.9) 14 (53) 8.2 (0.56)18 x 18 (5.5x5.5) 18 (68.1) 13.5 (0.93)20 x 20 (6.1x6.1) 20 (75.7) 16.7 (1.14)

“A”Cover Adjustment

Inch (mm)

“B”CCP HeightInch (mm)

12 (12.7) 15

16 (24)

516 (7.9) 3

4 (19)

CCP Options Data:

FP Position “A”Inch (mm)

Max. Recessed 716 (11)

Min. Recessed 1516 (24)

FP Data “A”:

Note: Sprinklers shown in Fig. 3 and Fig. 4 are notsuitable for installation in ceilings which havepositive pressure in the space above.

Technical Data: F1 Res 49 CCP Pendent and Recessed Pendent / FP

jkobobel
Highlight
jkobobel
Highlight
Page 11: SYSTEM EQUIPMENT · 2018. 7. 27. · Model RFC43 (SIN RA0612) Model RFC49 (SIN RA0616) Flat Concealed Residential Sprinklers A Concealed Residential Sprinkler engineered for a minimum

6.

Model F1 Res 44 & 58 HSW Model F1 Res 44 & 58Recessed HSW/F2

F2 escutcheon, 12� (13mm)

adjustment

ThreadSize

NominalOrificeInch(mm)

SprinklerTemp.Rating

Max.Pressure

psi(bar)

Max.AmbientTemp.

KFactor

SprinklerLengthInch

(mm)�F �C �F �C

½� NPT(R½)

38" (10) 155

1756879

175 (12)100150

3866

4.4 2.45 (62)

Type AdjustmentInch (mm)

Face of Fittingto wall

Inch (mm)F2 1

2 (13) 316 - 11

16 (4.7 - 17.4)

Escutcheon, F2, Data:

Technical Data: F1 Res 44 HSW & HSW/F2

Max. SprinklerSpacing

ft (m)

“A”Ceiling -to-DeflectorInch (mm)

Sprinkler Temp.Rating�F (�C)

Flowgpm(Lpm)

Pressurepsi (bar)

SprinklerIdentificationNumber (SIN)

12 x 12 (3.6x3.6)

4 - 6(101-152)

155 (68) 175 (79) 12 (45.4) 7.5 (0.52)

R3531

14 x 14 (4.3x4.3) 155 (68) 175 (79) 14 (53.0) 10.2 (0.71)

16 x 16 (4.9x4.9) 155 (68) 175 (79) 16 (60.6) 13.3 (0.92)

16 x 18 (4.9x5.5) 155 (68) 175 (79) 18 (68.1) 16.8 (1.16)

18 x 18 (5.5x5.5) 155 (68) 175 (79) 19 (72.0) 18.7 (1.29)

16 x 20 (4.9x6.1) 155 (68) 175 (79) 23 (87.1) 27.4 (1.89)

12 x 12 (3.6x3.6)

6 - 12(152-305)

155 (68) 175 (79) 14 (53.0) 10.2 (0.71)

14 x 14 (4.3x4.3) 155 (68) 175 (79) 16 (60.6) 13.3 (0.92)

16 x 16 (4.9x4.9) 155 (68) 175 (79) 17 (64.4) 15.0 (1.04)

16 x 18 (4.9x5.5) 155 (68) 175 (79) 20 (75.7) 20.7 (1.43)

16 x 20 (4.9x6.1) 155 (68) 175 (79) 23 (87.1) 27.4 (1.89)

Page 12: SYSTEM EQUIPMENT · 2018. 7. 27. · Model RFC43 (SIN RA0612) Model RFC49 (SIN RA0616) Flat Concealed Residential Sprinklers A Concealed Residential Sprinkler engineered for a minimum

ThreadSize

NominalOrificeInch(mm)

SprinklerTemp.Rating

Max.Pressure

psi(bar)

Max.AmbientTemp.

KFactor

SprinklerLengthInch(mm)

�F �C �F �C½� NPT

(R½)1

2" (13) 155175

6879

175 (12)100150

3866

5.8 2.45 (62)

Type AdjustmentInch (mm)

Face of Fittingto wall

Inch (mm)F2 1

2 (13) 316 - 11

16 (4.7 - 17.4)

Escutcheon, F2, Data:

Technical Data: F1 Res 58 HSW & HSW/F2

Max. SprinklerSpacing

ft (m)

“A”Ceiling -to-DeflectorInch (mm)

Sprinkler Temp.Rating�F (�C)

Flowgpm(Lpm)

Pressurepsi (bar)

SprinklerIdentificationNumber (SIN)

12 x 12 (3.6x3.6)

4 - 6(101-152)

155 (68) 175 (79) 16 (60.6) 7.6 (0.53)

R3533

14 x 14 (4.3x4.3) 155 (68) 175 (79) 18 (68.2) 9.7 (0.67)

16 x 16 (4.9x4.9) 155 (68) 175 (79) 21 (79.5) 13.2 (0.91)

16 x 18 (4.9x5.5) 155 (68) 175 (79) 25 (94.7) 18.6 (1.28)

16 x 20 (4.9x6.1) 155 (68) 175 (79) 29 (109.8) 25 (1.73)

12 x 12 (3.6x3.6)

6 - 12(152-305)

155 (68) 175 (79) 22 (83.3) 14.4 (1.0)

14 x 14 (4.3x4.3) 155 (68) 175 (79) 22 (83.3) 14.4 (1.0)

16 x 16 (4.9x4.9) 155 (68) 175 (79) 26 (98.4) 20.1 (1.39)

16 x 18 (4.9x5.5) 155 (68) 175 (79) 31 (117.4) 28.6 (1.97)

7.

Page 13: SYSTEM EQUIPMENT · 2018. 7. 27. · Model RFC43 (SIN RA0612) Model RFC49 (SIN RA0616) Flat Concealed Residential Sprinklers A Concealed Residential Sprinkler engineered for a minimum

8.

Model F1 Res 44 SWC

Fig. 5

Max. SprinklerSpacing

ft (m)

“A”Ceiling -to-DeflectorInch (mm)

Flowgpm(Lpm)

Pressurepsi (bar)

SprinklerIdentificationNumber (SIN)

12 x 12 (3.6x3.6)

4 - 6(101-152)

13 (49.2) 8.7 (0.60)

R3531

14 x 14 (4.3x4.3) 14 (53.0) 10.2 (0.71)

16 x 16 (4.9x4.9) 17 (64.3) 15.0 (1.1)

16 x 18 (4.9x5.5) 19 (71.8) 18.7 (1.13)

16 x 20 (4.9x6.1) 23 (87.1) 27.4 (1.89)

12 x 12 (3.6x3.6)

6 - 12(152-305)

14 (52.9) 10.2 (0.71)

14 x 14 (4.3x4.3) 15 (56.7) 11.7 (0.81)

16 x 16 (4.9x4.9) 18 (68.1) 16.8 (1.16)

16 x 18 (4.9x5.5) 20 (75.6) 20.7 (1.43)

ThreadSize

NominalOrificeInch(mm)

SprinklerTemp.Rating

CoverTemp.Rating

Max.Pressure

psi(bar)

Max.AmbientTemp. K

Factor

SprinklerLengthInch

(mm)�F �C �F °C �F �C

½� NPT(R½)

38" (10) 155 68 135 57 175 (12) 100 38 4.4 2.45 (62)

Technical Data: F1 Res 44 SWC

Page 14: SYSTEM EQUIPMENT · 2018. 7. 27. · Model RFC43 (SIN RA0612) Model RFC49 (SIN RA0616) Flat Concealed Residential Sprinklers A Concealed Residential Sprinkler engineered for a minimum

2.

9.

Model F1 Res 40 HSWModel F1 Res 40 Recessed

HSW/F2

F2 escutcheon, 12� (13mm)

adjustment

Fig. 6 Fig. 7

Max. SprinklerSpacing

ft (m)

“A”Ceiling -to-DeflectorInch (mm)

Sprinkler Temp.Rating�F (�C)

Flowgpm(Lpm)

Pressurepsi (bar)

SprinklerIdentificationNumber (SIN)

12 x 12 (3.6x3.6)

4 - 6(101-152)

155 (68) 175 (79) 13 (49.0) 10.6 (0.73)

R3538

14 x 14 (4.3x4.3) 155 (68) 175 (79) 16 (60.5) 16.0 (1.10)

16 x 16 (4.9x4.9) 155 (68) 17 (64.3) 18.1 (1.24)

16 x 16 (4.9x4.9) 175 (79) 18 (68.1) 20.2 (1.39)

16 x 18 (4.9x5.5) 155 (68) 175 (79) 20 (75.7) 25.0 (1.72)

18 x 18 (5.5x5.5) 155 (68) 175 (79) 22 (83.3) 30.2 (2.08)

16 x 20 (4.9x6.1) 155 (68) 175 (79) 23 (87.0) 33.1 (2.28)

12 x 12 (3.6x3.6)6 - 12

(152-305)

155 (68) 175 (79) 13 (49.0) 10.6 (0.73)

14 x 14 (4.3x4.3) 155 (68) 175 (79) 17 (64.3) 18.1 (1.24)

16 x 16 (4.9x4.9) 155 (68) 175 (79) 20 (75.7) 25.0 (1.72)

ThreadSize

NominalOrificeInch(mm)

SprinklerTemp.Rating

Max.Pressure

psi(bar)

Max.AmbientTemp.

KFactor

SprinklerLengthInch(mm)

�F �C �F �C½� NPT

(R½)3

8" (10) 155175

6879

175 (12)100150

3866

4.0 2.45 (62)

Type AdjustmentInch (mm)

Face of Fittingto wall

Inch (mm)F2 1

2 (13) 316 - 11

16 (4.7 - 17.4)

Escutcheon, F2, Data:Technical Data: F1 Res 40 HSW & HSW/F2

Page 15: SYSTEM EQUIPMENT · 2018. 7. 27. · Model RFC43 (SIN RA0612) Model RFC49 (SIN RA0616) Flat Concealed Residential Sprinklers A Concealed Residential Sprinkler engineered for a minimum

Ordering InformationSpecify:1. Sprinkler Model

2. Sprinkler Type

3. Temperature Rating

4. Sprinkler Finish

5. Escutcheon Finish

6. Cover Plate Finish

MaintenanceModel F1 Res 30, 49, F1 Res 58, F1 Res 76, F1 Res 44

and F1 Res 40 Sprinklers should be inspected quarterly,and the sprinkler system maintained in accordance withNFPA 25, 13, 13D, and 13R. Do not clean sprinkler withsoap and water, Ammonia or any other cleaning fluids.Remove dust by using a soft brush or gentle vacuuming.Remove any sprinkler which has been painted (other thanfactory applied) or damaged in any way. A stock of sparesprinklers should be maintained to allow quickreplacement of damaged or operated sprinklers. Prior toinstallation, sprinklers should remain in the original cartonsand packaging until used. This will minimize the potentialfor damage to sprinklers that could cause improperoperation or non-operation.

Standard Finishes

Sprinkler F1, F2, FPEscutcheons Cover Plates

BronzeChrome PlatedWhite PolyesterCoated

BrassBright Chrome PlatedWhite Painted

White PaintedChrome

Special Application Finishes

Sprinkler F1, F2,Escutcheons Cover Plates

Bright BrassBlack PlatedBlack PaintOff WhiteSatin Chrome

Bright BrassBlack PlatedBlack PaintOff WhiteSatin Chrome

Bright BrassBlack PlatedBlack PaintOff WhiteSatin Chrome

Finishes(1)

(1)Other finishes and colors are available on special order.Consult factory for details.

Paint or any other coating applied over the factory finish willvoid all approvals and warranties.

10.

Model F1 Res 30, 49 & 58 PendentSprinkler Specifications

Sprinklers shall be [cULus Listed] [New York City MEAApproved (258-93-E)] low flow residential pendentsprinklers engineered to provide a minimum designdensity of 0.05 gpm/ft2 over the listed coverage area.Listed flows as specified by the manufacturer’s technicaldata sheets are to be used. Residential sprinklers shall beinstalled in conformance with the manufacturer’sinstallation guidelines and the applicable installationstandard. Where pendent residential sprinklers areinstalled under sloped ceilings having a pitch from [4/12] to[8/12], the sprinklers shall be listed for such use.Deflector-to-ceiling distance listing shall be 1” to 8”maximum. Sprinkler frame and deflector shall be of bronzeframe construction having a ½” NPT thread. Water sealassembly shall consist of a Teflon-coated Belleville springwasher with top-loaded extruded or cold head cup with 3mm glass bulb containing no plastic parts, and having atemperature rating of [155�F (68�C)] [175�F (79�C)].Sprinklers shall have a nominal K-factor of 3.0, 4.9 and 5.8.Standard finish: [Bronze] [Chrome-plated] [WhitePolyester] [Special finish– specify]. Residential pendentsprinklers shall be Reliable Model F1 Res 30, 49 & 58, SINR3511, R3516 & R3513 (Bulletin 135).

Model F1 Res 49 & 58 Recessed Pendent/F1,ModelF1Res30,49&58RecessedPendent/F2,ModelF1Res30,49&58RecessedPendent/FP

Sprinklers shall be [cULus Listed] [New York City MEAApproved (258-93-E)] low flow residential recessedpendent sprinklers engineered to provide a minimumdesigndensityof0.05gpm/ft2 over the listedcoveragearea.Listed flows as specified by the manufacturer’s technicaldata sheets are to be used. Residential sprinklers shall beinstalled in conformance with the manufacturer’s installationguidelines and the applicable installation standard. Wherependent residential sprinklers are installed under slopedceilings having a pitch from [4/12] to [8/12], the sprinklersshall be listed for such use. Deflector-to-ceiling distancelisting shall be 1” to 8” maximum. Sprinkler frame anddeflector shall be of bronze frame construction having a ½”NPT thread. Water seal assembly shall consist of aTeflon-coated Belleville spring washer with top-loadedextruded or cold head cup with 3 mm glass bulb containingno plastic parts, and having a temperature rating of [155�F(68�C)] [175�F (79�C)]. Sprinklers shall have a nominalK-factor of 3.0, 4.9 & 5.8. Standard finish: [Bronze][Chrome-plated] [White Polyester] [Special finish– specify].Recessed escutcheon assembly shall be a steel, two-pieceescutcheon [with ½” adjustment (Model F2)] [with ¾”adjustment (Model F1)] [of push-on and thread off designwith ½” adjustment (Model FP)]. Standard finish shall be[brass][bright chrome] [white painted]. Residentialrecessed pendent sprinklers shall be Reliable [Model F1Res 3.0, 49 & 58 Recessed Pendent/F1] [Model F1 Res 30,49 & 58 Recessed Pendent/F2] [Model F1 Res 30, 49 & 58Recessed Pendent/FP] SIN R3511, R3516 & R3513(Bulletin 135).

Page 16: SYSTEM EQUIPMENT · 2018. 7. 27. · Model RFC43 (SIN RA0612) Model RFC49 (SIN RA0616) Flat Concealed Residential Sprinklers A Concealed Residential Sprinkler engineered for a minimum

ModelF1Res30,49&58CCPPendent(Concealed)Sprinklers shall be [cULus Listed] [New York City MEA

Approved (258-93-E)] low flow residential concealedsprinklers engineered to provide a minimum designdensity of 0.05 gpm/ft2 over the listed coverage area.Listed flows as specified by the manufacturer’s technicaldata sheets are to be used. Residential sprinklers shallbe installed in conformance with the manufacturer’sinstallation guidelines and the applicable installationstandard. Where pendent residential sprinklers areinstalled under sloped ceilings having a pitch from [4/12]to [8/12], the sprinklers shall be listed for such use.Sprinkler frame and deflector shall be of bronze frameconstruction having a ½” NPT thread. Water sealassembly shall consist of a Teflon-coated Bellevillespring washer with top-loaded extruded or cold headcup with 3 mm glass bulb containing no plastic parts, andhaving a temperature rating of 155�F (68�C). Cover plateassembly shall consist of a brass cover plate and copperalloy retainer flange. Method of attaching the cover plateto the sprinkler cup shall be a push-on and thread-offdesign allowing a ½” cover plate adjustment. Coverplate temperature rating shall be 135�F (57�C). A plasticprotective cap shall be provided and factory installedinside the sprinkler cup to protect the sprinkler fromdamage, which could occur during construction beforethe cover plate is installed. Standard cover plate finish:[White] [Custom Color– specify]. ]. Concealed pendentsprinklers shall be Reliable Model F1 Res 30, 49 & 58CCP, SIN R3511, R3516 & R3513 (Bulletin 135).

ModelF1RES40andF1Res44HorizontalSidewallResidential Sprinkler Specifications

Model F1 Res 40 Horizontal Sidewall SprinklerSprinklers shall be [cULus Listed] [New York City MEA

Approved (258-93-E)] low flow residential horizontalsidewall sprinklers engineered to provide a minimumdesign density of 0.05 gpm/ft2 over the listed coveragearea. Listed flows as specified by the manufacturer’stechnical data sheets are to be used. Residentialsprinklers shall be installed in conformance with themanufacturer’s installation guidelines and the applicableinstallation standard. Where horizontal sidewallresidential sprinklers are installed under sloped ceilingshaving a pitch from [4/12] to [8/12], the sprinklers shall belisted for such use. Sprinkler frame and deflector shall beof bronze frame construction having a ½” NPT thread.Water seal assembly shall consist of a Teflon-coatedBelleville spring washer with top-loaded extruded or coldhead cup with 3 mm glass bulb containing no plasticparts, and having a temperature rating of [155�F (68�C)][175�F (79�C)]. Sprinklers shall have a nominal K-factor of4.0 (57.1). Standard finish: [Bronze] [Chrome-plated][White Polyester] [Special finish– specify]. Residentialhorizontal sidewall sprinklers shall be Reliable Model F1Res 40, SIN R3538 (Bulletin 135).

Model F1 Res 40 RecessedHorizontal Sidewall Sprinkler

Use description for the Model F1 Res 40 horizontalsidewall sprinkler with the following modifications: Replace“horizontal sidewall sprinkler” with “recessed horizontalsprinkler.” Add: Recessed escutcheon assembly shall bea steel, two-piece escutcheon with ½” adjustment (ModelF2). Standard finish shall be [brass][bright chrome] [whitepainted] [Special finish– specify]. Residential recessedhorizontal sidewall sprinklers shall be Reliable Model F1Res 40/F2, SIN R3538 (Bulletin 135).

Model F1 Res 44 Horizontal Sidewall SprinklerSprinklers shall be [cULus Listed] [New York City MEA

Approved (258-93-E)] low flow residential horizontalsidewall sprinklers engineered to provide a minimumdesign density of 0.05 gpm/ft2 over the listed coveragearea. Listed flows as specified by the manufacturer’stechnical data sheets are to be used. Residentialsprinklers shall be installed in conformance with themanufacturer’s installation guidelines and theapplicable installation standard. Where horizontalsidewall residential sprinklers are installed under slopedceilings having a pitch from [4/12] to [8/12], thesprinklers shall be listed for such use. Sprinkler frameand deflector shall be of bronze frame constructionhaving a ½” NPT thread. Water seal assembly shallconsist of a Teflon-coated Belleville spring washer withtop-loaded extruded or cold head cup with 3 mm glassbulb containing no plastic parts, and having atemperature rating of [155�F (68�C)] [175�F (79�C)].Sprinklers shall have a nominal K-factor of 4.4 (62.8).Standard finish: [Bronze] [Chrome-plated] [WhitePolyester] [Special finish– specify]. Residentialhorizontal sidewall sprinklers shall be Reliable Model F1Res 44, SIN R3531 (Bulletin 135).

Model F1 Res 44 RecessedHorizontal Sidewall Sprinkler

Use description for the Model F1 Res 44 horizontalsidewall sprinkler with the following modifications:Replace “horizontal sidewall sprinkler” with “recessedhorizontal sprinkler.” Add: Recessed escutcheonassembly shall be a steel, two-piece escutcheon with ½”adjustment (Model F2). Standard finish shall be[brass][bright chrome] [white painted] [Special finish–specify]. Residential recessed horizontal sidewallsprinklers shall be Reliable Model F1 Res 44/F2, SINR3531 (Bulletin 135).

11.

Page 17: SYSTEM EQUIPMENT · 2018. 7. 27. · Model RFC43 (SIN RA0612) Model RFC49 (SIN RA0616) Flat Concealed Residential Sprinklers A Concealed Residential Sprinkler engineered for a minimum

The equipment presented in this bulletin is to be installed in accordance with the latest pertinent Standards of the National Fire Protection Association, Factory Mutual ResearchCorporation, or other similar organizations and also with the provisions of governmental codes or ordinances, whenever applicable.

Products manufactured and distributed by RELIABLE have been protecting life and property for over 80 years, and are installed and serviced by the most highly qualified and reputable

sprinkler contractors located throughout the United States, Canada and foreign countries.

Manufactured by

(800) 431-1588 Sales Offices

(800) 848-6051 Sales Fax

(914) 829-2042 Corporate Offices

www.reliablesprinkler.com Internet Address

RecycledPaper

Revision lines indicate updated or new data.

EG. Printed in U.S.A. 06/08 P/N 9999970235

Model F1 Res 76 PendentSprinklers shall be [cULus Listed] low flow residential

pendent sprinklers engineered to provide a minimumdesign density of 0.05 gpm/ft2 over the listed coveragearea. Listed flows as specified by the manufacturer’stechnical data sheets are to be used. Residentialsprinklers shall be installed in conformance with themanufacturer’s installation guidelines and the applicableinstallation standard. Sprinkler frame and deflector shall beof bronze frame construction having a ¾” NPT thread.Water seal assembly shall consist of a Teflon-coatedBelleville spring washer with machined or cold head cupwith 3 mm glass bulb containing no plastic parts, andhaving a temperature rating of [155�F (68�C)] [175�F(79�C)]. Sprinklers shall have a nominal K-factor of 7.6.Standard finish: [Bronze] [Chrome-plated] [WhitePolyester] [Special finish– specify]. Residential pendentsprinklers shall be Reliable Model F1 Res 76, SIN R7618(Bulletin 135).

Model F1 Res 76 Recessed Pendent/F1,Model F1 Res 76 Recessed Pendent/F2,Model F1 Res 76 Recessed Pendent/FP

Sprinklers shall be [cULus Listed] low flow residentialrecessed pendent sprinklers engineered to provide aminimum design density of 0.05 gpm/ft2 over the listedcoverage area. Listed flows as specified by themanufacturer’s technical data sheets are to be used.Residential sprinklers shall be installed in conformancewith the manufacturer’s installation guidelines and theapplicable installation standard. Sprinkler frame anddeflector shall be of bronze frame construction having a¾” NPT thread. Water seal assembly shall consist of aTeflon-coated Belleville spring washer with machined orcold head cup with 3 mm glass bulb containing noplastic parts, and having a temperature rating of [155�F(68�C)] [175�F (79�C)]. Sprinklers shall have a nominalK-factor of 7.6. Standard finish: [Bronze][Chrome-plated] [White Polyester] [Special finish–specify]. Recessed escutcheon assembly shall be asteel, two-piece escutcheon [with ½” adjustment (ModelF2)] [with ¾” adjustment (Model F1)] [of push-on andthread off design with ½” adjustment (Model FP)].Standard finish shall be [brass][bright chrome] [whitepainted]. Residential recessed pendent sprinklers shallbe Reliable [Model F1 Res 76 Recessed Pendent/F1][Model F1 Res 76 Recessed Pendent/F2] [Model F1 Res76 Recessed Pendent/FP] SIN R7618 (Bulletin 135).

Model F1 Res 76 CCP Pendent (Concealed)Sprinklers shall be [cULus Listed] low flow residential

concealed sprinklers engineered to provide a minimumdesign density of 0.05 gpm/ft2 over the listed coveragearea. Listed flows as specified by the manufacturer’stechnical data sheets are to be used. Residential sprinklersshall be installed in conformance with the manufacturer’sinstallation guidelines and the applicable installationstandard. Sprinkler frame and deflector shall be of bronzeframe construction having a ¾” NPT thread. Water sealassembly shall consist of a Teflon-coated Belleville springwasher with machined or cold head cup with 3 mm glassbulb containing no plastic parts, and having a temperaturerating of 155�F (68�C). Cover plate assembly shall consistof a brass cover plate and copper alloy retainer flange.Method of attaching the cover plate to the sprinkler cupshall be a push-on and thread-off design allowing a ½”cover plate adjustment. Cover plate temperature ratingshall be 135�F (57�C). A plastic protective cap shall beprovided and factory installed inside the sprinkler cup toprotect the sprinkler from damage, which could occurduring construction before the cover plate is installed.Standard cover plate finish: [White] [Custom Color–specify]. ]. Concealed pendent sprinklers shall be ReliableModel F1 Res 76 CCP, SIN R7618 (Bulletin 135).

Page 18: SYSTEM EQUIPMENT · 2018. 7. 27. · Model RFC43 (SIN RA0612) Model RFC49 (SIN RA0616) Flat Concealed Residential Sprinklers A Concealed Residential Sprinkler engineered for a minimum

Eddythread 40

A company

1819 Clarkson RoadChesterfield, MO 63017(800) 325-4467FAX: (636) 537-2645www.bullmoosetube.come-mail: [email protected]

For additional information,contact your salesperson today at(800) 325-4467 or (636) 537-2600in the USA, or from Canadacall (800) 882-4666

All information contained herein is accurate as known at the time of publication. Bull Moose Tube reserves the right to change product specifications without notice and without incurring obligation.3/01

A Lightweight Schedule 40 Replacement PipeThat Has a Corrosion Resistance Ratio of 1.0

Bull Moose Tube Company has been making pipe for a long time and is recognized as a producer of quality pipeproducts. Eddythread 40 is designed with the same thoroughness as our other fine pipe products and now ourcustomers have an option to buy a carefully designed replacement for Schedule 40 that:

• Has a Corrosion Resistance Ratio of 1.0• Has No Thread Warning• Has a Pressure Rating of 300 psi• Is Lighter Weight Than Schedule 40• Is Approved by Factory Mutual and Listed by Underwriters Laboratories• Is Produced in Accordance to ASTM A-135 and A-795• Can be Used With Standard Schedule 40 Threaded Fittings, Couplings and Valves• Is Produced From Steel With Excellent Properties of Strength and Threadability• Can be Used in Wet, Dry, Preaction, and Deluge Type Sprinkler Systems*• Offers Lower Freight Costs

EDDYTHREAD 40 SPECIFICATIONS

Nominal Pipe Size (in)

WeightLb./Ft

I.D.(in)

BundleSize

11-1/41-1/2

2

1.6002.1392.5623.364

1.0901.4251.6552.124

61373737

CORROSION RESISTANCE RATIOS

NominalPipe Size (in)

Sch. 40 EDDYTHREAD 40 EDDYLITE

11-1/41-1/2

2

1.001.001.001.00

1.001.001.001.00

0.740.480.470.38

* Eddythread 40 can be hot dipped galvanized to meet FM's requirement for dry systems

Page 19: SYSTEM EQUIPMENT · 2018. 7. 27. · Model RFC43 (SIN RA0612) Model RFC49 (SIN RA0616) Flat Concealed Residential Sprinklers A Concealed Residential Sprinkler engineered for a minimum

TECHNICAL INFORMATIONWEIGHTS & DIMENSIONS

FlameGuard™CPVC FIRE SPRINKLER

PIPING PRODUCTS

February 1, 2010SUPERSEDES ALL PREVIOUS EDITIONS

FG-4-0210Visit our web site

www.spearsmfg.com

Page 20: SYSTEM EQUIPMENT · 2018. 7. 27. · Model RFC43 (SIN RA0612) Model RFC49 (SIN RA0616) Flat Concealed Residential Sprinklers A Concealed Residential Sprinkler engineered for a minimum

FlameGuard™ CPVC FIRE SPRINKLER PIPING PRODUCTS

1 SPEARS® MANUFACTURING COMPANY

CPVC FIRE SPRINKLER PIPE SDR 13.5 (ASTM F 442)

Part NumberNominal Size Average O.D. Average I.D.

Approx. Weight Lbs./Ft. Inches (mm) Inches (mm) Inches (mm)

CP-007 3/4 (19.1) 1.050 (26.7) .874 (22.5) .181CP-010 1 (25.4) 1.315 (33.4) 1.101 (28.2) .280CP-012 1-1/4 (31.8) 1.660 (42.2) 1.394 (35.6) .418CP-015 1-1/2 (38.1) 1.900 (48.3) 1.598 (40.7) .550CP-020 2 (50.8) 2.375 (60.3) 2.003 (50.9) .872CP-025 2-1/2 (63.5) 2.875 (73.0) 2.423 (61.5) 1.260CP-030 3 (76.2) 3.500 (88.9) 2.950 (75.0) 1.900

Dimension ReferenceG = (LAYING LENGTH) Intersection of center lines to bottom of socket/thread; 90° elbows, tees, crosses; ± 1/32 inch.H = Intersection of center lines to face of fitting; 90° elbows tees, crosses; ± 1/32 inch.J = Intersection of center lines to bottom of socket/thread; 45° elbows; ± 1/32 inch L = Overall length of fittings; ± 1/16 inch.

M = Outside diameter of socket/thread hub; ± 1/16 inch.N = Socket bottom to socket bottom; couplings; ± 1/16 inch.Q = Width of flats; ±1/16 inch.W = Height of cap; ± 1/16 inch.

WARNING: DO NOT USE COMPRESSED AIR OR GAS TO TEST ANY PVC OR CPVC THERMOPLASTIC PIPING PRODUCT OR SYSTEM, AND DO NOT USE DEVICES PROPELLED BY COMPRESSED AIR OR GAS TO CLEAR SYSTEMS. THESE PRACTICES MAY RESULT IN EXPLOSIVE FRAGMENTATION OF SYSTEM PIPING AND COMPONENTS CAUSING SERIOUS OR FATAL BODILY INJURY.

NOT FOR USE WITH COMPRESSED AIR OR GASES

The information contained in this publication is based on current information and Product design at the time of publication and is subject to change without notification. Our ongoing commitment to product improvement may result in some variation. No representations, guarantees or warranties of any kind are made as to its accuracy, suitability for particular applications or results to be obtained therefrom. For verification of technical data or additional information not contained herein, please contact Spears® Technical Services Department [West Coast: (818) 364-1611—East Coast: (717) 938-9006].

General InformationRECOMMENDATIONS FOR INSTALLERS AND USERS:Plastic piping systems should be ENGINEERED, INSTALLED and OPERATED in accordance with ESTABLISHED DESIGN AND ENGINEERING STANDARDS AND PROCEDURES for plastic piping systems. Suitability for the intended service application should be determined by the installer and/or user prior to installation of a plastic piping system. All Installation and maintenance personnel should be trained in the proper handling and installation requirements and precautions of plastic piping systems. PRIOR TO ASSEMBLY, all piping system components should be inspected for damage or irregularities. Mating components should be checked to assure that tolerances and engagements are compatible. Do not use any components that appear irregular or do not fit properly. Contact the appropriate manufacturer of the component product in question to determine usability. Consult all applicable codes and regulations for compliance prior to installation.

Installation must be made in accordance with Spears® Manufacturing CompanyFlameGuard™ CPVC Fire Sprinkler Piping Products Installation Instructions - FG-3

NOTE — Individual or group instruction in correct solvent welding procedures is available by contacting your local distributor or your servicing Spears® Regional Distribution Center.SOLVENT CEMENT CONNECTIONS — Spears® Manufacturing Company recommends the use of Spears® Two Step FS-1 primer with FS-3 solvent cement OR Spears® FS-5 One Step solvent cement for joining Spears® products. Use of solvent cementing products not approved for CPVC fire sprinkler systems, or failure to follow installation instructions will automatically void the warranty.THREADED CONNECTION — Spears® Manufacturing Company recommends the use of Spears® BLUE 75™ Thread Sealant. This product has been tested by Spears® and the sealant manufacturer for compatibility with the Spears® CPVC fire sprinkler products. Consult the sprinkler head manufacturer before using this product. WARNING: OTHER PIPE JOINT COMPOUNDS OR PASTES MAY CONTAIN SUBSTANCES THAT COULD CAUSE STRESS CRACKING IN THE CPVC OR OTHER FITTING COMPONENTS. Care must be taken to avoid over torquing - generally 1 to 2 turns beyond finger tight is all that is required to make up a threaded connection. Factory testing has indicated 10-25 ft. lbs. of torque is adequate to obtain a leak free seal.GASKET SEALED THREAD CONNECTIONS — This type of connection can only be made with Spears® TorqueSafe™ style Gasket Sealed Female Sprinkler Adapters. DO NOT USE ANY TYPE OF THREAD SEALANT WHEN INSTALLING THIS TYPE OF ADAPTER. Tape or paste may impair proper sealing and function. Testing has shown that hand tight until snug is all that is needed to seal this special connection.

Page 21: SYSTEM EQUIPMENT · 2018. 7. 27. · Model RFC43 (SIN RA0612) Model RFC49 (SIN RA0616) Flat Concealed Residential Sprinklers A Concealed Residential Sprinkler engineered for a minimum
Page 22: SYSTEM EQUIPMENT · 2018. 7. 27. · Model RFC43 (SIN RA0612) Model RFC49 (SIN RA0616) Flat Concealed Residential Sprinklers A Concealed Residential Sprinkler engineered for a minimum

DescriptionFPPI TrimFit Bronze Globe

Valves are precision cast then

machined using state of the art

facilities. Each valve features a

full floating seat holder for

reduced seat wear when clos-

ing the valve. Seat is made of

pure virgin Teflon* for longer

seat life and reduced mainte-

nance as compared to rubber

seat valves. TrimFit trim valves

are suitable for use in regular

(175psi) and high pressure

(300psi) sprinkler systems.

Standard configuration is FNPT

x FNPT and is available in 1/4"

IPS through 2" IPS sizes. Each

valve carrries the UL Listing and

is rated for use to 300psi.

UL/ULC Listed 2R97

InstallationInstall in accordance with usual

and customary installation

techniques for fire sprinkler

systems. Use a suitable thread

sealant on the male threads of

the pipe being threaded into the

valve body. We recommend

either Teflon* tape or PipeFit

Thread Sealant Paste with

PTFE. (PTFE is the chemical

equivalent of Teflon*) DO NOT

OVERTIGHTEN. OVERTIGHTEN-

ING MAY CAUSE CRACKS OR

LEAKS.

*Teflon is a registered trade-

mark of DuPont.

PipeFit, TrimFit are regis-

tered trademarks of Fire Protec-

tion Products, Inc.

SpecsMaterial:

Brass or bronze

Seat-Teflon*

Hand wheel-JIS FC 20 painted

red.

Sizes:

06-798 1/4" IPS FNPT

06-800 1/2"

06-802 3/4"

06-804 1"

06-806 1 1/4"

06-808 1 1/2"

06-810 2"

©2000-2002 Fire Protection Products, Inc.

For questions:

1 800 344-1822

1 800 344-3775 fax

http://www.fppi.com

[email protected]

TrimFit

Bronze Globe

Valve with Teflon*

Seat, UL/ULC

Listed 300 psi

Page 23: SYSTEM EQUIPMENT · 2018. 7. 27. · Model RFC43 (SIN RA0612) Model RFC49 (SIN RA0616) Flat Concealed Residential Sprinklers A Concealed Residential Sprinkler engineered for a minimum

DescriptionThe bronze swing check valvefeatures a full floating clapperassembly that provides for apositive seal each time thevalve is cycled. This featureimproves the swing checkvalves ability to "clear" anydebris that may be present inthe water supply. The re-cessed access cap designeliminates unnessessarymaterial, keeping the overallcost of the valve low. The seatmaterial is NBR which pro-vides for a positive seal evenunder light residual pres-sures. Note: This valve is notintended to be user service-able. The recessed cap doesnot provide access to anysevicable components.

InstallationThe female by female swingcheck valve should be in-stalled in accordance withcommonly used installationpractices for the fire sprinklerindustry. Proper seal of thethreads can be accomplishedby applying a liberal amountof PTFE based thread seal-ant such as PipeFit ThreadSealant Paste or PTFE Tape.Make sure to tighten the valveno more than 1-2 revolutionspast initial thread contact ofthe male and female threads.

Refer to service instruc-tions on page 2 for clap-per/seat replacement.

WARNINGDO NOT OVER TIGHTEN.Over tightening maycaused the valve body tocrack and leak.

SpecsValve Body:

Cast Bronze(85-5-5-5)

Clapper Assembly:Forged Brass

Seat:NBR (Chloramine

Resistant)

Sizes:1/2" IPS- 2" IPSFemale by female

Rated Pressure:175 Psi

©1999-2000 Fire Protection Products, Inc.

For questions:800 344-1822800 344-3775 faxhttp://www.fppi.com

Swing CheckValve,Full FloatingClapper Assembly

Page 24: SYSTEM EQUIPMENT · 2018. 7. 27. · Model RFC43 (SIN RA0612) Model RFC49 (SIN RA0616) Flat Concealed Residential Sprinklers A Concealed Residential Sprinkler engineered for a minimum

Service Instructions for swing check valve with full floating clapper assembly

The swing check valve has been designed with a serviceable clapper assembly that can be serviced with thevalve left in place. Service would only be required in the event of seat failure or an obstruction caused by theintroduction of foreign material in the water way.

To service the FPPI Swing Check Valve with Full Clapper Assemply, shut off the water supply at its' source.Drain water from the system. As a safety precaution, it is recommended that the control valve for the watersupply be marked so as to notify all personnell that the system is being serviced and that the water has beenshut-off until repairs have been completed.

Once the system is drained, it is safe to remove the access cap from the swing check valve with an adjustablewrench. Use appropriate care when removing the cap as to not cause damage to the access cap or the valvebody.Once the cap has been removed the clapper assembly will be in plain view. Simply lift the clapperassemply from is resting place. Before installing the replacement clapper assembly, visually inspect themachined seat surface of the valve to make sure that is clean and free of any foreign materials and that thewater ways at each end of the valve are clear of obstruction. To install the replacement clapper assembly,reinsert the new assembly in the same fashion that the origianal was removed. Make sure the replacementclapper assembly is properly seated and swings freely. Replace access cap. Tighten the access cap until fullyseated. It is recommended that a small amount of thread sealant such as PipeFit Thread Sealant with PTFE isused on the threads of the access cap. To assure future serviceability do not use anaoerbic or hardening threadsealants.

Visually inspect the area to make sure that all removed parts can be accounted for and the access cap hasbeen reinstalled correctly. The system can now be placed back into service by opening the valve that controlsthe flow of water to the system.

After the system has been pressurized, visually reinspect the check valve to make sure there are no apparentleaks. Notify appropriate personnel that the system is back in service.

For questions or additional information contact Fire Protection Products, Inc at 1 800 344-1822 or your nearestdistributor.

Page 25: SYSTEM EQUIPMENT · 2018. 7. 27. · Model RFC43 (SIN RA0612) Model RFC49 (SIN RA0616) Flat Concealed Residential Sprinklers A Concealed Residential Sprinkler engineered for a minimum

a companyTMZURN

DOCUMENT #: REVISION:BF-975XL(lg) 6/09

SPECIFICATION SUBMITTAL SHEET

Page 1 of 2

Model 975XLReduced Pressure Principle Assembly

WILKINS a Zurn company, 1747 Commerce Way, Paso Robles, CA 93446 Phone:805/238-7100 Fax:805/238-5766In Canada: ZURN INDUSTRIES LIMITED, 3544 Nashua Dr., Mississauga, Ontario L4V 1L2 Phone:905/405-8272 Fax:905/405-1292

Product Support Help Line: 1-877-BACKFLOW (1-877-222-5356) • Website: http://www.zurn.com

FEATURESSizes: 3/4" 1" 1 1/4" 1 1/2" 2"

Maximum working water pressure 175 PSIMaximum working water temperature 180°FHydrostatic test pressure 350 PSIEnd connections Threaded ANSI B1.20.1

OPTIONS(Suffixes can be combined)

- with full port QT ball valves (standard) L - less ball valves U - with union ball valves MS - with integral relief valve monitor switch P - for reclaimed water systems S - with bronze "Y" type strainer BMS - with battery operated monitor switch FDC - with fire hydrant connection; 2" only TCU - with test cocks up V - with union swivel elbows (3/4" & 1") SE - with street elbows FT - with integral male 45° flare SAE test fitting

ACCESSORIES Air gap (Model AG) Repair kit (rubber only) Thermal expansion tank (Model XT) Soft seated check valve (Model 40XL) Shock arrester (Model 1250) QT-SET Quick Test Fitting Set Ball valve handle locks Test Cock Lock (Model TCL24)

DIMENSIONS & WEIGHTS (do not include pkg.)

APPLICATIONDesigned for installation on potable water lines to protect against both backsiphonage and backpressure of contami-nated water into the potable water supply. Assembly shall provide protection where a potential health hazard exists.

STANDARDS COMPLIANCE● ASSE® Listed 1013● IAPMO® Listed● UL® Classified (less shut-off valves or with OS&Y valves)● C-UL® Classified ● CSA® Certified● AWWA Compliant C511● Approved by the Foundation for Cross Connection Control and Hydraulic Research at the University of Southern California● NYC MEA 425-89-M VOL 3

MATERIALSMain valve body Cast Bronze ASTM B 584Access covers Cast Bronze ASTM B 584Fasteners Stainless Steel, 300 SeriesElastomers Silicone (FDA Approved) Buna Nitrile (FDA Approved)Polymers Noryl™, NSF ListedSprings Stainless steel, 300 series

Relief Valve discharge port:3/4” - 1” - 0.63 sq. in.1 1/4” - 2” - 1.19 sq. in.

MODEL SIZE

DIMENSIONS (approximate) WEIGHT

A A UNIONBALL VALVES

B LESS BALLVALVES C D E F G

LESS BALL

VALVES

WITH BALL

VALVESin. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm lbs kg lbs. kg3/4 20 12 305 13 3/4 349 7 3/4 197 2 1/8 54 3 76 3 1/2 89 5 127 16 1/8 410 10 4.5 12 5.51 25 13 330 14 1/2 368 7 3/4 197 2 1/8 54 3 76 3 1/2 89 5 127 17 3/8 441 10 4.5 14 6.4

1 1/4 32 17 432 18 13/16 478 10 15/16 278 2 3/4 70 3 1/2 89 5 127 6 3/4 171 22 9/16 573 22 10 28 12.71 1/2 40 17 3/8 441 19 3/8 492 10 15/16 278 2 3/4 70 3 1/2 89 5 127 6 3/4 171 24 1/16 611 22 10 28 12.7

2 50 18 1/2 470 20 1/2 521 10 15/16 278 2 3/4 70 3 1/2 89 5 127 6 3/4 171 26 1/2 673 22 10 34 15.4

AB

G

CD

F

E

Page 26: SYSTEM EQUIPMENT · 2018. 7. 27. · Model RFC43 (SIN RA0612) Model RFC49 (SIN RA0616) Flat Concealed Residential Sprinklers A Concealed Residential Sprinkler engineered for a minimum

Page 2 of 2

WILKINS a Zurn company, 1747 Commerce Way, Paso Robles, CA 93446 Phone:805/238-7100 Fax:805/238-5766IN CANADA: ZURN INDUSTRIES LIMITED, 3544 Nashua Dr., Mississauga, Ontario L4V 1L2 Phone:905/405-8272 Fax:905/405-1292

Product Support Help Line: 1-877-BACKFLOW (1-877-222-5356) • Website: http://www.zurn.com WILKINS a Zurn company, 1747 Commerce Way, Paso Robles, CA 93446 Phone:805/238-7100 Fax:805/238-5766In Canada: ZURN INDUSTRIES LIMITED, 3544 Nashua Dr., Mississauga, Ontario L4V 1L2 Phone:905/405-8272 Fax:905/405-1292

Product Support Help Line: 1-877-BACKFLOW (1-877-222-5356) • Website: http://www.zurn.com

0 20 40 60 805

10

15

20

0 50 100 150 200 2505

10

15

20

Rated Flow (Established by approval agencies)

FLOW RATES (GPM)

PRES

SUR

E LO

SS (P

SIG

)

69

PR

ES

SU

RE

LO

SS

(kpa

)

FLOW RATES (l/s)

MODEL 975XL 3/4", 1", 1 1/4", 1 1/2" & 2" (STANDARD & METRIC)

35

3/4" (20mm) 1" (25mm) 1 1/4" (32mm)2" (50mm)

103

15.812.69.56.33.25.03.82.521.261 1/2”

(40mm)137

TYPICAL INSTALLATION

Local codes shall govern installation require-ments. To be installed in accordance with the manufacturers’ instructions and the latest edition of the Uniform Plumbing Code. Unless otherwise specified, the assembly shall be mounted at a minimum of 12” (305mm) and a maximum of 30” (762mm) above adequate drains with sufficient side clearance for testing and maintenance. The installation shall be made so that no part of the unit can be submerged.

OUTDOOR INSTALLATIONINDOOR INSTALLATION(*Shown w/ optional BMS)

SPECIFICATIONSThe Reduced Pressure Principle Backflow Preventer shall be ASSE® Listed 1013, rated to 180°F and supplied with full port ball valves. The main body and access covers shall be bronze (ASTM B 584), the seat ring and all internal polymers shall be NSF® Listed Noryl™ and the seat disc elastomers shall be silicone. The first and second checks shall be accessible for maintenance without removing the relief valve or the entire device from the line. If installed indoors, the installation shall be supplied with an air gap adapter and integral monitor switch. The Reduced Pressure Principle Backflow Preventer shall be a WILKINS Model 975XL.

Capacity thru Schedule 40 PipePipe size 5 ft/sec 7.5 ft/sec 10 ft/sec 15 ft/sec

1/8" 1 1 2 31/4" 2 2 3 53/8" 3 4 6 91/2" 5 7 9 143/4" 8 12 17 251" 13 20 27 40

1 1/4" 23 35 47 701 1/2" 32 48 63 95

2" 52 78 105 167

BATTERYMONITORSWITCH*

AIR GAPFITTING

12" MIN.30" MAX.

FLOOR DRAIN

DIRECTION OF FLOW

FLOOR

CENTRALSTATIONALARMPANEL

12" MIN30" MAX

PROTECTIVEENCLOSURE

OPTIONALWATER METER

INLET SHUT-OFF

AIR GAP

DRAIN

DIRECTION OF FLOW

FLOW CHARACTERISTICS

jkobobel
Accepted
Page 27: SYSTEM EQUIPMENT · 2018. 7. 27. · Model RFC43 (SIN RA0612) Model RFC49 (SIN RA0616) Flat Concealed Residential Sprinklers A Concealed Residential Sprinkler engineered for a minimum

System Sensor WFDT Retard and WFDTNR Non-Retard T-Tap Waterflow Detectors aredesigned for primary signaling in residential systems and branch line signaling in larger systems. Both models fit any tee that has a 1″ NPT branch, including: 1″, 11⁄4″ and 11⁄2″ NPT threaded ferrous and brass tees; 1″, 11⁄4″, 11⁄2″ and 2″ coppersweat tees; Central, Spears®, and Victaulic® brand 1″ CPVC tees; and 11⁄2″ polybuty-lene tees.

Design. The design of the WFDT and WFDTNR makes them easy to install andsimple to maintain. Either can be mounted in the vertical or horizontal posi-tion. Two conduit openings permit easy attachment to the local alarm system.The retard mechanism (Model WFDT only) and switch assemblies are field-replaceable.

Features. Nine different flexible plastic paddles fit 1″, 11⁄4″, 11⁄2″ and 2″ tees.Sizes are marked clearly on the paddle for ease of installation. Plastic paddlesslip over the actuating lever and are securely fastened with one screw. Thehandy depth gauge insures the proper installation depth and clearance of thedetector to the tee.

Construction. The WFDT and WFDTNR include a durable tamper resistantenclosure and rugged switch assembly. The long lasting covers completelyenclose the electrical components to keep out dust and dirt. Improved self-guid-ing security screws and removal tools make detectors resistant to tampering andsimplify field maintenance. Dual SPDT switches are enclosed in a durable termi-nal block for added strength.

Sealed retard mechanism (Model WFDT)assures that the retard is not contami-nated by dust and dirt when the cover isremoved

Visual Switch Activation (Model WFDT)permits installer to accurately set theretard even under extremely noisy conditions

100% Synchronization activates bothalarm panel and local bell simultaneously

Accommodates up to 12 AWG wire

Models Available

WFDT Waterflow DetectorWFDTA Waterflow Detector

(ULC/Canadian)WFDTNR Waterflow Detector

(non-retard)

Replacement Parts

A77-01-02 Terminal Block for WFDTA77-01-08 Terminal Block for WFDTNRA3008-00 Retard MechanismPRK9 Paddle Kit546-7000 Cover Tamper Switch KitS07-66-02 Tamper Screws for CoverWFDW Cover WrenchWFDN4 NEMA-4 Gasket KitC58-164-01 Metal Cover

Product Overview

WFDT Water flow Detector

T-TapWaterflow Detector

WFDTNR Water flow Detector

Page 28: SYSTEM EQUIPMENT · 2018. 7. 27. · Model RFC43 (SIN RA0612) Model RFC49 (SIN RA0616) Flat Concealed Residential Sprinklers A Concealed Residential Sprinkler engineered for a minimum

System Sensor Sales and Service

©2000 System Sensor. The company reserves the right to change product specifications without notice. A05-195-06•8/00(10K)•#672Spears® is a registered trademark of the Spears Manufacturing Company; Victaulic® is a registered trademark of Victaulic Company of America.

Engineering Specifications

Model shall be a WFDT or WFDTNR as manufactured by System Sensor. T-tap water flow detectors shallbe installed on a tee that has a 1″ NPT branch including: 1″, 11⁄4″ , or 11⁄2″ threaded ferrous or brasstee; 1–2″ copper sweat tees; Central, Spears®, and Victaulic® brand 1″ CPVC tees; or 11⁄2″ polybutylenetee as designated on the drawings and/or as specified herein. Detectors shall mount on any clear pipespan of the appropriate size, either a vertical or horizontal run at least 6″ from any fittings or valveswhich may change water direction, flow rate, or pipe diameter or no closer than 24″ from a valve ordrain. Detectors shall have a sensitivity in the range of 4 to 10 gallons per minute and a static pressurerating of 250 psi. The retard t-tap detector shall be a sealed mechanical pneumatic unit with visual indi-cation of actuation. The actuation mechanism shall include a polyethylene vane inserted through thetee fitting and connected by a mechanical linkage to the delay mechanism. The non-retard t-tap detec-tor shall respond with no time delay to water flow in the specified direction and range. Outputs shallconsist of dual SPDT switches (Form C contacts). Two conduit entrances (one of which is a knockouttype) for standard fittings of commonly used electrical conduit shall be provided on the detectors. Agrounding provision is provided. All detectors shall be listed by Underwriters Laboratories for indoor oroutdoor use.

B k i h f

Ordering Information

Model Number Description

WFDT Waterflow Detector, Fits 1″, 11⁄4″, 11⁄2″ ferrous and brass threaded tees; 1″, 11⁄4″, 11⁄2″, 2″ copper sweat tees; 1″ CPVC tees;and 11⁄2″ polybutylene tees

WFDTNR Waterflow Detector, non-retard, fits same tees as Model WFDT

A77-01-02 Replacement Terminal Block for WFDT

A77-01-08 Replacement Terminal Block for WFDTNR

A3008-00 Replacement Retard Mechanism

PRK9 Replacement Paddle Kit — 11 paddles for WFDT and WFDTNR (see WFDT for sizes)

546-7000 Cover Tamper Switch Kit for WFDT

S07-66-02 Replacement Tamper Screws for Covers of WFDT, WFDTNR

WFDW Replacement Tamper Proof Wrench for Cover of WFDT, WFDTNR

WFDN4 NEMA-4 Gasket Kit

C58-164-01 Replacement Metal Cover

Static Pressure Rating250 PSI

Triggering Threshold Bandwidth (Flow Rate)4 – 10 GPM

Maximum Surge18 FPS

Compatible Tee FittingsThreaded ferrous and brass tees, copper sweattees, CPVC tees, and polybutylene tees

Contact Ratings Two sets of SPDT (Form C)10.0 A @ 125/250 VAC2.5 A @ 24 VDC

Overall Dimensions, InstalledWFDT: 4.5″ H x 3.75″ W x 6.7″ L(11.4cm H x 9.5cm W x 17cm L)

WFDTNR: 3.75″ H x 3.25″ W x 4.25″ L(9.5cm H x 8.2cm x W x 10.8cm L)

Conduit Entrances2 openings for 1⁄2″ conduit

Operating Temperature Range32°F – 120°F (0°C – 49°C)

Cover Tamper SwitchUL Models: optional P/N 546-7000ULC/Canadian Models: factory installed

EnclosureUL Indoor/Outdoor Rated

Shipping WeightWFDT: 2.6 lbs. (1.2 kg.)WFDTNR: 1.5 lbs. (0.7 kg.)

Service UseAutomatic Sprinkler: NFPA 13One or Two Family Dwelling: NFPA 13DResidential Occupancies up to 4 Stories: NFPA 13RNational Fire Alarm Code: NFPA 72

Warranty3 years

U.S. Patent Nos.3,845,259; 4,782,333; 5,213,205

Top View

Switch 1

COM COM

A B B A Switch 2

NOTE: Ccwpo

Electrical Connections for WFDT

CONTACT RATINGS125/250 VAC

24 VDC10 AMPS2.5 AMPS

WFDTH

B B

COM COM

WFDTH

B B

COM COM

itiatingd FACP

End of line resistorTo nonsilenceable initiatingzone of listed FACP

Typical FACP Connection

{

B

COM

to power sourcecompatible

with belllocalbell

Typical Local Bell Connection

To power sourcecompatible with bell

WFDTH Switch Assembly

Common and B connections will close whenvane is deflected, i.e., when water is flowing.Dual switches permit applications to be com-bined on a single detector.

Break wire as shown for supervision of connec-tion. Do not allow stripped wire leads to extendbeyond switch housing. Do Not loop wires.

40 1 2 315 30

545 55 70

Dial settingDelay (seconds)

0

12

3

45

32

0

1 4

51530 45 55

70

ONNU MBER DIAL

TIME

APP

ROX IM

ATEDEL AY (SECON

DS)

Table of dial settingsembossed here

(see below)

Delayadjustment

dial

0

0

Delay Adjustment Dial

General Specifications

System Sensor Headquarters3825 Ohio Avenue St. Charles, IL 60174Ph: 800-SENSOR2 Fx: 630/377-6495Documents On Demand: 1-800-736-7672 x3Web: www.systemsensor.com

System Sensor in CanadaPh: 905.812.0767 Fx: 905.812.0771

System Sensor in EuropePh: + 44.1403.276500 Fx: + 44.1403.276501

System Sensor in ChinaPh: + 86.29.524.6253 Fx: + 86.29.524.6259

System Sensor in SingaporePh: + 65.273.2230 Fx: + 65.273.2610

System Sensor in the Far EastPh: + 852.21919003 Fx: + 852.27366580

System Sensor in AustraliaPh: + 613.54.281.142 Fx: + 613.54.281.172

System Sensor in IndiaPh: + 91.11.558.2119Fx: + 91.11.567.6815

Page 29: SYSTEM EQUIPMENT · 2018. 7. 27. · Model RFC43 (SIN RA0612) Model RFC49 (SIN RA0616) Flat Concealed Residential Sprinklers A Concealed Residential Sprinkler engineered for a minimum

SPECIFICATION SUBMITTAL SHEET

.ONTNEMUCOD .VER

WILKINS OPERATION OF ZURN INDUSTRIES, 1747 Commerce Way, Paso Robles, CA 93446 Phone:805/238-7100 Fax:805/238-5766IN CANADA: ZURN INDUSTRIES LIMITED, 3544 Nashua Dr., Mississauga, Ontario L4V 1L2 Phone:905/405-8272 Fax:905/405-1292

Product Support Help Line: 1-877-222-5356 • Website: http://www.zurn.com

Model HXT

FEATURESSizes(liters): 15 30 60 90

Fill Pressure ( and air charge pressure) 12 psiMaximum working water pressure 75 psiMaximum working water temperature 240° FThreaded connections (FNPT) ANSI B1.20.1

DIMENSIONS & WEIGHTS (do not include pkg.)

MATERIALSMain body SteelCoatings EpoxyBladder Butyl

Hydronic Expansion Tank

APPLICATION

Designed for installation on residential and commercial hy-dronic heating and cooling systems as a means of pressurecontrol due to thermal expansion.

10/00WXT-HXT

B

A

C

INLET

TO SYSTEM

CHECKFLOW

PRESSURE RELIEF VLV.

AIR VENT(MODEL WFV)

TANK(MODEL HXT)

EXPANSION

AIR SCOOP(MODEL WAS)

TEMP. PRESSURERELIEF VLV.(MODEL TP1100A)

FILLVLV.

AUTO

BOILER

(MODEL P1000A)

TYPICAL INSTALLATION

ACCESSORIES80CI - fast fill regulator

TP1100A - temperature and pressure relief valveP1000A - pressure relief valve

750 - dual check valve with atmospheric vent875CI - combination 80CI and 750WAS - Air scoopWFV - Float vent

psi (gallons) (gallons) psi in. mm in. mm lbs. kg

HXT-15 75 2.10 0.84 12 9 5/8 245 11 1/4 286 1/2 NPT 5 2.3HXT-30 75 4.50 1.81 12 12 7/8 327 12 5/16 313 1/2 NPT 8 3.6HXT-60 75 6.10 2.45 12 14 1/8 359 14 5/16 364 1/2 NPT 10 4.5HXT-90 100 15.00 6.03 12 16 406 20 3/4 527 3/4 NPT 28 12.7

"C" CONNECTION

WEIGHT

DIMENSIONSTANK DIMENSIONS AND CAPACITIES

MODEL NUMBER

"A" DIA. "B" HEIGHT TANK

VOLUME

MAXIMUM ACCEPTANCE

VOLUME

MAXIMUM WORKING

PRESSURE

FACTORY PRECHARGE