synco living train the tainer functions & operation safety & security spring 2008

32
Page 1/32 Train the Trainer - Spring 2008 Overview Window / Door Supervision Signalling Faults Displays Absence & Supervision Exercises Synco living Train the Tainer Functions & Operation Safety & Security Spring 2008

Upload: cedric

Post on 05-Jan-2016

40 views

Category:

Documents


4 download

DESCRIPTION

Synco living Train the Tainer Functions & Operation Safety & Security Spring 2008. Functions & Operation Safety & Security Overview. Settings Absence & supervision Window / door supervision Signaling (buzzer / status output) Fault inputs Fault outputs Displays Exercises. - PowerPoint PPT Presentation

TRANSCRIPT

Page 1: Synco living Train the Tainer Functions & Operation  Safety & Security Spring 2008

Page 1/32 Train the Trainer - Spring 2008

Overview Window / Door SupervisionSignalling Faults DisplaysAbsence & Supervision Exercises

Synco living

Train the Tainer

Functions & Operation Safety & Security

Spring 2008

Page 2: Synco living Train the Tainer Functions & Operation  Safety & Security Spring 2008

Page 2/32 Train the Trainer - Spring 2008

Overview Window / Door SupervisionSignalling Faults DisplaysAbsence & Supervision Exercises

Functions & Operation Safety & SecurityOverview

Settings

Absence & supervision

Window / door supervision

Signaling (buzzer / status output)

Fault inputs

Fault outputs

Displays

Exercises

Page 3: Synco living Train the Tainer Functions & Operation  Safety & Security Spring 2008

Page 3/32 Train the Trainer - Spring 2008

Overview Window / Door SupervisionSignalling Faults DisplaysAbsence & Supervision Exercises

Functions & Operation Safety & Security Absence & Supervision

Operating buttonAbsence and the monitoring pattern can be set with the central

apartment unit‘s Absence / monitoring button.

Page 4: Synco living Train the Tainer Functions & Operation  Safety & Security Spring 2008

Page 4/32 Train the Trainer - Spring 2008

Overview Window / Door SupervisionSignalling Faults DisplaysAbsence & Supervision Exercises

Functions & Operation Safety & Security Absence & Supervision

Presence & absenceWhen coming or going, the user must press the Absence /

monitoring button to make the settings for absence and supervision via the

following dialogs.

A short press on the button (< 0.4 s) lets the dialog for absence settings

appear on the display:AbsentPresent Absent

Present

Absence

Page 5: Synco living Train the Tainer Functions & Operation  Safety & Security Spring 2008

Page 5/32 Train the Trainer - Spring 2008

Overview Window / Door SupervisionSignalling Faults DisplaysAbsence & Supervision Exercises

Functions & Operation Safety & Security Absence & Supervision

AbsenceAbsence has the following impact on the plant:

Space heating and DHW heating are controlled in accordance with the selected operating mode:Main menu > Heating > Room x > Room operating mode > Optg mode absence > … Main menu > Ventilation > Operating mode > Operating mode absence > …Main menu > DHW > Operating mode > Optg mode absence > …

Simulation of presence is started:Main menu > Switching groups > Switching group x > Presence simulation > …

Switching groups are triggered (event):Main menu > Switching groups > Switching group x > . . . > Events …

SwitchDimmBlindScene

Page 6: Synco living Train the Tainer Functions & Operation  Safety & Security Spring 2008

Page 6/32 Train the Trainer - Spring 2008

Overview Window / Door SupervisionSignalling Faults DisplaysAbsence & Supervision Exercises

Functions & Operation Safety & Security Absence & Supervision

Presence & absence

Switching groups

Operating mode

Presence simulation

Page 7: Synco living Train the Tainer Functions & Operation  Safety & Security Spring 2008

Page 7/32 Train the Trainer - Spring 2008

Overview Window / Door SupervisionSignalling Faults DisplaysAbsence & Supervision Exercises

Functions & Operation Safety & Security Absence & Supervision

SupervisionAn extended press on the Absence / monitoring button (> 0.4 s) lets

the dialogfor the supervision settings appear on the display:

InactivePartly monitoredAll monitored

After the setting of absence has been confirmed (present / absent), or after 8 s, the dialog for the supervision settings opens.

Note:If supervision is not enabled, the dialog for setting absence also appears after an extended press on the button (> 0.4 s).

Supervision InactivePartly monitoredAll monitored

Page 8: Synco living Train the Tainer Functions & Operation  Safety & Security Spring 2008

Page 8/32 Train the Trainer - Spring 2008

Overview Window / Door SupervisionSignalling Faults DisplaysAbsence & Supervision Exercises

Functions & Operation Safety & Security Absence & Supervision

Procedure

a) Press button briefly

b) Confirm absence (ok) or wait 8 s

c) Confirm supervision (ok) or wait 8 s

Page 9: Synco living Train the Tainer Functions & Operation  Safety & Security Spring 2008

Page 9/32 Train the Trainer - Spring 2008

Overview Window / Door SupervisionSignalling Faults DisplaysAbsence & Supervision Exercises

Functions & Operation Safety & Security Window / Door Supervision

Supervision delay timeMain menu > Supervision > Supervision delay > {00.00…59.55}

The supervision delay time indicates after what period of time the “Window / door supervision“ function becomes active after “Supervision“ was selected.

During the delay time (countdown), monitored windows and doors can still be opened or closed without delivering a fault status message.

The supervision delay time appears on the central apartment unit‘s display:

SymbolCountdown (resolution 5 s) Tuesday 30.03.200713:47

Absent

Partly monitored

Page 10: Synco living Train the Tainer Functions & Operation  Safety & Security Spring 2008

Page 10/32 Train the Trainer - Spring 2008

Overview Window / Door SupervisionSignalling Faults DisplaysAbsence & Supervision Exercises

Functions & Operation Safety & Security Window / Door Supervision

Supervision delay time

ÜberwachungAktiv

Inaktiv

Verzögerung Ein

Aus

FensterOffen

Zu

Ein

Aus

A B C D E Zeit

Signalton

TüreOffen

Zu

Continuous tone Bleep

Supervision

Delay

Window

Door

Signaling

ActiveInactive

OnOff

OpenClosed

OpenClosed

OnOff

Time

Page 11: Synco living Train the Tainer Functions & Operation  Safety & Security Spring 2008

Page 11/32 Train the Trainer - Spring 2008

Overview Window / Door SupervisionSignalling Faults DisplaysAbsence & Supervision Exercises

Functions & Operation Safety & Security Window / Door Supervision

Volume of supervision delay signalThe volume of the supervision delay signal can be adjusted:Main menu > Supervision > Volume supervision delay > …

Supervision delay uses 3 types of signals:Continuous toneA monitored window is open during the supervision delay timeBleep (frequency 1 Hz)All monitored windows and doors are closedBleep (frequency 2 Hz)During the last 15 s of the supervision delay time

Note:The volume is independent of the buzzer volume and the volume of the delay time signal.

Page 12: Synco living Train the Tainer Functions & Operation  Safety & Security Spring 2008

Page 12/32 Train the Trainer - Spring 2008

Overview Window / Door SupervisionSignalling Faults DisplaysAbsence & Supervision Exercises

Functions & Operation Safety & Security Window / Door Supervision

Supervisory functionsMain menu > Supervision > Windows > …

2 parameters are used to select the rooms for which the window supervision function is enabled:

Partly monitoredAll monitored

All rooms are always listed (12).

Release „Partly monitored“ Living room

Kitchen Nursery

Release „All monitored“ Living room

Kitchen Nursery

Page 13: Synco living Train the Tainer Functions & Operation  Safety & Security Spring 2008

Page 13/32 Train the Trainer - Spring 2008

Overview Window / Door SupervisionSignalling Faults DisplaysAbsence & Supervision Exercises

Functions & Operation Safety & Security Window / Door Supervision

Supervisory functions

Partly monitored:Room C

All monitored:Rooms A, B, C

Page 14: Synco living Train the Tainer Functions & Operation  Safety & Security Spring 2008

Page 14/32 Train the Trainer - Spring 2008

Overview Window / Door SupervisionSignalling Faults DisplaysAbsence & Supervision Exercises

Functions & Operation Safety & Security Window / Door Supervision

Supervisory functionsMain menu > Supervision > Doors > …

2 parameters are used to select the doors for which the door supervisory function is enabled:

Partly monitoredAll monitored

All doors are always listed (2).

Release „Partly monitored“

Release „All monitored“ Entrance door

Garage

Entrance door Garage

Page 15: Synco living Train the Tainer Functions & Operation  Safety & Security Spring 2008

Page 15/32 Train the Trainer - Spring 2008

Overview Window / Door SupervisionSignalling Faults DisplaysAbsence & Supervision Exercises

Functions & Operation Safety & Security Window / Door Supervision

Supervisory functions

Partly monitored:Door A

All monitored:Doors A & B

Page 16: Synco living Train the Tainer Functions & Operation  Safety & Security Spring 2008

Page 16/32 Train the Trainer - Spring 2008

Overview Window / Door SupervisionSignalling Faults DisplaysAbsence & Supervision Exercises

Functions & Operation Safety & Security Window / Door Supervision

Message delay timeMain menu > Supervision > Doors > Message delay > {00.00…59.55}

The message delay time indicates the period of time on completion of which – after the monitored door was opened – a fault status message is delivered.

The fault status message can be suppressed only when supervision is set to “Inactive“ before the message delay time has elapsed , or when a new value is set.

Note:Even if the door is immediately closed again, the central apartment unit delivers a fault status message when the message delay time has elapsed.

Page 17: Synco living Train the Tainer Functions & Operation  Safety & Security Spring 2008

Page 17/32 Train the Trainer - Spring 2008

Overview Window / Door SupervisionSignalling Faults DisplaysAbsence & Supervision Exercises

Functions & Operation Safety & Security Window / Door Supervision

Message delay time

ÜberwachungAktiv

Inaktiv

Meldeverz. Ein

Aus

FensterOffen

Zu

Ein

Aus

A B C D Zeit

Signalton

TüreOffen

ZuAlarm active

Supervision

Delay

Window

Door

Signaling

Active

Inactive

On

Off

Open

Closed

Open

Closed

On

Off

Time

Page 18: Synco living Train the Tainer Functions & Operation  Safety & Security Spring 2008

Page 18/32 Train the Trainer - Spring 2008

Overview Window / Door SupervisionSignalling Faults DisplaysAbsence & Supervision Exercises

Functions & Operation Safety & Security Window / Door Supervision

Volume of message delay signalThe volume of the signal tone for the message delay time can be adjusted:Main menu > Supervision > Doors > Volume message delay > …

Supervision delay uses 2 types of signals:Bleep (frequency 1 Hz)A monitored door was openedBleep (frequency 2 Hz)During the last 15 s of the message delay time

Note:The volume is independent of the buzzer volume and the volume of the delay time signal.

Page 19: Synco living Train the Tainer Functions & Operation  Safety & Security Spring 2008

Page 19/32 Train the Trainer - Spring 2008

Overview Window / Door SupervisionSignalling Faults DisplaysAbsence & Supervision Exercises

Functions & Operation Safety & Security Signalling

BuzzerBased on which events shall the buzzer be triggered:

Main menu > Supervision > Signaling > Event buzzer > … SmokeWindow/door supervisionFault input 1…8

Page 20: Synco living Train the Tainer Functions & Operation  Safety & Security Spring 2008

Page 20/32 Train the Trainer - Spring 2008

Overview Window / Door SupervisionSignalling Faults DisplaysAbsence & Supervision Exercises

Functions & Operation Safety & Security Signaling

Buzzer volumeThe buzzer volume can be adjusted:

Main menu > Settings > Device > Buzzer volume > …

Page 21: Synco living Train the Tainer Functions & Operation  Safety & Security Spring 2008

Page 21/32 Train the Trainer - Spring 2008

Overview Window / Door SupervisionSignalling Faults DisplaysAbsence & Supervision Exercises

Functions & Operation Safety & Security Signaling

Status outputBased on which events shall the status output be activated:

Main menu > Supervision > Signaling > Event status output > …SmokeWindow/door supervisionFault input 1…8

Page 22: Synco living Train the Tainer Functions & Operation  Safety & Security Spring 2008

Page 22/32 Train the Trainer - Spring 2008

Overview Window / Door SupervisionSignalling Faults DisplaysAbsence & Supervision Exercises

Functions & Operation Safety & Security Signaling

Signal durationFor what period of time shall the buzzer and the status output remain activated:

Main menu > Supervision > Signaling > Signal duration > {1…60 min.}

Note:On completion of the signal duration, the buzzer / status output will again be deactivated, even if the triggering event is still pending. As soon as one of the buttons on the central apartment unit is pressed, the buzzer / status output will immediately be deactivated, independent of the adjusted signal duration.

Page 23: Synco living Train the Tainer Functions & Operation  Safety & Security Spring 2008

Page 23/32 Train the Trainer - Spring 2008

Overview Window / Door SupervisionSignalling Faults DisplaysAbsence & Supervision Exercises

Functions & Operation Safety & Security Fault Inputs

Enter the fault text on the central apartment unit: “Oil tank empty“.

Press Esc to quit the menu and then ok to confirm the entry.

Fault textMain menu > Settings > Faults > Fault input x > . . .

Page 24: Synco living Train the Tainer Functions & Operation  Safety & Security Spring 2008

Page 24/32 Train the Trainer - Spring 2008

Overview Window / Door SupervisionSignalling Faults DisplaysAbsence & Supervision Exercises

Functions & Operation Safety & Security Fault Inputs

Fault priorityMain menu > Settings > Faults > Fault input x > Fault priority > . . .

UrgentNot urgent

It can be selected whether or not the fault status message shall immediately appear on the central apartment unit‘s display.

UrgentBoiler fault

Non-urgentOil tank 1/3 full

Page 25: Synco living Train the Tainer Functions & Operation  Safety & Security Spring 2008

Page 25/32 Train the Trainer - Spring 2008

Overview Window / Door SupervisionSignalling Faults DisplaysAbsence & Supervision Exercises

Functions & Operation Safety & Security Fault Inputs

Fault releaseMain menu > Settings > Faults > Fault input x > Fault release >. . .

AlwaysIf absent

It can be selected whether the fault status message shall Always be delivered or only when the central apartment unit is set to If absent.

AlwaysBoiler fault

If absentGarage door open

Page 26: Synco living Train the Tainer Functions & Operation  Safety & Security Spring 2008

Page 26/32 Train the Trainer - Spring 2008

Overview Window / Door SupervisionSignalling Faults DisplaysAbsence & Supervision Exercises

Functions & Operation Safety & Security Fault Inputs

Fault status message delayMain menu > Settings > Faults > Fault input x > Fault stat mess dly > {Time}

What is the delay time allowed for a pending fault to trigger a fault status message?

30 minLevel of aquarium

Note:If the fault status message disappears within the delay time, no fault status message will be delivered.

Page 27: Synco living Train the Tainer Functions & Operation  Safety & Security Spring 2008

Page 27/32 Train the Trainer - Spring 2008

Overview Window / Door SupervisionSignalling Faults DisplaysAbsence & Supervision Exercises

Functions & Operation Safety & Security Fault Inputs

Normal positionMain menu > Settings > Faults > Fault input x > Normal position > . . .

OpenClosed

It can be selected whether an open or a closed contact shall be identified as a fault.

Normal position: Closed

Everything ok

Page 28: Synco living Train the Tainer Functions & Operation  Safety & Security Spring 2008

Page 28/32 Train the Trainer - Spring 2008

Overview Window / Door SupervisionSignalling Faults DisplaysAbsence & Supervision Exercises

Functions & Operation Safety & Security Fault Outputs

Fault priorityMain menu > Settings > Faults > Fault output x > Fault priority > . . .

Urgent Not urgentAll

Priority, when the fault output shall be activated. Refer to the settings under:

Main menu > Settings > Faults > Fault input x > Fault priority > . . .

UrgentBoiler fault

Non-urgentOil tank 1/3 full

All

Page 29: Synco living Train the Tainer Functions & Operation  Safety & Security Spring 2008

Page 29/32 Train the Trainer - Spring 2008

Overview Window / Door SupervisionSignalling Faults DisplaysAbsence & Supervision Exercises

Functions & Operation Safety & Security Fault Outputs

Origin of faultMain menu > Settings > Faults > Fault output x > Fault source > . . .

InternalBus

Defines whether the fault input shall be activated only with internal or also with external faults (via KNX TP1).

Note:Faults of devices connected to the central apartment unit via KNX RF are also considered to be internal faults.

KNX TP1

Page 30: Synco living Train the Tainer Functions & Operation  Safety & Security Spring 2008

Page 30/32 Train the Trainer - Spring 2008

Overview Window / Door SupervisionSignalling Faults DisplaysAbsence & Supervision Exercises

Functions & Operation Safety & Security Display

Symbols appearing on the display of the central apartment unit:

Present

Absent

Fault

Fault (acknowledgement required)

Door open

Monitored door open

Window open

Monitored windows open

Windows / doors “Partly monitored“

Windows / doors “All monitored“

Page 31: Synco living Train the Tainer Functions & Operation  Safety & Security Spring 2008

Page 31/32 Train the Trainer - Spring 2008

Overview Window / Door SupervisionSignalling Faults DisplaysAbsence & Supervision Exercises

Functions & Operation Safety & Security Display

Configured inputs and outputsMain menu > Inputs/outputs > …

InputsOutputs

Inputs Display

0 = present1 = absent0 = no fault1 = fault

Outputs Display

0 = no fault1 = fault0 = contact open1 = contact closed0 = all windows & doors closed1 = min. one window or one door is open

Absence

Fault input

Fault output 1 - 2

Door / window state

Status output

Page 32: Synco living Train the Tainer Functions & Operation  Safety & Security Spring 2008

Page 32/32 Train the Trainer - Spring 2008

Overview Window / Door SupervisionSignalling Faults DisplaysAbsence & Supervision Exercises

Functions & Operation Safety & Security Exercises

1. Activate window supervision for room 1. After a change to “Absent“ and after a delay time of 1 minute, the buzzer and the status output shall be activated for 2 minutes if the window is left open.

2. Activate a door supervision. After opening the door (come home) the buzzer shall be activated after 1 minute, without deactivation of the supervision.

3. After closure of fault input 1, an urgent fault status message “Low oil level“ shall appear on the central apartment unit after 10 s and, in addition, the status output shall be activated.

4. Check an open window/door at the info-page.