Symmetra LXTechnical Training

Page 2: Symmetra LX Range

© 2003 APC corporation.

Agenda

Mechanical DesignSystem ArchitectureTheory of OperationSystem User InterfaceInformation SourcesQuestions and Answers

The target audience of this presentation is expected to have completed Symmetra LX Family Overview and Symmetra LX Configuration trainings.

Technical Training

Page 3: Symmetra LX Range

© 2003 APC corporation.

SystemsTower 230V

8kVA N+1 (5.6kW)•Ships (1) Power Modules, (1) Battery Modules installed, rest ship on pallet

•Up to (2) Battery Modules•50A hard-wire input

•230V L-N-G•400V L-L-L-N-G

•No receptacles

16kVA N+1 4-batts (11.2kW)•Ships (2) Power Modules, (2) Battery Modules installed, rest ship on pallet

•Up to (4) Battery Modules•100A hard-wire input

•230V L-N-G•400V L-L-L-N-G

•No receptacles

16kVA N+1 13-batts (11.2kW)•Ships with (2) Power Modules, (9) Battery Modules installed, rest ship on pallet

•Up to (13 Battery Modules)•100A hard-wire input

•230V L-N-G•400V L-L-L-N-G

•No receptaclesSymmetra LX

Page 4: Symmetra LX Range

© 2003 APC corporation.

SystemsRack-mount 230/480V

8kVA N+1 13U (6.4kW)

•Ships as empty frame w/ modules on pallet•50A hard-wire input

•230V L-N-G•400V L-L-L-N-G

•(6) IEC320C19; (8)IEC320C13

16kVA N+1 19U (12.8kW)

•Ships as empty frame w/ modules on pallet•100A hard-wire input

•230V L-N-G•400V L-L-L-N-G

•(10) IEC320C19; (8)IEC320C13

Symmetra LX

Page 5: Symmetra LX Range

© 2003 APC corporation.

Extended Run Frames

Symmetra LX

Stackable 3 and 9-battery rack-mount XR frames•Available Q4.

•Today use current black SYRMXR4I 4-battery frame.

Stackable 9-battery tower XR frame•18 battery modules in same space as 12 today.

•Available Q4.

•Today use current black Symmetra XR12 12-battery frame.

Battery cabinet extension cables•Enables connection from LX tower to current Symmetra XR12

•SYAOPT3- 208V 4-foot•SYAOPT3I- 230V 4-foot •SYOPT3- 208V 15-foot•SYOPT3I- 230V 15-foot

Page 6: Symmetra LX Range

© 2003 APC corporation.

16kVA XR frame

Mechanical design

5U

N/A

N/A

57.0 inches1446.5 mm

19U

34.2 inches869.0 mm

13U

23.7 inches602.0 mm

13U

23.7 inches 602.0 mm

RM

TWR

XR3 frame

XR9 frame 8kVA frame

16kVA frame

120/208 and 230 VAC

Footprint: 19.0 x 29.1 inches482.5 mm x 738.5 mm

Page 7: Symmetra LX Range

© 2003 APC corporation.

Mechanical design

Rack mount Tower

All systems

Page 8: Symmetra LX Range

© 2003 APC corporation.

Mechanical design

Symmetra

UPS Network Management Card with Environmental MonitoringProvides remote user interface, Manage via Web Browser, SNMP, and Telnet. Includes PowerChute Network Shutdown.

Removable Input/Output Wiring Tray (LX only)Allows easy hard-wiring at install and fast maintenance.

Field-replaceable Power Distribution Panels •Enable quick in-field modification of output receptacles to fit changing needs.

•Tower models ship with no receptacles, rack-mount models ship with receptacles appropriate for different voltage needs.

Extended Run Communication CardAllows Intelligence Modules to monitor the health of external batteries

Extended Run Connector

Allows hot-install of up to seven Extended Run Frames for quick, easy response to changing runtime needs

1:1 & 3:1 option in single product (230V LX only)Same product can be wired for either 3 or 1-phase input. (Rack/Tower 9 and 19 slot frames)

230V 200/208V

Page 9: Symmetra LX Range

© 2003 APC corporation.

Mechanical designAll systems

Rack mount Tower

Page 10: Symmetra LX Range

© 2003 APC corporation.Symmetra LX

All systemsFrame Electronic ModuleField-replaceable, Not Hot-swappable

PowerView DisplayHot-swappable

Flash upgradeable

Power Modules Hot-swappable

Battery ModulesHot-swappable

Intelligence ModulesHot-swappable

only one at a time!

Single Front DoorField-replaceable

Mechanical design

Page 11: Symmetra LX Range

© 2003 APC corporation.

All systems

Power sharing and redundancy N+1

Theory of operation

Page 12: Symmetra LX Range

© 2003 APC corporation.

Mechanical designAll systems

Power Module Battery Module

Intelligence ModuleFrame Electronic Module

Page 13: Symmetra LX Range

© 2003 APC corporation.

Mechanical design

Network Management Card

Symmetra LX communications card

EPO and Enable Switch

External battery connector

All systems

PDU

I/O wiring tray

Page 14: Symmetra LX Range

© 2003 APC corporation.

System architecture230 VAC

Page 15: Symmetra LX Range

© 2003 APC corporation.

Symmetra LX Theory of Operation

Rectifier &PFC +/- DC Bus

BatteryCharger

InverterOutputSection

155 -276VAC Input

120 VDCBattery

240 VACOutput

Power Module Diagram

A/C out (typical)

120/208V or 120/240V 60hz

220/230/240V 50hz

Page 16: Symmetra LX Range

© 2003 APC corporation.

Theory of operation

PFC(Power Factor

Correction)INVERTER

Battery Charger

DC Bus+/-400VDC

Symmetra LX Power Module

AC

MID

AC-OUTAC-1

MID

+BATT

Double conversion on-line UPS

230 VAC

Page 17: Symmetra LX Range

© 2003 APC corporation.

Utility power

PFC(Power Factor

Correction)INVERTER

Battery Charger

DC Bus+/-400VDC

Symmetra LX Power Module

AC

MID

AC-OUTAC-1

MID

+BATT

Theory of operation230 VAC

Page 18: Symmetra LX Range

© 2003 APC corporation.

Battery power

PFC(Power Factor

Correction)INVERTER

Battery Charger

DC Bus+/-400VDC

Symmetra LX Power Module

AC

MID

AC-OUTAC-1

MID

+BATT

Theory of operation230 VAC

Page 19: Symmetra LX Range

© 2003 APC corporation.

Theory of operation: Power module

Phase to Phase Per Phase Phase to Neutral200 208 240 100 120 220 230 240

Part number:Max Output Power (kVA) 3740 3890 4000 1870 2244 4000 4000 4000Max Output Power (Watts) 2800 3200 3200 1400 1600 2800 2800 2800Max Output Current (from Inverters) 18.7 18.7 16.7 18.7 18.7 18.2 17.4 16.7Output Power Factor (Watt/VA) 0.75 0.82 0.80 0.75 0.71 0.70 0.70 0.70Input Power Factor (Watt/VA) 0.90 0.90 0.98 0.90 0.90 0.98/0.90

100/200 and 120/208 VAC models 230 VAC models

SYPM4KISYPM4KP

All systems

Page 20: Symmetra LX Range

© 2003 APC corporation.

Theory of operation: OverloadAll systemsLess than 105%: indefinitely

More than 105%: 4 seconds. Then “Overload” fault is indicated.

Page 21: Symmetra LX Range

© 2003 APC corporation.

Theory of operation: Battery Module:

SYBT5 for 120/208 and 230VAC modelsSYBT5FR for 100/200 VAC model

120VDC: 10 X 12VDC 7.2AH

Maximum 7 extended run (XR) frames

4 Power Modules charge 4 Battery Modules in appx. 3 hours.Each Power Module contains a 300W charger.

All systems

XR3 frame

XR9 frame

Page 22: Symmetra LX Range

© 2003 APC corporation.

Theory of operation: Intelligence module

Diagnostics serial port

LEDs

Cold BootSwitch

UPS_ONBypassNormal operation

Module Fault

This IM in Control

All systems

Page 23: Symmetra LX Range

© 2003 APC corporation.

System user interface

Input circuit breaker Maintenance bypass switch

PowerView display

All systems

Page 24: Symmetra LX Range

© 2003 APC corporation.

System user interface

Network interface card (standard)

SmartSlot Cards

All systems

Simple signalling interface

ENABLE switch

Page 25: Symmetra LX Range

© 2003 APC corporation.

Left-hand barQuick link other

functions

Left-hand barQuick link other

functions

Main Status Screen:Overview of key

functions; UPS and card

Main Status Screen:Overview of key

functions; UPS and card

Browser AccessibleSaves installing software on the network management console.

Browser AccessibleSaves installing software on the network management console.

InfraStruXure Management Design BenefitsNetwork Management Card Screen Shot

InfraStruXure Management Design BenefitsNetwork Management Card Screen Shot

Page 26: Symmetra LX Range

© 2003 APC corporation.

All systems

System user interface

System enable switch

EPO switch connector(dry contact or external 24VDC)

XR battery module

External PowerView display (up to 15 feet / 5 meters away)

Page 27: Symmetra LX Range

© 2003 APC corporation.

DisplayHigh visibility and backlit

Status LightsIndicates current system status, alarms, warnings independent of LCD display

NavigationMenu, status, mode change and set point adjustment

HelpDetailed instruction on operation

EnterSelect current menu item, confirm change

EscapeEasy to return to previous menu item

User Interface Design Benefits

Consistent User InterfaceSame user interface across all APC UPS, cooling, and environmental monitoring products

SecurityPassword protected

Page 28: Symmetra LX Range

© 2003 APC corporation.Symmetra LX

208/120VSYAPD1

- (1) L14-30R, (2) L5-20R

SYPD3- (1) L6-30R, (2) L6-20R

SYPD7- (3) L6-20R

SYPD11- (2) L6-30R

230VSYPD4

- (2) IEC320C19, (8) IEC320C13

SYPD8- (4) IEC320C19

SYPD9- (1) 32A hard-wire connection

SYPD10- (1) IEC309, (2) IEC320C19

Replacement internal back-plates

Retaining Screws

Accessories

Page 29: Symmetra LX Range

© 2003 APC corporation.

Accessories

Symmetra LX

•Wall-mount or rack-mount•Online, test, and bypass modes•Different options for SYLX

•World-wide•SBP16KP- All hardwire connections

•208/120V•SBP16KRMP4U- (6) L14-30R•SBP16KRMP4U-HW

•(1) L14-30R, (3) L5-20R, (1) HW 100A

•230V •SBP16KRMI4U- (3) HW 32A

1Phase Service Bypass Panels

Page 30: Symmetra LX Range

© 2003 APC corporation.

Accessories

Symmetra LX

Power Distribution Units (PDU)

Expansion PDU•Used to enable extra Rack PDU•L14-30P input plug w/ 28 ft cord•Output receptacles:

•120V•AP7580- (4) L5-20R•AP7582- (12) 5-20R•AP7583- (4) L5-30R

•208V•AP7581- (4) L6-20R•AP7584- (4) L6-30R

•230V (require SYPD9)•AP7585- (4) IEC320C19 16A•AP7586- (4) IEC309 32A

Page 31: Symmetra LX Range

© 2003 APC corporation.

Rack PDU: Basic, Metered, Switched

Input SelectorPress to invert displayPress to monitor the next phase

Serial PortProvides local access to the control console

Reset ButtonResets Rack PDU without affecting outlet state

Current MonitorDisplays current draw for the phase indicated

Load Indicator LEDIdentifies overload and warning conditions

Network ConnectionAccess, configure, and manage via Web, SNMP, Telnet, or InfraStruXure Manager

Vertical & Tool less MountZero U mounting

Snap into a NetShelter VX rear channel

Single inputOne branch whip connection

Multi-branch input provides 5.7kW of AC power

Multiple OutletsConnect multiple pieces of equipment

Provides 120V/208V on one strip

Page 32: Symmetra LX Range

© 2003 APC corporation.

Questions

Symmetra LX