syed mohd zulfadhli bin syed adnan

26
ENERGY SAVING THROUGH LED REPLACEMENT FOR STREET LIGHTING SYED MOHD ZULFADHLI BIN SYED ADNAN A project report submitted in partial fulfilment of the requirements for the award of the degree of Master of Engineering (Electrical Power) School of Electrical Engineering Faculty of Engineering Universiti Teknologi Malaysia JANUARY 2020

Upload: others

Post on 08-Jun-2022

9 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: SYED MOHD ZULFADHLI BIN SYED ADNAN

ENERGY SAVING THROUGH LED REPLACEMENT FOR STREET LIGHTING

SYED MOHD ZULFADHLI BIN SYED ADNAN

A project report submitted in partial fulfilment of the

requirements for the award of the degree of

Master of Engineering (Electrical Power)

School of Electrical Engineering

Faculty of Engineering

Universiti Teknologi Malaysia

JANUARY 2020

Page 2: SYED MOHD ZULFADHLI BIN SYED ADNAN

iv

DEDICATION

Special dedication to

My mother, Che Fatimah Binti Che Ismail, my father, Syed Adnan Bin Syed Jaafar

and my wife, Siti Mariyam Binti Sulong

And also to

My supervisor, Dr. Rasyidah Binti Mohamad Idris who guide me and encourage me

throughout this report.

Page 3: SYED MOHD ZULFADHLI BIN SYED ADNAN

v

ACKNOWLEDGEMENT

In preparing this report, I was in contact with many people, researchers,

academicians, and practitioners. They have contributed towards my understanding

and thoughts. In particular, I wish to express my sincere appreciation to my main

report supervisor, Dr. Rasyidah Binti Mohamad Idris, for encouragement, guidance,

critics and friendship. Without her continued support and interest, this thesis would

not have been the same as presented here.

Not forget my both parents and my wife whom always ready to help and

support in morale and financial. I am also indebted to Kaneka Malaysia to give

facility to do research and study until get fruitful result.

My fellow postgraduate student should also be recognised for their support.

My sincere appreciation also extends to all my colleagues and others who have

provided assistance at various occasions. Their views and tips are useful indeed.

Unfortunately, it is not possible to list all of them in this limited space. I am grateful

to all of my family members.

Page 4: SYED MOHD ZULFADHLI BIN SYED ADNAN

vi

ABSTRACT

Kaneka Malaysia Sdn. Bhd totally have 182 units of street lighting which is

53 percent are High Pressure Sodium Vapour (HPSV) lighting. All street lighting

was controlled by timer. This traditional method is out of date and huge of energy

waste mainly due to timer malfunction. Moreover, HPSV street lighting is very

costly to maintain. On February 2019, audit for street lighting was carried out and

result of energy consumption was 317.56kWh per day or 114,321.02kWh per year.

Motivated from this audit, HPSV street lighting was proposed to replace with

highly efficient Light Emitted Diode (LED) street lighting. To realise this project,

the prototype was built by implemented a smart system of LED street lighting

controller to gain reduction of energy consumption and introduction of smart

controlling technique by using Internet of Things (IOT). The prototype is design by

employ Arduino NANO, PIR Motion Sensor, ESP8266 module and Blynk platform

as wireless communication tool. The brightness of the LED street lighting being

controlled depends on the motion detected from 11:00pm until 7:00am. By

implement this idea, energy consumption will be save 50 percent and cut 20 percent

of maintenance cost.

Page 5: SYED MOHD ZULFADHLI BIN SYED ADNAN

vii

ABSTRAK

Kaneka Malaysia Sdn. Bhd. mempunyai 182 lampu jalan secara keseluruhan

di mana 53 peratus adalah pencahayaan Sodium Tekanan Tinggi (HPSV). Semua

lampu jalan dikendalikan oleh pemasa. Kaedah tradisional ini sudah lapuk dan

pembaziran tenaga yang besar kebanyakannya disebabkan oleh kerosakan pemasa.

Selain itu, lampu jalan jenis HPSV sangat mahal kos penyelenggaraan. Pada Februari

2019, audit untuk lampu jalan telah dijalankan dan hasil penggunaan tenaga adalah

317.56kWh sehari atau 114,321.02kWh setahun. Bermotivasi daripada audit ini,

pencahayaan lampu HPSV dicadangkan untuk digantikan dengan pencahayaan Diod

Pemancar Cahaya (LED) yang kecekapan tinggi. Untuk merealisasikan projek ini,

sebuah prototaip telah dibina dengan mengimplementasikan pengawalan pintar

lampu jalan LED untuk memperolehi pengurangan penggunaan tenaga dan

pengenalan kepada teknik pengawalan pintar Internet of Things (IOT). Prototaip ini

direka bentuk dengan Arduino NANO, Sensor Pergerakan PIR, Modul ESP8266 and

pelantar Blynk sebagai alat komunikasi tanpa wayar. Kecerahan lampu jalan LED

dikendalikan bergantung kepada gerakan yang dikesan daripada jam 11:00pm

sehingga 7:00am. Dengan melaksanakan idea ini, penggunaan tenaga akan

menjimatkan 50 peratus dan mengurangkan 20 peratus kos penyelenggaraan.

Page 6: SYED MOHD ZULFADHLI BIN SYED ADNAN

viii

TABLE OF CONTENTS

TITLE PAGE

DECLARATION iii

DEDICATION iv

ACKNOWLEDGEMENT v

ABSTRACT vi

ABSTRAK vii

TABLE OF CONTENTS viii

LIST OF TABLES xi

LIST OF FIGURES xii

LIST OF ABBREVIATIONS xiv

LIST OF APPENDICES xv

CHAPTER 1 INTRODUCTION 1

1.1 Company Background 1

1.2 Energy Saving and Energy Efficient in Kaneka

Malaysia 2

1.3 Street Lighting Background in Kaneka Malaysia Sdn.

Bhd. 2

1.4 Problem Statement 4

1.5 Motivation 6

1.6 Research Objectives 6

1.7 Scopes of Project 7

1.8 Methodology 7

1.9 Thesis Outline 8

CHAPTER 2 LITERATURE REVIEW 11

2.1 Introduction 11

2.2 HPSV and LED Street Lighting 12

2.3 Benefits of LED Street Lighting 14

2.3.1 Energy Saving 14

Page 7: SYED MOHD ZULFADHLI BIN SYED ADNAN

ix

2.3.2 Lighting Pollution 15

2.3.3 Color Comfortability 16

2.3.4 Safety 17

2.3.5 Maintenance Cost 18

2.4 Energy Saving and Smart Street Lighting 18

2.4.1 LED 18

2.4.2 Controlled Sensors 19

2.4.3 Arduino NANO microcontroller 19

2.5 Previous Works 20

CHAPTER 3 RESEARCH METHODOLOGY 27

3.1 Introduction 27

3.2 Data Collection 28

3.3 Smart LED Design 29

3.4 Data collection for hardware 34

3.5 Economic Calculation 34

3.6 Measurement Equipment 36

CHAPTER 4 PROPOSED WORK 39

4.1 Introduction 39

4.2 Energy Survey 39

4.2.1 Discussion of Energy Survey 42

4.3 Maintenance and Reliability Analysis 43

4.4 Street Lighting Audit 44

4.5 Electricity Consumption Audit 45

4.6 Economic Analysis 47

4.6.1 Existing Electricity Consumption 47

4.6.2 After installation of LED (Expectation

Calculation) 48

4.6.3 Initial Investment Cost 49

4.6.4 Simple Payback Period and Return of

Investment 49

4.6.5 Discussion of Economic Analysis 50

4.7 Hardware Analysis 51

Page 8: SYED MOHD ZULFADHLI BIN SYED ADNAN

x

4.7.1 Conventional Bulb 51

4.7.2 LED Lighting 53

4.7.3 Cost Saving Analysis 54

4.7.3.1 Conventional Bulb with and without

Motion Sensor 54

4.7.3.2 LED with and without Motion

Sensor 55

4.7.3.3 LED vs Conventional Bulb without

Motion Sensor 55

4.7.3.4 LED vs Conventional Bulb with

Motion Sensor 56

CHAPTER 5 CONCLUSION AND RECOMMENDATIONS 57

REFERENCES 59

APPENDICES A-E 63-69

Page 9: SYED MOHD ZULFADHLI BIN SYED ADNAN

xi

LIST OF TABLES

TABLE NO. TITLE PAGE

Table 1.1 List of lighting and quantity in KM premise. 3

Table 1.2 Methodology and techniques that apply for this project. 8

Table 3.1 List of feeder pillar and distribution board for KM’s

street lighting. 28

Table 3.2 Data collection sample for hardware. 34

Table 4.1 Energy survey result. 42

Table 4.2 List of HPSV street lighting breakdown. 43

Table 4.3 Number of unit street lighting bulb in Kaneka Malaysia. 45

Table 4.4 Electricity consumption in KM. 46

Table 4.5 Subtraction method for SPP calculation. 50

Table 4.6 Data collection sample for conventional bulb. 52

Table 4.7 Total Energy consumption of conventional bulb (with

motion sensor). 52

Table 4.8 Total Energy consumption conventional bulb (without

motion sensor). 53

Table 4.9 Data collection sample for LED Lighting. 53

Table 4.10 Total Energy consumption of LED lighting (with motion

sensor). 54

Table 4.11 Total Energy consumption of LED lighting (without

motion sensor). 54

Table 4.12 Total saving of Conventional bulb compare to

conventional bulb. 55

Table 4.13 Total saving of LED lighting with and without motion

sensor. 55

Table 4.14 Total saving of LED lighting compare to conventional

bulb without equipped with motion sensor. 55

Table 4.15 Total saving of LED lighting compare to conventional

bulb with motion sensor. 56

Page 10: SYED MOHD ZULFADHLI BIN SYED ADNAN

xii

LIST OF FIGURES

FIGURE NO. TITLE PAGE

Figure 1.1 Type of street lighting’s bulb in KM. 3

Figure 1.2 Street lighting condition 5

Figure 2.1 Surgical lighting goggle composed of white LED arrays

introduced by Yoichi Kawakami, Junichi Shimada and

Shigeo Fujita. 11

Figure 2.2 Lighting samples. 13

Figure 2.3 Lighting pollution effect from street lighting. 15

Figure 2.4 Kruithof curve. 16

Figure 2.5 Overall block diagram. 22

Figure 2.6 Detail block diagram. 22

Figure 2.7 Overall framework of the system. 23

Figure 2.8 LabView interface diagram. 24

Figure 2.9 LED lighting control system. 25

Figure 2.10 Dimming controller of LED street lighting. 25

Figure 2.11 7 days’ graph of energy saving. 26

Figure 3.1 Flow chart diagram. 27

Figure 3.2 Block diagram of the smart LED street lighting. 29

Figure 3.3 Flowchart of the Smart Street Lighting controller. 31

Figure 3.4 Blynk interface inside mobile phone. 32

Figure 3.5 Blynk code integrated with Arduino code program. 33

Figure 3.5 Clamp meter Kyoritsu AC Digital Clamp Meter KEW

2117R. 36

Figure 3.5 Multimeter Fluke 101 Basic Multimeter 37

Figure 3.5 Data Logger DEHN ElitePro XC Power Meter 37

Figure 4.1 Sample of energy survey Questionnaire. 40

Figure 4.2 Demography of gender 41

Figure 4.3 Demography of designation. 41

Page 11: SYED MOHD ZULFADHLI BIN SYED ADNAN

xiii

Figure 4.4 Demography of department 41

Figure 4.5 Pareto Chart of HPSV lamps. 44

Figure 4.6 Electricity trend in IMODA plant. 46

Figure 4.7 Saving year after 7.9 years. 51

Page 12: SYED MOHD ZULFADHLI BIN SYED ADNAN

xiv

LIST OF ABBREVIATIONS

KM - Kaneka Malaysia Sdn. Bhd.

KPP - Kaneka Paste Polymer Sdn. Bhd.

LED - Light Emitted Diode

HPSV - High Pressure Sodium Vapour

KET - Kaneka Electec Sdn. Bhd.

TV - Television

LCD - Liquid Crystal Display

KIF - Kaneka Innovative Fibers

KAM - Kaneka Apical Malaysia Sdn. Bhd.

IMODA - Kaneka Imoda Sdn. Bhd.

SGA - Small Group Activity.

REEM - Registered Electrical Energy Manager

MH - Metal Halide

CO2 - Carbon Dioxide

GSM - Global System for Mobile Communication

DB - Distribution Board

JSA - Job Safety Analysis

SHEQ - Safety, Health, Environment and Quality

SCM - Supply Chain Management

SHEQ - Safety, Health, Environment and Quality

PTW - Permit to Work

EIP - Electrical Isolation Permit

SS - Senior Superintendent

OSHA - Occupational Safety and Health Administration

Page 13: SYED MOHD ZULFADHLI BIN SYED ADNAN

xv

LIST OF APPENDICES

APPENDIX TITLE PAGE

Appendix A Project 1 – Gantt Chart 63

Appendix B Project 2 – Gantt Chart 65

Appendix C Questionnaire result by Person 66

Appendix D Parts List 67

Appendix E Full Schematic 69

Page 14: SYED MOHD ZULFADHLI BIN SYED ADNAN

1

CHAPTER 1

INTRODUCTION

1.1 Company Background

Kaneka Malaysia Sdn. Bhd. (KM) is Japanese based company which is

starting to corporate and established in Malaysia on August 1995. KM was located at

Gebeng Industrial Estate. The first plant that had been built in KM premise is Kaneka

Electec Sdn. Bhd. (KET) on September 1995. KET started to operate from 1996 but

ceased its operation on 2008 due to downtrend consumption of color TVs and

monitors and increasing LED and LCD TV trend on last decade. Along with KET,

Kaneka Modifiers Sdn Bhd (MOD) was established and started to operate almost at

same month with KET. MOD was produced a quality product of impact modifier

which is had trade name Kane Ace. Kane Ace is main raw materials in many

applications such as high impact pipes and fittings, PVC door, window frame and so

on. Due to its transparent properties, Kane Ace is also used in packaging of tablets

and blister packages for stationery, toys and general merchandise. Until 2010, KM

were established three plants and company in Malaysia. Kaneka Eperan Sdn Bhd

(KEP) and Kaneka Paste Polymers Sdn. Bhd (KPP) was started its operation on July

1996 and January 1999. Meanwhile, Kaneka Innovative Fibers Sdn Bhd (KIF) was

produced first products on September 2010. KM does not turn back and moving

forward by established another four plants and companies for 2010 year. Kaneka

Apical Malaysia Sdn. Bhd. (KAM) and Kaneka MS Malaysia Sdn. Bhd were started

its operation on February 2012 and May 2015. KAM plants consist of two companies

and premises which are known as KAM-GS and KAM-PI. Kaneka Imoda Sdn. Bhd.

(i-MODA) was latest and also the largest factory in KM which is started its

production on July 2017.

Page 15: SYED MOHD ZULFADHLI BIN SYED ADNAN

2

1.2 Energy Saving and Energy Efficient in Kaneka Malaysia

KM is company that support and encourage staffs to initiate the energy

saving and energy efficient practising. It was proved by hired external consultant and

registered electrical energy manager (REEM), Ir. Hj. Abdul Aziz to assists and

develop baseline energy saving and energy efficient strategy starting from 2014.

Since Ir. Hj. Abdul Aziz become an external REEM and consultant, KM was

complied with Energy Supply Act, Efficient Management of Electrical Energy

Regulations 2008 [1]. Ir. Hj. Abdul Aziz initiate to create Kaneka Malaysia energy

team which participated almost of plant representatives and administration personnel.

Energy Management’s vision and mission was idealized by give the pressing to

reduce energy consumption by five percent in 5 years. Therefore, management

directors of KM were encouraged each plant in KM to develop their Small Group

Activity (SGA) to drive an energy saving and energy efficient project.

1.3 Street Lighting Background in Kaneka Malaysia Sdn. Bhd.

In beginning of KM establishment in 1996, KM only had 83 street lightings

surrounding plants and factory. However, due to establishment another four plants

and factories in KM in 2010, street lightings drastically increased to 182 street

lighting. In parallel, electricity consumption also increases drastically. Before 2010-

year, street lighting electricity cost average about RM800.00 to RM 1,000.00 per

month. However, after year 2010 and recent, KM need to bear the electricity cost of

street lighting average about RM2,750.00 per month or average RM 33,000.00 per

year.

Street lighting in KM have many fixtures with difference model. Most of

street lighting’s luminaires are High Pressure Sodium Vapor (HPSV), LED and

Metal Halide (MH). Below Table 1.1 and Figure 1.1 are list of street lighting bulbs in

KM plants.

Page 16: SYED MOHD ZULFADHLI BIN SYED ADNAN

3

Table 1.1 List of lighting and quantity in KM premise.

Nos Lighting Quantity

1 High Pressure Sodium Vapour 96

2 Metal Halide 4

3 LED 83

Total 182

Figure 1.1 Type of street lighting’s bulb in KM.

Purpose of outdoor lighting such as street lighting in premise compound is to

enhance vision of operator and increases the security of property during night. In

term of purpose, it slightly different between highway street lighting and premise

street lighting. Most of street lighting in KM are used to illuminate roadways,

parking lots, yards, sidewalks, plant site and building exteriors.

In KM, most of area have lighting levels that are greater than the OSHA

minimums. Very good lighting increases the visibility of hazards, improves the

safety of operator and provides a sense of security in the plant communities. The

Occupational Safety and Health Administration (OSHA) Regulation 1926.56(a)

stated that any construction areas, ramps, runways, corridors, offices, shops, and

storage areas shall be lighted, with minimum footcandle levels ranging from 3 to 30

in various areas [2].

HPSV

53% LED

45%

Metal Halide

2%

Type of Street Lighting in Kaneka Malaysia

Page 17: SYED MOHD ZULFADHLI BIN SYED ADNAN

4

1.4 Problem Statement

On February 2019, energy audit for street lighting in Kaneka Malaysia was

carried out. As a result, electricity consumption of street lighting is 317.56kWh per

day or 114,321.02kWh per year. HPSV’s bulb street lighting contributed a huge

electricity consumption than LED street lighting and was observed very significant

effect to electricity cost.

Every month, management of KM spends average RM500.00 per month and

average RM6,000.00 per year in repair and maintenance (R&M) cost. Budget also

increased since 2010 about 20%. Most of budget directed to HPSV street lighting in

purchase of spare ballast, capacitor, ignitor and bulb.

LED lights are over 60% more cost effective in terms of maintenance. Due to

LED’s substantially longer life span, High Pressure Sodium Vapour (HPSV) and

Mercury Vapour (MV) lamps would have to be replaced at least three to four times

during the lifespan of an LED. Lifetime of HPSV lamp is around 5,000 hours while

the LED lamp has lifetime over than 50,000 hours. In other hand, LED has lifetime

10 greater than HPSV lamps [3].

Weakness of conventional streetlight, such as uneven of light was identified.

Yellow and amber colour of HPSV attains uncomfortable to lorry driver and operator

as well as premise guard during night shift supervise. Compare with the white colour

LED lamps, the vision was better, and light also become more even and sharp. The

good feature of LED lamp is dimmable which can reduce it brightness using external

controller.

Street lighting always turn on automatically at 7:00pm and turn off at 7:00am

by conventional timer controller. Some location in KM, timer always malfunction

and out of the setting. Because of that, street lighting will be remaining switch on

until 9:00am to 10:00am or switch on too early at 6:40pm in evening. This routine

caused waste of energy and increasing of electricity cost by 5% per day. Energy

wasting also cause a more hundred-ringgit spending by KM management for only

Page 18: SYED MOHD ZULFADHLI BIN SYED ADNAN

5

street lightings. Figure 1.2 below shown the reality of electricity waste in one of

plant in KM. This scenario of energy waste cannot be accepted by management of

KM and raise my concern to introduce a reliable system to replace this existing

controller.

Figure 1.2 Street lighting condition

Another reason premise is implementing green technologies such as LED

lighting is to reduce light pollution and carbon dioxide (CO2) emission. Many of the

conventional lighting fixtures are not directing light properly, creating over

expanding areas, and emitting light pollution into the atmosphere. Some of the

problems related with light pollution are the disruption of the ecosystem, adverse and

poor health effects created by carbon dioxide emissions, the obstruction of the night

sky for astronomical studies, and the disturbance of neighbouring regions created by

light trespass. LED lamps has lower annual greenhouse gas emission rather than

HPSV lamp for example 250 watt lamp, the annual greenhouse gas emission is

around 850kg while LED light only 355kg. This mean that LED has lower emission

by percentage to 40% from HPSV lamp.

From observation in Kaneka Malaysia premise, street lighting has significant

effect on the mood of animal life. For example, many insects are attracting to the

light of street lighting even it is HPSV, Mercury Vapour or LED. The problem is

when insects attract to the Mercury Vapour lamp, it effects 100% of animal life due

Page 19: SYED MOHD ZULFADHLI BIN SYED ADNAN

6

to chemical reaction and 47% for HPSV lamp. However, LED lamp only give lower

impact between all light sources which is about 20% [4]. Due to that problem,

maintenance cost to cleaning up the fixture especially Mercury Vapour lamp

significantly higher than other lamps.

1.5 Motivation

Motivation of this project is to comply Industrial 4.0’s vision of Kaneka

Malaysia. By implement smart street lighting, we able to control the lit of street.

More advance, we can switch on and off street lighting by access it through tablet or

smart phone from remote location.

1.6 Research Objectives

The main objective is to evaluate and measure electricity consumption of

existing street lighting in Kaneka Malaysia Sdn. Bhd. As per discuss in Introduction

section, all 182 units of street lighting will be evaluating, measure and analyse.

Energy audit will be carrying on realizing this objective.

Second objective to investigate the possibility of energy saving through

replacement of conventional luminaire of street lighting with LED luminaire. LED

street lighting will determine to be save about 30 percent of recent energy

consumption in Kaneka Malaysia Sdn. Bhd. By reducing to 30 percent, we will

achieve Kaneka Energy Management’s objective which is targeted to reduce 5% total

consumption within 5 years. To achieve this objective, economic analysis such as

Return of Investment (ROI) and Simple Payback Period (SPP) will be carry on.

Besides, energy survey also conducted for 55 respondents, mainly focus on operators

and maintenance personnel.

Page 20: SYED MOHD ZULFADHLI BIN SYED ADNAN

7

Third objective is to analyse energy saving through LED Smart Street

lighting hardware. Conventional controller targeted to be eliminated through

introduction of smart street lighting control.

1.7 Scopes of Project

This feasibility study is limited in Kaneka Malaysia premises which consists

of 182 units of street lighting. Overall studies are consisting of electricity

consumption, maintenance cost, energy survey about street lighting and economic

analysis (return of investment and simple payback period).

The circuit of prototype hardware will be suit for 5V, 5A after regulated by

XL4015-5A module from 12V, 5A power supply. PIR motion sensor used as

intelligent control and Arduino NANO is utilizing as microcontroller. For wireless

control, ESP8266 was chosen as WIFI module. This hardware will be

communication and control by using Blynk apps from android smart phone.

1.8 Methodology

To obtain a good result in the end of this project, feasibility study was

conducted. Items number 1, number 2 and number 3 were covered for feasibility

study phase meanwhile item number 4 for prototype or hardware implementation.

Table 1.2 below is the lists of methods and techniques.

Page 21: SYED MOHD ZULFADHLI BIN SYED ADNAN

8

Table 1.2 Methodology and techniques that apply for this project.

Nos Methodology Techniques

1 Audit and survey 1. Counting units of street lighting in

Kaneka Malaysia.

2. Carry out energy survey.

2 Measurement of parameter 1. Use clamp meter to measure

current.

2. Use data logger to take current,

voltage, power and harmonic

reading.

3 Mathematical calculation and

analysis.

1. Statistical technique such SPP and

ROI.

2. Cost comparison technique.

3. Economical technique.

4 Design prototype for smart street

lighting.

1. Electronic wiring technique.

2. Arduino NANO programming.

1.9 Thesis Outline

This thesis is divided into five chapters. Chapter 1 is introduction which are

describe history background of Kaneka Malaysia Sdn. Bhd. and background of street

lighting in this premise. In this chapter, problem statements, motivations, objectives

and methodology were summarized and stated.

Chapter 1: Introduction was followed with Chapter 2: Literature Review

which describes previous works by other researchers that gives motivation to carry

out this project and work. Chapter 2 also presents the approach taken and

mathematical tools used in their analysis.

Chapter 3 is describing about methodology that will used in this project. Data

was collected and analysis for before and after. Also, survey for specific respondents

in Kaneka Malaysia is carry on in order to get the solid reason and justification of

problem statement that describe in Chapter 1. Smart street lighting prototype will be

describing and elaborate in this chapter.

Page 22: SYED MOHD ZULFADHLI BIN SYED ADNAN

9

For chapter 4 is presentation the experimental results that close related with

the chapter 3. In Chapter 3, method is present but for chapter 4, result and discussion

will be detailed.

Chapter 5 is last chapter in this thesis which is conclusion overall of project.

Also, in this chapter is presentation of the recommendation and point out next

opportunities and potentials to improve the recent project.

Page 23: SYED MOHD ZULFADHLI BIN SYED ADNAN

59

REFERENCES

[1] Efficient Management of Electrical Energy Regulations 2008. Part III:

Registered Electrical Energy Manager, paragraph 11(1), Electricity Supply

Act 1990, 2018 Edition, pg 12.

[2] Occupational Safety & Health Administration Regulation Standard 1926.56

Illumination,https://www.osha.gov/pls/oshaweb/owadisp.show_document?p

table=STANDARDS&p_id=10630

[3] Mahmoud I. Masoud, “Street lighting using solar powered LED light

technology Sultan Qaboos University Case Study”, Proceedings of the 8th

IEEE GCC Conference and Exhibition, Muscat, Oman, 1-4 February, 2015.

[4] “Advantages of using energy efficient lighting for society and environment”,

http://www.grahlighting.eu/en/learning-centre/studies.

[5] Shimada J., Kawakami Y., and Fujita S. “Medical lighting composed of LEDs

arrays for surgical operation” SPIE Photonics West: Light Emitting Diodes:

Research, Manufacturing, and Applications, 4278, 165, San Jose, January 24–

25 (2001)

[6] Shimada J., Kawakami Y., and Fujita S. “Development of lighting goggle

with power white LED modules” SPIE Photonics West: Light Emitting

Diodes: Research, Manufacturing, and Applications, 4996, 174, San Jose,

January 28–29 (2003) Stringfellow G. B. and Craford M. G. (Editors) High

Brightness Light-Emitting Diodes Semiconductors.

[7] J. Shimada, Y. Kawakami and Sg. Fujita, “Medical lighting composed of

LEDs arrays for surgical operation”, Proceedings of SPIE Vol. 4278, pp. 165-

172, 2001.

[8] R. Bourne, "The beginnings of electric street lighting in the City of London",

Engineering Science and Education Journal, IET Journals & Magazines, pg

81 - 88.

[9] Electrical Engineering Hall of Fame: “Charles F. Brush", Proceedings of the

IEEE, IEEE Journals & Magazines pg 1955 - 1957.

Page 24: SYED MOHD ZULFADHLI BIN SYED ADNAN

60

[10] J.M. Anderson, "First electric street lamps", IEEE Power Engineering

Review, IEEE Journals & Magazines, pg 39 - 40.

[11] A.M.E. Pereira , V.A. Teixeira, M.Z. Fortes ,A.P. Fragoso , G.M. Tavares,

"Some considerations about LED technology in public lighting",2015

CHILEAN Conference on Electrical, Electronics Engineering, Information

and Communication Technologies (CHILECON), pg 561-565

[12] Vitor C. Bender, Fernanda B. Mendes, Tiago Maggi, Marco A. Dalla Costa

and Tiago B. Marchesan, "Design Methodology for Street Lighting

Luminaires based on a Photometrical Analysis" 2013 Brazilian Power

Electronics Conference, 27-31 Oct. 2013, IEEE, pg 1160-1165.

[13] Fusheng Li, Dahua Chen, Xianjie Song and Yuming Chen, "Analysis of

Energy Savings from Replacing HPSV Lighting with LED Lighting in Road

LightingApplication", 2009 Asia-Pacific Power and Energy Engineering

Conference, 2009, pg1-3.

[14] Addendum No. 1 Revision 1 to L-S20: Specification for Road Lighting

Installation (August 1999), Section A2.0: Road Lighting Luminaires – LED.

retrived February,21,2018 from https://jmal.jkr.gov.

[15] Su-Chin Huang Li-Ling Lee Ming-Shan Jeng, and Yao-Ching Hsieh,

"Assesment of Energy Efficient Led Street Lighting Through Large Scale

Demostration" Industrial Technology Research Institute and National Dong Hwa

University.

[16] Tu Menglong,"The discussion of LED outdoor display's light pollution and

technical solution", 2014 11th China International Forum on Solid State

Lighting (SSLCHINA), 18 June 2015,pg 63-70.

[17] Muhammad M. A. S. Mahmoud, "Typical economic model for calculating the

saving norm of replacement HPS street lighting by LED fixtures in access

road of gas production company at GCC", 2018 5th International Conference

on Electrical and Electronic Engineering (ICEEE), pg 189 - 192.

[18] Steve Fotios School of Architecture, University of Sheffield, Sheffield, UK,

"A Revised Kruithof Graph Based on Empirical Data", The journal of the

Illuminating Engineering Society of North America, LEUKOS, chapter 13 pg

3–17, 2017.

Page 25: SYED MOHD ZULFADHLI BIN SYED ADNAN

61

[19] Ian Ashdown, P. Eng., FIES, Chief Scientist, Lighting Analysts Inc.The

Kruithof Curve: A Pleasing Solution,

https://www.researchgate.net/publication/273763550, 2015/01/12, pg 1-11

[20] Kruithof, A. A. Tubular luminescence lamps for general illumination. Philips

Tech. Rev. 6(3): pg 65-73, 1941.

[21] Asiri Jayawardena, David Duffy , Joseph Manahan,"Impact Of Light on

Safety in Industrial Environments", 2015 IEEE Petroleum and Chemical

Industry Committee Conference (PCIC), pg 1-9.

[22] Devon Jenkins, Anshuman Bhargava, "Selecting the proper LED light fixture

to enhance safety in harsh & hazardous environments", 2014 IEEE

Industry Application Society Annual Meeting, pg 1-4.

[23] Dev V. Savla , Heet R. Savla , Krishna B. Kansara, Brainy streets an

automatic lighting system, 2018 2nd International Conference on Inventive

Systems and Control (ICISC), pg 16-21.

[24] M. Abdul Kader Riyaz , S. ArunJeyakumar , M. Abdul Hameed Sharik , A.

Tamilarasi, Graphene coated LED based automatic street lighting system

using Arduino microcontroller, 2017 IEEE International Conference on

Power, Control, Signals and Instrumentation Engineering (ICPCSI), pg 1555

-1560.

[25] Kao Chen, Lighting Esthetics with Energy Saving Ideas,IEEE Transactions

on Industry Applications,IEEE Journals & Magazines,Year: 1976 , Volume:

IA-12 , Issue: 1, Pg 35 – 38.

[26] P. Van Tichelen, D. Weyen, R. Geens, J. Lodeweyckx, G. Heremans, A novel

dimmable electronic ballast for street lighting with HPS lamps, Conference

Record of the 2000 IEEE Industry Applications Conference. Thirty-Fifth IAS

Annual Meeting and World Conference on Industrial Applications of

Electrical Energy (Cat. No.00CH37129), 8-12 Oct. 2000.

[27] Francis Rubinstein, Michael Siminovitch, and Rudolph Verderber, Fifty

Percent Energy Savings with Automatic Lighting Controls, IEEE

Transactions on Industry Applications, Vol. 29, No. 4, July/August 1993, pg

767-773.

Page 26: SYED MOHD ZULFADHLI BIN SYED ADNAN

62

[28] S.K. Biswas ; R.P. Dhanuka, Reliability of electronic ballasts in industrial

fluorescent lighting applications, Conference Record of the 1992 IEEE

Industry Applications Society Annual Meeting, 4-9 Oct. 1992, pg 1915-1919.

[29] Siddha Pimputkar, James S. Speck, Steven P. Den Baars and Shuji

Nakamura, Prospects for LED lighting, Nature Photonics, Vol. 3, Apr 2009,

2009 Macmillan Publishers Limited, pg 180-182,

www.nature.com/naturephotonics.

[30] Matthias Wendt, Jan-willem Andriesse, LEDs in Real Lighting Applications:

from Niche Markets to General Lighting, Conference Record of the 2006

IEEE Industry Applications Conference Forty-First IAS Annual Meeting, pg

2601 - 2603.

[31] Po-Yen Chen, Yi-Hua Liu, Yeu-Torng Yau, Hung-Chun Lee, Development of

an energy efficient street light driving system, 2008 IEEE International

Conference on Sustainable Energy Technologies, 24-27 Nov. 2008, pg 761 –

764.

[32] Mukul Joshi, Rajashri Madri, Shruti Sonawane, Abhinav Gunjal, Dr.

D.N.Sonawane, "Time Based Intensity Control for Energy Optimization Used

for Street Lighting", College of Engineering, Pune, 2013 Texas Instruments

India Educators' Conference, pg 211-215.

[33] Hao Deng, Xiaogao Xie, Wei Zhong Ma, Yang Han, "A LED Street Lamp

Monitoring System Based on Bluetooth Wireless Network and LabVIEW",

Hangzhou Dianzi University, 2016 2nd

IEEE International Conference on

Computer and Communications, pg 2286 - 2291.

[34] Chun-ling Fan and Yuan Guo, "The application of a ZigBee based wireless

sensor network in the LED street lamp control system"

[35] Somchai Biansoongnern, Boonyang Plangklan,"Efficiency Improvement Of

Energy Management For Led Street Lightings",5th International Electrical

Engineering Congress Pattaya, Thailand On 8th Until 10 March 2017.

[36] Tenaga Nasional Berhad. (2014). Tariff Rates. Available:

http://www.tnb.com.my