Automation and Drives
SIMATIC S7Software Redundancy
-
8/14/2019 Swred e Cern
2/15
Automation and Drives
A D AS SM6 R.Fischer 2IMATIC Software Redundancy
SIMATICSW Redundancy
SW RedundancyPrinciple
Steam Production
Boiler 1 Mixer Boiler 2 Dryer
REDUNDANCY Area
PrinciplePositioningApplication FieldsConfigurationFeaturesOrder number and deliveryform
-
8/14/2019 Swred e Cern
3/15
Automation and Drives
A D AS SM6 R.Fischer 3IMATIC Software Redundancy
SIMATICSW Redundancy
SW RedundancyPositioningLow Cost / Low Performance Redundancy solution based on standard componentsUniversal solution for all CPU
from CPU 315-2DP until CPU 417-4Marketing parallel to S7-400H
PrinciplePositioningApplication FieldsConfigurationFeaturesOrder number and deliveryform
-
8/14/2019 Swred e Cern
4/15
Automation and Drives
A D AS SM6 R.Fischer 4IMATIC Software Redundancy
SIMATICSW Redundancy
SWRedundancyApplication FieldsApplication for processes that tolerate a Master-Slave switchover time of about a secondExamples:
Water treatment Control of cooling systems Control and monitoring of
temperature levels
Traffic control Measuring registration
PrinciplePositioningApplication FieldsConfigurationFeaturesOrder number and deliveryform
-
8/14/2019 Swred e Cern
5/15
Automation and Drives
A D AS SM6 R.Fischer 5IMATIC Software Redundancy
SIMATICSW Redundancy
SW Redundancy with S7-400Configuration
Redundant AreaNon redundant
MPI/ Profibus/ Ethernet
Redundancy Connection
Master
controller
Back up
controller
Non redundant
AreaArea
ET 200M with
IM 153-2
Active Bus Backup Bus
PrinciplePositioningApplication FieldsConfigurationFeaturesOrder number and deliveryform
-
8/14/2019 Swred e Cern
6/15
Automation and Drives
A D AS SM6 R.Fischer 6IMATIC Software Redundancy
SIMATICSW Redundancy
Profibus DP Redundancywith Standard IM 153-2
IM
IM
Bus module (BM)
Active
Bus module
Profibus DP
ET 200M
with active Bus modules
L+
L+
Redundant IM 153-2PrinciplePositioningApplication FieldsConfigurationFeaturesOrder number and deliveryform
Available as individual componentsIM: 6ES7 153-2AA02-0XB0BM: 6ES7 195-7HD00-0XA0
or as Bundle (2 x IM + 1 BM)6ES7 153-2AR00-0XA0
-
8/14/2019 Swred e Cern
7/15
Automation and Drives
A D AS SM6 R.Fischer 7IMATIC Software Redundancy
SIMATICSW Redundancy
SW RedundancyFunction
Master
Reception of status information
from reserve controller
Non redundant user program
processing
Redundant user program
processing
Transmission of redundant data to
reserve controller
Writing of non redundant and
redundant outputs
Reserve
Reception of information from
master controller
Reading of Inputs
Writing of non redundant
outputs
Non redundant user program
processing
Transmission of information to
the master controller
Reading of Inputs
PrinciplePositioningApplication FieldsConfigurationFeaturesOrder number and deliveryform
A d D
-
8/14/2019 Swred e Cern
8/15
Automation and Drives
A D AS SM6 R.Fischer 8IMATIC Software Redundancy
SIMATICSW Redundancy
SW Redundancy with S7-400
Redundant area
MPI/ PROFIBUS/ Ethernet
Redundancy Connection
Master
controller
Back up
controller
PrinciplePositioningApplication FieldsConfigurationFeaturesOrder number and deliveryform
A i d D i
-
8/14/2019 Swred e Cern
9/15
Automation and Drives
A D AS SM6 R.Fischer 11IMATIC Software Redundancy
SIMATICSW Redundancy
SW Redundancy with S7-400 and WinCC
Redundanzbereich
PROFIBUS/MPI/Ethernet
Master
controller
Back up
controller
Non
redundant
area
WinCC Redundancy script
Redundant area
PrinciplePositioningApplication FieldsConfigurationFeaturesOrder number and deliveryform
A t ti d D i
-
8/14/2019 Swred e Cern
10/15
Automation and Drives
A D AS SM6 R.Fischer 13IMATIC Software Redundancy
SIMATICSW Redundancy
SW Redundancywith single PROFIBUS
MPI/PROFIBUS/ Ethernet
Master
controller
Back up
controller
PrinciplePositioningApplication FieldsConfigurationFeaturesOrder number and deliveryform
Automation and Dri es
-
8/14/2019 Swred e Cern
11/15
Automation and Drives
A D AS SM6 R.Fischer 14IMATIC Software Redundancy
SIMATICSW Redundancy
SW Redundancy withredundant Ringbus
MPI/PROFIBUS/ Ethernet
Master
controller
Back up
controller
OLM
PrinciplePositioningApplication FieldsConfigurationFeaturesOrder number and deliveryform
Automation and Drives
-
8/14/2019 Swred e Cern
12/15
Automation and Drives
A D AS SM6 R.Fischer 15IMATIC Software Redundancy
SIMATICSW Redundancy
SW Redundanz with Multi Redundancy
Back upcontroller
Redundant areaRedundant area
Nonredundantarea
Nonredundantarea
PrinciplePositioningApplication FieldsConfigurationFeaturesOrder number and deliveryform
Automation and Drives
-
8/14/2019 Swred e Cern
13/15
Automation and Drives
A D AS SM6 R.Fischer 16IMATIC Software Redundancy
SIMATICSW Redundancy
SW RedundancyFeaturesMaster slave switchover time dependant on:
CPU-Type number of I/O and number of DP-slaves volume of data to be transfered communication device
Example with 2 CPU 414-2 DP, 4 DP-Slaves, 4 kBytes Data, communication throught Profibus Data transfer time appr. 1 s DP-Slave swithover appr. 20 ms Fault detection time appr. 100ms Sum appr. 1,1 s
PrinciplePositioningApplication FieldsConfigurationFeaturesOrder number and deliveryform
Automation and Drives
-
8/14/2019 Swred e Cern
14/15
Automation and Drives
A D AS SM6 R.Fischer 17IMATIC Software Redundancy
SIMATICSW Redundancy
SW RedundancyFeaturesSwitchover procedure
Outputs are beeing frozen during the switchover After the switchover, the transfered data are used
Switchover reasons Master failure (Power off or CPU-STOP) Failure of the Profibus-DP of the master controller Manual switchover
Memory requirement is 10 kBytesSTEP7 V 4.02 is required
PrinciplePositioningApplication FieldsConfigurationFeaturesOrder number and deliveryform
Automation and Drives
-
8/14/2019 Swred e Cern
15/15
Automation and Drives
SIMATIC S7Software-Redundancy