swred e cern

Upload: sina20795

Post on 04-Jun-2018

215 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/14/2019 Swred e Cern

    1/15

    Automation and Drives

    SIMATIC S7Software Redundancy

  • 8/14/2019 Swred e Cern

    2/15

    Automation and Drives

    A D AS SM6 R.Fischer 2IMATIC Software Redundancy

    SIMATICSW Redundancy

    SW RedundancyPrinciple

    Steam Production

    Boiler 1 Mixer Boiler 2 Dryer

    REDUNDANCY Area

    PrinciplePositioningApplication FieldsConfigurationFeaturesOrder number and deliveryform

  • 8/14/2019 Swred e Cern

    3/15

    Automation and Drives

    A D AS SM6 R.Fischer 3IMATIC Software Redundancy

    SIMATICSW Redundancy

    SW RedundancyPositioningLow Cost / Low Performance Redundancy solution based on standard componentsUniversal solution for all CPU

    from CPU 315-2DP until CPU 417-4Marketing parallel to S7-400H

    PrinciplePositioningApplication FieldsConfigurationFeaturesOrder number and deliveryform

  • 8/14/2019 Swred e Cern

    4/15

    Automation and Drives

    A D AS SM6 R.Fischer 4IMATIC Software Redundancy

    SIMATICSW Redundancy

    SWRedundancyApplication FieldsApplication for processes that tolerate a Master-Slave switchover time of about a secondExamples:

    Water treatment Control of cooling systems Control and monitoring of

    temperature levels

    Traffic control Measuring registration

    PrinciplePositioningApplication FieldsConfigurationFeaturesOrder number and deliveryform

  • 8/14/2019 Swred e Cern

    5/15

    Automation and Drives

    A D AS SM6 R.Fischer 5IMATIC Software Redundancy

    SIMATICSW Redundancy

    SW Redundancy with S7-400Configuration

    Redundant AreaNon redundant

    MPI/ Profibus/ Ethernet

    Redundancy Connection

    Master

    controller

    Back up

    controller

    Non redundant

    AreaArea

    ET 200M with

    IM 153-2

    Active Bus Backup Bus

    PrinciplePositioningApplication FieldsConfigurationFeaturesOrder number and deliveryform

  • 8/14/2019 Swred e Cern

    6/15

    Automation and Drives

    A D AS SM6 R.Fischer 6IMATIC Software Redundancy

    SIMATICSW Redundancy

    Profibus DP Redundancywith Standard IM 153-2

    IM

    IM

    Bus module (BM)

    Active

    Bus module

    Profibus DP

    ET 200M

    with active Bus modules

    L+

    L+

    Redundant IM 153-2PrinciplePositioningApplication FieldsConfigurationFeaturesOrder number and deliveryform

    Available as individual componentsIM: 6ES7 153-2AA02-0XB0BM: 6ES7 195-7HD00-0XA0

    or as Bundle (2 x IM + 1 BM)6ES7 153-2AR00-0XA0

  • 8/14/2019 Swred e Cern

    7/15

    Automation and Drives

    A D AS SM6 R.Fischer 7IMATIC Software Redundancy

    SIMATICSW Redundancy

    SW RedundancyFunction

    Master

    Reception of status information

    from reserve controller

    Non redundant user program

    processing

    Redundant user program

    processing

    Transmission of redundant data to

    reserve controller

    Writing of non redundant and

    redundant outputs

    Reserve

    Reception of information from

    master controller

    Reading of Inputs

    Writing of non redundant

    outputs

    Non redundant user program

    processing

    Transmission of information to

    the master controller

    Reading of Inputs

    PrinciplePositioningApplication FieldsConfigurationFeaturesOrder number and deliveryform

    A d D

  • 8/14/2019 Swred e Cern

    8/15

    Automation and Drives

    A D AS SM6 R.Fischer 8IMATIC Software Redundancy

    SIMATICSW Redundancy

    SW Redundancy with S7-400

    Redundant area

    MPI/ PROFIBUS/ Ethernet

    Redundancy Connection

    Master

    controller

    Back up

    controller

    PrinciplePositioningApplication FieldsConfigurationFeaturesOrder number and deliveryform

    A i d D i

  • 8/14/2019 Swred e Cern

    9/15

    Automation and Drives

    A D AS SM6 R.Fischer 11IMATIC Software Redundancy

    SIMATICSW Redundancy

    SW Redundancy with S7-400 and WinCC

    Redundanzbereich

    PROFIBUS/MPI/Ethernet

    Master

    controller

    Back up

    controller

    Non

    redundant

    area

    WinCC Redundancy script

    Redundant area

    PrinciplePositioningApplication FieldsConfigurationFeaturesOrder number and deliveryform

    A t ti d D i

  • 8/14/2019 Swred e Cern

    10/15

    Automation and Drives

    A D AS SM6 R.Fischer 13IMATIC Software Redundancy

    SIMATICSW Redundancy

    SW Redundancywith single PROFIBUS

    MPI/PROFIBUS/ Ethernet

    Master

    controller

    Back up

    controller

    PrinciplePositioningApplication FieldsConfigurationFeaturesOrder number and deliveryform

    Automation and Dri es

  • 8/14/2019 Swred e Cern

    11/15

    Automation and Drives

    A D AS SM6 R.Fischer 14IMATIC Software Redundancy

    SIMATICSW Redundancy

    SW Redundancy withredundant Ringbus

    MPI/PROFIBUS/ Ethernet

    Master

    controller

    Back up

    controller

    OLM

    PrinciplePositioningApplication FieldsConfigurationFeaturesOrder number and deliveryform

    Automation and Drives

  • 8/14/2019 Swred e Cern

    12/15

    Automation and Drives

    A D AS SM6 R.Fischer 15IMATIC Software Redundancy

    SIMATICSW Redundancy

    SW Redundanz with Multi Redundancy

    Back upcontroller

    Redundant areaRedundant area

    Nonredundantarea

    Nonredundantarea

    PrinciplePositioningApplication FieldsConfigurationFeaturesOrder number and deliveryform

    Automation and Drives

  • 8/14/2019 Swred e Cern

    13/15

    Automation and Drives

    A D AS SM6 R.Fischer 16IMATIC Software Redundancy

    SIMATICSW Redundancy

    SW RedundancyFeaturesMaster slave switchover time dependant on:

    CPU-Type number of I/O and number of DP-slaves volume of data to be transfered communication device

    Example with 2 CPU 414-2 DP, 4 DP-Slaves, 4 kBytes Data, communication throught Profibus Data transfer time appr. 1 s DP-Slave swithover appr. 20 ms Fault detection time appr. 100ms Sum appr. 1,1 s

    PrinciplePositioningApplication FieldsConfigurationFeaturesOrder number and deliveryform

    Automation and Drives

  • 8/14/2019 Swred e Cern

    14/15

    Automation and Drives

    A D AS SM6 R.Fischer 17IMATIC Software Redundancy

    SIMATICSW Redundancy

    SW RedundancyFeaturesSwitchover procedure

    Outputs are beeing frozen during the switchover After the switchover, the transfered data are used

    Switchover reasons Master failure (Power off or CPU-STOP) Failure of the Profibus-DP of the master controller Manual switchover

    Memory requirement is 10 kBytesSTEP7 V 4.02 is required

    PrinciplePositioningApplication FieldsConfigurationFeaturesOrder number and deliveryform

    Automation and Drives

  • 8/14/2019 Swred e Cern

    15/15

    Automation and Drives

    SIMATIC S7Software-Redundancy