switchgear and protection 3
TRANSCRIPT
![Page 1: Switchgear and protection 3](https://reader036.vdocuments.site/reader036/viewer/2022082218/589c77ef1a28abc2258b490f/html5/thumbnails/1.jpg)
Unit-III Apparatus Protection:
Md Irshad [email protected]
Electrical Engineering DepartmentSubject: NEE –602: SWITCHGEAR AND
PROTECTION
![Page 2: Switchgear and protection 3](https://reader036.vdocuments.site/reader036/viewer/2022082218/589c77ef1a28abc2258b490f/html5/thumbnails/2.jpg)
Unit-III Protection of
Transmission Line: Over current protection Distance protection, Pilot wire protection Carrier current protection Protection of bus Auto re-closing,
![Page 3: Switchgear and protection 3](https://reader036.vdocuments.site/reader036/viewer/2022082218/589c77ef1a28abc2258b490f/html5/thumbnails/3.jpg)
As the fault impedance is less than load impedance, the fault current is more than load current. If a short circuit occurs the circuit impedance is reduced to a low value and therefore a fault is accompanied by large current.
Over-current protection is that protection in which the relay picks up when the magnitude of current exceeds the pickup level.
The Over-current relays are connected to the system, normally by means of CT's
Over current protection
![Page 4: Switchgear and protection 3](https://reader036.vdocuments.site/reader036/viewer/2022082218/589c77ef1a28abc2258b490f/html5/thumbnails/4.jpg)
1. High speed Over-current protection.
2. Definite time Over-current protection.
3. Inverse minimum time Over-current protection.
4. Directional Over-current protection
(of above types).
Over-current relaying has following types:
![Page 5: Switchgear and protection 3](https://reader036.vdocuments.site/reader036/viewer/2022082218/589c77ef1a28abc2258b490f/html5/thumbnails/5.jpg)
Construction and working principle of instantaneous over current relay quite simple.
Magnetic core is wound by current coil. A piece of iron is so fitted by hinge support and restraining spring in the relay, that when there is not sufficient current in the coil, the NO contacts remain open. When current in the coil crosses a present value, the attractive force becomes sufficient to pull the iron piece towards the magnetic core and consequently the no contacts are closed.
Instantaneous Over Current Relay
![Page 6: Switchgear and protection 3](https://reader036.vdocuments.site/reader036/viewer/2022082218/589c77ef1a28abc2258b490f/html5/thumbnails/6.jpg)
Definite Time Over Current Relay This relay is created by applying intentional time delay after
crossing pick up value of the current. A definite time over current relay can be adjusted to issue a trip output at definite amount of time after it picks up. Thus, it has a time setting adjustment and pick up adjustment.
Inverse Time Over Current Relay Inverse time is a natural character of any induction type
rotating device. This means the speed of rotation of rotating art of the device is faster if input current is increased.
Inverse Definite Minimum Time Over Current Relay or IDMT O/C Relay
Inverse time characteristics can not be achieved, in an over current relay. As the current in the system increases, the secondary current of the current transformer is increased proportionally. The secondary current is fed to the relay current coil. But when the CT becomes saturated
![Page 7: Switchgear and protection 3](https://reader036.vdocuments.site/reader036/viewer/2022082218/589c77ef1a28abc2258b490f/html5/thumbnails/7.jpg)
Classification of Transmission Lines
Short Lines Length < = 80kM
Medium Lines Length < = 240kM
Long Lines Length > 240kM
![Page 8: Switchgear and protection 3](https://reader036.vdocuments.site/reader036/viewer/2022082218/589c77ef1a28abc2258b490f/html5/thumbnails/8.jpg)
Types of faults in the transmission system
Short circuit faults Frequency
Phase – Ground faults 85%Phase- Phase faults 8%Phase – Phase –Ground faults 5%3 Ph faults 2%
Open circuit faults
Broken conductorOpen jumper
![Page 9: Switchgear and protection 3](https://reader036.vdocuments.site/reader036/viewer/2022082218/589c77ef1a28abc2258b490f/html5/thumbnails/9.jpg)
Protection SchemeProtection Scheme for Transmission lines as per CBIP guidelines• Should have two independent high speed main protection schemes• Two stage over voltage protection• Sensitive IDMT directional E/F relays• Auto reclose relay suitable for 1 ph/3ph (with deadline charging and synchro check) reclosure.
Types of main Protections:
• Over Current Protection.
• Differential or Phase Comparison or Unit Protection.
• Distance Protection.
![Page 10: Switchgear and protection 3](https://reader036.vdocuments.site/reader036/viewer/2022082218/589c77ef1a28abc2258b490f/html5/thumbnails/10.jpg)
• Shall have min. of three independent zones with directional characteristics.• Shall be non switched type with separate measurement for both earth faults
and phase faults• Capable of 1phase and 3 phase tripping.• Capable of operation for close up faults and switch on to faults• Accuracy of better than 5% of reach setting for Zone 1, 10% for Zone-2 &3.• Shall have variable residual compensation.• Shall include power swing detection feature for selectively blocking.• Shall include fuse failure feature to monitor all types of fuse failures and block
distance protection.
Requirements of distance protection:
![Page 11: Switchgear and protection 3](https://reader036.vdocuments.site/reader036/viewer/2022082218/589c77ef1a28abc2258b490f/html5/thumbnails/11.jpg)
If = E/(ZS+ZL)
The reach of over current relay is function of Source Impedance which varies considerably, making it difficultto get fast and Selective tripping .
E ZS ZL
If
X XXXX
Over Current Protection
![Page 12: Switchgear and protection 3](https://reader036.vdocuments.site/reader036/viewer/2022082218/589c77ef1a28abc2258b490f/html5/thumbnails/12.jpg)
Phase Comparison Protection
Current Phase comparison type Suitable for operation with PLCC High sensitivity and selectivity for all types of
faults Capable of single and three pole tripping. Un effected By: Heavy load transfer Power swings CT saturation CT Phase errors
![Page 13: Switchgear and protection 3](https://reader036.vdocuments.site/reader036/viewer/2022082218/589c77ef1a28abc2258b490f/html5/thumbnails/13.jpg)
Distance ProtectionType of distance relaysReactance Suitable for short lines Not effected by fault resistance Effected by power swings Non directionalImpedance Suitable for medium lines Non directional Effected by fault resistanceMho Directional Least effected by power swings Less effected by fault resistance
![Page 14: Switchgear and protection 3](https://reader036.vdocuments.site/reader036/viewer/2022082218/589c77ef1a28abc2258b490f/html5/thumbnails/14.jpg)
Impedance Relay Characteristics
LoadArea
X
RZ1
Z2Z3
![Page 15: Switchgear and protection 3](https://reader036.vdocuments.site/reader036/viewer/2022082218/589c77ef1a28abc2258b490f/html5/thumbnails/15.jpg)
MHO relay characteristic The characteristic of a mho impedance element , when plotted on a R/X diagram, is a circle whose circumference pass through the origin .
Y
Y = relay characteristic angle
R
X
![Page 16: Switchgear and protection 3](https://reader036.vdocuments.site/reader036/viewer/2022082218/589c77ef1a28abc2258b490f/html5/thumbnails/16.jpg)
OFF set MHO characteristic Under close up faults, when the voltage is near to zero then MHO will not operate. The mho characteristic can be shifted towards origin for operation of close up faults. This is know as OFF set MHO.
Y
Y = relay characteristic angle
R
X
![Page 17: Switchgear and protection 3](https://reader036.vdocuments.site/reader036/viewer/2022082218/589c77ef1a28abc2258b490f/html5/thumbnails/17.jpg)
Load
Lenticular characteristics The characteristic of lenticular mho will be useful to provide maximum load transfer condition with maximum fault resistance coverage.
Y
Y = relay characteristic angle
Z-1
Z-2
Z-3
Z-3
R
![Page 18: Switchgear and protection 3](https://reader036.vdocuments.site/reader036/viewer/2022082218/589c77ef1a28abc2258b490f/html5/thumbnails/18.jpg)
Quadrilateral characteristic It is a basically a reactance relay superseded with controlled resistive reach.
Y
Y = relay characteristic angle
Z-1&2
Z-1
Z-2
Z-3
Z-3
![Page 19: Switchgear and protection 3](https://reader036.vdocuments.site/reader036/viewer/2022082218/589c77ef1a28abc2258b490f/html5/thumbnails/19.jpg)
Zones of Distance Protection:
Z1Z2
Z3
BASIC SETTING PHILOSOPHY
ZONE –1 : 80 % of protected line ZONE –2 : 100 % of protected line + 20 % of shortest adj. line section or 100% + 50% of transformer impedance
ZONE –3 : 100% of protected line + 100 % of longest adj. line or 100 % + 100% of transformer impedance.
ZONE -4 : To cover close up back-up non-directional faults generally reverse reach will be provided in relays (10%).
X X X X X X
![Page 20: Switchgear and protection 3](https://reader036.vdocuments.site/reader036/viewer/2022082218/589c77ef1a28abc2258b490f/html5/thumbnails/20.jpg)
Parallel CompensationNecessity of parallel compensation:
For the fault on the parallel line, fault current also fed from healthy line and this current pass through ground. This current changes the mutual inductance and in turn causes relay measuring impedance to increase and is more than actual fault impedance.
This effect will be compensated by connecting neutral current of the line to parallel line.
This compensation will not work, if the parallel line neutral current is more than line neutral current.
![Page 21: Switchgear and protection 3](https://reader036.vdocuments.site/reader036/viewer/2022082218/589c77ef1a28abc2258b490f/html5/thumbnails/21.jpg)
ZONE-II CHARACTERISTICS Delayed tripping and non selective phase tripping.
Provide back up protection for part of adjacent line.
Trip the faulty line instantaneously using carrier aided tripping.Time delay is normally 500ms
ZONE-III CHARACTERISTICSThis provides back up protection for the adjacent lines or transformer
Time delay is normally 1500ms
ZONE –IV CHARACTERISTICSThis provides back up protection for the station faults
It is normally in the reverse direction
Time delay is normally 1500ms
![Page 22: Switchgear and protection 3](https://reader036.vdocuments.site/reader036/viewer/2022082218/589c77ef1a28abc2258b490f/html5/thumbnails/22.jpg)
Distance Schemes:
1 . P . U . R -- Permissive under reach scheme
2. P . O . R -- Permissive Over Reach scheme
3. BLOCKING SCHEME
4. WEAK END FEED
![Page 23: Switchgear and protection 3](https://reader036.vdocuments.site/reader036/viewer/2022082218/589c77ef1a28abc2258b490f/html5/thumbnails/23.jpg)
AUTORECLOSE – PHILOSOPHY
NEED FOR AUTO RECLOSE
1. REDUCING OUTAGE TIME 2. IMPROVED RELIABILITY 3. RESTORATION OF NETWORK STABILITY AND SYNCHRONISM
TYPES OF FAULTS
4. TRANSIENT FAULTS 5. SEMI PERMANENT FAULTS 6. PERMANENT FAULTS
![Page 24: Switchgear and protection 3](https://reader036.vdocuments.site/reader036/viewer/2022082218/589c77ef1a28abc2258b490f/html5/thumbnails/24.jpg)
TRANSIENT FAULTS -CHARACTERISTIC
Chracterised by disappearnance after Short dead time and aredisapper without any action being taken.
TYPES OF TRANSIENT FAULTS
1. Lightning strokes resulting in fashovers 2. Conductor swinging due to high winds3. Bird fault 4. Temporary contact with foreign objects like tree etc.
About 85 % of faults on transmission lines are transient in nature
![Page 25: Switchgear and protection 3](https://reader036.vdocuments.site/reader036/viewer/2022082218/589c77ef1a28abc2258b490f/html5/thumbnails/25.jpg)
DEAD TIME :
The time between the autoreclose scheme being energised and the operation of the contacts which energise the CB closing Circuit.
RECLAIM TIME :
The time following a successful closing operation measured from the instant the A/R relay closing contacts make, which must elapse before the autoreclose relay will initiate reclosingsequence in the event of a further fault.
![Page 26: Switchgear and protection 3](https://reader036.vdocuments.site/reader036/viewer/2022082218/589c77ef1a28abc2258b490f/html5/thumbnails/26.jpg)
CHOICE OF RECLAIM TIME The reclaim time must not be set to such a low value thatthe intended operating cycle of the breaker is exceededwhen two fault incidents occurs close together.
for example the reclaim time for a air blast circuit breakersmust allow time for air pressure to recover to its normal value.
CHOICE OF DEAD TIME Dead time for EHV system lower limit is decided by de-ionising time, upper limit is decided by transient stability and synchronism
![Page 27: Switchgear and protection 3](https://reader036.vdocuments.site/reader036/viewer/2022082218/589c77ef1a28abc2258b490f/html5/thumbnails/27.jpg)
Power SwingPower Swings are disturbances in system due to various reasons such as sudden load throw, bad synchronization etc
Power swings are characterized by slow power flow oscillations,resulting in swinging of voltages and currents, resulting in operating point movement into distance relay characteristics, in turn can cause tripping of distance relays.
Tripping during power swings is undesirable since no actual fault is present and moreover a line outage during power swing maycause further deterioration to system stability.
Detection of power swing will block the distance protectionZones 2,3,4. Normally tripping in Zone-I is not blocked even after detection of power swing.
![Page 28: Switchgear and protection 3](https://reader036.vdocuments.site/reader036/viewer/2022082218/589c77ef1a28abc2258b490f/html5/thumbnails/28.jpg)
X
R
Z1
Z2Z3
Power swing detection zones
Power Swing detection
Time taken by fault locus to cross the power swing detection zones is more than 40-50ms, then it is called power swing.
![Page 29: Switchgear and protection 3](https://reader036.vdocuments.site/reader036/viewer/2022082218/589c77ef1a28abc2258b490f/html5/thumbnails/29.jpg)
Fuse Failure FunctionAsymmetrical measuring voltage failure:
Substantial asymmetry of measured voltage, while the measured currents are in symmetry indicates fuse failAsymmetry of voltage detected by 3Uo or U2 > thresholdSymmetry in current detected by 3Io or I2 < thresholdDuring blocking of distance protection by fuse fail, the distance protection switched to emergency over current function automatically.
If the asymmetry in measured current is detected during blocking by FF function, then FF block will released.
![Page 30: Switchgear and protection 3](https://reader036.vdocuments.site/reader036/viewer/2022082218/589c77ef1a28abc2258b490f/html5/thumbnails/30.jpg)
Switch on to fault
This feature provide protection against energisation of the tr. line with fault or dead short.Distance protection will not provide protection in this case as voltage is not available for distance measurement.It can be activated by TNC switch or CB aux. binary input or internal detection of current rise.It provides instantaneous 3Ph trip and blocks auto reclose.
![Page 31: Switchgear and protection 3](https://reader036.vdocuments.site/reader036/viewer/2022082218/589c77ef1a28abc2258b490f/html5/thumbnails/31.jpg)
One and Half Breaker SchemeCkt-1 Ckt-2
Bus-1
Bus-2
21
Stub Protection
![Page 32: Switchgear and protection 3](https://reader036.vdocuments.site/reader036/viewer/2022082218/589c77ef1a28abc2258b490f/html5/thumbnails/32.jpg)
DEF Protection
It provides back up protection for tr. line.It provides reliable protection for high resistance earth faults.It uses cross polarized voltage for directional discrimination.
![Page 33: Switchgear and protection 3](https://reader036.vdocuments.site/reader036/viewer/2022082218/589c77ef1a28abc2258b490f/html5/thumbnails/33.jpg)
Carrier current protection scheme is mainly used for the protection of the long transmission line.
In the carrier, current protection schemes, the phase angle of the current at the two phases of the line are compared instead of the actual current.
Phase angle of the line decides whether the fault is internal and external.
The main elements of the carrier channel are a transmitter, receiver, coupling equipment, and line trap
Carrier Current Protection of Transmission Lines
![Page 34: Switchgear and protection 3](https://reader036.vdocuments.site/reader036/viewer/2022082218/589c77ef1a28abc2258b490f/html5/thumbnails/34.jpg)
In Absence Of BUSBAR Protection, Fault Clearance takes place
in Zone II of Distance Relay by Remote End Tripping
This Means Slow & Unselective Tripping and wide spread blackout
NEED FOR BUS BAR PROTECTION
![Page 35: Switchgear and protection 3](https://reader036.vdocuments.site/reader036/viewer/2022082218/589c77ef1a28abc2258b490f/html5/thumbnails/35.jpg)
Minimizing damage at fault location
Maintaining system stability
Localizing isolation to avoid wide spread disruption
Delayed clearance create shock to inter connected equipment like Generator shaft and windings of Transformer
NEED FOR BUS BAR PROTECTION
![Page 36: Switchgear and protection 3](https://reader036.vdocuments.site/reader036/viewer/2022082218/589c77ef1a28abc2258b490f/html5/thumbnails/36.jpg)
High speed operation
Selectivity – shall isolate the faulty bus bar only
Stability – stable for through faults upto 40 KA fault level
Reliability – Check feature
Applicable for any type of bus bar protection
Shall provide zone indication
REQUIREMENT OF BUS BAR PROTECTION
![Page 37: Switchgear and protection 3](https://reader036.vdocuments.site/reader036/viewer/2022082218/589c77ef1a28abc2258b490f/html5/thumbnails/37.jpg)
Continuous supervision for CT Secondaries against any possible Open Ckt.
In case of detection of any Open Circuiting of CT secondary, after a time delay, the affected zone of protection shall be rendered(provide) in-operative and an alarm initiated.
REQUIREMENT OF BUS BAR PROTECTION
![Page 38: Switchgear and protection 3](https://reader036.vdocuments.site/reader036/viewer/2022082218/589c77ef1a28abc2258b490f/html5/thumbnails/38.jpg)
Bus bar protection must be provided in all new 400kV and 220kV Substations as well as Generation Switch Yards
For existing substations, provision of bus bar protection is considered a must at 400kV level and for 220kV level it is essential at substations having multiple feed.
In case of radially fed 220kv substations, having more than one bus it is desirable to have bus bar protection but is not a must
RECOMMENDATIONS FOR PROVIDING BUS BAR PROTECTION
![Page 39: Switchgear and protection 3](https://reader036.vdocuments.site/reader036/viewer/2022082218/589c77ef1a28abc2258b490f/html5/thumbnails/39.jpg)
NEED FOR BUSBAR PROTECTION
In Its Absence Fault Clearing Takes Place In Zone-2 Of Distance Relay By Remote End Tripping. this means slow and unselective tripping and wide spread blackout.
EFFECT OF DELAYED CLEARENCE
Greater damage at fault point.
Indirect shock to connected equipment like shafts of generator and windings of transformer.
BASIC THEORY
Kirchoff’s current law states that the sum of the currents entering a given node must be equal to the currents leaving at that node.
BASICS OF BUSBAR PROTECTION
![Page 40: Switchgear and protection 3](https://reader036.vdocuments.site/reader036/viewer/2022082218/589c77ef1a28abc2258b490f/html5/thumbnails/40.jpg)
TYPES OF BUS BAR PROTECTION
Low Impedance High Impedance
Both use Circulating Current Differential Principle - To isolate the entire bus bar section by disconnecting all the feeders connected to the bus.
![Page 41: Switchgear and protection 3](https://reader036.vdocuments.site/reader036/viewer/2022082218/589c77ef1a28abc2258b490f/html5/thumbnails/41.jpg)
HIGH SPEED DIFFERENTIAL PROTECTION
Simple Current Differential Circuit:
![Page 42: Switchgear and protection 3](https://reader036.vdocuments.site/reader036/viewer/2022082218/589c77ef1a28abc2258b490f/html5/thumbnails/42.jpg)
Simple Current Differential Circuit with Bus Fault
![Page 43: Switchgear and protection 3](https://reader036.vdocuments.site/reader036/viewer/2022082218/589c77ef1a28abc2258b490f/html5/thumbnails/43.jpg)
Simple Current Differential Circuit with Close in Line Fault
![Page 44: Switchgear and protection 3](https://reader036.vdocuments.site/reader036/viewer/2022082218/589c77ef1a28abc2258b490f/html5/thumbnails/44.jpg)
44
AUTO-RECLOSING It is placed on over head transmission line and nearer
to the CB . It is also one of the protective relay.
![Page 45: Switchgear and protection 3](https://reader036.vdocuments.site/reader036/viewer/2022082218/589c77ef1a28abc2258b490f/html5/thumbnails/45.jpg)
45
What is Auto – Reclosing ?
![Page 46: Switchgear and protection 3](https://reader036.vdocuments.site/reader036/viewer/2022082218/589c77ef1a28abc2258b490f/html5/thumbnails/46.jpg)
46
Introduction to auto-reclosing scheme
![Page 47: Switchgear and protection 3](https://reader036.vdocuments.site/reader036/viewer/2022082218/589c77ef1a28abc2258b490f/html5/thumbnails/47.jpg)
47
Types Of Faults
• Transient Faults• Semi Permanent faults• Permanent Faults
Utility Substation Customers
![Page 48: Switchgear and protection 3](https://reader036.vdocuments.site/reader036/viewer/2022082218/589c77ef1a28abc2258b490f/html5/thumbnails/48.jpg)
48
STEPS TO BE FOLLOWED IN AUTORECLOSING
Visual Check
Check of thePower Supply
Test of the Auto-re-closure settings
Functional Testing (involving operation of
Protective Relays & Circuit Breaker(s)
INSTALLATION
OPERATION
![Page 49: Switchgear and protection 3](https://reader036.vdocuments.site/reader036/viewer/2022082218/589c77ef1a28abc2258b490f/html5/thumbnails/49.jpg)
49
Scheme Of Operation
• Live bus\ Dead Line Charging• Other end closing under synchronism check relay• Live bus\ Live line charging
![Page 50: Switchgear and protection 3](https://reader036.vdocuments.site/reader036/viewer/2022082218/589c77ef1a28abc2258b490f/html5/thumbnails/50.jpg)
Types of Auto Reclosing1. Medium voltage auto-reclose
• Aim of continuity of supply• the obvious advantages are continuous supply except for short duration when tripping and re-closure operations are being performed.• high speed protection decreases the amount of damage incurred and thus increases the probability of auto reclosure.
2. High voltage auto-reclose• main considerations are of stability and synchronizing.• the fault levels associated are extremely high.• High speed re-closure in high voltage circuits improves the stability to a considerable extent on single-circuit ties.
![Page 51: Switchgear and protection 3](https://reader036.vdocuments.site/reader036/viewer/2022082218/589c77ef1a28abc2258b490f/html5/thumbnails/51.jpg)
51
FACTORS TO BE CONSIDERED FOR AUTO RECLOSING SYSTEM• Protection Characteristics• De- Ionization of Fault Arc• Circuit Breaker Characteristics• Reclaim Time• Number of Shots
![Page 52: Switchgear and protection 3](https://reader036.vdocuments.site/reader036/viewer/2022082218/589c77ef1a28abc2258b490f/html5/thumbnails/52.jpg)
52
SINGLE PHASE AUTO – RECLOSING
ADVANTAGES:-•Maintenance of System Integrity• Reduced switching overvoltage due to reclosing• Reduced shock to generators.• Sudden changes in mechanical output are less
• Longer De – ionization time
DISADVANTAGE:-
![Page 53: Switchgear and protection 3](https://reader036.vdocuments.site/reader036/viewer/2022082218/589c77ef1a28abc2258b490f/html5/thumbnails/53.jpg)
53
1. Densely interconnected systems.
Where the Loss of a single line is unlikely to
cause loss of synchronism between two ends
2. Dead Time is allowed to be long enough for any power swings due to fault and tripping allowed to decay before reclosing
a) Less shock to system than with high speed A/R
b) Problems of arc de – ionization times, and circuit breaker operating characterstics are eliminated.
Delayed Auto-Reclose Application
![Page 54: Switchgear and protection 3](https://reader036.vdocuments.site/reader036/viewer/2022082218/589c77ef1a28abc2258b490f/html5/thumbnails/54.jpg)
54
Operating feature of Auto reclosing schemes
• Dead Timer• Anti Pumping Devices• Reclaim timer• CB Lockout• Manual Closing• Multi Shot Scheme
![Page 55: Switchgear and protection 3](https://reader036.vdocuments.site/reader036/viewer/2022082218/589c77ef1a28abc2258b490f/html5/thumbnails/55.jpg)
55
Auto - Reclose Blocking• Receipt of transfer Trip• Manual Trip• Breaker failure• Three phase Fault• Faults On Buses• Under frequency/ Under voltage load shedding trips
![Page 56: Switchgear and protection 3](https://reader036.vdocuments.site/reader036/viewer/2022082218/589c77ef1a28abc2258b490f/html5/thumbnails/56.jpg)
56
Benefits Of Auto - Reclosing
• Minimizing the interruption of supply.• Maintenance of system stability and Synchronism.• Minimum Outage and least expenditure of manpower.• Ability to run substation unattended.
![Page 57: Switchgear and protection 3](https://reader036.vdocuments.site/reader036/viewer/2022082218/589c77ef1a28abc2258b490f/html5/thumbnails/57.jpg)