Page 1: Surge current rating (or Imax)-Everything about it-VCrevenat...Imax could be… There isn’t a right or wrong definition of the Imax, and this paper is an attempt to sum up all the

Presented by:Vincent Crevenat

Director of EngineeringCitel

Surge current rating (or Imax): everything about it

Page 2: Surge current rating (or Imax)-Everything about it-VCrevenat...Imax could be… There isn’t a right or wrong definition of the Imax, and this paper is an attempt to sum up all the

• The discussion is about one of the most famous characteristics claimed by the USSPD manufacturers and requested by the SPD’s users through specifications.Surprisingly, that characteristic is not defined anywhere in the official literature.There are several discussions on how to clarify the definition of the Imax at variousstandardization organization levels but no agreement yet has been reached.This means that manufacturers and users are totally free to interpret what theImax could be… There isn’t a right or wrong definition of the Imax, and this paperis an attempt to sum up all the various interpretations that can be found in thefield depending on who is addressing them or justifying them.

• This paper will also attempt to provide various key points on the definition for theselection of SPDs based on this characteristic and its impact when the SPD is inuse.

• During the discussion, the surge risk will be addressed and the expected lifeduration of an SPD.

Page 3: Surge current rating (or Imax)-Everything about it-VCrevenat...Imax could be… There isn’t a right or wrong definition of the Imax, and this paper is an attempt to sum up all the

3 – PRODUCTS...

3.2 AC POWER : ...3.2.2PERFORMANCE

...3.2.2.2  SPD Maximum Discharge Current per phase (Imax – 8/20µs) shall be: 

a. 450 kA or above for Service Entrance or transfer Switch.b. 200 kA or above for Distribution Panelboard and MCCc. 100 kA or above for Branch Panel

...

Page 4: Surge current rating (or Imax)-Everything about it-VCrevenat...Imax could be… There isn’t a right or wrong definition of the Imax, and this paper is an attempt to sum up all the

B. Service Entrance/Transfer Switch SPDs:…

5. Minimum Surge Current Rating:  200kA per phase.…

Page 5: Surge current rating (or Imax)-Everything about it-VCrevenat...Imax could be… There isn’t a right or wrong definition of the Imax, and this paper is an attempt to sum up all the

…2.11 SURGE PROTECTIVE DEVICE(S)

A. Electrical Requirements2. …3. The device shall have a minimum surge current rating of 125kA per 

mode / 250kA per phase with a minimum of 20,000 category C3 impulses (10kA, 20kV) per mode.

4.  …

Page 6: Surge current rating (or Imax)-Everything about it-VCrevenat...Imax could be… There isn’t a right or wrong definition of the Imax, and this paper is an attempt to sum up all the

What Is this Surge Current Ratingor Imax??

What does it mean for SPD selection??? 

Page 7: Surge current rating (or Imax)-Everything about it-VCrevenat...Imax could be… There isn’t a right or wrong definition of the Imax, and this paper is an attempt to sum up all the
Page 8: Surge current rating (or Imax)-Everything about it-VCrevenat...Imax could be… There isn’t a right or wrong definition of the Imax, and this paper is an attempt to sum up all the
Page 9: Surge current rating (or Imax)-Everything about it-VCrevenat...Imax could be… There isn’t a right or wrong definition of the Imax, and this paper is an attempt to sum up all the
Page 10: Surge current rating (or Imax)-Everything about it-VCrevenat...Imax could be… There isn’t a right or wrong definition of the Imax, and this paper is an attempt to sum up all the
Page 11: Surge current rating (or Imax)-Everything about it-VCrevenat...Imax could be… There isn’t a right or wrong definition of the Imax, and this paper is an attempt to sum up all the

From Specifications and MOV 

manufactures:

8/20µs

Page 12: Surge current rating (or Imax)-Everything about it-VCrevenat...Imax could be… There isn’t a right or wrong definition of the Imax, and this paper is an attempt to sum up all the

Depending on MOV manufacturers…

Page 13: Surge current rating (or Imax)-Everything about it-VCrevenat...Imax could be… There isn’t a right or wrong definition of the Imax, and this paper is an attempt to sum up all the

500

505

510

515

520

525

530

535

540

0 2 4 6 8 10 12

Voltage to get 1mA(V)

Number of shocs

Evolution of the voltage to get 1mA of current flowing through an MOV rated 40kA Imax (20kA In) versus the number of shocks set to Imax (40kA 8/20)

Echantillon # 2 U1mA en > 0 (en Volt) Echantillon # 2 U1mA en < 0 (en Volt)

Page 14: Surge current rating (or Imax)-Everything about it-VCrevenat...Imax could be… There isn’t a right or wrong definition of the Imax, and this paper is an attempt to sum up all the

What can happen in this box???

How the surge current will split?

Is the power system impacting this surge current sharing?

SPD

Page 15: Surge current rating (or Imax)-Everything about it-VCrevenat...Imax could be… There isn’t a right or wrong definition of the Imax, and this paper is an attempt to sum up all the

SPDN

L1 L2

Page 16: Surge current rating (or Imax)-Everything about it-VCrevenat...Imax could be… There isn’t a right or wrong definition of the Imax, and this paper is an attempt to sum up all the

N

L1 L2 Per Mode:L1‐N = 40kAL2‐N = 40kAL1‐G = 80kAL2‐G = 20kAN‐G = 60kA

Let’s assume that 1 MOV is 20kA

Page 17: Surge current rating (or Imax)-Everything about it-VCrevenat...Imax could be… There isn’t a right or wrong definition of the Imax, and this paper is an attempt to sum up all the

N

L1 L2 Per Phase:L1:(L1‐G)+(L1‐N)= 120kA

L2(L2‐G)+(L1‐N)= 60kA

Let’s assume that 1 MOV is 20kA

Page 18: Surge current rating (or Imax)-Everything about it-VCrevenat...Imax could be… There isn’t a right or wrong definition of the Imax, and this paper is an attempt to sum up all the

N

L1 L2 Total:(L1‐G) + (L2‐G) +(N‐G)= 160kA

Let’s assume that 1 MOV is 20kA

Page 19: Surge current rating (or Imax)-Everything about it-VCrevenat...Imax could be… There isn’t a right or wrong definition of the Imax, and this paper is an attempt to sum up all the

• When several MOVs in parallel are subject to surgecurrent, the exact quantity of energy that each singleMOV will have to withstand is not equal to the otherMOVs resulting in the chance that one MOV isexposed to higher energy that it can handle.

• It is possible to apply a de‐rating coefficient toconsider this point.

Page 20: Surge current rating (or Imax)-Everything about it-VCrevenat...Imax could be… There isn’t a right or wrong definition of the Imax, and this paper is an attempt to sum up all the

1          40kA

2          40kA

50% ?

100%

50% ?

• Worst case: Imax = 0.8 x ( Imax1 + Imax2 )   Imax = 65kA• Medium case: Imax = 0.9 x ( Imax1 + Imax2 )   Imax = 72kA• Dreamed case: Imax = 1 x ( Imax1 + Imax2 )   Imax = 80kA

Page 21: Surge current rating (or Imax)-Everything about it-VCrevenat...Imax could be… There isn’t a right or wrong definition of the Imax, and this paper is an attempt to sum up all the

1          40kA

2          40kA

25% ?

25% ?

1          40kA

2          40kA

25% ?

100%

25% ?

Page 22: Surge current rating (or Imax)-Everything about it-VCrevenat...Imax could be… There isn’t a right or wrong definition of the Imax, and this paper is an attempt to sum up all the

1          65kA

2          65A

50% ?

100%

50% ?

• Worst case: Imax = 0.8 x ( 65 + 65 )   Imax = 104kA

Instead of: 4x40 = 160kA!!!!!

Page 23: Surge current rating (or Imax)-Everything about it-VCrevenat...Imax could be… There isn’t a right or wrong definition of the Imax, and this paper is an attempt to sum up all the

IEC propose one but it is optional:

2 shocks at In (+&‐) + 1 single shock at Imax .

– These 3 shocks are with cooling time in betweeneach shocks.

– Power is supplied to the SPD during shocks (90° and270°).

Pass Criteria:No explosion (only!!!)

SPD

Page 24: Surge current rating (or Imax)-Everything about it-VCrevenat...Imax could be… There isn’t a right or wrong definition of the Imax, and this paper is an attempt to sum up all the

No test is today available in the US do test this Imax or Surge 

rating for an SPD.SPD

Page 25: Surge current rating (or Imax)-Everything about it-VCrevenat...Imax could be… There isn’t a right or wrong definition of the Imax, and this paper is an attempt to sum up all the

First approach is to reject these values for thevery good reason that an installed SPD will neverbe subjected to these (as a recall, usual stressevaluated by various US guides or standards isless than 20kA).

Page 26: Surge current rating (or Imax)-Everything about it-VCrevenat...Imax could be… There isn’t a right or wrong definition of the Imax, and this paper is an attempt to sum up all the

0

5

10

15

20

25

30

35

40

45

0 20 40 60 80 100 120 140

8/20

 surge w

itstand

e (1 sh

ot)

Fuse rating  in A

Page 27: Surge current rating (or Imax)-Everything about it-VCrevenat...Imax could be… There isn’t a right or wrong definition of the Imax, and this paper is an attempt to sum up all the
Page 28: Surge current rating (or Imax)-Everything about it-VCrevenat...Imax could be… There isn’t a right or wrong definition of the Imax, and this paper is an attempt to sum up all the

IEC has a different approach when the maximum threatis to be considered… But not to be discussed here…

Even if recent input from IEEE groups introduced newparameters such as:

• Different wave form (See RHU IEEE guide)• Number or surge repetitions

Page 29: Surge current rating (or Imax)-Everything about it-VCrevenat...Imax could be… There isn’t a right or wrong definition of the Imax, and this paper is an attempt to sum up all the

• Marketing horse power race??? For sure!!!!

• Expressing the maximum stress that the SPD can withstand??? More than doubtful!!!

• Expressing the maximum stress that the installation is going see one day??? No way!!!

Page 30: Surge current rating (or Imax)-Everything about it-VCrevenat...Imax could be… There isn’t a right or wrong definition of the Imax, and this paper is an attempt to sum up all the

Usually, high declared values can only be achieved by using multi MOVs in parallel…

Page 31: Surge current rating (or Imax)-Everything about it-VCrevenat...Imax could be… There isn’t a right or wrong definition of the Imax, and this paper is an attempt to sum up all the

0

100

200

300

400

500

600

Volts

Number of shots

U1mA positive and negative value

1.1 1.2 1.3 2.1 2.2 2.3

The 1 mA voltage value increase when the MOV is stressed If several MOV are in parallel, the current is going to be self balanced 

Page 32: Surge current rating (or Imax)-Everything about it-VCrevenat...Imax could be… There isn’t a right or wrong definition of the Imax, and this paper is an attempt to sum up all the

70

300When the current is divided by 2, the surge amount that can withstand the same MOV is multiplied by more than !!!

5 000     10 000

Page 33: Surge current rating (or Imax)-Everything about it-VCrevenat...Imax could be… There isn’t a right or wrong definition of the Imax, and this paper is an attempt to sum up all the
Page 34: Surge current rating (or Imax)-Everything about it-VCrevenat...Imax could be… There isn’t a right or wrong definition of the Imax, and this paper is an attempt to sum up all the
Page 35: Surge current rating (or Imax)-Everything about it-VCrevenat...Imax could be… There isn’t a right or wrong definition of the Imax, and this paper is an attempt to sum up all the

• If tested (standard’s request) it will drasticallydecrease the numbers that are used in US sincedecades… But Why not? This will imply to declarevarious pass criteria (e.g. Withstand, Disconnected,

• If declared high values for Surge current rating (orImax) are the reflect of multi MOV, then it can beused for SPD selection in regards either to lifeduration or co