SureFlow
Presented by:
Ron Porter LEED AP
IEC Oklahoma City
Copyright 2012
![Page 2: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/2.jpg)
Topics
• Fan Coil Basics• Traditional System Design• SureFlow Hydronics• SureFlow Unit Design• SureFlow Applications
![Page 3: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/3.jpg)
This Is A Fan Coil
Fan + Coil = Fan CoilRoom Air Conditioner
![Page 4: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/4.jpg)
Moves air through a coil with:
Chilled WaterHot WaterElectric HeatR410a
Let’s focus on the water systems…
How Do They Work ?
![Page 5: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/5.jpg)
FCU
ChillerChiller
FCUFCUFCU
Central Pump Pushes Water Through Piping to Supply Each Fan Coil
Standard Water Pressure Differential System
![Page 6: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/6.jpg)
How Do We Size The Main Pump ?
![Page 7: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/7.jpg)
Central Pump Horsepower = __Head x GPM__
3960 x Efficiency
![Page 8: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/8.jpg)
FCU
ChillerChiller
FCUFCUFCU
Calculate All Circuits
Pump Sizing Based On Highest Pressure Drop Circuit
![Page 9: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/9.jpg)
FCU
ChillerChiller
FCUFCUFCU
Water Always Takes The Path Of Least Resistance
How Do We Know The Fan Coils Will Operate As Advertised ?
![Page 10: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/10.jpg)
FCU
ChillerChiller
FCUFCUFCU
Water Pipe Has Resistance To Water Flow
Pipe and Riser Diameters ?
![Page 11: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/11.jpg)
Continuity : Water In = Water Out (GPM Per Minute)
Velocity : Speed of Travel (Feet Per Second)
D1 D2
Vel1 Vel2Area1 Area2
Flow In “Q” Flow Out “Q”
Flow In “Q” = 10 GPM
D1= 1 Inch “L” Copper
Vel1 = 3.9 Ft Per Second
Flow Out “Q” = 10 GPM
D2= 2 Inches “L” Copper
Vel2 = 1.05 Ft Per Second
![Page 12: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/12.jpg)
Pressure drop is defined as:
The difference in pressure between any two points
on a piece of equipment.
D1D2
Vel1 Vel2Area1 Area2
Flow In “Q” Flow Out “Q”
Flow In “Q” = 10 GPM
D1= 1 Inch “L” Copper
Vel1 = 3.9 Ft Per Second
PD1 = 6.71 Ft per 100 Ft
Flow Out “Q” = 10 GPM
D2= 2 Inches “L” Copper
Vel2 = 1.05 Ft Per Second
PD2 = 0.29 Ft per 100 Ft
PD1 PD2
![Page 13: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/13.jpg)
Coil Pressure Drop =Cost of Operation
Determined from several parameters-• Unit size• Coil rows• Coil circuits• GPM• Tube water velocity• Water temperature
Use IEC Rating Program to determine pressure drop through
the coil at actual operating conditions
Example
@ 3.0 GPM
Coil PdFt = 5.9
![Page 14: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/14.jpg)
Valve Pressure Drop:
• Resistance to water flow
• Based on water volume through the valve at
Full Open
• Calculated using Cv Rating Number
• PdFt = ( GPM / ( 0.658 x Cv ))^2
![Page 15: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/15.jpg)
Typical Ball Valve Pressure Drop:
• PdFt = ( GPM / ( 0.658 x Cv ))^2
• Ball valve Cv = 5.84 (1/2 inch)• GPM = 3• PdFt = (3 / (0.658 x 5.84))^2
• PdFt = 0.61
![Page 16: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/16.jpg)
Full-Port Ball Valve Pressure Drop:
• PdFt = ( GPM / ( 0.658 x Cv ))^2
• Ball valve Cv = 14.2 (1/2 inch B&K # 107-503T)• GPM = 3• PdFt = (3 / (0.658 x 14.2))^2
• PdFt = 0.10
![Page 17: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/17.jpg)
![Page 18: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/18.jpg)
Erie Valve Pressure Drop:
• PdFt = ( GPM / ( 0.658 x Cv ))^2
• Cv = 3.5 (1/2 inch VT2213)
• GPM = 3
• PdFt = (3 / (0.658 x 3.5))^2
• PdFt = 1.7
VT2213
3.5 Cv (7/16” Port)
25 PSI Close-Off
![Page 19: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/19.jpg)
Erie Valve Pressure Drop:
• PdFt = ( GPM / ( 0.658 x Cv ))^2
• Cv = 2.5 (1/2 inch VT2212)
• GPM = 3
• PdFt = (3 / (0.658 x 2.5))^2
• PdFt = 3.3
VT2212
2.5 Cv (5/16” Port)
40 PSI Close-Off
![Page 20: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/20.jpg)
Erie Valve Pressure Drop:
• PdFt = ( GPM / ( 0.658 x Cv ))^2
• Cv = 1.0 (1/2 inch VT2211)
• GPM = 3
• PdFt = (3 / (0.658 x 1.0))^2
• PdFt = 20.8
VT2211
1.0 Cv
60 PSI Close-Off
![Page 21: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/21.jpg)
FCU
Analyze Combined Unit And Valve Package Pressure Drop
@ GPM = 3.0
Ball Valve PdFt = 0.1
Coil PdFt = 5.9
Erie Valve PdFt = 3.3
Ball Valve PdFt = 0.1
Total PdFt = 9.4
÷ 2.33
= 4.0 PSI Diff
Total Value Required For Proper Fan Coil Operation
![Page 22: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/22.jpg)
BoilerBoiler
FCUFCUFCU
Will This Design Operate Properly ?
Supply
Return
80 PSI
Δ 10 PSI
70 PSI 65 PSI
85 PSI
Δ 20 PSI
Units &
Valves
@ 3.0 GPM
Require
4.0 PSI Diff Pump
60 GPM
60 Ft Head60 PSI
Δ 25 PSI
Typical of 20 Units
![Page 23: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/23.jpg)
BoilerBoiler
FCUFCUFCU
Water Balancing Is Required
Supply
Return
5 PSI
Δ 1 PSI
4 PSI 70 PSI
80 PSI
Δ 10 PSI
Pump
60 GPM
60 Ft Head60 PSI
Δ 25 PSI
Units &
Valves
@ 3.0 GPM
Require
4.0 PSI Diff
Excessive FlowLow Flow
![Page 24: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/24.jpg)
BoilerBoilerFCUFCUFCUFCU
Cartridge Valves For Automatic Balancing
Supply
Return
![Page 25: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/25.jpg)
Hays 2517 Automatic Balancing Valve
2-80 PSID range up to 5.5 GPM
+/- 10% Accuracy
![Page 26: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/26.jpg)
Valve Will Add Resistance As Required For Specified Water GPM
![Page 27: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/27.jpg)
Analyze Combined Unit And Valve Package Pressure Drop
@ GPM = 3.0
Ball Valve PdFt = 0.1
Hays Valve PdFt = 4.6
Coil PdFt = 5.9
Erie Valve PdFt = 3.3
Ball Valve PdFt = 0.1
Total PdFt = 14
÷ 2.33
= 6.0 PSI Diff
FCU
![Page 28: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/28.jpg)
BoilerBoilerFCUFCUFCUFCU
80 PSI
70 PSI
Full Load
Pump
60 GPM
60 Ft Head
VFD
ΔP
Δ 10 PSI
Full-Load Variable Frequency Drive
![Page 29: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/29.jpg)
BoilerBoilerFCUFCUOFFFCU
80 PSI
70 PSI
Part Load
Pump
45 GPM
VFD
ΔP
Δ 10 PSI
Part-Load Variable Frequency Drive
![Page 30: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/30.jpg)
BoilerBoilerFCUFCUFCUFCU
80 PSI
70 PSI
Full Load
Pump
60 GPM
60 Ft Head
VFD
ΔP
Δ 10 PSI
Direct Return System
![Page 31: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/31.jpg)
ChillerChiller
Reverse Return –Balancing is reduced, therefore the need for balancing valves is reduced, but only if all coils have identical ΔP and system
pressure differential always equals coil required ΔP.
VFD
ΔP
FCU FCU FCU FCU
![Page 32: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/32.jpg)
Chiller / Boiler Equipment Plant Pumps Create Water Pressure Differential Pipes Running To and From Each Unit Valves – On/Off or Modulating Balancing Valves – Flow Regulators Strainers Pressure Relief Valves Variable Speed Drives on Pumps Controls, DDC, Building Energy Management System Installation Labor – vs. – 2/Pipe – vs. – 4/Pipe Test & Balance Maintenance
System Design Issues
![Page 33: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/33.jpg)
System Complexity Issues
There Must Be A Better
Way
![Page 34: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/34.jpg)
Primary Circuit Water Flow
Integrated CirculatorCycles on Thermostat
Demand
2008 ASHRAE Handbook HVAC Systems and Equipment
Chapter 12.
ThermostatOFF
![Page 35: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/35.jpg)
Cool AirCool AirCool AirCool Air
Primary Circuit Water Flow
2008 ASHRAE Handbook HVAC Systems and Equipment
Chapter 12.
ThermostatON
![Page 36: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/36.jpg)
Primary Circuit Water Flow
2008 ASHRAE Handbook HVAC Systems and Equipment
Chapter 12.
ThermostatOFF
![Page 37: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/37.jpg)
![Page 38: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/38.jpg)
![Page 39: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/39.jpg)
• Average 40% Less Piping
• Fewer Pipe Hangers
• Less Insulation
Massachusetts College of Pharmacy and Health Sciences
Worcester, Massachusetts
![Page 40: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/40.jpg)
• Reduced Core Drilling
• Fewer Joints = Fewer Leaks
• Contractor Savings
Westin Cupples StationSt. Louis, Missouri
![Page 41: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/41.jpg)
Westin Cupples StationSt. Louis, Missouri
![Page 42: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/42.jpg)
CPF SureFlow Unit
What Happened To The Zone Valves
and Flow Control Valves ?
![Page 43: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/43.jpg)
Circulator – 1/40 HP• 30+ Years In Production
• Millions In Use
• Quiet Operation
• Chilled Water CERTIFIED
• Wet Rotor Cartridge Design
• Internal Flow Check Valve
• 200 PSI Rating
• Cycles On-Off (Thermostat Controlled)
• Low Energy Consumer – 65 Watts
![Page 44: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/44.jpg)
![Page 45: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/45.jpg)
![Page 46: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/46.jpg)
Two Pipe CoolingWith Only One Installed Pipe
Chiller
FANCOIL
FANCOIL
FANCOIL
FANCOIL
Water Circulation Rate ≈ 3 GPM per TonPump Head & Energy Reduced
![Page 47: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/47.jpg)
Chiller
FANCOIL
FANCOIL
FANCOIL
FANCOIL
Boiler
Two Pipe Cooling & Heating “Change Over”
With One Installed Pipe
![Page 48: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/48.jpg)
2-Pipe Cooling and Heating Changeover With Only One Installed Pipe
Massachusetts College of Pharmacy and Health Sciences
Worcester, Massachusetts
![Page 49: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/49.jpg)
Four Pipe Heat & CoolWith Only Two Installed Pipes
Chiller
FANCOIL
Boiler
FANCOIL
FANCOIL
FANCOIL
![Page 50: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/50.jpg)
1. What Happens To The Water Temperature ?
2. Will It Control Humidity ?
Challenges:
![Page 51: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/51.jpg)
42ºF 46.6ºF46.6ºF 48.6ºF
44.4ºF
Chiller
Off
52.1ºF
Water Temperature Changes As BTUs Are Injected Into The SureFlow Loop
1 Ton13177t 9954s
1 Ton
12052t 9519s
1 Ton
14424t 10448s
1 Ton
![Page 52: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/52.jpg)
Cooling Loop Water Pipe Size
Design GuideType L Copper
Pipe Size 1” 1-1/4 1-1/2 2 2-1/2 3
GPM 8 16 25 53 85 127
FPS Vel 3.13 4.1 4.53 5.54 5.74 6.01
PdFt / 100Ft 4.53 5.66 5.46 5.58 4.57 4
Tons @ 8ΔT 2.7 5.3 8.3 17.7 28.3 42.3
Tons @ 10ΔT 3.3 6.7 10.4 22.1 35.4 52.9
![Page 53: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/53.jpg)
Pipe Size 1” 1-1/4 1-1/2 2 2-1/2 3
GPM 8 16 25 53 85 127
FPS Vel 3.13 4.1 4.53 5.54 5.74 6.01
PdFt / 100Ft 4.53 5.66 5.46 5.58 4.57 4
MBH @ 20ΔT 80 160 250 530 850 1270
MBH @ 25ΔT 100 200 312 662 1062 1587
Design GuideType L Copper
Heating Loop Water Pipe Size
![Page 54: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/54.jpg)
8 Degree Loop Delta-T = 3 GPM per Ton
Cooling Loop Water Temperature
![Page 55: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/55.jpg)
10 Tons Peak x 3 GPM per Ton = 30 GPM1-1/2” L Copper @ 30GPM = 5.43 fps = 7.55 ftpd/100ft
2” L Copper Pipe @ 30GPM = 3.14 fps = 2.02 ftpd/100ft
Peak Load Analysis Sample
![Page 56: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/56.jpg)
7.5 Tons Block / 10 Tons Peak = 75% Diversity Ratio
Block vs Peak Load Analysis
![Page 57: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/57.jpg)
With 42F Supply, 3 GPM Per Ton, 75% RatioMax Actual Water Temperature = 48F
BLOCK LOAD RATIO
Design For Diversity
![Page 58: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/58.jpg)
With 42F Supply, 3 GPM Per Ton, 75% RatioMax Actual Water Temperature = 48F
Design For Diversity
SOME UNITS
ARE NOT RUNNING
ARE SOME UNITS OVER
SIZED ?
![Page 59: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/59.jpg)
SureFlow Allows Adjustment Of The Design For Occupancy
– School Classroom vs. Common areas– Hotel Rooms– Offices– Usage patterns, time of day
![Page 60: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/60.jpg)
SureFlow Allows Modification Of The Design For Run Time and Fan Speed
– Actual hours of operation with full water flow
– Good water flow rate results in excellent humidity control
– Take full advantage of controls capabilities
– Always recommend automatic fan speed reduction for extended run-time on coil
![Page 61: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/61.jpg)
Circulators Only Consume Power When Running
Local Circulators Controlled by Room Thermostats
System Strategy: Demand Controlled Pumping
The Building Hydronic System Becomes An Energy Management System
Horsepower Savings
LEED 2009-NC Credit EAc1Optimize Energy Performance
Up To 19 Points Available
![Page 62: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/62.jpg)
Complex 2-way valve package
= 32 solder joints
SureFlow valve package
= 16 solder joints
Installation and Maintenance Savings
![Page 63: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/63.jpg)
Primary Pump
Common Load
Secondary Pump
Chiller - Or -Heat
Exchanger
Compound Primary-Secondary Pumping
![Page 64: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/64.jpg)
Building 1 of X Building 2 of X
Central Plant
Campus Chilled Water
![Page 65: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/65.jpg)
Balance Valves
3 Way Control Valve
Load
Replace Your Original Existing 2-pipe FCU….
CW Supply
CW Return
![Page 66: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/66.jpg)
…. With a New SureFlow Unit and Have 4-Pipe Performance With Two Pipes
Existing Pipes
HeatingCoil
HeatingCoil
CoolingCoil
CoolingCoil
CW Supply/Return
HW Supply/Return
![Page 67: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/67.jpg)
1839 US Tariff Building – General Post Office
Owner: US Department of Interior – Park Service
Lease: Kimpton Hotel & Restaurant Group
232 Rooms – AAA 4 Diamond
Opened Summer 2002
SureFlow Fan CoilsHotel MonacoWashington DC
Case Study
![Page 68: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/68.jpg)
Fernando Garcia, P.E.Vice PresidentCTA Consulting Engineers Inc.Rockville, MD(301) 637-0058
![Page 69: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/69.jpg)
Chicago Blackstone Renaissance Hotel
636 South Michigan332 Rooms
Restoration of 1908 HotelOpened Fall 2007
1920: Location of the famous “Smoke Filled Rooms” where Warren G. Harding was chosen as the Republican nominee for President.
1940: Franklin Delano Roosevelt’s 3rd-term Democratic Nomination was forged here.
1944: Harry S. Truman stayed here when he received Vice Presidential Nomination.
1952: Dwight D. Eisenhower stayed here during first Republican ballot.
![Page 70: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/70.jpg)
The Nines, The Luxury Collection, Starwood Hotels
Top 9 Floors - 331 Guest RoomsPortland’s First 5-Star Hotel
Lower 5 Floors is Macys Dept Store
Redevelopment of 1909 Meier & Frank Department Store
National Register of Historic Places
Opened Oct 2008 LEED Silver
Portland, Oregon
![Page 71: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/71.jpg)
Elysian / Waldorf Astoria
60 Stories on East Walton Street in the Gold Coast52 Private Residences
188 Room Waldorf Astoria Hotel
Constructed 2006-2010Renamed Waldorf Astoria Chicago February 1, 2012
AAA Five DiamondTripAdvisor.com Ranked # 1 Hotel in USA
Conde Nast Traveler Ranked Best Hotel in USA
Chicago
As of Feb 1, 2012:
Hotel rates: start at $395
Condo Sales up to $8 Million
Condo Rent: $16,000/month 3-Bed, 3.5-Bath, 3,747 Sq Ft
![Page 72: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/72.jpg)
12,000 Units over 12 Years
![Page 73: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/73.jpg)
Cool AirCool AirCool AirCool Air
Average 40% Less Piping
Installed Cost Savings $$$
Pump Energy Savings For Owner $$$
Reliable Operation
Occupant Comfort
LEED Credit Opportunities4 – Pipe
Performance With 2 Installed Pipes
Low Maintenance
Easy To Design
![Page 75: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/75.jpg)
Application:SureFlow
75
![Page 76: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/76.jpg)
FCU
ChillerChiller
FCUFCUFCU
Part Load Pump Controls
Standard Piping Method
76
![Page 77: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/77.jpg)
System Design Issues
• Chiller / Boiler Equipment Plant• Pumps Create Water Pressure Differential• Pipes Running To and From Each Unit• Valves – On/Off or Modulating• Balancing Valves – Flow Regulators• Strainers• Pressure Relief Valves• Variable Speed Drives on Pumps• Controls, DDC, Building Energy Management System• Installation Labor – vs. – 2/Pipe – vs. – 4/Pipe• Test & Balance • Maintenance
77
![Page 78: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/78.jpg)
Primary
Circuit Water
Flow
Integrated Circulator
Cycles on Thermostat
Demand
Thermostat
OFF
78
![Page 79: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/79.jpg)
79
![Page 80: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/80.jpg)
SureFlow
Average 40%
Less Piping
Less Core
Drills on
Renovation
Contractor
Savings
80
![Page 81: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/81.jpg)
• 30+ Years In Production
• Millions In Use
• Quiet Operation
• Chilled Water CERTIFIED
• Wet Rotor Cartridge Design
• Internal Flow Check Valve
• 200 PSI Rating
• Cycles On-Off (Thermostat
Controlled)
• Low Energy Consumer – 65 Watts
SureFlow Circulator – 1/40 HP
81
![Page 82: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/82.jpg)
Two Pipe Cooling
With Only One Installed Pipe
Chiller
FAN
COIL
FAN
COIL
FAN
COIL
FAN
COIL
FAN
COIL
FAN
COIL
FAN
COIL
FAN
COIL
82
![Page 83: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/83.jpg)
Two Pipe Heat & Cool
With Only One Installed Pipe
Chiller
FAN
COIL
FAN
COIL
FAN
COIL
FAN
COIL
Boiler
83
![Page 84: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/84.jpg)
42ºF 46.6ºF46.6ºF 48.6ºF
44.4ºF
Chiller
Off
52.1ºF
Central Pump Is NOT Responsible For Pressure Drop Of Coil Or Valve Packages
1 Ton13177t 9954s
1 Ton
12052t 9519s
1 Ton
14424t 10448s
1 Ton
SureFlow System Pumping
84
![Page 85: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/85.jpg)
7.5 Tons Block / 10 Tons Peak = 75% Diversity Ratio
Block vs Peak Load Analysis
85
![Page 86: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/86.jpg)
1839 US Tariff Building –
General Post Office
Owner: US Department of
Interior – Park Service
Lease: Kimpton Hotel &
Restaurant Group
232 Rooms – AAA 4
Diamond
Opened Summer 2002
SureFlow Fan Coils
Hotel MonacoWashington DC
SureFlow Installation - Case Study
86
![Page 87: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/87.jpg)
Application:SureFlow
87
![Page 88: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/88.jpg)
Standard Piping Method
ChillerChiller
FCUFCUFCUFCU
88
![Page 89: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/89.jpg)
FCU
ChillerChiller
FCUFCUFCU
Primary-Secondary Pumping
Standard Piping Method
89
![Page 90: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/90.jpg)
FCU
ChillerChiller
FCUFCUFCU
Part Load Pump Controls
Standard Piping Method
90
![Page 91: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/91.jpg)
System Design Issues
• Chiller / Boiler Equipment Plant• Pumps Create Water Pressure Differential• Pipes Running To and From Each Unit• Valves – On/Off or Modulating• Balancing Valves – Flow Regulators• Strainers• Pressure Relief Valves• Variable Speed Drives on Pumps• Controls, DDC, Building Energy Management System• Installation Labor – vs. – 2/Pipe – vs. – 4/Pipe• Test & Balance • Maintenance
91
![Page 92: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/92.jpg)
Primary
Circuit Water
Flow
Integrated Circulator
Cycles on Thermostat
Demand
Thermostat
OFF
92
![Page 93: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/93.jpg)
Cool AirCool AirCool AirCool Air
Primary
Circuit Water
Flow
Integrated Circulator
Cycles on Thermostat
Demand
Thermostat
ON
93
![Page 94: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/94.jpg)
Design Considerations: Piping Circuits - Diverting
Series
One-pipe diverting series circuits – “when coupled with
compound pumping systems, series circuits can be
applied to multiple control zones on larger commercial
or institutional systems.”
2008 ASHRAE Handbook
HVAC Systems and Equipment
Chapter 12.94
![Page 95: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/95.jpg)
95
![Page 96: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/96.jpg)
SureFlow
Average 40%
Less Piping
Less Core
Drills on
Renovation
Contractor
Savings
96
![Page 97: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/97.jpg)
• 30+ Years In Production
• Millions In Use
• Quiet Operation
• Chilled Water CERTIFIED
• Wet Rotor Cartridge Design
• Internal Flow Check Valve
• 200 PSI Rating
• Cycles On-Off (Thermostat
Controlled)
• Low Energy Consumer – 65 Watts
SureFlow Circulator – 1/40 HP
97
![Page 98: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/98.jpg)
Two Pipe Cooling
With Only One Installed Pipe
Chiller
FAN
COIL
FAN
COIL
FAN
COIL
FAN
COIL
FAN
COIL
FAN
COIL
FAN
COIL
FAN
COIL
98
![Page 99: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/99.jpg)
Two Pipe Heat & Cool
With Only One Installed Pipe
Chiller
FAN
COIL
FAN
COIL
FAN
COIL
FAN
COIL
Boiler
99
![Page 100: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/100.jpg)
Four Pipe Heat & Cool
With Only Two Installed Pipes
Chiller
FAN
COIL
Boiler
FAN
COIL
FAN
COIL
FAN
COIL
100
![Page 101: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/101.jpg)
42ºF 46.6ºF46.6ºF 48.6ºF
44.4ºF
Chiller
Off
52.1ºF
Central Pump Is NOT Responsible For Pressure Drop Of Coil Or Valve Packages
1 Ton13177t 9954s
1 Ton
12052t 9519s
1 Ton
14424t 10448s
1 Ton
SureFlow System Pumping
101
![Page 102: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/102.jpg)
Coil Pressure Drop is Redesigned to Match
Circulator Pump Curve
102
![Page 103: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/103.jpg)
8 Degree Loop Delta-T = 3 GPM per Ton
Cooling Loop Water Temperature
103
![Page 104: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/104.jpg)
10 Tons Peak x 3 GPM per Ton = 30 GPM1-1/2” L Copper @ 30GPM = 5.43 fps = 7.55 ftpd/100ft
2” L Copper Pipe @ 30GPM = 3.14 fps = 2.02 ftpd/100ft
SureFlow Peak Load Design
104
![Page 105: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/105.jpg)
7.5 Tons Block / 10 Tons Peak = 75% Diversity Ratio
Block vs Peak Load Analysis
105
![Page 106: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/106.jpg)
With 42F Supply, 3 GPM Per Ton, 75% RatioMax Actual Water Temperature = 48F
BLOCK LOAD RATIO
Design For Diversity
106
![Page 107: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/107.jpg)
With 44F Supply, 3 GPM Per Ton, 75% RatioMax Actual Water Temperature = 50F
BLOCK LOAD RATIO
Warmer Supply Temperature?
107
![Page 108: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/108.jpg)
10,000 Units over 10 Years
108
![Page 109: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/109.jpg)
1839 US Tariff Building –
General Post Office
Owner: US Department of
Interior – Park Service
Lease: Kimpton Hotel &
Restaurant Group
232 Rooms – AAA 4
Diamond
Opened Summer 2002
SureFlow Fan Coils
Hotel MonacoWashington DC
SureFlow Installation - Case Study
109
![Page 110: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/110.jpg)
Fernando Garcia, P.E.
Vice President
CTA Consulting Engineers Inc.
Rockville, MD
(301) 637-0058
110
![Page 111: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/111.jpg)
Chicago Blackstone Renaissance Hotel
636 South Michigan332 Rooms
Restoration of 1908 HotelOpened Fall 2007
Location of the famous “Smoke Filled
Rooms” where Warren G. Harding
was chosen as the Republican
nominee for President in June 1920.
Franklin Delano Roosevelt’s 3rd-term
Democratic Nomination was forged
in 1940.
Harry S. Truman stayed when he
received 1944 Vice Presidential
Nomination.
Dwight D. Eisenhower stayed during
first Republican ballot in 1952. 111
![Page 112: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/112.jpg)
Portland, OregonThe Nines Hotel
Part of The Luxury Collection, Starwood Hotels & ResortsTop 9 Floors - 331 Rooms
Lower 5 floors is Macy’s
Redevelopment of 1909 Meier & Frank Department Store
National Register of Historic Places
Opened October 16, 2008LEED Silver
112
![Page 113: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/113.jpg)
New Orleans Monaco Hotel
250 Units
Historic 1926 Masonic Temple Lodge
June 2001 Conversion to a 4-Star Luxury
Hotel
Kimpton Sold to Dimension Development Co.
Reopened 2007 as the Hilton Saint
Charles
Humidity Kept Under Control
113
![Page 114: SureFlow Presented by: Ron Porter LEED AP IEC Oklahoma City Copyright 2012](https://reader038.vdocuments.site/reader038/viewer/2022103121/56649c775503460f9492c4e2/html5/thumbnails/114.jpg)
Cool AirCool AirCool AirCool Air
Average
40% Less
Piping
Installed Cost
Savings $$$
Pump
Energy
Savings For
Owner $$$
Reliable
Operation
Occupant
Comfort
LEED Credit
Opportunitie
s
4 – Pipe
Performance
With 2 Installed
Pipes
Low
Maintenance
Easy To
Design
114