3. WIRING DIAGRAM - iPFC
PROGRAMMING GUIDEPower Factor Controller (iPFC)
www.elmeasure.com
1. UNIQUE FEATURES
STAR (Wye)/ DELTA / Single CT Programmable.
Auxiliary supply of 180 - 300V AC/DC.
CT ratio programmable including CT secondary
3 phase measurement
Capacitor value programmable
6/8/12 stages optional
Automatic or Manual Control
Four Quadrant Operation
Fault Detection
Intelligent Power Factor Controlling based on the capacitor bank
switching history
PG/PFC/V7/0918
2. KEY FUNCTIONS
Key In SET (Programming) mode In RUN (Measurement) mode
Right To select the value and to accept the value
NO ACTION
DOWN To edit the value/system typesdownward in edit mode and scrollthrough the parameters.
To scroll pages in DOWNWARDdirection and view differentparameters
UP To edit the value/system type up-ward in edit mode and scroll through the parameters.
To scroll pages in upward direction and view different parameters.
Step Actions Display Reads Range/Options/Comments
1 Press RIGHT & UP keys together to enter SETUP
4. ENTERING CONFIGURATION (SETUP) MODE To configure the setup parameters in PFC meter through front panel keys, the
following steps can be followed.
2 Press DOWN key (Password)
with first digit “0” blinking.
3
(default/factory set).
Press UP key once to increment the first digit to “1”.
4 Press RIGHT key four times to accept the password.
(Displays last programmed type)
5 Press RIGHT key to selectrequired system type
(selected mode blinks)
If any other password is already set move up and down key to set the right password
Defines the power system configuration.Options: STAR /DELTA/1Ph
6
7
Press RIGHT key to accept
V - A - Hz - W - PF - VAR - Wh
C1 C2 C3 C4 C5 C6 C7 C8
C9 C10 C11 C12
INTELLIGENT PFC
PFC12 08 06
CLR PRG
3Ø Measurements
Star
co
nn
ecti
on
(3E
)3P
has
e 4w
ire
syst
em
AUX
S1 S2
S1 S2
S1 S2
R
Y
B
N
LOADRECEIVEDDELIVEREDLINE
RS 485
NVBVYVRABAYARS1 S2 S1 S2 S1 S2
Control Wiring : Control Wiring for Capacitor Switching Section
1 2 3 4 5 6 7 8 9
COM
1 2 3 4 5 6 7 8
K8 K6 K4 K2
K7 K5 K3 K1
FreewheelingDiode 1N4007
DC supplyTo Contactor coil
AC supplyTo Contactor coil
RC Snubber R: 330 /3W.c:0.1 F/1kV.
iPFC
Ωμ
+
-
HO & Unit -1 :
Plot NO.: 47-P, Hardware Park, Huvinayakanahalli KIADB Jala hobli, Bengaluru North, Yelahanka Taluk, Bengaluru District, Karnataka - 562 149 INDIA.
Unit -2 : Goutham Garden, No.4, Veerapandi, Coimbatore - 641 019 INDIAT : 0422 2697200. TF : 0422 2695200. E : [email protected]
Sales Offices : BENGALURU CHENNAI COIMBATORE MUMBAI DELHI HYDERABAD USA UAE
Press DOWN key
(CT Primary)(5.000 – default/factory set)
Program range for CT Primary: 0.5A to 99kA
+91 639-1010-320
+++ + + +
+ + +-
VR, VY, VB PT(op�onal)
RS 485
R
Y
B
N
AUX
S1 AR S2
LINE DELIVERED RECEIVED LOAD
1C
T C
on
nec
�o
n
UTILITYMETER
iPFC CAPACITORPANEL
INCOMMER DIAGRAM - iPFC
Del
ta c
on
nec
tio
n (
2E)
3Ph
ase
3 w
ire
syst
em
AUX
S1 S2
S1 S2
LOADRECEIVEDDELIVEREDLINE
RS 485
R
Y
B
N
NVBVYVRABAYARS1 S2 S1 S2 S1 S2
For single CTconnection. Connect3Phase voltage &any one of thecurrent phase.
Press UP/DOWN key to select the required option
36
Follow the procedure as described in steps 28 to 30.
Press DOWN key Capacitor VAR value for C7
37
Follow the procedure as described in steps 28 to 30.
Press DOWN key Capacitor VAR value for C8
38
Follow the procedure as described in steps 28 to 30.
Press DOWN key Capacitor VAR value for C9
39
Follow the procedure as described in steps 28 to 30.
Press DOWN key Capacitor VAR value for C10
40
Follow the procedure as described in steps 28 to 30.
Press DOWN key Capacitor VAR value for C11
44 Press DOWN key 2nd Analog input parameter
45 Press DOWN key Range :0.001 to 9999M
41
Follow the procedure as described in steps 28 to 30.
Press DOWN key Capacitor VAR value for C12
42 Press DOWN key 1st Analog input parameter
43 Press DOWN key Range :0.001 to 9999M
11 Press DOWN key togo to the next parameter.
(CT Secondary)(5.000 -default/factory set)Repeat steps 8 to 10 toChange the settings.
Range: 0.5A to 6A. If valueset is above this limit, itreturns to the maximumCT sec value acceptable.
30
Decimal point blinking. Can be set at appropriate location using UP/DOWN key. Ascertain the correct scale (Kilo/Mega) is selected. Kilo/Mega is placed on the right hand side of the display as K/M. Press RIGHT key to accept the edited value.
Press RIGHT key. Eg: To set 11.00KVAR Set first four digits (1100) as explained above press UP/DOWN key to place decimal point at appropriate location. Use UP/DOWN KEY. Letter K/M will indicate the Kilo/Mega.
31
Follow the procedure as described in steps 28 to 30.
Press DOWN key Capacitor VAR value for C2
32
Follow the procedure as described in steps 28 to 30.
Press DOWN key Capacitor VAR value for C3
33
Follow the procedure as described in steps 28 to 30.
Press DOWN key Capacitor VAR value for C4
34
Follow the procedure as described in steps 28 to 30.
Press DOWN key Capacitor VAR value for C5
35
Follow the procedure as described in steps 28 to 30.
Press DOWN key Capacitor VAR value for C6
46 Press DOWN key Defines the baud rate. Option : 1200,2400, 4800, 9600, 19.20k
(baud rate).Communication speed. (9600 -default/factory set)
47 Press DOWN key Internal communication error check EUEn (even)/odd(odd)/no(no parity) Comment: Can change the option using UP & DOWN keys.
48 Press DOWN key Defines the (ID) communications identification number. Option: 1-247
(Device ID)
49 Press DOWN key Caution : If password other than the default or user defined is used, meter will reject programming.CAUTION: Password can only be reset and recalibrated at factory.
Range:1000 -9999. Password user definable.
50 Starting current value to be displayed in the meter Range: (0.2 to 10 % of full scale)
Press DOWN key
12 Press DOWN key
(Method of VA Selection).
Arithmetic (Arith), Vector harmonics(UEC.H). Vector (VECtor) can be selected using UP/DOWN key.
13 Press DOWN key
(no.of relays)
Range: 1 to 12 (Depends on the No. of stages)
14 Press DOWN key
(Control type)
Auto/Manual
Press DOWN key Relay on time. Range: 4 to 999 seconds
Press DOWN key Relay off time. Range: 4 to 999 seconds
Press DOWN key Discharge time. Range: 4 to 999 seconds
16 Press DOWN key PF limit – Capacitive (leading PF). Range: 0.800 to 0.990
17
18
19
Press DOWN key Average time. Range: 2 to 200 seconds
20
15 Press DOWN key PF limit – Inductive(lagging PF).Range: 0.800 to 0.990
Press DOWN key Over voltage. Range : 48 to 999KV
21
Press DOWN key Over current. Range: 0.050 to 99KA
22 Press DOWN key Under voltage. Range: 20 to 999KV
27
23
Press DOWN key Under current. Range: 0.050 to 99KA
24
Press DOWN key Over harmonics. Range: 1% to 200%
25
Press DOWN key Alarm time delayRange: 3 to 99 seconds
26
Press DOWN key Capacitor VAR value for C1.
Press RIGHT key to setthe Capacitor VAR value for C1
First digit blinking can be edited using UP/DOWN key.
28
29
Second digit blinking, can be edited using UP/DOWN key. Press RIGHT key to accept the edited value. Continue the same method till fourth digit.
Press RIGHT key to accept the edited value for first digit.
Range: 500VAR to 9999MVAR
8 Press RIGHT key toset the CT Primary value
(CT Primary)First digit blinking can beedited using UP/DOWN key.
9 Press RIGHT key toset accept the edited valuefor first digit. (CT Primary)
Second digit blinking can beedited using UP/DOWN key.Press RIGHT key to accept theedited value. Continue thesame method till forth digit.
10 Press RIGHT key.
(CT Primary)Decimal point blinking.Can be set at appropriatelocation using UP/DOWN key.Ascertain the correct scale(Kilo/Mega/Giga) is selected.Kilo/Mega/Giga is placed onthe right hand side of thedisplay as K/M/G. Press RIGHTkey to accept the edited value.
Eg: To set 55.00kASet first four digits (5500) asexplained above press UP/DOWN key to place decimalpoint at appropriate locationUSE UP/DOWN KEY LetterK/M/G will indicate the Kilo/Mega/Giga.
C1 - ON
C2 - ON
C3 - ON
C4 - ON
C5 - ON
C6 - ON
C7 - ON
C8 - ON
C9 - ON
C10 - ON
C11 - ON
C12 - ON
Capacitor Bank 1 ON / Relay 1 ON status
Capacitor Bank 2 ON / Relay 2 ON status
Capacitor Bank 3 ON / Relay 3 ON status
Capacitor Bank 4 ON / Relay 4 ON status
Capacitor Bank 5 ON / Relay 5 ON status
Capacitor Bank 6 ON / Relay 6 ON status
Capacitor Bank 7 ON / Relay 7 ON status
Capacitor Bank 8 ON / Relay 8 ON status
Capacitor Bank 9 ON / Relay 9 ON status
Capacitor Bank 10 ON / Relay 10 ON status
Capacitor Bank 11 ON / Relay 11 ON status
Capacitor Bank 12 ON / Relay 12 ON status
10. Display of Parameters:
Power Factor Y Phase
Power Factor B PhaseAverage Power Factor
VAr R PhaseTotal VAR
VAr Y PhaseVoltage line to line
Current RPhaseVoltage line to Neutral
VAr B PhaseVoltage RY Phase
Under VoltageVoltage YB Phase
Over VoltageVoltage BR Phase
Over CurrentVoltage R phase
Over Compensa�onFrequency
Under Compensa�onWa�s Total
Reverse AmpsPower Factor
Over HarmonicsPower Factor R Phase
Under CurrentCurrent Average
Display Meaning Meaning Display
9. LED INDICATION
LED Status
K - ON
M - ON
K & M - ON
Meaning
Kilo
Mega
Giga
Direct readingK & M - OFF
Lag/Minus
Communica�on ON
Alarm On
- - ON
- ON
- ON
8. Manual Mode:Press UP and DOWN Keys together, and 'CLEAr' (Clear) is shown on the display. Enter the Password (default password is 1000. Set up and clear has the same password) and it will display “CLr.I”. Press DOWN Key and meter displays “Manual”. Once manual selected it will display C1 OFF or C1.On (depends on whether the capacitor is ON or OFF). Press RIGHT key to make it ON or OFF. Continue this for other no. of relays programmed. Once the required no. of relays are switched ON or OFF display will prompt to “CLEAr.”or Manual . When display prompts to CLEAr press DOWN key and 'n' will display and Press the RIGHT key to come out.
7. Enabling and Disabling of Auto scrolling:Enabling auto scrolling: Press UP key continuously for 5 seconds or until display shows EnbL Au for upward scrolling. Press Down key continuously for 5 seconds or until display shows EnbL Au for downward scrolling.
Disabling auto scrolling: Press any key (RIGHT/UP/DOWN), display show dSbL Au and returns to normal mode.
6. Clearing the Integrator:To Clear parameters from the front panel, Press UP and DOWN Keys together, and 'CLEAr' (Clear) is shown on the display. Enter the Password (default password is 1000. Set up and clear has the same password) and it will display “CLr.I”. Press UP / DOWN Key for selecting CLr.I (Integ Clear). Once the parameter to be cleared is selected it will prompt to 'y' or 'n'. Press UP and DOWN key for changing 'y' or 'n' and Press the RIGHT key to do the operation.
5. The List of parameters can be configured and the range is given below
Default setup Range / Options
UEC.H Arith (Arithmetic) / Vector/ VEC.H (vector harmonics)
VA selection (UA)
Auto/ManualAutoControl type (C.t)6
5.000 0.5A - 99kACT Primary (CP)25.000 0.5A - 6ACT SECondary (CS3
Sl.No. Parameter
STAR STAR/ DELTAConnection mode(EL)1
Average PF page to be displayed in the meter. Options: Enable/Disable
51 Press DOWN key
If “n”(no) is selected then Meter enters into RUN mode without memorizing any edited Values in the setup
Display returns to Run mode.
Once the required parameter is programmed press the DOWN key continuously till it reaches SAVE page directly.
57 Press DOWN key
58 Press RIGHT key to store the changes done
Under Compensation condition to be displayed in the meter. Options: Enable/Disable
52 Press DOWN key
Over Compensation condition to be displayed in the meter. Options: Enable/Disable
53 Press DOWN key
Under Amps condition to be displayed in the meter. Options: Enable/Disable
54 Press DOWN key
Over Amps condition to be displayed in the meter. Options: Enable/Disable
55 Press DOWN key
56 Press DOWN key Other warnings to be displayed in the meter. Options: Enable/Disable
12.000 1-6/8/12No.of Relays (nr)5
0.950 0.800 to 0.990PF lag(Lg)
Dimension Bezel: 96 x 96 mm (Depth 69mm behind Bezel)
Panel Cutout:+2 +290 x 90 mm-0 -0
11. Mechanical Specification:
+290 mm-0
Over current(o.A)
Under current(u.A)
Over Harmonics(O.H)
Alarm delay (A.d)
6.000
0.200
200.0
3.000
0.050 to 99.00 KA
0.050 to 99.00 KA
1 to 200%
3 to 99 seconds
Switch OFF time(oF) 20.00 4 to 999 seconds
Discharge time(t.d) 50.00 4 to 999 secondsAverage Time(t.A) 15.00 2 to 200 seconds
Over voltage(o.u) 498.0 48 to 999KV
Under voltage(uu) 48.00 20 to 999KV
Capacitor(C2) 1000.0 500 VAR to 9999 MVAR
Switch ON time(on) 20.00 4 to 999 seconds
Capacitor(C1) 1000.0 500 VAR to 9999 MVAR (default 1000 VAR = 1 kVAR)
0.950 0.800 to 0.990PF lead(Ld)
Capacitor(C4
Capacitor(C5)
Capacitor(C6)
Capacitor(C7)
Capacitor(C8)
Capacitor(C9)
Capacitor(C10)
Capacitor(C11)
Capacitor(C12)
1000.0
1000.0
1000.0
1000.0
1000.0
1000.0
1000.0
1000.0
1000.0
500 VAR to 9999 MVAR
500 VAR to 9999 MVAR
500 VAR to 9999 MVAR
500 VAR to 9999 MVAR
500 VAR to 9999 MVAR
500 VAR to 9999 MVAR
500 VAR to 9999 MVAR
500 VAR to 9999 MVAR
500 VAR to 9999 MVAR
Analog input(An) disA Disable Analog input
Analog input full scale value 1200 0.001 to 9999M
Analog input(An) disA Disable Analog input
Analog input full scale value(An) 1200 0.001 to 9999M
Baud rate(b.A) 9600 1200 to 19.2k
Parity Even Even/ Odd/ noDevice Id (dE) 1.000
Password (PW) 1000 1000 to 9999
Starting Current(St) 0.400 0.2 to 10 %
Average PF (AP)
Under Compensation(UC)
Over Compensation (OC)
Under Amps(UA)
Over Amps(OA)
Other Warnings(OW)
EnbL Enable/Disable
Enable/Disable
Enable/Disable
Enable/Disable
Enable/Disable
Enable/Disable
21 Capacitor(C3) 1000.0 500 VAR to 9999 MVAR
(An)
(PA)
EnbL
EnbL
EnbL
EnbL
EnbL
4
87
10
11
12
13
14
15
16
17
18
20
9
19
22
23
24
25
26
27
28
29
30
3132
3334
35
3637
38
3940
41
43
44
42
45
69 m
m