Supplemental Dehumidification For Humid Climates ACI Conference, Denver, May 2, 2013 Armin Rudd ACI Conference – Supplemental Dehumidification 2 May 2013, Denver 2 Overview of Results From ACI Conference – Supplemental Dehumidification 2 May 2013, Denver 3 What is Supplemental Dehumidification? Moisture removal, supplemental to the cooling system, when there is no need for cooling. ACI Conference – Supplemental Dehumidification 2 May 2013, Denver 4 When is it needed? Mostly when the house is floating between cooling and heating setpoints Spring/Fall swing seasons and summer shoulder months Some winter conditions in hot-humid climates Some summer nights and rainy periods in hot- humid climates and coastal warm-humid climates Affordable Comfort Inc. Conference Supplemental Dehumidification for Humid Climates May 2, 2013 Rudd © buildingscience.com 1 of 8

Upload: others

Post on 02-Oct-2020

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Supplemental Dehumidification For Humid Climates · 2013. 5. 2. · ACI Conference – Supplemental Dehumidification 2 May 2013, Denver 2 ... humidity levels in homes with conventional

Supplemental Dehumidification For Humid Climates

ACI Conference, Denver, May 2, 2013

Armin Rudd

ACI Conference – Supplemental Dehumidification 2 May 2013, Denver 2

Overview of Results From

ACI Conference – Supplemental Dehumidification 2 May 2013, Denver 3

What is Supplemental Dehumidification?

Moisture removal, supplemental to the cooling system, when there is no need for cooling.

ACI Conference – Supplemental Dehumidification 2 May 2013, Denver 4

When is it needed?

  Mostly when the house is floating between cooling and heating setpoints

  Spring/Fall swing seasons and summer shoulder months

  Some winter conditions in hot-humid climates   Some summer nights and rainy periods in hot-

humid climates and coastal warm-humid climates

Affordable Comfort Inc. Conference Supplemental Dehumidification for Humid Climates May 2, 2013

Rudd © buildingscience.com 1 of 8

Page 2: Supplemental Dehumidification For Humid Climates · 2013. 5. 2. · ACI Conference – Supplemental Dehumidification 2 May 2013, Denver 2 ... humidity levels in homes with conventional

ACI Conference – Supplemental Dehumidification 2 May 2013, Denver 5

Shade Plot of Humidity Bins

Shades of Gray

0 – below 55% 1 – 55-60% 2 – 60-65% 3 – 65-70% 4 – 75-80% 5 – above 80%

Space Conditions (Miami, HERS100, Conv. Sys, Exhaust vent)

ACI Conference – Supplemental Dehumidification 2 May 2013, Denver 7

What is a good metric for determining the need?

Hours above 60% relative humidity

ACI Conference – Supplemental Dehumidification 2 May 2013, Denver 8

1449-RP Conventional Cooling System

Affordable Comfort Inc. Conference Supplemental Dehumidification for Humid Climates May 2, 2013

Rudd © buildingscience.com 2 of 8

Page 3: Supplemental Dehumidification For Humid Climates · 2013. 5. 2. · ACI Conference – Supplemental Dehumidification 2 May 2013, Denver 2 ... humidity levels in homes with conventional

ACI Conference – Supplemental Dehumidification 2 May 2013, Denver 9

1449-RP Conventional Cooling System

ACI Conference – Supplemental Dehumidification 2 May 2013, Denver 10

Conventional Cooling System Runtime 2-spd systems for HERS 70 and 50

ACI Conference – Supplemental Dehumidification 2 May 2013, Denver 11

Hours > 60% RH by HERS Index and Climate Conventional Cooling System and Mechanical Ventilation

ACI Conference – Supplemental Dehumidification 2 May 2013, Denver 12

Duration of Events > 60% RH

Affordable Comfort Inc. Conference Supplemental Dehumidification for Humid Climates May 2, 2013

Rudd © buildingscience.com 3 of 8

Page 4: Supplemental Dehumidification For Humid Climates · 2013. 5. 2. · ACI Conference – Supplemental Dehumidification 2 May 2013, Denver 2 ... humidity levels in homes with conventional

ACI Conference – Supplemental Dehumidification 2 May 2013, Denver 13

Impact of Duct Location

HERS  50 HERS  70

ACI Conference – Supplemental Dehumidification 2 May 2013, Denver 14

Impact of Duct Location

Total Space Conditioning Cost Reduction Impact of Moving Ducts

from Attic to the Conditioned Space

Elevated Indoor Relative Humidity Impact of Moving Ducts from Attic to the

Conditioned Space (due to sensible cooling load reduction)

ACI Conference – Supplemental Dehumidification 2 May 2013, Denver 15

Comparing High Humidity Levels with Different Ventilation Options

ACI Conference – Supplemental Dehumidification 2 May 2013, Denver 16

Effect of Enhanced Cooling Strategy Low airflow (200 cfm/ton) and Overcooling (2oF)

Affordable Comfort Inc. Conference Supplemental Dehumidification for Humid Climates May 2, 2013

Rudd © buildingscience.com 4 of 8

Page 5: Supplemental Dehumidification For Humid Climates · 2013. 5. 2. · ACI Conference – Supplemental Dehumidification 2 May 2013, Denver 2 ... humidity levels in homes with conventional

ACI Conference – Supplemental Dehumidification 2 May 2013, Denver 17

Mode 1: “normal cooling” 350 cfm/ton Mode 2: “cool to dehumidify” 280 cfm/ton only with a call for cooling Mode 3: “super dehumidify” 210 cfm/ton for 10 minutes on / 10 minutes off

limited to 3oF overcooling

However, it has its limitations

ACI Conference – Supplemental Dehumidification 2 May 2013, Denver 18

Mode 1: “normal cooling” 350 cfm/ton Mode 2: “cool to dehumidify” 280 cfm/ton only with a call for cooling Mode 3: “super dehumidify” 210 cfm/ton for 10 minutes on / 10 minutes off

limited to 3oF overcooling

ACI Conference – Supplemental Dehumidification 2 May 2013, Denver 19

How much supplemental dehumidification is needed?

ACI Conference – Supplemental Dehumidification 2 May 2013, Denver 20

Houston Field Study

Variation in occupant behaviors impacting internal generation has a big impact

Affordable Comfort Inc. Conference Supplemental Dehumidification for Humid Climates May 2, 2013

Rudd © buildingscience.com 5 of 8

Page 6: Supplemental Dehumidification For Humid Climates · 2013. 5. 2. · ACI Conference – Supplemental Dehumidification 2 May 2013, Denver 2 ... humidity levels in homes with conventional

ACI Conference – Supplemental Dehumidification 2 May 2013, Denver 21

Supplemental DH Results – HERS 85, 60% setpt

ACI Conference – Supplemental Dehumidification 2 May 2013, Denver 22

Supplemental DH Results – HERS 85, 50% setpt

ACI Conference – Supplemental Dehumidification 2 May 2013, Denver 23

Supplemental Dehumidification Energy and Cost

ACI Conference – Supplemental Dehumidification 2 May 2013, Denver 24

Supplemental DH Energy, HERS 85 - Min/Max/Avg

Affordable Comfort Inc. Conference Supplemental Dehumidification for Humid Climates May 2, 2013

Rudd © buildingscience.com 6 of 8

Page 7: Supplemental Dehumidification For Humid Climates · 2013. 5. 2. · ACI Conference – Supplemental Dehumidification 2 May 2013, Denver 2 ... humidity levels in homes with conventional

ACI Conference – Supplemental Dehumidification 2 May 2013, Denver 25

Supplemental DH Energy and Cost – HERS 50

ACI Conference – Supplemental Dehumidification 2 May 2013, Denver 26

Lessons Learned

  Periods of high relative humidity mostly occur at mild conditions in the winter and swing seasons when there is little or no need for sensible cooling. Humidity is rarely out of control during the main summer periods.

  The number of hours above a certain humidity threshold (say 60% RH) is good metric for comparing the humidity control performance of different systems. A similar result is found when analyzing the duration of high humidity events.

  Moving ducts from the attic to the conditioned space saves energy but increases space humidity levels in hot-humid climates. The reduction in sensible heat gains is greater than the reduction in latent loads, resulting in a mix of sensible and latent loads that increases space humidity levels in homes with conventional air conditioning systems.

ACI Conference – Supplemental Dehumidification 2 May 2013, Denver 27

Lessons Learned

  In a multi-home field study in Houston, TX, measured supplemental dehumidification energy consumption from two mechanically ventilated homes was 209 kWh/yr for a representative home with a stand-alone dehumidifier and 463 kWh/yr for another representative home with a ducted dehumidifier.

  The ducted dehumidifier was more efficient, and the homes had similar temperature and relative humidity control, but variability in occupant behaviors has a strong impact on internal moisture generation which has a strong impact on supplemental dehumidification requirements.

ACI Conference – Supplemental Dehumidification 2 May 2013, Denver 28

Lessons Learned (cont.)

  Detailed simulations showed that a number of humidity control solutions can be effective in hot-humid climates.

  The most effective solutions, having relatively low operating cost and essentially eliminating indoor humidity above 60% RH, were:   full condensing modulating reheat integrated with the central

cooling system   ducted dehumidifier   stand-alone dehumidifier with central system mixing   condenser regenerated desiccant dehumidifier

  About 170 kWh/yr could be expected for a HERS 50 house (having ducts inside conditioned space) with a 60% RH setpoint.

  About five times that, and more, could be expected with a 50% RH setpoint.

Affordable Comfort Inc. Conference Supplemental Dehumidification for Humid Climates May 2, 2013

Rudd © buildingscience.com 7 of 8

Page 8: Supplemental Dehumidification For Humid Climates · 2013. 5. 2. · ACI Conference – Supplemental Dehumidification 2 May 2013, Denver 2 ... humidity levels in homes with conventional

ACI Conference – Supplemental Dehumidification 2 May 2013, Denver 29

Lessons Learned (cont.)

  A close second was central cooling system with subcooling reheat but it showed more elevated RH hours.

  A more distant third place was enhanced cooling controls for 2oF over-cooling and lower airflow (200 cfm/ton) activated at 50% RH and above.

  Two-speed and variable speed systems did little to reduce hours of elevated relative humidity in hot-humid climates unless coupled with the enhanced cooling methods listed above.

  An Energy Recovery Ventilators by itself increased hours above 60% RH in hot-humid climates, however, when coupled with supplemental dehumidification having a 50% RH setpoint an ERV reduced supplemental dehumidification energy needed

ACI Conference – Supplemental Dehumidification 2 May 2013, Denver 30

Lessons Learned (cont.)

  When controlling to 60% relative humidity, the required capacity for supplemental dehumidification in average homes in hot-humid climates is not large – about 1.5 lb/h, or that of a typical 40 to 50 pint/day unit.

  Expected cost to operate such a unit at 60% RH is less than $50 yr depending on house efficiency level

  Expected cost to operate such a unit at 50% RH is less than $175/yr depending on house efficiency level

  Finally, supplemental dehumidification, in and of itself, does not save energy, rather, it is justified by enabling the energy savings from dramatically reduced sensible cooling loads in high-performance homes in hot-humid climates.

Web Access to 1449-RP Results http://cloud.cdhenergy.com/rp1449/

Web Access to 1449-RP Results http://cloud.cdhenergy.com/rp1449/

Affordable Comfort Inc. Conference Supplemental Dehumidification for Humid Climates May 2, 2013

Rudd © buildingscience.com 8 of 8