SUBMITTAL DATA SHEET
SINGLE PACKAGE AIR CONDITIONERS ANDGAS/ELECTRIC HEAT UNITS, 3 THROUGH 12-1/2 TONSMODELS: ZH/ZJ/ZR/ZT037-150, ZF078-150, ZB078-150
JOB NAME: LOCATION:
PURCHASER: ORDER NO:
ENGINEER:
SUBMITTED TO: FOR: REF: APPROVAL: CONSTRUCTION:
SUBMITTED BY: DATE:
UNIT DESIGNATION: SCHEDULE NO. MODEL NO.
COOLING PERFORMANCE
TOTAL CAPACITY- - - - - - - - - - - - - - _____ MBH
SENSIBLE CAPACITY - - - - - - - - - - - _____ MBH
OUTDOOR DESIGN TMP. _________ °F DB/WB
TOTAL SUPPLY AIR - - - - - - - - - - - - _____ CFM
TEMP. OF AIR ENTERINGEVAPORATOR COIL - - - - - - - - - - - - - - _____ °F
POWER INPUT REQ. - - - - - - - - - - - - - _____ KW(LESS BLOWER MOTOR)
HEATING PERFORMANCE
ELECTRIC HEAT - - - - - - - - - - - - - - - - _____ KW
GAS-FIRED INPUT CAP. - - - - - - - - - _____ MBH
SUPPLY AIR BLOWER PERFORMANCE
TOTAL SUPPLY AIR - - - - - - - - - - - - _____ CFM
EXT. STATIC PRESS. - - - - - - - - - - - _____ IWG
BLOWER SPEED- - - - - - - - - - - - - - - - ____ RPM
POWER OUTPUT REQ. - - - - - - - - - - _____ BHP
MOTOR RATING - - - - - - - - - - - - - - - - _____ HP
POWER INPUT REQ. - - - - - - - - - - - - - _____ KW
ELECTRICAL DATA
POWER SUPPLY - - - - - - - - - - - - - - -__________
TOTAL UNIT AMPACITY - - - - - - - - _____ AMPS
MAX. OVERCURRENT DEVICE__ FUSE __ BREAKER - - - - - - - - - _____ AMPS
TOTAL UNIT WEIGHT
INCLUDING FACTORY- INSTALLEDOPTIONS- - - - - - - - - - - - - - - - - - - - - _____ LBS
Johnson Controls Ducted Systems 335691-YSD-M-0320
![Page 2: SUBMITTAL DATA SHEET · submittal data sheet single package air conditioners and gas/electric heat units, 3 through 12-1/2 tons models: zh/zj/zr/zt037-150, zf078-150, zb078-150](https://reader033.vdocuments.site/reader033/viewer/2022051811/601db64bfe63d00cb5115123/html5/thumbnails/2.jpg)
335691-YSD-M-0320
3 thru 4 Ton ZH/ZJ, 3 Ton ZR (See Physical Dimensions table for exact models)
Ø 25.31
59.00
15.51
29.75
59
LEFT
11 3/8
21 3/16
89
27 5/16
4 3/16FRONT
See detail A for gas inlet
A
See detail B for drain location
B
C D EF
29.52
2 Johnson Controls Ducted Systems
![Page 3: SUBMITTAL DATA SHEET · submittal data sheet single package air conditioners and gas/electric heat units, 3 through 12-1/2 tons models: zh/zj/zr/zt037-150, zf078-150, zb078-150](https://reader033.vdocuments.site/reader033/viewer/2022051811/601db64bfe63d00cb5115123/html5/thumbnails/3.jpg)
335691-YSD-M-0320
3, 4, and 5 Ton ZT, 5 Ton ZH/ZJ, 4 and 5 Ton ZR and 6.5 thru 10 Ton ZF/ZH/ZJ/ZR/ZB (See Physical Dimensions table for exact models)
LEFT
A
59.00
CD
E
F
4.19
27.31
89.00
21.19
11.38
15.38
59.00
15.38
29.69
15.25
FRONT
SEE DETAIL BFOR DRAIN LOCATION
SEE DETAIL A FOR GAS INLET
B
2X Ø 24.38
Johnson Controls Ducted Systems 3
![Page 4: SUBMITTAL DATA SHEET · submittal data sheet single package air conditioners and gas/electric heat units, 3 through 12-1/2 tons models: zh/zj/zr/zt037-150, zf078-150, zb078-150](https://reader033.vdocuments.site/reader033/viewer/2022051811/601db64bfe63d00cb5115123/html5/thumbnails/4.jpg)
335691-YSD-M-0320
10 - 12.5 Ton ZT and 12.5 Ton ZH, ZJ, ZR, ZB
15.23
29.03
14.85
29.03
14.85
15.23
28.86 29.66
44.09
Ø 24.58 TYP. 4 PL.
FRONT
See detail B for drain location
See detail A for gas inlet
CD
E
F
B
4 3/16
27 5/16
89
21 3/16
11 3/8
A
LEFT
59
4 Johnson Controls Ducted Systems
![Page 5: SUBMITTAL DATA SHEET · submittal data sheet single package air conditioners and gas/electric heat units, 3 through 12-1/2 tons models: zh/zj/zr/zt037-150, zf078-150, zb078-150](https://reader033.vdocuments.site/reader033/viewer/2022051811/601db64bfe63d00cb5115123/html5/thumbnails/5.jpg)
335691-YSD-M-0320
6.5 - 8.5 Ton ZT and 12.5 Ton ZF
LEFT
59.00
A
CD
E
F
4.19
27.31
89.00
21.19
FRONT
SEE DETAIL BFOR DRAIN LOCATION
11.38
SEE DETAIL A FOR GAS INLET
B
29.95 30.11
14.92
58.09
14.92
14.92
45.64
4X Ø 24.38
Johnson Controls Ducted Systems 5
![Page 6: SUBMITTAL DATA SHEET · submittal data sheet single package air conditioners and gas/electric heat units, 3 through 12-1/2 tons models: zh/zj/zr/zt037-150, zf078-150, zb078-150](https://reader033.vdocuments.site/reader033/viewer/2022051811/601db64bfe63d00cb5115123/html5/thumbnails/6.jpg)
335691-YSD-M-0320
Detail A
Detail B
3 to 12.5 Ton Unit Physical Dimensions
Unit Model NumberDimension (in.)
A B C D E FZF078, 090 42 89 22 1/8 18 3/16 15 3/16 6 3/16ZF102, 120 50 3/4 89 30 3/16 24 3/16 17 3/16 6 3/16
ZF150 50 3/4 119 1/2 30 3/16 24 3/16 17 3/16 6 3/16ZH037, 049, 061, 078, 090 42 89 22 1/8 18 3/16 15 3/16 6 3/16
ZH102, 120 50 3/4 89 30 3/16 24 3/16 17 3/16 6 3/16ZH150 50 3/4 119 1/2 30 3/16 24 3/16 17 3/16 6 3/16
ZJ037, 049, 061 42 89 22 1/8 18 3/16 15 3/16 6 3/16ZJ078, 090, 102, 120 50 3/4 89 30 3/16 24 3/16 17 3/16 6 3/16
ZJ150 50 3/4 119 1/2 30 3/16 24 3/16 17 3/16 6 3/16ZR037, 049, 061 42 89 22 1/8 18 3/16 15 3/16 6 3/16
ZR078, 090 42 89 22 1/8 18 3/16 15 3/16 6 3/16ZR102, 120 50 3/4 89 30 3/16 24 3/16 17 3/16 6 3/16
ZR150 50 3/4 119 1/2 30 3/16 24 3/16 17 3/16 6 3/16ZT037, 049, 061 42 89 22 1/8 18 3/16 15 3/16 6 3/16
ZT078, 090 and 102 50 3/4 119 1/2 30 3/16 24 3/16 17 3/16 6 3/16ZT120 and 150 50 3/4 119 1/2 30 3/16 24 3/16 17 3/16 6 3/16
ZB078, 090, 102, 120 50 3/4 89 30 3/16 24 3/16 17 3/16 6 3/16ZB150 50 3/4 119 1/2 30 3/16 24 3/16 17 3/16 6 3/16
42” CABINET
Ø 3.126
Ø 2.000
3.184
4.727
7.705
14.594
Gas Pipe Inlet
Gas Exhaust Vent
50 3/4” CABINET
Ø 3.126
Ø 2.000
3.184
4.737
7.715
17.541
Gas Pipe Inlet
Gas Exhaust Vent
5-3/8
1” FPT
6 Johnson Controls Ducted Systems
![Page 7: SUBMITTAL DATA SHEET · submittal data sheet single package air conditioners and gas/electric heat units, 3 through 12-1/2 tons models: zh/zj/zr/zt037-150, zf078-150, zb078-150](https://reader033.vdocuments.site/reader033/viewer/2022051811/601db64bfe63d00cb5115123/html5/thumbnails/7.jpg)
335691-YSD-M-0320
3 to 12.5 Ton Unit Side Duct Openings
12.5 Ton Unit Side Duct Openings - ZT120, 150 and ZH/ZJ/ZR/ZB 150
12.5 Ton Unit Side Duct Openings - ZT078, 090, 102 and ZF150
D o t P l u g s
5 - 5 /3 2
3 1 - 1 1 /1 6
2 - 3 1 /3 2
1 8 - 1 /4
ReturnAir
Supply Air
A
B
C
D
Dot Plugs
2-7/8
5-5/32
D
C 31-5/8
18-1/4
B
A
Dot Plugs
2-7/85-5/32
D
C 31-5/8
18-1/4
B
A
Johnson Controls Ducted Systems 7
![Page 8: SUBMITTAL DATA SHEET · submittal data sheet single package air conditioners and gas/electric heat units, 3 through 12-1/2 tons models: zh/zj/zr/zt037-150, zf078-150, zb078-150](https://reader033.vdocuments.site/reader033/viewer/2022051811/601db64bfe63d00cb5115123/html5/thumbnails/8.jpg)
335691-YSD-M-0320
3 to 12.5 Ton Side Duct Dimensions
Unit Model NumberDimension (in.)
A B C D
ZF078, 090 27 3/4 12 1/16 27 1/2 16ZF102, 120 28 1/4 18 1/16 28 1/4 18 1/4
ZF150 28 1/4 18 1/16 28 1/4 18 1/4ZH037, 049, 061, 078, 090 27 3/4 12 1/16 27 1/2 16
ZH102, 120 28 1/4 18 1/16 28 1/4 18 1/4ZH150 28 1/4 18 1/16 28 1/4 18 1/4
ZJ037, 049, 061 27 3/4 12 1/16 27 1/2 16ZJ078, 090, 102, 120 28 1/4 18 1/16 28 1/4 18 1/4
ZJ150 28 1/4 18 1/16 28 1/4 18 1/4ZR037, 049, 061 27 3/4 12 1/16 27 1/2 16
ZR078, 090 27 3/4 12 1/16 27 1/2 16ZR102, 120 28 1/4 18 1/16 28 1/4 18 1/4
ZR150 28 1/4 18 1/16 28 1/4 18 1/4ZT037, 049, 061 27 3/4 12 1/16 27 1/2 16ZT078, 090, 102 28 1/4 18 1/16 28 1/4 18 1/4
ZT120, 150 28 1/4 18 1/16 28 1/4 18 1/4ZB078, 090, 102, 120 28 1/4 18 1/16 28 1/4 18 1/4
ZB150 28 1/4 18 1/16 28 1/4 18 1/4
3 to 12.5 Ton Unit Clearances
Direction Distance (in.) Direction Distance (in.)Top1
1. Units must be installed outdoors. Over hanging structure or shrubs should not obscure condenser air discharge outlet.
72 Right 12Front 36 Left 36Rear 36 Bottom2
2. Units may be installed on combustible floors made from wood or class A, B or C roof covering materials.
0
8 Johnson Controls Ducted Systems
![Page 9: SUBMITTAL DATA SHEET · submittal data sheet single package air conditioners and gas/electric heat units, 3 through 12-1/2 tons models: zh/zj/zr/zt037-150, zf078-150, zb078-150](https://reader033.vdocuments.site/reader033/viewer/2022051811/601db64bfe63d00cb5115123/html5/thumbnails/9.jpg)
335691-YSD-M-0320
3 to 12.5 Ton Unit Bottom Duct Openings (inches)
TOP VIEW
Bottom condensate drain
Bottom gassupply entry
FRONT
RETURNAIR
SUPPLYAIR
RIGHTLEFT
20 1/8 19 1/8 17 1/8
6 13/16
6 13/16
32 11/16
14 1/2
16 3/8
18 1/16
25 9/16
12 5/16
27 1/224
2118
89
Ø 2.469
3X Ø 0.875
Bottom power, controland convenience outlet
wiring entry
Johnson Controls Ducted Systems 9
![Page 10: SUBMITTAL DATA SHEET · submittal data sheet single package air conditioners and gas/electric heat units, 3 through 12-1/2 tons models: zh/zj/zr/zt037-150, zf078-150, zb078-150](https://reader033.vdocuments.site/reader033/viewer/2022051811/601db64bfe63d00cb5115123/html5/thumbnails/10.jpg)
335691-YSD-M-0320
3 to 12.5 Ton Unit Electrical Entry (inches)
3 to 12.5 Ton Unit Left Economizer Duct Opening (inches)
Disconnect Swith Cover
Power Entry Ø 2-1/2
Control Entry Ø 7/8
Power Entry Ø 2-1/2
Convenience Outlet Cover
Convenience OutletPower Entry Ø 7/8 FRONT
4-5/16
A
C
B
10 Johnson Controls Ducted Systems
![Page 11: SUBMITTAL DATA SHEET · submittal data sheet single package air conditioners and gas/electric heat units, 3 through 12-1/2 tons models: zh/zj/zr/zt037-150, zf078-150, zb078-150](https://reader033.vdocuments.site/reader033/viewer/2022051811/601db64bfe63d00cb5115123/html5/thumbnails/11.jpg)
335691-YSD-M-0320
3.5 to 12.5 Ton Left/End Duct Dimensions
Unit Model NumberDimension (in.)
A B C
ZF078, 090 30.357 13.365 22.516ZF102, 120, 150 30.358 22.580 22.330
ZH037, 049, 061, 078, 090 30.357 13.365 22.516ZH102, 120 30.358 22.580 22.330
ZH150 30.358 22.580 22.330ZJ037, 049, 061 30.357 13.365 22.516
ZJ078, 090, 102, 120 30.358 22.580 22.330ZJ150 30.358 22.580 22.330
ZR037, 049, 061 30.357 13.365 22.516ZR078, 090 30.357 13.365 22.516ZR102, 120 30.358 22.580 22.330
ZR150 30.358 22.580 22.330ZT037, 049, 061 30.357 13.365 22.516ZT078, 090, 102 30.358 22.580 22.330
ZT120, 150 30.358 22.580 22.330ZB078, 090, 102, 120 30.358 22.580 22.330
ZB150 30.358 22.580 22.330
Johnson Controls Ducted Systems 11
![Page 12: SUBMITTAL DATA SHEET · submittal data sheet single package air conditioners and gas/electric heat units, 3 through 12-1/2 tons models: zh/zj/zr/zt037-150, zf078-150, zb078-150](https://reader033.vdocuments.site/reader033/viewer/2022051811/601db64bfe63d00cb5115123/html5/thumbnails/12.jpg)
335691-YSD-M-0320
3 to 12.5 Ton Unit Roof Curb (inches)
3 to 12.5 Ton Unit Transition Roof Curb (inches)
8 or 14
50-1/2
30
20
20
80-5/8
6
2 TYP.
INSULATED DECK UNDERCOMPRESSOR SECTION
INSULATED DECK UNDERCONDENSER SECTION
FRONT
RIGHT
SUPPLY
RETURN
76-5/8
94
50-1/2 30-1/2
64-1/4
59-1/4
10
23 4
26 80-5/8
2 TYP
FRONT RIGHT
SUPPLY
RETURN
12 Johnson Controls Ducted Systems
![Page 13: SUBMITTAL DATA SHEET · submittal data sheet single package air conditioners and gas/electric heat units, 3 through 12-1/2 tons models: zh/zj/zr/zt037-150, zf078-150, zb078-150](https://reader033.vdocuments.site/reader033/viewer/2022051811/601db64bfe63d00cb5115123/html5/thumbnails/13.jpg)
335691-YSD-M-0320Economizer Downflow W/Power Exhaust
Economizer End Return W/Power Exhaust
Fresh Air Hood
Barometric ReliefHood
BarometricRelief Damper
Power Exhaust
Low Leak Economizer
Fresh Air Hood
Field InstalledDuct Work
Power Exhaust
Barometric Relief Damper
Barometric Relief Hood
Low LeakEconomizer
Johnson Controls Ducted Systems 13
![Page 14: SUBMITTAL DATA SHEET · submittal data sheet single package air conditioners and gas/electric heat units, 3 through 12-1/2 tons models: zh/zj/zr/zt037-150, zf078-150, zb078-150](https://reader033.vdocuments.site/reader033/viewer/2022051811/601db64bfe63d00cb5115123/html5/thumbnails/14.jpg)
335691-YSD-M-0320
Field Installed Horizontal Economizer W/Power Exhaust
Roof Curb Cutaway
BarometricRelief Hood
BarometricRelief Damper
Power Exhaust
Fresh Air Hood
Fresh Air Damper
Return Air Damper
Field Installed Duct Work
3/4” X 1-1/4” WIDE GASKETING FOR CURB FRAME AND ALL DUCT SUPPORT SURFACES
2“
UNIT BASE
WOOD NAILER
8“ MIN. ABOVE FINISHED ROOF
CURB FRAME
INSULATION
UNIT BASE RAILS
COUNTERFLASHING
CAN’T STRIP
INSULATION AND ROOFING MATERIAL
ROOF DECK AND SUPPORT STRUCTURE
14”
3.56”
3.75”
14 Johnson Controls Ducted Systems
![Page 15: SUBMITTAL DATA SHEET · submittal data sheet single package air conditioners and gas/electric heat units, 3 through 12-1/2 tons models: zh/zj/zr/zt037-150, zf078-150, zb078-150](https://reader033.vdocuments.site/reader033/viewer/2022051811/601db64bfe63d00cb5115123/html5/thumbnails/15.jpg)
FACTORY INSTALLED OPTIONS
ELECTRIC HEATER MODEL - KW_____VOLTS_____STAINLESS STEEL HEAT EXCHANGER - - - - - - - - - - ALUMINIZED STEEL HEAT EXCHANGER - - - - - - - - - STAINLESS STEEL DRAIN PAN- - - - - - - - - - - - - - - - - ECONOMIZER, DOWNFLOW, END RETURN HORIZON-TAL- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - POWER EXHAUST - - - - - - - - - - - - - - - - - - - - - - - - - - MOTORIZED AIR DAMPER - - - - - - - - - - - - - - - - - - - - HIGH STATIC INDOOR BLOWER MOTOR - - - - - - - - - DISCONNECT SWITCH - - - - - - - - - - - - - - - - - - - - - - - CONVENIENCE OUTLET, POWERED - - - - - - - - - - - - CONVENIENCE OUTLET, NON-POWERED - - - - - - - - SMOKE DETECTOR (RETURN) - - - - - - - - - - - - - - - - - SMOKE DETECTOR (SUPPLY) - - - - - - - - - - - - - - - - - PHASE MONITOR1 - - - - - - - - - - - - - - - - - - - - - - - - - - COIL GUARD - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - DIRTY FILTER SWITCH- - - - - - - - - - - - - - - - - - - - - - - FILTERS, 2" PLEATED, MERV 7 - - - - - - - - - - - - - - - - FILTERS, 4" PLEATED, MERV 13 - - - - - - - - - - - - - - - PHENOLIC COATED EVAPORATOR COILS - - - - - - - - PHENOLIC COATED CONDENSER COILS- - - - - - - - - E-COAT EVAPORATOR COILS - - - - - - - - - - - - - - - - - E-COAT CONDENSER COILS - - - - - - - - - - - - - - - - - - INTELLISPEED WITH VFD - - - - - - - - - - - - - - - - - - - - INTELLISPEED, VFD AND MANUAL BYPASS - - - - - - INTELLISPEED, VFD READY (FOR CUSTOMER-PRO-VIDED, FIELD-INSTALLED DRIVE) - - - - - - - - - - - - - - VAV W/VFD - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - VAV W/VFD AND MANUAL BYPASS - - - - - - - - - - - - - VAV, VFD READY (FOR CUSTOMER-PROVIDED, FIELD-INSTALLED DRIVE) - - - - - - - - - - - - - - - - - - - - - - - - - - BAS OPTION
Smart Equipment™ w/Communication - - - - - - - - - - - BACnet MS/TP (programmable to Modbus or N2 proto-cols) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - Verasys - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - Honeywell™ - - - - - - - - - - - - - - - - - - - - - - - - - - - - - Novar® - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - CPC - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
FIELD INSTALLED ACCESSORIES
ROOF CURB, 8" - - - - - - - - - - - - - - - - - - - - - - - - - - - - ROOF CURB, 14"- - - - - - - - - - - - - - - - - - - - - - - - - - - - TRANSITION ROOF CURB - - - - - - - - - - - - - - - - - - - - COIL GUARD - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - HAIL GUARD- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - PERMANENT FILTERS - - - - - - - - - - - - - - - - - - - - - - - METAL FILTER FRAME KIT - - - - - - - - - - - - - - - - - - - - DIRTY FILTER SWITCH - - - - - - - - - - - - - - - - - - - - - - - AIR PROVING SWITCH - - - - - - - - - - - - - - - - - - - - - - - BURGLAR BARS (DOWNFLOW ONLY) - - - - - - - - - - - LOW AMBIENT KIT - - - - - - - - - - - - - - - - - - - - - - - - - - SMOKE DETECTOR (RETURN) - - - - - - - - - - - - - - - - - SMOKE DETECTOR (SUPPLY) - - - - - - - - - - - - - - - - - CO2 SENSOR - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - PHASE MONITOR1 - - - - - - - - - - - - - - - - - - - - - - - - - - ECONOMIZER, DOWNFLOW, END RETURN HORIZON-TAL- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - ECONOMIZER, HORIZONTAL - - - - - - - - - - - - - - - - - - SINGLE ENTHALPY- - - - - - - - - - - - - - - - - - - - - - - - - - DUAL ENTHALPY - - - - - - - - - - - - - - - - - - - - - - - - - - - POWER EXHAUST - - - - - - - - - - - - - - - - - - - - - - - - - - MOTORIZED OUTDOOR AIR DAMPER - - - - - - - - - - - MANUAL OUTDOOR AIR DAMPER - - - - - - - - - - - - - - ELECTRIC HEATER MODEL - KW_____VOLTS_____FLUE EXTENSION KIT- - - - - - - - - - - - - - - - - - - - - - - - GAS PIPING KIT - - - - - - - - - - - - - - - - - - - - - - - - - - - - GAS HEAT PROPANE ADAPTER KIT - - - - - - - - - - - - - GAS HEAT HIGH ALTITUDE KIT, NATURAL GAS - - - - GAS HEAT HIGH ALTITUDE KIT, PROPANE- - - - - - - - -60°F GAS HEAT KIT - - - - - - - - - - - - - - - - - - - - - - - - - WALL MOUNT TEMPERATURE SENSOR- - - - - - - - - - WALL MOUNT TEMPERATURE SENSOR WITHOVERRIDE - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - WALL MOUNT TEMPERATURE SENSOR WITHOVERRIDE & SET POINT ADJ. - - - - - - - - - - - - - - - - - - HUMIDITY SENSOR - - - - - - - - - - - - - - - - - - - - - - - - -
1. Phase monitor standard on units with scroll compressors.
Subject to change without notice. Printed in U.S.A. 335691-YSD-M-0320Copyright © 2019 by Johnson Controls, Inc. All rights reserved. Supersedes: 335691-YSD-L-1018