study of dissolved gas analysis under electrical & thermal stresses for oil

Upload: rasheed313

Post on 03-Jun-2018

223 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    1/176

    Study of Dissolved Gas Analysis under Electricaland Thermal Stresses for Natural Esters used in

    Power Transformers

    A thesis submitted to The University of Manchester for the degree of MPhil in the Faculty ofEngineering and Physical Sciences

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    2/176

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    3/176

    Contents

    Contents ..................................................................................................................................... 3

    List of Figures ........................................................................................................................... 7

    List of Tables ........................................................................................................................... 11

    Abstract ................................................................................................................................... 13

    Declaration .............................................................................................................................. 15

    Copyright Statement .............................................................................................................. 17

    Acknowledgement .................................................................................................................. 19

    Chapter 1 Introduction .......................................................................................................... 21

    1.1 Background Study ............................................................................................. 21

    1.2 Research Objectives .......................................................................................... 22

    1.3 Outline of Thesis ................................................................................................ 22

    Chapter 2 Literature Review of Dissolved Gas Analysis on Natural Ester ...................... 25

    2.1 Introduction of Transformer Liquid ............................................................... 25

    2.1.1 Mineral Oil Nytro Gemini X .................................................................. 25

    2.1.2 Natural Ester FR3 ................................................................................... 26

    2.1.3 Sample Processing Methodology ............................................................... 27

    2.2 Transformer Faults ........................................................................................... 28

    2 2 1 P i l Di h F l 28

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    4/176

    2.4.3 PC Data Analysis ......................................................................................... 38

    2.5 Previous Work Review ...................................................................................... 39

    2.5.1 Electrical Sparking ..................................................................................... 39

    2.5.2 Electrical PD Test ........................................................................................ 40

    2.5.3 Thermal Test ................................................................................................ 43

    2.6 Tests Comparison and Summary ..................................................................... 48

    Chapter 3 Experimental Study on DGA under Sparking Faults ....................................... 51

    3.1 Introduction ........................................................................................................ 51

    3.2 Experiment Setup .............................................................................................. 51

    3.2.1 Test Circuit Design ...................................................................................... 51

    3.2.2 Test Vessel Design ........................................................................................ 53

    3.3 Test Procedure .................................................................................................... 56

    3.3.1 Drain Oil out of System .............................................................................. 57

    3.3.2 Clean Test System and Fill Processed Oil into the System ...................... 58

    3.3.3 Measuring Background DGA level ............................................................ 59

    3.3.4 Generating Sparking Faults ....................................................................... 59

    3.4 Data Measurement and Analysis ...................................................................... 60

    3.4.1 GIG and GIT ............................................................................................... 60

    3.4.2 Dissolved Gas Generation Calculation ..................................................... 61

    3 4 3 Sparking Energy Calculation 63

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    5/176

    4.1 Introduction ....................................................................................................... 79

    4.2 Experiment Setup .............................................................................................. 79

    4.3 Test Procedure ................................................................................................... 80

    4.3.1 Calibrate the PD Detector ......................................................................... 81

    4.3.2 Measuring Background PD Noise ............................................................. 82

    4.3.3 Generating PD Faults ................................................................................. 82

    4.4 Data Measurement and Process Method ......................................................... 83

    4.4.1 Total Gas Generation Calculation ............................................................ 83

    4.4.2 PD Energy Calculation .............................................................................. 84

    4.5 Test Condition and Observation ...................................................................... 88

    4.6 Test Result and Analysis ................................................................................... 89

    4.6.1 PD Fault Gas Generation .......................................................................... 89

    4.6.2 PD Fault Energy ......................................................................................... 91

    4.6.3 Gas generation rate (per J) ........................................................................ 93

    4.6.4 Absolute Gas generation rate (per J) ........................................................ 95

    4.6.5 Duval Triangle Analysis ............................................................................. 96

    4.6.6 Laboratory DGA and Online Monitor Comparison ............................... 98

    4.7 Summary ............................................................................................................ 99

    Chapter 5 Experimental Study on DGA under Thermal Fault ....................................... 101

    5 1 Introduction 101

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    6/176

    5.6.2 Gas Generation Rate Comparison under Different Temperatures ...... 109

    5.6.3 Duval Triangle Analysis ............................................................................ 111

    5.6.4 Laboratory DGA and Online Monitor Comparison .............................. 113

    5.7 Summary ........................................................................................................... 113

    Chapter 6 Conclusions and Future Work .......................................................................... 115

    6.1 Conclusions ....................................................................................................... 115

    6.1.1 Research Areas .......................................................................................... 115

    6.1.2 Main Findings ........................................................................................... 116

    6.2 Future Work ..................................................................................................... 117

    Reference ............................................................................................................................... 119

    Appendix I. Matlab Code Used In the Thesis .................................................................... 123

    I.1 Sparking Energy Calculation ..................................................................................... 123

    I.1.1 High Frequency Energy Calculation .......................................................... 123

    I.1.2 Low Frequency Energy Calculation ........................................................... 125

    I.2 PD Energy Calculation ............................................................................................... 128

    Appendix II. The Results Used in the Thesis ...................................................................... 131

    Words count: 34975

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    7/176

    List of Figures

    Figure 2.1 Basic Hydrocarbon Structures in Mineral Oil [20] ................................. 25

    Figure 2. 2 Molecular Structure of FR3 [23] .............................................................. 27

    Figure 2. 3 Diagram of Indicator Gases and Faulty Type and Severity in

    Transformers Filled By Mineral Oil [38] ............................................................ 32

    Figure 2. 4 Headspace Sampling Method [39] ............................................................ 33

    Figure 2. 5 Gas Chromatograph Concept Diagram [41] ........................................... 34

    Figure 2. 6 Duval Triangle Diagrams .......................................................................... 35

    Figure 2. 7 TM8 Online Transformer Monitor .......................................................... 36

    Figure 2. 8 The Working Principle Diagram of TM8 ................................................ 37

    Figure 2. 9 Dual- Column GC Analysis Diagram ....................................................... 38

    Figure 2. 10 Example of Analysis Diagram of TM8 Viewer [17] .............................. 38 Figure 2. 11 Photo of Lighting Impulse Sparking Test Vessel [12] .......................... 39

    Figure 2. 12 Comparision of Fault Gas-in-Oil Generation between Lyra X and FR3

    [12] .......................................................................................................................... 40

    Figure 2. 13 Electrical PD Test Diagram [10] ............................................................ 40

    Figure 2. 14 Test Vessel Diagram of PD Test [10] ...................................................... 41 Figure 2. 15 Thermal Test 1(Heating Element) [11] .................................................. 44

    Figure 2. 16 Thermal Test 2 (Heating Element) [12] ................................................. 45

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    8/176

    Figure 3.8 Example Filtered Waveform of Power Frequency Sparking Current ... 66

    Figure 3.9 Different Types of Sparking ....................................................................... 67

    Figure 3.10 Total Gas Generation in Gemini X /FR3 Tests ....................................... 70

    Figure 3.11 GIT Generation rate (per) J in Gemini X and FR3 Sparking Tests ..... 73

    Figure 3.12 GIT Generation rate (per J) Comparison between Gemini X and FR3

    ................................................................................................ ................................. 75

    Figure 3.13 Duval Triangle Evaluation (GIO) of Sparking Fault in Gemini X and

    FR3 .......................................................................................................................... 77

    Figure 4.1 Schematic Diagram of Electrical PD Test Circuit .................................... 80

    Figure 4.2 PD Calibration Panel of PD Measuring System Software ....................... 81

    Figure 4.3 PD Noise in FR3 under 60 kV .................................................................... 82

    Figure 4.4 Example of PD Test DGA Peak Value ....................................................... 84

    Figure 4.5 PD Noise Filter ............................................................................................. 85

    Figure 4.6 Gas Generation in Gemini X and FR3 PD Test ........................................ 90

    Figure 4.7 PD Patterns of Gemini X (60 Minutes PD signals from the 3000 pC Test)

    and FR3 (1 Minute PD signals from 3000 pC Test 1) ......................................... 91

    Figure 4.8 GIT Generation rate (per J) Comparison between 2000 pC Tests ofGemini X and FR3 ................................................................................................. 93

    Figure 4 9 GIT Generation rate (per J) Comparison between 3000 pC Tests of

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    9/176

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    10/176

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    11/176

    List of Tables

    Table 2.1 Key Properties of Nytro Gemini X [18] ...................................................... 26

    Table 2.2 Key Properties of FR3 [24] .......................................................................... 27

    Table 2.3 Water Content and Relative Humidity of Processed Liquid Samples at

    Room Temperature [25] ....................................................................................... 28

    Table 2.4 Bond Dissociation Energy [33] .................................................................... 31

    Table 2.5 GIO DGA Results under PD Fault of Various Amplitudes [10] .............. 42

    Table 2.6 GIO DGA Results under PD Fault of Various Energy [10] ..................... 43

    Table 2.7 GIO DGA Result of Thermal Test 1 (Heating Element)........................... 45

    Table 2.8 GIO DGA Results in both Liquids .............................................................. 46

    Table 2.9 Tests Features Comparison ......................................................................... 49

    Table 3.1 Example GIO Concentration in Gemini X ................................................. 62

    Table 3.3 Sparking Types ............................................................................................. 67

    Table 3.4 Example of Group Sparking Energy Calculation ..................................... 68

    Table 3.6 Sparking Energy for Each Test Group inside Gemini X/ FR3 ................ 71

    Table 3.7 Absolute GIT Generation Rate (t/J) of Sparking Tests .......................... 74 Table 3.8 GIO Generation Rate (ppm/J) .................................................................... 76

    Table 3.9 Comparison of GIO Results between TM8 and Laboratory Analysis .... 78

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    12/176

    Table 5.3 Comparison of GIO DGA Results between TM8 and Laboratory

    Analysis ................................................................................................................. 113

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    13/176

    Abstract Mineral oil has been traditionally used as an insulating liquid in power transformers for over a

    century, and Dissolved Gas Analysis (DGA) technique has been used for decades as one of the most useful

    diagnosis tools to assess the conditions of mineral oil filled transformers. However, due to increasing

    awareness of environmental protection and fire safety, there is a trend of replacing mineral oil with

    environmentally friendly natural esters; DGA data interpretation method should then be studied, if necessary

    revised, in order to be applicable for natural ester filled transformers.

    This thesis covers experimental studies on performances of a mineral oil (Gemini X) and a naturalester (FR3) in terms of fault gas generation. Laboratory simulated faults include electrical sparks, electrical

    partial discharges (PD) and high temperature thermal hotspot types.

    The electrical sparking fault was generated by using a sharp needle electrode with a tip radius of

    curvature of 5 micrometers, a 2.57 L sealed test vessel was designed and built with the TM8 online DGA

    monitoring system, and two CTs were used to measure the high frequency and power frequency components

    of the sparking current, respectively. The electrical PD fault was simulated using the same test system but

    under lower voltages, and a traditional PD detector was used to record the characteristics of PD signals,

    including the repetition rate and amplitude. The hotspot thermal fault was generated by heating up a copper

    element locally in a 2.73 L sealed test vessel, and three thermocouples were used to measure the temperatures

    of the heating element.

    Furthermore, the dissolved fault gases in oil were measured by both the online DGA monitoringsystem and the oil analysis laboratory, and the DGA results were also compared.

    The main findings of this thesis are outlined below:

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    14/176

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    15/176

    Declaration

    I declare that no part of the work referred to in the thesis has been submitted in support of an

    application for another degree or qualification of this or any other university or other institutes

    of learning.

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    16/176

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    17/176

    Copyright Statement

    I. The author of this thesis (including any appendices and/or schedules to this thesis) owns

    certain copyright or related rights in it (the Copyright) and he has given The University of

    Manchester certain rights to use such Copyright, including for administrative purposes.

    II. Copies of this thesis, either in full or in extracts and whether in hard or electronic copy,

    may be made only in accordance with the Copyright, Designs and Patents Act 1988 (as

    amended) and regulations issued under it or, where appropriate, in accordance with

    licensing agreements which the University has from time to time. This page must form part of

    any such copies made.

    III. The ownership of certain Copyright, patents, designs, trade marks and other

    intellectual pro perty (the Intellectual Property) and any reproductions of copyright

    works in the thesis, for example graphs and tables (Reproductions), which may bedescribed in this thesis, may not be owned by the author and may be owned by third parties.

    Such Intellectual Property and Reproductions cannot and must not be made available for

    use without the prior written permission of the owner(s) of the relevant Intellectual Property

    and/or Reproductions.

    IV. Further information on the conditions under which disclosure, publication andcommercialisation of this thesis, the Copyright and any Intellectual Property and/or

    Reproductions described in it may take place is available in the University IP Policy (see

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    18/176

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    19/176

    Acknowledgement

    Firstly I would like to express my sincerely gratitude to my supervisor Professor Zhondong

    Wang for her support and guidance during my MPhil research study at the University of

    Manchester. My MPhil research project would not succeed without her hard work and patient

    guidance.

    I am also truly grateful to all the sponsoring companies, i,e. Serveron and TJH2B who provided

    continuous support to this project at the University of Manchester. In particular, John Hinshaw

    from Severon and John Noakhes from TJ2HB are extremity helpful. I would also like to thank

    Cooper Power System for providing natural ester over the years.

    To all my colleagues in the transformer research group , I appreciate for your company

    and thank you for offering me an enjoyable working environment. Special thanks to Dr.

    Xin Wang who taught me so much on test cell design, experimental setup and thesis writingthrough all the project and Dr. Xiao Yi who offered many patient and wise suggestions.

    Last but not least, I would like to take this opportunity to thank my parents for their continuous

    support and understanding, to my girlfriend Miss Jinping Huang for her support and selfless

    love. They encouraged me to go through all the hard work all the time.

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    20/176

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    21/176

    Chapter 1 Introduction

    1.1 Background Study

    Mineral oil has been used as a traditional insulating liquid for power transformers for over a

    century. However, in face of the increasing awareness of environmental protection recently,

    applying environmental friendly transformer liquids such as natural esters or synthetic esters

    in transformers of distribution or transmission level is getting more and more popular [1, 2, 3].

    Up to now, ester based transformer liquids have been widely used in distribution transformers

    and there are more and more development work in the aim of used by esters in power

    transformers [4, 5].

    DGA, short for dissolved gas analysis, is one of the most useful diagnosis tools for incipient

    fault indication of oil-filled transformers [6]. When either thermal or electrical faults are

    occurred, transformer oil will decompose and recombine into many kinds of fault gases. In the

    past several decades, experience of DGA based fault interpretation of mineral oil-filled

    transformers has been accumulated after a wide range of lab research and on-site operation

    practices. Many standards were established for assessing conditions of mineral oil-filled

    transformers, such as IEC 60599 and IEEE C57.104 [7, 8]. Among all kinds of DGA

    interpretation methods listed in the above guide, the most comprehensive one is Duval triangle

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    22/176

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    23/176

    development of TM8 online DGA monitor, the three main types of transformer fault and a

    recent experimental study of natural ester DGA.

    Chapter 3 Experimental Study on DGA under Sparking Fault

    This chapter shows the method to generate the sparking fault and also the method to measure

    the sparking current. By using a needle to plate electrode configuration, a test cell is designed.

    It has achieved a good sealing state and complete oil circulation. The sealing state of the

    electrical test cell is verified by a pressure gauge based sealing test. A proper test procedure is

    carefully followed to use the test cell TM8 close loop measuring system in order to obtain

    reliable test results. The experiment in this chapter shows the gas generation characteristics of

    Gemini X and FR3 under the sparking faults. The simulated faults for both liquids are also

    evaluated by using the original and revised Duval triangle. Furthermore, oil samples are

    collected after the electrical sparking test and sent out for laboratory DGA analysis.

    Chapter 4 Experimental Study on DGA under PD Fault

    This chapter describes the method to generate the PD fault using similar configuration to

    previous sparking test under lower voltage/ electrical fields and also the method to calculate

    the PD energy. The same electrical test cell as Chapter 3 is used and the proper test procedureis carefully followed to reduce gas leakage. The experiments in this chapter study the gas

    generation of Gemini X and FR3 under the controlled PD faults up to 2 days

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    24/176

    Chapter 6 Conclusions and Further Work

    This chapter summarizes the main conclusions of the thesis and also gives some suggestions

    for future studies.

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    25/176

    Chapter 2 Literature Review of Dissolved Gas Analysis onNatural Ester

    2.1 Introduction of Transformer Liquid

    This MPhil thesis explores the differences of fault gas generation characteristics between

    conventional mineral oil which is widely used in large power transformers, and natural ester

    which is expected to be an alternative for mineral oil. From now on, Gemini X will stand for

    the mineral oil and FR3 will represent natural ester.

    2.1.1 Mineral Oil Nytro Gemini X

    Nytro Gemini X, a type of inhibited insulating transformer oil, which is produced by Nynas

    Oil Company to replace the previous uninhibited Nytro 10GBN, consists of saturated

    hydrocarbon molecules, like paraffins and naphthenes and unsaturated aromatics and

    polyaromates as shown in Figure 2.1.

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    26/176

    with a high anti-oxidation ability. The dielectric strength of Gemini X is higher than 70 kV

    (measurement based on IEC 60156 with a 2.5 mm gap distance) when the liquid is preserved.

    However, once it has been contaminated by water or particles, the dielectric strength will

    reduce accordingly [19]. The major drawbacks of Gemini X are fire hazards and less

    biodegradability. The water saturation level of Gemini X is 55 Parts per Million (ppm) at room

    temperature. Table 2.1 shows the key properties of Gemini X.

    Table 2.1 Key Properties of Nytro Gemini X [18]

    Property Unit Test Method Typical DataPhysical

    Density,20 C kg/dm 3 ISO12185 0.882Viscosity,40 C mm 2/s ISO3104 8.7

    Flash point C ISO2719 144Pour point C ISO3016 -60

    ChemicalAcidity mg KOH/g IEC62021

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    27/176

    Figure 2.2 Molecular Structure of FR3 [23]

    FR3 is highly biodegradable but can also oxidize easily due to the structure of triglycerides.

    The dielectric strength of FR3 is above 56 kV (measured by ASTM D1816 using a 2 mm gap

    distance). FR3 is now mainly applied in distribution transformers in North and South America

    [22]. The water saturation level of FR3 is 1100 ppm at room temperature which is 20 times

    higher than that of Gemini X. Table 2.2 shows the key properties of FR3.

    Table 2.2 Key Properties of FR3 [24]

    Property Unit Test Method Typical DataPhysical

    Density,20 C kg/dm 3 ASTM D1298 0.92Viscosity,40 C mm 2/s ASTM D445 32

    Flash point C ASTM D92 330Pour point C ASTM D97 -20

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    28/176

    under 5 mbar inner pressure and 85 C, a further 24 hours cooling down is also required

    afterwards. The qualities of both Gemini X and FR3 are trusted to be the same. The water

    content was measured according to the Karl Fisher titration analysis, using Metrohm 684

    coulometer and 832 Termoprep ovens [25]. The dissolved gas is measured by the TM8 online

    transformer monitor. The result of relative humidity (water content versus saturation level) and

    dissolved gas for the processed liquid sample are below 5% and very close to 0 ppm

    respectively [10]. Table 2.3 shows the water content and relative humidity of processed

    samples.

    Table 2.3 Water Content and Relative Hu midity of Processed Liquid Samples at RoomTemperature [25]

    2.2 Transformer Faults

    The IEC standard 60599 [7] classifies the DGA detectable transformer faults into 2 categories:

    the electrical fault and the thermal fault. These two main categories can be further sorted into

    6 types of transformer fault, according to the magnitudes of the fault energy: the electrical fault:

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    29/176

    while the others such as the one which occurs in a transformer liquid is commonly named as

    streamer [7, 8].

    Partial discharges, known as one of the most influencing reasons for insulator degradation,

    could lead to electric breakdown when they accumulate and propagate fully between two

    conductors. To avoid costly transformer failures, it is critically important to monitor the PD

    activities for early detection of the incipient of transformer fault. Dissolved gas analysis (DGA)

    is now the most widely used method to determine the condition of transformer insulation liquid

    as it is a non-destructive technique [26-30].

    2.2.2 Electrical Sparking Fault

    After decades of study, it is now generally accepted that the breakdown occurs after the

    streamers fully propagate through the gap of the electrodes. When the energy of dielectric

    breakdown is limited, it will act as small arcs which are named as sparking faults [7]. In

    comparison with PD faults, sparking fault generate much more amount of fault gases under the

    same fault time and could be critical for transformer operation.

    2.2.3 Thermal Fault

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    30/176

    Dissolved gas analysis (DGA) is known as one of the most widely used diagnosis tools of oil-

    filled transformers, it is noted as the non-interrupt test method which has already functioned

    for decades. Furthermore, DGA is also famous for the reliable fault forecast tool that is

    developed based on a vast amount of faulty oil-filled equipment in service and laboratory

    experiment results worldwide [7, 8].

    In general, DGA can be divided into 4 steps: collect oil sample, extract dissolved gas, gas

    chromatograph measurement and data interpretation. The oil sample collection is based on the

    international standard IEC 60567 which gives the recommended procedure for taking an oil

    sample from oil filled equipment. The oil sample collection is considered to be the first primary

    factor of a good DGA result; therefore, the recommended procedure needs to be followed

    carefully.

    The extraction of dissolved gas from the oil sample is the second step. The traditional vacuum

    method or the alternative vacuum pump method such as headspace and stripper methods are

    also available in IEC60567 [31]. The headspace method is used in the TM8 and will be

    explained in Section 2.3.2.

    The third step is the gas chromatograph (GC) which could separate and analyze different gas

    components Detail of the GC will be described in Section 2 3 3

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    31/176

    2.3.1 Gas Formation

    The transformer liquid consists of different hydrocarbon atomic groups like CH 3, CH 2 and CH.The molecular bond which is used to link the molecular group together, such as C-H and C-C

    bonds, will be broken when electrical or thermal energy is applied. Newly formed unstable

    radical or ionic fragments will recombine swiftly into gas molecules like hydrogen (H-H),

    methane (CH 3-H), ethane (CH 3-CH 3), ethylene (CH 2=CH 2), acetylene (CH CH), CO (C O)

    and CO 2 (O=C=O). Different energy levels are required to break different kind of molecular bonds, as a result, different types and amounts of fault gases will be formed according to the

    severity and category of the transformer fault. The energy which is mandatory to crack the

    typical molecular bond inside the transformer oil is shown in Table 2.4.

    Table 2.4 Bond D issociation Energy [33]

    BondC-C (CH 3-

    CH 3)

    C-H

    (average)

    C=C

    (H2C=CH 2)

    CC

    (HCCH)

    Dissociationenergy

    (kJ/mol) 356 410 632 837

    Arcing, low energy sparking, PD and overheating are some of the common faults that could

    happen in the oil-filled transformers. Once any of these faults occurs, the insulation liquid will

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    32/176

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    33/176

    2.3.2 Headspace Method

    Headspace method is a calculation method used to compute gas-in-total or gas-in-oil

    concentration using gas-in-gas (GIG) concentration. The case shown in Figure 2.4 is an oil-

    filled vial with V L volume of oil and left a V G volume of headspace.

    Figure 2.4 Headspace Sampling Method [39]

    Some of the dissolved gas will spread to the headspace from the oil until the equilibrium

    condition of a certain temperature, agitation and pressure is reached. Afterwards, the headspace

    gas will be passed to the gas chromatograph (GC) columns. Then the obtained gas

    concentration in headspace, GIG, will be used to calculate gas-in-oil (GIO) or gas-in-total (GIT)

    according to Henry s law.

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    34/176

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    35/176

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    36/176

    fault. With the help of software, those monitors will be able to calculate and display some of

    the interpretation results like the Duval triangle [42].

    2.4 Serveron Online Transformer Monitor TM8

    The Online DGA monitor used in this thesis is Serveron TM8 (shown in Figure 2.7). It is able

    to provide useful and timely information for oil-filled transformer condition assessment. Withthe help of the built-in sensors and special chromatographic columns, TM8 can provide up to

    hourly DGA sampling covering all 8 types of transformer fault gases with 5% accuracy [17].

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    37/176

    Transformer oilTransformer

    gas

    Liquid blockagemembrane

    Gas flow

    Selective

    columns

    Dual-column

    GC analysis

    Extractor

    Oil flow

    Carrier gases

    Heliumflow

    PC basedTM8

    system

    Data flow

    Test cell/transformer

    Figure 2.8 The Working Principle Diagram of TM8

    In the closed loop system, transformer oil keeps circulating between the test vessel/ transformer

    and the oil chamber of the TM8 extractor. The gases dissolved inside the transformer oil will

    go through the liquid blockage membrane into the gas chamber of the TM8 extractor. The

    carrier gas helium flow (red arrows) will carry the dissolved gases into the extractor gas

    chamber and will go to the selective columns. These will separate all 8 kinds of gases and let

    them reach the GC analysis part at different times. Lastly, in the GC analysis part, the fault

    gases are analyzed by the sequence as shown in next Section.

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    38/176

    Figure 2.9 Dual- Column GC Analysis Diagram

    2.4.3 PC Data Analysis

    The raw result from the GC analyzer will be further computed based on the built-in partition

    coefficient K, the measured oil temperature and the equilibrium pressure in the extractor. The

    result plots out timely DGA curves (Figure 2.10 (a)) and can also provide an automatic

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    39/176

    2.5 Previous Work Review

    Many researchers made great efforts to understand the FR3 performance under electrical and

    thermal fault conditions such as [10-15]. Their research is studied and described below.

    2.5.1 Electrical Sparking

    Figure 2.11 shows the lighting impulse sparking experiment carried out by Mark. Jovalekic to

    investigate the fault gas generation under the lighting impulse sparking fault in mineral oil,

    Lyra X and natural ester FR3.

    Figure 2.11 Photo of Lighting Impulse Sparking Test Vessel [12]

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    40/176

    Figure 2.12 Comparision of Fault GIO Generation between Lyra X and FR3 [12]

    2.5.2 Electrical PD Test

    Figure 2.13 shows the electrical PD test that was designed by X. Wang [10]. As we can see

    from the circuit diagram, the 50 Hz power transformer is used to provide up to 70 kV test

    voltage. A 500 pF discharge free capacitor is connected in parallel with the test vessel. The

    measuring impedance of the LDS-6 PD detector is connected in series with the capacitor. The

    PD detector is calibrated and used to measure the PD signal with less than 5 pC noise (70 kV

    test voltage).

    0500

    10001500200025003000350040004500

    CO2 C2H4 C2H2 C2H6 H2 CH4 CO TDCGLyra X 219 214 2100 0 1775 155 0 4244

    FR3 182 229 953 0 605 99 155 2041

    L/L

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    41/176

    The test vessel diagram is shown in Figure 2.14. It can be seen from the diagram that the 100

    ml glass vial sealed by an aluminum crimp cap is fully filled with test oil. The needle electrode

    is penetrated into the rubber sealing whose tip radius of curvature is 6-7 m from front view

    and 2-3 m from lateral view.

    Figure 2.14 Test Vessel Diagram of PD Test [10]

    The assemble of the test vessel and the needle electrode is immersed inside an insulating oil

    filled container. A copper base of 100 mm diameter is placed under the bottom of the test vessel

    as a plate electrode. The gap distance between the needle and plate electrode is kept as 50 mm

    for all tests. A new needle electrode will be replaced after each test. The oil sample is

    immediately sealed by the Acrylic-based sealing compound from RS Ltd [43] and is then sent

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    42/176

    Table 2.5 GIO DGA Results under PD Fault of Various Amplitudes [10]

    Oil Test PD amplitude (pC)DGA(ppm)

    C 2H 4 C 2H 2 C 2H 6 H 2 CH 4 CO TCG

    Gemini X

    G.Test1 200 0.2 0.2 0.4 12.4 0.9 21.7 35.8

    G.Test2 300 0.2 0.1 0.2 7 0.5 12.4 20.4

    G.Test3 500 0.2 0.3 0.3 62.4 0.4 13.9 77.5

    G.Test4 1000 1.5 3.5 0.9 163 2.9 13.6 185.4

    FR3

    F.Test1 200 0.2 0 44.7 29.9 1.2 20.1 96.1

    F.Test2 300 2.7 5 83.4 63.7 3.9 36.2 194.9

    F.Test3 500 5.5 11.5 46 69.1 5.8 30 167.9

    F.Test4 1000 9.1 22.4 63.4 140 11.4 49.9 296.2Note: Those unexpected results listed in bold and italic style may be caused by leakage.

    The difference is mainly contributed by C 2H6 which makes up to 46.5% (200 pC), 42.8% (300

    pC), 80.5% (500 pC), and 21.4% (1000 pC) of the total gas generation for FR3. H 2 is the most

    significant hydrocarbon gases except C 2H6. H 2 is making up to 34.6% (200 pC), 34.3% (300

    pC), 27.4% (500 pC), and 87.9% (1000 pC) of the total gas generation in Gemini X tests while

    that is only 31.1% (200 pC), 32.7% (300 pC), 41.2% (500 pC), and 47.3% (1000 pC) in FR3.

    The concentration of CO in FR3 is around twice of that in Gemini X. C 2H2 starts to generate

    under the 1000 pC PD fault inside Gemini X while the trace of it could be found inside FR3

    under 300 pC PD fault.

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    43/176

    Table 2.6 GIO DGA Results under PD Fault of Various Energy [10]

    Oil Test Times(mins)

    PDenergy

    (mJ)

    DGA(ppm)l/J

    C 2H 4 C 2H 2 C 2H 6 H 2 CH 4 CO TCG

    Gemini X

    1 15 7.7 0.5 0.4 0.2 31.3 1.7 10.9 45.0 584.4

    2 30 8.1 0.2 0.3 0.3 62.4 0.4 13.9 77.5 956.7

    3 45 9.2 0.3 0.5 0.2 70.9 0.9 12.5 85.3 927.2

    4 60 15.7 0.6 0.7 0.3 110.0 1.8 40.5 153.9 980.3

    FR3

    1 15 148.2 0.4 0.6 12.7 46.7 0.7 10.1 71.2 48.0

    2 30 161.4 1.5 3.1 18.2 88.4 1.9 17.9 131.0 81.2

    3 45 486.6 3.3 7.0 28.0 74.7 3.9 29.7 146.6 30.14 60 1020 6.0 13.6 63.5 138.0 6.6 39.6 267.3 26.2

    Note: The unexpected result in bold and italic style may be caused by leakage.

    It can be seen from Table 2.6 that the PD fault in Gemini X generates around half of total fault

    gases than FR3 under the same test conditions. However, when the PD energy is taken into

    consideration, the amount of gas generation rate (per J) in Gemini X is 10 times higher than

    that in FR3. The reason is that PD repetition rate in FR3 is much higher than that Gemini X.

    For the same type of liquid, the gas generation is increased as the voltage applying time

    becomes longer. However, the amount of gas generation rate (per J) in FR3 test is not linearfor different voltage applying times because the needle electrode changed as the test carried on.

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    44/176

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    45/176

    during the test. The test is then redesigned so that it can be carried out inside a sealed closed

    loop system in this thesis.

    Table 2.7 GIO DGA Result of Thermal Test 1 (Heating Element)

    OilTimes(mins)

    DGA(ppm/min)C 2H 4 C 2H 2 C 2H 6 H 2 CH 4 CO TCG

    Gemini X 35 0.1 0.0 0.3 1.2 4.7 13.8 20.1FR3 50 20.9 0.0 16.9 1.7 6.7 14.4 60.7

    2.5.3.2 Thermal Test 2

    Mark designed a localized heating element test using a special material which linearly changed

    the resistor in a wide range of temperatures up to 550C [12]. Figure 2.16 shows Mark s test

    design. As shown in the figure below, the special material Resistherm is used as the heating

    element and put inside the oil-filled sealed test vessel. A funnel is set upside down to collect

    the generated fault gases; the fault gases will finally go into the top syringe and held there.

    Another syringe is used to release the pressure that is caused by the oil expansion during the

    test. The voltage across the heating element and the current that passes through it are recorded

    for temperature calculation.

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    46/176

    The heating element is maintained at 300C to 600C for 1 to 6 hours. Higher temperatures

    cannot be achieved due to the melting of the Resistherm. The DGA results for all tests in bothliquids are shown below in Table 2.8.

    Table 2.8 GIO DGA Results in both Liquids(a) GIO DGA Results in FR3

    Temperature

    (C ) Duration(h)DGA( l/J )

    CO 2 C 2H 4 C 2H 2 C 2H 6 H 2 CH 4 CO TCG300 6 1353 27 0 489 92 33 932 1573400 6 2973 209 0 934 278 214 4219 5854500 2 3698 631 0 1005 472 351 3095 5554600 1 3923 1061 0 1307 382 453 5148 8351

    (b) GIO DGA Results in Lyra X

    Temperature(C ) Duration(h)

    DGA( l/J )CO 2 C 2H 4 C 2H 2 C 2H 6 H 2 CH 4 CO TCG

    300 1.5 57 8 0 2 11 20 510 551400 1 169 198 38 7 70 149 687 1149

    It can be seen from the table that the total generated fault gases in Lyra X is around 5 times

    higher than that in FR3 under 400C thermal stress. CO and CO2 are the main generated fault

    gases under the thermal fault for both oils. C2H4, CH4 and C2H6 are also significant in FR3

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    47/176

    1. An expansion chamber which is maintained at atmospheric pressure. An insolation valve is

    installed between the connection of equipment 1 and 3.

    2. A pressure gauge.

    3. A gas chamber that can be sealed by the isolation valve.

    4. A liquid reservoir.

    5. A pump that circulates liquid between 4 and 6. .

    6. An oven.

    Figure 2.17 Thermal Test 3

    The natural ester (the soybean oil, the high oleic sunflower oil) and the mineral oil are all heatedfor 8 hours. The test results are shown below in Figure 2.18. It can be seen from Figure 2.18

    there is a 50C temperature difference for main fault gases yielding between the soybean oil

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    48/176

    (a) Gas Generation in Soybean Oil under Various Temperatures

    (b) Gas Generation in Oleic Sunflower Oil under various Temperatures

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    49/176

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    50/176

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    51/176

    Chapter 3 Experimental Study on DGA under Sparking Faults

    3.1 Introduction

    With the purpose of applying the standard diagnosis method for traditional mineral oil to

    alternative natural esters, the gas performances of a mineral oil, Gemini X, and a natural ester,

    FR3, are studied in this chapter under electrical sparking faults. A specially designed test vesselwith a good sealing capability was tested and used in this study, and the needle to plate

    electrode configuration was used to produce electrical sparking faults. It was found that the

    amount of fault gases is closely related with the fault energy; therefore the gas generation rate

    (per J) was considered as a good parameter to compare the gas performance between FR3 and

    Gemini X. The TM8 DGA monitor was used to measure the DGA results. Additionally, some

    oil samples were also sent to TJH2B for laboratory analysis in order to compare with online

    DGA methods. The results indicated that the two methods agree with each other with an

    acceptable deviation.

    3.2 Experiment Setup

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    52/176

    R1

    R2

    Test vesselVoltagedividerRatio

    10000:1

    TM8

    Over Current

    Protectionrelay5 A 240V/80kV

    Powerfrequency

    CTOutput

    V/A=1/100

    OutputV/A =1/10

    CT

    500 pF

    600 k Water resistor

    CT

    High frequency CT

    PC based TM8 control software

    The cage

    100 MHzoscilloscope 1

    100 MHzoscilloscope 2

    Oilinlet

    Oiloutlet

    Variac0-240 V

    Figure 3.1 Schematic View of Electrical Sparking Test Circuit

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    53/176

    60 current clamp, bandwidth from 40 Hz to 40 kHz) with a 1/100 output ratio was used to

    measure the power frequency component of the sparking current, and another high frequency

    current transformer (Stangenes pulse current transformer, model No. 0.5-0.1, Square Pulse

    Rise Time = 20 ns) with a 1/10 ratio was used to measure the high frequency component of the

    sparking current. The results of the two current transformers were combined together to get the

    total result of current.

    3.2.2 Test Vessel Design

    To generate a proper amount of fault gases, the gap distance between the needle-to-plate

    electrodes is chosen as 35 mm. The plate electrode was made of brass and has a diameter of 20

    mm. The needle electrode was a medical needle with a tip radius of curvature in the range from

    6-7 m from front view.

    3.2.2.1 Main Design Advantages

    To obtain a reliable result, the test vessel should be kept in a good sealing state and a complete

    oil circulation should be maintained in the test. As the photo of the test vessel that is shown inFigure 3.2, two design factors were tried in this thesis to keep the test working in sealed

    condition they are: inner cap and o rings The inner cap is a cap that placed right close to the

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    54/176

    (a) Design Diagram

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    55/176

    and outlet pipe are installed at the top/bottom of the test vessel to make sure that all oil is in

    the circulation loop. Finally, the tube between the inlet pipe of TM8 and the syringe adaptor

    was as short as possible to reduce the dead volume , since oil in this area is barely circulated

    and it represents dead volume .

    The syringe of 50 ml connecting to the top of the test cell is also used to remove the gas bubbles

    during test setup and also balance the inner system pressure with outside atmosphere pressure

    during test operation.

    3.2.2.2 Sealing Tests

    Two sealing tests are carried out to check whether the sealing state is qualified for both the

    electrical sparking and electrical partial discharge (PD) tests.

    Sealing test 1 is designed to check how much pressure difference between the inner and outside

    of the test vessel is reduced in a period of 23 hours. The setup of sealing test 1 is shown in

    Figure 3.3.

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    56/176

    and the test vessel was kept for a further 23 hours. Figure 3.4 plots the pressure difference with

    time (the pressure data is not recorded at night).

    Figure 3.4 Pressure Versus. Time of Sealing Test 1

    Sealing test 1 showed that the test vessel was in a good sealing state, and the pressure difference

    between the inside and the outside of the test vessel fell from 98 mbar to 89 mbar after 23 hours.

    This means only 10% gas leaked out within 23 hours and equivalent 0.4% in the first hour.

    Sealing test 2 aimed at finding out the relationship between pressure, gas volume and sparking

    numbers. A test circuit was built up according to Figure 3.1 (the TM8 was not connected in the

    circuit) with the same electrode configuration. The test vessel was fully filled with FR3. After

    50 sparking tests, a 51.5 mbar pressure difference was detected by the pressure gauge and the

    0

    2040

    60

    80

    100

    0 5 10 15 20 25

    Sealing test

    Pressure(mbar)

    Pressure(mbar)

    Time(h)

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    57/176

    Process transformer oil as described in Section 2.1.3. Drain oil out of the system. Clean test system, fill processed oil into the system (eliminate the headspace). Measure background gases. Generate sparking faults. Use syringe to push fault gases to be dissolved back into the oil circulation, and measure

    the amount of fault gases.

    Process and analyze test data.

    3.3.1 Drain Oil out of System

    After fresh oil is well processed, it needs to be filled into the TM8 test vessel system. To dothis, transformer oil from the previous test should be drained out first by TM8 which can pump

    oil forwards and backwards for several times (normally 2 times). Some of the oil trapped in

    TM8 would not be drained out easily if only forward pumping is applied; accordingly, pumping

    oil in both directions is helpful to remove the residual oil efficiently. Detail of the steps is

    described below.

    First of all, the oil inlet pipe of TM8 needs to be disconnected and put into a waste oil barrel.

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    58/176

    pipe of TM8 needs to be disconnected and put into the waste oil barrel while the oil inlet pipe

    needs to be taken out from the waste oil barrel and then put on to an empty oil beaker. Next,

    the pump oil 35 command needs to be used, making the oil pump rotate forwards at the

    maximum pumping speed. Wait around 10 minutes and repeat the pump oil backward and

    forward procedures again to make sure most of the oil is drained out from TM8. According to

    the test experiment, the previous dissolved gas residue can be reduced to less than 10% after

    this procedure.

    Sometimes the needle electrode needs to be changed before the processed oil is filled into the

    system. In the sparking test, the needle electrode needs to be changed only when the oil is

    changed from Gemini X to FR3. To change the needle electrode, the top brass cap nut needs

    to be screwed out first and then the needle fixer has to be released to remove the medical needle.

    A new medical needle is put into the needle fixer. The needle is carefully measured by ruler,making sure the gap distance is 35 mm.

    3.3.2 Clean Test System and Fill Processed Oil into the System

    Processed oil can be filled into the system after the previous oil residue was cleaned. The oiloutlet pipe of TM8 needs to be connected back to the bottom of the test vessel while the inlet

    i f TM8 d b i h d il l Th il l l f h

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    59/176

    system when the pressure is applied, the leakage place of the vessel or the connection must be

    checked and sealed.

    Normally the GIO concentration of previous test will reduce to nil after procedure 3.3.1,

    therefore the test system didnt require a formal clean procedure. However, the test system

    needs to be washed and cleaned by processed oil under two certain circumstances: (1) the GIO

    concentration is too high, i.e. several thousand ppm, (2) the next test oil type is different with

    previous one.

    In this two cases, the Procedure 3.3.1 and 3.3.2 needs to be repeated for a totally clean

    background.

    3.3.3 Measuring Background DGA level

    Before measuring the background dissolved gas value of test oil, the gas extractor chamber

    needs to be cleaned. Gas residue inside the gas chamber could be pumped out by using the xtr

    resume command and xtr gas.purge command in sequence, resuming TM8 extractor to

    normal operation state and then making the oil pump rotate forwards at the maximum speed.The pre command could be used to print out the gas chamber pressure; the gas chamber

    ill d d 3 i d h i b k d 15 i (1 h ) i hi

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    60/176

    During the sparking test, the output voltage was increased at a rate of 2 kV/s until a sparking

    (an interrupted breakdown) occurred. The reason 5 kV/s is applied is to avoid any sparking

    will be formed due to the fast increasing voltage. The sparking voltage and current (high

    frequency and power frequency) were recorded for further analysis. This procedure was

    repeated 15 times for each liquid sample.

    3.4

    Data Measurement and Analysis

    3.4.1 GIG and GIT

    As mentioned in Section 2.3.2, the TM8 on-line DGA monitor measures the amount of gases

    using the headspace method. The headspace method actually measures the amount of fault

    gases in the gas phase at equilibrium states and then calculates the amount of dissolved fault

    gases or the total amount of fault gases. The total amount of fault gases can be calculated by

    the Equation (2.1), in which GIT and GIG are the concentrations of total fault gases and fault

    gases in gas phase respectively. K, partition coefficient, is a ratio of GIO over GIG at

    equilibrium.

    The K under different temperatures and pressures can be derived from TM8 monitor. Figure

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    61/176

    FR3 Gemini X

    Figure 3.5 Partial Coefficients for FR3 and Gemini X

    In Equation (2.1), is the ratio of gas volume and oil volume inside the oil circulation system.

    In the sparking test and PD test , =V gas/Voil= 77 ml/ 2570 ml = 0.02996. P 0 is the equilibrium

    pressure given by the unit of psi and P is the pressure of one atmosphere that is equal to 14.67

    psi. T 0 is the oil temperature and T is the standard temperature that is equal to 25 C which is

    298.2 K.

    When the test data were plotted in Duval triangle, the GIG value should be converted into GIO

    value first. The way to calculate GIO is shown in Equation (3.1) [39].

    0.01

    0.1

    1

    10

    0 40 80 120 160

    H2

    N2

    CO

    O2

    CH4

    CO2

    C2H4

    C2H2C2H6

    C

    0.01

    0.1

    1

    10

    0 40 80 120 160

    H2

    N2

    CO

    O2

    CH4

    CO2

    C2H4

    C2H2C2H6

    C

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    62/176

    hour after the sparking test, and then it started to fluctuate and fell due to leakage, consumption

    and temperature change. On the other hand, the GIG values of C 2H4, C2H2, CH 4 and CO

    reached their peaks at the 3 rd hour after the sparking test. Since all the GIG values will reach

    their peaks within 3 hours, the average values around 3 rd hour (result from 2 nd 3rd and 4 th hours)

    after the test were reported as the final results in order to minimize the error. The GIT amount

    can be obtained as the difference between the background and the final results using the

    equation below:

    GIT = GIT average - GIT0.

    Taking H 2 value as an example, the background GIT value can be calculated as GIT = GIG

    (K + ) P/P 0 T 0/T = 48.4 ppm (K+0.02996) 14.3 psi/14.7 psi 298.2 K / 295.5 K.

    According to Figure 3.5, K = 0.044 when T is 22.3 C. Substitute K = 0.044 into the aboveEquation, we have GIT = 3.5 ppm.

    Following the same calculation step, the GIT1, GIT2 and GIT3 can be obtained as 135.3 ppm,

    152.1 ppm, 151.0 ppm. The average GIT is GIT average = (GIT1 + GIT2 + GIT3)/ 3 = (135.3

    ppm + 152.1 ppm + 151.0 ppm) / 3 = 146.1 ppm. Therefore, the total amount of H 2 generated

    during the test is GIT = GIT average - GIT0 = 146.1 ppm 3.5 ppm = 142.6 ppm.

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    63/176

    Table 3.2 Example GIT Concentration in Gemini X

    Mineral oil test 1 GIT (ppm)

    No. C 2H 4 C 2H 2 C 2H 6 H 2 O 2 CH 4 COGIT0 0 3 -0.7 3.5 21037.1 0 6.2GIT1 11.9 76 0 135.3 21111.9 11.3 5.8GIT2 15.2 93.7 0 152.1 21126.3 14.4 6GIT3 16.4 94.5 0 151 21030.5 14.5 7.5

    Average GIT 14.5 88.1 0 146.1 21089.6 13.4 6.4Generation GIT 14.5 85.1 0 142.6 52.5 9.8 0.3

    TDCG 252.2

    3.4.3 Sparking Energy Calculation

    The sparking energy for each test could be quite different even when the test condition was

    well controlled. As shown in Figure 3.1, the fault current was measured by using two current

    transformers with one in the power frequency (50 Hz) range and the other in the high frequency

    range (5 MHz). The voltage was measured using a voltage divider. Two 100 MHz oscilloscopes

    made by Lecroy were used to record low frequency signal and high frequency signal separately.

    High frequency sparking current and voltage signals were recorded with 500 k sample points

    at a 1 GHz sampling rate while power frequency sparking signals were recorded with a 500 k

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    64/176

    In Section 3.5, it could be found that the oscilloscopes were set to compensate the CT output

    ratio and as a result, thus the CT ratios have been taken in account in the recorded readings and

    therefore will not affect the calculation equation. On the other hand, as stated in section 3.1,

    the voltage divider is used to reduce the voltage to 1/10 k and the probe of the oscilloscope is

    also set to 10:1 in compensation, Equation (3.3) needs to be rewritten into Equation (3.4).

    W = ( ( ) ( ) )0 10000/10

    W = ( ( ) ( ) )0 1000 (3.4)

    3.4.3.1 High Frequency Component of Sparking Signal

    For the calculation of high frequency energy, the V (n) and I (n) were converted into absolute

    value since sparking in both the negative and positive direction will produce fault gases.

    Consequently, Equation (3.4) can be rewritten into Equation (3.5).

    W h = (| ( )| | ( )| )0 1000 (3.5)

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    65/176

    (a) 200 s time range (b) 2 s time range

    Figure 3.6 Example of High Frequency Component of Sparking Current

    3.4.3.2 Power Frequency Component of Sparking Signal

    For the calculation of power frequency energy, the power frequency current was measured in

    the primary winding side of the voltage supply transformer because the current is too small to

    be measured in the secondary winding side. Therefore, the measured current should be

    converted to the value at the secondary winding side by a factor of 240/ 80k. Equation (3.4)can be rewritten into Equation (3.6) to compute power frequency power.

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    66/176

    can be obtained by using the sparking energy W 1 (as shown in Figure 3.7) minus the

    corresponding background energy W 0.

    Figure 3.7 Example of Power Frequency Component of Sparking Current

    It should be noted that the power frequency current transformer (made by Chauvin Arnoux)

    has a frequency range from 40 to 10 kHz. Therefore, the high frequency noises should be

    filtered. A Matlab ellipse filter is applied to filter the current signals for two times. As shown

    in Figure 3.8, the high frequency noises contained in the original power frequency current (blue

    curve) were removed, leaving only the filtered power frequency current (red curve).

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    67/176

    Similar to the high frequency energy, Matlab is used to calculate the power frequency energy.

    500 k points are recorded for each sparking test and therefore n in Equation (3.6) is 500,000.

    The V[n] and I[n] are stored in two arrays and time step t = 1 ns.

    3.4.3.3 Sparking Types

    Since sparking (interrupted breakdown) is of the random nature, three different types of

    sparking were observed during the tests even under the similar test conditions. The sparking

    could be classified as normal sparking, slight sparking and continuous sparking as shown in

    Table 3.3.

    Table 3.3 Sparking TypesSparking type cut off or not dips before cut off

    Normal sparking Yes 1

    Slight sparking No 1Continuous sparking Yes 2 or more

    A normal sparking is followed by the interruption of the current relay, after which the applied

    voltage is cut off. A slight sparking is not followed by the interruption of the current relay, and

    the voltage is continuously applied on the sample liquid after having a slight voltage dip.

    Therefore, the energy of the slight sparking was not calculated since the amount of fault gases

    is small and the sparking energy is also small. A continuous sparking contains two or more

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    68/176

    3.4.3.4 Example of Sparking Energy Calculation

    To calculate the energy for each sparking test, firstly, the number of sparking faults should bedetermined. Secondly, the average high frequency power and power frequency power need to

    be used for group sparking energy estimation.

    For example, Table 3.4 shows the energy of Gemini X sparking test group 2. This group

    contains 13 normal sparking and 1 continuous sparking (including two consecutive sparking)

    which in total form 15 sparking in this group. When the double sparking occurred, the power

    frequency signal is completely recorded as shown in Figure 3.9 (c) while the high frequency

    pulse of the second consecutive sparking ( Sparking 10 b) is missed for the sampling period of

    the oscilloscope is too short (200 s) to catch the second pulse.

    Table 3.4 Example of Group Sparking Energy Calculation

    Test 2PF

    Energy(J)

    HFEnergy(J

    )Test 2 PF Energy(J) HF Energy(J)

    Sparking 1 1.77 2.02 Sparking 10 a4.93

    1.55

    Sparking 2 1.37 1.07 Sparking 10 b Missed

    Sparking 3 1.64 1.42 Sparking 11 1.75 1.73

    Sparking 4 1.63 1.79 Sparking 12 1.81 1.89Sparking 5 1.51 1.42 Sparking 13 2.04 2.3

    S ki 6 4 01 2 24 S ki 14 1 92 2 07

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    69/176

    On the other hand, the high frequency energy of sparking 10 only stands for the first

    consecutive sparking ( Sparking 10 a) whose energy (1.55 J) is close to the average value (1.75

    J). The sum of high frequency power is 15 average energy of high frequency energy (1.75 J)

    and such the total energy is 1.75 J 15 = 26.20 J. Group energy is the summary of total power

    frequency energy and high frequency energy which is 29.37 J +26.20 J = 55.57 J.

    3.5

    Test Condition and Observation

    Detail of the oscilloscope setting is listed below in Table 3.5. All 13 groups of test including

    13 15 normal sparking are controlled in the same conditions for a better comparison. In this

    setting, the oil volume of the whole TM8 test vessel system contains 2.57 L oil and 77 ml

    headspace.

    Table 3.5 Oscilloscope Settings

    Oscilloscope SettingPower frequency current High frequency current

    Channel 1 Channel 1 Voltage div 50 V Voltage div 50 V

    probe 10/1 probe 10/1Voltage divider ratio 1/10 k Voltage divider ratio 1/10 kChannel 2 Channel 3

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    70/176

    Gemini X requires higher energy for the incipient of sparking and will also generate a higher

    amount of gas bubbles after each sparking.

    3.6 Test Result and Analysis

    3.6.1 Gas Generation of Sparking Faults

    The amount of total fault gases is summarized in Figure 3.10 for both Gemini X and FR3.

    (a) GIT of Gemini X Tests

    0.050.0

    100.0

    150.0

    200.0

    250.0

    C2H4 C2H2 C2H6 H2 CH4 COTest group 1 14.5 85.1 0.0 142.6 9.8 0.3

    Test group 2 17.7 100.6 1.4 207.1 14.4 0.9

    Test group 3 18.0 103.3 1.8 211.6 14.3 2.0

    Test group 4 17.8 101.3 0.0 228.3 14.9 0.7

    Test group 5 15.6 90.4 0.5 156.4 12.9 1.2

    ppm

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    71/176

    It can be seen that the total amount of fault gases of Gemini X and FR3 are similar at about

    200 ppm. However, the fault gases generation of FR3 is relatively stable compared with GeminiX, and the fault gas amount varies in each group probably due to different energies even when

    the test condition was well controlled. Therefore, the sparking energy should be taken into

    account to compare the gas performance of different oils. Generally speaking, fault gas

    generation is relatively similar when the same numbers of sparking faults are applied. However,

    when the sparking energy is taken into consideration, the conclusion is varied slightly.

    3.6.2 Energy of Sparking Faults

    The calculated energy of each test is listed below in Table 3.6, using the energy calculation

    method described in Section 3.4.3.

    Table 3.6 Sparking Energy for Each Test Group inside Gemini X/ F R3

    Gemini X test group Average(J) Total(J) PF average(J) HF average(J)1 2.96 44.47 1.71 1.252 3.7 55.57 1.96 1.75

    3 3.52 52.74 1.77 1.754 3.65 54.79 1.76 1.895 3.6 54.05 1.73 1.87

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    72/176

    The sparking energy for each test group is different with the maximum deviation of 20%. FR3

    has a 20% lower energy compared with Gemini X. The difference of the energy is mainly

    attributed to the high frequency component of the sparking faults, since the difference of high

    frequency component energy for Gemini X and FR3 is 48% while that of power frequency

    component energy is only 9%.

    3.6.3 Gas generation rate (per J)

    Figure 3.11 shows the amount of gas generation rate (per J) for Gemini X and FR3. It can be

    noticed that the gas generation rate (per J) was different from the total gas amount as shown in

    Figure 3.10. Taking H 2 generation of Gemini X test as an example, the H 2 generation of test

    group 5 (156.4 ppm) is larger than that of test group 1 (142.6 ppm) in Figure 3.10; however,

    the H 2 generation (per J) of test group 5 (3.0 ppm / J) is less than that of test group 1 (3.2 ppm

    / J) in Figure 3.11.

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    73/176

    (a) Gas generation rate (per J) in Gemini X tests

    0.0

    2.0

    4.0

    6.0

    8.0

    C2H4 C2H2 C2H6 H2 CH4 CO TDCGTest group 1

    0.3 1.9 0.0 3.2 0.2 0.0 5.6Test group 2 0.3 1.9 0.0 3.9 0.3 0.0 6.5

    Test group 3 0.4 2.0 0.0 4.2 0.3 0.0 7.0

    Test group 4 0.3 1.9 0.0 4.4 0.3 0.0 6.9

    Test group 5 0.3 1.8 0.0 3.0 0.2 0.0 5.4

    Average of groups 0.3 1.9 0.0 3.7 0.3 0.0 6.3

    ppm/ J

    4.00

    6.00

    8.00

    10.00

    12.00 ppm/ J

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    74/176

    It can also be seen from Figure 3.11 that the gas generation rate (per J) is repeatable for all

    groups. For both liquids, H 2 is the main fault indicator which takes up to 60% of the total fault

    gases, followed by C 2H2 which takes up to 25% of the total fault gases. However, CO is only

    significant in FR3 which always takes up to 12% of total fault gases, which probably due to

    the ester part in the FR3 molecular structure.

    3.6.4 Absolute Gas generation rate (per J)

    When considering the oil volume of the test system (2.57 L), the gas generation rate in the unit

    of ppm/J can be calculated into the absolute gas generation rate in the unit of l/J , as listed in

    Table 3.7. It can be seen from Table 3.7 that the gas generation rates of the sparking fault reach

    21 l/J for FR3 and 16 l/J for Gemini X, which is comparable with that of Dr. X. Wang s test

    conclusion. [10]

    Table 3.7 Absolute GIT Generation Rate ( t /J) of Sparking TestsOil Test J/BD ppm/BD ul/BD ppm/J ul/J ml/test

    GeminiX

    1 3.0 16.8 43.2 5.59 14.4 0.652 3.5 22.8 58.6 6.46 16.6 0.883 3.4 23.4 60.1 6.96 17.9 0.904 3.5 24.2 62.2 6.94 17.8 0.935 3.4 18.5 47.5 5.37 13.8 0.71

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    75/176

    Figure 3.12 GIT Generation rate (per J) Comparison between Gemini X and FR3

    It can be seen that the sparking faults in FR3 generates 33% higher amount of total fault gases

    than that in Gemini X. The amount of H 2 in FR3 is 27% higher than that in Gemini X, while

    the amount of C 2H2 in FR3 is 16% higher. Furthermore, CO takes up to 12% in FR3 while it

    is almost 0 for Gemini X.

    0.0

    1.0

    2.0

    3.0

    4.0

    5.0

    6.0

    7.0

    8.0

    9.0

    C2H4 C2H2 C2H6 H2 CH4 CO TDCGGemini X 0.3 1.9 0.0 3.7 0.3 0.0 6.3

    FR3 0.3 2.2 0.0 4.7 0.2 1.0 8.4

    ppm/ J

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    76/176

    Table 3.8 GIO Generation Rate (ppm/J)

    Mineral oil GIO DGA(ppm)

    C 2H 4 C 2H 2 C 2H 6 H 2 CH 4 CO TDCG

    Test group 1 14.2 82.7 0 84.9 9 0.2 191.1

    Duval ratio 13.40% 78.10% 8.50%

    Test group 2 17.4 97.8 1.4 123.4 13.3 0.7 254.1

    Duval ratio 13.50% 76.10% 10.40%

    Test group 3 17.6 100.4 1.8 125.9 13.2 1.6 260.6

    Duval ratio 13.40% 76.50% 10.10%

    Test group 4 17.8 101.3 0 228.3 14.9 0.7 363.1

    Duval ratio 13.30% 75.60% 11.10%

    Test group 5 15.2 87.9 0.5 93.7 1191.20% 1 210.1

    Duval ratio 13.20% 76.40% 10.40%

    FR3GIO DGA(ppm)

    C 2H 4 C 2H 2 C 2H 6 H 2 CH 4 CO TDCG

    Test group 1 14.2 91.3 0.6 123.1 5.8 33.2 268.1

    Duval ratio 12.80% 82.10% 5.20%

    Test group 2 11.4 83.5 0.1 123.4 5.7 30.2 254.3

    Duval ratio 11.40% 83.00% 5.70%

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    77/176

    that the Duval triangle plots for different tests of the same oil are quite close to one another,

    indicating that the test repeatability is good. It can be seen that the sparking faults in Gemini X

    and FR3 were all plotted in D1 area (low energy discharge), indicating that the energy of

    sparking faults was not very high because the sparking current was interrupted by the current

    protection relay immediately after the fault occurred. Therefore, a continuous arcing path could

    not be formed in the oil.

    Figure 3.13 Duval Triangle Evaluation (GIO) of Sparking Fault in Gemini X and FR3

    3.6.7

    Laboratory DGA and Online Monitor Comparison

    To make sure that the results from TM8 are reliable some of the oil samples are sent to TJH2B

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    78/176

    Table 3.9 Comparison of GIO Results between TM8 and Laboratory Analysis

    Oil type GIO (ppm)

    FR3 C 2H 4 C 2H 2 C 2H 6 H 2 O 2 CH 4 COTM8 sample 24 197.3 3 80.4 14190.4 12.1 53.5

    Laboratory sample 19 151 3 59 59060 8 34Laboratory / TM8 79.08% 76.52% 99.84% 73.43% 416.20% 65.91% 63.60%

    3.7 Summary

    In this chapter, the amount of total fault gases in FR3 and Gemini X are measured using a

    sealed online DGA test system.

    The main summaries are listed as follows:

    1. FR3 generates a similar amount of fault gases to Gemini X under sparking faults.

    2. Considering the sparking energy, FR3 generates fault gases (per J) 25% higher than

    Gemini X.

    3. The fault gas generation (per J) might be a more reasonable parameter to evaluate the

    gas performances of different liquids.4. The Duval triangle method can recognize these sparking faults as low energy

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    79/176

    Chapter 4 Experimental Study on DGA under PD Faults

    4.1 Introduction

    In this chapter, the electrical partial discharge (PD) faults is studied using the needle to plate

    electrodes and the online DGA monitor and oil circulation system which is similar to the one

    described in last chapter. Although in previous publications the PD faults was usually presented

    by the PD amplitude [11], it is found in this chapter that the PD energy can be correlated with

    the amount of s gases much better. As a result, the gas generation rate (versus energy) is proved

    to be a useful parameter to show the gas performances of Gemini X and FR3. In order to

    compare the DGA results between online and laboratory methods, some oil samples were also

    sent to TJH2B for laboratory analysis.

    4.2 Experiment Setup

    The experimental setup of PD test is similar to the sparking test, as shown in Figure 4.1. The

    same test container was connected with the TM8 online monitor using the same method,

    providing a good sealing capability of the oil circulation system. However, the distance

    between the needle and plate electrodes was increased to 50 mm. Furthermore, the PD signals

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    80/176

    R1

    R2

    Test vesselVoltagedividerRatio

    10000:1

    TM8

    Over CurrentProtection relay

    6.5 A

    240 V/80 kV

    500 pF

    600 k Water resistor

    PC based TM8 control software

    The cage

    100 MHzoscilloscope

    Oilinlet

    Oiloutlet

    Zm

    Measuring

    impedence

    500 kHz PC based PD

    detector

    Variac0-240 V

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    81/176

    Clean test system, fill processed oil into the system (eliminate the headspace). (Chapter

    3.3)

    Calibrate PD detector. Measure the background gases. Generate PD faults. Measure the amounts of fault gases. Data processing and analysis.

    4.3.1 Calibrate the PD Detector

    A PD experiment system is required to be calibrated and PD background noise needs to be

    measured before the start of test.

    To calibrate the LEMKE LDS-6 PC based PD detector, both the PD amplitude and voltage

    readings need to be calibrated. The PD calibrator was connected in parallel to the test vessel in

    order to apply a 50 pC PD signal to the test vessel. The PD detector will then be used to check

    and calibrate the measured signal to see if it is 50 pC. The PD calibrator needs to be removed

    and a 30 kV voltage will be applied to the test vessel. The measured voltage from the PD

    detector was checked and adjusted until the voltage reading matches that of the oscilloscope.

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    82/176

    4.3.2 Measuring Background PD Noise

    Before the PD test, the maximum background PD noise signal in air should be determined. Theneedle electrode was firstly removed, and the test circuit was set up as shown in Figure 4.1.

    Then, the maximum applied voltage of 60 kV was applied to the test vessel. The PD signal was

    recorded for 1 minute and the result are shown in Figure 4.3.

    As we can see from Figure 4.3, the maximum PD noise in FR3 under 60 kV is only 30 pCwhich is extremely low in comparison with 4000 pC PD amplitude when the needle electrode

    is installed. For this case, the background PD noise could be ignored since the noise is much

    lower than the noise cutoff level when the needle electrode is in use. The noise cutoff level was

    used to remove the background noise in the PD test, and the detail is described in Section

    4.4.2.1.

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    83/176

    is of vital importance for a reliable test result. For this reason, anything could reduce the

    dissolved gas concentration such as (1) leakage caused by oil flow or (2) gas consumption

    caused by TM8 sampling must be prevented.

    To generate a PD fault, the applied voltage is raised at the rate of 2 kV/s until the target voltage

    is reached. The voltage is then kept for a certain period of time according to the fault gas

    generation rate of each liquid. In FR3 test, because the PD repetition rate is high, the PD signal

    was recorded for 1 minute in every 15 minutes; On the other hand, the PD signal in Gemini Xtest was recorded from the beginning to the end due to a much lower repetition rate. The test

    voltage was reduced to zero after the test is finished. Then the oil valves were re-opened and

    the oil circulation was resumed before the measurement of fault gases by TM8.

    4.4 Data Measurement and Process Method

    4.4.1 Total Gas Generation Calculation

    The calculation method of total fault gases is almost the same as that described in Section 3.4.

    The only difference between the total gas generation calculation of the sparking test and the

    PD test is that the GIT and GIO are calculated by the peak value instead of the average value.

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    84/176

    Figure 4.4 Example of PD Test DGA Peak Value

    The H 2 is the most significant and easy-leaking gas among all generated fault gases. The H 2

    peak is therefore chosen as the sign for peak value to obtain a maximum H 2 reading. As we

    can see from Figure 4.4, the H 2 (dark blue curve) reaches a peak in 4 hours after the test.

    Therefore, the readings of fault gases at the 4th

    hour after the test should be used as the results.

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    85/176

    noted that the noise of the PD signal should be filtered out via LDS-6 PD measurement software

    before the calculation.

    4.4.2.1 Instrument Noise Filtering

    During the PD recording, the PD detector was able to remove the small PD noises. This was

    achieved by applying a cut-off level manually provided by the operator, and any PDs or noises

    with magnitude less than the threshold level was removed. The cut-off level was determined

    as a level slightly higher than the PD noise, i.e. a cut-off level of 50 pC based on the noise

    result in Figure 4.3. Figure 4.5 shows the effect of noise filtering of a 44 kV test of FR3. As

    shown in Figure 4.5, the filtered PD signal (Figure 4.5 (b)) was obtained by removing the noises

    less than 130 pC in the recording of all signals (Figure 4.5 (a)).

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    86/176

    W = (4.1)

    where the unit of Q is pC and the unit of V is kV. If we convert the pC to C, kV to V, Equation

    (4.1) can be rewritten into Equation (4.2) to get the energy in J.

    W = (4.2)

    In order to judge the PD energy distribution to each band of PD amplitude, the PD energy is

    calculated according to 6 PD amplitude bands: 0-1000 pC, 1000-2000 pC, 2000-3000 pC,

    3000-4000 pC, 4000-5000 pC, and 5000- 6000 pC (barely used). The Find function of Matlab

    will be used here to pick out these PD that are within the proper amplitude band. Equation (4.2)

    is still capable for PD energy computation after the qualified PDs are picked out by the Findfunction.

    In order to calculate the overall PD energy, the PD power should be obtained by following

    Equation (4.3) and linearly extrapolated to the overall period.

    P = W/ t (4.3)

    S b tit t E ti (4 2) i t E ti (4 3) h

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    87/176

    As stated at the beginning of Chapter 4.4, the PD signal is recorded into several individual PD

    files, after the power of each individual file is calculated by Equation (4.5); the average power

    needs to be acquired by Equation (4.6):

    (4.6)

    Lastly, the PD energy can now be computed by Equation (4.7):

    (4.7)

    Where t total is the full time duration for each PD test. Equation (4.7) is used to compute the total

    PD faults energy by Excel, example shown in next Section.

    4.4.2.3 Example of PD Energy Calculation

    Table 4.1 presents the detail of PD files of the 2000 pC Gemini X PD test which lasts for 1380

    minutes. This continuous PD test is separated into 5 PD files. The PD detector recorded 5 PD

    files for this continuous PD test with a 60 minutes interval. In this case, according to Equation(4.6), the average power P average of all PD files is equal to (0.02mW*60minutes +

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    88/176

    Table 4.1 Example of PD Test Energy Calculation

    PD file of Gemini X test3

    Recordingduration

    (minutes)

    PD power(mW) Energy(J)

    1 60 0.02 0.082 60 0.08 0.303 60 0.12 0.44

    4 120 0.12 0.865 1020 0.06 3.63

    6(not recorded) 60 0.07(notrecorded)0.3(not

    recorded)Total 1380 0.07 5.61

    4.5 Test Condition and Observation

    Table 4.2 shows the list of PD tests. It can be seen that 4 PD tests were carried out in Gemini

    X with the PD amplitude of 1500 pC, 2000 pC, 3000 pC and 4000 pC. On the other hand, 8

    PD tests were carried out in FR3 with the PD amplitude from 1000 pC to 4000 pC. The PD

    faults were applied for different test durations (from 62 minutes to 2880 minutes) until a proper

    amount of fault gases was generated Details of the test conditions are listed in Table 4 2

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    89/176

    Table 4.2 List of PD Tests

    Oil TestTest

    Voltage(kV)

    Test duration

    (minutes)

    PD

    amplitude

    (pC)

    Needle

    Gemini X

    1 50 2880 1500 New

    2 50 2580 3000 After test 1

    3 58 1380 2000 New

    4 58 1290 4000 After test 3

    FR3

    1 34 390 1000 New

    2 34 360 1000 New

    3 44 180 2000 New

    4 44 235 2000 After test1

    5 57 70 3000 After test 3

    6 57 150 3000 After test 5

    7 57 70 3000 New

    8 61 62 4000 After test 7

    All headspace is eliminated from the test vessel before the test started. The oil and headspace

    volume of the whole TM8-test vessel system are 2 57 L oil and 77 ml which is the same as the

  • 8/12/2019 Study of Dissolved Gas Analysis Under Electrical & Thermal Stresses for Oil

    90/176

    Figure 4.6 shows the gas generation rate per hour for Gemini X (Figure 4.6 (a)) and FR3

    (Figure 4.6 (b)). The result of FR3 shows in Figure 4.6(b) is the average of two tests with the

    same PD magnitude.

    (a) Gas generation per hour in Gemini X

    0.01.02.0

    3.04.05.06.0

    C2H4 C2H2 C2H6 H2 CH4 CO TDCG1500pC 0.0 0.1 0.0 0.1 0.0 0.1 0.4

    2000pC 0.0 0.5 0.0 0.7 0.1 0.2 1.5

    3000pC 0.1 0.3 0.1 0.6 0.1 0.1 1.2

    4000pC 0.3 1.2 0.2 3.2 0.6 0.2 5.6

    ppm/h

    100.0

    150.0

    200.0