STRUCTURAL DESIGN CRITERIA
1. GOVERNING CODE: 2009 IBC
2. FLOOR LIVE LOAD (1603.1.1) N/A
3. ROOF LIVE LOAD (1603.1.2)
MINIMUM ROOF LIVE LOAD: 20 PSF
4. ROOF SNOW LOAD (1603.1.3)
GROUND SNOW LOAD: PG = 25 PSFFLAT-ROOF SNOW LOAD: PF = 17.5 PSFSNOW EXPOSURE FACTOR: CE = 1.0SNOW LOAD IMPORTANCE FACTOR: IS = 1.0THERMAL FACTOR: CT = 1.0
5. WIND DESIGN DATA (1603.1.4)
BASIC WIND SPEED (3-SECOND GUST): V3S = 90 MPHOCCUPANCY CATEGORY: IIWIND IMPORTANCE FACTOR: IW = (VALUE)WIND EXPOSURE: CINTERNAL PRESSURE COEFFICIENT: GCPI = +/- 0.55
6. EARTHQUAKE DESIGN DATA (1603.1.5)
OCCUPANCY CATEGORY: IIIMPORTANCE FACTOR: IE = 1.0
MAPPED, MCE, 5% DAMPED, SPECTRAL ACCELERATIONS:AT SHORT PERIODS: Ss = 0.193 GAT A PERIOD OF 1 SECOND: S1 = 0.067 G
SITE CLASS: C
DESIGN EARTHQUAKE SPECTRAL ACCELERATIONSAT SHORT PERIODS: SDS = 0.155 GAT A PERIOD OF 1 SECOND: SD1 = 0.076 G
SEISMIC DESIGN CATEGORY: SDC = BBASIC SEISMIC-FORCE-RESISTING-SYSTEM: SFRS = PER CONTRACTOR
7. FLOOD DESIGN DATA (1603.1.6)
BUILDING IS NOT LOCATED IN FLOOD HAZARD AREA; THEREFORE FLOODDESIGN DATA IS NOT REQUIRED
8. SPECIAL LOADS (1603.1.7)
SPECIAL LOADING CONDITIONS ARE NOT APPLICABLE TO THE DESIGN OFTHIS BUILDING; THEREFORE SPECIAL LOADS ARE NOT REQUIRED
9. SPECIAL INSPECTIONS FOR SEISMIC RESISTANCE (1603.1.8)
BUILDING IS DESIGNATED SEISMIC DESIGN CATEGORY B; THEREFORESPECIALINSPECTIONS FOR SEISMIC RESISTANCE ARE NOT REQUIRED.
FOUNDATION NOTES
NET ALLOWABLE SOIL BEARING PRESSURE = 3000 PSF PER GEOTECHNICAL REPORT.
F-1. ALL COLUMN FOOTINGS ARE TO BE CENTERED UNDER COLUMN CENTERLINES,UNLESS NOTED OR DETAILED OTHERWISE.
F-2. THE FOUNDATION CONTRACTOR SHALL FULLY REVIEW UNDER-GROUNDPLUMBING DRAWINGS AND SHALL COORDINATE WITH THE UNDER-GROUNDPLUMBING CONTRACTOR TO DEPRESS FOOTINGS AND PROVIDE PIPE SLEEVESTHROUGH FOUNDATION WALLS AS NECESSARY TO ACCOMMODATE PLUMBINGLINES OR TRAPS WHICH PENETRATE CONCRETE FOOTINGS OR FOUNDATIONS.
F-3. PROVIDE PVC SLEEVES THROUGH FOUNDATION WALLS/FOOTINGS FOR PIPE,CONDUIT, AND CABLE PENETRATIONS, INCLUDING ELECTRICAL GROUNDINGSYSTEM CABLES. SEE APPROPRIATE DRAWINGS FOR LOCATIONS/SIZES.PLACE SLEEVES IN LOCATIONS TO AVOID DISPLACING REINFORCING STEEL.
F-4. FOOTING SUBGRADES SHALL BE CLEAN AND FREE OF DEBRIS, STANDINGWATER, AND LOOSE SOIL.
F-5. COORDINATE WITH ARCHITECTURAL AND CIVIL DRAWINGS FORMISCELLANEOUS FOUNDATIONS NOT SHOWN ON STRUCTURAL DRAWINGS.
F-6. CONTROL JOINTS IN THE CAST-IN-PLACE CONCRETE FOUNDATION WALLSSHALL BE PLACED AT SPACING NOT TO EXCEED 20' O.C. OR AS LOCATEDPER DRAWINGS AND SHOULD ALIGN WITH MASONRY CONTROL JOINTSWHERE APPLICABLE. SEE DETAIL SHEETS FOR CONTROL JOINT DETAILS.PROVIDE VERTICAL "V" GROOVE AT ALL CONSTRUCTION AND CONTROLJOINTS. CONTRACTOR SHALL SUBMIT PLANS OF JOINT LOCATIONS FORAPPROVAL.
F-7. SEE TYPICAL SLAB-ON-GRADE DETAILS FOR SLAB AND SUB-BASEREQUIREMENTS. THESE WILL BE TYPICAL THROUGHOUT UNLESS NOTEDOTHERWISE.
F-8. A LEAN CONCRETE MUD SLAB 2" TO 3" THICK SHALL BE USED IN THE FOOTINGEXCAVATION IF THE BOTTOM OF THE EXCAVATION TENDS TO BECOME MUDDYAND SOFT DUE TO CONSTRUCTION ACTIVITY. LEAN CONCRETE SHALL HAVE AMINIMUM 28 DAY COMPRESSIVE STRENGTH OF 2000 PSI.
F-9. COORDINATE GROUNDING REQUIREMENTS FOR FOUNDATION/FOOTINGREINFORCING STEEL WITH ELECTRICAL DRAWINGS. COORDINATEINSTALLATION OF GROUNDING WIRES/EQUIPMENT WITH ELECTRICALCONTRACTOR PRIOR TO CASTING CONCRETE.
CONCRETE & REINFORCING STEEL NOTES
MATERIAL PROPERTIES (U.N.O.)COMPRESSIVE STRENGTH - F'c = 4 KSICONCRETE REINFORCEMENT - Fy = 60 KSI (A615 GR 60)
CR-1. PROVIDE ONE (1) HOOKED REINFORCING BAR IN CONCRETE FLOOR SLABTO SERVE AS A “CONCRETE ENCASED ELECTRODE” IN ACCORDANCEWITH THE NATIONAL ELECTRIC CODE. COORDINATE WITH ELECTRICALCONTRACTOR FOR EXACT LOCATION. HOOKED REINFORCING BAR SHALLCONFORM TO THE FOLLOWING:
A. UNCOATED, LOW-ALLOY STEEL, CONFORMING TO ASTM A706.B. BAR SIZE NUMBER 4.C. HOOKED AT ONE END ONLY.D. MINIMUM HORIZONTAL LENGTH OF REINFORCING BAR ENCASED IN
CONCRETE SLAB SHALL BE 20’-0”.E. MINIMUM VERTICAL PROJECTION OF REINFORCING BAR HOOK ABOVE
CONCRETE SLAB SHALL BE 1’-8”.F. MINIMUM COVER ALL AROUND REINFORCING BAR SHALL BE 2”.
CR-2. ALL BAR LAPS SHALL CONFORM TO ACI 318 CLASS "B" SPLICE CRITERIA.USE TOP BAR LAP LENGTHS FOR TOP BARS IN SLABS AND BEAMS OVER14" DEEP. MINIMUM BAR LAPS AS FOLLOWS U.N.O.:
#3: 1'-4" #4: 1'-4" #5: 1'-10" #6: 2'-7" #7: 4'-2"#8: 5'-2" #9: 6'-4" #10: 7'-8" #11: 9'-0"
FOR EPOXY COATED BARS, PROVIDE 1.5 TIMES THE INDICATED LAP LENGTH.FOR TOP BARS PROVIDE 1.3 TIMES THE INDICATED LAP LENGTH.
CR-3. LAP LENGTH SHALL BE SPECIFICALLY NOTED ON SHOP DRAWINGSWHERE MORE THAN ONE BAR MAKES UP A CONTINUOUS STRING.
CR-4. HORIZONTAL BARS SHALL BE DETAILED TO SHOW THE DISTANCE FROMAT LEAST ONE END OF THE BAR TO THE NEAREST BUILDING GRID LINEOR WALL.
CR-5. REINFORCING SHALL BE DETAILED IN ACCORDANCE WITH ACI 315.
CR-6. ALL REINFORCEMENT BARS SHALL BE FABRICATED IN ACCORDANCEWITH THE LATEST CRSI MANUAL OF STANDARD PRACTICE AND SHALL BECLEAN AND FREE OF GREASE AND SCALING RUST.
CR-7. CONTINUOUS TOP AND BOTTOM BARS, WHEN SHOWN IN TRANSVERSESECTION ONLY, SHALL BE LAPPED AS FOLLOWS:
TOP BARS NEAR MID-SPANS;BOTTOM BARS DIRECTLY OVER SUPPORTS, U.N.O.
CR-8. HOOK HORIZONTAL WALL AND BEAM REINFORCING BARS ATDISCONTINUOUS ENDS, TYPICAL U.N.O. EXTEND REINFORCEMENTTO FAR FACE OF PIERS/PEDESTALS AND/OR COLUMNS U.N.O.
CR-9. PROVIDE HOT/COLD WEATHER PROCEDURES AND PROTECTIONIN ACCORDANCE WITH ACI RECOMMENDATIONS AND PROJECTSPECIFICATIONS.
CR-10. CONCRETE REINFORCEMENT PROTECTION/CLEAR COVER, U.N.O.:
FOOTINGS:BOTTOM & SIDES 3"TOP 2"
WALLS:EXTERIOR EXPOSURE 2"INTERIOR EXPOSURE 1"
BEAMS/COLUMNS:OVER TIES OR STIRRUPS 1 1/2"
ELEVATED SLABS: 1"
CR-11. PROVIDE ADDITIONAL #5 BARS AT 4'-0" LONG 3" BELOW TOP OFSLAB AT 45° TO ALL REENTRANT CORNERS AND OPENINGS INCONCRETE SLABS AND AS SHOWN.
CR-12. ALL CONCRETE FOUNDATION WALLS SHALL HAVE A MINIMUM OF(2) #5 BARS CONTINUOUS TOP AND BOTTOM, UNLESS NOTED ORDETAILED OTHERWISE.
CR-13. EXTEND ALL PIER STEEL TO PROVIDE STD. HOOK UNDER FOOTINGREINFORCEMENT, UNLESS NOTED OTHERWISE.
CR-14. ALL CONCRETE DESIGN AND CONSTRUCTION SHALL CONFORM WITHTHE LOCAL BUILDING CODE REQUIREMENTS AND THOSE OF THEFOLLOWING STANDARDS (LATEST EDITION):
"ACI 318, BUILDING CODE REQUIREMENTS FOR REINFORCED CONC.""ACI 315, DETAILS AND DETAILING OF CONCRETE REINFORCEMENT""ACI 301, SPECIFICATIONS FOR STRUCTURAL CONCRETE FOR BLDGS.""ACI 307, RECOMMENDED PRACTICE FOR CONCRETE FORM WORK"
CR-15. SEE SECTION 033000 OF SPECIFICATIONS FOR INFORMATION REGARDINGCONCRETE MIX DESIGN, TESTING, MATERIALS, AND ADMIXTURES.
CR-16. ALUMINUM CONDUIT IS NOT PERMITTED TO BE EMBEDDED IN CONCRETE.
CR-17. REFER TO FLATWORK DRAWINGS AND/OR SPECIFICATIONS FORSLAB-ON-GRADE FINISH TYPES AND DEPRESSIONS REQUIRED FOR MATS,TILE, AND OTHER FINISH MATERIALS.
CR-18. PROVIDE FOOTING DOWELS TO MATCH VERTICAL WALL REINFORCING.WHERE WALL REINFORCING IS NOT INDICATED, DOWEL FOOTING TOFOUNDATION WALLS WITH #5 REBAR AT 16" O.C. BY 3'-0" LONG, WITHSTANDARD HOOKS EMBEDDED A MINIMUM OF 9" INTO FOOTING.
CR-19. ALL PIER FOOTINGS TO HAVE DOWELS WITH STANDARD HOOKS OF SAMESIZE AND QUANTITY AS PIER STEEL. DOWELS TO LAP PIER STEEL ASREQUIRED FOR A CLASS "B" TENSION SPLICE.
CR-20. ALL OPENINGS IN CONCRETE FOUNDATION WALLS ARE TO HAVE (4) #5DIAGONAL BARS EACH FACE OF THE WALL UNLESS OTHERWISE NOTED.BARS SHALL EXTEND 2 FEET BEYOND OPENING ON EACH SIDE.
CR-21. UNLESS NOTED OTHERWISE, THICKEN THE SLAB-ON-GRADE BENEATHINTERIOR MASONRY PARTITIONS 8 INCHES BELOW BOTTOM OF SLAB ONGRADE. THICKENED PORTION TO EXTEND 8 INCHES BEYOND THE FACEOF THE WALL ON EACH SIDE. REINFORCE THE THICKENED PORTION WITH(3) #5 CONTINUOUS LONGITUDINAL REINFORCING BARS AND #5 TRANSVERSEBARS AT 16" O.C., U.N.O.
CR-22. PITCH CONCRETE TO FLOOR DRAINS. COORDINATE WITH PLUMBING ANDARCHITECTURAL DRAWINGS.
CR-23. UNLESS NOTED OTHERWISE, PROVIDE CONTROL OR CONSTRUCTION JOINTSIN SLABS-ON-GRADE AT 15 FOOT MAXIMUM CENTERS EACH DIRECTION.CONTRACTOR SHALL SUBMIT PLANS OF JOINT LOCATIONS TO THEARCHITECT/ENGINEER FOR APPROVAL PRIOR TO CASTING SLABS-ON GRADE.COORDINATE WITH ARCHITECTURAL DRAWINGS AND FLOOR FINISHES SUCHAS TILE AND TERRAZZO.
GENERAL NOTES
G-1. FIELD VERIFY ALL DIMENSIONS AND EXISTING CONDITIONS PRIOR TO STARTOF CONSTRUCTION - RESOLVE ANY DISCREPANCY WITH ARCHITECT/ENGINEER.
G-2. FOR CLARITY, ALL EXTERIOR SLABS AND SIDEWALKS MAY NOT BE SHOWN.FOR EXACT DIMENSIONS, LOCATIONS, JOINTS AND SCORE LINES, SEEARCHITECTURAL AND/OR CIVIL DRAWINGS.
G-3. VERIFY ALL SIZES, WEIGHTS AND LOCATIONS OF MECHANICAL AND ELECTRICALEQUIPMENT, ROOF PENETRATIONS, DUCTS, ETC. WITH MECHANICAL ANDELECTRICAL CONTRACTORS AND FIELD CONDITIONS.
G-4. DETAILS MARKED "TYPICAL" MAY OR MAY NOT BE CUT ON PLANS, BUT SHALLAPPLY UNLESS NOTED OTHERWISE.
G-5. STRUCTURAL SYSTEM IS DESIGNED TO WORK AS A COMPLETED SYSTEM, ANYSHORING OR BRACING NECESSARY DURING CONSTRUCTION SHALL BE THERESPONSIBILITY OF THE GENERAL CONTRACTOR.
G-6. SEE ARCHITECTURAL, MECHANICAL, ELECTRICAL, AND PLUMBING PLANS FORSLEEVES, INSERTS, ETC. NOT SHOWN ON STRUCTURAL PLANS.
G-7. NO PIPES OR SLEEVES FOR MECHANICAL TRADES SHALL PASS THROUGHSTRUCTURAL MEMBERS WITHOUT APPROVAL OF THE STRUCTURAL ENGINEER.
G-8. THE CONTRACTOR IS SOLELY RESPONSIBLE FOR ALL SITE SAFETY AND ALLACCIDENTS WHICH RESULT IN DEATH, PERSONAL INJURY, OR DAMAGE TOPROPERTY ARISING OUT OF OR IN CONNECTION WITH THE PERFORMANCE OFTHE WORK.
G-9. IT IS THE OWNER'S RESPONSIBILITY TO POST LIVE LOADS PER SECTION 1603.3OF THE GOVERNING CODE.
G-10. SECTIONS, DETAILS, AND NOTES SHOWN ON THE DRAWINGS ARE INTENDEDTO BE TYPICAL AND SHALL APPLY TO SIMILAR CONDITIONS ELSEWHERE,UNLESS OTHERWISE SHOWN.
DO NOT SCALE DRAWINGS!!!!
EARTHWORK NOTES
EW-1. SEE GEOTECHNICAL REPORT AND SPECIFICATIONS FOR DEFINITION OFMATERIALS AND COMPACTION REQUIREMENTS.
EW-2. U.N.O., THE CONTRACTOR SHALL RETAIN AN INDEPENDENT, QUALIFIEDGEOTECHNICAL ENGINEERING FIRM/TESTING AGENCY TO IDENTIFY AREASOF POOR SOILS, TO MONITOR PROPER SUBGRADE PREPARATIONS AND TOOVERSEE AND TEST THE PLACEMENT OF COMPACTED FILL MATERIAL.
EW-3. ALL SUBTERRANEAN STRUCTURES, UTILITIES, PIPING, ETC. IIN THE AREAOF EXCAVATIONS TO BE LOCATED AND MARKED BY CONTRACTOR PRIORTO EARTH REMOVAL WORK. CONTRACTOR TO MAINTAIN MARKERS UNTILEXCAVATION ACTIVITIES HAVE CEASED. IF UNDERGROUND UTILITYCONFLICTS ARE DISCOVERED BEFORE OR ENCOUNTERED DURINGEXCAVATION, NOTIFY THE ARCHITECT/ENGINEER IMMEDIATELY.
EW-4. BEFORE PLACING FOOTINGS, FOUNDATIONS OR SLAB-ON-GRADE,THE SUB-GRADE SHALL BE PREPARED AND INSPECTED AS REQUIREDBY THE SPECIFICATIONS.
EW-5. REFERENCE THE GEOTECHNICAL REPORT INCLUDED IN PROJECT MANUALFOR REQUIREMENTS FOR EXCAVATION AND CONTROL OF GROUND WATERDURING CONSTRUCTION. EXISTING SOILS MAY EXPERIENCE A LOSS OFSTRENGTH IF SURFACE WATER IS ALLOWED TO ACCUMULATE IN THE EXCAVATIONS; DO NOT ALLOW SURFACE WATER TO ACCUMULATE INTHE BOTTOM OF EXCAVATIONS.
EW-6. WHERE STRUCTURES DERIVE SUPPORT FROM FILL-SUPPORTEDFOUNDATIONS AND AT SLAB-ON-GRADE, FILL SHALL BE COMPACTED TO92% OF MODIFIED PROCTOR MAXIMUM DRY DENSITY U.N.O.
EW-7. NO FILL SHALL BE PLACED OVER FROZEN, MUDDY, OR OTHER DELETERIOUSMATERIAL. NO FILL SHALL BE PLACED OVER A PREVIOUS LIFT THAT HASNOT BEEN ADEQUATELY COMPACTED PER SPECIFICATIONS.
EW-8. BACKFILL AGAINST FOUNDATION WALLS SHALL BE PLACED EVENLY ONALL SIDES IN ORDER TO ACHIEVE GENERALLY BALANCED LOADINGS.
ABBREVIATIONS
B.O.
GENERAL SYMBOLS
KEYED NOTE
STRUCTURAL WALL TYPE
ELEVATION
DECK SPAN
STRUCTURAL SLAB TYPE
STRUCTURAL ELEVATION
DETAIL OR SECTION
LINTEL DESIGNATION
SLAB X
S-201 #
#
S-501
SW#
STRUCTURAL SYMBOLOGY
MASONRY (CMU) WALLON CONCRETE FOOTING
CONCRETE FOOTING
CONCRETE FOUNDATION WALLON CONCRETE FOOTING
TOP OF FOOTING ELEVATION
TOP OF WALL ELEVATION
FOOTING STEP
STRIP FOOTING DESIGNATION
DENOTES DEPRESSION FORWALL/DOOR OPENING (-8" U.N.O.)
INDICATES PIER MARK
INDICATES PIER
INDICATES COLUMN
INDICATES CONCRETE FOOTING
INDICATES SPREAD FOOTING MARK
INDICATES NEW GRID DESIGNATION(HEXAGON SHAPE AT EXISTING GRID)
TOF
96'-0"
TOW
100'-0"
SF1
1
A
F1P1
FOUNDATION PLAN
FRAMING PLAN
INDICATES BEAM FRAMING OVER HOLLOWSTRUCTURAL SECTION (HSS) COLUMN
INDICATES BEAM FRAMINGOVER WIDE FLANGE (WF) COLUMN
INDICATES BRACING CONNECTED TO BEAM(BELOW FRAMING MEMBER)
INDICATES BEAM FRAMINGINTO SIDE OF COLUMN
INDICATES MOMENT CONNECTION
W16x36
(000'-0")
[14]
46k
(0.7
5)
INDICATES REQUIRED UPWARD CAMBERIN BEAM (INCHES)
INDICATES BEAM SIZE
INDICATES TOP OF STEEL ELEVATION
INDICATES NUMBER OF 3/4" x 5" SHEAR STUDSFULLY WELDED TO TOP OF BEAM PER 1/2-SPAN
INDICATES CONNECTION DESIGNED BY FABRICATORTO DELIVER 46k VERTICAL LOAD TO CENTERLINEOF COLUMN OR CONNECTION MEMBER
INDICATES TYPICAL BEAM SHEAR SPLICE
INDICATES BEAM FRAMING INTO SIDE OF BEAM
INDICATES BEAM FRAMING OVER BEAM
L#
FOUNDATION WALL DESIGNATIONFW08
INDICATES KNEE BRACING CONNECTED TO BEAM(BELOW FRAMING MEMBER)
#.###
© CopyrightThis document, or any portion thereof, shallnot be duplicated, disclosed, or used on anyother project or extension of this projectexcept by written agreement with Mead &Hunt, Inc. Mead & Hunt shall not beresponsible for any unauthorized use of, oralteration to these documents.
SHEET CONTENTS
DO NOT SCALE DRAWINGS
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
ISSUED
SHEET NO.:
Mead & Hunt, Inc.6501 Watts Road
Madison, WI 53719phone: 608-273-6380
meadhunt.com
NGB PN.: W90FYQ-10-D-0009-9E01
3/2
4/2
014 1
2:4
9:2
9 P
MC
:\R
evit L
ocal\3288700-1
21973.0
1-A
S-C
entr
al_
586m
jb.r
vt
ILLIN
OIS
AR
MY
NA
TIO
NA
L G
UA
RD
2900 W
JE
FF
ER
SO
N S
TR
EE
TJO
LIE
T, IL
LIN
OIS
S-001
3288700-121973.01
ACT
DXC
STRUCTURAL NOTES
RE
HA
B +
AD
DIT
ION
TO
JO
LIE
T F
MS
12
2014
03/25/14
DXC
17090578IL ARNG PN.:
B.O. = BOTTOM OF ________
BP# = BASE PLATE TYPE
BRG = BEARING
C TO C = CENTER TO CENTER
CCJ = CONSTRUCTION CONTROL JOINT
CJ = CONTROL JOINT
CLSM = CONTROLLED LOW STRENGTH MATERIAL ("FLOWABLE FILL")
CONT = CONTINUOUS
DBLT = DOUBLE-TEE
DIA = DIAMETER
DTB = DOUBLE-TEE BEARING
EF = EACH FACE
EL = ELEVATION
EW = EACH WAY
F# = SPREAD FOOTING TYPE
FDTN = FOUNDATION
FV = FIELD VERIFY
GALV = GALVANIZED
HPC = HIGH PERFORMANCE COATING
JB = JOIST BEARING
LLH = LONG LEG HORIZONTAL
LLV = LONG LEG VERTICAL
MBS = METAL BUILDING SUPPLIER
NIC = NOT IN CONTRACT
NTS = NOT TO SCALE
OC = ON CENTER
P# = PIER TYPE
PCB = PRECAST BEARING (ELEVATION)
PRCST = PRECAST
Rxn = REACTION
SF# = STRIP FOOTING TYPE
SIM = SIMILAR
SST = STAINLESS STEEL
STL = STEEL
T.O. = TOP OF ________
TBD = TO BE DETERMINED
TOC = TOP OF CONRETE
TOF = TOP OF FOOTING
TOL = TOP OF LEDGE
TOP = TOP OF PIER
TOS = TOP OF STEEL
TOW = TOP OF WALL
TPC = TOP OF PRECAST
TSL = TOP OF SLAB
TYP = TYPICAL
UNO = UNLESS NOTED OTHERWISE
WWF = WELDED WIRE FABRIC/REINFORCEMENT
03/25/14 TYPE B-3 FINALSUBMITTAL
STRUCTURAL TESTING AND INSPECTION
TI-1.IT IS THE CONTRACTOR'S RESPONSIBILITY TO INSPECT ALL STRUCTURALWORK FOR CONFORMANCE WITH THE CONTRACT DOCUMENTS. ANYSTRUCTURAL INSPECTION PROVIDED BY OTHERS DOES NOT RELIEVE THECONTRACTOR OF THIS RESPONSIBILITY. ANY STRUCTURAL DEVIATIONSFROM THE CONTRACT DOCUMENTS THAT ARE FOUND AT A LATER DATEAND ARE DECLARED TO BE SIGNIFICANT BY THE STRUCTURAL ENGINEERSHALL BE CORRECTED BY THE CONTRACTOR WITHOUT COST OR ANYDELAY TO THE PROJECT SCHEDULE.
TI-2.THE CONTRACTOR SHALL RETAIN AN INDEPENDENT TESTING AGENCY TOPROVIDE FIELD AND LAB TESTING OF CONSTRUCTION MATERIALS AND TOPROVIDE CONSTRUCTION INSPECTIONS. THE CONSTRUCTION INSPECTIONSHALL BE DONE BY QUALIFIED INSPECTORS THAT ARE SATISFACTORY TOTHE ARCHITECT AND ENGINEER.
TI-3.THE CONTRACTOR SHALL PROVIDE THE TESTING AND INSPECTING AGENCYACCESS TO ALL PLACES WHERE THE WORK IS BEING PERFORMED. AMINIMUM OF 24 HOURS NOTIFICATION SHALL BE GIVEN TO THE TESTINGAGENCY AND ARCHITECT/ENGINEER PRIOR TO THE COMMENCEMENT OFWORK REQUIRING TESTING OR INSPECTION.
TI-4.THE TESTING AGENCY IS NOT AUTHORIZED TO DIRECT OR APPROVE ANYCHANGES FROM THE CONTRACT DOCUMENTS. IF THE CONTRACTOR WISHESTO QUESTION THE TESTING AGENCY'S INTERPRETATION OF THE CONTRACTDOCUMENTS, HE MAY DO SO DIRECTLY WITH THE ARCHITECT ORSTRUCTURAL ENGINEER.
TI-5.THE TESTING AGENCY IS NOT AUTHORIZED TO STOP OR DELAY THE WORK.IF THE CONTRACTOR ELECTS TO CONTINUE WITH A CERTAIN PORTION OFWORK AFTER BEING NOTIFIED BY THE TESTING AGENCY THAT SUCH WORKIS NOT IN ACCORDANCE WITH THE CONSTRUCTION DOCUMENTS, THECONTRACTOR DOES SO AT THEIR OWN RISK AND MAY BE REQUIRED TO CORRECT THE WORK AT A LATER DATE.
TI-6.THE TESTING AND INSPECTING AGENCY IS NOT INSPECTING FOR O.S.H.A.COMPLIANCE OR REQUIRED TO INSPECT TEMPORARY CONSTRUCTION,SUCH AS TEMPORARY BRACING. TEMPORARY CONSTRUCTION IS THECONTRACTOR'S SOLE RESPONSIBILITY.
TI-8.TESTING AND INSPECTION IS NOT REQUIRED FOR WORK PERFORMEDAT AN OFF-SITE FABRICATION SHOP, UNLESS SPECIFICALLY NOTED ORSPECIFIED OTHERWISE.
TI-9.THE PROJECT SPECIFICATIONS TYPICALLY INDICATE THE FREQUENCYOF CONSTRUCTION TESTING AND INSPECTIONS. WHERE THE FREQUENCYIS NOT INDICATED, THE TESTING AGENCY SHALL SUBMIT A PROPOSAL OFINSPECTION INTERVALS TO THE ARCHITECT/ENGINEER.
TI-10. THE TESTING AND INSPECTING AGENCY SHALL ISSUE ONGOING REPORTSOF INSPECTIONS AND TESTS TO THE CONTRACTOR, ENGINEER, ANDARCHITECT OF RECORD. ALL DISCREPANCIES SHALL BE BROUGHT TOTHE IMMEDIATE ATTENTION OF THE CONTRACTOR FOR CORRECTION,THEN IF UNCORRECTED, TO THE ENGINEER AND ARCHITECT OF RECORD.
TI-11. INSPECTION AGENCY SHALL INSPECT FOR CONFORMANCE TO SPECIFIEDREQUIREMENTS FOR PROTECTING NEW CONCRETE AND MASONRY FROMTHE ADVERSE EFFECTS OF WEATHER, HEATING EQUIPMENT AND OTHERPOTENTIALLY HARMFUL CONDITIONS.
TI-12. CONSTRUCTION TESTING AND INSPECTION BY THE TESTING ANDINSPECTING AGENCY IS REQUIRED AS FOLLOWS:
A. CONCRETE TESTING PER THE SPECIFICATIONS.
B. CONCRETE INSPECTION SHALL INCLUDE THE PLACEMENT OFREINFORCEMENT. REINFORCING BAR SIZES, SPACING, TIES,LAPS, AND COVER.
C. MASONRY TESTING PER THE SPECIFICATIONS.
D. MASONRY INSPECTION SHALL INCLUDE THE PLACEMENT OFREINFORCEMENT. REINFORCING BAR SIZES, SPACING, AND LAPS.
E. INSPECTION OF FIELD WELDED MOMENT CONNECTIONS SHALLINCLUDE VISUAL AND/OR ULTRASONIC TESTING, AT THE TESTINGAGENCY'S OPTION. ALL OTHER FIELD WELDED CONNECTIONSSHALL BE VISUALLY INSPECTED AT A MINIMUM. THE WELDER'SCERTIFICATION SHALL ALSO BE VERIFIED.
F. FIELD BOLTING INSPECTIONS SHALL INCLUDE VISUAL INSPECTIONOF ALL THE CONNECTIONS RELATED TO STRUCTURAL STEEL. THESIZE, TYPE, AND QUANTITY OF BOLTS AND THEIR INSTALLATIONSHALL BE INSPECTED. WHERE SLIP-CRITICAL OR PRE-TENSIONEDBOLTS ARE SPECIFIED, PRE-TENSIONING OF BOLTS SHALL BEVERIFIED BY TESTING.
METAL BUILDING
MB-1. STRUCTURAL REQUIREMENTS FOR THE METAL BUILDING ARE SHOWN ONTHE S SHEETS AND ELSEWHERE. IT IS THE CONTRACTOR'S RESPONSIBILITYTO COORDINATE AND INCLUDE ALL REQUIREMENTS ON THE ENTIRE PROJECT.SEE 8/A-501 FOR LOW ROOF SUPPORT CONCEPT. SEE 4, 5/A-301 FOR CRANEBRACKET. SEE 4/A-301 FOR FRAME CLEARANCE AT HAUNCH.
MB-2. THIS IS A CRANE BUILDING. SEE SPECIFICATION 133419 FOR CRANE DATA INFORMATION.
MB-3. ON LOW ROOF, ROOF DECK WILL BE FASTENED TO TOP FLANGE OF PURLINSAS DESCRIBED UNDER METAL DECK NOTES. THIS WILL PROVIDE FULL LATERALBRACING TO THE TOP FLANGE OF THE PURLINS ON THE LOW ROOF.
MB-4. SEE ARCHITECTURAL FOR FRAME CLEARANCES AND CRANE BRACKETPLACEMENT.
MB-5. THE LOW ROOF IS A DIAPHRAGM CANTILEVERED FROM THE HIGHER NEW BUILDING. DESIGN BY METAL BUILDING MANUFACTURER. DO NOT PUT RODBRACING NEAR LINE 5.
MB-6. DESIGN ROD BRACING CONNECTIONS SO THAT BRACING HARDWARE IS ABOVECONCRETE FLOOR.
SHOP DRAWINGS
SD-1. SHOP DRAWINGS SHALL BE SUBMITTED FOR STRUCTURAL ITEMS AS REQUIREDBY THE SPECIFICATIONS. CONSTRUCTION DOCUMENTS SHALL NOT BEREPRODUCED FOR USE AS SHOP DRAWINGS.
SD-2. THE GENERAL CONTRACTOR SHALL REVIEW ALL SHOP DRAWINGS ANDPRODUCT DATA FOR CONFORMANCE WITH THE CONSTRUCTION DOCUMENTSPRIOR TO SUBMITTAL. REVIEWED SUBMITTALS SHALL BE STAMPED BY THECONTRACTOR. ANY SHOP DRAWING OR PRODUCT DATA NOT REVIEWED ANDSTAMPED BY THE GENERAL CONTRACTOR WILL BE REJECTED. GENERALCONTRACTOR SHALL CLOUD OR FLAG ALL ITEMS NOT IN ACCORDANCE WITHTHE CONTRACT DOCUMENTS AND SHALL VERIFY ALL DIMENSIONS.
SD-3. ANY CHANGES, SUBSTITUTIONS OR DEVIATIONS FROM THE ORIGINALCONTRACT DRAWINGS SHALL BE CLOUDED BY THE MANUFACTURER ORFABRICATOR. ANY CHANGES, SUBSTITUTIONS, OR DEVIATIONS WHICH ARECLOUDED OR FLAGGED BY SUBMITTING PARTIES SHALL NOT BE CONSIDEREDAPPROVED AFTER THE ENGINEER'S REVIEW, UNLESS SPECIFICALLY NOTEDACCORDINGLY BY THE ENGINEER.
SD-4. THE APPROVED SHOP DRAWINGS DO NOT REPLACE THE ORIGINAL CONTRACTDRAWINGS. ITEMS OMITTED OR SHOWN INCORRECTLY ARE NOT TO BECONSIDERED CHANGES TO THE ORIGINAL CONTRACT DRAWINGS. IT IS THECONTRACTOR'S RESPONSIBILITY TO ENSURE THAT ITEMS OMITTED OR SHOWNINCORRECTLY ARE CONSTRUCTED IN ACCORDANCE WITH THE CONTRACTDRAWINGS.
SD-5. SHOP DRAWING REVIEW IS INTENDED ONLY FOR GENERAL CONFORMANCETO THE DESIGN CONCEPT AND CONSTRUCTION DOCUMENTS.
SD-6. SHOP DRAWINGS WILL BE RETURNED FOR RESUBMITTAL IF MAJOR ERRORSARE FOUND DURING REVIEW.
SD-7. ALLOW A MINIMUM OF (10) WORKING DAYS FOR REVIEW OF SHOP DRAWINGSBY THE STRUCTURAL ENGINEER.
METAL DECK
MATERIAL PROPERTIES (U.N.0)ROOF DECK: 1.5B20, GALVANIZED, Fy = 33 KSI
MD-1. FASTEN ROOF DECK TO PURLINS WITH #12 SCREWS IN 36/3 PATTERN AND(2) #10 CSCREWS IN SIDELAP.
MD-2. U.N.O., ALL MISCELLANEOUS OPENINGS IN METAL ROOF DECK ARE TO BEFRAMED BY 5x3x3/8" ANGLES. LONG LEG OF ANGLES SHALL BE VERTICAL.ANGLES SHALL BE WELDED TO THE TOP CHORD/FLANGE OF ROOF FRAMINGAND EACH OTHER.
MD-3. U.N.O., METAL DECKING SHALL BE CONTINUOUS OVER 3 SPANS AND HAVEJOINTS OVER SUPPORTING MEMBERS.
MD-4. CONTRACTOR IS RESPONSIBLE FOR PROVIDING POUR STOPS AT EDGESOF METAL DECK PER SDI POUR STOP SELECTION TABLE/RECOMMENDATIONSOR BENT PLATE POUR STOPS AS REQUIRED TO FORM THE SLAB EDGE.
MD-5. MAXIMUM PURLIN SPACING EQUALS 6'-0". PURLIN DESIGN BY METAL BUILDINGSUPPLIER.
© CopyrightThis document, or any portion thereof, shallnot be duplicated, disclosed, or used on anyother project or extension of this projectexcept by written agreement with Mead &Hunt, Inc. Mead & Hunt shall not beresponsible for any unauthorized use of, oralteration to these documents.
SHEET CONTENTS
DO NOT SCALE DRAWINGS
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
ISSUED
SHEET NO.:
Mead & Hunt, Inc.6501 Watts Road
Madison, WI 53719phone: 608-273-6380
meadhunt.com
NGB PN.: W90FYQ-10-D-0009-9E01
3/2
4/2
014 1
2:4
9:5
1 P
MC
:\R
evit L
ocal\3288700-1
21973.0
1-A
S-C
entr
al_
586m
jb.r
vt
ILLIN
OIS
AR
MY
NA
TIO
NA
L G
UA
RD
2900 W
JE
FF
ER
SO
N S
TR
EE
TJO
LIE
T, IL
LIN
OIS
S-002
3288700-121973.01
ACT
DXC
STRUCTURAL NOTES
RE
HA
B +
AD
DIT
ION
TO
JO
LIE
T F
MS
12
2014
03/25/14
DXC
17090578IL ARNG PN.:
03/25/14 TYPE B-3 FINALSUBMITTAL
1. SITE DATUM OF FINISHED FIRST FLOOR INDICATED ON CIVIL SITE PLAN =ELEVATION 100'-0" ON STRUCTURAL DRAWINGS.
2. FIELD VERIFY ALL DIMENSIONS, BRING ANY DISCREPANCIES TO THEATTENTION OF THE ARCHITECT/ENGINEER FOR FINAL DECISION.
3. NOT USED.
4. REFER TO SHEET S-001 FOR STRUCTURAL LEGENDS, ABBREVIATIONS,AND SYMBOLOGY.
5. REFER TO SHEETS S-501 AND S-502 FOR TYPICAL DETAILSNOT REFERENCED ON THIS SHEET.
6. TOP OF FOOTING ELEVATION = 97'-6" UNLESS NOTED OTHERWISE.
7. REFER TO DETAILS OF SHEET S-502 FOR TOP OF PIER ELEVATIONS.
8. TOP OF FOUNDATION WALL ELEVATION = 100'-8" UNLESS NOTEDOTHERWISE.
9. STRIP FOOTINGS SHALL BE CENTERED UNDER FOUNDATION/MASONRYWALLS UNLESS NOTED OTHERWISE.
10. PIER SIZES ARE MINIMUM REQUIRED FOR FOUNDATION STRENGTH.PIERS MUST BE AT LEAST 2 INCHES LARGER THAN METAL BUILDING BASEPLATES. IF NECESSARY, INCREASE PIER SIZES TO ACCOMODATE METALBUILDING BASE PLATES.
11. SEE ARCHITECTURAL FOR ADDITIONAL LINTELS, FRAMING AND METAL DECK.
FOUNDATION PLAN GENERAL NOTES
2 2
3 3
BCD A
57' -
8"
42' -
8"
57' -
8"
38' -
4"
4' -
4"
100' -
4"
100' -
4"
65' - 10" 6' - 10"
11' -
11"
20' -
0"
11' -
11"
12' -
8"
1' -
2"
1' - 0" 20' - 0" 23' - 10" 20' - 0" 1' - 0"
1 1
4 4
5' -
11"
6' -
0"
F8 F8F8
F6
F6
F8 F8 F8
F6
F6
P18P18P18
P14
P14P18 P18 P18
P14
P14S
F2
SF2
11' -
11"
20' -
0"
11' -
11"
12' -
8"
1' -
2"
5' -
11"
6' -
0"
0"
6' -
8"
83' - 0"
61' - 4" 21' - 8"
5' - 0" 4' - 0" 14' - 0" 6' - 0" 14' - 0" 5' - 2" 14' - 0" 4' - 2"
SF2
3.1013.1013.101
3.101
3.101
3.1013.101
3.1013.101
3.101
5 5
SF
2
SF
2
F3A
P17F3A
P17 F3
P17F3P17
F8
P18
F8
P18
1' - 6" 1' - 6"
3.103
3.103 3.103
3.103
TOW
99' - 0"
TOW ATDOORTOW
99' - 0"
TOW ATDOOR
2S-501
1S-501
TYP
2S-501
7
S-511
7
S-511
SF2.6SF2.6
3.105
TYPICALOF (4)
3.105
TYPICALOF (4)
TY
P
3' -
6"
TY
P
4' -
6"
TYP
4' - 0"
TYP
4' - 0"
TYP
4' - 0"
TYP
4' - 0"
TY
P
3' -
6"
TY
P
4' -
6"
12S-502
11S-502
SF2SF2
SF2SF2
11
S-511
3.1043.104
1S-501
1S-501
TYP.TYP
10' - 3" 3' - 4"
KEYED NOTES
© CopyrightThis document, or any portion thereof, shallnot be duplicated, disclosed, or used on anyother project or extension of this projectexcept by written agreement with Mead &Hunt, Inc. Mead & Hunt shall not beresponsible for any unauthorized use of, oralteration to these documents.
SHEET CONTENTS
DO NOT SCALE DRAWINGS
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
ISSUED
SHEET NO.:
Mead & Hunt, Inc.6501 Watts Road
Madison, WI 53719phone: 608-273-6380
meadhunt.com
NGB PN.: W90FYQ-10-D-0009-9E01
3/2
4/2
014 1
2:5
0:0
9 P
MC
:\R
evit L
ocal\3288700-1
21973.0
1-A
S-C
entr
al_
586m
jb.r
vt
ILLIN
OIS
AR
MY
NA
TIO
NA
L G
UA
RD
2900 W
JE
FF
ER
SO
N S
TR
EE
TJO
LIE
T, IL
LIN
OIS
S-101
3288700-121973.01
ACT
DXC
FOUNDATION PLAN
RE
HA
B +
AD
DIT
ION
TO
JO
LIE
T F
MS
12
2014
03/25/14
DXC
17090578IL ARNG PN.:
NORTH
1/8" = 1'-0"1FOUNDATION PLAN - OVERALL
3.101 EXISTING FOUNDATION TO REMAIN.
3.103 PROVIDE (2) LAYERS OF BUILDING FELT BETWEEN NEW ANDEXISTING FOUNDATIONS.
3.104 NEW FOUNDATION WALL AT EXISTING, SEE DETAIL 4/S-501.
3.105 BOLLARD, SEE ARCHITECTURAL.
0 1684
CONCRETE STRIP FOOTING SCHEDULE
MARK
SIZE TOP REINFORCEMENT BOTTOM REINFORCEMENT
REMARKS
WIDTH
"W"
HEIGHT
"H" LONG. TRANS. LONG. TRANS.
SF1.5 1' - 6" 1' - 6" (2) #5
SF2 2' - 0" 1' - 0" (2) #5
SF2.6 2' - 8" 1' - 0" (2) #5
CONCRETE STRIP FOOTING SCHEDULE NOTES
1. SEE NOTE SHEET S-001 FOR BEARING SOILS PREPARATION REQUIREMENTS.
2. SEE 12/S-501 FOR TYPICAL FOOTING INTERSECTION REINFORCING.
3. EMBED DOWELS INTO FOOTING, 3" CLEAR COVER FROM BOTTOM OF FOOTING.
4. EXCEPT WHERE SPECIFICALLY NOTED, TYPE "A" FOOTING DOWELS SHALL BE TIED IN PLACE PRIOR TO CONCRETEPLACEMENT.
CONCRETE SPREAD FOOTING SCHEDULE
MARK
SIZE BOTTOM REINFORCEMENT TOP REINFORCEMENT
REMARKSWIDTH LENGTH THICKNESS LONGITUDINAL TRANSVERSE LONGITUDINAL TRANSVERSE
F3 3' - 0" 3' - 0" 1' - 0" #4 AT 6" O.C. #4 AT 6" O.C. #4 AT 6" O.C. #4 AT 6" O.C. 1
F3A 3' - 0" 4' - 0" 1' - 0" #4 AT 6" O.C. #4 AT 6" O.C. #4 AT 6" O.C. #4 AT 6" O.C. 1
F6 6' - 0" 6' - 0" 1' - 6" (6) #5 (6) #5 (6) #5 (6) #5
F8 8' - 0" 8' - 0" 1' - 6" (8) #6 (8) #6 (8) #6 (8) #6
CONCRETE SPREAD FOOTING SCHEDULE GENERAL NOTES
1. SEE NOTE SHEET S-001 FOR BEARING SOILS PREPARATION REQUIREMENTS.
2. EMBED DOWELS INTO FOOTING, 3" CLEAR COVER FROM BOTTOM OF FOOTING.
CONCRETE SPREAD FOOTING SCHEDULE REMARKS
1. BOTTOM OF FOOTING TO MATCH BOTTOM OF EXISTING FOOTING.
03/25/14 TYPE B-3 FINALSUBMITTAL
1. SITE DATUM OF FINISHED FIRST FLOOR INDICATED ON CIVIL SITE PLAN =ELEVATION 100'-0" ON STRUCTURAL DRAWINGS.
2. FIELD VERIFY ALL DIMENSIONS, BRING ANY DISCREPANCIES TO THEATTENTION OF THE ARCHITECT/ENGINEER FOR FINAL DECISION.
3. NOT USED.
4. REFER TO SHEET S-001 FOR STRUCTURAL LEGENDS, ABBREVIATIONS,AND SYMBOLOGY.
5. REFER TO SHEET S-511 FOR TYPICAL DETAILS NOT REFERENCED ONTHIS SHEET.
6. REFER TO DETAIL 1/S-511 FOR STRUCTURAL SLAB TYPES.
7. FLOOR FINISH :ROOMS 106, 109, 110 FLOAT, TROWEL AND SEAL.ROOMS 102, 107 108 FLOAT AND FINISH PER FLOORING MANUFACTURER'S RECOMMENDATIONS.
8. (2) DASHED LINES INDICATE (2) ADDITIONAL #4 BARS(5'-0" LONG) DIAGONAL 6" FROM CORNER IN SLAB, 2" CLEAR FROMTOP OF SLAB.
9. SEE ARCHITECTURAL FOR ADDITIONAL LINTELS, FRAMING AND METAL DECK.
FLATWORK PLAN GENERAL NOTES
2 2
3 3
BCD A
1 1
4 4
57' -
8"
42' -
8"
8"
13' -
2"
16' -
2"
13' -
10"
13' -
10"
6' -
0"
8"
13' -
2"
16' -
2"
13' -
10"
13' -
10"
6' -
0"
100' -
4"
100' -
4"
11' -
11"
20' -
0"
11' -
11"
12' -
8"
1' -
2"
57' -
8"
38' -
4"
4' -
4"
1' -
2"
12' -
8"
11' -
11"
20' -
0"
11' -
11"
83' - 0"
5' - 0" 61' - 4" 21' - 8"
10' - 2" 10' - 2" 11' - 11" 11' - 11" 10' - 2" 10' - 2"
10' - 0" 10' - 0"
SLB08
SLB05
CJ
CJ
CJ
CJ
CJ
CJ
6' -
8"
SLB05
5 5
CJ
CJ
CJ
10' - 2" 10' - 2" 11' - 11" 11' - 11" 10' - 2" 10' - 2"
CJ
CJ
CJ
CJ
CJ
CJ
CJ
CJ
CJ
CJ
TSL
100' - 0"
TSL
99' - 10"
TSL
99' - 10"
FD RIM FD RIM
TSL
100' - 0"
TSL
100' - 0"
TSL
100' - 0"
TSL
100' - 0"
TSL
100' - 0"
TSL
100' - 0"
5' - 0"5' - 0"
TSL
100' - 0"
65' - 10"
1' - 0" 20' - 0" 23' - 10" 20' - 0" 1' - 0"
4
S-511
5S-511
5S-511
6
S-511
6
S-511
3.2013.201
3.202
CJ
11
S-511
3.105
TYPICALOF (4)
TYPICALOF (4)
3.105
3.203
3.203
TYP
TYP
9
S-511
10
S-511
13
S-511
14S-511
14S-511
3.204
3.2053.205
KEYED NOTES
© CopyrightThis document, or any portion thereof, shallnot be duplicated, disclosed, or used on anyother project or extension of this projectexcept by written agreement with Mead &Hunt, Inc. Mead & Hunt shall not beresponsible for any unauthorized use of, oralteration to these documents.
SHEET CONTENTS
DO NOT SCALE DRAWINGS
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
ISSUED
SHEET NO.:
Mead & Hunt, Inc.6501 Watts Road
Madison, WI 53719phone: 608-273-6380
meadhunt.com
NGB PN.: W90FYQ-10-D-0009-9E01
3/2
4/2
014 1
2:5
0:3
1 P
MC
:\R
evit L
ocal\3288700-1
21973.0
1-A
S-C
entr
al_
586m
jb.r
vt
ILLIN
OIS
AR
MY
NA
TIO
NA
L G
UA
RD
2900 W
JE
FF
ER
SO
N S
TR
EE
TJO
LIE
T, IL
LIN
OIS
S-111
3288700-121973.01
ACT
DXC
FLATWORK PLAN
RE
HA
B +
AD
DIT
ION
TO
JO
LIE
T F
MS
12
2014
03/25/14
DXC
17090578IL ARNG PN.:
NORTH
1/8" = 1'-0"1FLATWORK PLAN - OVERALL
0 1684
3.105 BOLLARD, SEE ARCHITECTURAL.
3.201 PROVIDE (2) LAYERS OF BUILDING PAPER BETWEEN CONCRETESTOOP AND OH DOOR APRON.
3.202 REMOVE EXISTING CONCRETE FLOOR IN THIS ROOM. REPLACEWITH SLAB TYPE SLB05, SEE DETAIL 1/S-511.
3.203 HAIRPIN IN SLAB, SEE DETAIL 12/S-511.
3.204 SLAB-ON-GRADE CONCRETE EQUIPMENT PAD (SEE DETAIL15/S-511). COORDINATE EXACT SIZE AND LOCATION WITHMECHANICAL EQUIPMENT CONTRACTOR.
3.205 PATCH FLOOR SLAB WITH SLAB TYPE SLB05. DOWEL PATCH TOSURROUNDING CONCRETE WITH #4 AT 12" ALL AROUND,CENTERED IN SLAB THICKNESS.
03/25/14 TYPE B-3 FINALSUBMITTAL
REINFORCING CONTINUOUSTHROUGH JOINTS, TYPICAL
CLASS "B" LAP
L CONSTRUCTION JOINTC
60'-0" MAX. SPACING 60'-0" MAX. SPACING
BENT BAR AT CORNERSSHALL MATCH FOOTINGREINFORCING
CONTINUOUS STRIPFOOTING REINFORCING,SEE SCHEDULE,PROVIDE STANDARDHOOK AT BAR ENDSAS SHOWN
CLASS B LAP CLASS B LAP
CLA
SS
B L
AP
"W"
"W"
"W"
"W"
"W" "W"
"W" "W"
REINFORCEMENT EACH FACE
REINFORCEMENT CENTERED
TYPICAL
2' - 0" BAR LAP
TYPICAL
2' - 0" BAR LAP
TY
PIC
AL
2' -
0"
BA
R L
AP
TY
PIC
AL
2' -
0"
BA
R L
AP
TYPICAL
2' - 0" BAR LAP
TYPICAL
2' - 0" BAR LAP
NOTES:
1.VERTICAL REINFORCING NOT SHOWN FOR CLARITY.2.FOUNDATION WALL LEDGE NOT SHOWN FOR CLARITY.3. "W" = FOUNDATION WALL WIDTH.
HORIZONTAL WALLREINFORCING
OPTIONAL WALLCONSTRUCTION JOINT
CORNER BARS TO MATCHWALL REINFORCING
HORIZONTAL WALLREINFORCING
OPTIONAL WALLCONSTRUCTION JOINT
CORNER BARS TO MATCHWALL REINFORCING
FLOOR SLAB(SEE FLATWORK PLAN)
8" CONCRETE WALL WITH#5 BARS AT 18" O.C.EACH WAY, CENTERED
DOWEL, MATCH WALL STEELSIZE AND SPACING
FOOTING(SEE FOUNDATION PLAN)
EQ 8" EQ
T.O. FOOTING
(SEE FNDN PLAN)
T.O. FLOOR
100' - 0"
T.O. WALL
100' - 8"
1/2" RIGID INSULATIONWITH SEALANT AT SURFACE
ENGINEERED FILL(SECTION 312100)
1
1
1
1
PREPARED SUB-GRADE(SECTION 312100)
GRADE
REINFORCING CONTINUOUSTHROUGH JOINTS
CANT STRIP (EACH SIDE)
CLASS "B" LAPNOTE:
SIMILAR AT WALLS WHEREREINFORCEMENT IS PLACEDEACH FACE.
L CONSTRUCTION JOINTC
60'-0" MAX. SPACING 60'-0" MAX. SPACING
REINFORCING CONTINUOUSTHROUGH JOINTS
CANT STRIP (EACH SIDE)
NOTE:
SIMILAR AT WALLS WHEREREINFORCEMENT IS PLACEDEACH FACE.
L CONTROL JOINTC
20'-0" MAX. SPACING 20'-0" MAX. SPACING
NOTE:
WHEN MASONRY IS ABOVEALIGN MASONRY ANDCONCRETE CONTROL JOINTS.
(2) #5 BARS EACH FACE,TYPICAL
TYPICAL RECTANGULAR OPENING IN
CAST IN PLACE CONCRETE
TYPICAL CIRCULAR OPENING IN
CAST IN PLACE CONCRETE
A
B
(2) #5 BARS x 4'-0" LONG EACHFACE, TYPICAL
NOTES:
1. APPLIES TO ALL OPENINGS WHERE 'A' OR 'B' IS GREATER THAN OR EQUAL TO CAST IN PLACE CONCRETE THICKNESS.
2. VERIFY SIZE AND LOCATION OF OPENINGS WITH TRADE OR SUB- CONTRACTOR REQUIRING OPENINGS.
(2) #5 BARS EACH FACE,TYPICAL
(2) #5 BARS x 4'-0" LONG EACHFACE, TYPICAL
NOTES:
1. APPLIES TO ALL HOLES WHERE DIAMETER IS GREATER THAN OR EQUAL TO CAST IN PLACE CONCRETE THICKNESS.
2. VERIFY SIZE AND LOCATION OF OPENINGS WITH TRADE OR SUB- CONTRACTOR REQUIRING OPENINGS.
3. 2'-0" MAXIMUM OPENING UNLESS NOTED OTHERWISE.
MA
X3"
MA
X
3"
NOTES:1. VERIFY OPENING AND LOCATION OF OPENING AND PIPE SLEEVE WITH TRADE OR SUB- CONTRACTOR.
2. SEE FOUNDATION PLANS FOR VERTICAL AND HORIZONTAL WALL REINFORCING.
CAST IRON PIPE SLEEVE
3" T
YPICAL
DIAGONAL BARS:(4) #5 BARS, EACH FACE
2' - 0" MIN
16" CONCRETE WALL WITH(2) #5 BARS TOP AND BOTTOM
#5 DOWEL AT 18" O.C.
FOOTING(SEE FOUNDATION PLAN)
EQ 1' - 4" EQ
T.O. FOOTING
(SEE FNDN PLAN)
T.O. FLOOR
100' - 0"
T.O. WALL BEYOND
100' - 8"
T.O. WALL
99' - 0"
S-511
5FOUNDATION WALL BEYOND
(2) #5 BARS x 16" LONG.DRILL AND GROUT INTOEXISTING FOOTING(8" EMBED)
T.O. EXISTING FOOTING
97' - 6" (VERIFY)
NEW CMU INFILL
T.O. EXISTING WALL
100' - 0"
T.O. NEW WALL
100' - 8"
EXISTING FOUNDATION WALL
NEW FOUNDATION WALL
(2) LAYERS BUILDING PAPER
ALIGN
12" CONCRETE WALL WITH(2) #5 BARS TOP AND BOTTOM
#5 DOWEL AT 18" O.C.
FOOTING(SEE FOUNDATION PLAN)
8" 1' - 0" 4"
T.O. FOOTING
(SEE FNDN PLAN)
T.O. FLOOR
100' - 0"
T.O. WALL BEYOND
100' - 8"
T.O. WALL
99' - 0"
FOUNDATION WALL BEYONDS-511
6
© CopyrightThis document, or any portion thereof, shallnot be duplicated, disclosed, or used on anyother project or extension of this projectexcept by written agreement with Mead &Hunt, Inc. Mead & Hunt shall not beresponsible for any unauthorized use of, oralteration to these documents.
SHEET CONTENTS
DO NOT SCALE DRAWINGS
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
ISSUED
SHEET NO.:
Mead & Hunt, Inc.6501 Watts Road
Madison, WI 53719phone: 608-273-6380
meadhunt.com
NGB PN.: W90FYQ-10-D-0009-9E01
3/2
4/2
014 1
2:5
0:5
4 P
MC
:\R
evit L
ocal\3288700-1
21973.0
1-A
S-C
entr
al_
586m
jb.r
vt
ILLIN
OIS
AR
MY
NA
TIO
NA
L G
UA
RD
2900 W
JE
FF
ER
SO
N S
TR
EE
TJO
LIE
T, IL
LIN
OIS
S-501
3288700-121973.01
ACT
DXC
FOUNDATIONDETAILS
RE
HA
B +
AD
DIT
ION
TO
JO
LIE
T F
MS
12
2014
03/25/14
DXC
17090578IL ARNG PN.:
1" = 1'-0"11
TYPICAL
FOOTING CONSTRUCTION JOINT
1/2" = 1'-0"12TYPICAL FOOTING INTERSECTIONS
1" = 1'-0"7
TYPICAL
FOUNDATION WALL INTERSECTIONS
3/4" = 1'-0"1TYPICAL FOUNDATION WALL
1/2" = 1'-0"10
TYPICAL BACKFILL REQUIREMENTS
AT EXTERIOR FOUNDATION
1" = 1'-0"5
TYPICAL FOUNDATION
WALL CONSTRUCTION JOINT
1" = 1'-0"6
TYPICAL FOUNDATION
WALL CONTROL JOINT
1/4" = 1'-0"9
TYPICAL CONCRETE
PENETRATION REINFORCEMENT
1/2" = 1'-0"8FOUNDATION WALL PENETRATION
3/4" = 1'-0"2FOUNDATION WALL AT APRON
3/4" = 1'-0"4
NEW TO EXISTING
FOUNDATION CONNECTION
3/4" = 1'-0"3FOUNDATION WALL AT STOOP
03/25/14 TYPE B-3 FINALSUBMITTAL
4
1' -
4"
8"
FOUNDATION WALL FW08(SEE DETAIL 1/S-501)
1' - 0"9"
T.O. PIER
99' - 0"
T.O. WALL
100' - 8"
2' -
0"
WALL
8"4"9"
METAL BUILDING COLUMNBY MBS
1
WA
LL
8"
1' -
4"
FOUNDATION WALL FW08(SEE DETAIL 1/S-501)
1' - 0"9"
T.O. PIER
99' - 0"
T.O. WALL
100' - 8"
2' -
0"
WALL
8"4"9"
METAL BUILDING COLUMNBY MBS
1 1/2" BLOCK-OUT OF WALLIF NECESSARY
#4 BENT BARAT BLOCK-OUT.EXTEND 8" MINIMUMPAST BLOCK-OUT.
1
WA
LL
8"
1' -
4"
FOUNDATION WALL FW08(SEE DETAIL 1/S-501)
PIER(SEE DETAIL)
9"9"
T.O. PIER
99' - 0"
T.O. WALL
100' - 8"2' -
0"
1 1/2" BLOCK-OUT OF WALLIF NECESSARY
#4 BAR AT BLOCK-OUT.EXTEND 8" MINIMUMPAST BLOCK-OUT.
METAL BUILDING COLUMNBY MBS
4
1' -
4"
8"
PIER P18(SEE PIER SCHEDULE)
1' - 6"
T.O. PIER
99' - 0"
2' -
0"
9"9"
METAL BUILDING COLUMNBY MBS
5
8 1
/2"
8 1
/2"
5 1
/2"
FOUNDATION WALL FW08(SEE DETAIL 1/S-501)
1' - 0"8 1/2"
T.O. PIER
99' - 4"
T.O. WALL
100' - 8"
1' -
5"
WALL
8"4"
EXISTING FOUNDATION WALL
T.O. EXISTING WALL
100' - 0" (VERIFY)
STEEL COLUMN PER MBS.HSS 5X5 MAX
BASE PLATE DESIGNCOMPLETE BY MEAD & HUNT(SEE DETAIL 10/S-502)
CMU INFILL(SEE DETAIL 4/S-501)
3"
1' -
2"
2 1
/2"
2 1
/2"
CLEAR2"
T.O. FOOTING
(SEE PLAN)
COLUMN AND BASE PLATEBY METAL BUILDING SUPPLIER
VERTICAL REINFORCEMENT WITHSTANDARD HOOK (SEE SCHEDULE)LOOP CONTINUOUS OVER TOP
TIES (SEE SCHEDULE)
FOOTING (SEE PLAN)
T.O. PIER
99' - 4"
T.O. FLOOR
100' - 0"
FLOOR SLAB(SEE FLATWORK PLAN)
5
8 1
/2"
8 1
/2"
5 1
/2"
PIER P17(SEE PIER SCHEDULE)
1' - 5"
T.O. PIER
99' - 4"
1' -
5"
8 1/2"8 1/2"
EXISTING FOUNDATION WALL
T.O. EXISTING WALL
100' - 0" (VERIFY)
STEEL COLUMN PER MBSHSS 5X5 MAX
BASE PLATE DESIGNCOMPLETE BY MEAD & HUNT(SEE DETAIL 9/S-502)
FOUNDATION WALL FW08(SEE DETAIL 1/S-501)
1' - 0"1' - 0"
T.O. WALL
100' - 8"
8"4"4"8" T.O. PIER
99' - 0"
T.O. WALL
99' - 0"
1' -
2"
1' -
5"
7"
7"
16' -
0"
DO
OR
OP
EN
ING
2S-501
COLUMN AND BASE PLATEBY MBS
BA
CK
DE
PT
H O
F IM
P
HO
LD
JA
MB
PO
ST
8"
T.O. PIER
99' - 0"
3' - 6" 4' - 6"
T.O. SLAB
100' - 0"
T.O. WALL
100' - 8"
T.O. FOOTING
97' - 6"
RIGID FRAME COLUMN(BY METAL BUILDING SUPPLIER)
SECOND SLAB POUR
SLAB ON GRADE (SEE PLAN)
CONCRETE PIER (SEE PLAN)
ANCHOR RODS(DESIGNED AND SUPPLIED BYMETAL BUILDING SUPPLIER)
VERTICAL REINFORCEMENT WITHSTANDARD HOOK (SEE SCHEDULE)LOOP CONTINUOUS OVER TOP
2 1
/2"
2 1
/2"
10"
3"
CLEAR2"
1 1/2" BLOCK-OUT OF WALLIF NECESSARY
HAIRPIN (SEE DETAIL 12/S-511)
SPREADFOOTING(SEE PLAN)
(MIN
IMU
M 1
'-0"
)
18 X
RO
D D
IAM
ET
ER
1 1
/2"
1/4" LEVELING PLATE,REMOVE AFTER LEVELINGNUTS HAVE BEEN SET
ANCHOR RODS SHALL BE(4 PER BASE PLATE)3/4" DIA F1554 GR 55 MINIMUM.IF NECESSARY,INCREASE SIZE REQUIRED BYMETAL BUILDING SUPPLIER.
LEVELING NUT
GROUT BED
WELDED PLATE WASHERWHERE REQUIRED, SEE SPEC.(2x2x1/4" AT 3/4" ANCHORS,3x3x1/2" AT 1 1/4" ANCHORS)
1"
COLUMN BASE PLATE(SEE COLUMN SCHEDULE)
1/2" THICK BASE PLATE
(4) BOLT HOLES,HOLE DIAMETER = ANCHOR BOLT DIA. + 5/16"(SEE COLUMN SCHEDULE)
HSS COLUMN(BY MBS)
1/4
CO
LU
MN
WID
TH
+ 8
" 2"
2"
WID
TH
CO
LU
MN
2"
2"
2" 2"
WIDTH
COLUMN 2" 2"
COLUMN WIDTH + 8"
1/2" THICK BASE PLATE
(4) BOLT HOLES,HOLE DIAMETER = ANCHOR BOLT DIA. + 5/16"(SEE COLUMN SCHEDULE)
HSS COLUMN(BY MBS)
1/4
CO
LU
MN
WID
TH
+ 8
" 2"
2"
WID
TH
CO
LU
MN
2"
2"
4"
WIDTH
COLUMN 1/2"
COLUMNWIDTH + 4 1/2"
2" 5 1/2" 2"
TYPE - BTYPE - A TYPE - C
TYPE - D TYPE - E TYPE - F
TYPICAL TIE DETAILS
© CopyrightThis document, or any portion thereof, shallnot be duplicated, disclosed, or used on anyother project or extension of this projectexcept by written agreement with Mead &Hunt, Inc. Mead & Hunt shall not beresponsible for any unauthorized use of, oralteration to these documents.
SHEET CONTENTS
DO NOT SCALE DRAWINGS
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
ISSUED
SHEET NO.:
Mead & Hunt, Inc.6501 Watts Road
Madison, WI 53719phone: 608-273-6380
meadhunt.com
NGB PN.: W90FYQ-10-D-0009-9E01
3/2
4/2
014 1
2:5
1:4
8 P
MC
:\R
evit L
ocal\3288700-1
21973.0
1-A
S-C
entr
al_
586m
jb.r
vt
ILLIN
OIS
AR
MY
NA
TIO
NA
L G
UA
RD
2900 W
JE
FF
ER
SO
N S
TR
EE
TJO
LIE
T, IL
LIN
OIS
S-502
3288700-121973.01
MJE
DXC
FOUNDATIONDETAILS
RE
HA
B +
AD
DIT
ION
TO
JO
LIE
T F
MS
12
2014
03/25/14
DXC
17090578IL ARNG PN.:
3/4" = 1'-0"2TOP OF PIER
3/4" = 1'-0"4TOP OF PIER
3/4" = 1'-0"8TOP OF PIER
3/4" = 1'-0"6TOP OF PIER
3/4" = 1'-0"1TOP OF PIER
3/4" = 1'-0"11PIER SECTION
3/4" = 1'-0"5TOP OF PIER
3/4" = 1'-0"3TOP OF PIER
3/4" = 1'-0"12RIGID FRAME PIER SECTION
1 1/2" = 1'-0"7BASE PLATE ANCHORAGE
1 1/2" = 1'-0"9HSS COLUMN BASE PLATE
1 1/2" = 1'-0"10HSS COLUMN BASE PLATE
CONCRETE PIER SCHEDULE
MARK SIZE
VERTICAL
REINFORCEMENT
TIES
REMARKSTYPE
# AND
SPACING
P14 14" x 24" (6) #5 D (3) #4
P17 17" x 17" (6) #5 D (3) #4
P18 18" x 24" (6) #5 D (3) #4
CONCRETE PIER SCHEDULE GENERAL NOTES
1. SEE PIER DETAILS ON S-502 FOR TOP OF PIER ELEVATIONS.
2. REFERENCE TYPICAL TIE DETAILS FOR CROSS-TIE REQUIREMENTS.
3. WHEN PIERS ARE INTEGRAL WITH WALLS, PIER DIMENSIONS ARE INDICATED FOR THE PURPOSE OF DIMENSIONINGPIER TIES, SETTING VERTICAL REINFORCING, DEFINING EXTENT OF TOP OF PIER RECESS OR PROJECTION FROM TOPOF WALL. CENTER PIER REINFORCING CAGE BELOW COLUMN AND ORIENT LONG DIMENSION OF PIER WITH AXIS OFWALL UNLESS NOTED OR DETAILED OTHERWISE. CONTINUE WALL REINFORCING THROUGH PIERS WITH LAPS ASREQUIRED.
CONCRETE PIER SCHEDULE REMARKS
1.
03/25/14 TYPE B-3 FINALSUBMITTAL
TYPE SLB05
3"
8"
TYPE SLB08
CONCRETE SLAB WITH#4 BARS AT 16" O.C. EACH WAY,AT 2" CLEAR FROM TOP OF SLAB
FINE-GRADED GRANULAR
ENGINEERED FILL
PREPARED SUB-GRADE(SECTION - 312000)
3"
5"
CONCRETE SLAB WITH 6x6 -W2.9xW2.9 WWF, AT 2" CLEARFROM TOP OF SLAB
FINE-GRADED GRANULAR
VAPOR BARRIER(SECTION - 033000)
ENGINEERED FILL
PREPARED SUB-GRADE(SECTION - 312000)
RE
Q.
AS
RE
Q.
AS
1/4" WIDE JOINT (2 BLADES).SAW CUT 4 TO 12 HOURSAFTER CONCRETE IS PLACED.FILL WITH FLOOR CONTROLJOINT FILLER
CONCRETE SLAB(SEE FLATWORK PLAN)
X X X XX X X
C CONSTRUCTION JOINTL
(1 1
/4"
MIN
IMU
M)
1/4
SLA
B T
HIC
KN
ES
S
#5 DOWEL (3'-0" LONG)AT 36" O.C. CENTERED ONJOINT (CENTERED IN SLAB)
EQUAL EQUAL
1/8" WIDE JOINT.SAW CUT 4 TO 12 HOURSAFTER CONCRETE IS PLACED.FILL WITH FLOOR CONTROLJOINT FILLER
CONCRETE SLAB(SEE FLATWORK PLAN)
X X X XX X X
C CONTROL JOINTL
(1 1
/4"
MIN
IMU
M)
1/4
SLA
B T
HIC
KN
ES
S
S-511
6
5" CONCRETE SLAB WITH 4x4-W4.0xW4.0 WWFSLAB SHALL RECEIVE BROOM FINISH
STOOP FOUNDATION WALLWITH CONTINUOUS #5 BARTOP AND BOTTOM.
#5 DOWELS AT 16" O.C.AROUND PERIMETER OF STOOP
FOOTING SF1.5(SEE STRIP FOOTING SCHEDULE)
18"
18"
12" FOUNDATION WALLWITH #5 TOP AND BOTTOMAND #5 DOWELS AT 18" O.C.
COMPACTED GRANULAR FILLFROM BOTTOM OF SLABTO TOP OF FOOTING
T.O. STOOP WALL
99' - 8"
T.O. FOOTING
MATCH BLDG FOOTING
#5 DOWELS AT 16" O.C.AROUND PERIMETER OF STOOP
FLOOR SLAB (SEE FLATWORK PLAN)
8" 1' - 0" 4"
FOOTING SF2(SEE STRIP FOOTING SCHEDULE)
1/8" / FOOT
BUILDING FOUNDATION WALL(SEE FOUNDATION PLAN)
PASS DOOR(SEE ARCHITECTURAL)
STOOP SLAB(SEE DETAIL 7/S-511)
1" RIGID INSULATIONWITH SEALANT AT SURFACE,ALIGN WITH PASS DOOR.
FLOOR SLAB(SEE PLAN)
2" RIGID INSULATION, EXTENDDOWN TO TOP OF FOOTING
1/8" / 1'-0"
1/4
"
#4 DOWELS AT 12" O.C.
1/4" WIDE JOINT (2 BLADES).SAW CUT 4 TO 12 HOURSAFTER CONCRETE IS PLACED.FILL WITH FLOOR CONTROLJOINT FILLER
CONCRETE SLAB SLB05(SEE DETAIL 1/S-511)
X
1 1
/4"
8"
CONCRETE SLAB SLB08(SEE DETAIL 1/S-511)
4
1
2
PROVIDE (2) LAYERSOF BUILDING PAPERBETWEEN SLAB POURSTO PREVENT BOND
X X X
1/2" ISOLATION JOINT MATERIALWITH FLEXIBLE JOINT SEALANTAT TOP OF JOINT
RIGID FRAME COLUMN
CJ CONTROL JOINTS
1
1
CJ
1
1
FOUNDATIONWALL(SEE PLAN)
1/2" ISOLATION JOINT MATERIALWITH FLEXIBLE JOINT SEALANTAT TOP OF JOINT
CONTROL JOINTS
RIGID FRAME ALONG GRID 4
FINAL SLAB POUR
RIGID FRAME ALONG GRID 1
1
4
9" 9"
SLB05
SLB08
4
S-511
EXTENT OF PIER BELOW
2' - 4" 2' - 4"
RIGID FRAME COLUMN
FINAL SLAB POUR
EXTENT OF PIER BELOW
1/2" ISOLATION JOINT MATERIALWITH FLEXIBLE JOINT SEALANTAT TOP OF JOINT
HSS COLUMN
CJ
CONTROL JOINTS
1
1
HSS COLUMNS ALONG GRID 5
FINAL SLAB POUR
5
8 1/2" 8 1/2"
EXTENT OF PIER BELOW
1' -
2"
8 1
/2"
EXISTING WALL
1" RIGID INSULATION WITHSEALANT AT SURFACE(ALIGN WITH OVERHEAD DOOR)
FOUNDATION WALL(SEE FOUNDATION PLAN)
#4 DOWELS AT 12" O.C.
1/2
"
CONCRETE APRON(SEE CIVIL DRAWINGS)
FOUNDATION WALL BEYOND
OVERHEAD DOOR(SEE ARCHITECTURAL)
FLOOR SLAB(SEE PLAN)
FOUNDATION WALL
#4 HAIRPIN8'-0" LONG EACH LEGCENTERED IN SLAB
HAIRPINS AT ENDS
RIGID FRAME COLUMNBY MBS
HAIRPINS AT CORNERS
30° 30°45°
45°
5" CONCRETE SLAB WITH 4x4-W4.0xW4.0 WWFSLAB SHALL RECEIVE BROOM FINISH
STOOP FOUNDATION WALLWITH CONTINUOUS #5 BARTOP AND BOTTOM.
#5 DOWELS AT 16" O.C.AROUND PERIMETER OF STOOP
FOOTING, SF1.5(SEE SCHEDULE)
5' - 0"
18"
18"
EXISTING BUILDINGFOUNDATION WALLAND FOOTING
COMPACTED GRANULAR FILLFROM BOTTOM OF SLABTO TOP OF FOOTING
T.O. STOOP WALL
99' - 8"
T.O. FOOTING
MATCH BLDG FOOTING
#5 DOWELS AT 16" O.C.AROUND PERIMETER OF STOOP
EXISTING FLOOR SLAB
5" BAR AT 16" O.C. (12" LONG, 6" EMBED)
1/4
"
1/8" / FOOT
EXISTING CMU WALLBEYOND
NEW SLAB SLB05(SEE DETAIL 1/S-511)
1/2" ISOLATION JOINT MATERIALWITH FLEXIBLE JOINT SEALANTAT TOP OF JOINT
X X X X
EXISTING 6" SLAB
EXISTING FOUNDATION WALL
NEW SLAB SLB05(SEE DETAIL 1/S-511)
REMOVE EXISTING 4" SLAB
EXISTING EXTERIORCMU WALL BEYOND
XXX
DRILL AND GROUT(3) #4 BENT BARS INTOEXISTING FOUNDATION WALL
EXISTING FOUNDATION WALL,REMOVE TOP 5" FORNEW CONCRETE SLAB
NEW SLAB SLB05(SEE DETAIL 1/S-511)
EXISTING 4" SLAB
EXISTING CMU WALL BEYOND
1/2" ISOLATION JOINT MATERIALWITH FLEXIBLE JOINT SEALANTAT TOP OF JOINT
X X X
TRENCH DRAIN(SEE PLUMBING)
#4 BENT BARSAT 16" O.C.
(2) #4 BARSCONTINUOUS
CONCRETE SLAB(SEE FLATWORK PLAN)
TD RIM
SEE FLATWORK PLAN
1' - 0" 1' - 0"
1' -
8"
48"
2" CLEAR
WIDTH x LENGTH (SEE PLAN)
FIELD VERIFYT.O. GRADE
#4 BARS AT 12" O.C.EACH WAY TOP & BTM
STEEL TROWEL AND SEAL
ISOLATEDEQUIPMENT PAD
#4 BENT BARS AT12" O.C. ALLAROUND
8"
VARIES
TOOL EDGES
8"
1/2" ISOLATION JOINTMATERIAL WTIH 1/2"FLEXIBLE JOINT SEALANTAT TOP OF JOINT
ADJACENT SLABAND/OR ASPHALT
6"
6"
© CopyrightThis document, or any portion thereof, shallnot be duplicated, disclosed, or used on anyother project or extension of this projectexcept by written agreement with Mead &Hunt, Inc. Mead & Hunt shall not beresponsible for any unauthorized use of, oralteration to these documents.
SHEET CONTENTS
DO NOT SCALE DRAWINGS
M&H NO.:
DATE:
DESIGNED BY:
DRAWN BY:
CHECKED BY:
ISSUED
SHEET NO.:
Mead & Hunt, Inc.6501 Watts Road
Madison, WI 53719phone: 608-273-6380
meadhunt.com
NGB PN.: W90FYQ-10-D-0009-9E01
3/2
4/2
014 1
2:5
2:0
7 P
MC
:\R
evit L
ocal\3288700-1
21973.0
1-A
S-C
entr
al_
586m
jb.r
vt
ILLIN
OIS
AR
MY
NA
TIO
NA
L G
UA
RD
2900 W
JE
FF
ER
SO
N S
TR
EE
TJO
LIE
T, IL
LIN
OIS
S-511
3288700-121973.01
ACT
DXC
FLATWORK DETAILS
RE
HA
B +
AD
DIT
ION
TO
JO
LIE
T F
MS
12
2014
03/25/14
DXC
17090578IL ARNG PN.:
1" = 1'-0"1STRUCTURAL SLAB TYPES
1 1/2" = 1'-0"2
CONCRETE SLAB
CONSTRUCTION JOINT (TYPICAL)
1 1/2" = 1'-0"3
CONCRETE SLAB
CONTROL JOINT "CJ" (TYPICAL) 3/4" = 1'-0"75" STOOP SECTION
1 1/2" = 1'-0"6SLAB AT PASS DOOR
1 1/2" = 1'-0"4
CONCRETE SLAB JOINT
AT SLB08 TO SLB05 TRANSITION
3/4" = 1'-0"8SLAB JOINTS AT ISOLATED COLUMN
1 1/2" = 1'-0"5TYPICAL APRON AT OVERHEAD DOOR
1/2" = 1'-0"12HAIRPINS IN SLAB
3/4" = 1'-0"11NEW STOOP AT EXISTING WALL
1 1/2" = 1'-0"9NEW SLAB IN EXISTING BUILDING
1 1/2" = 1'-0"10NEW SLAB IN EXISTING BUILDING
1 1/2" = 1'-0"13NEW SLAB AT EXISTING BUILDING
1" = 1'-0"14THICKENED SLAB AT TRENCH DRAIN
03/25/14 TYPE B-3 FINALSUBMITTAL
1" = 1'-0"15ISOLATED EQUIPMENT PADS