ISSN (PRINT): 2393-8374, (ONLINE): 2394-0697, VOLUME-7, ISSUE-1, 2020 1 STRUCTURAL ANALYSIS OF AN EARTHQUAKE RESISTANT BUILDING Harshita Tiwari 1 , P.H. Patil 2 1 M.Tech Scholar, Department of Civil Engineering, IES Institute of Technology & Management, Bhopal, M.P., India 2 Assistant Professor, Department of Civil Engineering, IES Institute of Technology & Management, Bhopal, M.P., India Abstract Safety of building at the time of construction is an important aspect to be considered. India is a nation where earthquakes takes place at higher scales. Hence it becomes essential to engineer the design of building in such a way that it can resist the shaking during an earthquake. In the present work the Comparative analysis of ( G + 9 ) multi- storey R.C. structure as per Seismic Code IS 1893( Part-1) 2002 clauses and Seismic Code IS 1893 ( part-1) 2016 clauses. A plan of size 35.90m X 17m and overall height 30 m has been selected. Analysis made for dead load, live load,earthquake load and various load combination are presented. This analysis is made by using computer software STAAD PRO Keywords: earthquake, dead load, live loads, stadd pro, construction INTRODUCTION An earthquake may be defined as wave like motion generated by forces in constant turmoil under the surface layer of the earth, enormous amounts of energy are released. The size and asperity of an earthquake is estimated by two important parameter- intensity and magnitude. The magnitude is a measure amount of energy released, while the intensity is the apparent effect experienced at a specific location. The response of structure to strong earthquake motion are discussed the need of seismic zoning and general principles to be observed in the earthquake resistant design of structure are also discussed. When structure is subjected to ground motion in an earthquake, it provides a response by undergoing vibration comprising the random movement regarding the ground takes place due to earthquake can be settled in any three commonly perpendicular course the two even bearing ( X and Y ) and the vertical heading ( Z). Civil engineering structures are designed on the basis of two main criteria – strength and stiffness. The strength is related to damageability or ultimate limit state, whereas the stiffness is related to serviceability limit state for the structure displacements must remain limited. In case of earthquake – resistant design, a new criteria, the ductility should also be added. The first two criteria, can be achieved by-(a) specifying severe ( or moderate ) design earthquake levels, (b) limiting the maximum stresses at internal forces in critical members, and ( c ) Limiting the story drift ratio. The third criterion, which is prevention of building collapse, is achieved by providing sufficient strength and ductility to ensure that the structure do not collapse in a service earthquake. In structure building field numerous kinds of programming are available in advertise, as – STAAD PRO, RISA, ETABS, SAFE, TKKLA, and SAP2000. In this venture work staad master programming are utilized to plan and investigation of structure. STAAD PRO is the most mainstream structure building programming item for 3D model age, examination and multi material plan Types of Structures Braced structures A typical braced frame is shown in fig 1.5. In braced frames the lateral loads like wind earthquake etc, are resisted by special arrangements like shear walls, shear trusses, bracing or special supports. Thus the beam

Upload: others

Post on 14-May-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: STRUCTURAL ANALYSIS OF AN EARTHQUAKE RESISTANT …troindia.in/journal/ijcesr/vol7iss1/1-27.pdf · STAAD PRO is the most mainstream structure building programming item for 3D model

ISSN (PRINT): 2393-8374, (ONLINE): 2394-0697, VOLUME-7, ISSUE-1, 2020

1

STRUCTURAL ANALYSIS OF AN EARTHQUAKE RESISTANT

BUILDING Harshita Tiwari1, P.H. Patil2

1M.Tech Scholar, Department of Civil Engineering, IES Institute of Technology & Management, Bhopal, M.P., India

2Assistant Professor, Department of Civil Engineering, IES Institute of Technology & Management, Bhopal, M.P., India

Abstract Safety of building at the time of construction is an important aspect to be considered. India is a nation where earthquakes takes place at higher scales. Hence it becomes essential to engineer the design of building in such a way that it can resist the shaking during an earthquake. In the present work the Comparative analysis of ( G + 9 ) multi-storey R.C. structure as per Seismic Code IS 1893( Part-1) 2002 clauses and Seismic Code IS 1893 ( part-1) 2016 clauses. A plan of size 35.90m X 17m and overall height 30 m has been selected. Analysis made for dead load, live load,earthquake load and various load combination are presented. This analysis is made by using computer software STAAD PRO Keywords: earthquake, dead load, live loads, stadd pro, construction INTRODUCTION An earthquake may be defined as wave like motion generated by forces in constant turmoil under the surface layer of the earth, enormous amounts of energy are released. The size and asperity of an earthquake is estimated by two important parameter- intensity and magnitude. The magnitude is a measure amount of energy released, while the intensity is the apparent effect experienced at a specific location. The response of structure to strong earthquake motion are discussed the need of seismic zoning and general principles to be observed in the earthquake resistant design of structure are also discussed. When structure is subjected to ground motion in an earthquake, it provides a response by undergoing vibration comprising the random movement regarding the ground

takes place due to earthquake can be settled in any three commonly perpendicular course the two even bearing ( X and Y ) and the vertical heading ( Z). Civil engineering structures are designed on the basis of two main criteria – strength and stiffness. The strength is related to damageability or ultimate limit state, whereas the stiffness is related to serviceability limit state for the structure displacements must remain limited. In case of earthquake – resistant design, a new criteria, the ductility should also be added. The first two criteria, can be achieved by-(a) specifying severe ( or moderate ) design earthquake levels, (b) limiting the maximum stresses at internal forces in critical members, and ( c ) Limiting the story drift ratio. The third criterion, which is prevention of building collapse, is achieved by providing sufficient strength and ductility to ensure that the structure do not collapse in a service earthquake.

In structure building field numerous kinds of programming are available in advertise, as – STAAD PRO, RISA, ETABS, SAFE, TKKLA, and SAP2000. In this venture work staad master programming are utilized to plan and investigation of structure. STAAD PRO is the most mainstream structure building programming item for 3D model age, examination and multi material plan

Types of Structures Braced structures A typical braced frame is shown in fig 1.5. In braced frames the lateral loads like wind earthquake etc, are resisted by special arrangements like shear walls, shear trusses, bracing or special supports. Thus the beam

Page 2: STRUCTURAL ANALYSIS OF AN EARTHQUAKE RESISTANT …troindia.in/journal/ijcesr/vol7iss1/1-27.pdf · STAAD PRO is the most mainstream structure building programming item for 3D model

INTERNATIONAL JOURNAL OF CURRENT ENGINEERING AND SCIENTIFIC RESEARCH (IJCESR)

ISSN (PRINT): 2393-8374, (ONLINE): 2394-0697, VOLUME-7, ISSUE-1, 2020

2

column frames are not subjected to horizontal loads. In other words the sidesway or joint translation is not possible in column. The structure is called a braced structure and columns occurring in such structure are called the braced column. The shear walls, shear trusses or bracing provided in the building must have stiffness to act as effective bracings. According to SP: 24 the bracing system must provide a total stiffness equal to at least six times the sum of stiffness of all the columns, within the storey. They may become uneconomical for larger height as shear walls are designed as vertical cantilevers from the ground.

Unbraced Structures A typical unbraced frame is shown in Figure 1.5 where resistance to horizontal loads is provided by bending in the beam and column in that plane. In other words, the sidesway or joint translation do occur in such frames. These structures are called unbraced structures and the columns occurring in such structures are called unbraced columns. Dual structures Dual structures are combination of the above two. The resistance to horizontal loads is provided by both, the bending in frames and by shear walls. The frames and shear walls will resist horizontal forces in proportion to their relative stiffness. However, the frame should be designed to carry minimum 25% horizontal shear.

Fig.1:Type Of Structure Load Combinations The load which is ever acting on a structure is the dead load which includes the load of partitions also. which may vary in intensity from 0 to 100% of its value , is additive to the effect of the dead load ; as both these loads are gravity or vertical loads .So the structures should be designed by the limit state method for the dead and live load combinations and it is given by the Code [8].

U = 1.2 (DL+LL+WL or EL)

For checking over turning live loads in above equation may be made zero and 10% reduction may be made in the dead load to account for

any inaccuracy in the calculation of the dead load . This will give the following load combinations for isolated tall structure,

U=1.2(0.9DL+WL or EL )

For inclusion of the blast effect in structural design, we consider a load factor of 1.5 for blast loading, as it occurs frequently in the open cast mining areas. So, for such areas the governing load combination, in addition to those given above, is also,

U=1.5(D+L+B)

Page 3: STRUCTURAL ANALYSIS OF AN EARTHQUAKE RESISTANT …troindia.in/journal/ijcesr/vol7iss1/1-27.pdf · STAAD PRO is the most mainstream structure building programming item for 3D model

INTERNATIONAL JOURNAL OF CURRENT ENGINEERING AND SCIENTIFIC RESEARCH (IJCESR)

ISSN (PRINT): 2393-8374, (ONLINE): 2394-0697, VOLUME-7, ISSUE-1, 2020

3

Also it is assumed that the worst effect of blast will not take place together with the worst effect of earthquake or wind or temperature.

The notation in equations is explained below: U= ultimate load D= dead load L= live load W=wind load E= earthquake load T=temperature and shrinkage load B= blast load

Literature Reviews P.S. Girigosavi, Prof. M. S. Kakamare Apr-2018“ STATIC ANALYSIS OF MULTI-STORIED BUILDING AS PER IS 1893-2002 AND IS 1893-2016”[3]:This paper worried about investigation on modification of IS 1893-2016.The static analysis of multi-celebrated structure is finished by utilizing FEM based programming. In present examination, the static analysis is done according to IS 1893-2016 and results, for example, parallel uprooting, base shear, story drift are contrasted and IS1893-2002. This paper manages the examination of configuration powers for multi-celebrated buildings, acquired by utilizing IS 1893-2016 code, with those got by the past IS1893-2002 rendition. From the aftereffects of seismic analysis of buildings it is presumed that the IS1893-2016 is increasingly moderate for tremor analysis of multi-story buildings.

Urunkar S. S., Bogar V. M., Hadkar P. S.(COMPARATIVE STUDY OF CODAL PROVISIONS IN IS 1893 (PART 1): 2002 & IS 1893 (PART 1): 2016 ) [4]: The conditions gave in seismic code manage the planners to improve the conduct of structures during a quake and withstand against it without critical death toll and property. For India, Indian Standard Criteria for Earthquake Resistant Design of Structures (IS 1893 Part 1) provides the required clauses to structural designers for designing earthquake resistant buildings. Because of nonstop research, picked up information and encounters, the IS 1893 Part 1 has been updated at whatever point required. The relative investigation of codal arrangements is required to be made at whatever point the code is reconsidered. This paper contains the near investigation of an IS 1893 (Part 1):2002 and IS 1893 (Part 1):2016. The paper for the

most part centers around the modified codal arrangements in IS 1893 (Part 1):2016.

S. Farrukh Anwar, A. K. Asthana (2013) “Evaluation of Seismic Design Forces of Indian Building Code” [5]: The ongoing fifth modification of Indian Seismic Code, IS: 1893 has been part into five separate parts for various kinds of structures. The new code IS: 1893 (Part-1) 2002 contains arrangements explicit to buildings just, alongside general arrangements appropriate to all structures. This paper manages the examination of seismic plan powers for multi-celebrated buildings, acquired by utilizing the new code, with those got by the past 1984 adaptation. From the aftereffects of seismic analysis of buildings it is reasoned that the new code is increasingly traditionalist for buildings laying on delicate and medium soils.

S.K. Ahirwar, S.K. Jain and M. M. Pande (2008) “earthquake loads on multistorey buildings as per is: 1893- 1984 and is: 1893-2002: a comparative study” [6]: Accordingly Indian seismic code Seems to be: 1893 has likewise been amended in year 2002.This paper shows the seismic burden estimation for multi-story buildings according to May be: 1893-1984 and IS: 1893-2002 proposals. Four multistorey RC encircled buildings going from three celebrated to nine celebrated are considered and broke down. The procedure gives a lot of five individual analysis successions for each building and the outcomes are utilized to think about the seismic reaction viz. story shear and base shear registered according to the two adaptations of seismic code. The seismic powers, processed by IS: 1893-2002 are seen as essentially higher, the distinction fluctuates with structure properties. It is reasoned that such examination should be done for singular structure to foresee seismic helplessness of RC confined buildings that were planned utilizing before code and because of updates in the codal arrangements may have rendered perilous.

A. A. Kale,, S. A. Rasal, (2017) [7]: In this proposed examination four unique states of same territory multistorey model is created and tried by the ETABS under the rule of IS-875-Part3 and IS1893-2002-Part1. The conduct of 15, 30 and 45 story building has been contemplated. The Dynamic impacts additionally find by Response range strategy.

Page 4: STRUCTURAL ANALYSIS OF AN EARTHQUAKE RESISTANT …troindia.in/journal/ijcesr/vol7iss1/1-27.pdf · STAAD PRO is the most mainstream structure building programming item for 3D model

INTERNATIONAL JOURNAL OF CURRENT ENGINEERING AND SCIENTIFIC RESEARCH (IJCESR)

ISSN (PRINT): 2393-8374, (ONLINE): 2394-0697, VOLUME-7, ISSUE-1, 2020

4

Every one of the parameters like Story uprooting, Story drift, Base shear, Overturning minutes, Acceleration and Time period are determined. In the wake of contrasting all structure shapes results presumed what area is helpful and either seismic or wind impact is basic.

S.K. Ahirwar, S.K. Jain and M. M. Pande (2008) [8] :This paper exhibits the seismic burden estimation for multistorey buildings according to May be: 1893-1984 and IS: 1893-2002 suggestions. Four multistorey RC surrounded buildings extending from three storeyed to nine storeyed are considered and broke down. The procedure gives a lot of five individual analysis arrangements for each building and the outcomes are utilized to think about the seismic reaction viz. story shear and base shear registered according to the two adaptations of seismic code. The seismic powers, processed by IS: 1893-2002 are seen as altogether higher, the distinction fluctuates with structure properties. It is reasoned that such examination should be completed for singular structure to foresee seismic powerlessness of RC confined buildings that were planned utilizing before code and because of corrections in the codal arrangements may have rendered dangerous.

Dr. H. SudarsanaRao [9]: thought about lateral powers determined according to the arrangements of IS 1893-1984 and IS 1893-2002 for two buildings, one is of 12 stories in region which was in zone I yet later on moved up to zone II, and another structure is of 11 stories arranged in zone II. The STAAD Pro programming was utilized for analysis of both contextual investigations. Creator inferred that the powers determined according to IS 1893-2002 gave higher qualities than the past rendition of working in zone I moved up to zone II. The perception made that the base shear an incentive according to amended IS 1893-2002 is higher for structures in zone II.

Anoj Surwase, Dr. Sanjay K. Kulkarni , Prof. Manoj Deosarkar(2018) [10]:"Seismic Analysis and Comparison of IS 1893(Part-1) 2002 and 2016 of (G+4) Regular and Irregular Building": Considerable improvement in tremor safe structure has been seen in later past. Thus, Indian seismic code IS: 1893 has additionally

been reconsidered in year 2016, following a hole of 14 years. This paper displays the seismic burden estimation for multistorey buildings according to May be: 1893-2002 and IS: 1893-2016 proposals. The strategy for analysis and structure of multi-story (G+4) private structure situated in zone III, IV. The extension behind exhibiting this task is to learn applicable Indian standard codes are utilized for plan of different structure component, for example, shaft, segment, section, establishment and stair case utilizing a product E-tab under the seismic burden and wind load acting the structure. We need to discover the qualities in venture base shear, timespan, most extreme story removal.

N.Veerababu, B Anil Kumar, 2016, [11] : In this investigation an undertaking has been made to deliver response spectra using site specific soil parameters for a couple of goals in seismic zone V, for example Arunachal Pradesh and Meghalaya and the delivered response spectra is used to separate a couple of structures using business programming STAAD Pro. The effect of soil properties, its sorts and the significance of soil in the response go is discussed. The response go is gotten in which the physical properties and time history data of a tremor for example North-East seismic tremor of September 10, 1986 which had the significance of 5.2 is considered. Finally assessments have been made in the structure plot by taking IS 1893:2002 response spectra under idea with the structure arranged by considering the made response spectra for various sorts of soil for the seismic zone the extent that bending minute, shear forces and fortress.

K Venu Manikanta, Dr. Dumpa Venkateswarlu, 2016, [12] :The principle reason for this investigation is to do a point by point analysis on reenactment instruments ETABS and STAAD PRO,which have been utilized for analysis and structure of rectangular Plan with vertical normal and rectangular Plan with Vertical geometrically unpredictable multi-story building. This examination is centeredaround bringing out focal points of utilizing ETABS overcurrent practices of STAAD PRO forms to light. It was seen that ETABS is more easy to understand, precise, perfect for dissecting configuration results and a lot more points of interest to be examined in

Page 5: STRUCTURAL ANALYSIS OF AN EARTHQUAKE RESISTANT …troindia.in/journal/ijcesr/vol7iss1/1-27.pdf · STAAD PRO is the most mainstream structure building programming item for 3D model

INTERNATIONAL JOURNAL OF CURRENT ENGINEERING AND SCIENTIFIC RESEARCH (IJCESR)

ISSN (PRINT): 2393-8374, (ONLINE): 2394-0697, VOLUME-7, ISSUE-1, 2020

5

this investigation over STAADPRO. Upsides and downsides of utilizing these product's are additionally be referenced in this investigation.

Sanjay Kumar Sadh, Dr. Umesh Pendharkar, 2016, [13] :Creators centers around the impact of both Vertical Aspect Ratio (H/B proportion for example Thinness Ratio) and Horizontal or Plan Aspect Ratio (L/B proportion), where H is the all out Height of the structure outline, B is the Base width and L is the Length of the structure outline with various Plan Configurations on the Seismic Analysis of Multistoried Regular R.C.C. Buildings. In the present examination, four structure models having distinctive Horizontal Aspect

proportions viz. 1, 4, 6 and 8 running from 12m.to 96m.length of various Vertical Aspect proportions (slimness proportions) viz. 1, 4, 6 and 8 of shifting 4, 16, 24 and 32 stories have been considered and their impact on the conduct of the RCC Multi celebrated buildings is illustrated, utilizing the parameters for the plan according to the Seems to be 1893-2002-Part-1 for the seismic zone-3. Along these lines all out 16 structure models are examined for various burden blends by Linear Elastic Static Analysis (Equivalent static power analysis) with the assistance of ETABS-2015 programming and the outcomes acquired on seismic reaction of buildings have been outlined.

Methodology

Fig. 2:Method of Analysis Analysis by using staad pro STAAD.PRO is the most famous basic building programming item for 3D model age, examination and multi-material plan. It has a natural, easy to understand GUI, representation devices, ground-breaking examination and plan offices and consistent coordination to a few other displaying and structure programming items.

For static or dynamic investigation of extensions, control structures, implanted structures (passages and ducts), pipe racks, steel, solid, aluminum or timber structures,

transmission towers, arenas or some other basic or complex structure, STAAD.PRO has been the decision of plan experts around the globe for their particular examination needs.

Load Acts on the structure In my analysis three type of load was consider which is given below:

• Dead load • Live load • Seismic load As Per IS: 1893-2002

(Part-1), IS 1893-2016 (Part 1).

Page 6: STRUCTURAL ANALYSIS OF AN EARTHQUAKE RESISTANT …troindia.in/journal/ijcesr/vol7iss1/1-27.pdf · STAAD PRO is the most mainstream structure building programming item for 3D model

INTERNATIONAL JOURNAL OF CURRENT ENGINEERING AND SCIENTIFIC RESEARCH (IJCESR)

ISSN (PRINT): 2393-8374, (ONLINE): 2394-0697, VOLUME-7, ISSUE-1, 2020

6

Table 1: Seismic Definition as per IS 1893 ( Part-1) 2002 Clauses Parameters Value

Zone ( II) 0.10 Response Reduction Factor ( RF ) 5

Importance Factor ( I ) 1 Rock and soil site factor ( SS ) 1

Type Of Structure ( ST ) 1 Damping ratio ( DM ) 0.05

Period in X direction ( PX ) 0.45 [( 0.09 X h)/√dx]

[( 0.09 X 30)/√35.90 = 0.45 s] Period in Z direction ( PZ ) 0.65 [( 0.09 X h)/√dz]

[( 0.09 X 30)/√17.00 = 0.65 s] Depth of Foundation ( DT ) 1.8

Table 2: Seismic definition as per IS 1893 ( Part-1) 2016 clauses

Parameters Value Zone ( II) 0.10

Response Reduction Factor ( RF ) 5 Importance Factor ( I ) 1.2

Rock and soil site factor ( SS ) 1 Type Of Structure ( ST ) 1

Damping ratio ( DM ) 0.05 Period in X direction ( PX ) 0.45 [( 0.09 X h)/√dx]

[( 0.09 X 30)/√35.90 = 0.45 s] Period in Z direction ( PZ ) 0.65 [( 0.09 X h)/√dz]

[( 0.09 X 30)/√17.00 = 0.65 s] Depth of Foundation ( DT ) 1.8

Plan of Building

Fig. 3:Plan Of Building

Page 7: STRUCTURAL ANALYSIS OF AN EARTHQUAKE RESISTANT …troindia.in/journal/ijcesr/vol7iss1/1-27.pdf · STAAD PRO is the most mainstream structure building programming item for 3D model

INTERNATIONAL JOURNAL OF CURRENT ENGINEERING AND SCIENTIFIC RESEARCH (IJCESR)

ISSN (PRINT): 2393-8374, (ONLINE): 2394-0697, VOLUME-7, ISSUE-1, 2020

7

Plan of Structure

Fig.2:Plan Of Building Plan of Structure With shear wall

Fig. 5:Plan Of Building With Shear Wall Height of structure

Fig. 6:Height Of Structure

Page 8: STRUCTURAL ANALYSIS OF AN EARTHQUAKE RESISTANT …troindia.in/journal/ijcesr/vol7iss1/1-27.pdf · STAAD PRO is the most mainstream structure building programming item for 3D model

INTERNATIONAL JOURNAL OF CURRENT ENGINEERING AND SCIENTIFIC RESEARCH (IJCESR)

ISSN (PRINT): 2393-8374, (ONLINE): 2394-0697, VOLUME-7, ISSUE-1, 2020

8

Loading Combination used for analysis Table 3: Table Caption in Title Case.

I 1.5 (DL+LL) II 1.2 (DL+LL+ELZ) III 1.2 (DL+LL-ELZ) IV 1.2 (DL+LL+ELx) V 1.2 (DL+LL-ELx) VI 1.5 (DL+ELZ) VII 1.5 (DL-ELZ) VIII 1.5 (DL+ELx) IX 1.5 (DL-ELx) X 0.9 DL +1.5ELZ XI 0.9 DL -1.5ELZ XII 0.9 DL +1.5ELx XIII 0.9 DL -1.5ELx

Modelling Of Structure Table 5: Table Caption in Title Case.

Number of Nodes 3945 Number Of Beam 7853

Number Of Support 71

Fig. 7:Plan of structure

Fig. 8:Plan of structure with shear wall

Page 9: STRUCTURAL ANALYSIS OF AN EARTHQUAKE RESISTANT …troindia.in/journal/ijcesr/vol7iss1/1-27.pdf · STAAD PRO is the most mainstream structure building programming item for 3D model

INTERNATIONAL JOURNAL OF CURRENT ENGINEERING AND SCIENTIFIC RESEARCH (IJCESR)

ISSN (PRINT): 2393-8374, (ONLINE): 2394-0697, VOLUME-7, ISSUE-1, 2020

9

Fig. 8:elevation

Fig. 9:3D view Results Comparison of base shear when structure is analyzed as per Seismic code IS 1893( Part-1)

2002 Clauses and as per Seismic code IS 1893( Part-1)2016 Clauses

.

Page 10: STRUCTURAL ANALYSIS OF AN EARTHQUAKE RESISTANT …troindia.in/journal/ijcesr/vol7iss1/1-27.pdf · STAAD PRO is the most mainstream structure building programming item for 3D model

INTERNATIONAL JOURNAL OF CURRENT ENGINEERING AND SCIENTIFIC RESEARCH (IJCESR)

ISSN (PRINT): 2393-8374, (ONLINE): 2394-0697, VOLUME-7, ISSUE-1, 2020

10

Table 6: Comparison Base shear

IS Code Base shear Direction - X

Base shear Direction - Z

IS 1893-2002 3306.13 2253.23 IS 1893-2016 3963.13 2705

Fig.30:Comparison Base shear Parameter 3. Comparison of nodal displacement when structure is analyzed as per Seismic code IS 1893(Part-1) 2002 Clauses and

as per Seismic code IS 1893(Part -1)2016 Clauses.

Table 7: Comparison Nodal Displacement Column C1 Floor Level Displacement (mm)

IS 1893(Part 1)-2002 IS 1893(Part 1)-2016 X-

Direction Z- Direction X- Direction

Z- Direction

N.F. 24.652 0.928 58.965 22.732 E.F. 23.678 0.920 57.208 22.169 S.F. 22.100 0.901 54.447 21.155 S.F. 20.153 0.855 50.568 19.674 F.F. 17.802 0.784 45.623 17.764 F.F. 15.140 0.690 39.694 15.485 T.F. 12.259 0.578 32.927 12.87 S.S. 9.246 0.451 25.551 9.979 F.F. 6.189 0.310 17.712 6.875 G.F. 3.209 0.162 9.551 3.644 P.L. 0.618 0.032 1.873 0.707

0

500

1,000

1,500

2,000

2,500

3,000

3,500

4,000

4,500

Base shear Direction - X Base shear Direction - Z

Base

She

ar(k

n)

Base Shear

IS 1893-2002

IS 1893-2016

Page 11: STRUCTURAL ANALYSIS OF AN EARTHQUAKE RESISTANT …troindia.in/journal/ijcesr/vol7iss1/1-27.pdf · STAAD PRO is the most mainstream structure building programming item for 3D model

INTERNATIONAL JOURNAL OF CURRENT ENGINEERING AND SCIENTIFIC RESEARCH (IJCESR)

ISSN (PRINT): 2393-8374, (ONLINE): 2394-0697, VOLUME-7, ISSUE-1, 2020

11

Fig.41:C1 Column Displacement (mm)- X Direction

Fig.52:C1 Column Displacement (mm) - Z Direction

0

10

20

30

40

50

60

70

80

90

N.F. E.F. S.F. S.F. F.F. F.F. T.F. S.S. F.F. G.F. P.L.

Disp

lace

men

t (m

m)

Floor Level

IS 1893(part1)-2016

IS 1893(part1)-2002

0

5

10

15

20

25

N.F. E.F. S.F. S.F. F.F. F.F. T.F. S.S. F.F. G.F. P.L.

Disp

lace

men

t (m

m)

Floor Level

IS 1893(part1)-2016

IS 1893(part1)-2002

Page 12: STRUCTURAL ANALYSIS OF AN EARTHQUAKE RESISTANT …troindia.in/journal/ijcesr/vol7iss1/1-27.pdf · STAAD PRO is the most mainstream structure building programming item for 3D model

INTERNATIONAL JOURNAL OF CURRENT ENGINEERING AND SCIENTIFIC RESEARCH (IJCESR)

ISSN (PRINT): 2393-8374, (ONLINE): 2394-0697, VOLUME-7, ISSUE-1, 2020

12

Table 8: Comparison Nodal Displacement

Column C2 Floor Level Displacement (mm)

IS 1893(Part 1)-2002 IS 1893(Part 1)-2016 X-

Direction Z- Direction X- Direction Z- Direction

N.F. 24.497 0.515 58.736 20.782 E.F. 23.669 0.528 57.320 20.248 S.F. 22.266 0.528 54.668 19.301 S.F. 20.323 0.512 50.820 17.93 F.F. 17.961 0.481 45.884 16.174 F.F. 15.287 0.436 39.954 14.076 T.F. 12.398 0.378 33.173 11.675 S.S. 9.379 0.306 25.754 9.021 F.F. 6.308 0.22 17.852 6.193 G.F. 3.286 0.122 9.641 3.279 P.L. 0.635 0.025 1.910 0.635

Fig.63:C2 Column Displacement (mm) - X Direction

0

10

20

30

40

50

60

70

80

90

N.F. E.F. S.F. S.F. F.F. F.F. T.F. S.S. F.F. G.F. P.L.

Disp

lace

men

t (m

m)

Floor Level

IS 1893(part1)-2016

IS 1893(part1)-2002

Page 13: STRUCTURAL ANALYSIS OF AN EARTHQUAKE RESISTANT …troindia.in/journal/ijcesr/vol7iss1/1-27.pdf · STAAD PRO is the most mainstream structure building programming item for 3D model

INTERNATIONAL JOURNAL OF CURRENT ENGINEERING AND SCIENTIFIC RESEARCH (IJCESR)

ISSN (PRINT): 2393-8374, (ONLINE): 2394-0697, VOLUME-7, ISSUE-1, 2020

13

Fig.74:C2 Column Displacement (mm) - Z Direction Table 9: Comparison Nodal Displacement

Column C3 Floor Level Displacement (mm)

IS 1893(Part 1)-2002 IS 1893(Part 1)-2016 X-

Direction Z- Direction X- Direction

Z- Direction

N.F. 25.816 0.919 59.738 22.732 E.F. 24.983 0.916 58.313 22.172 S.F. 23.524 0.897 55.596 21.158 S.F. 21.491 0.852 51.728 19.676 F.F. 19.008 0.782 46.488 17.769 F.F. 16.192 0.689 41.014 15.487 T.F. 13.149 0.578 34.346 12.872 S.S. 9.969 0.451 26.931 9.98 F.F. 6.732 0.311 18.902 6.876 G.F. 3.526 0.164 10.335 3.646 P.L. 0.689 0.033 2.047 0.707

0

5

10

15

20

25

N.F. E.F. S.F. S.F. F.F. F.F. T.F. S.S. F.F. G.F. P.L.

Disp

lace

men

t (m

m)

Floor Level

IS 1893(part1)-2016

IS 1893(part1)-2002

Page 14: STRUCTURAL ANALYSIS OF AN EARTHQUAKE RESISTANT …troindia.in/journal/ijcesr/vol7iss1/1-27.pdf · STAAD PRO is the most mainstream structure building programming item for 3D model

INTERNATIONAL JOURNAL OF CURRENT ENGINEERING AND SCIENTIFIC RESEARCH (IJCESR)

ISSN (PRINT): 2393-8374, (ONLINE): 2394-0697, VOLUME-7, ISSUE-1, 2020

14

Fig.85:C3 Column Displacement (mm) - X Direction

Fig.96:C3 Column Displacement (mm) - Z Direction

0

10

20

30

40

50

60

70

80

90

N.F. E.F. S.F. S.F. F.F. F.F. T.F. S.S. F.F. G.F. P.L.

Disp

lace

men

t (m

m)

Floor Level

IS 1893(part1)-2016

IS 1893(part1)-2002

0

5

10

15

20

25

N.F. E.F. S.F. S.F. F.F. F.F. T.F. S.S. F.F. G.F. P.L.

Disp

lace

men

t (m

m)

Floor Level

IS 1893(part1)-2016

IS 1893(part1)-2002

Page 15: STRUCTURAL ANALYSIS OF AN EARTHQUAKE RESISTANT …troindia.in/journal/ijcesr/vol7iss1/1-27.pdf · STAAD PRO is the most mainstream structure building programming item for 3D model

INTERNATIONAL JOURNAL OF CURRENT ENGINEERING AND SCIENTIFIC RESEARCH (IJCESR)

ISSN (PRINT): 2393-8374, (ONLINE): 2394-0697, VOLUME-7, ISSUE-1, 2020

15

Table 10: Comparison Nodal Displacement

Column C4 Floor Level Displacement (mm)

IS 1893(Part 1)-2002 IS 1893(Part 1)-2016 X-

Direction Z- Direction X- Direction Z- Direction

N.F. 24.979 0.147 58.182 4.124 E.F. 24.193 0.120 56.757 4.003 S.F. 22.79 0.102 54.140 3.800 S.F. 20.834 0.087 50.359 3.533 F.F. 18.437 0.074 45.527 3.213 F.F. 15.711 0.060 39.742 2.847 T.F. 12.755 0.046 33.111 2.437 S.S. 9.658 0.030 25.738 1.984 F.F. 6.498 0.016 17.801 1.480 G.F. 3.379 0.005 9.515 0.860 P.L. 0.665 0.001 1.871 0.175

Fig.107:C4 Column Displacement (mm) - X Direction

0

10

20

30

40

50

60

70

80

90

N.F. E.F. S.F. S.F. F.F. F.F. T.F. S.S. F.F. G.F. P.L.

Disp

lace

men

t (m

m)

Floor Level

IS 1893(part1)-2016

IS 1893(part1)-2002

Page 16: STRUCTURAL ANALYSIS OF AN EARTHQUAKE RESISTANT …troindia.in/journal/ijcesr/vol7iss1/1-27.pdf · STAAD PRO is the most mainstream structure building programming item for 3D model

INTERNATIONAL JOURNAL OF CURRENT ENGINEERING AND SCIENTIFIC RESEARCH (IJCESR)

ISSN (PRINT): 2393-8374, (ONLINE): 2394-0697, VOLUME-7, ISSUE-1, 2020

16

Fig.118:C4 Column Displacement (mm) – Z Direction Table 11: Comparison Nodal Displacement

Column C5 Floor Level Displacement (mm)

IS 1893(Part 1)-2002 IS 1893(Part 1)-2016 X-

Direction Z- Direction X- Direction Z- Direction

N.F. 24.623 0.324 57.611 13.611 E.F. 23.848 0.318 56.224 13.249 S.F. 22.466 0.309 53.643 12.618 S.F. 20.537 0.295 49.888 11.713 F.F. 18.175 0.275 45.068 10.562 F.F. 15.490 0.247 39.286 9.196 T.F. 12.579 0.212 32.667 7.630 S.S. 9.529 0.169 25.353 5.888 F.F. 6.418 0.119 17.518 4.040 G.F. 3.346 0.064 9.364 2.150 P.L. 0.659 0.012 1.841 0.415

0

0.5

1

1.5

2

2.5

3

3.5

4

4.5

N.F. E.F. S.F. S.F. F.F. F.F. T.F. S.S. F.F. G.F. P.L.

Disp

lace

men

t (m

m)

Floor Level

IS 1893(part1)-2016

IS 1893(part1)-2002

Page 17: STRUCTURAL ANALYSIS OF AN EARTHQUAKE RESISTANT …troindia.in/journal/ijcesr/vol7iss1/1-27.pdf · STAAD PRO is the most mainstream structure building programming item for 3D model

INTERNATIONAL JOURNAL OF CURRENT ENGINEERING AND SCIENTIFIC RESEARCH (IJCESR)

ISSN (PRINT): 2393-8374, (ONLINE): 2394-0697, VOLUME-7, ISSUE-1, 2020

17

Fig.129:C5 Column Displacement (mm) – X Direction

Fig. 20:C5 Column Displacement (mm) –Z Direction Parameter 4. Comparison of storey drift when structure is analyzed as per Seismic code IS

1893(Part-1) 2002 Clauses and as per Seismic code IS 1893(part-1)2016 Clauses.

0

10

20

30

40

50

60

70

80

90

N.F. E.F. S.F. S.F. F.F. F.F. T.F. S.S. F.F. G.F. P.L.

Disp

lace

men

t (m

m)

Floor Level

IS 1893(part1)-2016

IS 1893(part1)-2002

0

2

4

6

8

10

12

14

16

N.F. E.F. S.F. S.F. F.F. F.F. T.F. S.S. F.F. G.F. P.L.

Disp

lace

men

t (m

m)

Floor Level

IS 1893(part1)-2016

IS 1893(part1)-2002

Page 18: STRUCTURAL ANALYSIS OF AN EARTHQUAKE RESISTANT …troindia.in/journal/ijcesr/vol7iss1/1-27.pdf · STAAD PRO is the most mainstream structure building programming item for 3D model

INTERNATIONAL JOURNAL OF CURRENT ENGINEERING AND SCIENTIFIC RESEARCH (IJCESR)

ISSN (PRINT): 2393-8374, (ONLINE): 2394-0697, VOLUME-7, ISSUE-1, 2020

18

Table 12: Comparison Storey Drift

Column C1 Floor Level Storey Drift (mm)

IS 1893(Part 1)-2002 IS 1893(Part 1)-2016 X-

Direction Z- Direction X- Direction Z- Direction

N.F. 0.974 0.008 1.757 0.563 E.F. 1.578 0.019 2.761 1.014 S.F. 1.947 0.046 3.879 1.481 S.F. 2.351 0.071 4.945 1.910 F.F. 2.662 0.094 5.929 2.279 F.F. 2.881 0.112 6.767 2.615 T.F. 3.013 0.127 7.376 2.891 S.S. 3.057 0.141 7.839 3.104 F.F. 2.980 0.148 8.161 3.231 G.F. 2.591 0.130 7.678 2.937 P.L. 0.618 0.032 1.873 0.707

Fig. 213:C1 Column Storey Drift(mm)- X Direction

0

2

4

6

8

10

12

N.F. E.F. S.F. S.F. F.F. F.F. T.F. S.S. F.F. G.F. P.L.

Drift

(mm

)

Floor Level

IS 1893(Part 1)-2016

IS 1893(Part 1)-2002

Page 19: STRUCTURAL ANALYSIS OF AN EARTHQUAKE RESISTANT …troindia.in/journal/ijcesr/vol7iss1/1-27.pdf · STAAD PRO is the most mainstream structure building programming item for 3D model

INTERNATIONAL JOURNAL OF CURRENT ENGINEERING AND SCIENTIFIC RESEARCH (IJCESR)

ISSN (PRINT): 2393-8374, (ONLINE): 2394-0697, VOLUME-7, ISSUE-1, 2020

19

Fig. 22:C1 Column Storey Drift(mm)- Z Direction Table 13: Comparison Storey Drift

Column C2 Floor Level Storey Drift (mm)

IS 1893(Part 1)-2002 IS 1893(Part 1)-2016 X-

Direction Z- Direction X- Direction Z- Direction

N.F. 0.828 0.006 1.416 0.534 E.F. 1.403 0.010 2.652 0.947 S.F. 1.943 0.016 3.848 1.371 S.F. 2.362 0.031 4.936 1.756 F.F. 2.674 0.045 5.930 2.098 F.F. 2.889 0.058 6.781 2.401 T.F. 3.019 0.072 7.419 2.654 S.S. 3.071 0.086 7.902 2.828 F.F. 3.022 0.098 8.211 2.914 G.F. 2.651 0.097 7.731 2.644 P.L. 0.635 0.025 1.910 0.635

0.0

0.5

1.0

1.5

2.0

2.5

3.0

3.5

4.0

N.F. E.F. S.F. S.F. F.F. F.F. T.F. S.S. F.F. G.F. P.L.

Drift

(mm

)

Floor Level

IS 1893(Part 1)-2016

IS 1893(Part 1)-2002

Page 20: STRUCTURAL ANALYSIS OF AN EARTHQUAKE RESISTANT …troindia.in/journal/ijcesr/vol7iss1/1-27.pdf · STAAD PRO is the most mainstream structure building programming item for 3D model

INTERNATIONAL JOURNAL OF CURRENT ENGINEERING AND SCIENTIFIC RESEARCH (IJCESR)

ISSN (PRINT): 2393-8374, (ONLINE): 2394-0697, VOLUME-7, ISSUE-1, 2020

20

Fig. 23:C2 Column Storey Drift (mm)- X Direction

Fig. 24:C2 Column Storey Drift (mm) - Z Direction

0

2

4

6

8

10

12

N.F. E.F. S.F. S.F. F.F. F.F. T.F. S.S. F.F. G.F. P.L.

Drift

(mm

)

Floor Level

IS 1893(Part 1)-2016

IS 1893(Part 1)-2002

0.0

0.5

1.0

1.5

2.0

2.5

3.0

3.5

N.F. E.F. S.F. S.F. F.F. F.F. T.F. S.S. F.F. G.F. P.L.

Drift

(m

m)

Floor Level

IS 1893(Part 1)-2016

IS 1893(Part 1)-2002

Page 21: STRUCTURAL ANALYSIS OF AN EARTHQUAKE RESISTANT …troindia.in/journal/ijcesr/vol7iss1/1-27.pdf · STAAD PRO is the most mainstream structure building programming item for 3D model

INTERNATIONAL JOURNAL OF CURRENT ENGINEERING AND SCIENTIFIC RESEARCH (IJCESR)

ISSN (PRINT): 2393-8374, (ONLINE): 2394-0697, VOLUME-7, ISSUE-1, 2020

21

Table 14: Comparison Storey Drift Column C3 Floor Level Storey Drift (mm)

IS 1893(Part 1)-2002 IS 1893(Part 1)-2016 X-

Direction Z- Direction X- Direction Z- Direction

N.F. 0.833 0.003 1.425 0.560 E.F. 1.459 0.019 2.717 1.014 S.F. 2.033 0.045 3.868 1.482 S.F. 2.483 0.070 5.240 1.907 F.F. 2.816 0.093 5.474 2.282 F.F. 3.043 0.111 6.668 2.615 T.F. 3.180 0.127 7.415 2.892 S.S. 3.237 0.140 8.029 3.104 F.F. 3.206 0.147 8.567 3.230 G.F. 2.837 0.131 8.288 2.939 P.L. 0.689 0.033 2.047 0.707

Fig. 25:C3 Column Storey Drift (mm) - X Direction

0

2

4

6

8

10

12

14

N.F. E.F. S.F. S.F. F.F. F.F. T.F. S.S. F.F. G.F. P.L.

Drift

(m

m)

Floor Level

IS 1893(Part 1)-2016

IS 1893(Part 1)-2002

Page 22: STRUCTURAL ANALYSIS OF AN EARTHQUAKE RESISTANT …troindia.in/journal/ijcesr/vol7iss1/1-27.pdf · STAAD PRO is the most mainstream structure building programming item for 3D model

INTERNATIONAL JOURNAL OF CURRENT ENGINEERING AND SCIENTIFIC RESEARCH (IJCESR)

ISSN (PRINT): 2393-8374, (ONLINE): 2394-0697, VOLUME-7, ISSUE-1, 2020

22

Fig. 26:C3 Column Storey Drift (mm) - Z Direction Table 14: Comparison Storey Drift

Column C4 Floor Level Storey Drift (mm)

IS 1893(Part 1)-2002 IS 1893(Part 1)-2016 X-

Direction Z- Direction X- Direction Z- Direction

N.F. 0.786 0.027 1.425 0.121 E.F. 1.403 0.018 2.617 0.203 S.F. 1.956 0.015 3.781 0.267 S.F. 2.397 0.013 4.832 0.320 F.F. 2.726 0.014 5.785 0.366 F.F. 2.956 0.014 6.631 0.410 T.F. 3.097 0.016 7.373 0.453 S.S. 3.160 0.014 7.937 0.504 F.F. 3.119 0.011 8.286 0.620 G.F. 2.714 0.004 7.644 0.685 P.L. 0.665 0.001 1.871 0.175

0.0

0.5

1.0

1.5

2.0

2.5

3.0

3.5

4.0

N.F. E.F. S.F. S.F. F.F. F.F. T.F. S.S. F.F. G.F. P.L.

Drift

(mm

)

Floor Level

IS 1893(Part 1)-2016

IS 1893(Part 1)-2002

Page 23: STRUCTURAL ANALYSIS OF AN EARTHQUAKE RESISTANT …troindia.in/journal/ijcesr/vol7iss1/1-27.pdf · STAAD PRO is the most mainstream structure building programming item for 3D model

INTERNATIONAL JOURNAL OF CURRENT ENGINEERING AND SCIENTIFIC RESEARCH (IJCESR)

ISSN (PRINT): 2393-8374, (ONLINE): 2394-0697, VOLUME-7, ISSUE-1, 2020

23

Fig. 27:C4 Column Storey Drift (mm) - X Direction

0

2

4

6

8

10

12

N.F. E.F. S.F. S.F. F.F. F.F. T.F. S.S. F.F. G.F. P.L.

Drift

(mm

)

Floor Level

IS 1893(Part 1)-2016

IS 1893(Part 1)-2002

0.0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

N.F. E.F. S.F. S.F. F.F. F.F. T.F. S.S. F.F. G.F. P.L.

Drift

(mm

)

Floor Level

IS 1893(Part 1)-2016

IS 1893(Part 1)-2002

Page 24: STRUCTURAL ANALYSIS OF AN EARTHQUAKE RESISTANT …troindia.in/journal/ijcesr/vol7iss1/1-27.pdf · STAAD PRO is the most mainstream structure building programming item for 3D model

INTERNATIONAL JOURNAL OF CURRENT ENGINEERING AND SCIENTIFIC RESEARCH (IJCESR)

ISSN (PRINT): 2393-8374, (ONLINE): 2394-0697, VOLUME-7, ISSUE-1, 2020

24

Fig. 28:C4 Column Storey Drift (mm) - Z Direction Table 15: Comparison Storey Drift

Column C5 Floor Level Storey Drift (mm)

IS 1893(Part 1)-2002 IS 1893(Part 1)-2016 X-

Direction Z- Direction X- Direction Z- Direction

N.F. 0.775 0.006 1.387 0.362 E.F. 1.382 0.009 2.581 0.631 S.F. 1.929 0.014 3.755 0.905 S.F. 2.362 0.020 4.820 1.151 F.F. 2.685 0.028 5.782 1.366 F.F. 2.911 0.035 6.619 1.566 T.F. 3.050 0.043 7.314 1.742 S.S. 3.111 0.050 7.835 1.848 F.F. 3.072 0.055 8.154 1.890 G.F. 2.687 0.052 7.523 1.735 P.L. 0.659 0.012 1.841 0.415

Fig. 29:C5 Column Storey Drift (mm) - X Direction

0

2

4

6

8

10

12

N.F. E.F. S.F. S.F. F.F. F.F. T.F. S.S. F.F. G.F. P.L.

Drift

(mm

)

Floor Level

IS 1893(Part 1)-2016

IS 1893(Part 1)-2002

Page 25: STRUCTURAL ANALYSIS OF AN EARTHQUAKE RESISTANT …troindia.in/journal/ijcesr/vol7iss1/1-27.pdf · STAAD PRO is the most mainstream structure building programming item for 3D model

INTERNATIONAL JOURNAL OF CURRENT ENGINEERING AND SCIENTIFIC RESEARCH (IJCESR)

ISSN (PRINT): 2393-8374, (ONLINE): 2394-0697, VOLUME-7, ISSUE-1, 2020

25

Fig. 30:C5 Column Storey Drift (mm) - Z Direction Conclusions In the present work the Seismic investigation of ( G + 9 ) multi-story R.C. structure according to Seismic Code IS 1893( Part-1) 2002 statements and Seismic Code IS 1893 ( section 1) 2016 provisions. An arrangement of size 35.90m X 17m and generally speaking tallness 30 m has been chosen. Examination made for dead burden, live burden ,seismic tremor load and different burden mix are displayed. This investigation is made by utilizing PC programming STAAD PRO.

The structure is broke down for Six diverse Parameter and results are produced for these Six Parameter. First Parameter includes examination of Seismic code IS 1893(Part-1) 2002 Clauses and Seismic code IS 1893(Part-1) 2016 Clauses.

Second Parameter includes correlation of Base shear when structure is examined according to Seismic code IS 1893(Part-1) 2002 Clauses and Seismic code IS 1893(Part-1) 2016 Clauses. For this Parameter results dependent on correlation

of Base shear are introduced in unthinkable structure and thought about by charts.

Third Parameter includes correlation of Nodal Displacement when structure is examined according to Seismic code IS 1893(Part-1) 2002 Clauses and Seismic code IS 1893(Part-1) 2016 Clauses. For this Parameter results dependent on examination of Nodal Displacement are introduced in unthinkable structure and thought about by diagrams.

Fourth Parameter includes examination of Story Drift when structure is broke down according to Seismic code IS 1893(Part-1) 2002 Clauses and Seismic code IS 1893(Part-1) 2016 Clauses. For this Parameter results dependent on examination of Story Drift are exhibited in unthinkable structure and thought about by charts.

Fifth Parameter includes Comparison of nodal dislodging when structure is broke down with shear divider and without shear divider according to Seismic code IS 1893( section 1)2016 Clauses . For this Parameter results

0.0

0.5

1.0

1.5

2.0

2.5

N.F. E.F. S.F. S.F. F.F. F.F. T.F. S.S. F.F. G.F. P.L.

Drift

(mm

)

Floor Level

IS 1893(Part 1)-2016

IS 1893(Part 1)-2002

Page 26: STRUCTURAL ANALYSIS OF AN EARTHQUAKE RESISTANT …troindia.in/journal/ijcesr/vol7iss1/1-27.pdf · STAAD PRO is the most mainstream structure building programming item for 3D model

INTERNATIONAL JOURNAL OF CURRENT ENGINEERING AND SCIENTIFIC RESEARCH (IJCESR)

ISSN (PRINT): 2393-8374, (ONLINE): 2394-0697, VOLUME-7, ISSUE-1, 2020

26

dependent on correlation of nodal relocation are displayed in unthinkable structure what's more, looked at by charts.

6th Parameter includes Comparison of Story Drift when structure is dissected with shear divider and without shear divider according to Seismic code IS 1893( section 1)2016 Clauses . For this Parameter results dependent on correlation of Story Drift are displayed in unthinkable structure and thought about by diagrams.

In this section we characterize the correlation of code and after examination of code provisions float ,removal and base shear esteem is higher in X and Z bearing in Parameter 2, Parameter 3 and Parameter 4 as indicated by Seismic code IS 1893 ( part-1)2016 statements as contrast with Seismic code IS 1893 (section 1) 2002 provisos.

The explanation of base shear esteem is higher as I ( Importance factor ) as indicated by old code provisions: 6.4.2 significance factor( I) 1.0 for every single other structure however now in new code conditions 7.2.3 for private or business working with inhabitance in excess of 200 people significance factor 1.2 has been appointed. After a progressions an incentive As I increment ,Ah will increment and in this manner base shear VB will increment.

This may prompt increment in measure of sidelong loads on the structure and in the end increment the size of the parallel burden opposing individuals and fortification. eventually structure cost may increment however in a similar time the auxiliary quality is likewise increase.to ward the seismic tremor load. float and dislodging esteem is higher in Case of snapshot of Inertia ( I), this conditions is included for security and post-quake impact. In Seismic code IS 1893 (Part-1) 2002 full area, full M.I. of segment and pillar considered. In Seismic code IS 1893(Part-1) 2016, split segment with 70 % MI of Columns and 35 % MI of Beam is considered. As concrete is appear to be broken segment record-breaking, one can't consider the full MI of RC segment for examination. Full MI of RC individuals makes make structure solid thus the redirection at top story, float of story, Lateral removal of story and so forth assessed wrongly as littler

qualities. Then again by thinking about the broke snapshot of idleness horizontal redirection, floats and so on will increment and to control one ought to need to expand the size of parallel burden opposing individuals which eventually cause wellbeing of structure. Thus for wellbeing it is increasingly sensible to consider broken area properties in investigation.

Diminishing the higher estimation of float and dislodging factor, we giving the shear divider framework in this structure according to Seismic code IS 1893 (section 1) 2016 provisions. Think about the outcomes without shear divider and with shear divider framework in Parameter 5 and Parameter 6 according to Seismic code IS 1893 ( Part-1) 2016 provisions. After contrast the parameter and the assistance of shear divider and without shear divider framework in seismic code IS 1893(Part-1) 2016,Drift and Displacement esteem is lessen in X and Z bearing

References 1. IS: 1893(Part 1): 2002, " Criteria for Earthquake Resistant Design of Structures." Part-1, Bureau of Indian Standards, New Delhi, 2002. 2. IS: 1893(Part 1): 2016, " Criteria for Earthquake Resistant Design of Structures." Part-1, Bureau of Indian Standards, New Delhi, 2016. 3. Earthquake‐Resistant Design of Structures Second Edition S.K.Duggal. 4. Mayur R. Rethaliya, Bhavik R. Patel , Dr. R. P. RethaliyaComparative Study of Various Clauses of New IS 1893 (Part 1):2016 and Old IS 1893 (Part1):2002 International Journal for Research in Applied Science & Engineering Technology (IJRASET) Volume 6 Issue I, January 2018- 5. Urunkar S. S., Bogar V. M., Hadkar P. S.(COMPARATIVE STUDY OF CODAL PROVISIONS IN IS 1893 (PART 1): 2002 & IS 1893 (PART 1): 2016 ) International Journal for Research in Applied Science & Engineering Technology (IJRASET) Volume 7 special Issue no. 1 march 2018- 6. P.S. Girigosavi, Prof. M. S. KakamareSTATIC ANALYSIS OF MULTI-STORIED BUILDING AS PER IS 1893-2002 AND IS 1893-2016 International Research Journal of Engineering and Technology (IRJET)Volume: 05 Issue: 04 | Apr-2018.

Page 27: STRUCTURAL ANALYSIS OF AN EARTHQUAKE RESISTANT …troindia.in/journal/ijcesr/vol7iss1/1-27.pdf · STAAD PRO is the most mainstream structure building programming item for 3D model

INTERNATIONAL JOURNAL OF CURRENT ENGINEERING AND SCIENTIFIC RESEARCH (IJCESR)

ISSN (PRINT): 2393-8374, (ONLINE): 2394-0697, VOLUME-7, ISSUE-1, 2020

27

7. S. Farrukh Anwar, A. K. Asthana (2013) “Evaluation of Seismic Design Forces of Indian Building Code” International Journal of Engineering Research & Technology (IJERT)( ISSN: 2278-0181, Vol. 2 Issue 6, June – 2013). 8. S.K. Ahirwar, S.K. Jain and M. M. Pande (2008) “Earthquake loads on multistorey buildings as per is:1893-1984 and is: 1893-2002: a comparative study” The 14th World Conference on Earthquake Engineering October 12-17, 2008, Beijing, China. 9. A. A. Kale, S. A. Rasal, Seismic & Wind Analysis of Multistorey Building: A Review, International Journal of Science and Research (IJSR), Volume 6 Issue 3, March 2017. 10. S.K. Ahirwar, S.K. Jain and M. M. Pande, Earthquake Loads on Multistorey Buildings as Per IS: 1893-1984 AND IS: 1893- 2002: A COMPARATIVE STUDY, The 14th World Conference on Earthquake Engineering October 12-17, 2008, Beijing, China. 11. Dr. H. SudarsanaRao, Comparative study of seismic lateral forces as per IS 1893- 1984 & IS 1893- 2002, International Journal of Emerging Trends Engineering & Development, issue 4, vol. 4,282-299. 12. AnojSurwase, Dr. Sanjay K. Kulkarni, Prof. ManojDeosarkarSeismic Analysis and Comparison of IS 1893(Part-1) 2002 and 2016 of (G+4) Regular and Irregular Building International Journal of Innovative Research in Science, Engineering and Technology Vol. 7, Issue 6, June 2018 13. N.Veerababu, B Anil Kumar, Design of Earthquake Resistant Building Using Response Spectra,International Journal of Mechanical Engineering and Computer, Vol 4, No. 1, 2016. 14. K VenuManikanta, Dr. DumpaVenkateswarlu,Comparative Study On Design Results Of A Multi- Storied Building Using Staad Pro And ETABS For Regular And Irregular Plan Configuration, Volume 2, Issue 15, PP: 204 - 215, September’ 2016. 15. Sanjay Kumar Sadh, Dr. Umesh Pendharkar, Effect of Aspect Ratio & Plan Configurations on Seismic Performance of Multistoreyed Regular R.C.C. Buildings: An Evaluation by Static Analysis, International Journal of Emerging Technology and Advanced Engineering, Volume 6, Issue 1, January 2016. 16. Pardeshisameer, Prof. N. G. Gore, Study of seismic analysis and design of multi storey

symmetrical and asymmetrical building, International Research Journal of Engineering and Technology (IRJET), Volume:03 Issue: 01, Jan-2016. 17. S.Mahesh, B.PandurangaRao, Comparison of analysis and design of regular and irregular configuration of multi-Storey building in various seismic zones and various types of soils using ETABS and STAAD IOSR Journal of Mechanical and Civil Engineering (IOSRJMCE), Volume 11, Issue 6 Ver. I (Nov- Dec. 2014), PP 45-52. 18. Gauri G. Kakpure, Ashok R. Mundhada, Comparative Study of Static and Dynamic Seismic Analysis of Multistoried RCC Building by ETAB: A Review, International Journal of Emerging Research in Management &Technology, Volume-5, Issue-12, 2016. 19. Prashanth.P, Anshuman.S, Pandey.R.K, Arpan Herbert, and Comparison of design results of a Structure designed using STAAD and ETABS Software, International Journal of Civil and Structural Engineering Volume 2, No 3, 2012. 20. Sudhir K Jain (2003) “Review of Indian seismic code, IS 1893 (Part 1): 2002” The Indian Concrete Journal , November 2003. 21. Naveen. G.M, Chaya. S( November 2016 ) [20]: “STUDY ON REGULAR AND IRREGULAR BUILDING STRUCTURES DURING AN EARTHQUAKE” International Journal of Latest Engineering Research and Applications (IJLERA) ISSN: 2455-7137 Volume – 01, Issue – 08, November – 2016 22. Balaji.U and Selvarasan M.E “Design And Analysis of Multi Storied Building Under Static And Dynamic Loading Condition Using ETABS.” International Journal of Technical Research and Applications Volume 4, Issue 4. (July-Aug, 2016. 23.https://www.civilsimplified.com/resources/what-are-shear-walls 24. Structural Analysis and Design of Commercial Building for Earthquake Resistance. 25. Akshay R. Kohli, Prof. N. G. Gore ”Analysis and Design of an Earthquake Resistant Structure using STADD”. Pro International Research Journal of Engineering and Technology (IRJET)Volume: 04 Issue: 12 | Dec-2017