Page 1: STRONGER THAN STEEL · 2017-10-30 · ASTM E-814 Standard Method of Fire Tests of Fire Stop Systems ULC S115-M95 Standard Method of Fire Tests of Fire Stop Systems ASTM E-119 Evaluation

BlazeFrame®

I N T E G R AT E D F I R E S T O P S Y S T E M S

S T R O N G E R

T H A N S T E E LSM

.

clarkdietrich.com/BlazeFrame

Page 2: STRONGER THAN STEEL · 2017-10-30 · ASTM E-814 Standard Method of Fire Tests of Fire Stop Systems ULC S115-M95 Standard Method of Fire Tests of Fire Stop Systems ASTM E-119 Evaluation

The technical content of this literature is efective 5/12/16 and supersedes all previous information.Pub. No. CD-BlazeFrame 5/16 clarkdietrich.com

What is BlazeFrame? BlazeFrame products are innovative steel framing proile/intumescent composites, that combine ease of installation, inspection, life safety and joint protection dependability into one unique product.

How does it work? Using a cured factory metered dosage intumescent material, BlazeFrame proiles provide ire stopping, smoke and sound dampening that is efective immediately after framing components are installed. When exposed to heat above 375° F, the intumescent material expands up to 35 times its size. This provides additional protection from heat and lame passage during a ire event.

What does it replace? BlazeFrame's factory metered dosage intumescent material eliminates elastomeric ire prooing caulks and spray. The cured intumescent tape eliminates VOC's and of gases associated with caulked spray ire prooing. With the intumescent tape factory applied it eliminates both overage and underage often associated with the messy caulks and sprays.

BlazeFrame Advantages:

• Installed & inspected as " joint framing" (before obstructions)

• Unafected by dirty, oily, wet or freezing conditions

• Cured intumescent efective immediately (no VOC)

• No fatigue to joint or substrate materials for life of assembly

BlazeFrame Design Advantages

One to three hour assembly

BLAZEFRAME FIRE STOP

DEEP LEG DEFLECTION

TRACK (DL2, DSL2)

STEEL STUD

1, 2, 3, LAYERS

FOR 1, 2, 3 HR RATING

5/8” TYPE X

GYPSUM WALLBOARD

CONCRETE DECK

2

Page 3: STRONGER THAN STEEL · 2017-10-30 · ASTM E-814 Standard Method of Fire Tests of Fire Stop Systems ULC S115-M95 Standard Method of Fire Tests of Fire Stop Systems ASTM E-119 Evaluation

The technical content of this literature is efective 5/12/16 and supersedes all previous information. Pub. No. CD-BlazeFrame 5/16clarkdietrich.com

Fire Stopping

• UL 2079 Classiied and listed for up to 3 hr assemblies

• Protection for up to 3" overall movement capability (1-1/2" up and 1-1/2" down)

• Eliminates ire prooing caulks and sprays

• Shaftwall Assemblies certiied for use with all UL listed "liner" boards and inish side gypsum products

Sound Dampening

• NVLAP certiied to provide up to STC 62 (based on wall assembly)

• Open unencumbered joints (no caulk required)

• Fluted deck exposed with only BlazeFrame Deck Plug or Flute Cover STC = 50+

Smoke barrier-air leakage - IBC 2009 BlazeFrame assemblies have been UL Classiied

with the lowest possible L-Rating (less than 1 CFM/lft).

Seismic Requirements BlazeFrame is UL 2079 Classiied for Class III Cycling of 500 cycles at 30 cycles per minute of vertical movement which may be capable of meeting seismic design and building code requirements.

Code Compliance BlazeFrame joint protection complies with up to date building codes and is listed by Underwriters Laboratories Inc.

UL 2079 Tests for Fire Resistance of Building Joint SystemsASTM E-1966 Standard Test Method for Fire Resistive Joint SystemsASTM E-814 Standard Method of Fire Tests of Fire Stop SystemsULC S115-M95 Standard Method of Fire Tests of Fire Stop SystemsASTM E-119 Evaluation of a Non-Load Bearing Wall Assembly with FAS-093X Control JointASTM E-2837 Rated Wall Assemblies Installed to Non-Rated Assemblies (pending)

Expanded intumescent strip after ire test

BlazeFrame delection track & deck plugs in sound test

3

Page 4: STRONGER THAN STEEL · 2017-10-30 · ASTM E-814 Standard Method of Fire Tests of Fire Stop Systems ULC S115-M95 Standard Method of Fire Tests of Fire Stop Systems ASTM E-119 Evaluation

C O N C R E T E D E C K C O N D I T I O N

M E T A L D E C K C O N D I T I O N

The technical content of this literature is efective 5/12/16 and supersedes all previous information.Pub. No. CD-BlazeFrame 5/16 clarkdietrich.com

• Head of Wall assembly complete before studs are installed.

• Mineral wool only needed for lute ill.

• Earlier, easier, and accurate inspection.

• Clean transition from wall sheathing to substrate.

• Exposed and inished joints are ire and sound rated.

BLAZEFRAME FIRE STOP

DEEP LEG DEFLECTION

TRACK (DL2, DSL2)

STEEL STUD

1, 2, 3, LAYERS

FOR 1, 2, 3 HR RATING

5/8” TYPE X

GYPSUM WALLBOARD

CONCRETE DECK

MINERAL WOOL

FLUTE FILL

BLAZEFRAME FIRE

STOP DEEP LEG

DEFLECTION TRACK

(DL2, DSL2)

1, 2, 3, LAYERS

FOR 1, 2, 3, HR

RATING

ATTACH GYPSUM PER UL

DESIGN REQUIREMENT

STEEL STUD

BlazeFrame Design Advantages

4

Page 5: STRONGER THAN STEEL · 2017-10-30 · ASTM E-814 Standard Method of Fire Tests of Fire Stop Systems ULC S115-M95 Standard Method of Fire Tests of Fire Stop Systems ASTM E-119 Evaluation

B E A M P E N E T R A T I O N C O N D I T I O N

P A R A L L E L O F F S E T C O N D I T I O N

The technical content of this literature is efective 5/12/16 and supersedes all previous information. Pub. No. CD-BlazeFrame 5/16clarkdietrich.com

• Eliminates contour cutting of wall sheathing, caulks/sprays.

• Spray ire prooing or mineral wool are the easy option for beam cavity ill.

METAL PAN DECK

BLAZEFRAME FIRE STOP

DEEP LEG DEFLECTION

TRACK (DL2)

STEEL STUD

ANGLE OR Z-CLIPCENTERED

5/8” TYPE XGYPSUM WALLBOARD

FIRE PROOFINGor MINERAL WOOL

5/8” TYPE XGYPSUM WALLBOARD

BLAZEFRAME OFFSET DEEP

LEG DEFLECTION TRACK (ODL2, ODSL2)

14GA STRAP / ANGLEOUTRIGGER

STEEL STUD

• Eliminates z-clips, lath basket, voids in ire prooing.

• 14 ga angle outrigger/proile preassembled prior to installation.

5

Page 6: STRONGER THAN STEEL · 2017-10-30 · ASTM E-814 Standard Method of Fire Tests of Fire Stop Systems ULC S115-M95 Standard Method of Fire Tests of Fire Stop Systems ASTM E-119 Evaluation

BlazeFrame Sample Profiles

The technical content of this literature is efective 5/12/16 and supersedes all previous information.Pub. No. CD-BlazeFrame 5/16 clarkdietrich.com

* 4" leg length is not available for 2-1/2" wide system

DSL 2 (DEEP LEG - SLOT TED BOTH SIDES)

SL 1 (DEEP LEG - SLOT TED ONE SIDE)

Proile with two slotted legs w/ ire stop on both sides

Composite Fire Stop/Framing for use in ire rated wall assemblies. Provides 100% unencumbered joint protection. Accommodates up to 1 1/2" overall movement with UL 2079 Level III Certiication. Minimum CP60 coating. Legs with slots spaced 1" o.c. for positive attachment of studs per listed assemblies in UL Fire Resistance Directory.

Widths: 2-1/2", 3-5/8", 4", 6" and 8" Thicknesses: 33mils (20ga), 43mils (18ga) and 54mils (16ga) DSLE 30mils

Proile Leg Length (L)

Tape Width (I)

Slot Height (S)

Joint Protection

DSLE 2 2.50" 0.75" 1.50" 0.50"

DSL 2 3.00" 1.00" 1.50" 0.75"

DSLW 2 3.00" 1.25" 1.50" 1.00"

DSLX 2 4.00" * 1.75" 2.00" 1.50"

Proile with one slotted leg and one solid leg w/ ire stop on slotted side

Composite Fire Stop/Framing for use in ire rated wall assemblies. Provides 100% unencumbered joint protection. Accommodates up to 1 1/2" overall movement with UL 2079 Level III Certiication. Minimum CP60 coating. One leg with slots spaced 1" o.c. for positive attachment of studs per listed assemblies in UL Fire Resistance Directory.

Widths: 2-1/2", 3-5/8", 4", 6" and 8" Thicknesses: 33mils (20ga), 43mils (18ga) and 54mils (16ga)

Proile Slotted Leg Length (L1)

Solid Leg Length (L2)

Tape Width (I)

Slot Height (S)

Joint Protection

SL 1 3.00" 2.00" 1.00" 1.50" 0.75"

SLW 1 3.00" 2.00" 1.25" 1.50" 1.00"

SLX 1 4.00" * 2.50" 1.75" 2.00" 1.50"

(L)

Width

(L)

(S)

(I)

(L)

.22”1.00”

Fastener mid-height of exposed slot

(L2)

Width

(L1)(I)

(I)

* 4" leg length is not available for 2-1/2” wide system

6

Page 7: STRONGER THAN STEEL · 2017-10-30 · ASTM E-814 Standard Method of Fire Tests of Fire Stop Systems ULC S115-M95 Standard Method of Fire Tests of Fire Stop Systems ASTM E-119 Evaluation

The technical content of this literature is efective 5/12/16 and supersedes all previous information. Pub. No. CD-BlazeFrame 5/16clarkdietrich.com

(DL 1 Series)

(DL 2 Series)

* 4" leg length is not available for 2-1/2" wide system

* Additional sizes available.

DL (DEEP LEG - SOLID)

JR (J-RUNNER)

Composite Fire Stop/Framing for use in ire rated wall assemblies. Provides 100% unencumbered joint protection. Accommodates up to 3" overall movement with UL 2079 Level III Certiication. Minimum CP60 coating. Two solid legs supporting "free loating" studs per listed assemblies in UL Fire Resistance Directory.

Widths: 2-1/2", 3-5/8", 4", 6" and 8" Thicknesses: 33mils (20ga), 43mils (18ga) and 54mils (16ga) DLE 30mils

(DL 1 Series) Proile with two solid legs w/ ire stop on one side (DL 2 Series) Proile with two solid legs w/ ire stop on both sides

Proile Leg Length (L)

Tape Width (I)

Joint Protection

DLE 2.00" 0.75" 0.50"

DL 2.00" 1.00" 0.75"

DLW 2.00" 1.25" 1.00"

DLX 2.50" 1.75" 1.50"

DLZ 3.00" 2.25" 2.00"

DLY 4.00" * 3.25" 3.00"

Proile with two solid legs w/ ire stop on one side

Composite Fire Stop/Framing for use in up to 3 hr ire rated shaft wall assemblies. Provides 100% unencumbered joint protection. Accommodates up to 1 1/2" overall movement with UL 2079 Level III Certiication. Minimum CP60 coating. One leg (front) having intumescent per listed assemblies in UL Fire Resistance Directory.

Widths: 2-1/2", 4" and 6" Thicknesses: 33mils (20ga), 43mils (18ga) and 54mils (16ga)

Proile Front Leg Length (FL)

Back Leg Length (BL)

Tape Width (I)

Joint Protection

JR 1 2.00" 3.00" 1.00" 0.75"

JRW 1 2.00" 3.00" 1.25" 1.00"

JRX 1 2.00" 3.00" 1.75" 1.50"

(L) (L)

(I)(I)

(BL)(FL)

(I)

Width

Width

7

Page 8: STRONGER THAN STEEL · 2017-10-30 · ASTM E-814 Standard Method of Fire Tests of Fire Stop Systems ULC S115-M95 Standard Method of Fire Tests of Fire Stop Systems ASTM E-119 Evaluation

BlazeFrame Sample Profiles

The technical content of this literature is efective 5/12/16 and supersedes all previous information.Pub. No. CD-BlazeFrame 5/16 clarkdietrich.com

ODL 2 (OFFSET DEEP LEG)

ODSL 2 (OFFSET DEEP SLOT TED LEG)

Proile with two solid legs w/ ire stop on both sides

Composite Fire Stop/Framing with "ofset step" accommodates various depths of ireprooing in head of wall and wall to wall (column) assemblies. (Other ofset depths available to accommodate other sprayed thicknesses). Provides 100% unencumbered joint protection. Accommodates up to 2" overall movement with UL 2079 Level III Certiication. Minimum CP60 coating. Two solid legs per listed assemblies in UL Fire Resistance Directory.

Widths: 3-5/8", 4", 6" and 8" Thicknesses: 33mils (20ga), 43mils (18ga) and 54mils (16ga) "D" Dimension: Varies with depth of ire stop material required.

Proile Lower Leg Length (L)

Tape Width (I)

Joint Protection

ODL 2 2.00" 1.00" 0.75"

ODLW 2 2.00" 1.25" 1.00"

ODLX 2 2.50" 1.75" 1.50"

ODLZ 2 3.00" 2.25" 2.00"

Proile with two slotted lower legs w/ ire stop on both sides

Composite Fire Stop/Framing with "ofset step" accommodates various depths of ireprooing in head of wall and wall to wall (column) assemblies. (Other ofset depths available to accommodate other sprayed thicknesses). Provides 100% unencumbered joint protection. Accommodates up to 1-1/2" overall movement with UL 2079 Level III Certiication. Minimum CP60 coating. Two legs with slots spaced 1" o.c. for positive attachment of studs per listed assemblies in UL Fire Resistance Directory.

Widths: 3-5/8", 4", 6" and 8" Thicknesses: 33mils (20ga), 43mils (18ga) and 54mils (16ga) "D" Dimension: Varies with depth of ire stop material required.

Proile Lower Leg Length (L)

Tape Width (I)

Slot Height (S)

Joint Protection

ODSL 2 3.00" 1.00" 1.50" 0.75"

ODSLW 2 3.00" 1.25" 1.50" 1.00"

ODSLX 2 4.00" 1.75" 2.00" 1.50"

Width

(L)

0.75”0.75”

D

Width

(L)

0.75” 0.75”

D

(I)

(I)

8

Page 9: STRONGER THAN STEEL · 2017-10-30 · ASTM E-814 Standard Method of Fire Tests of Fire Stop Systems ULC S115-M95 Standard Method of Fire Tests of Fire Stop Systems ASTM E-119 Evaluation

The technical content of this literature is efective 5/12/16 and supersedes all previous information. Pub. No. CD-BlazeFrame 5/16clarkdietrich.com

FAS-093X FIRE RATED CONTROL JOINT

Proile for protection of control joints A composite control joint with intumescent tape factory applied to the back side of the control joint. The FAS-093X has been tested according to UL-2079 “Test For Fire Resistance of Building Joint Systems” and is used to relieve stresses of expansion and contraction of drywall interior partitions or ceilings running in a horizontal or vertical direction. The opening is protected by an orange plastic tape to indicate the ire rating this tape is removed after joint compound has been applied and the inish is completed. The section is fabricated from hot-dipped galvanized steel complying with ASTM A653, and ASTM A1003. Width: 2" Length: 10'-0" Thicknesses: 13mils Packaging: 20 Pcs./Ctn. - 24 Ctn. per pallet

FC (FLUTE COVER)

Proile strap for under luted decks Corrugated strap for horizontal use to span luted areas of unprotected or protected metal decks in up to 2 hr rated assemblies. Proile attached to deck "valley" surfaces a max 16" o.c. on both sides. Proiles provide a surface area for attachment of head of wall partition track proiles centered or ofset underneath and parallel to deck luted areas per listed assemblies in UL Fire Resistance Directory.

Sizes: 675 (6-3/4") or 700 (7") Length: 10'-0" Thicknesses: 33mils (20ga)

1.50” 1.50”0.875” 0.875”

Width varies to match

lute opening0.5

63”

BLAZEFRAME COMPOSITE(DL2, DSL2)

(FC) FLUTE COVER(continuous)

5/8” TYPE XGYPSUM WALLBOARD STEEL STUD

FLUTED DECK

9

Page 10: STRONGER THAN STEEL · 2017-10-30 · ASTM E-814 Standard Method of Fire Tests of Fire Stop Systems ULC S115-M95 Standard Method of Fire Tests of Fire Stop Systems ASTM E-119 Evaluation

The technical content of this literature is efective 5/12/16 and supersedes all previous information.Pub. No. CD-BlazeFrame 5/16 clarkdietrich.com

BLAZEFRAME COMPOSITETRACK/FIRE STOP

(DL1, SL1)

5/8” TYPE XGYPSUM WALLBOARD

CONCRETE DECK

STEEL STUD

BLAZEFRAME FIRE STOP

DEEP LEG DEFLECTION

TRACK (DL2, DSL2)

STEEL STUD

1, 2, 3, LAYERS

FOR 1, 2, 3 HR RATING

5/8” TYPE X

GYPSUM WALLBOARD

CONCRETE DECK

Post Tension or Structural Concrete Overhead

PT-1

HW-D-0498

Chase Wall Post Tension or Structural Flat Concrete

PT-2

HW-D-0505

METAL PAN DECK

BLAZEFRAME FIRE STOP

DEEP LEG DEFLECTION

TRACK (DL2)

STEEL STUD

ANGLE OR Z-CLIPCENTERED

5/8” TYPE XGYPSUM WALLBOARD

FIRE PROOFINGor MINERAL WOOL

MINERAL WOOL

FLUTE FILL

BLAZEFRAME FIRE

STOP DEEP LEG

DEFLECTION TRACK

(DL2, DSL2)

1, 2, 3, LAYERS

FOR 1, 2, 3, HR

RATING

ATTACH GYPSUM PER UL

DESIGN REQUIREMENT

STEEL STUD

Perpendicular Unprotected Deck (UD) – Mineral Wool Fill

UD-1

HW-D-0513

Head of Wall Beam Penetration

SS-1

HW-D-0495

BlazeFrame Sample Details

10

Page 11: STRONGER THAN STEEL · 2017-10-30 · ASTM E-814 Standard Method of Fire Tests of Fire Stop Systems ULC S115-M95 Standard Method of Fire Tests of Fire Stop Systems ASTM E-119 Evaluation

The technical content of this literature is efective 5/12/16 and supersedes all previous information. Pub. No. CD-BlazeFrame 5/16clarkdietrich.com

BLAZEFRAME COMPOSITE(DL2, DSL2)

(FC) FLUTE COVER(continuous)

5/8” TYPE XGYPSUM WALLBOARD STEEL STUD

FLUTED DECK

BLAZEFRAME COMPOSITETRACK/FIRE STOP

(DL2, DSL2)

FIRE PROOFING

5/8” TYPE XGYPSUM WALLBOARD

MINERAL WOOL

STEEL STUD

Centered Under Flute Unprotected Deck (UD) – Flute Cover

UD-6

HW-D-0544

Perpendicular Protected Deck (PD) – Mineral Wool Flute Fill

PD-12

HW-D-0513

Parallel Under Structural Support (Z-Clips)

SS-16

HW-D-0502

Wall to Wall Gypsum to Protected Steel (I-Beam)

VM-3

Design Based on

WW-S-0055

HW-D-0558

BLAZEFRAME COMPOSITETRACK/FIRE STOP

(DL2, DSL2)

5/8” TYPE XGYPSUM WALLBOARD

Z-CLIPS

STEEL STUD

STEEL COLUMN

BLAZEFRAME “OL” PROFILE(ODL2)

5/8” TYPE XGYPSUM WALLBOARD

FIRE PROOF COATING

11

Page 12: STRONGER THAN STEEL · 2017-10-30 · ASTM E-814 Standard Method of Fire Tests of Fire Stop Systems ULC S115-M95 Standard Method of Fire Tests of Fire Stop Systems ASTM E-119 Evaluation

The technical content of this literature is efective 5/12/16 and supersedes all previous information.Pub. No. CD-BlazeFrame 5/16 clarkdietrich.com

CONCRETE COLUMN / WALL

5/8” TYPE XGYPSUM WALLBOARD

STEEL STUD

BLAZEFRAME COMPOSITE TRACK / FIRESTOP

(DL2)

Wall to Wall Gypsum to Concrete Column/Wall

VM-1

WW-S-0055

5/8” TYPE XGYPSUM WALLBOARD

BLAZEFRAME COMPOSITETRACK / FIRE STOP

“OL” - SERIES(ODL2, ODSL2)

STEEL STUD 5/8” TYPE XGYPSUM WALLBOARD

BLAZEFRAME OFFSET DEEP

LEG DEFLECTION TRACK (ODL2, ODSL2)

14GA STRAP / ANGLEOUTRIGGER

STEEL STUD

5/8” TYPE X

GYPSUM WALLBOARD

093 CONTROL JOINT

(optional)

SHAFT LINER BOARD

BLAZEFRAME COMPOSITE

TRACK / FIRE STOP

(JR1)

CH, CT, OR I STUD

Parallel Under Structural Support (Ofset Leg Proile)

SS-2

HW-D-0502

Edge of Structural Support with Angle (Ofset Leg Proile)

SS-28

HW-D-0631

Hollow Steel Shape - Non RatedSS-21

Design Based on

HW-D-0543

HW-D-0559

BlazeFrame Sample Details

12

Page 13: STRONGER THAN STEEL · 2017-10-30 · ASTM E-814 Standard Method of Fire Tests of Fire Stop Systems ULC S115-M95 Standard Method of Fire Tests of Fire Stop Systems ASTM E-119 Evaluation

The technical content of this literature is efective 5/12/16 and supersedes all previous information. Pub. No. CD-BlazeFrame 5/16clarkdietrich.com

Under UL G500 Series DesignVM-6

HW-D-0503

BLAZEFRAME COMPOSITE

TRACK / FIRE STOP

(DL2, DSL2)

5/8” TYPE X

GYPSUM WALLBOARD

FURRING CHANNEL

STEEL STUD

5/8” TYPE X

GYPSUM WALLBOARD

Bottom of WallVM-12

BW-S-0021

5/8” TYPE X

GYPSUM WALLBOARD

BLAZEFRAME COMPOSITE

TRACK / FIRE STOP

(DL2) CONCRETE FLOOR

STEEL STUD

Flat Strap PatchVertical Cavity Obstructions

ECA - End Cap AngleExterior Corner Application

FIELD MODIFIED - VERTICAL OBSTRUCTION

TOP VIEW SIDE VIEW

FASTEN FSP TO OUTERSURFACE OF TRACK LEG

FSP (Flatstrap Patch)

TOP VIEW TOP VIEWINSERT ECA

SIDE VIEW INSERT ECA

ECA ATTACHED WITH FASTENER

INTERSECTING WALL BLAZEFRAME “BUTTED”

13

Page 14: STRONGER THAN STEEL · 2017-10-30 · ASTM E-814 Standard Method of Fire Tests of Fire Stop Systems ULC S115-M95 Standard Method of Fire Tests of Fire Stop Systems ASTM E-119 Evaluation

The technical content of this literature is efective 5/12/16 and supersedes all previous information.Pub. No. CD-BlazeFrame 5/16 clarkdietrich.com

CONCRETE DECK

BLAZEFRAME COMPOSITE

TRACK / FIRE STOP

(JR1)

3 LAYERS FOR

3 HOUR RATING

CH, CT, OR I STUD

LINER BOARD

MINERAL WOOL

5/8” TYPE X

GYPSUM WALLBOARD

BLAZEFRAMECOMPOSITE

TRACK / FIRE STOP(JR1)

FASTENER AT BOTTOMOF OBSTRUCTION

(when exists)CT, CH, OR I STUD

LINER BOARD

MINERAL WOOL

MINERAL WOOL orFIRE PROOFING

5/8” TYPE XGYPSUM WALLBOARD

5/8” TYPE X

GYPSUM WALLBOARD

FAS-093X

CONTROL JOINT

STEEL STUDS

5/8” TYPE X

GYPSUM WALLBOARD

FAS-093X

CONTROL JOINT

STEEL STUDS

Shaft Wall Post Tension or Structural Concrete

PT-3

HW-D-0496

FAS-093X Control Joint one layer each side (1-hour)

UL-2079

Shaft Wall Perpendicular to Unprotected Deck

UD-10

HW-D-0504

FAS-093X Control Joint two layers each side (2-hour)

UL-2079

BlazeFrame Sample Details

14

Page 15: STRONGER THAN STEEL · 2017-10-30 · ASTM E-814 Standard Method of Fire Tests of Fire Stop Systems ULC S115-M95 Standard Method of Fire Tests of Fire Stop Systems ASTM E-119 Evaluation

The technical content of this literature is efective 5/12/16 and supersedes all previous information. Pub. No. CD-BlazeFrame 5/16clarkdietrich.com

UL Approvals

UL Control - R25833 (US)- 1, 2 and 3 hr designs - UL 2079 standard compliant

UL Listings

HW-D-0495 Protected Beam Penetration HW-D-0496 Under Flat Concrete (shaft wall) HW-D-0497 Parallel to Protected Beam (shaft wall) HW-D-0498 Under PT or Structural Concrete HW-D-0499 Parallel to Unprotected Fluted Metal Deck HW-D-0500 Perpendicular Unprotected Fluted Metal Deck HW-D-0501 Parallel to Beam (standard wall) HW-D-0502 Parallel & Edge Overlap Under Structural Support HW-D-0503 Under Layer "Type C" UL 500 Series Designs HW-D-0504 Under Unprotected Fluted Metal Deck (shaft wall) HW-D-0505 Under PT or Structural Concrete (chase wall) HW-D-0506 Under Fluted Metal Deck (chase wall) HW-D-0512 Perpendicular Protected Deck w/Fire Prooing Flute Fill HW-D-0513 Perpendicular Unprotected Deck w/Mineral Wool only Flute Fill HW-D-0543 Stair Shaft (093 Control Joint Optional) HW-D-0544 Parallel under Flute (Flute Cover Plate) HW-D-0558 Ofset Leg Standard Wall Protected Roof Deck/Substrate HW-D-0559 Ofset Leg Shaft Wall Protected Roof Deck/Substrate HW-D-0597 Parallel to Beam (Z-clip & Drywall Rip) HW-D-0631 Shaft Wall Parallel & Edge Overlap Under Structural Support HW-D-0632 PT or Structural Concrete Bare Slotted with Caulks HW-D-0633 Fluted Metal Deck Bare Slotted with Flute Plate/Caulks WW-S-0055 Vertical Wall to Wall Joint BW-S-0021 Bottom of Wall

Details shown are a limited sample of assemblies based on UL certified and listed assemblies. Additional assembly details, submittal sheets, and constructability designs are periodically added upon design and approval. Information can be viewed, downloaded, and printed from www.clarkdietrich.com/BlazeFrame.

Project Information

Name:

Address:

City/ST/ZIP:

Contractor Information

Name:

Contact:

Phone:

Fax:

Architect Information

Name:

Contact:

Phone:

Fax:

- ClarkDietrich products are manufactured from cold-formed steel. Steel is 100% recyclable, which helps divert debris from the waste

stream. The contribution to LEED must be calculated by the contractor based on weight or volume.

- ClarkDietrich’s steel products have a minimum of 25.5% post-consumer recycled content, and 6.8% pre-consumer. If you wish to

report a higher number for your project or seek Credit MR 5 please contact Technical Services at 888-437-3244 or visit www.clarkdietrich.com.

® (CJB)

“CJB” (Control Joint Backer)

Composite Fire Stop/Control Joint Backer for use to protect Architectural

design joints (optional control joint over gap) for up to 2 hr rated assemblies.

between opposing drywall edge at control joint locations. Also eliminates the

need for a second stud in the gypsum assembly.

Material:

Yield Strength: Grade 33ksi

Coating:

G40

18mils: 25 Gauge, 0.0188” Design Thickness, 0.0179“ Min. Thickness

Dimensions:

Width:

3-1/4”

Length:

10’-0”

Packaging:

14 Pieces/Carton

Intumescent

Width

Width

Gap

Width

Flange

Width

CJB-181.25”

3.25”

.75”

1.25”

ASTM A1003, C955

WFCI 12033

is available @ www.clarkdietrich.com

CD-BlazeFrame-CJB © 08/12 ClarkDietrich Building Systems

Wallboard

Eliminates the need

for a second stud in

the gypsum assembly

Steel Stud

093 Control Joint

CJB - Control Joint Backer

Product Submittal Sheet

Technical Services: 888-437-3244

Engineering Services: 877-832-3206

Sales: 800-543-7140

clarkdietrich.com

FAS-093X Fire Rated Control Joint

A

Product Data & Ordering Information:

ASTM & Code Standards:

� � �

� No Drywall Rips Required

� No Sealant Required

� No Mineral Wool Required

� UL Listed Joint System

� US Patent 8,671,632

Fir

e R

ate

d C

on

tro

l Jo

int

2.00”

.478”.693”

8

1 Hour Fire Rating

2 Hour Fire Rating

09.22.16 (Non-Structural Metal Framing)

Project Information

Name:

Address:

City/ST/ZIP:

Contractor Information

Name:

Contact:

Phone:

Fax:

Architect Information

Name:

Contact:

Phone:

Fax:

- ClarkDietrich products are manufactured from cold-formed steel. Steel is 100% recyclable, which helps divert debris from the waste

stream. The contribution to LEED must be calculated by the contractor based on weight or volume.

- ClarkDietrich’s steel products have a minimum of 25.5% post-consumer recycled content, and 6.8% pre-consumer. If you wish to

report a higher number for your project or seek Credit MR 5 please contact Technical Services at 888-437-3244 or visit www.clarkdietrich.com.

Material:

Yield Strength: Grade 33ksi for 33mils & 43mils, 50ksi for 54mils

Coating: CP60 (G90 available)

33mils: 20 Gauge, 0.0346” Design Thickness, 0.0329“ Min. Thickness

43mils: 18 Gauge, 0.0451” Design Thickness, 0.0428“ Min. Thickness

54mils: 16 Gauge, 0.0566” Design Thickness, 0.0538“ Min. Thickness

Dimensions:

Inside width: Equal to the outside width of the stud

Widths (W): 3-5/8”, 4”, 6” and 8”

Track length: 10’-0”

Lower Leg

Length (L)

Tape

Width (I)

Slot

Height (S)

Joint

Protection

ODSL 2 3.00” 1.00” 1.50” 0.75”

ODSLW 2 3.00” 1.25” 1.50” 1.00”

ODSLX 2 4.00” * 1.75” 2.00” 1.50”

ASTM A1003, C955

UL2079, E814, E1966, E119

is available @ www.clarkdietrich.com

CD-BlazeFrame-ODSL2 © 08/12 ClarkDietrich Building Systems

Width (W)

(L)0.75” 0.75”

(1-1/4”) **

®

“ODSL 2” (Offset Slotted Leg)

Two offset slotted lower legs

Composite F

up to 1-1/2” thick in head of wall and wall to wall (column) assemblies. Pro-

vides 100% unencumbered joint protection. Accommodates up to 3” overall

legs with slots spaced 1”o.c. for positive attachment of studs per listed

assemblies in UL Fire Resistance Directory.

provides air, smoke and sound seals. When exposed to heat above 325

degrees Fahrenheit, the intumescent material expands up to 35 times its size.

* 4” leg length is not available for 2-1/2” wide system** Other offset step depths available

(I)

Product Submittal Sheet

Technical Services: 888-437-3244

Engineering Services: 877-832-3206

Sales: 800-543-7140

clarkdietrich.com

Project InformationName: Address: City/ST/ZIP: Contractor Information

Name: Contact: Phone: Fax:

Architect InformationName: Contact: Phone: Fax:

- ClarkDietrich products are manufactured from cold-formed steel. Steel is 100% recyclable, which helps divert debris from the waste

stream. The contribution to LEED must be calculated by the contractor based on weight or volume.

- ClarkDietrich’s steel products have a minimum of 25.5% post-consumer recycled content, and 6.8% pre-consumer. If you wish to

report a higher number for your project or seek Credit MR 5 please contact Technical Services at 888-437-3244 or visit www.clarkdietrich.com.

®

Composite Fire Stop/Framing for

100% unencumbered joint protection. Accommodates up to 1 1/2” overall

with slots spaced 1”o.c. for positive attachment of studs per listed assemblies

in UL Fire Resistance Directory.

provides air, smoke and sound seals. When exposed to heat above 325

degrees Fahrenheit, the intumescent material expands up to 35 times its size.

Material: Yield Strength: Grade 33ksi for 33mils & 43mils

Grade 50ksi for 54mils

Coating:

CP60 (G90 available)

33mils: 20 Gauge, 0.0346” Design Thickness, 0.0329“ Min. Thickness

43mils: 18 Gauge, 0.0451” Design Thickness, 0.0428“ Min. Thickness

54mils: 16 Gauge, 0.0566” Design Thickness, 0.0538“ Min. Thickness

Dimensions: Inside width: Equal to the outside width of the stud

Widths (W):

2-1/2”, 3-5/8”, 4”, 6” and 8”

Vertical slots: 0.22” wide & spaced every 1”o.c.

Track length: 10’-0”

Leg Length (L)

Tape Width (I) Slot

Height (S) Joint Protection

DSL 23.00”

1.00”1.50”

0.75”

DSLW 23.00”

1.25”1.50”

1.00”

DSLX 24.00” *

1.75”2.00”

1.50”

ASTM A1003, C955UL2079, E814, E1966, E119

is available @ www.clarkdietrich.com

CD-BlazeFrame-DSL2 © 08/12 ClarkDietrich Building Systems

(L)

(W)

(L)

(S)

(I)

(L)

.22”

1.00”

Fastener mid-height of exposed slot

* 4” leg length is not available for 2-1/2” wide system

Product Submittal Sheet

Technical Services: 888-437-3244

Engineering Services: 877-832-3206 Sales: 800-543-7140clarkdietrich.com

NEED TO SEND PRODUCT SUBMIT TALS?

Build BlazeFrame Product Submittals for your next project. Use ClarkDietrich's SubmittalPro® Product Submittal System to create and send a PDF package of BlazeFrame's product information and technical submittals based on your project's layout conditions.

Launch SubmittalPro® from clarkdietrich.com

Code Approvals

15

Page 16: STRONGER THAN STEEL · 2017-10-30 · ASTM E-814 Standard Method of Fire Tests of Fire Stop Systems ULC S115-M95 Standard Method of Fire Tests of Fire Stop Systems ASTM E-119 Evaluation

CD-BlazeFrame 5/16 © ClarkDietrich Building Systems. The technical content of this literature is effective 5/12/16 and supersedes all previous information.