Page 1: Starbreaker Consumer Units & Devices - Electrium · CONSUMER UNITS FOR USE IN DOMESTIC HOUSEHOLD PREMISES REGULATIONS 2 CONSUMER UNIT OVERVIEW 4 STARBREAKER CONSUMER UNITS 5 STARBREAKER

StarbreakerConsumer Units

& Devices

Page 2: Starbreaker Consumer Units & Devices - Electrium · CONSUMER UNITS FOR USE IN DOMESTIC HOUSEHOLD PREMISES REGULATIONS 2 CONSUMER UNIT OVERVIEW 4 STARBREAKER CONSUMER UNITS 5 STARBREAKER

Acknowledged as one the leadingbrands in the UK and in BritishStandard markets around the world,Crabtree offers designers & specifiersa wide range of quality products thatcaters for a vast array of applicationsincluding Commerce, Offices,Education, Hospitals & Health, Hotels& Leisure facilities, in fact whereverquality products are required.

Crabtree factories operate a series of internationally recognized standards including ISO9001 for quality, OHSAS 18001 forHealth & Safety and ISO14001 for EnvironmentalManagement. The UK production locations are hometo the product management, engineering, design,quality & logistics teams.

In the UK Crabtree operates two UKAS accredited Laboratories that carry out R&D andcompliance testing on all Crabtree products, these highly accredited facilities ensure that safety,quality & reliability remain consistent with UK & EU legislation regulations & Siemens internalstandards, policies and practices.

Crabtree products are all designed manufactured and tested in accordance with the recognisedproduct standards, and backed by standard & extended guarantees.

Crabtree also operates to recognised standards for product safety & sustainability, Crabtreewiring accessories are RoHS and REACH compliant often in excess of the UK market standards.

Crabtrees WEEE compliance process and recycling scheme ensures that the end of product lifecircumstances are catered for in line with UK & EU Legislation.

Recycled materials are used in product packaging, and declared into a recyclingscheme locally to control environmental impacts and assure that the maximumlevel of recycling of materials and use of recycled materials is achieved.

As a Siemens company Crabtree also operates a zero harm scheme within all of itsmanufacturing, logistics & sales facilities, and is proud to have achieved a 5 starHealth & Safety rating.

Page 3: Starbreaker Consumer Units & Devices - Electrium · CONSUMER UNITS FOR USE IN DOMESTIC HOUSEHOLD PREMISES REGULATIONS 2 CONSUMER UNIT OVERVIEW 4 STARBREAKER CONSUMER UNITS 5 STARBREAKER

CONSUMER UNITS FOR USE IN DOMESTICHOUSEHOLD PREMISES

REGULATIONS 2CONSUMER UNIT OVERVIEW 4STARBREAKER CONSUMER UNITS 5STARBREAKER MCBs & RCBOs 10STARBREAKER AFDDs 10DIN DEVICES 11DIMENSIONS 12

Conten

ts

All Crabtree products comply with the applicable British Standard specification and should be installed by suitablyqualified personnel in accordance with the requirements of relevant legislation, regulations (including IET WiringRegulations) and the accepted practice in the industry.

The products listed or described in this publication may be protected by one or more patents, and/or registered designsand/or applications. A full list of patents registered designs and applications may be obtained from the companysecretary of Electrium Limited.

1. Cannock Commercial Headquarters Home to Sales & Marketing, Supply ChainManagement, Finance & Customer Service.

2. Wythenshawe Manufacturing location for domestic &commercial circuit protection, with R&D, UKAStest laboratory ISO9001 production facilities.

3. Hindley Green Production location for wiring accessories & domestic circuit protection with R&D, UKAS test laboratory ISO9001 production, warehouse, distribution & logistics facilities.

1

Page 4: Starbreaker Consumer Units & Devices - Electrium · CONSUMER UNITS FOR USE IN DOMESTIC HOUSEHOLD PREMISES REGULATIONS 2 CONSUMER UNIT OVERVIEW 4 STARBREAKER CONSUMER UNITS 5 STARBREAKER

This guide to Starbreaker consumer units is not intended as a substitute for the standards and regulations that should always be used for all types of electrical installation design & installation work.

THE WIRING REGULATIONS &DOMESTIC HOUSEHOLD PREMISES

NON COMBUSTIBLE CONSUMER UNIT ENCLOSURES

BS 7671 (IET Wiring Regulations) prescribe that within domestic householdpremises consumer units & similar switchgear assemblies must have theenclosures manufactured from noncombustible material e.g. steel, and comply withBS EN 61439-3. The term enclosure includes the box, cover, door, hinges, & fixingscrews, all of which must be noncombustible. It can also include the blanks thatare used in the cover where there are unused ways.

Similar switchgear includes domestic switch fuse units, small consumer units thatmay be used in detached garages & outbuildings, and other circuit protectionassemblies that are used in domestic household premises.

ADDITIONAL PROTECTION BY 30mA RCD

Several regulations call for additional protection by use of 30mA RCBO / RCDthese requirements apply to circuits & accessories in domestic applicationsincluding; all lighting circuits, all socket outlets up to & including 32A rating, anymobile equipment for use outdoors up to & including 32A rating, all circuitsburied an walls or partitions (at less than 50mm depth) and without earthedmechanical protection, all circuits serving a room with a fixed bath or shower, andall circuits passing through a room with a fixed bath or shower.

DIVISION OF THE INSTALLATION

Chapter 31 requires the installation to be divided into as many circuits asnecessary to avoid danger in the event of a fault. Take account of hazards that mayarise from the failure of a single circuit e.g. lighting circuit. Prevent unwantedtripping of RCDs due to PE (non-fault) leakage currents and to allow safe testing& maintenance.

UNWANTED TRIPPING OF RCDs

Chapter 53 provides guidance on ways to maintain power continuity & avoidunwanted tripping. Designers & installers can use an individual RCBO on eachcircuit, or ensure that any standing leakage current (from equipment- not fromfault conditions) is less than 30% of the RCD trip rating e.g. 30% of 30mA. This isin addition to the requirements of Chapter 31 above.

OVERVOLTAGE PROTECTION & SURGE PROTECTION DEVICES

Individual dwelling units will require surge protection devices where the value ofthe installation and all of the equipment connected to it justifies the investment inSPD protection see 443.4.

AFDDs ADDITIONAL PROTECTION AGAINST ELECTRICAL FIRES

Chapter 42 deals with protection against thermal effects and includes regulationsthat deal with devices that provide protection against the risk of electrical fires i.e.RCDs and AFDDs (arc fault detection devices) AFDDs are recommended for thespecific purpose of providing additional protection against fires caused by arcfaults in 230v AC final circuits.

AFDDs are combined with RCBO technology and should be installed at the originof each circuit that is being protected i.e. in the consumer unit. The combinedtechnology in AFDDs will provide overcurrent protection, short circuitprotection, earth leakage protection & additional protection against fires caused byarc faults.

METER TAILS FIXINGS & CABLE ENTRIES

Chapter 52 incudes requirements for cables (including meter tails) to be installedto avoid any undue strain on conductors and terminations. Where necessary thiswill mean clipping / fixing meter tails to make sure that stresses & strains are notplaced on the tails inadvertently. This is in addition to any other requirements forprotecting meter tails at the point of entry into metal consumer unit enclosures.

2

Page 5: Starbreaker Consumer Units & Devices - Electrium · CONSUMER UNITS FOR USE IN DOMESTIC HOUSEHOLD PREMISES REGULATIONS 2 CONSUMER UNIT OVERVIEW 4 STARBREAKER CONSUMER UNITS 5 STARBREAKER

INSTALLATIONS IN DOMESTIC HOUSEHOLD PREMISES

REGULATIONS RELATING TO: EXAMPLES ADDITIONAL PROTECTION Upstairs Sockets Downstairs Sockets Kitchen Sockets Cooker outlet with integral 13A socket Garage Sockets Plus any other sockets up to 32A rated Shower circuit Lighting circuit Heating circuit Ventilation circuit Plus other circuits Upstairs Lighting Downstairs Lighting Plus other lighting circuits Downstairs Lighting Upstairs Lighting Immersion heater Smoke Alarms (Safety service) Burglar Alarm Plus any other circuits

* Regulation 411.3.3 socket outlets with a rated current not exceeding 32A.

** Regulation 701.411.3.3 Additional protection shall be provided for all circuits serving the location and any circuits not serving but passing through zones 1 or 2 ofthe location by use of one or more 30mA RCD.

*** Regulations in the 522.6.200 series, cables concealed in a wall or partition at less than 50mm depth and without earthed mechanical protection e.g. conduit.

**** Regulation 314.1 Every installation shall be divided into circuits as necessary to avoid danger and inconvenience in the event of a fault, take account of danger thatmay arise from the failure of a single circuit such as a lighting circuit, reduce the possibility of unwanted tripping of RCDs etc.

**** Regulation 314.2 Separate circuits to be provided for parts of the installation that need to be separately controlled in such a way that those circuits are notaffected by the failure of other circuits.

***** Regulation 560.7.1 Chapter 56 circuits for safety services shall be independent of other circuits.

In addition Chapter 51 requires designers/ installers to take account of all relevant British Standards and manufacturers instructions. For example BS5839 Part 6 is theBritish Standard for fire detection and alarm systems in dwellings. It states that power supplies to Grade D smoke alarms should be an independent circuit at theconsumer unit, or a separately electrically protected local lighting circuit.

Regulation 416.2.2 requires that the installed consumer unit achieves IP4X (1mm probe) on the top elevation. All other elevations should be to IP2XC (2.5mm probe).

30mA RCDs

Taking into account3.14.1 ****3.14.2 ****

411.3.3*

701.411.3.3**

522.6.200 series***and

560.7.1*****

Sockets up to a 32A rating

411.3.4 Luminaire circuits

All circuits serving a roomcontaining a fixed bath or showeror circuits not serving but passingthrough zones 1 or 2 of a roomcontaining a fixed bath or shower.

All circuits buried in a wall orpartition at less than 50mm andwithout mechanical protection

1 The IET onsite guide also recommends that where metal consumer units are installed into TT systems protection from faults arising from the possibility of mains tails becoming loose and making contact with the metal enclosure by incorporating into the installation a 100mA time delayed (S type) RCCB.

2 Furthermore in all cases the mains tails should be protected at the point of entry into the metal enclosure by use of a mains tails gland to protect against the possibility of mechanical damage and or disturbance that could lead to tails becoming loose and making contact with the metal enclosure.

l Lighting circuits in domestic dwellings must be protected by30mA RCD

lAll socket outlets should be protected by 30mA RCD*l All circuits serving or passing through a room with a fixed bathor shower should be protected by one or more 30mA RCDs**

l All cables buried beneath the plaster surface of the wall orpartition (at less than 50mm) should be protected by 30mARCDs***

l All cables concealed in metal stud partitions (common in newbuilds) should be protected by 30mA RCDs***

l Installations should be divided up into circuits so as to takeaccount of danger and inconvenience caused by a single fault -e.g. such as a lighting circuit****

l Installations should be designed and arranged so as to preventunwanted tripping of RCDs****

l Safety services such as smoke alarms should be on independentcircuits*****

ALL INDEPENDENT CIRCUITSFull metal Main Switch unit with RCBOs

HALF INDEPENDENT CIRCUITSFull metal Split Load unit with RCBOs and MCBs

SOME INDEPENDENT CIRCUITSFull metal High Integrity unit with RCBOs and MCBs

TT SYSTEMAll independent circuits & 100mA

Time Delay RCD

NO INDEPENDENT CIRCUITSFull metal Dual RCD unit with MCBs

S

I

0

1

2

2

2

2

2

17th

EDITIO

N W

IRING REGULATIO

NS IN

CLUDING AMENDMENT No.3

3

Page 6: Starbreaker Consumer Units & Devices - Electrium · CONSUMER UNITS FOR USE IN DOMESTIC HOUSEHOLD PREMISES REGULATIONS 2 CONSUMER UNIT OVERVIEW 4 STARBREAKER CONSUMER UNITS 5 STARBREAKER

4

l Fully compatible with Arc Fault Detection Devices (AFDD) contact Crabtree technical forfurther details

l Fully compatible with miniature RCBOs with switched neutral as standard

l Full metal enclosure, no exposed plastic parts

l Low Smoke & Fume paint

lTop hinged self closing, stay shut door & metal hinges

l Cable entry knockouts on all sides & large square knockouts on the rear

l Mains tails cable entry gland for supplementary insulation similar to Class II level of protection to tails

l Non combustible cover blanks for unused ways

l Plug in MCB & RCBO 25% fewer connections to make - reducing risk of loose connections

CONSUMER UNITS FOR USE INDOMESTIC HOUSEHOLD PREMISES

l Add or upgrade circuits without removing busbar - no need to disturb adjacent devices -reducing risk of installation errors

l RoHS compliant in excess of UK standards

l UKAS certified to BS EN 61439-3

l Finger safe, insulated busbar assembly - provides greater personal protection

l Permanent factory fitted, non removable busbar shield - can’t be lost or left out

l Plug in MCB and RCBOs for instant guaranteed connections

l Extra height for added wiring space with single module RCBOs

l DIN control devices can be fitted in any position along the DIN rail - without affecting anyother devices or busbar connections

l High capacity neutral & earth terminals

l Factory fitted incoming devices for reduced installation time

AFDD

MINIATURERCBO

Page 7: Starbreaker Consumer Units & Devices - Electrium · CONSUMER UNITS FOR USE IN DOMESTIC HOUSEHOLD PREMISES REGULATIONS 2 CONSUMER UNIT OVERVIEW 4 STARBREAKER CONSUMER UNITS 5 STARBREAKER

518/2B

515/2963B

515/2883B

MAIN SWITCH UNITS MS Total MCB/ MainRating RCBO Ways Switch Metal40A 2* 2 502/2B63A 2* 2 502/26B100A 4 4 504/2B100A 7 7 507/2B100A 10 10 510/2B100A 13 13 513/2B100A 18 18 518/2B

*RCBOs are not recommended for use within 502/-- units.

SPLIT LOAD UNITS 100A SWITCH 63A 30mA RCCBMS Total MainRating Ways Switch RCCB Metal100A 4 2 2 504/2263B100A 7 2 5 507/2263B100A 7 3 4 507/2363B100A 7 4 3 507/2463B100A 7 5 2 507/2563B100A 10 3 7 510/2363B100A 10 4 6 510/2463B100A 10 5 5 510/2563B100A 10 6 4 510/2663B100A 10 7 3 510/2763B100A 15 5 10 515/2563B100A 15 6 9 515/2663B100A 15 7 8 515/2763B100A 15 8 7 515/2863B100A 15 9 6 515/2963B100A 15 10 5 515/2163B

Both MCBs and RCBOs may be included for final circuit positions that are not protected byresident RCCBs.

SPLIT LOAD UNITS 100A SWITCH 80A 30mA RCCBMS Total MainRating Ways Switch RCCB Metal100A 7 2 5 507/2283B100A 7 3 4 507/2383B100A 7 4 3 507/2483B100A 7 5 2 507/2583B100A 10 3 7 510/2383B100A 10 4 6 510/2483B100A 10 5 5 510/2583B100A 10 6 4 510/2683B100A 12 6 6 512/2683B100A 15 6 9 515/2683B100A 15 7 8 515/2783B100A 15 8 7 515/2883B100A 15 9 6 515/2983B100A 15 10 5 515/2183B

Both MCBs and RCBOs may be included for final circuit positions that are not protected byresident RCCBs.

For consumer unit components see page 12.

STARBREAKER

ALL M

ETA

L C

ONSUMER U

NITS 5

Page 8: Starbreaker Consumer Units & Devices - Electrium · CONSUMER UNITS FOR USE IN DOMESTIC HOUSEHOLD PREMISES REGULATIONS 2 CONSUMER UNIT OVERVIEW 4 STARBREAKER CONSUMER UNITS 5 STARBREAKER

DUAL RCD SPLIT LOAD UNITS Total RCCB 1 RCCB 2MS MCB Main 63A 63A Rating Ways Switch 30mA 30mA Metal100A 13 0 7 6 513/2637636B100A 13 0 8 5 513/2638635B100A 13 0 9 4 513/2639634B

Total RCCB 1 RCCB 2MS MCB Main 80A 63A Rating Ways Switch 30mA 30mA Metal100A 8 0 4 4 508/2834634B100A 13 0 7 6 513/2837636B100A 13 0 8 5 513/2838635B100A 13 0 9 4 513/2839634B

RCD INCOMER UNIT WITH MCBs RCCB Rating MCB 1 (B) MCB 2 (B) Metal63A 30mA 2 2 6A 32A 502/363GU

For consumer unit components see page 12.

513/236565B

513/2837636B

HIGH INTEGRITY DUAL RCD UNITS RCCB 1 RCCB 2MS Total Main 63A 63A Rating Ways Switch 30mA 30mA Metal100A 8 2 3 3 508/226363B100A 13 2 6 5 513/226665B100A 13 2 7 4 513/226764B100A 13 2 8 3 513/226863B100A 13 3 5 5 513/236565B100A 13 3 6 4 513/236664B100A 13 3 7 3 513/236763B100A 13 4 5 4 513/246564B100A 13 4 6 3 513/246663B100A 13 5 4 4 513/256464B100A 13 5 5 3 513/256563B100A 13 6 4 3 513/266463B

Total RCCB 1 RCCB 2MS MCB Main 80A 80A Rating Ways Switch 30mA 30mA Metal100A 9 1 4 4 509/218484B100A 13 3 5 5 513/238585B

Total RCCB 1 RCCB 2MS MCB Main 80A 63A Rating Ways Switch 30mA 30mA Metal100A 13 3 5 5 513/238565B100A 13 2 6 5 513/228665B

518/383B

RCD INCOMER UNITS RCCB Total MCBRating Ways RCCB Metal40A 30mA 2 2 502/343B63A 30mA 2 2 502/363B40A 30mA 4 4 504/343B80A 30mA 4 4 504/383B40A 30mA 7 7 507/343B80A 30mA 7 7 507/383B 80A 30mA 10 10 510/383B100A 30mA 10 10 510/313B80A 30mA 13 13 513/383B100A 30mA 13 13 513/313B80A 30mA 18 18 518/383B100A 30mA 18 18 518/313B

STARBREAKER

ALL M

ETA

L C

ONSUMER U

NITS

6

Page 9: Starbreaker Consumer Units & Devices - Electrium · CONSUMER UNITS FOR USE IN DOMESTIC HOUSEHOLD PREMISES REGULATIONS 2 CONSUMER UNIT OVERVIEW 4 STARBREAKER CONSUMER UNITS 5 STARBREAKER

STARBREAKER

ALL M

ETA

L C

ONSUMER U

NITS 7

513/22623B

MULTI TARIFF UNITS Total Main Main MainMCB/ Switch Switch SwitchRCBO 100A 100A 100A Ways Tariff 1 Tariff 2 Tariff 3 Metal9 4 1 4 509/242124B14 8 1 5 514/282125B14 7 1 6 514/272126B

SPLIT LOAD DUAL TARIFF UNITS Main Switch

MS Total Main RCCB 100A Rating Ways Switch 63A 30mA Tariff 2 Metal100A 8 2 3 3 508/22623B100A 13 5 2 6 513/25626B100A 13 3 6 4 513/23624B

Both MCBs and RCBOs may be included for final circuit positions that are not protected byresident RCCBs.

Total Main MCB/ SwitchMS RCBO Main RCCB 100A Rating Ways Switch 80A 30mA Tariff 2 Metal100A 13 3 6 4 513/23824B

Both MCBs and RCBOs may be included for final circuit positions that are not protected byresident RCCBs.

516/262B

DUAL TARIFF UNITS Main Switch Main Switch Total MCB/ 100A 100A RCBO Ways Tariff 1 Tariff 2 Metal5 3 2 505/232B8 3 5 508/232B8 4 4 508/242B8 5 3 508/252B8 6 2 508/262B11 4 7 511/242B11 5 6 511/252B11 6 5 511/262B11 7 4 511/272B11 8 3 511/282B16 6 10 516/262B16 7 9 516/272B16 8 8 516/282B16 9 7 516/292B16 10 6 516/212B16 11 5 516/2112B

TWO BANK MAIN SWITCH METAL UNITSMS Rating Total Ways LIST No

100A 21 521/2B

100A 27 527/2B

100A 37 537/2B

TWO BANK SPLIT LOAD METAL UNITSMS Total Main RCCB Rating Ways Switch 80A 30mA LIST No

100A 20 10 10 520/283B

100A 26 13 13 526/283B

100A 36 18 18 536/283B

TWO BANK DUAL RCD SPLIT LOAD METAL UNITSMS Total Main RCCB 1 RCCB 2 Rating Ways Switch 63A 30mA 80A 30mA LIST No

100A 17 0 7 10 517/26383B

100A 23 0 10 13 523/26383B

100A 33 0 15 18 533/26383B

526/283B

Page 10: Starbreaker Consumer Units & Devices - Electrium · CONSUMER UNITS FOR USE IN DOMESTIC HOUSEHOLD PREMISES REGULATIONS 2 CONSUMER UNIT OVERVIEW 4 STARBREAKER CONSUMER UNITS 5 STARBREAKER

STARBREAKER METAL CASED SKELETON UNITS - 273mm WIDE FIXING CENTRES

DESCRIPTION LIST No

MAIN SWITCH METAL CASED SKELETON UNITS

7 Way Main Switch Unit 607/2Bl 100A DP Main Switch

607/2B

STARBREAKER METAL CASED SKELETON UNITS - 320mm WIDE FIXING CENTRES

DESCRIPTION LIST No

MAIN SWITCH METAL CASED SKELETON UNITS

10 Way Main Switch Unit 610/2B

SPLIT LOAD METAL CASED SKELETON UNITS

8 Way Split Load Unit, 4+4 608/2483B

HIGH INTEGRITY METAL CASED UNITS

6 Way High Inegrity Unit, 2+2+2 606/228282B

DUAL RCD METAL CASED SKELETON UNITS

6 Way Dual RCD Unit, 3+3 606/2833833Bl 100A DP Main Switchl All RCDs have an 80A 30mA rating

610/2B

STARBREAKER METAL CASED SKELETON UNITS - 430mm WIDE FIXING CENTRES

DESCRIPTION LIST No

MAIN SWITCH METAL CASED SKELETON UNITS

13 Way Main Switch Unit 613/2B

SPLIT LOAD METAL CASED SKELETON UNITS

11 Way Split Load Unit, 5+6 611/2583B

HIGH INTEGRITY METAL CASED UNITS

9 Way High Integrity Unit, 1+4+4 609/218484B

DUAL RCD METAL CASED SKELETON UNITS

9 Way Dual RCD Unit, 5+4 609/2835834Bl 100A DP Main Switchl All RCDs have an 80A 30mA rating

613/2B

STARBREAKER

AMENDMENT 3 SKELETON C

ONSUMER U

NITS

8

Page 11: Starbreaker Consumer Units & Devices - Electrium · CONSUMER UNITS FOR USE IN DOMESTIC HOUSEHOLD PREMISES REGULATIONS 2 CONSUMER UNIT OVERVIEW 4 STARBREAKER CONSUMER UNITS 5 STARBREAKER

STARBREAKER

CONSUMER U

NIT PA

TTRESSES

9

CONSUMER UNIT PATTRESSESENCLOSURE PATTRASS LEFT/RIGHT TOP/BOTTOM

WIDTH DEPTH ENTRY ENTRY

6 Module 16mm MNSPE6670/1NR MNSPE6584/1NR

9 Module 16mm MNSPE6670/2NR MNSPE6584/2NR

12 Module 16mm MNSPE6670/3NR MNSPE6584/3NR

15 Module 16mm MNSPE6670/4NR MNSPE6584/4NR

20 Module 16mm MNSPE6670/5NR MNSPE6584/5NRFor use with all metal consumer units. Allows surface cable entry through rearknockouts and automatically maintains enclosure IP rating to comply with BS7671and BSEN61439-3 l Cable entry slot may be positioned to suitl Not suitable for use with skeleton units

H913/2WB

ASSEMBLED SPINE BACKPLATES MAIN SWITCH Total MCB/ MS Rating RCBO Ways Main Switch LIST No

100A 13 13 H913/2WB

100A 18 18 H918/2WB

SPLIT LOAD 100A SWITCH 63A 30mA RCCB MS Rating Total Ways Main Switch RCCB LIST No

100A 10 4 6 H910/2463WB

100A 10 5 5 H910/2563WB

100A 10 6 4 H910/2663WBMCBs and RCBOs may be included for final circuit positions not protected by residentRCCBs.

SPLIT LOAD 100A SWITCH 80A 30mA RCCB MS Rating Total Ways Main Switch RCCB LIST No

100A 10 4 6 H910/2483WB

100A 10 5 5 H910/2583WB

DUAL RCD SPLIT LOAD Total Main RCCB 1 RCCB 2 MS Rating Ways Switch 80A 30mA 63A 30mA LIST No

100A 8 0 4 4 908/2834634WBMCBs and RCBOs may be included for final circuit positions not protected by residentRCCBs.Starbreaker spine backplates (H) accept both MCBs and single module RCBOs.For use in domestic household premises these spine units must be mounted within a non-combustible enclosure.

Page 12: Starbreaker Consumer Units & Devices - Electrium · CONSUMER UNITS FOR USE IN DOMESTIC HOUSEHOLD PREMISES REGULATIONS 2 CONSUMER UNIT OVERVIEW 4 STARBREAKER CONSUMER UNITS 5 STARBREAKER

61/B16 61/B20 61/B40

61/BM40AFD

STARBREAKER

CONSUMER U

NIT O

UTGOIN

G D

EVIC

ES

10

ACCESSORIES

Blanking Plate 443

Blanking Unit (960º) CSB1

Blanking Plate twist fit CSBC

MCB Padlocking Device MCBLD

MINIATURE CIRCUIT BREAKERS (6kA)

B CURVE C CURVERATING POLES MODULES LIST NO. LIST NO.

6A 1 1 61/B06 61/C06

10A 1 1 61/B10 61/C10

16A 1 1 61/B16 61/C16

20A 1 1 61/B20 61/C20

32A 1 1 61/B32 61/C32

40A 1 1 61/B40 61/C40

50A 1 1 61/B50 61/C50

Not suitable for use in conjunction with AFDD

MINIATURE RCBO 6kA (MCB sized 1 module with switched neutral)

RCD B CURVE C CURVERATING RATING POLES MODULES LIST NO. LIST NO.

6A 30mA 2 1 61/BM0630 61/CM0630

10A 30mA 2 1 61/BM1030 61/CM1030

16A 30mA 2 1 61/BM1630 61/CM1630

20A 30mA 2 1 61/BM2030 61/CM2030

25A 30mA 2 1 61/BM2530 -

32A 30mA 2 1 61/BM3230 61/CM3230

40A 30mA 2 1 61/BM4030 61/CM4030

Type A - Pure AC and pulsating DC sensitivity

ARC FAULT DETECTION DEVICES (AFDD)

RCD B CURVE C CURVERATING RATING POLES MODULES LIST NO. LIST NO.

6A 30mA 2 2 61/BM06AFD 61/CM06AFD

10A 30mA 2 2 61/BM10AFD 61/CM10AFD

16A 30mA 2 2 61/BM16AFD 61/CM16AFD

20A 30mA 2 2 61/BM20AFD 61/CM20AFD

25A 30mA 2 2 61/BM25AFD -

32A 30mA 2 2 61/BM32AFD 61/CM32AFD

40A 30mA 2 2 61/BM40AFD 61/CM40AFD

Starbreaker arc fault detection devices are only available combined withMiniature RCBOs and so provide the highest levels of protection applied per circuit. For use in main switch controlled units / applications.

61/BM0630 61/BM1030 61/BM3230

Page 13: Starbreaker Consumer Units & Devices - Electrium · CONSUMER UNITS FOR USE IN DOMESTIC HOUSEHOLD PREMISES REGULATIONS 2 CONSUMER UNIT OVERVIEW 4 STARBREAKER CONSUMER UNITS 5 STARBREAKER

BELL TRANSFORMERS TIM

E SWITCHES

11

301/TD1 302/TD2

301/TQ24 303/TQ7

DIGITAL TIMESWITCHES

DESCRIPTION MOD LIST No

1 Channel Digital Timeswitch 1 301/TD1

1 Channel Digital Timeswitch 2 302/TD1

2 Channel Digital Timeswitch 2 302/TD2

1 Channel Digital Timeswitch + data key facility 2 402/TD1

2 Channel Digital Timeswitch + data key facility 2 402/TD2

1 Channel Digital Astro Timeswitch + data key facility 2 502/TD1

2 Channel Digital Astro Timeswitch + data key facility 2 502/TD2

1-10 min Staircase Timeswitch 1 301/S10

Software USB/S

Data Key 4/5DK

Data Key 6DK

ANALOGUE TIMERS

DESCRIPTION MODULES LIST No

24hr Analogue Quartz 1 301/TQ24

24hr Analogue Quartz 3 303/TQ24

7 Day Analogue Quartz 3 303/TQ7

24hr Analogue Synchronous 1 301/TS11

24hr Analogue Synchronous 3 303/TS24

303/B12

BELL TRANSFORMER

DESCRIPTION MODULES LIST No

12V bell transformer 2 303/B12

l With overload protection.

ACCESSORIES

Metal Blanking Plate 543

MCB Padlocking Device MCBLD

Universal Adaptor (mains tail gland) MTCG32

See page 16 for modular control devices

Page 14: Starbreaker Consumer Units & Devices - Electrium · CONSUMER UNITS FOR USE IN DOMESTIC HOUSEHOLD PREMISES REGULATIONS 2 CONSUMER UNIT OVERVIEW 4 STARBREAKER CONSUMER UNITS 5 STARBREAKER

CONSUMER UNIT PATTRESSES lENCLOSURE PATTRASS LEFT/RIGHT TOP/BOTTOM

WIDTH DEPTH ENTRY ENTRY6 Module 16mm MNSPE6670/1NR MNSPE6584/1NR9 Module 16mm MNSPE6670/2NR MNSPE6584/2NR12 Module 16mm MNSPE6670/3NR MNSPE6584/3NR15 Module 16mm MNSPE6670/4NR MNSPE6584/4NR20 Module 16mm MNSPE6670/5NR MNSPE6584/5NR

For use with Crabtree All Metal consumer units. Allows surface cable entry through rear knockouts andautomatically maintains enclosure IP rating to comply with BS7671 and BSEN61439-3 and the IET onsite guide.

Cable entry slot line up with rear knockouts, the minimum number of knockouts only should be removed for cableentry.

Suitable for use with trunking systems.

METAL ENCLOSURES

DIMENSIONS l

D

IMENSIO

NSSTA

RBREAKER

12

STARBREAKER SIZE 4 ENCLOSURE (504/0A)

DIMENSIONS A =185mm B =130mm C =104mm

502/26B502/2B

502/343B502/363B

502/363GU

STARBREAKER SIZE 6 ENCLOSURE (506/0A)

DIMENSIONS A =261mm B =188mm C =121mm

504/2B 504/383B504/343B

STARBREAKER SIZE 9 ENCLOSURE (509/0A)

DIMENSIONS A =261mm B =242mm C =121mm

504/2263B505/232B

507/2B507/383B507/343B

STARBREAKER SIZE 12 ENCLOSURE (512/0A)

DIMENSIONS A =261mm B =292mm C =121mm

507/2263B507/2283B507/2363B507/2383B507/2463B507/2483B

507/2563B507/2583B508/232B508/242B508/252B508/262B

510/2B510/313B510/383B

STARBREAKER SIZE 15 ENCLOSURE (515/0A)

DIMENSIONS A =261mm B =343mm C =121mm

508/22623B508/226363B508/2834634B509/242124B510/2363B510/2383B510/2463B510/2483B510/2563B510/2583B510/2663B

510/2683B510/2763B511/242B511/252B511/262B511/272B511/282B513/2B513/313B513/383B509/218484B

TOP/BOTTOM CABLE ENTRY LEFT/RIGHT CABLE ENTRY

STARBREAKER SIZE 20 ENCLOSURE (520/0A)

DIMENSIONS A =261mm B =438mm C =121mm

513/226764B513/226863B513/23624B513/236565B513/236664B513/236763B513/23824B513/246564B513/246663B513/25626B513/256464B

513/256563B513/2637636B513/2638635B513/2639634B513/266463B513/2837636B513/2838635B513/2839634B514/272126B514/282125B515/2163B

515/2183B515/2563B515/2663B515/2683B515/2763B515/2783B515/2863B515/2883B515/2963B515/2983B516/2112B

516/212B516/262B516/272B516/282B516/292B518/2B518/313B518/383B512/2683B513/226665B513/238585B

513/238565B513/228665B

B16

255

B16

B

A

C

Page 15: Starbreaker Consumer Units & Devices - Electrium · CONSUMER UNITS FOR USE IN DOMESTIC HOUSEHOLD PREMISES REGULATIONS 2 CONSUMER UNIT OVERVIEW 4 STARBREAKER CONSUMER UNITS 5 STARBREAKER

C B

A

DIMENSIONS l

TWO BANK UNITS

SPINE BACKPLATE ASSEMBLIES (White PVC Cover)

STARBREAKER INCOMING DEVICES AND ENCLOSURES

STARBREAKER SIZE 24 ENCLOSURE (524/2A)

DIMENSIONS A =506mm B =295mm C =121mm

517/26383B 520/283B

STARBREAKER SIZE 30 ENCLOSURE (530/2A)

DIMENSIONS A =506mm B =345mm C =121mm

523/26383B 526/283B

STARBREAKER SIZE 40 ENCLOSURE (540/2A)

DIMENSIONS A =506mm B =440mm C =121mm

533/26383B 536/283B

STARBREAKER 15 MODULE SPINE BACKPLATE UNIT (10W & 13W)

DIMENSIONS A =235mm B =335mm C =106mm D =180mm E =319.5mm

H910/2463WBH910/2483WB

H910/2563WBH910/2583WBH910/2663WB

H913/2WB

DOUBLE POLE MAIN SWITCH DISCONNECTORS

RATING MODULAR WIDTH LIST No

40A 2 40/M12*63A 2 63/M12*100A 2 100/MI2*100A 2 100/2MT**

* Used within main switch only and split-load applications** Used within high integrity and dual RCD applications

RESIDUAL CURRENT CIRCUIT BREAKERS

RATING MODULAR WIDTH LIST No

40A 30mA 2 340/03063A 30mA 2 363/03080A 30mA 2 380/030100A 30mA 2 310/03063A 30mA 3 363/S030*80A 30mA 3 380/S030*

* Dedicated as a split-load RCCB (3 modules)

AM 3 UPGRADE / REPLACEMENT COVERS FOR 8 SERIESENCLOSURES

MODULAR WIDTH LIST No

6 806/LID255G 9 809/LID255G 12 812/LID255G 15 815/LID255G 20 820/LID255G

ENCLOSURES

MODULAR WIDTH ALL METAL

4 504/0A 6 506/0A 9 509/0A 12 512/0A 15 515/0A 20 520/0A 24 524/0A 30 530/0A 40 540/0A

FLUSH MOUNTING KIT

MODULAR WIDTH ALL METAL

6 506/FLA 9 509/FLA 12 512/FLA 15 515/FLA 20 520/FLA 24 524/FLA 30 530/FLA 40 540/FLA

REPLACEMENT COVERS FOR 5 SERIES ENCLOSURES

MODULAR WIDTH ALL METAL

6 506/LID 9 509/LID 12 512/LID 15 515/LID 20 520/LID

STARBREAKER 20 MODULE SPINE BACKPLATE UNIT (18W)

DIMENSIONS A =235mm B =448mm C =106mm D =180mm E =435mm

H918/2WB

STARBREAKER 15 MODULE DRCD (8W)

DIMENSIONS A =205mm B =333mm C =106mm D =140mm E =320mm

908/2834634B

DIM

ENSIO

NSSTA

RBREAKER

13

CB

A

E

D

UNIT FIXING POSITIONS

Page 16: Starbreaker Consumer Units & Devices - Electrium · CONSUMER UNITS FOR USE IN DOMESTIC HOUSEHOLD PREMISES REGULATIONS 2 CONSUMER UNIT OVERVIEW 4 STARBREAKER CONSUMER UNITS 5 STARBREAKER

ELECTRIUM SALES LIMITED A SIEMENS COMPANYCommercial Centre, Lakeside Plaza, Walkmill Lane, Bridgtown, Cannock WS11 0XE.

eMail: [email protected] Web: www.electrium.co.uk

UK SALESTelephone: 01543 455010 Facsimile: 01543 455011 eMail: [email protected]