standard filter vessel installation and operation manual (vf & hf)
TRANSCRIPT
VEL2199 04/14
Velcon Filtration Division
Effective: April 2014
StandardFilter Vessel Installation and OperationManual (VF & HF)
Parker Hannifi n CorporationVelcon Filtration Division
1210 Garden of the Gods RoadColorado Springs, CO 80907+1 719 531 5855 Phone+1 719 531 5690 [email protected]
2 Parker Hannifi n CorporationVelcon Filtration Division
Colorado Springs, CO 80907 USA
Velcon Filtration DivisionFilter Vessel Installation & Operation Manual
VEL2199 0414
WARNING
DO NOT PRESSURE TESTTHIS VESSEL WITH AIR!
PRESSURE TESTINGWITH AIR IS A
HAZARDOUS PROCEDURE!
THIS VESSEL IS TO BE PRESSURIZED ONLY WITH THE LIQUID FOR WHICH IT IS INTENDED TO BE USED AND ONLY
TO THE MAXIMUM DESIGN PRESSURE SHOWN ON THE VESSEL NAME PLATE.
3 Parker Hannifi n CorporationVelcon Filtration Division
Colorado Springs, CO 80907 USA
Velcon Filtration DivisionFilter Vessel Installation & Operation Manual
VEL2199 0414
TABLE OF CONTENTS
General Description .....................................................................................................................4 Installation of Vessel ....................................................................................................................5Start-Up Procedure .....................................................................................................................6Operating Information .................................................................................................................7Cartridge Change or Inspection Procedure ..............................................................................13
Installation Instructions
Open-Ended Filter Cartridges ...................................................................................................10Torque Requirements for Vessels with O-ring Closures ............................................................11Installing Tie Rods .....................................................................................................................12
Appendix
A - Pleated Media Filter Cartridges .................................................................................... 16-17 B - F0-6xxA3 & FOH-6xxA1 - EI1590 Qualifi ed Filter Cartriges ......................................... 18-19 C - VF Series - Vertical Filter Vessels .................................................................................. 20-21 D - Assembly Torque Recommendations ........................................................................... 22-23
DISCLAIMER: This generic vessel manual is provided for your information with the understanding that each vessel sent out from Velcon is customized for the particular vessel and contains accessory information not included in this document. This docu-ment makes references to other pieces of literature, such as schematics and drawings that are added to the manual as needed depending on the vessel parameters.
4 Parker Hannifi n CorporationVelcon Filtration Division
Colorado Springs, CO 80907 USA
Velcon Filtration DivisionFilter Vessel Installation & Operation Manual
VEL2199 0414
5 Parker Hannifi n CorporationVelcon Filtration Division
Colorado Springs, CO 80907 USA
Velcon Filtration DivisionFilter Vessel Installation & Operation Manual
VEL2199 0414
GENERAL DESCRIPTION
The Velcon that you have received consists of the vessel, filter elements, and accessory equipment to meet your specific requirements. Descriptive literature covering the accessories is included near the back of this manual.
A Velcon is specifically designed to remove solid contaminants from the product being filtered. The product enters from the inlet nozzle, rising vertically behind a baffle until it reaches the region above the top of the highest elements. The elements are arranged in vertical stacks rising up from a flat division plate. The fluid enters the outside of each element and flows toward the center of the element. The flow then goes downward to the outlet.
Velcon are manufactured to meet a variety of different end uses and specifications. The finest workmanship has gone into the building of this Velcon. It is of no value, however, if elements are improperly installed or the unit is improperly operated. We urge you to read the manual carefully and follow the instructions given.
NOTE Velcon has qualified the FO-6xxA3 pleated media filter cartridges to EI Specification 1590, “Specifications and Qualification Procedures for Aviation Fuel Microfilters.”
INSTALLATION OF VESSEL
1. Identify the Filter inlet and outlet by the markings provided on the vessel piping. The Filter must be installed in the correct direction of fl ow to perform properly and to avoid damage to the system.
2. INLET and OUTLET PIPING should be carefully aligned to avoid stressing the Filter connections during installation. Installation of shut-off valves on either side of the Filter is recommended so that it can be independently drained for cartridge change or inspection.
CAUTION
STEPS 3 AND 4 SHOULD BE
PERFORMED BEFORE REMOV-
ING HINGE OR PIVOT MOUNTED
COVER TO ENSURE STABILITY OF
THE FILTER.
3. Bolt the fi lter to a stable base.
4. Carefully install correct gaskets on the inlet and outlet connections and connect to the inlet and outlet piping.
5. Connect any accessories that are not already installed. See Accessory Parts List and literature as required.
6. Cartridges are normally packed separately. Open the vessel cover and install cartridges as explained on page 8 and as per enclosed element stack drawing. Tighten nuts on tie rods until the rubber washers begin to curl. Do not over-torque.sequence.
7. Be sure the cover gasket is in place and properly aligned. Replace cover and secure tightly.
NOTE FILTERS MUST BE PROVIDED WITH PRESSURE RELIEF VALVES IF THE SYSTEM HAS POSITIVE DISPLACEMENT PUMPS UPSTREAM OR AUTOMATIC SHUT-OFF VALVES DOWNSTREAM OF THE VESSEL.
START UP PROCEDURE
If the Velcon Filter has the accessories listed below, they should be placed in the following positions:
1. Manual drain valves closed.
2. Manual air eliminator valve open.
3. The valves in the inlet and outlet piping should be closed.
4. The pressure gauge valve to OFF position. For Filters equipped with selector valves, this is done by turning the handle outward so that the arrow points toward the vessel.
For information on operation of accessories, turn to Accessory Instructions in the back of the manual.
After the valves have been positioned as outlined, the unit is ready to be filled.
The following operating instructions can be used for initial start-up and for subsequent start-ups after installation of replacement elements or servicing of the unit.
1. Start the system pump.
2. Slightly open the inlet valve, allowing the Filter to slowly fi ll with fl uid. (Take about 10 – 15 minutes to fi ll the vessel to eliminate the possibility of an internal fi re.)
3. If the unit is equipped with a manual air eliminator valve, leave the valve cracked open until the fl uid fl ows from the opening; then close quickly.
4. If equipped with an automatic air eliminator, the unit is fi lled when the air eliminator stops fl owing air. When the Velcon Filter is fi lled with fl uid, slowly open the valve on the inlet line, then slowly open
6 Parker Hannifi n CorporationVelcon Filtration Division
Colorado Springs, CO 80907 USA
Velcon Filtration DivisionFilter Vessel Installation & Operation Manual
VEL2199 0414
the valve on the outlet line.
5. When the unit is in operation, open the pressure gauge, take a differential pressure reading and record the reading. If there is no pressure differen-tial, the system should be shut down and the Filter inspected for broken seals or possibly elements left out. See Differential Pressure Readings on Page 5
OPERATING INFORMATION
Below are the Velcon recommendations for operating procedures. Your Company Maintenance and/or Quality Control procedures may provide alternate instructions on these matters.
1. FILTER CARTRIDGES should be changed in accor-dance with one of the following (whichever comes fi rst):
A. When the differential pressure reaches the level specifi ed on the cover page of this manual. For Filters equipped with differential pressure gauges, see paragraph 2 below.
B. When the fl ow rate is reduced to an unaccept-able level because the cartridges are plugged with contaminant.
C. Whenever effl uent product is unacceptably contaminated.
2. DIFFERENTIAL PRESSURE READINGS Differential pressure is the difference between the pressure upstream and downstream of the Filter. Differential pressure increases when contaminant is fi ltered by the fi lter cartridges and causes fl ow restriction.
Readings should be taken when the system is fl owing at maximum capacity. If the Filter is equipped with a direct reading differential pressure gauge, the reading shown on the gauge is the dif-ferential pressure across the Filter.
If the Filter is equipped with a pressure gauge and a selector valve, use the following procedure for determining differential pressure:
A. Turn the handle one way and record the pres-sure reading.
B. Turn the handle the other way (90° or 180°, depending on the type of valve) and record the pressure reading.
C. Subtract the lower reading from the higher reading to determine differential pressure. (The higher reading is inlet pressure.)
If the fi lter/separator is equipped with a pressure gauge and a selector valve, use the following procedure for determining differential pressure:
A. Turn the handle one way and record the pressure reading.
B. Turn the handle the other way (90° or 180°, depending on the type of valve) and record the pressure reading.
C. Subtract the lower reading from the higher reading to determine differential pressure. The higher reading is inlet pressure.
Differential pressure readings should be taken at least once during every operating week and more frequently in high throughput installations or when the differential is increasing rapidly. Records of the differential pressure and throughput should be maintained to determine when cartridges should be changed.
A sudden drop in pressure differential is an indica-tion of a possible problem. Check fi rst to be sure that readings were taken at equivalent fl ow rates. If so, shut the system down, open the Filter, and inspect for the following:
A. Collapsed or ruptured cartridges caused by severe pressure differential or shocks in excess of design limits.
B. Ruptured seals. Check to see that all O-ring seals and gaskets seals are in place and have the same alignment as when the elements and parts were installed.
C. Broken end plates. Inspect all of the end plates of the elements.
D. If any of the above are observed, check the system for possible hydraulic shock condi-tions. If the system is not provided with ad-equate surge controls, the sudden start-up of a high-pressure pump can create extremely high shock
CARTRIDGE CHANGE OR INSPECTION PROCEDURE
A. Shut off the pump.
B. Close the inlet and outlet pipe valves.
C. Open the drain valves and remove the product from the Filter.
D. Open the manual air eliminator valve. This will permit the unit to drain faster.
7 Parker Hannifi n CorporationVelcon Filtration Division
Colorado Springs, CO 80907 USA
Velcon Filtration DivisionFilter Vessel Installation & Operation Manual
VEL2199 0414
E. Open the cover and inspect the cover gasket – replace the gasket if it is damaged.
F. Completely drain fi lter chamber.
G. Remove spent cartridges for cartridge change.
H. Wipe off or wash down any foreign matter from the vessel interior.
I. Install the cartridges in accordance with in-structions on page 8.
J. Tighten nuts on tie rods until the rubber wash-ers begin to curl. Do not over-torque.
K. Check the cover gasket for alignment, re-place the cover and secure tightly. The Filter is now ready for the start-up procedure.SUMP CHECKS
NOTE USE ONLY PARKER VELCON CARTRIDGES IN THIS FILTER. VELCON CANNOT WARRANT PERFORMANCE IF ANY OTHER MANUFACTURER’S CARTRIDGES ARE USED.
To reorder cartridges and replacement parts or to obtain further information, contact your Velcon representative:
Parker Hannifi n CorporationFiltration Group
Velcon Filtration Division1210 Garden of the Gods Road
Colorado Springs, CO 80907-3410
Tel: +1 719 531 5855Fax: +1 719 531 [email protected]
www.velcon.com
8 Parker Hannifi n CorporationVelcon Filtration Division
Colorado Springs, CO 80907 USA
Velcon Filtration DivisionFilter Vessel Installation & Operation Manual
VEL2199 0414
9 Parker Hannifi n CorporationVelcon Filtration Division
Colorado Springs, CO 80907 USA
Velcon Filtration DivisionFilter Vessel Installation & Operation Manual
VEL2199 0414
InstallationInstructions
10 Parker Hannifi n CorporationVelcon Filtration Division
Colorado Springs, CO 80907 USA
Velcon Filtration DivisionFilter Vessel Installation & Operation Manual
VEL2199 0414
Installation Instruction for Open-End Filter Cartridges
1. Turn off pump. Close inlet and outlet valves and open drain valve. Open the air eliminator or manual bleed valve and drain the vessel.
2. Open vessel after making sure the vessel is com-pletely drained.
3. Jack-up head and swing aside. Remove the spider (if installed). Remove nuts and washers, endcaps, old cartridges, and center plates, if any.
4. Wipe vessel clean whenever possible or fl ush.
5. Place cartridge over the center rod making sure the cartridge is centered over the guide bar or mounting adapter attached to the deck plate. The cartridge must be seated fl at against the adapter or deck plate.
6. For vessels with stacked cartridges, place the fi rst tier of fi lter cartridges in position at all bulkhead ports (per step 6). Insert center plate onto center rod and insert into each cartridge. Next, install the second tier of cartridges over the center plates. There must always be a center plate between every two stacked cartridges. Be sure the circular guide on both sides of the center plate projects into each cartridge.
7. When all cartridges are loaded, insert sealing cap over center rod.
8. Install rubber washer, fl at washer, lock washer, and nut in that order, onto each center rod. Tighten to 4 to 5 foot pounds of torque. (DO NOT TOUCH THE OUTER FILTER MEDIA.)
9. Replace the spider as follows (if spider is not in-cluded proceed to step #10):
Install the flat washer over each cartridge end and install the spider over the ends of the cartridges.
Affix the spider to the threaded clips on the vessel walls using the nut and lockwasher.
Adjust the spider clip nuts, so the spider lies flat on the ends of the cartridges
Install the washer and nut over the ends of the cartridges, to affix the spider to the cartridge ends. Snug the nuts. DO NOT TIGHTEN YET.
Adjust the ends of each cartridge to create even separation between the cartridges and between the cartridge and vessel wall. Cartridges should NOT be touching each other, nor touching the vessel wall. The ends of the cartridges can be shifted within the spider plate holes as follows:
Cartridge Length
Shift Within the Spider Hole
Greater than 33"
Full movement within the spider hole
30" Less than 5/8" (16 mm)28" Less than 9/16" (14 mm)24" Less than 1/2" (12 mm)22" Less than 1/2" (12 mm)20" Less than 3/8" (10 mm)18" Less than 3/8" (10 mm)16" Less than 1/4" (8 mm)14" Less than 1/4" (6 mm)11" Less than 1/4" (5 mm)9" Less than 3/16" (5 mm)
When the cartridges are spaced properly, tighten the spider nuts to 5 ft-lbs.
10. Inspect the cover gasket and replace it if neces-sary. Tighten the cover securely in a cross-pattern process.
11. Close the drain valve and start the system pump.
12. With the outlet valve closed, slightly open the inlet valve and allow the vessel to fi ll SLOWLY with fuel until the air eliminator closes or fl uid begins to fl ow from the manual air vent. Close the vent valve. Fully open the inlet valve.
13. Open the outlet valve SLOWLY.
14. When the unit is operating, check the differential pressure across the cartridges. There should be indication of positive pressure, normally 1-5 psid. This insures that all seals have been properly made during the installation.
OPERATING PROCEDURES
Velcon Recommended Cartridge Changeout (also reference your company guidelines):
1 year or 15 psid for AVIATION APPLICATIONS
3 years or 25 psid for NON-AVIATION APPLICATIONS whichever occurs first (INSPECT VESSEL ANNUALLY)
11 Parker Hannifi n CorporationVelcon Filtration Division
Colorado Springs, CO 80907 USA
Velcon Filtration DivisionFilter Vessel Installation & Operation Manual
VEL2199 0414
Torque Requirements for Vessels with “O-Ring Closure”
Bolted pressure vessel closures operate on the premise that the joint is clamped closed with a force sufficient to resist the internal pressure yet still maintain a seal. The clamping force, or pre-load, is applied by the closure bolts and its magnitude is controlled by the torque applied. Application of the correct preload is essential to maintaining a positive seal and avoiding closure failures from fatigue or overstressed vessel components.
The short term, and most obvious effect of grossly under-torqued bolts is insufficient clamping force resulting in a leaking closure. A more ominous result of under-torqued bolts in systems which see a great number of pressure cycles (such as refuelers, loading racks etc.), is bolt fatigue failure. Repeated applications of stress to the bolt eventually create a small crack at the surface of the bolt which continues to grow until the bolt breaks and the closure fails.
It is a good idea to re-torque the closure bolts after they have been in use for a month or so to ensure the joint has not “relaxed” and the preload reduced.
Over-torquing closure bolts will result in breaking or bending vessel bolt clips or actually breaking the bolt itself. Table One lists guideline torque values for lubricated bolts for common sizes used for vessel closures. Always use lubricated bolts, as this reduces the required torque, improves torque accuracy, and retards corrosion.
A common cause of inaccurate bolt torque is inappropriate bolt torquing procedures. Key elements to the procedure are application of the torque in stages and in a specific cross-torquing sequence. For most applications, torque is applied to all bolts to 30% of full torque, then to all bolts to 60% of full torque, and finally to all bolts to 100% of full torque. Each torquing cycle is carried out in the applicable cross-torquing sequence. Torquing sequences vary with the number of bolts on the cover.
The tightening pattern is as follows: Tighten two bolts diametrically opposite from each other, then tighten a second pair of bolts diametrically opposite each other, approximately 90 degrees away from the first pair, and so on until all bolts have been tightened.
Using a clock as an example, the sequence would be: 12 - 6, 9 - 3, 11 - 5, 10 - 4, 7 - 1, and 8 - 2.
On large vessels, the cross-torquing process is tedious but the addition of a second operator applying torque improves the situation vastly.
Correct closure torquing will result in many years of trouble-free vessel operation. Occasional inspections for bolt cracks or clip damage is good practice to detect possible closure problems before they occur.
TABLE ONE*Bolt Diameter
mm (in.)Recommended Torque
m-kgs (ft-lb)
13 (1/2) 3 (20)
19 (3/4) 6 (45)
25 (1) 14 (100)
32 (1-1/4) 22 (160)
38 (1-1/2) 36 (260)
*NOTE: These recommended torque values are only for vessels with an O-Ring closure.
12 Parker Hannifi n CorporationVelcon Filtration Division
Colorado Springs, CO 80907 USA
Velcon Filtration DivisionFilter Vessel Installation & Operation Manual
VEL2199 0414
Installation of Tie Rods
REFERENCE MATERIAL
Form 1801- “Assembly Torque Recommendations”
VESSELS WITH TIE RODS
Filter vessels Clay vessels Monitor vessels containing 6” Aquacon® cartridges Filter/separator vessels (for coalescer and separators)
HARDWARE
Tie rods Hardware (nuts, flat washers, lock washers, seal nuts) Cartridges Mounting adapters Center spacers End caps
MOUNTING CONFIGURATIONS
With spider Without spider With seal nut
VERTICAL OR HORIZONTAL OPEN ENDED CARTRIDGES WITH SPIDER PLATE:
1. Screw a nut on one end of the tie rod to about 2” from the end (see note on bottom of page 2).
2. Slide a lock washer up against the nut on the shortened side of the tie rod.
3. Slide a mounting adapter (on vessels with integral cast-in or welded-in mounting adapters, no ad-ditional adapter is required) on the short side of the tie rod with the cartridge seal side facing the nut and washer.
4. While holding the mounting adapter on the end of the rod, screw the short end of the tie rod into the tie rod bar on the vessel. Screw in about one inch.
5. Install a cartridge over the tie rod and into place on the mounting adapter.
6. If cartridges are stacked, install center spacers between cartridges.
7. Place an end seal plate on the top or end of the cartridge (or cartridge stack) with the tie rod ex-tending out from the end seal plate tie rod hole.
8. Adjust the tie rod by screwing it in or out until the amount extending beyond the end cap is 1-5/8”. Remove the cartridges, spacers, and caps.
9. Screw the nut at the end of the tie rod down against the mounting adapter while preventing the tie rod from turning.
10. Tighten the nut to 5 foot pounds of torque.
11. Install the other tie rods so that they extend out from the mounting adapters the same length as the fi rst rod.
VERTICAL OR HORIZONTAL OPEN ENDED CARTRIDGES WITH NO SPIDER PLATE:
1. Screw a nut on one end of the tie rod to about 2” from the end. (See note below.)
2. Slide a lock washer up against the nut on the shortened side of the tie rod.
3. Slide a mounting adapter (on vessels with integral cast-in or welded-in mounting adapters, no ad-ditional adapter is required) on the short side of the tie rod with the cartridge seal side facing the nut and washer.
4. While holding the mounting adapter on the end of the rod, screw the short end of the tie rod into the tie rod bar on the vessel. Screw in about one inch.
5. Install a cartridge over the tie rod and into place on the mounting adapter.
6. If cartridges are stacked, install center spacers between cartridges.
7. Place an end seal plate on the top or end of the cartridge (or cartridge stack) with the tie rod ex-tending out from the end seal plate tie rod hole.
8. Adjust the tie rod by screwing it in or out until the amount extending beyond the end seal plate is one (1) inch.
9. Remove the cartridges, spacers, and seal plates.
13 Parker Hannifi n CorporationVelcon Filtration Division
Colorado Springs, CO 80907 USA
Velcon Filtration DivisionFilter Vessel Installation & Operation Manual
VEL2199 0414
10. Screw the nut at the end of the tie rod down against the mounting adapter while preventing the tie rod from turning.
11. Tighten the nut to 5 foot pounds of torque.
12. Install the other tie rods so that they extend out from the mounting adapters the same length as the fi rst rod.
SEPARATOR WITH SEAL NUT (WITH OR WITHOUT SPIDER PLATE):
1. Screw a nut on one end of the tie rod to about 2” from the end. (See note below.)
2. Slide a lock washer up against the nut on the shortened side of the tie rod.
3. Slide a mounting adapter (on vessels with integral cast-in or welded-in mounting adapters, no ad-ditional adapter is required) on the short side of the tie rod with the cartridge seal side facing the nut and washer.
4. While holding the mounting adapter on the end of the rod, screw the short end of the tie rod into the tie rod bar on the vessel. Screw in about one inch.
5. Install a separator over the tie rod and into place on the mounting adapter so the tie rod extends from the end seal cap tie rod hole.
6. On double open ended separators, place an end seal plate on the top or end of the separator, with the tie rod extending out from the end seal plate tie rod hole.
7. Adjust the tie rod by screwing it in or out until the amount extending beyond the end seal plate is one (1) inch.
8. Remove the cartridges, spacers, and seal plates.
9. Screw the nut at the end of the tie rod down against the mounting adapter while preventing the tie rod from turning.
10. Tighten the nut to 5 foot pounds of torque.
11. Install the other tie rods so that they extend out from the mounting adapters the same length as the fi rst rod.
NOTE 1. In AHM06xxx, AVM06xxx, HM06xxx, and VM06xxx Aquacon® vessels, the nut should be screwed on to the tie rod to about 4” from the end instead of 2”.
2. In three stage HVM-xxxx fi lter/sepa-rator vessels, the nut on the separa-tor tie rods should be screwed on to the tie rod to about 4” from the end instead of 2”.
14 Parker Hannifi n CorporationVelcon Filtration Division
Colorado Springs, CO 80907 USA
Velcon Filtration DivisionFilter Vessel Installation & Operation Manual
VEL2199 0414
15 Parker Hannifi n CorporationVelcon Filtration Division
Colorado Springs, CO 80907 USA
Velcon Filtration DivisionFilter Vessel Installation & Operation Manual
VEL2199 0414
Appendix / Accessories
16 Parker Hannifi n CorporationVelcon Filtration Division
Colorado Springs, CO 80907 USA
Velcon Filtration DivisionFilter Vessel Installation & Operation Manual
VEL2199 0414
Pleated Media Filter CartridgesHigh Effi ciency, Long Life Cartridges for Aviation Fuel
FO-412PLxx FO-718PLxxFO-512PLxx FO-644PLFxxTBFO-614PLFxx
FEATURES
Large Surface Area – Allows high flow rate with low initial pressure drop and maximum contaminant holding capacity.
Resin Impregnated Media – Maintains strength, resists effects of water and heat.
75 psi Collapse Strength – Heavy gauge carbon steel endcaps and center tube give safety margin against pressure surges.
Coated Steel Components – Resist corrosion from most industrial fluids.
Corrugated Media – Prevents pleat pinch-off, assuring all filtration media is utilized.
Buna-N Gaskets – The best general gasket material available assures positive seal in most fluids.
Thermoset Bonding Material – Durable endcap-to-media bond prevents internal bypassing.
Threaded base filter elements – Available for easier installation.
SPECIFICATIONS
• 75 psi Collapse strength
• 5 - 9 Operating pH range
• Micron ratings from 1/4 to 75
• 98%+ Nominal filtration efficiency
• 250°F Maximum operating temperature
• Recommended changeout differential pressure - 25 psid
• Multi-pass (Beta Ratio) data available on request
For information about Flow Ratings with various viscosity fluids, refer to Form #1532
Please note – The outer wrap of a cartridge can be either nylon jacket, beaming paper, or PVC-coated screen wrap. Actual cartridges may not look exactly like those shown in photo.
17 Parker Hannifi n CorporationVelcon Filtration Division
Colorado Springs, CO 80907 USA
Velcon Filtration DivisionFilter Vessel Installation & Operation Manual
VEL2199 0414
Model Dim.Nominal Micron Rating
Protec-tive Outer
Wrap
FO-412PL2 4” x 12¼”x 1¾” ID
2 No
FO-412PL5 5 No
FO-418PL5 4” x 18”x 1¾” ID
5 No
FO-418PL15 15 No
FO-512PL1/2For VF-61 Housing
½ No
FO-512PL05 5 No
FO-512PL25 25 No
FO-614PLF½
6” x 14½”x 3½” ID
½ No
FO-614PLF1 1 No
FO-614PLF2 2 No
FO-614PLF5 5 No
FO-614PLF5M 5 Yes
FO-614PLF10 10 No
FO-614PLF15 15 No
FO-614PLF15M 15 Yes
FO-614PLF25 25 No
FO-614PLF25M 25 Yes
FO-614PLF75 75 No
FO-629PLF1/4
6” x 29”x 3½” ID
¼ Yes
FO-629PLF1/2 ½ Yes
FO-629PLF1 1 Yes
FO-629PLF2 2 Yes
FO-629PLF5 5 Yes
FO-629PLF10 10 Yes
FO-629PLF20 20 Yes
FO-629PLF25 25 Yes
FO-629PLF1/2TB
6” x 29”Threaded Base
½ Yes
FO-629PLF1TB 1 Yes
FO-629PLF2TB 2 Yes
FO-629PLF5TB 5 Yes
FO-629PLF25TB 25 Yes
FO-644PLF1/2
6” x 44”x 3½” ID
½ No
FO-644PLF1M 1 Yes
FO-644PLF2M 2 Yes
FO-644PLF5M 5 Yes
FO-644PLF10M 10 Yes
FO-644PLF15M 15 Yes
FO-644PLF25M 25 Yes
Model Dim.Nominal Micron Rating
Protec-tive Outer
Wrap
FO-644PLF1/4TB
6” x 44”Threaded
Base
¼ Yes
FO-644PLF1/2TB ½ Yes
FO-644PLF1TB 1 Yes
FO-644PLF2TB 2 Yes
FO-644PLF5TB 5 Yes
FO-644PLF10TB 10 Yes
FO-644PLF25TB 25 Yes
FO-656PLF1M 6” x 56” x 3½” ID 1 Yes
FO-656PLF1/2TB
6” x 56”Threaded
Base
½ Yes
FO-656PLF1TB 1 Yes
FO-656PLF2TB 2 Yes
FO-656PLF5TB 5 Yes
FO-656PLF25TB 25 Yes
FO-718PLP3
6¼” x 18” x 2 9∕16” ID
0.3 No
FO-718PL1/2 ½ No
FO-718PL01 1 Yes
FO-718PL02 2 Yes
FO-718PL05 5 Yes
FO-718PL10 10 Yes
FO-718PL15 15 Yes
FO-718PL25 25 Yes
FO-718PL50 50 Yes
FO-736PLP36¼” x 36”
2 9∕16” ID
0.3 No
FO-736PL1/2 ½ No
FO-736PL05 5 Yes
FO-736PL15 15 Yes
FO-822PLP3
8” x 22 1∕8” x 2” ID
0.3 No
FO-822PL1/2 ½ No
FO-822PL05 5 No
FO-829PL05 8” x 29 ½” 2” ID 5 No
FOH
FOH-644PLF1 6” x 44” x 3½” ID 1 Yes
FOH-644PLF1/2 6” x 44” x 3½” ID 0.5 Yes
FOH-644PLF1TB 6” x 44”Threaded Base
1 Yes
FOH-644PLF2TB 2 Yes
FOH-644PLF5 6” x 44” x 3½” ID 5 Yes
CARTRIDGE INFORMATION
The following table lists a few of the broad range of available Velcon cartridges. Your local Velcon representative can provide more complete information.
18 Parker Hannifi n CorporationVelcon Filtration Division
Colorado Springs, CO 80907 USA
Velcon Filtration DivisionFilter Vessel Installation & Operation Manual
VEL2199 0414
F0-6xxA3 & FOH-6xxA1EI 1590 Qualifi ed Filter Cartridges. 1 and 3 Micron Rated Cartridges for Aviation Fuel
Description
Primarily designed to be used as prefilter (micronic) cartridges for use in jet fuel handling systems.
Used to extend the life of coalescer cartridges in filter/separator vessels described in EI 1581.
Velcon has qualified cellulose and microfiberglass media filter cartridges to EI Specification 1590, “Specifications and Qualification Procedures for Aviation Fuel Microfilters.”
Product Features:
Large Surface Area – Allows high flow rate with low initial pressure drop and maximum contaminant holding capacity.
Resin Impregnated Microfiberglass/Cellulose Media – Maintains strength, resists effects of water and heat.
75 psi Collapse Strength – Heavy gauge carbon steel endcaps and center tube give safety margin against pressure surges.
Coated Steel Components – Resist corrosion from most industrial fluids.
Corrugated Media – Prevents pleat pinch-off, assuring all filtration media is utilized.
Buna-N Gaskets – The best general gasket material available assures positive seal in most fluids.
Epoxy Bonding Material – Endcaps epoxy-bonded to media to prevent internal bypassing.
Threaded Base also available
FOH-644A1KFO-614A3
19 Parker Hannifi n CorporationVelcon Filtration Division
Colorado Springs, CO 80907 USA
Velcon Filtration DivisionFilter Vessel Installation & Operation Manual
VEL2199 0414
SPECIFICATIONS
75 psi Collapse strength
1 & 3 micron efficiency (per EI 1590)
5 - 9 Operating pH range
250°F Maximum operating temperature
CARTRIDGE INFORMATION
VELCON MODEL NUMBER DIMENSIONS
OUTER WRAP
API MICRONEFFICIENCY
MAXIMUM FLOW RATE
FO-614A3 6” x 141/2” x 31/2” ID NO 3 53
FO-614A3TB 6” x 141/2” x 31/2” ID NO 3 47
FO-629A3 6” x 29” x 31/2” ID YES 3 111
FO-629A3TB 6” x 29” x 31/2” ID YES 3 105
FO-644A3 6” x 44” x 31/2” ID YES 3 171
FO-644A3TB 6” x 44” x 31/2” ID YES 3 165
FO-656A3 6” x 56” x 31/2” ID YES 3 219
FO-656A3TB 6” x 56” x 31/2” ID YES 3 213
FOH-614A1K 6” x 141/2” x 31/2” ID YES 1 53
FOH-614A1TB 6” x 141/2” x 31/2” ID YES 1 47
FOH-629A1K 6” x 29” x 31/2” ID YES 1 111
FOH-629A1TB 6” x 29” x 31/2” ID YES 1 105
FOH-644A1K 6” x 44” x 31/2” ID YES 1 171
FOH-644A1TB 6” x 44” x 31/2” ID YES 1 165
FOH-656A1K 6” x 56” x 31/2” ID YES 1 219
FOH-656A1TB 6” x 56” x 31/2” ID YES 1 213
Please see Data Sheet #1936 for more information about the FOH Series Cartridges.
20 Parker Hannifi n CorporationVelcon Filtration Division
Colorado Springs, CO 80907 USA
Velcon Filtration DivisionFilter Vessel Installation & Operation Manual
VEL2199 0414
STANDARD DESIGN FEATURES
150 psi welded steel ASME Code construction.
Choice of micron rating from 0.5 to 75 microns.
Choice of pleated or depth type media.
Epoxy coated interior, primed exterior.
Buna-N O-ring cover seals.
RECOMMENDED OPTIONAL ACCESSORIES
Automatic Air Eliminator
Pressure Relief Valve
Differential Pressure Gauge
Drain Valve(s)
Sampling Probes
ASME Code Stamp
VF SeriesVertical Filter Vessels
DESCRIPTION
Consult our cartridge data sheets to select the micron rating and type of cartridge that is right for your application – PLF Series (pleated sur-face type filtration), FG Series (fi-berglass depth type filtration), or Aquacon® Series (dehydration and filtration).
Filter vessels VF814 through VF844, such as the VF814150 shown at right, have through-bolt covers, NPT connections, and include fittings for drain, pressure gauge and air vent.
VF1614 and larger vessels, such as the VF2044150 shown at top right, are provided with swing bolt closure, RF flange connections and fittings for pressure gauge, air eliminator, pressure relief valve and drain valve.
Note: In applications where increased dirt contamination is present, it may be desirable to oversize filtration equipment. Contact Velcon for oversizing recommenda-tions. For API/EI applications, please consult Velcon
APPLICATION
• Jet Fuel
• Diesel Fuel
• Gasoline
VF814150VF2044150
21 Parker Hannifi n CorporationVelcon Filtration Division
Colorado Springs, CO 80907 USA
Velcon Filtration DivisionFilter Vessel Installation & Operation Manual
VEL2199 0414
Ves
sel
Mo
del
N
um
ber
Maximum FlowUSGPM
FO Series
Fig
. No
.
Dimensions in Inches
Wei
gh
t w
ith
S
kid
, lb
s.
Volu
me
U.S
.G
allo
ns
Jet
Fu
el
Gas
olin
e
Die
sel
Len
gth
Qty
.
A B C D E F G H I J K
VF814 67 68 65 14 1 2 85⁄8 3 24¾ 26¾ 39 2 13 103⁄8 6½ - - 225 5
VF829 133 136 130 29 1 2 85⁄8 3 39 411⁄8 68 2 13 103⁄8 6½ - - 265 8
VF844 200 204 195 44 1 2 85⁄8 3 571⁄16 597⁄16 101 2 13 103⁄8 6½ - - 305 11
VF1614 267 272 260 14 4 1 16 15 3713⁄16 4013⁄16 52 4 24¼ 9 75⁄8 75⁄8 187⁄16 500 22
VF1629 533 544 520 29 4 1 16 15 5213⁄16 5513⁄16 82 4 24¼ 9 75⁄8 75⁄8 187⁄16 560 35
VF1644 800 816 780 44 4 1 16 15 66¾ 69¾ 110 4 24¼ 9 75⁄8 75⁄8 187⁄16 620 48
VF2029 800 816 780 29 6 1 20 19½ 601⁄8 655⁄8 89 6 28 13 7½ 7½ 26 1000 67
VF2044 1200 1224 1170 44 6 1 20 19½ 745⁄8 807⁄16 118 6 28 13 7½ 7½ 26 1100 88
VF2829 1600 1632 1560 29 12 1 28 24 48½ 64¼ 77 8 36 18 9 9 35 1500 125
VF2844 2400 2448 2340 44 12 1 28 24 643⁄8 79¾ 108 8 36 18 9 9 35 1600 165
VF3644 3600 3672 3510 44 18 1 365⁄8 26 633⁄8 84 109 10 48 23 12½ 12½ 44 2250 288
VF4244 5400 5508 5265 44 27 1 42¾ 28 66 873⁄8 110 12 54 28 13 13 52¼ 3800 400
1. Flow rates are for FO-614PLF series pleated paper cartridges. For higher viscosity fluids, consult your Velcon Representative.
2. VF Series Filters are designed to accommodate our standard 6 in. O.D., 31/2 in. I.D., 141/2 in. long cartridges that are stacked one, two, or three high. Many cartridges are available in longer lengths that eliminate stacking. For example, a 44 inch long FO-644PLF1M could be used in place of three 141/2 inch long cartridges. This makes for easier and less expensive changeouts.
3. A number of threaded base filter cartridges (e.g. FO-644PLF5TB) are available, which allow for easier cartridge changeout and removal of particulate matter from the deckplates. See data sheet #1549. The threaded base cartridges mount on the 6000T Adapters.
4. Dimensions shown are for estimating purposes only. For exact dimensions, obtain certified drawing.
5. VF16 and VF20 Series vessels have flat covers. VF16 Series vessels do not have hydraulic lift jacks.
6. Available Aquacon® Cartridges are AC-6xx05 and AD-6xx25 where xx represents cartridge lengths of 14, 29, and 44 inches.
Figure 1 Figure 2
22 Parker Hannifi n CorporationVelcon Filtration Division
Colorado Springs, CO 80907 USA
Velcon Filtration DivisionFilter Vessel Installation & Operation Manual
VEL2199 0414
NOTES
23 Parker Hannifi n CorporationVelcon Filtration Division
Colorado Springs, CO 80907 USA
Velcon Filtration DivisionFilter Vessel Installation & Operation Manual
VEL2199 0414
NOTES
North AmericaCompressed Air TreatmentFiltration & Separation/BalstonHaverhill, MA978 858 0505www.parker.com/balston
Finite Airtek Filtration Airtek/domnick hunter/ZanderLancaster, NY716 686 6400www.parker.com/faf
Finite Airtek Filtration/FiniteOxford, MI248 628 6400www.parker.com/fi nitefi lter
Engine Filtration & Water Purifi cationRacor Modesto, CA209 521 7860www.parker.com/racor
Holly Springs, MS662 252 2656www.parker.com/racor
Beaufort, SC843 846 3200www.parker.com/racor
Racor – Village Marine Tec.Gardena, CA310 516 9911desalination.parker.com
Parker Sea RecoveryCarson, CA310 637 3400www.searecovery.com
Hydraulic FiltrationHydraulic FilterMetamora, OH419 644 4311www.parker.com/hydraulicfi lter
Laval, QC Canada450 629 9594www.parkerfarr.com
Process Filtration domnick hunter Process FiltrationOxnard, CA805 604 3400www.parker.com/processfi ltration
Madison, WI608 824 0500www.scilog.com
Phoenixville, PA610 933 1600www.parker.com/processfi ltration
Aerospace FiltrationVelcon FiltrationColorado Springs, CO719 531 5855www.velcon.com
EuropeCompressed Air Treatmentdomnick hunter Filtration & Separation Gateshead, England+44 (0) 191 402 9000 www.parker.com/dhfns
Parker Gas SeparationsEtten-Leur, Netherlands+31 76 508 5300www.parker.com/dhfns
Hiross Zander Padova Business UnitPadova, Italy+39 049 9712 111www.parker.com/hzd
Hiross ZanderEssen Business UnitEssen, Germany+49 2054 9340www.parker.com/hzd
Engine Filtration & Water Purifi cationRacor Dewsbury, England+44 (0) 1924 487 000 www.parker.com/rfde
Racor Research & DevelopmentStuttgart, Germany+49 (0)711 7071 290-10www.parker.com/rfde
Hydraulic FiltrationHydraulic Filter Arnhem, Holland+31 26 3760376www.parker.com/hfde
Urjala Operation Urjala, Finland+358 20 753 2500www.parker.com/hfde
Condition Monitoring CentreNorfolk, England +44 (0) 1842 763 299www.parker.com/hfde
Parker KittiwakeWest Sussex, England+44 (0) 1903 731 470 www.kittiwake.com
Parker ProcalPeterborough, England+44 (0) 1733 232 495 www.kittiwake.com
Process Filtration domnick hunter Process FiltrationBirtley, England+44 (0) 191 410 5121www.parker.com/processfi ltration
Parker Twin Filter BVZaandam, Netherlands+31(0)75 655 50 00www.twinfi lter.com
Asia Pacifi cAustralia Castle Hill, Australia+61 2 9634 7777www.parker.com/australia
China Shanghai, China+86 21 5031 2525www.parker.com/china
IndiaNavi Mumbai, India+91 22 651 370 8185www.parker.com/india
Parker FowlerBangalore, India+91 80 2783 6794www.johnfowlerindia.com
Japan Tokyo, Japan+81 45 870 1522www.parker.com/japan
Parker TechnoOsaka, Japan+81 66 340 1600www.techno.taiyo-ltd.co.jp
Korea Hwaseon-City+82 31 359 0852www.parker.com/korea
SingaporeJurong Town, Singapore+65 6887 6300www.parker.com/singapore
Thailand Bangkok, Thailand+66 2186 7000www.parker.com/thailand
Latin AmericaParker Comercio Ltda. Filtration Division Sao Paulo, Brazil+55 12 4009 3500www.parker.com/br
Pan American Division Miami, FL305 470 8800www.parker.com/panam
AfricaAeroport Kempton Park, South Africa+27 11 9610700www.parker.com/africa
Parker Hannifi n CorporationVelcon Filtration Division
1210 Garden of the Gods RoadColorado Springs, CO 80907phone 719 531 5855www.parker.com
© 2014 Parker Hannifi n Corporation. Product names are trademarks or registered trademarks of their respective companies. VEL2162 02/14
Worldwide Filtration Manufacturing Locations