    Technical Brochure

    Brochure SPEM 1 A GB 97-09

    Low Voltage Apparatus

    ABB Control Oy

    Motor Protection RelaySPEM

  • 8/3/2019 SPEM 1A GB 97-09

    2/122 ABB Control Oy

    Motor Protection Relay SPEM

    1) In the following cases please contact the manufacturer:- Frequency Converters- Star-Delta Starters- Soft Starters- Power Factor Correction Banks (PFC)

    ApplicationsThe SPEM relay is the ideal answer to problems requiringmore versatile or accurate protection for a motor than canbe offered by a standard thermal overload relay.SPEM relays can be used for protecting low voltagesquirrel cage (AC) motors 1).

    Use of SPEM motor protection relay:- helps in extending life time of motor- helps in optimizing motor size- helps in planning maintenance work- protects the drive from mechanical damage

    TCM - Thermal Capacity Memory

    The SPEM relay is based on microprosessor techniqueswith a built in logic supervising thermal behaviour of motor.

    The thermal capacity memory monitors the motor currentand continuously compares the data to the known thermalrecord of the motor, and operates when the thermal limit ofthe motor is exceeded.

    The microprosessor based construction ensures long timestability, high accuracy and disturbance free operation.

    The compact size enables installation in cramped places.

    Protection

    SPEM offers protection in the following ways: Thermal Overload Protection with complete

    Thermal Capacity Memory (TCM) Start-up Current Protection Under Current Protection Unbalance Protection

    - phase unbalance- phase failure- incorrect phase sequence

    Earth Fault Protection Self Supervision Fail Safe Operation

    In designing the SPEM motor protection relay the principle aim has not onlybeen to fully protect the motor, but also to reduce down time to a minimum.

    S00789A

    S00790A

    EMC-testedTested according to EMC-directive No: 89/336/EEC.

  • 8/3/2019 SPEM 1A GB 97-09

    3/12ABB Control Oy 3

    Thermal Overload Protection

    Provides reliable protection formotor starting as well as for heavyand repeated starting.

    1s3 421

    I / I ~5 6

    10s

    5s

    3s2s

    40s30s20s

    1min

    2min

    3min

    5min

    10min

    20min

    30min

    1h

    2h

    3htime

    0

    1.05s

    t6x

    5s

    2s

    30s20s

    10s

    S00782A

    Thermal tripping characteristics:

    1s3 421

    I / I ~5 6

    10s

    5s

    3s2s

    40s30s20s

    1min

    2min

    3min

    5min

    10min

    20min

    30min

    1h

    2h

    3htime

    0

    1.05

    t6x

    5s

    2s

    30s

    20s

    10s

    S00783A

    Without prior load (Cold curve)

    Cooling time-constant = 4 x the heatingtime-constant.

    With prior load 0.9 x I

    (Hot curve)

    100% Tripping

    Thermalcapacity

    1)2)

    3)

    S00793A

    The microprosessor is continuously calculating thethermal capacity available in the motor:

    1) starting2) overloading3) stand still (even after tripping)

    Tripping takes place, when the thermal capacity ofmotor is exceeded i.e. motor current is higher than1.05 x full load current I

    . Refer to the thermal

    tripping characteristics below.

    I

    tS00792A

  • 8/3/2019 SPEM 1A GB 97-09

    4/124 ABB Control Oy

    S00781A

    Start-Up Current Protection

    The relay trips if the thermalcapacity of motor is exceededduring starting. The tripping curveis defined by the preset maximumstarting time (t

    6time). In the hot

    state SPEMs TCM takes intoaccount also the thermal historyof the motor during starting.

    The maximum motor starting times are available fromthe motor manufacturers. If the preset maximumstarting time exceeds 1.7 x the real motor starting time,SPEM allows two starts in the cold state and one in thehot state.

    Thermalcapacity

    Restart inhibit

    t

    100%

    40%

    S00794A

    After tripping, if there is less than 60 % ofmotor capacity available, SPEM does notallow a new start until the motor cools down(restart inhibit). In this case, a new start ispossible approximately after 30 s.

    Unbalance Protection

    Provides protection against:1. Phase unbalance2. Phase failure3. Incorrect phase sequence

    Under Current ProtectionProvides protection against asudden loss of loads e.g.

    Dry running pumps Broken conveyer belts

    This feature can be selected by means of switch S2(I OFF/ON) on the front panel of the SPEM relay(see page 6).

    % Full load current

    55

    100

    90

    80

    70

    60

    50

    40

    30

    2010

    0

    12

    S00786A

    Typical off load currentfor large and mediumsized motors.

    S00797A

    Tripping is activated if the currentstays between 12...55 % of fullload current (I

    ) longer than 10 s.

  • 8/3/2019 SPEM 1A GB 97-09

    5/12ABB Control Oy 5

    Earth Fault Protection(SPEM40_ and SPEM50_ types)

    Provides an indication of a defect

    in motor winding. Motor canremain in operation if necessaryfrom process point of view.

    The maintenance of the motor canbe postponed to an appropriatetime.

    A

    S00788A

    Unbalance percentage

    (%)

    t(s)

    00 10 20 30 40 50

    10

    20

    30S00796AIn case of complete phase failure or incorrect

    phase sequence, the tripping time is 6 s.Otherwise according to the curve shown.

    By means of switch S3 (I0

    / TRIP) on the front panelof SPEM, it is possible to select either tripping andsignalling or only signalling in case of earth faultfailure.

    If only signalling is selected, there will be no tripping ofthe SPEM relay but the signalling contact (9-10) of therelay operates.

    In case a tripping function is selected and the SPEMrelay has tripped, it will be automatically reset after200 ms when automatic reset is selected from switchS1 (Reset A/M).

    Time lag 1 second for eliminating short time failures.

    The tripping level for the earth fault current can be setwith the potentiometer I

    0/I

    non the front panel of the

    SPEM relay.

    Self SupervisionThe functions of the electronic circuits are continuouslysupervised by means of a hardware watchdog.

    In case of an internal fault, contact 9-10 closes givingan alarm and contact 11 - 12 remains in its positionkeeping the motor circuit closed, and enablingcontinuation of the process.

    Fail Safe OperationIn case of loss of external auxiliary voltage, the motorprotection relay trips and can be taken into operationafter reconnection of the auxiliary voltage.

    After reconnection of auxiliary voltage supply, theSPEM considers the situation as 75 % of the thermalcapacity of motor would have been used.

    Every time when the auxiliary voltage will beconnected, contact 9 - 10 closes for a short period oftime (10 ms) giving an OK signal e.g. to PLC.

    The time-lag of the unbalance/singlephasing unit.

  • 8/3/2019 SPEM 1A GB 97-09

    6/126 ABB Control Oy

    Presetting

    t6

    time

    Adjustability from 2 s to 30 s. Informationfrom motor manufactures.

    Switches S1...S8

    S1Automatic or manual resettingThe SPEM is always automatically reset, whentripping takes place caused by thermal overload orstart-up current protection. Otherwise either manualor automatic resetting.Manual resetting by operating S1 from manualposition to automatic position and back to manualposition.

    S2Undercurrent protection OFF/ONWhether underload protection is required or not

    S3Alarm/trip from earth faultSelection of alarm or tripping and alarm.

    S4...S8Full load current (I

    ) preset.Operation of dipswitches to ON-position by movingto the right.

    Selectable from 60 % up to 122 % with accuracy of 1 %.

    Steps are: 60 % (fixed)32 %16 %

    8 %4 %2 %

    Earth fault

    (SPEM40_ and SPEM50_ types).Adjustability from 20 % to 60 % of ratedzero sequence (SPEM40_) or residual(SPEM50_) current.See table on the page 8.

    SPEM

    12

    11OK

    I

    I~

    Reset A/M

    I< OFF / ON

    Io / Trip

    2

    4

    8

    16

    32

    I =+60

    [% In]

    t x (s)

    I /I

    0~

    0n0

    0

    610 20

    2 30

    0.3

    0.4

    0.2 0.6

    MADE IN FINLAND

    0.5

    MOTOR PROTECTION RELAY

    Setting of full load current preset in percentage (I

    %) andadjustement of current transfomers.

    The functions (except earth fault protection) arebased on full load current, which is the maximumallowed continuous on load current of the motor. Thepresets, in percent, can be calculated from thefollowing formula:

    II

    % = x 100%ICT

    I

    % = full load current preset in percentageI

    = maximum allowed continous onload current = full load current

    ICT

    = rated primary current of current transformer

    Example:ABB motor M2BA 315 SMC 4B3

    Pn

    = 160 kW, In

    = 282 A,400 V used with 5 % overload allowedby themanufacturerFull load current:

    I = 282 A x 1.05 = 296 ASPEM type selected from the table on page 9SPEM40B310 (with earth fault protection)

    setting value:296 A

    I

    = x 100% = 95 %310 A

    Select switches S8 and S4. Fixed 60% no need toselect.(60 + 32 + 2) % = 94 % < 95 %The t

    6time for the motor:

    M2BA 315 SMC 4B3 is 15 s

    (information from motor manufacturer)

  • 8/3/2019 SPEM 1A GB 97-09

    7/12ABB Control Oy 7

    When the relay is reset (manually or automatically),the OK LED lights again. Failure indications go out,when the motor is restarted.

    Indicates when relay permits starting(steady yellow light)

    Front Panel Indicators

    Failure indications:When there is a failure, the relay trips and the yellowOK LED goes out and the correspondant red LEDfailure indication shows.

    Tripping caused by:

    Thermal overload, start-up current Steady red light on the middle LED Always automatically reset The tripped indication cancels when the motor

    is restarted

    Phase unbalance Irregular red flash of the middle LED Automatic or manual reset The tripped indication cancels when the motor

    is restarted

    Under current Steady red flash of the middle LED Automatic or manual reset The tripped indication cancels when the motor

    is restartedEarth fault

    Steady red light on the lower LED Automatic or manual reset The earth fault indication cancels when the motor is

    restarted or if the fault disappears

    SPEM

    12

    11OK

    I

    I~

    Reset A/M

    I< OFF / ON

    Io / Trip

    2

    4

    8

    16

    32

    I =+60

    [% In]

    t x (s)

    I /I

    0~

    0n0

    0

    610 20

    2 30

    0.3

    0.4

    0.2 0.6

    MADE IN FINLAND

    0.5

    MOTOR PROTECTION RELAY

    SPEM function chartPROTECTION PRESETTING INDICATION FUNCTION RESETTING

    Tripping Alarm Automatic Manual

    THERMAL I

    % S4...S8 Steady Middle

    OVERLOAD light LED x x x -

    - overload Upper

    - start-up current t6/ s potentiom.

    UNDER CURRENT OFF/ON S2 Steady Middle x x x x

    I

    % (S4...S8) flash LED

    UNBALANCE I

    % (S4...S8) Irregular Middle x x x x

    flash LED

    - phase interrupt

    - single phase

    - incorrect phase

    sequence

    EARTH FAULT I0/ I

    nLower Steady Lower

    % potentiom. light LED

    Alarm S3 - x - x

    Trip S3 x x x x

    SELFSUPERVISION - - - - - x Self Self

    Internal fault resetting resetting

    FAIL SAFE Upper

    OPERATION - - "OK" OFF LED x - - -

    Failure of

    auxiliary voltage

  • 8/3/2019 SPEM 1A GB 97-09

    8/12

  • 8/3/2019 SPEM 1A GB 97-09

    9/12ABB Control Oy 9

    Motor Protection Relay SPEMOrdering Information

    Supply voltage 110 V 50...60 Hz. Current transformer included.

    Type Rated Rated current Maximum Earth fault protection Orderingcurrent I

    nrange I

    nsetting Rated zero Rated residual Number

    [A][A] of I

    /[%] sequence current

    current I0n/[A] I

    0n/[A]

    SPEM30C060 60 4.5...63 106 - -

    SPEM30C105 105 63...111 106 - -

    SPEM30C185 185 111...186 102 - -

    SPEM30C310 310 186...310 100 - -

    SPEM30C400 400 240...400 100 - -

    SPEM30C500 500 300...500 100 - -

    SPEM40C060 60 4.5...63 106 60 -

    SPEM40C105 105 63...111 106 105 -

    SPEM40C185 185 111...186 102 185 -

    SPEM40C310 310 186...310 100 310 -

    SPEM40C400 400 240...400 100 400 -

    SPEM40C500 500 300...500 100 500 -

    SPEM50C060 60 4.5...63 106 - 1

    SPEM50C105 105 63...111 106 - 1

    SPEM50C185 185 111...186 102 - 1

    SPEM50C310 310 186...310 100 - 1

    SPEM50C400 400 240...400 100 - 1

    SPEM50C500 500 300...500 100 - 1

    Motor Protection Relays SPEM

    Supply voltage 230 V 50...60 Hz. Current transformer included.

    Type Rated Rated current Maximum Earth fault protection Orderingcurrent I

    nrange I

    nsetting Rated zero Rated residual Number

    [A][A] of I

    /[%] sequence current

    current I0n/[A] I

    0n/[A]

    SPEM30B060 60 4.5...63 106 - -

    SPEM30B105 105 63...111 106 - -

    SPEM30B185 185 111...186 102 - -

    SPEM30B310 310 186...310 100 - -

    SPEM30B400 400 240...400 100 - -

    SPEM30B500 500 300...500 100 - -

    SPEM40B060 60 4.5...63 106 60 -

    SPEM40B105 105 63...111 106 105 -

    SPEM40B185 185 111...186 102 185 -

    SPEM40B310 310 186...310 100 310 -

    SPEM40B400 400 240...400 100 400 -

    SPEM40B500 500 300...500 100 500 -

    SPEM50B060 60 4.5...63 106 - 1

    SPEM50B105 105 63...111 106 - 1

    SPEM50B185 185 111...186 102 - 1

    SPEM50B310 310 186...310 100 - 1

    SPEM50B400 400 240...400 100 - 1

    SPEM50B500 500 300...500 100 - 1

    S00789A

    S00790A

    The connection cable between SPEM and current transformer can be shortened but not madelonger. Cable length appr. 75 cm.

    1SCA022388R3210

    1SCA022388R5090

    1SCA022388R5170

    1SCA022388R5250

    1SCA022388R5330

    1SCA022388R5410

    1SCA022388R6140

    1SCA022388R6220

    1SCA022388R6310

    1SCA022388R6490

    1SCA022388R6570

    1SCA022388R6650

    1SCA022388R6730

    1SCA022388R6810

    1SCA022388R6900

    1SCA022388R7030

    1SCA022388R7110

    1SCA022388R7200

    1SCA022388R5500

    1SCA022388R5680

    1SCA022388R5760

    1SCA022388R5840

    1SCA022388R5920

    1SCA022388R6060

    1SCA022388R7380

    1SCA022388R7460

    1SCA022388R7540

    1SCA022388R7620

    1SCA022388R7710

    1SCA022388R7890

    1SCA022388R7970

    1SCA022388R8010

    1SCA022388R8190

    1SCA022388R8270

    1SCA022388R8350

    1SCA022388R8430

  • 8/3/2019 SPEM 1A GB 97-09

    10/1210 ABB Control Oy

    Motor Protection Relays SPEMConnection Diagrams

    Primary windings for lower rated currents

    Only for types SPEM_060

    Current range In

    Turns around Max. setting[A] current transformer of I

    /[%]

    [turns]

    4.5 ... 7.5 8 100

    7.2 ... 12.0 5 100

    12.0 ... 20.0 3 100

    18.0 ... 36.0 2 120

    36.0 ... 63.6 1 106

    1pc 2pc 3pc

    S00787A

  • 8/3/2019 SPEM 1A GB 97-09

    11/12ABB Control Oy 11

    Motor Protection Relays SPEMConnection Diagrams

    Connection diagram with a separate residual current transformer

    Direct On Line Starters

    F1

    1

    2

    L1

    F2

    3

    4

    L2

    F3

    5

    6

    L3

    K1

    M

    3 ~

    M1U1

    V1

    W1

    V2

    U2 W2

    7

    8

    9

    101

    1

    12

    SPEM

    TRIP

    SIGNAL

    UauxA

    B

    C

    DE

    F

    T1

    T2

    T3

    S1

    S2S1

    S2

    S1

    S2

    F4

    L1

    21

    22

    S1

    O

    13

    14

    A1

    A2K1

    13

    14

    I K1

    S2

    N

    S00785A

    H2H1 1

    2

    1

    2

    F1

    1

    2

    L1

    F2

    3

    4

    L2

    F3

    5

    6

    L3

    K1

    M3 ~

    M1U1

    V1

    W1

    V2

    U2 W2

    7

    8

    9

    10

    11

    12

    SPEM

    TRIP

    SIGNAL

    Uaux

    T1

    T2

    T3

    S1

    S2S1

    S2

    S1

    S2

    F4

    L1

    21

    22

    S1

    O

    13

    14

    A1

    A2K1

    13

    14

    I K1

    S2

    N

    H1 H21 1

    2 2

    S00784A

    A

    B

    C

    D

    E

    F

  • 8/3/2019 SPEM 1A GB 97-09

    12/12

    SYSTEM

    QUALITY

    CERTIFIEDSFS

    ISO 9001

    CERT

    IFIED

    ENVIR

    ONMENTA

    LSYSTEM

    SFSISO 14001

    ISO 9001

    ABB Control OyP.O. Box 622FIN - 65101 VAASA

    Finland

    Tel +358 10 22 4000Fax +358 10 22 45708

    Motor Protection Relays SPEMDimensionDrawings

    SPEM _60...400 SPEM_500

    82 82

    245

    82

    42

    203

    111

    44

    22

    6080

    100

    O7

    SPEM

    12

    11

    OK

    I I

    ~

    ResetA/M

    I