spega e.control catalogue 2014

104
e.control™ Room automation catalogue 2014/2015

Upload: spega-spelsberg-gebaudeautomation-gmbh-co-kg

Post on 26-Mar-2016

220 views

Category:

Documents


3 download

DESCRIPTION

spega product catalogue for e.control room automation system

TRANSCRIPT

Page 1: spega e.control catalogue 2014

e.control™

Room automation

catalogue 2014/2015

Page 2: spega e.control catalogue 2014
Page 3: spega e.control catalogue 2014

3

Dear spega and Delta Dore partner,

In your hands is our current catalogue for room automation. It underscores our goal to be your preferred solution provider for the automation of ALL systems in ALL rooms for ALL building types!

Although we have already established ourselves in the past as a leading manufacturer of highly energy-efficiency, highly flexible and highly integrated room automation systems for office and administration buildings with e.control, we are now expanding our offering with the new clima DL-110 universal controller series to provide sys-tem-specific solutions for room temperature and climate control. Together with our new Web-based device configuration tools and automatic BACnet integration, we can now offer you everything from one-room controllers to fully integrated solutions for the Green Building, probably the most extensive room automation line on the market.

We have this new capability not least thanks to the fact that, since the start of 2013, we are a part of the Delta Dore Group, a Breton family company with 800 employees and more than 40 years of competence in the development and production of elec-tric controllers and regulators for customers in technical building equipment. For example, every year more than 4 million electronic devices and components leave the production plant in Bonnemain, where spega devices are also produced. High produc-tion quality and reliable delivery are the positive consequences.

How e.control supports your goals, how it works and how it’s built, is yours for the discovery in this catalogue.

In the first section of the catalogue, we inform you about the functionality of e.control: What makes e.control capable of saving energy and how can it also reduce lifecycle costs at the same time? How does e.control support different area usage without cable mess, and how does e.control support the Green Building certification according to LEED or DGNB? We look closer at the technology to explain which sub-bus technologies are supported by e.control and how it integrates into the BACnet and IP worlds. An overview of the most important software functions and their energy efficiency effects round out the section.

The second section is the actual product catalogue, summarizing all the important information about the devices of the e.control system. The associated technical data sheets, application programs and parameterization software can be found on the e.control CD or on the Internet at www.spega.com/software.

Our whole team of spega and Delta Dore is looking forward to working with you!

Yours, Jan Spelsberg

Page 4: spega e.control catalogue 2014

4

spega, e.homeTM, e.controlTM and FastConTM are trademarks for Spelsberg Gebäudeautomation GmbH.LON, LNS and LonWorks are registered trademarks for Echelon Corporation in the USA and other countries. LonMark and the LonMark Logo are managed, granted, and used by LonMark International under a license granted by Echelon Corporation.

Subject to technical or design change. Please take note of technical data sheets.

Image sources: p.1 Frankonia, p.6-7 S. Vogel, Frankonia, Klocke Verlag, E.ON, Arnoldius, Bayerische Hausbau

Symbols:

Power supply 230V AC (mains voltage)

Power supply 24V DC

Power supply 24V AC/DC

Demo software available*

Plug-in available*

Software application available*

Technical data sheet available*

e.control™

Ethernet (LON/IP, BACnet/IP, etc.)

LON-transceiver FTT10

* on e.control CD or online at www.spega.com/software

catalogue 2014/2015

© 3/2014 by spega - a member of the group Delta Dore

spelsberg gebäudeautomation gmbhzechenstr. 7047443 moersgermany

Page 5: spega e.control catalogue 2014

5

Table of content

Expertise in Building Automation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Increasing energy efficiency, reducing costs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Create flexibility. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Increase performance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 The best recommendation for Green Buildings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Best-in-class as principle. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Functionality without limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Lighting functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Sunblind functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Room climate functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Energy efficiency with e.control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Use in flexible office buildings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Use in fixed rooms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Use in hotel rooms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 Planning with e.control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

Web-based room operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 Universal room control devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 nova Room control devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 Standard 55 Room control panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44 RC series - EnOcean radio sensors and receivers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 Multisensors and presence detectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56 M series - Modular actuator system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60 R series - Modules for distribution boards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68 Room climate controllers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .80 Fire damper actuators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88 Weather sensors and controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90 Automation servers and network infrastructure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94 Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .100

about spega and Delta Dore

e.control system

e.control products

Page 6: spega e.control catalogue 2014

6

spega and Delta Dore – expertise in building automation

Customer benefits is the most important priority for spega‘s development depart-ment. All products need to improve the building‘s sustainability from an ecological, economic and functional point of view.

The unique modular hardware and software concept use simple commissioning tools. Thereby, spega guarantees reliable and eco-nomic solutions.

Leading in room automation Member of a strong group

Focus on customer‘s benefits

Supporting open standards

In 2013 spega joined the Delta Dore group, the French specialist for energy consump-tion control and comfort management in residential (individual or collective), com-mercial and industrial buildings.

Delta Dore‘s home automation offer allows, locally or remotely, to control home equip-ments like heating, lighting, shutters and alarm systems.

Delta Dore also offers reliable and custo-mized solutions for commercial buildings which guarantee energy efficiency and com-fort while simplifying the management of the facilities with the help of a comprehen-sive, modular and easy-to-use BMS system.

In addition Delta Dore developed a deep expertise in energy management and inte-gration of multi-protocol and multi-brand building automation equipment. Tailored services guarantee long-term energy per-formance and continuous improvements to the customers.

Within the Delta Dore group, spega will contribute as the competence center for room automation solutions to expand the leading position of the group in the field of building automation and energy manage-ment services.

spega consciously rely only on open stan-dards from the building automation and IT environment. In this way, e.control com-bines the best-in-class technologies like LON, BACnet, DALI, SMI and EnOcean with the IP world. As an active member in various organizations, spega is committed to the further development of technical standards for the benefit of the customers.

Founded in 2000, spega recognized early the importance of room automation for the energy efficiency, flexibility of use and ergonomics of commercial buildings. These requirements led to the creation of its room automation system e.control. Today the product range is the most comprehensive and functional of its kind.

About the Delta Dore group

800 employees

2 production sites in France

8 subsidiaries around the world

8,000 commercial and industrial sites use Delta Dore’s and spega’s services, management software or automation products

3 million homes are equipped with Delta Dore control products

Page 7: spega e.control catalogue 2014

7

References

Allianz Global Investors, Frankfurt, GermanyAxis-flexible room automation system

Chartis Tower, Paris, FranceBuilding management system with room automation

Federal Administrative Court, St. Gallen, SwitzerlandAxis-flexible room automation system

E.ON Headquarters, Essen, GermanyAxis-flexible room automation system

Fraport Headquarters, Frankfurt, GermanyAxis-flexible room automation system

Les Miroirs Tower, La défense, FranceBuilding management system with room automation

Löwenbräu Red, Zurich, SwitzerlandAxis-flexible room automation system

NEXTOWER (Palais Quartier), Frankfurt, GermanyAxis-flexible room automation system

Postquartier, Stuttgart, GermanyComplete room automation system

Rheinwerk II, Bonn, GermanyAxis-flexible room automation system

Roche ORM Office Replacement, Mannheim, GermanyAxis-flexible lighting and sunblind control system

Singapore Sports Hub, SingaporeBuilding management system with room automation

Süddeutscher Verlag Media Group, Munich, GermanyAxis-flexible lighting and sunblind control system

Stadtwerke Ulm (Building K3), Ulm, GermanyAxis-flexible room automation system

The m.pire Tower, Munich, GermanyAxis-flexible room automation system

ThyssenKrupp Headquarters, Essen, GermanyAxis-flexible room automation system

* BAC efficiency class of the automation system according to EN 15232** Achieved Green Building (pre-)certificate

A

A

A

B

A

A

A

***

A

A

A selection of reference projects

DGNB Silber

DGNB Gold

A DGNB Gold

A LEED Gold

DGNB Gold

LEED Gold

DGNB Gold

LEED Gold

DGNB Gold

ADGNB Gold

A DGNB Gold

Page 8: spega e.control catalogue 2014

8

Increasing energy efficiency, reducing costs

Commercial buildings offer their users not only appropriate working environments, but are also capital investments. Their cost- effective operation with low energy con-sumption makes a significant contribution to the retention of their value. e.control by spega helps.

As a highly functional room automation system, e.control ensures that all rooms use as little energy as possible, without reduc-ing comfort. To do this, it combines heating, air conditioning, ventilation, lighting and sun protection into a perfectly working team that reacts continuously to the current needs of the room and avoids any waste of energy. Heating with the windows open, lighting turned on in an empty room or a room supplied with daylight, are now permanently a thing of the past.

e.control provides added value

Save energy automatically

Top-level energy efficiency

Cost-effectiveness guaranteed

e.control masters energy savings so well that it meets the standards of the highest EN 15232 building automation efficiency class, Class A, for all building types and for all technical equipment variants. Exactly how that works is described on pages 20 through 23. It makes e.control the first and only choice for sustainable buildings.

The fact that energy savings reduce life cycle costs is well-known. How quickly and how reliably that works with e.control will convince you. The amortisation period is only a few years, since in comparison with conventional technological equipment, high savings of up to 35% are achieved with only slight investment.

The advantages

Retention of value by economical building operation

Stops wastes of energy by contin-uous adaptation to requirements

Reduction in energy consumption by up to 35%

Meets the requirements of the highest EN 15232 building auto-mation efficiency class, Class A

Short amortisation time

e.control meets the requirements of the highest EN 15232 efficiency class, Class A

e.controlTM

Page 9: spega e.control catalogue 2014

9

Create flexibility

Flexibility with e.control means being able to adjust area usage quickly and easily by variable division of individual rooms in operation using the graphical software tool – without changing HVAC and electrical installations.

That ensures low investment costs in basic construction and all possible freedom when it comes to design and function in tenant built-out.

Changes to corporate organisation or changes in tenants require adaptability from the building in terms of changed usage and variable room distribution, from individual offices to open space areas. The axially flexible, decentralised, modular structure of the e.control room automation system supports the flexibility needed, to an outstanding degree.

e.control can also be expanded later. Later upgrade to dimmed lighting, the addition of a cooling ceiling, or the installation of an additional control device is possible at any time. This is ensured not least by the variety of open communications standards that are supported by e.control. e.control adapts to your requirements perfectly – whatever you might expect from your building in the future.

e.control supports the change

No fear of the future

Move with the mouse

e.control doesn’t just consist of modular device combinations, but also of object- oriented software function blocks. This permits changes in function and usage to be carried out by Facility Management

The advantages

Investment protection thanks to built-in flexibility

Room divisions can be graphically changed by Facility Management

Elimination of rewiring saves time and money

Support for all open communi- cations standards

Arbitrarily functionally extensible

Graphical room management with e.control Designer

themselves, using the graphical e.control Designer software. Simply by a click of the mouse! Rewiring or opening of raised floors or suspended ceilings are eliminated.

Page 10: spega e.control catalogue 2014

10

Increase performance

Employees are the potential at any com- pany. Their motivation is a requirement for success. e.control helps regulate the daily work environment so employees feel good. In the background, the system ensures not only that the individual temperature settings are maintained, but also provide glare-free work and sufficient lighting – wherever possible with natural sunlight and a view outdoors.

With all this simplification, users still retain full control during their stay in the room. e.control provides an extensive selection of room control devices that communicate either by wire or by radio. Specifically for workplaces in flexible (open plan) office environments, the dialog Web server was designed to provide each and every em- ployee with a virtual room control device in the Web browser of the work PC or IP telephone. That’s not just nice for the user, but also for the DGNB or LEED auditor, who will assign full points for allowing users influence.

e.control ensures comfort Users are in control

Awarded as best automation system

• Exemplary solution for energy saving• Full functionality according to VDI 3813• Integrates all market-relevant sub-buses • Numerous DGNB and LEED references

e.control was honored with the „Building Efficiency Award 2011“ as the best automation system.

The advantages

Optimum room climate increases motivation

Convenient handling makes control easy

Full operability ensures acceptance

Innovative Web server brings the controller to the workstation

Page 11: spega e.control catalogue 2014

11

The best recommendation for Green Buildings

e.control improves the assessment in the leading sustainability certification systems.

Due to its high level of energy efficiency, flexibility and comfort, e.control supports multiple dimensions of sustainable con-struction right out of the box, making it one of the most attractive options available for Green Buildings. Here, sustainability is usually determined using different certifi-cation systems. In particular LEED (Leader-ship in Energy and Environmental Design) from the U.S. Green Building Council and the German Seal of Quality for Sustainable Construction, the DGNB, have been estab-lished. Both procedures evaluate ecological and functional criteria using a scoring system. In addition, DGNB also evaluates cost-effectiveness and especially investi-gates the interests of investors. But how and where does e.control specifically support the Green Building?

The significant reduction in primary energy consumption (according to DIN V 18599 [DGNB] or ASHREA 90.1 [LEED]) using de-mand-based room automation is directly reflected in a reduction of potential hazard-ous waste emission during the usage phase (DGNB criteria 1-5) and in the evaluation of the primary energy consumption itself (DGNB criteria 10-11 and the LEED EA c1). That means that 7 of 12 ecological criteria in the DGNB are optimised simultaneously, or up to 19 points in addition to minimum requirements (EA p2) in LEED.

Since energy savings always mean cost savings as well, life cycle costs (LCC) are also reduced. An e.control system in build-ing automation efficiency class A, for ex-ample, reduces LCC in an office building by over 100 €/m2 in comparison with the same building without room automation (DGNB criterion 16). e.control also increases value stability (DGNB criterion 17) due to its high repurposability (DGNB criterion 28). In con-trast with the DGNB, LEED does not include any evaluation of cost-effectiveness.

In addition to the repurposability already mentioned (DGNB criterion 28), e.control also improves thermal comfort in sum-mer (DGNB criterion 19, LEED IEQ c7) by controlling the sunshade based on the position of the sun, which simultaneously guarantees a high proportion of sunlight, eliminates glare and ensures good visibility (DGNB criterion 22, LEED IEQ c8). The exten-sive e.control line of innovative room op-eration solutions including the Web server also ensures extraordinarily high operating comfort (DGNB criterion 23, LEED IEQ c6).

Supports sustainable construction Cost-effectiveness

Ecological quality

Functionality

The advantages

Optimum design for the require-ments of Green Buildings

Significant optimisation point requiring little investment

Reduction in environmental effects

Significant reduction in lifecycle costs

Higher functionality and increased motivation

Page 12: spega e.control catalogue 2014

12

Best-in-class as principle

That’s also true for the e.control room auto-mation system. This includes the optimum integration of field devices and connection to other building automation equipment, such as management or automation stations, using suitable communications protocols. e.control is specifically designed to use the best technologies in the right places, that is, best-in-class as a design principle. It makes integration so seamless that transparent access down into the field level is consistently provided.

BACnet

LON

EnOcean

DALI

SMI

Only the best is good enough

MP-Bus

As a protocol between the management and the automation levels, BACnet/IP can now be considered a standard. So e.control has BACnet floor servers that automatically group all necessary data and management objects (such as time programs or trends) and provide them by room. That makes the integration of e.control into the manage-ment level child’s play.

LON is the most powerful technology for large control networks with many hundreds or even thousands of devices, such as for room automation. With its high perfor-mance, the unique concept of functional

DALI is the standard for the control of lighting. The advantage, aside from the option of variable group assignment, is also the provision of error responses if a light or ballast should fail. e.control DALI actuators can each control up to 128 lamps in up to 32 groups.

SMI is the counterpart of DALI in sunblind technology. Here, too, groups and error detection are supported. The drives can also be positioned with absolute accuracy and are nearly inaudibly quiet in alternating operation, which makes them a natural for energy-efficient slat tracking control. The e.control SMI actuators, available in 230V or 24V variants, can control up to 32 drives with free group assignment.

EnOcean is the no-battery radio standard in building technology. e.control offers an extensive operating and sensor line in the

MP-Bus controls positioning drives for ventilation and air conditioning tech- nology. In addition to the actual position responses, each drive also provides an error status and optionally the measured value of a connected sensor. The e.control MP-Bus actuators can control up to 16 drives and return values from 16 connected sensors to the network.

software objects and a unified engineering database, LON represents the ideal integra-tion platform even for the most complex automation tasks in the e.control system.

EnOcean technology. e.control EnOcean receivers are equipped with the same functional scope as wired system units, so there are no penalties in terms of energy efficiency or flexibility.

The advantages

All open protocols are supported and seamlessly integrated

Automatic room-by-room sorting of all BACnet objects

Use of the OpenLNS engineering database for all protocols

Status and error detection for all communicating field devices

e.control combines best-in-class technologies into one system:

BACnet for integration into the management level

LON for the automation level

DALI, SMI, MP-Bus and EnOcean for intelligent field devices

M series

Management

Automation

Field

dialog RC-E

BMS

Floor controller

Page 13: spega e.control catalogue 2014

13

Functionality without limits

All e.control devices have tested, highly function software objects that need only be parameterised appropriately to their tasks. Since all objects from spega are not only tested for internal functionality but also for appropriate system behaviour togeth-er, e.control represents a true functional guarantee. That makes e.control essentially different from programmable system solu-tions in which the entire functionality must be provided by the system integrator only during the course of the project.

All e.control software objects are based on VDI 3813, the world’s leading standard for room controls, and therefore meet the requirements of a very specific function-ality, for example, the regulation of the room climate or the lighting. They can be so extensively parameterised that they can be adapted to any local variants. And because each of these objects is exactly identical on all e.control devices, the system integrator and operator immediately have a perfect overview that provides a uniform functional model even when different devices are used. Examples:

Even in lighting regulation, there are numerous application cases with different requirements to be taken into considera-tion. The constant lighting of a workstation works differently from lighting regulation in an entry foyer, where a global brightness impression is important. With suspended lights, the indirect proportion of light must additionally be taken into consideration, and in deep rooms the separate regulation of two light strips can be a practical option. If it should only be possible to turn the lighting on and off, equivalent functions should still be applicable. So it’s good that e.control has constant light regulators that cover all these requirements.

Complex, priority-dependent sequences are characteristic for optimally used sunblinds. While e.control handles the slat tracking

The conditioning of the room climate is handled by the room climate controller in the e.control system. It is suitable for all heating/cooling systems, whether cooling ceilings, radiators, forced-air fans, cooling bars in facade ventilation units or air-bear-ing (VAV) systems, and can be used with any

e.control with functional guarantee

Uniformity provides clarity

Lighting regulation

Slat tracking control

Room climate control

type of valve or flap drives. It also controls air quality and free (night-time) cooling, even optionally using a mechanical air intake system or outdoor air flap. Adap-tive start optimisation, summer or winter compensation, automatic temperature averaging, etc. are more options that can be added. In combination with an air humidity sensor, the dew point temperature can also be determined, to ensure that the cooling is turned off when necessary. Thermal automation also works together with the climate regulator and uses the sunshade as additional support for heating or cooling.

control for the sunblinds uniformly over the facade – of course parameterised in terms of frequency and minimum deflection angle – every sunshade actuator individually uses shadow corrections to check whether, for example, the neighbouring building is cast-ing a shadow on its own window, permitting the slats to be turned up without any risk of glare. Then there are wind and weather, along with interventions by Facility Man-agement or the users, who can use exten-sive priority controls to specify the correct sequence of events. e.control handles it all without breaking a sweat.

The advantages

Functional guarantee through complete software objects

Transparency thanks to uniform objects on all devices

Complete support for EN 15232 BAC efficiency class A – without programming

Compatibility with VDI 3813

Interoperability according to LonMark

The function library of e.control Designer contains a huge selection of room functions for all systems. Project-related, these functions can be combined to function groups (room macros) and then applied to all rooms.

The figure shows, for example, a 2-segment space of the BAC efficiency class A with all sensors (light grey), actuators (dark grey), controllers (yellow) and operating functions (orange).

Page 14: spega e.control catalogue 2014

14

Lighting functions

e.control multisensors form the core of any energy-efficient room, because automatic presence detection and measurement of room brightness are essential factors.

e.control light actuators are suitable for any lighting application. Whether fluorescent lamps, high- or low-voltage halogens or LED lights, whether relays, dimmers, 1-10V or DALI, e.control always has the right actua-tor available. All e.control light actuators incorporate power-on and power-off delays, a delayed light switch and a scene memory. Suitable installation locations include elec-trical distributors and decentralised system distributors.

e.control offers numerous options for operating the lighting: Web services for browsers or IP telephones, touch panels, built-in room control devices and radio buttons that are integrated using corre-sponding receivers (dialog RC-E or lumina MS4/RC). All these permit the switching or dimming of lighting, the retrieval of sce-narios and manual logging into or out of the room.

The e.control occupancy evaluation deter-mines the correct layout of a room from a combination of presence detectors and presence buttons for all other application functions for lighting, sunshade and room climate control. The holding time works adaptively and can be configured separately for each system.

Operating functions

Sensor functions

Actuator functions Occupancy evaluation

VDI 3813 Function

Operator functionsActuate lightSelect room utilisation*Signal presenceSensor functionsPresence detectionBrightness measurem.Actuator functionsLight actuator (switched)Light actuator (dimm)Application functionsOccupancy evaluationRoom utilisation**Light controlStairwell light controlAutomatic lightsDaylight-dependend lightsConstant light controlTwilight control

dialog Web

dialog 1

nova 8dialog 8

nova/climaLCD/RCM/RO

EN 15232C B A

< only for rooms without sufficient daylight provision (e.g. corridors)

< only for occationally used rooms with daylight provision (e.g. archives)

< for all rooms with daylight provision (e.g. offices, class rooms)

LON

* Recall or learn scenes ** Scene memory

tactio Ltactio S

nova TSlumina T6

Page 15: spega e.control catalogue 2014

15

The daylight-dependend switch is used when lighting cannot be or should not be implemented with a dimming option. De-pending on the supply of daylight, artificial light is added – with e.control, this can even be a two-level process. A built-in learning function ensures that the lamps are turned back off once the daylight is sufficient.

Constant light control is the ideal way to save lighting energy and is therefore mandatory for any energy-efficient build-ing. In rooms supplied with daylight, this system mixes in just enough artificial light to ensure that the required lighting level is maintained. In deep rooms with uneven distribution of daylight, e.control constant light regulation can even control two sep-arate lighting groups. Thanks to a learning artificial lighting correction, even suspend-ed lamps with an indirect portion are no problem for e.control. Energy savings can come to up to 50%.

Constant light control Daylight-dependend lights

Dimming

luminaMS4/RC

dialogRC-E

luminaMS4

ombraW2/WS12

1 - 10 V

Relay

DALI

R series: actuators for distribution boards

M series: modular actuators

230V

In the outdoor or entry area, in traffic routes or for the illumination of a building, lighting is only needed during the hours of darkness. Since the time of twilight varies from day to day, a twilight switch works autonomously to ensure the right time to turn on the lights. The e.control ombra W2 compact weather sensor uses its brightness sensor to turn on the desired light actuators at the right time – and turns them back off as well. The threshold values and delay times are configurable, of course.

Twilight control

The e.control automatic light only turns on the lights in halls, sanitary facilities, and storage rooms when people are detected. This avoids the use of energy for the lighting of unused rooms.

Automatic lights

Page 16: spega e.control catalogue 2014

16

Sunblind functions

For energy-efficient buildings, in addition to automatic presence detection, the deter-mination of sun intensity and interior room temperatures are needed for the automatic positioning of the sunblind. e.control de-termines these values using multisensors, control devices, radio temperature sensors and weather stations.

e.control offers numerous operating op-tions for the sunblind: Web services for browsers or IP telephones, touch panels, built-in room control devices and radio buttons that are integrated using corre-sponding receivers (dialog RC-E or lumina MS4/RC). All permit the positioning of cur-tain lengths and slat angles, either direct or using scenes.

For particularly tough requirements, due to exact positioning accuracy, e.control SMI actuators are also available for 230V or 24V motors.

e.control actuators cover the entire spec-trum of sunblind drives, whether interior or exterior blinds, awnings, screens or roller shutters. All devices have built-in priority control and a scene memory for curtain positions, including angular position. All actuators also support e.control slat track-ing control, including shadow correction.

The e.control automatic solar control in the ombra W2 or ombra WSx weather sensors evaluates exterior brightness across the facade and determines the limit value above which and the delay with which a defined sunshade position will be selected in order to avoid subjecting the user to glare.

Sensor functions Operating functions

Actuator functions Automatic solar control

dialog 1

EN 15232C B A

VDI 3813 Function

Operator functionsActuate sunshadeSelect room utilisation*Signal presenceSensor functionsPresence detectionTemperature measurem.Brightness measurem.Wind velocity measurem.Precipitation detectionActuator functionsSunshade actuatorApplication functionsOccupancy evaluationRoom utilisation**Priority controlAutomatic solar controlSlat tracking controlShadow correctionAutomatic thermal controlWeather protection

nova 8dialog 8

nova/climaLCD/RCM/RO

dialog Web

* Recall or learn scene ** Scene memory

LON

tactio Ltactio S

nova TSlumina T6

Page 17: spega e.control catalogue 2014

17

Slat tracking control Automatic thermal control Weather protection

For energy-efficient buildings, sun position-dependent guidance of the slats is important. The e.control ombra BST slat tracking controller periodically calculates the exact angle at which the maximum day-light supply can be achieved without intro-ducing glare, and sends it to the e.control sunshade actuators. The adjustment cycle and angle are parameterisable, as is the behaviour in case of temporary shadow.

To support heating or cooling, automatic thermal control is used to regulate solar energy entry through the facade. While heat input is welcome in the spring and thermal control opens the sunblind appropriately, in summer it prevents unnecessary heating by closing up. It is an integral component of all e.control devices and multisensors, providing the link between sunshades and HVAC systems needed for energy-efficient buildings.

Every e.control sunblind actuator is capable of determining autonomously whether its curtain will be in the sunshine at a specific time or shaded by (parts of) the building. This permits the sunshade to be adjusted to maximum transparency in the shadowed phases to improve the daylight yield.

The e.control weather protection system protects exterior curtains from damage by wind, freezing and even from precipitation. The e.control ombra WSx weather station uses its precise sensors to measure all the weather data needed, and brings the sun-shade system into the defined safe position on a timely basis. Of course, different limit values and safe positions can be defined for different curtain types.

Shadow correction

luminaMS4/RC

dialogRC-E

SMI

luminaMS4

ombraWS8/WS12

ombraW2

230 V AC

ombraBST

24 V DC

R series: actuators for distribution boards

M series: modular actuators

230V

Page 18: spega e.control catalogue 2014

18

Room climate functions

With e.control, you have full control over the desired room climate, whether by Web browser or IP phone, touch panel, built-in room control device or radio sensors. In all cases, it is possible to influence the set point, fan level and even the exterior air intake.

In addition to temperature and if necessary also air humidity measurements with the e.control room control device, an ener-gy-efficient room must also know the occupancy status. This value is provided by the e.control multisensors or presence detectors.

e.control actuators cover all the appli-cations of HVAC technology. Whether for radiators, heating/cooling ceilings, fan convectors or ventilation flaps, e.control has the right binary or analogue actuators. All have sequence adaptation, min/max limitation and a valve opening function for longer periods of non-use.

Energy efficiency can be significantly in-creased by adjusting the room temperature to usage times. To this end, all e.control room climate controllers have 4 energy levels, each of which is assigned different settings for heating and cooling. In combi-nation with e.control timer programs, this permits the room temperature to be indi- vidually adapted to planned usage. Using the occupancy evaluation, further optimisa-tion is possible, since rooms can be heated to the comfort mode only if occupied.

Sensor functions Operating functions

Actuator functions

Energy mode selection

EN 15232C B A

dialog 1

VDI 3813 Function

Operator functionsAdjust temp. setpointActuate fan speedSignal presenceSensor functionsPresence detectionTemperature measurem.Actuator functionsActuator (valves/dampers)Actuator (fans)Application functionsOccupancy evaluationEnergy mode selectionStart optimisationSetpoint calculationFunction selectionTemperature controlFan controlAir quality controlNight-time coolingSequence controlValue limitingLoad optimisation

nova 8dialog 8

nova/climaRCM/RO

nova/climaLCD

dialog Web

* only nova/clima RCM

LON

tactio Ltactio S

Page 19: spega e.control catalogue 2014

19

Start optimisation

Setpoint calculation

Function selection

Air quality control

Night cooling

All e.control room climate controllers have a self-learning start optimisation that works to-gether with a timer program to determine the latest time to heat or cool before a planned change in energy mode. This eliminates the waste of energy due to premature heating or cooling.

All e.control room climate controllers have not only two heating and cooling sequences with supply air temperature limitation and a ventilator sequence, but also air quality control which, depending on room occupan-cy or actual room air quality, can control either an outdoor air or an air intake flap.

e.control room climate controllers can be switched to a night cooling function. Every controller then decides independently on the start and end of night-time cooling, depending on the outdoor and indoor tem-perature. In addition to exterior air fan convectors, volume flow flaps or motorised windows can also be used for ventilation.

In addition to individual setting offsets by the user, e.control room climate controllers also provide summer and winter compensa-tion for high or low outdoor temperatures. This behaviour can be adapted to the char-acteristics of the building.

All e.control room climate controllers can – depending on the heating/cooling sys-tem – be operated in the functions Heating, Cooling, Automatic, Precooling and Night cooling. Switching between modes takes place either through a timer program or automatically from the controller.

luminaMS4/RC

dialogRC-E

Multi-stage

luminaMS4

ombraW2/WS12

sistemaRC2

0-10V

MP-Bus

PWM/3-point

R series: actuators for distribution boards

M series: modular actuators

230V

Page 20: spega e.control catalogue 2014

20

DD

C

B

A

CB

A

DC

B

A

Manual on/off switch

Manual

––

Manual on/off switch with additional sweeping extinction signal

Automatic

Automatic detection Switching off the lighting in the event of non-occupancy eliminates energy use in unoccupied rooms.

Reduction in the luminous flux of artificial lighting to the required minimum.

- Presence detection- Occupancy evaluation- Automatic lights- Light actuator

- Brightness measurem.(indoor)- Constant-light control- Lighting actuator (dimmable)

- lumina MS4- lumina MS4/RC- all e.control lighting actuators

- lumina MS4- lumina MS4/RC- lumina(R)DALx- lumina (R)STx- lumina RDAx-UN

0

1

2

0

1

5.1 Occupancy control

5.2 Daylight control

BAC Eff.Class

Energy savings VDI 3813-2 functions Suitable spega devices

Manual operation –

–Motorized operation with manual control

–Motorized operation with automatic control

Combined control of lighting, blind and HVAC system

Maximisation of daylight penetration by means of slat tracking min-imises the proportion of artificial lighting, energy-optimised control of the solar energy inputs relieves the heating and cooling system.

- Brightness measurem. (outdoor)- Automatic solar control- Sunshade actuator

- Brightness measurem. (outdoor)- Temperature measurem.(indoor)- Slat tracking control- Shadow correction- Automatic thermal control- Sunshade actuator

- ombra W2- ombra WSx with ombra W7-C- all e.control Sunblind actuators

- ombra W2- ombra WSx with ombra W7-C- ombra BST- lumina MS4/RC with dialog RC-T(S)- all e.control room control panels- all e.control sunblind actuators

0

1

2

3

6 Blind control

Energy efficiency in lighting and sunblinds

The European EN 15232 standard gives direction for building automation, but specifies a list of room and building au-tomation and management methods that influence the energy efficiency of buildings. These are also assigned to one of four effi-ciency classes, in order to ensure practical minimum functionality in accordance with the requirements of general contractors. While efficiency class C just meets legal minimum standards, to qualify for class B the use of energy-efficient room automa-tion functions for all systems (heating, cooling, ventilation, lighting and sunblinds) is required. This is understandable, because improved energy efficiency is the definitive factor in controlling energy transfer, that is, within rooms. This is the only way in which energy waste that occurs as a consequence of energy transfer that is not useful, can effectively be ruled out.

The first two columns in the tables on pages 20 through 22 contain the EN 15232 methods for room automation in the systems of light-ing, sun protection, heating and cooling, and ventilation and room climate. The third column shows the building automation effi-ciency class that can be achieved with each method, while the following column explains how energy savings are achieved. During im-plementation of room automation systems, column 5 “VDI 3813-2 function” is particu-larly important, since it provides the link to the room automation functions described in the VDI 3813 sheet 2 guidelines. The final column lists the e.control devices and their combinations that meet the requirements of each method and thus the required room automation functions.

For lighting systems, the combination of an e.control multisensor and dimmable light actuators in the R or M series can achieve the highest efficiency class with automatic presence detection, combined with con-stant light control.

In sun protection, efficiency class B or A can be achieved by coordinating with the lighting (slat tracking control with shadow correction) and the HVAC systems (auto-matic thermal control). Here, e.control uses the ombra BST slat tracking controller in combination with any e.control sunblind actuators and any e.control room control device, or a multisensor with built-in auto-matic thermal control.

The EN 15232 standard Explanation of the tables Lighting

Sun-protection

Page 21: spega e.control catalogue 2014

21

DC

B

A

DC

B

A

DC

B

A

DDC

B

A

No automatic control –

–Outside temperature compensated control

Demand based control Acknowledgement of the effective loads of the individual room controllers reduces the distribution losses to a mini-mum by adopting the tempera-ture to the effective demand.

- Load optimisation - nova / clima RO (-CC / -FC)- nova / clima RCM (-CC / -FC)- nova / clima LCD (-CC)- nova 8 / dialog 8 / dialog 1- tactio S / tactio L- lumina MS4/RC with dialog RC-T(S)

0 1

2

1.3/3.3 Control of distribution network water temperature

No automatic controlCentral automatic control

No automatic control

No interlock

Individual room control by thermostatic valves or electronic controller

Automatic control with fixed time program

Partial interlock

Individual room control with communication between controllers and to BACS

Automatic control with optimum start

Automatic control with demand evaluation

Total interlock

Communication allows the use of time programs for reduction in the event of non-use. Centralised control is also possible.

The latest possible heating-up time reduces supply losses in the morning.

Reliable prevention of simul-taneous heating and cooling energy output with the effect of neutralisation.

- Time program- Setpoint calculation- Energy mode selection- Temperature control- (Window monitoring)

- Time program- Energy mode selection- Start optimisation

- Function selection

- nova / clima RO (-CC / -FC)- nova / clima RCM (-CC / -FC)- nova / clima LCD (-CC)- nova 8 / dialog 8 / dialog 1- tactio S / tactio L- all e.control actuators

- nova / clima RO (-CC / -FC)- nova / clima RCM (-CC / -FC)- nova / clima LCD (-CC)- nova 8 / dialog 8 / dialog 1- tactio S / tactio L- lumina MS4/RC with dialog RC-T(S)

- nova / clima RO (-CC / -FC)- nova / clima RCM (-CC / -FC)- nova / clima LCD (-CC)- nova 8 / dialog 8 / dialog 1- tactio S / tactio L- lumina MS4/RC with dialog RC-T(S)

Integrated individual room control including demand control (by occupancy sensors)

Automatic occupancy sensing leads to a further minimisation of supply losses in the event of total non-occupancy.

- Presence detection- Occupancy evaluation- Time program- Setpoint calculation- Energy mode selection- Temperature control- (Window monitoring)

- Room control panels as above with lumina MS4 - lumina MS4/RC with dialog RC-T(S)– all e.control actuators

0 1

2

3

4

0

1

2

3

0

1

2

1.1/3.1 Emission control

1.5/3.5 Intermittent control of emission

3.6 Interlock between heating and cooling control of emission

BAC Eff.Class

Energy savings VDI 3813-2 functions Suitable spega devices

Time-based heating to standby setpoint, heating-up to comfort setpoint only on presence.

same as above, plus:- Presence detection- Occupancy evaluation

Energy efficiency in heating and cooling operation

To achieve efficiency class B or A in heating and cooling operation, any e.control devices with built-in temperature sensors and room climate controllers can be used, that is, all control devices and multisensors. Since they already include all the needed functions, such as energy mode selection, start opti-misation and complete interlock between heating and cooling operation, they already meet all the requirements for efficiency

class B. For efficiency class A, a multisensor is needed that can provide the required presence detection. Although EN 15232 does not explicitly re-quire window monitoring, its use is strongly recommended to avoid ventilation losses. All e.control room climate controllers, of course, are prepared for this use.

Emission control Control of distribution network

For demands-oriented advance temperature regulation in the distribution network, which is required by efficiency classes B and A, knowledge of the current heating or cool-ing load of each individual room is required. To this end, all e.control room controllers have a load signal that is evaluated by the e.control floor controller and provided to any automation station.

Page 22: spega e.control catalogue 2014

22

DC

B

A

DC

B

A

No automatic control

No automatic control

Time control - Time program

Night cooling

Presence control

Free cooling

Reduction in volumetric rate of flow in the event of non-occupancy reduces the power required by the fans.

The use of night air for discharging the thermal mass of the building without using power for cooling.

- Presence detection- Occupancy evaluation- Air quality control- Control drive actuator- (Window monitoring)

- Temperature measurement (indoor/outdoor)- Function selection- Night-time cooling

- nova / clima RO (-CC / -FC)- nova / clima RCM (-CC / -FC)- nova / clima LCD (-CC)- nova 8 / dialog 8 / dialog 1- tactio S / tactio L- lumina MS4- lumina MS4/RC- clima (R)AAx-10V- clima (R)AA8-MP

- nova / clima RO (-CC / -FC)- nova / clima RCM (-CC / -FC)- nova / clima LCD (-CC)- nova 8 / dialog 8 / dialog 1- tactio S / tactio L- lumina MS4/RC with dialog RC-T(S)- ombra W2- ombra WSx with ombra W7-C

Demand control Demand-based control of the volumetric rate of flow according to the air quality reduces the required power to a minimum.

- Air quality measurement- Presence detection- Occupancy evaluation- Air quality control- Control drive actuator- (Window monitoring)

- devices as above

0 1

2

3

0 1

2

4.1 Air flow control at room level

4.5 Free mechanical cooling

Energy efficiency in ventilation and air conditioning

To ensure energy-efficient ventilation and air conditioning, for mechanical systems the air volume flow must be adjusted depend-ing on the room occupancy (for class B) or the air quality (class A). In the first case, an e.control multisensor covers the sensor requirements, while in the second case an additional CO2 or VOC sensor is required. The

Emission control Free cooling

control or regulation algorithm is already built into every e.control room climate controller. To control volume flow flaps, in addition to analogue output modules in the R or M series, the e.control MP-Bus controller is also needed, since it can manipulate the positioning drives as well as evaluate the air quality sensors.

e.control room controllers have a separate function for free cooling with outdoor air. This can be done either using cross-ven-tilation with windows, or if mechanical ventilation systems are available, then by controlling the volume flow flaps. In either case, the e.control room climate controller decides individually on the start and end of active ventilation based on individual room temperature, providing an optimum climate for the next day.

BAC Eff.Class

Energy savings VDI 3813-2 functions Suitable spega devices

Page 23: spega e.control catalogue 2014

23

Use in flexible office buildings

The architecture of modern office buildings is characterised by floor plans with axial grids that permit the flexible movement of the walls. Even during usage phases, it should be possible to change rooms without having to make changes to the wiring of the room automation system.

The objective The advantages

Cost-effective integration of all systems using M series system distribution boxes

Room changes without rewiring, using radio sensors

dialog Web is ideal for operation in open-plan offices

Graphical preparation and ope-ration possible using e.control Designer

Achieves BAC efficiency class A

To allow field devices like lights, blinds, and heating/cooling ceilings that are installed in segments to be integrated flexibly into the automation system, e.control system distribution boxes can be used with devices in the M series. Each room is additionally equipped with a lumina MS4/RC radio multisensor, which not only integrates the radio sensors and buttons, but also handles the regulation of all systems. Moreover, the dialog Web server can be used for control from each workstation.

The solution

LON

RC-TSRC-N2

System distribution box

MS4/RC

Heated/chilled ceiling

Heated/chilled ceiling

Heated/chilled ceiling

Heated/chilled ceiling

Overview of an flexible office building: the shaded area on the left defines a room.

Page 24: spega e.control catalogue 2014

24

Use in fixed rooms

In buildings with fixed floor plans, instal-lation is often planned and assigned on a system-by-system basis. The installation of room climate control and the control of lighting and sun protection are separate tasks.

The objective The advantages

System-based planning and assignment possible

Broad functional scope thanks to seamless integration

Achieves BAC efficiency class A according to EN 15232

For room climate control, the clima DL-110 universal room controller can be used. Equipped with multisensor and IR remote control, it can also provide the sensor data and operating requests for light and sun protection. Their operation is then handled by actuators in the R series, which are installed in the classical manner at the local level. The high degree of functional integ-ration means that here, too, no functional desire is left unfulfilled.

The solution

Overview of a building with fixed walls: lighting and sunblind controls are installed seperately from the room climate control. Nevertheless a common commissioning ensures full functionality.

R series

Window contact

DWM-20

LON

DMS-20

Heated/chilled ceiling

Dew point sensor

DL-110

Page 25: spega e.control catalogue 2014

25

Use in hotel rooms

For the efficient use of energy, heating and cooling in hotel rooms is adapted to room occupancy and window use. While fixed int-roduction is preferred in new construction, the renovation solution uses the approach of using only minimum installation times in order to avoid restricting the availability of the room.

The objective The advantages

Energy-efficient operation of heating and/or cooling

Cost-effective construction, with just one unit in new construction

Avoiding wiring work in the room during renovation

Integration into the hotel booking system supported

The demand-based control of the fan coil unit is handled by the clima DL-110 universal room controller, which is equipped with a wall control device and a hotel key card holder, and is connected to the hotel boo-king software using the LON network. While wired devices can be connected directly to the controller in new construction, radio sensors are also available for renovation that can contact receivers in the corridor to send packets through the LON network to the corresponding room controllers. Using the separate switch contact of the clima DL-110, a contactor can also be actuated that turns lighting off with a time delay after the hotel key card is removed from its holder, then turns it back on when it is replaced.

The solution

In new construction clima DL-110 forms the heart of a hotel room with wall module, hotel card switch and contactor for delayed switching off the lights.

DL-110

Window contact

DWM-20Hotel card

switch

Central o

Fan coil unit

LON

DL-110

Hotel card switch

Central o

Fan coil unit

LON

RC-E

RC-TS

RC-G

For renovation clima DL-110 waives wired compon-ents and instead receives all information via radio with dialog RC-E in the corridor.

Page 26: spega e.control catalogue 2014

26

Planning with e.control

Not all room automation is alike! Every construction plan has its own special de-tails and assumptions. But planning with e.control is still simple and clear. The e.control CD helps you with its extensi-ve product and planning information. This information can be viewed directly from the CD with the e.control viewer. It starts auto-matically when you insert the CD. Simply select the desired category from the main menu. A tree view shows you all the avail-able documents, sorted for clarity.

Planners find all relevant information on the e.control CD:

Product information Configuration tools Technical data sheets

For system integrators, the CD includes:

Product manuals Configuration software (LNS plug-ins) Various software programs

Everything clear and available The advantages

Detailed cost estimation during design planning

Estimation of cost-effectiveness with dynamic investment calculation

A special configuration tool helps deter-mine the right system distribution box for flexible-grid room automation solu-tions. The tool is started directly from the e.control viewer and works with the grid specifications of the field devices to be in-tegrated into the automation system, such as lighting, blinds and window motors and

Planning room automation

A software tool to calculate the cost effectiveness of room automation systems compares their investment costs with the operating cost savings that will result from their use. By entering the relevant quanti-ties, future yearly results and capital trends are available in a snap.

Checking cost-effectiveness

On the CD, the following software can be found:

ALEX Commissioning tool Configuration software (LNS plug-ins) IPLONGATE OPC data server Open LNS Server

Software on CD

positioning drives, as well as the selection of room control device. It then generates an exact specification for the system distribu-tor, a list of all required devices including the minimum quantity of infrastructure components, as well as a cost estimate.

Page 27: spega e.control catalogue 2014

27

Page 28: spega e.control catalogue 2014

28

Page 29: spega e.control catalogue 2014

29

ALEX commissioning software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101 e.control Designer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101 IPLONGATE OPC data server . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102 LPA protocol analyser and LSD system diagnostics. . . . . . . . . . . . . . . . . . . . . . . . 102

softw

are

infra Routers and terminators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96

Power supplies and interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98 Touch panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99

Web server and IP telephone server . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 Universal Room control panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 nova Room control panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 Standard 55 Room control panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44

pane

ls

Switch actuators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69 DALI Lighting controllers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70 1-10V Lighting controllers and dimmers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71 Sunblind actuators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72 SMI Sunblind actuators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74 Digital inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76 Digital outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77 Analogue I/O modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78 MP-Bus controllers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79

r ser

ies

m s

erie

s M series Distribution boxes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61 M series Lighting actuators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62 M series Sunblind actuators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64 M series Analogue and digital I/O modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66

Universal room controller clima DL-110 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81 nova Room controllers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84 Standard 55 Room controllers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86

Slat tracking controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91 Weather stations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92 Compact weather sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93w

eath

erse

rver BACnet Floor controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95

LON Application controller. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95

Multisensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57 Presence detectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58

e.control products

Radio receiver. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49 Multisensor with radio receiver . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49 nova Radio sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 Standard 55 Radio sensors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52 Radio window handles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54

enoc

ean

sens

cont

rolle

r

Fire damper modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89

Table of content

Page 30: spega e.control catalogue 2014

30

dialog Web – new perspectives in operation

lumina MS4 lumina MS4

L-IP M series

dialog Web

PC PCIP-Phone

With the e.control dialog Web server, every-day work tools such as the PC or phone can be turned into a virtual control device. That opens up new perspectives, particularly wherever conventional control devices are difficult to install, whether from an aest-hetic viewpoint or for reasons of flexibility of use. Using Web technologies like HTML and XML, every user can use a Web browser or an IP-capable phone to access all control functions, like adjusting the temperature setting, the fan level, lighting, the sunsha-de or individual windows.

The workstation as cockpit The advantages

Ideally well-suited for flexible (open-plan) office environments

Supports Web browsers and XML-capable IP telephones

Meets the strictest of DGNB and LEED requirements

Also suitable for buildings with multiple rented units

Full administration capabilities by users/tenants

Low investment costs

dialog Web is ideal for buildings with multi-ple rented units, since integration into the tenant‘s LAN is provided through an Ether-net connection separated from the building automation backbone, which also provides the Web-based administrative access for the tentant to manage their own users, rooms and access privileges, and adapt layouts to their corporate design.

Suitable for rental units

From the point of view of the system integ-rator, dialog Web is a device with up to 150 virtual room control devices, which due to its static network interface can be managed just as easily as any other e.control room control device – either in combination with the e.control Designer or even fully auto-matically. On the LON side, the server has its own Ethernet connection that is used to integrate it into the building automation backbone. As usual with spega, the parame-terisation of all functionality is done using production plug-ins, which also permit working offline.

Simple system integration

In addition to access via Web browser, dia-log Web also provides additional licenses to permit the integration of IP-capable phones with XML support (such as Siemens OpenSta-ge or Cisco Unified IP phones). This permits a Web layout to be prepared, then adapted to the display capabilities of the telephone with no additional configuration effort.

IP phones welcome

The possibility of operating multiple Web servers in a server cluster also means that the number of virtual room control devices and users is effectively unlimited. The in-stallation of over 20 servers for more than 2000 workstations in one German company demonstrates the robustness and perfor-mance of the dialog Web server cluster. Since administration is handled through the master, it is absolutely no different from management of a single unit.

We love large buildings

LAN

LON

BAC

back

bone

Page 31: spega e.control catalogue 2014

31

Specification Order No.Figure Technical data

dialog Web

dialog WebInternet web server

Server for controlling all room auto-mation functions via standard web browsers or IP phones (optional)

Static interface for a maximum of 150 rooms, multiple servers can be clustered for unlimited numbers of rooms with shared configuration

Separated building management IP network and user IP network via 2 Ethernet ports

User administration and access rights management via web inter-face

User-independent licensing per room, configurable via LNS plug-in

Server for switchboard mountingServer as tabletop unit w/ power sup.

Network:Port 1 10/100 Base-T (LON/IP)Port 2 10/100 Base T (TCP/IP LAN)

Licenses:15 licenses for virtual web control panels included, max. 150 licenses

Power supply: Switchb.: 12 or 24V DC, max. 15 W Tabletop: 230 V AC 50Hz

Metrics/Mounting:(HxWxD) 49 x 168 x 140mm

443 150443 151

dialog Web Virtual web control panel

Licenses an additional virtual web-based room control panel on the internet web server dialog Web

Each room requires one license

Number of users per virtual room panel is unlimited

Web license (per room)

Activation:Via license file upload from the admi-nistration webpage. Licenses can be upgraded at any time.

093 101

093 141dialog Web Virtual IP phone operation panel

Activates the XML interface for IP phones for a licensed virtual room panel

Supports the following XML-enabled IP phones: - Siemens Open Stage 40, 60, 80 - Cisco Unified IP Phone 7900

Each virtual room panel with IP phone interface requires a license

Number of phones per virtual room panel is unlimited

Add-on license (per room)

Activation:Via license file upload from the admi-nistration webpage. Licenses can be upgraded at any time.

Page 32: spega e.control catalogue 2014

32

Universal room control panels - function and design combined

The e.control universal room control panels represent the ideal interface between the room user and the automation system. The uniform control philosophy for all systems replaces conventional “isolated solutions” like thermostats, light switches and blinds controls. The lighted displays allow e.con-trol room control devices to show the user all significant status items, graphically and clearly.

Integration for the user The advantages

Uniform display and operating concept for all systems

Meets DGNB and LEED require-ments

3 operating concepts with the same functionality

Suitable as complete room reg-ulator or as a control unit for an external regulator

Modern high-quality designs in different colours

e.control doesn’t require any particular philosophy of operation. Instead, the user can select from one of three concepts:

dialog 1: Operation with rotary/push buttondialog 8: Operation using buttonstactio L/S: Operation by touch screen

Operation however you like All universal room control devices include the full e.control functional scope for con-trolling the room climate, lighting and sun protection, as well as presence detection and room climate control (see table). That means that the devices can be used either as control units for external room controllers such as the clima DL-110 (see pages 80 and up) as well as fully capable heating, cooling and air quality controllers in combination with positioning drive actuators in the R or M series.

Full functionality on board

Each of these concepts is consistently and appropriately implemented, so the user always has a clear overview. And because the functionality is identical on all devices despite the different operating concepts, the user can decide on a preferred design freely and without restrictions.

Built-in LonMark objects Function

SCC Command Module Operating unit with built-in temperature sensor for the display of heating/cooling functions and setting of presence, temperature settings, and fan level

Dew Point Sensor Internal humidity sensor (optional for tactio)

Occupancy Controller Detects presence using a presence button and (external) presence sensors

Space Comfort Controller Room climate controller for all static heating/cooling systems, fan convectors, VVR system with air quality regulation, night-time cooling and self-learning start optimisation

Dew Point Calculator Determining the dew point temperature using a humidity sensor

Thermal Controller Automation to integrate a sunshade into room climate control

Scene Panel Calling up and saving of scenes

Switch For operating lighting circuits, sunshade and window motors

Page 33: spega e.control catalogue 2014

33

Specification Order No.Figure Technical data

dialog 8

8 buttons, anthracite12 buttons, anthracite

Network:TP/FT-10 (FTT10)

Power supply:24V AC/DC, max. 65mA

Metrics/Mounting:(HxWxD) 154 x 83 x 45mmin cavity wall or flush mounting sockets

dialog 8 anthraciteLON LCD room control panel

Comfortable display and control unit for air conditioning, lighting, sunblinds, windows, fans etc.

Backlit display for temperatures, time, date and controller states

Available with 8 or 12 buttons

Integrated temperature sensor

Application with integrated room climate controller according to Lon-Mark and VDI 3813-2, complies with BAC Efficiency Class A (EN 15232)

341 508 B 8341 508 B12

8 buttons, aluminium12 buttons, aluminium

Network:TP/FT-10 (FTT10)

Power supply:24V AC/DC, max. 65mA

Metrics/Mounting:(HxWxD) 154 x 83 x 45mmin cavity wall or flush mounting sockets

dialog 8 aluminiumLON LCD room control panel

Comfortable display and control unit for air conditioning, lighting, sunblinds, windows, fans etc.

Backlit display for temperatures, time, date and controller states

Available with 8 or 12 buttons

Integrated temperature sensor

Application with integrated room climate controller according to Lon-Mark and VDI 3813-2, complies with BAC Efficiency Class A (EN 15232)

341 508 A 8341 508 A12

8 buttons, pure white12 buttons, pure white Network:TP/FT-10 (FTT10)

Power supply:24V AC/DC, max. 65mA

Metrics/Mounting:(HxWxD) 154 x 83 x 45mmin cavity wall or flush mounting sockets

dialog 8 pure whiteLON LCD room control panel

Comfortable display and control unit for air conditioning, lighting, sunblinds, windows, fans etc.

Backlit display for temperatures, time, date and controller states

Available with 8 or 12 buttons

Integrated temperature sensor

Application with integrated room climate controller according to Lon-Mark and VDI 3813-2, complies with BAC Efficiency Class A (EN 15232)

341 508 W 8341 508 W12

Scale of images approx. 1:3

Page 34: spega e.control catalogue 2014

34

Specification Order No.Figure Technical data

341 708 W341 709 W

WhiteWhite with humidity sensor

Network:TP/FT-10 (FTT10)

Power supply:24V AC/DC, max. 185mA

Equipment:- TFT display 320x240 pixels, 262k col.- Capacitive glass touch surface

Metrics/Mounting:(HxWxD) 197 x 82 x 52mmin cavity wall or flush mounting sockets

tactio L whiteLON Touch room control panel

Room control panel with tempera-ture and optional humidity sensor, 3.5" TFT graphic display and ca-pacitive glass surface for intuitive control of all climate functions

8 additional capacitive touch sensors for control of lights, blinds, windows or scenes

Anodised aluminium clip with touch sensor for manual logon

Application with integrated room climate controller according to LonMark and VDI 3813-2, com-plies with BAC Efficiency Class A (EN 15232)

341 501 WAluminium / white

Network:TP/FT-10 (FTT10)

Power supply:24V DC, max. 80mA

Equipment:- Display 4x16 characters, backlit- Control via push and turn knob- Realtime clock, battery backed- Buzzer, 3 LEDs (red, yellow, green)

Metrics/Mounting:(HxWxD) 125 x 125 x 40mmincl. box for cavity wall or flush mounting

341 701 W341 702 W

WhiteWhite with humidity sensor

Network:TP/FT-10 (FTT10)

Power supply:24V AC/DC, max. 185mA

Equipment:- TFT display 320x240 pixels, 262k col.- Capacitive glass touch surface

Metrics/Mounting:(HxWxD) 126 x 82 x 52mmin cavity wall or flush mounting sockets

tactio S whiteLON Touch room control panel

Room control panel with tempera-ture and optional humidity sensor, 3.5" TFT graphic display and ca-pacitive glass surface for intuitive control of all climate functions

Anodised aluminium clip with touch sensor for manual logon

Application with integrated room climate controller according to LonMark and VDI 3813-2, com-plies with BAC Efficiency Class A (EN 15232)

dialog 1 whiteIntegrated LON room control panel

Comfortable display and control unit for air conditioning, lighting, sunblinds, windows, fans etc.

White backlit display with 4x16 characters, 3 LEDs and buzzer

Front and push and turn knob made of anodised aluminium

Free configurable menu with fa-vourites and scene management

Application with integrated room climate controller according to Lon-Mark and VDI 3813-2, complies with BAC Efficiency Class A (EN 15232)

tactio / dialog 1

Page 35: spega e.control catalogue 2014

35

Specification Order No.Figure Technical data

Aluminium / black

Network:TP/FT-10 (FTT10)

Power supply:24V DC, max. 80mA

Equipment:- Display 4x16 characters, backlit- Control via push and turn knob- Realtime clock, battery backed- Buzzer, 3 LEDs (red, yellow, green)

Metrics/Mounting:(HxWxD) 125 x 125 x 40mmincl. box for cavity wall or flush mounting

BlackBlack with humidity sensor

Network:TP/FT-10 (FTT10)

Power supply:24V AC/DC, max. 185mA

Equipment:- TFT display 320x240 pixels, 262k col.- Capacitive glass touch surface

Metrics/Mounting:(HxWxD) 126 x 82 x 52mmin cavity wall or flush mounting sockets

Scale of images approx. 1:3

341 708 B341 709 B

BlackBlack with humidity sensor

Network:TP/FT-10 (FTT10)

Power supply:24V AC/DC, max. 185mA

Equipment:- TFT display 320x240 pixels, 262k col.- Capacitive glass touch surface

Metrics/Mounting:(HxWxD) 197 x 82 x 52mmin cavity wall or flush mounting sockets

tactio L blackLON Touch room operation panel

Room control panel with tempera-ture and optional humidity sensor, 3.5“ TFT graphic display and ca-pacitive glass surface for intuitive control of all climate functions

8 additional capacitive touch sensors for control of lights, blinds, windows or scenes

Anodised aluminium clip with touch sensor for manual logon

Application with integrated room climate controller according to LonMark and VDI 3813-2, com-plies with BAC Efficiency Class A (EN 15232)

341 501 A

341 701 B341 702 B

tactio S blackLON Touch room operation panel

Room control panel with tempera-ture and optional humidity sensor, 3.5“ TFT graphic display and ca-pacitive glass surface for intuitive control of all climate functions

Anodised aluminium clip with touch sensor for manual logon

Application with integrated room climate controller according to LonMark and VDI 3813-2, com-plies with BAC Efficiency Class A (EN 15232)

dialog 1 blackIntegrated LON room control panel

Comfortable display and control unit for air conditioning, lighting, sunblinds, windows, fans etc.

White backlit display with 4x16 characters, 3 LEDs and buzzer

Front and push and turn knob made of anodised aluminium

Free configurable menu with fa-vourites and scene management

Application with integrated room climate controller according to Lon-Mark and VDI 3813-2, complies with BAC Efficiency Class A (EN 15232)

tactio / dialog 1

Page 36: spega e.control catalogue 2014

36

nova 8 nova LCD nova TS

The e.control nova room con-trol device in LON or EnOcean technology variants always leave a shining impres-sion. A clean, linear design together with a high-gloss surface perfectly highlights the architecture of modern buildings. With three colour variants and a wide selection of bus-capable and wireless units, you can find the right control device for any appli-cation.

High-gloss surfaces and frames of pure white or deep black plastic set accents without being obtrusive. The structured surface of the covers and frames, with an aluminium look, harmonises perfectly with modern ar-chitecture of concrete, glass and steel.

dialog 8 and nova RC-T(S): Unit surface of matte plastic, together with a glossy frame.

LCD room climate controller (combinable with nova TS)

Push button sensors (combinable with nova LCD)

LCD room control panel

Wide selection

nova Room control panels – wide selection in modern designs

Page 37: spega e.control catalogue 2014

37

nova RCM/RO nova RC-LCD nova RC-T/TS nova RC-L/JRoom climate controller

with/without setpoint adj.Wireless temperature sensor

with LCD and setpoint adjusterWireless temperature sensor with/without setpoint adj.

Wireless push sensors

Wireless sensors see p. 50

Page 38: spega e.control catalogue 2014

38

Specification Order No.Figure Technical data

8 buttons, anthracite12 buttons, anthracite

Network:TP/FT-10 (FTT10)

Power supply:24V AC/DC, max. 65mA

Metrics/Mounting:(HxWxD) 154 x 83 x 45mmin cavity wall or flush mounting sockets

nova 8 anthraciteLON LCD room control panel

Comfortable display and control unit for air conditioning, lighting, sunblinds, windows, fans etc.

Backlit display for temperatures, time, date and controller states

Available with 8 or 12 buttons with plastic frame in nova design

Integrated temperature sensor

Application with integrated room climate controller according to Lon-Mark and VDI 3813-2, complies with BAC Efficiency Class A (EN 15232)

341 608 B 8341 608 B12

8 buttons, aluminium12 buttons, aluminium

Network:TP/FT-10 (FTT10)

Power supply:24V AC/DC, max. 65mA

Metrics/Mounting:(HxWxD) 154 x 83 x 45mmin cavity wall or flush mounting sockets

nova 8 aluminiumLON LCD room control panel

Comfortable display and control unit for air conditioning, lighting, sunblinds, windows, fans etc.

Backlit display for temperatures, time, date and controller states

Available with 8 or 12 buttons with plastic frame in nova design

Integrated temperature sensor

Application with integrated room climate controller according to Lon-Mark and VDI 3813-2, complies with BAC Efficiency Class A (EN 15232)

341 608 A 8341 608 A12

8 buttons, pure white12 buttons, pure white

Network:TP/FT-10 (FTT10)

Power supply:24V AC/DC, max. 65mA

Metrics/Mounting:(HxWxD) 154 x 83 x 45mmin cavity wall or flush mounting sockets

nova 8 pure whiteLON LCD room control panel

Comfortable display and control unit for air conditioning, lighting, sunblinds, windows, fans etc.

Backlit display for temperatures, time, date and controller states

Available with 8 or 12 buttons with plastic frame in nova design

Integrated temperature sensor

Application with integrated room climate controller according to Lon-Mark and VDI 3813-2, complies with BAC Efficiency Class A (EN 15232)

341 608 W 8341 608 W12

nova 8

Page 39: spega e.control catalogue 2014

39

Specification Order No.Figure Technical data

8 buttons, aluminium

Network:TP/FT-10 (FTT10)

Power supply:24V DC, max. 45mA

Metrics/Mounting:(HxWxD) 70 x 70 x 49mmin cavity wall or flush mounting sockets

Suitable frames:nova Rx, 1-3 fold, see p. 43

nova LCD aluminiumLON LCD Room temperature controller with 8 buttons

Room control panel with tempera-ture sensor, LC display and 8 push buttons for setpoint adjustment, presence, fan stages, lighting, blinds or scenes

Backlit display for temperatures and different controller states

Combinable with up to 8 nova TSx-e (p. 40) for additional push buttons, frame not included

Application with integrated room climate controller according to LonMark and VDI 3813-2 complies with BAC Efficiency Class A (EN 15232)

8 buttons, black glossy

Network:TP/FT-10 (FTT10)

Power supply:24V DC, max. 45mA

Metrics/Mounting:(HxWxD) 70 x 70 x 49mmin cavity wall or flush mounting sockets

Suitable frames:nova Rx, 1-3 fold, see p. 43

nova LCD blackLON LCD Room temperature controller with 8 buttons

Room control panel with tempera-ture sensor, LC display and 8 push buttons for setpoint adjustment, presence, fan stages, lighting, blinds or scenes

Backlit display for temperatures and different controller states

Combinable with up to 8 nova TSx-e (p. 40) for additional push buttons, frame not included

Application with integrated room climate controller according to LonMark and VDI 3813-2 complies with BAC Efficiency Class A (EN 15232)

8 buttons, pure white glossy

Network:TP/FT-10 (FTT10)

Power supply:24V DC, max. 45mA

Metrics/Mounting:(HxWxD) 70 x 70 x 49mmin cavity wall or flush mounting sockets

Suitable frames:nova Rx, 1-3 fold, see p. 43

231 618 W

231 618 B

231 618 A

nova LCD pure whiteLON LCD Room temperature controller with 8 buttons

Room control panel with tempera-ture sensor, LC display and 8 push buttons for setpoint adjustment, presence, fan stages, lighting, blinds or scenes

Backlit display for temperatures and different controller states

Combinable with up to 8 nova TSx-e (p. 40) for additional push buttons, frame not included

Application with integrated room climate controller according to LonMark and VDI 3813-2 complies with BAC Efficiency Class A (EN 15232)

Scale of images approx. 1:3

nova LCD control panels

Page 40: spega e.control catalogue 2014

40

Specification Order No.Figure Technical data

TS2 with LON interface:pure white glossyblack glossyaluminium

TS2-e Extension module:pure white glossyblack glossyaluminium

Network/Power supply (TS2):TP/FT-10 (FTT10)24V DC, max. 35mA (TS-e: 15mA)

Metrics/Mounting:(HxWxD) 70 x 70 x 49mmin cavity wall or flush mounting sockets

Suitable frames:nova Rx, 1-3 fold, see p. 43

nova TS2Push button sensor 2-gang

Sensor with 2 push buttons for lighting, blind or scene control

Each button with status LED for status indication

Version TS2 with LON interface and connection port for up to 7 additional TSx-e, application with switch profiles according to LonMark and VDI 3813-2

Version TS2-e as extension module for nova TS or nova LCD, connection via twisted pair cable

Available in 3 colours for nova design, frame not included

211 602 W211 602 B211 602 A

210 602 W210 602 B210 602 A

TS4 with LON interface:pure white glossyblack glossyaluminium

TS4-e Extension module:pure white glossyblack glossyaluminium

Network/Power supply (TS2):TP/FT-10 (FTT10)24V DC, max. 35mA (TS-e: 15mA)

Metrics/Mounting:(HxWxD) 70 x 70 x 49mmin cavity wall or flush mounting sockets

Suitable frames:nova Rx, 1-3 fold, see p. 43

nova TS4Push button sensor 4-gang

Sensor with 4 push buttons for lighting, blind or scene control

Each button with status LED for status indication

Version TS4 with LON interface and connection port for up to 7 additional TSx-e, application with switch profiles according to LonMark and VDI 3813-2

Version TS4-e as extension module for nova TS or nova LCD, connection via twisted pair cable

Available in 3 colours for nova design, frame not included

211 604 W211 604 B211 604 A

210 604 W210 604 B210 604 A

TS8 with LON interface:pure white glossyblack glossyaluminium

TS8-e Extension module:pure white glossyblack glossyaluminium

Network/Power supply (TS2):TP/FT-10 (FTT10)24V DC, max. 35mA (TS-e: 15mA)

Metrics/Mounting:(HxWxD) 70 x 70 x 49mmin cavity wall or flush mounting sockets

Suitable frames:nova Rx, 1-3 fold, see p. 43

nova TS8Push button sensor 8-gang

Sensor with 8 push buttons for lighting, blind or scene control

Each button with status LED for status indication

Version TS8 with LON interface and connection port for up to 7 additional TSx-e, application with switch profiles according to LonMark and VDI 3813-2

Version TS8-e as extension module for nova TS or nova LCD, connection via twisted pair cable

Available in 3 colours for nova design, frame not included

211 608 W211 608 B211 608 A

210 608 W210 608 B210 608 A

nova Push button sensors

Page 41: spega e.control catalogue 2014

41

Specification Order No.Figure Technical data

231 602 W 231 602 B 231 602 A 231 603 W 231 603 B 231 603 A 231 604 W 231 604 B 231 604 A 231 605 W 231 605 B 231 605 A

w/o buttons pure white gl. black gl. aluminium Presence pure white gl. black gl. aluminium Fan speed pure white gl. black gl. aluminiumPresence/fan pure white gl. black gl. aluminium

Network / Power supply:TP/FT-10 (FTT10)24V AC/DC, max. 60mA

Metrics/Mounting:(HxWxD) 70 x 70 x 49mm

Suitable frames:nova Rx, 1-3 fold, see p. 43

nova RCMLON Room control panel with 4 digital inputs

Control panel with temperature sensor, setpoint adjuster and max. 2 buttons incl. LEDs for controller states and fan speed

4 inputs for floating contacts, e.g. light, sunblind or hotel card switches (p. 42), window contacts or presence detectors (p. 58)

Available in 3 colours for nova design, frame not included

Application with integrated room climate controller according to Lon-Mark and VDI 3813-2, complies with BAC Efficiency Class A (EN 15232)

231 601 W 231 601 B 231 601 A

pure white glossyblack glossyaluminium

Network:TP/FT-10 (FTT10)

Power supply:24V AC/DC, max. 60mA

Metrics/Mounting:(HxWxD) 70 x 70 x 49mmin cavity wall or flush mounting sockets

Suitable frames:nova Rx, 1-3 fold, see p. 43

nova ROLON Climate controller for public buildings with 4 digital inputs

Continuous-action controller with temperature sensor and 2 LEDs for energy mode and heating or cooling activity

4 inputs for floating contacts, e.g. light or sunblind switches (p. 42), window contacts or presence detectors (p. 58)

Available in 3 colours for nova design, frame not included

Application according to LonMark and VDI 3813-2 complies with BAC Efficiency Class A (EN 15232)

nova Room controllers

231 612 W 231 612 B 231 612 A 231 613 W 231 613 B 231 613 A 231 614 W 231 614 B 231 614 A 231 615 W 231 615 B 231 615 A

w/o buttons pure white gl. black gl. aluminium Presence pure white gl. black gl. aluminium Fan speed pure white gl. black gl. aluminiumPresence/fan pure white gl. black gl. aluminium

Network / Power supply:TP/FT-10 (FTT10)24V AC/DC, max. 60mA

Metrics/Mounting:(HxWxD) 70 x 70 x 49mm

Suitable frames:nova Rx, 1-3 fold, see p. 43

nova RCM-rHLON Room control panel with hu-midity sensor and 4 digital inputs

Control panel with temperature and rel. humidity sensor, setpoint adjuster and max. 2 buttons incl. LEDs for controller states and fan speed

4 inputs for floating contacts, e.g. light, sunblind or hotel card switches (p. 42), window contacts or presence detectors (p. 58)

Available in 3 colours for nova design, frame not included

Application with integrated room climate controller according to Lon-Mark and VDI 3813-2, complies with BAC Efficiency Class A (EN 15232)

Scale of images approx. 1:3

Page 42: spega e.control catalogue 2014

42

Specification Order No.Figure Technical data

910 601 W 910 601 B 910 601 A

Model: pure white gl. black gl. aluminium

Metrics/Mounting:(HxWxD) 70 x 70 x 40mmin cavity wall or flush mounting sockets

Suitable frames:nova Rx, 1-3 fold, see p. 43

nova T1Push button 1-gang

Push button with changeover contact

Can be used with: nova RCM, RCM-CC, RCM-FC or nova RO, RO-CC, RO-FC or lumina T6

Available in 3 colours for nova design, frame not included

910 602 W 910 602 B 910 602 A

910 604 W 910 604 B 910 604 A

910 609 W 910 609 B 910 609 A

nova HCHotel card switch

Hotel card holder with normally open contact

Can be used with: nova RCM, RCM-CC, RCM-FC or nova RO, RO-CC, RO-FC or lumina T6

Available in 3 colours for nova design, frame not included

Model: pure white gl. black gl. aluminium

Metrics/Mounting:(HxWxD) 70 x 70 x 40mmin cavity wall or flush mounting sockets

Suitable frames:nova Rx, 1-3 fold, see p. 43

nova T2Push button 2-gang

2 push buttons with changeover contacts

Can be used with: nova RCM, RCM-CC, RCM-FC or nova RO, RO-CC, RO-FC or lumina T6

Available in 3 colours for nova design, frame not included

Model: pure white gl. black gl. aluminium

Metrics/Mounting:(HxWxD) 70 x 70 x 40mmin cavity wall or flush mounting sockets

Suitable frames:nova Rx, 1-3 fold, see p. 43

nova T4Push rocker 4-gang

2 push rockers with 4 normally open contacts

Can be used with: nova RCM, RCM-CC, RCM-FC or nova RO, RO-CC, RO-FC or lumina T6

Available in 3 colours for nova design, frame not included

Model: pure white gl. black gl. aluminium

Metrics/Mounting:(HxWxD) 70 x 70 x 40mmin cavity wall or flush mounting sockets

Suitable frames:nova Rx, 1-3 fold, see p. 43

nova Push buttons

Page 43: spega e.control catalogue 2014

43

Specification Order No.Figure Technical data

nova Frames

Scale of images approx. 1:3

920 601 W 920 601 B 920 601 A

R1, single pure white gl. black gl. aluminium

Metrics (HxWxD):83 x 83 x 10mm

nova R1Single frame for nova design

Available in 3 colours and 3 sizes for nova design line

920 602 W 920 602 B 920 602 A

R2, double pure white gl. black gl. aluminium

Metrics (HxWxD):154 x 83 x 10mm

nova R2Double frame for nova design

Combination frame suitable for vertical and horizontal installation

Available in 3 colours and 3 sizes for nova design line

920 603 W 920 603 B 920 603 A

R3, 3-fold pure white gl. black gl. aluminium

Metrics (HxWxD):225 x 83 x 10mm

nova R33-fold frame for nova design

Combination frame suitable for vertical and horizontal installation

Available in 3 colours and 3 sizes for nova design line

Page 44: spega e.control catalogue 2014

44

Standard 55 Room control panels – appropriate for all switch ranges

clima LCDPure white

Gira E2

Anthracite Gira Esprit steel

Aluminium Gira Esprit glass black

clima RCMAluminium Jung A 500

Anthracite Gira Event aluminium

Pure white Jung A creation glass grey-blue

e.control Standard 55 room control devices in LON or EnOcean technology variants can be combined with all Standard 55 switch ranges from any switch manufacturer. This permits operation to be integrated seamless-ly into the room design.

Compatible switch ranges include:

Berker: S1, B1, B3, B7 glass

Gira: Standard 55, E2, Event, Esprit, ClassiX, Profile 55

Jung: AS 500, A 500, A plus, A creation, A creation glass

Merten:1-M, M-Smart, M-Plan, M-Arc, M-Star, M-Plan glass The overview shows example combinations in different designs.

e.control always matches

Page 45: spega e.control catalogue 2014

45

clima RO dialog RC-TS dialog RC-TPure white Berker B1

Aluminium Merten M-Arc

Anthracite Merten M-Plan

Pure white Gira Esprit steel

Anthracite + dialog RC-L/J Berker B3 aluminium

Pure white + dialog RC-L/J Merten M-Star chrome

Pure white Jung A creation glass grey-blue

Aluminium Berker B7 glass alu

Pure white + dialog RC-L/J Berker B7 glass white

Aluminium + dialog RC-L/J Merten M-Plan Glas silver

dialog RC-LCDPure white

Gira E2

Radio sensors see page 52

Aluminium Gira Esprit glass black

Pure white + dialog RC-L/J Merten M-Star chrome

Page 46: spega e.control catalogue 2014

46

Specification Order No.Figure Technical data

231 505 W 231 505 B 231 505 A

Model: pure white anthracite aluminium

Network:TP/FT-10 (FTT10)

Power supply:24V AC/DC, max. 65mA

Metrics/Mounting:(HxWxD) 71 x 71 x 49mmin cavity wall or flush mounting sockets

clima LCDLON LCD Room control panel with 4 digital inputs

Control panel with temperature sensor, LCD and 4 buttons for setpoint or fan speed adjustment and presence

4 inputs for floating contacts, e.g. light or sunblind switches, window contacts or presence detectors

Available in 3 colours, suitable for - Berker S1, B1, B3, B7 glass - Gira System 55 (E2, Event, Esprit) - Jung Series A 500, AS500 - Merten System M (1-M, M-xxx)

Application with room climate con-troller according to LonMark and VDI 3813-2, complies with BAC Efficiency Class A (EN 15232)

231 302 W 231 302 B 231 302 A 231 303 W 231 303 B 231 303 A 231 304 W 231 304 B 231 304 A 231 305 W 231 305 B 231 305 A

w/o buttons pure white anthracite aluminium Presence pure white anthracite aluminium Fan speed pure white anthracite aluminiumPresence/fan pure white anthracite aluminium

Network / Power supply:TP/FT-10 (FTT10)24V AC/DC, max. 60mA

Metrics/Mounting:(HxWxD) 70 x 70 x 49mm

clima RCMLON Room control panel with 4 digital inputs

Control panel with temperature sensor, setpoint adjuster and max. 2 buttons for fan speed adjustment and presence

4 inputs for floating contacts, e.g. light or sunblind switches, window contacts or presence detectors

Available in 3 colours, suitable for - Berker S1, B1, B3, B7 glass - Gira System 55 (E2, Event, Esprit) - Jung Series A 500, AS500 - Merten System M (1-M, M-xxx)

Application with room climate con-troller according to LonMark and VDI 3813-2, complies with BAC Efficiency Class A (EN 15232)

Standard 55 Room controllers

231 312 W 231 312 B 231 312 A 231 313 W 231 313 B 231 313 A 231 314 W 231 314 B 231 314 A 231 315 W 231 315 B 231 315 A

w/o buttons pure white anthracite aluminium Presence pure white anthracite aluminium Fan speed pure white anthracite aluminiumPresence/fan pure white anthracite aluminium

Network / Power supply:TP/FT-10 (FTT10)24V AC/DC, max. 60mA

Metrics/Mounting:(HxWxD) 70 x 70 x 49mm

clima RCM-rHLON Room control panel with hu-midity sensor and 4 digital inputs

Control panel with temperature and rel. humidity sensor, setpoint adjuster and max. 2 buttons for fan speed adjustment and presence

4 inputs for floating contacts, e.g. light or sunblind switches, window contacts or presence detectors

Available in 3 colours, suitable for - Berker S1, B1, B3, B7 glass - Gira System 55 (E2, Event, Esprit) - Jung Series A 500, AS500 - Merten System M (1-M, M-xxx)

Application with room climate con-troller according to LonMark and VDI 3813-2, complies with BAC Efficiency Class A (EN 15232)

Page 47: spega e.control catalogue 2014

47

Specification Order No.Figure Technical data

231 301 W 231 301 B 231 301 A

Model: pure white anthracite aluminium

Network:TP/FT-10 (FTT10)

Power supply:24V AC/DC, max. 60mA

Metrics/Mounting:(HxWxD) 70 x 70 x 49mmin cavity wall or flush mounting sockets

clima ROLON Temperature controller for pu-blic buildings with 4 digital inputs

Continuous-action controller with temperature sensor and 2 LEDs for energy level and activity

4 inputs for floating contacts, e.g. light or sunblind switches, window contacts or presence detectors

Available in 3 colours, suitable for all USB/TAE cover plates of the following manufacturers: Berker, Busch-Jaeger, Gira, Jung, Merten, Peha and Siemens (cover plate not included)

Application according to LonMark and VDI 3813-2, complies with BAC Efficiency Class A (EN 15232)

Standard 55 Room controllers / push button interface

211 006 Clumina T6 LON Push button interface

Compact flush mounting device connecting installation push buttons to LON networks for lighting or sunblind control, scene re-calling or log-on/-off

6 inputs for floating contacts

2 outputs 24V, 100mA for control lamps, relays etc.

Suitable for all installation push buttons, fits into deep flush mou-ting or cavity wall socket

Network:TP/FT-10 (FTT10)

Power supply:24V AC/DC, max. 50mA (w/o outputs)

Metrics/mounting:(HxWxD) 50 x 50 x 20mmIn cavity wall or flush mounting sockets

NO / NC

6x

Scale of images approx. 1:3

Page 48: spega e.control catalogue 2014

48

RC series - wireless freedom without batteries

Modern office environments rely on flexible adaptability in room design. That means that walls are no longer fixed in place, but rather adapt to workplace organisation. This variability is supported perfectly by battery-free sensors in the e.control room automation system. Room temperature and humidity sensors, with or without settings options and buttons for operating the lighting or sunshade, can be mounted on any smooth surface – either with adhesive or screwed in place. No installation socket is required.

Flexibility with EnOcean The advantages

Battery-free EnOcean technology provides flexibility

Control devices and sensors matching all switch designs

Radio receiver with optional mag-netic foot antenna for difficult installation situations

Multisensor with built-in radio receiver as complete room con-troller for HVAC, lighting and sun protection

In addition to spega’s modern nova design in glossy white, black or aluminium, control devices in Standard 55 dimensions are also

Wide variety of design

The dialog RC-E is a receiver for up to 32 radio sensors, which converts the trans-mitted information into LON packets and provides them to other devices for further processing. Its mobile antenna provides it with a great deal of freedom during installa-tion. Even installation outside the optimum reception area, for example in suspended ceilings, is no problem thanks to the option-al magnetic foot antenna.

dialog RC-E receiver

available in three matte colours pure white, anthracite and aluminium for combination with the latest switch designs from Berker, Gira, Jung or Merten. Single or multiple frames can also be used.

The lumina MS4/RC multisensor represents an entirely new kind of integration of radio control devices and sensors. Mounted on the ceiling, it not only receives packets from the radio control devices and sensors mounted in the room, but also has the same innovative presence and light level meas-urement system as its little brother the lumina MS4 (see p. 56). Since it therefore has all the sensor data for an entire room, the multisensor can act as a complete room regulator, which can handle not only regula-tion of the room temperature, but also sup-port from the sunshade and constant light regulation. As a result, the multisensor has all LonMark functional objects used in the universal room control devices (see p. 32), so it meets all the requirements of EN 15232 BAC efficiency class A in a single device.

lumina MS4/RC multisensor

RC-GMS4/RC

RC-TSRC-N2

RC-G

RC-TSRC-N2

RC-G

RC-TSRC-N2

MS4/RC MS4/RC

RC-G

RC-TSRC-N2

RC-G

RC-TSRC-N2

RC-G

RC-TSRC-N2

RC-E

Perfect for common areas: dialog RC-E receives telegrams from up to 32 wireless sensors

Perfect for flexible offices: lumina MS4/RC handles the room‘s sensors

Page 49: spega e.control catalogue 2014

49

Specification Order No.Figure Technical data

EnOcean radio receivers

911 313 Wlumina MS4/RC-EB LON Multisensor w. radio receiver

Combination of presence detector, two light sensors, IR receiver and EnOcean radio receiver

Input for passive temperature sensors (Pt1000, Ni1000) or other lumina PM for range extension

Application supports occpuancy evaluation, constant light control, thermal control and room climate control functions according to VDI 3813-2 and BAC Efficiency class A (EN 15232)

Model: pure white

Network / power supply:TP/FT-10 (FTT10)24V AC/DC, max. 80mA

Radio frequency/technology:868.3 MHz (EnOcean)

Metrics: (ØxD) 83 x 65mm Fitting dimensions (ØxD): 68 x 45mm

Further specifications:as lumina MS4, see p. 57

911 314 Wlumina MS4/RC-AP LON Multisensor w. radio receiver

Same as above but with surface-mounted housing

Ceiling mounting via screw holes Cable entries rearward or sideward

with cable duct 20 x 20mm

Model: pure white

Network / power supply:TP/FT-10 (FTT10)24V AC/DC, max. 80mA

Radio frequency/technology:868.3 MHz (EnOcean)

Metrics: (Ø x D) 89 x 80mm

Further specifications:as lumina MS4, see p. 57

441 301dialog RC-E LON Radio receiver

Radio receiver for converting En-Ocean telegrams to LON mes-sages via LonMark objects

32 wireless push buttons or sen-sors assignable

Application supports following functions: temperature measure-ment, window monitoring, signal presence, adjust light and suns-hade, adjust setpoint and scene management

Network:TP/FT-10 (FTT10)

Radio frequency/technology:868.3 MHz (EnOcean) with omni-directional antenna

Power supply:24V DC, max. 30mA

Metrics/mounting: (HxWxD) 120 x 80 x 42mm, on-wall mounting

412 906dialog RC-A Magnetic base antenna

Magnetic base antenna for dialog RC-E when installed in lowered ceilings etc.

Replaces the standard omni-direc-tional antenna

Cable length:2.5 m

Radio frequency868.3 MHz

Metrics of antenna: (Ø x H) 29 x 88mm

Page 50: spega e.control catalogue 2014

50

Specification Order No.Figure Technical data

nova Radio sensors

442 623 W 442 623 B 442 623 A442 624 W 442 624 B 442 624 A

Setpoint: pure white black aluminium Setpoint/fan: pure white black aluminium

Radio frequency/technology/range:868.3 MHz (EnOcean), battery-free, photovoltaic (>200lx@3h),max. 30m inside

Metrics/mounting:(HxWxD) 71 x 71 x 20mmadhere or screw on all plane surfaces

nova RC-LCD-rHWireless LCD room control device with humidity sensor

Permanent display and periodic transmission of room temperature, relative humidity, setpoint offset and fan speed (optional)

Bi-directional operation with dialog RC-E and lumina MS4/RC

Adhesive or screw mounting on plane surfaces

Available in 3 colours for nova design, frame not includedSuitable frames on page 43

442 611 W 442 611 B 442 611 A

Model: pure white black aluminium

Radio frequency/technology:868.3 MHz (EnOcean), battery-free, photovoltaic (>200lx@3h)

Range:max. 30m inside

Metrics/mounting:(HxWxD) 71 x 71 x 20mmadhere or screw on all plane surfaces

nova RC-TSWireless room temperature sensor with setpoint adjuster

Sensor for periodic transmission of room temperature and setpoint offset

Compatible with radio receivers dialog RC-E and lumina MS4/RC

Adhesive or screw mounting on plane surfaces

Available in 3 colours for nova design, frame not included

Suitable frames on page 43

442 621 W 442 621 B 442 621 A

Model: pure white black aluminium

Radio frequency/technology:868.3 MHz (EnOcean), battery-free, photovoltaic (>200lx@3h)

Range:max. 30m inside

Metrics/mounting:(HxWxD) 71 x 71 x 20mmadhere or screw on all plane surfaces

nova RC-TS-rHWireless room temperature and hu-midity sensor w/ setpoint adjuster

Sensor for periodic transmission of room temperature, relative humidi-ty and setpoint offset

Compatible with radio receivers dialog RC-E and lumina MS4/RC

Adhesive or screw mounting on plane surfaces

Available in 3 colours for nova design, frame not included

Suitable frames on page 43

442 613 W 442 613 B 442 613 A442 614 W 442 614 B 442 614 A

Setpoint: pure white black aluminium Setpoint/fan: pure white black aluminium

Radio frequency/technology/range:868.3 MHz (EnOcean), battery-free, photovoltaic (>200lx@3h),max. 30m inside

Metrics/mounting:(HxWxD) 71 x 71 x 20mmadhere or screw on all plane surfaces

nova RC-LCDWireless LCD room control device

Permanent display and periodic transmission of room tempera-ture, setpoint offset and fan speed (optional)

Bi-directional operation with dialog RC-E and lumina MS4/RC

Adhesive or screw mounting on plane surfaces

Available in 3 colours for nova design, frame not included

Suitable frames on page 43

Page 51: spega e.control catalogue 2014

51

Specification Order No.Figure Technical data

442 610 W 442 610 B 442 610 A442 620 W442 620 B442 620 A

RC-T: pure white black aluminiumRC-T-rH: pure white black aluminium

Radio frequency/technology/range:868.3 MHz (EnOcean), battery-free, photovoltaic (>200lx@3h),max. 30m inside

Metrics/mounting:(HxWxD) 71 x 71 x 20mmadhere or screw on all plane surfaces

nova RC-T(-rH)Wireless room temperature sensor

Sensor for periodic transmission of room temperature and rel. humidity (only nova RC-T-rH)

Compatible with radio receivers dialog RC-E and lumina MS4/RC

Adhesive or screw mounting on plane surfaces

Available in 3 colours for nova design, frame not included

nova RC-L1 / RC-J1 / RC-N1Wireless push rocker 1-gang

Sensor transmits push events for one group of lights or sunblinds

Compatible with radio receivers dialog RC-E and lumina MS4/RC

Adhesive or screw mounting on plane surfaces

Available in 3 colours for nova design, frame not included

RC-L1 ( 0 / I ) pure white gl. black gl. aluminiumRC-J1 (/) pure white gl. black gl. aluminium RC-N1 neutral pure white gl. black gl. aluminium

Radio frequency/technology/range:868.3 MHz (EnOcean), battery-free, elec-trodynamic, max. 30m inside

Metrics:(HxWxD) 71 x 71 x 15mm

442 601 W 442 601 B 442 601 A442 605 W 442 605 B 442 605 A442 603 W 442 603 B 442 603 A

RC-L2 ( 0 / I ) pure white gl. black gl. aluminiumRC-J2 (/) pure white gl. black gl. aluminium RC-N2 neutral pure white gl. black gl. aluminium

Radio frequency/technology/range:868.3 MHz (EnOcean), battery-free, elec-trodynamic, max. 30m inside

Metrics:(HxWxD) 71 x 71 x 15mm

442 602 W 442 602 B 442 602 A442 606 W 442 606 B 442 606 A442 607 W 442 607 B 442 607 A

nova RC-L2 / RC-J2 / RC-N2Wireless push rocker 2-gang

Sensor transmits push events for two groups of lights or sunblinds

Compatible with radio receivers dialog RC-E and lumina MS4/RC

Adhesive or screw mounting on plane surfaces

Available in 3 colours for nova design, frame not included

Suitable frames on page 43

Suitable frames on page 43

Suitable frames on page 43

Suitable frames on page 43 Scale of images approx. 1:3

RC-HC pure white gl. black gl. aluminium

Radio frequency/technology/range:868.3 MHz (EnOcean), battery-free, elec-trodynamic, max. 30m inside

Metrics:(HxWxD) 71 x 71 x 25mm

442 609 W 442 609 B 442 609 A

nova RC-HCWireless hotel card switch

Sensor transmits insertion and removal of hotel cards

Compatible with radio receivers dialog RC-E and lumina MS4/RC

Adhesive or screw mounting on plane surfaces

Available in 3 colours for nova design, frame not included

nova Radio push buttons

Page 52: spega e.control catalogue 2014

52

Specification Order No.Figure Technical data

442 511 W 442 511 B 442 511 A

dialog RC-TSWireless room temperature sensor with setpoint adjuster

Sensor for periodic transmission of room temperature and setpoint offset

Compatible with radio receivers dialog RC-E and lumina MS4/RC

Adhesive or screw mounting on plane surfaces

Available in 3 colours, suitable for all 55mm frames (see above)

Model: pure white anthracite aluminium

Radio frequency/technology:868.3 MHz (EnOcean), battery-free, photovoltaic (>200lx@3h)

Range:max. 30m inside

Metrics/mounting:(HxWxD) 71 x 71 x 20mmadhere or screw on all plane surfaces

Standard 55 Radio sensors

442 521 W 442 521 B 442 521 A

dialog RC-TS-rHWireless room temperature and hu-midity sensor w/ setpoint adjuster

Sensor for periodic transmission of room temperature, relative humidi-ty and setpoint offset

Compatible with radio receivers dialog RC-E and lumina MS4/RC

Adhesive or screw mounting on plane surfaces

Available in 3 colours, suitable for all 55mm frames (see above)

Model: pure white anthracite aluminium

Radio frequency/technology:868.3 MHz (EnOcean), battery-free, photovoltaic (>200lx@3h)

Range:max. 30m inside

Metrics/mounting:(HxWxD) 71 x 71 x 20mmadhere or screw on all plane surfaces

442 523 W 442 523 B 442 523 A442 524 W 442 524 B 442 524 A

dialog RC-LCD-rHWireless LCD room control device with humidity sensor

Permanent display and periodic transmission of room temperature, relative humidity, setpoint offset and fan speed (optional)

Bi-directional operation with dialog RC-E and lumina MS4/RC

Adhesive or screw mounting on plane surfaces

Available in 3 colours, suitable for all type 55 frames (see above)

Setpoint: pure white anthracite aluminium Setpoint/fan: pure white anthracite aluminium

Radio frequency/technology/range:868.3 MHz (EnOcean), battery-free, photovoltaic (>200lx@3h),max. 30m inside

Metrics/mounting:(HxWxD) 71 x 71 x 20mmadhere or screw on all plane surfaces

dialog RC-LCDWireless LCD room control device

Permanent display and periodic transmission of room tempera-ture, setpoint offset and fan speed (optional)

Bi-directional operation with dialog RC-E and lumina MS4/RC

Available in 3 colours, suitable for - Berker S1, B1, B3, B7 glass - Gira System 55 (E2, Event, Esprit) - Jung Series A 500, AS500 - Merten System M (1-M, M-xxx)

442 513 W 442 513 B 442 513 A442 514 W 442 514 B 442 514 A

Setpoint: pure white anthracite aluminium Setpoint/fan: pure white anthracite aluminium

Radio frequency/technology/range:868.3 MHz (EnOcean), battery-free, photovoltaic (>200lx@3h),max. 30m inside

Metrics/mounting:(HxWxD) 71 x 71 x 20mmadhere or screw on all plane surfaces

Page 53: spega e.control catalogue 2014

53

Specification Order No.Figure Technical data

442 510 W 442 510 B 442 510 A

Model: pure white anthracite aluminium

Radio frequency/technology:868.3 MHz (EnOcean), battery-free, photovoltaic (>200lx@3h)

Range:max. 30m inside

Metrics/mounting:(HxWxD) 71 x 71 x 20mmadhere or screw on all plane surfaces

dialog RC-TWireless room temperature sensor

Sensor for periodic transmission of room temperature

Compatible with radio receivers dialog RC-E and lumina MS4/RC

Adhesive or screw mounting on plane surfaces

Available in 3 colours, suitable for - Berker S1, B1, B3, B7 glass - Gira System 55 (E2, Event, Esprit) - Jung Series A 500, AS500 - Merten System M (1-M, M-xxx)

dialog RC-L1 / RC-J1 / RC-N1Wireless push rocker 1-gang

Sensor transmits push events for one group of lights or sunblinds

Compatible with radio receivers dialog RC-E and lumina MS4/RC

Adhesive or screw mounting on plane surfaces

Available in 3 colours, suitable for - Berker S1, B1, B3, B7 glass - Gira System 55 (E2, Event, Esprit) - Jung Series A 500, AS500 - Merten System M (1-M, M-xxx)

RC-L1 ( 0 / I ) pure white anthracite aluminiumRC-J1 (/) pure white anthracite aluminium RC-N1 neutral pure white anthracite aluminium

Radio frequency/technology/range:868.3 MHz (EnOcean), battery-free, elec-trodynamic, max. 30m inside

Metrics:(HxWxD) 71 x 71 x 15mm

442 501 W 442 501 B 442 501 A442 505 W 442 505 B 442 505 A442 503 W 442 503 B 442 503 A

RC-L2 ( 0 / I ) pure white anthracite aluminiumRC-J2 (/) pure white anthracite aluminium RC-N2 neutral pure white anthracite aluminium

Radio frequency/technology/range:868.3 MHz (EnOcean), battery-free, elec-trodynamic, max. 30m inside

Metrics:(HxWxD) 71 x 71 x 15mm

442 502 W 442 502 B 442 502 A442 506 W 442 506 B 442 506 A442 507 W 442 507 B 442 507 A

dialog RC-L2 / RC-J2 / RC-N2Wireless push rocker 2-gang

Sensor transmits push events for two groups of lights or sunblinds

Compatible with radio receivers dialog RC-E and lumina MS4/RC

Adhesive or screw mounting on plane surfaces

Available in 3 colours, suitable for - Berker S1, B1, B3, B7 glass - Gira System 55 (E2, Event, Esprit) - Jung Series A 500, AS500 - Merten System M (1-M, M-xxx)

Scale of images approx. 1:3

Standard 55 Radio sensors and push buttons

442 520 W 442 520 B 442 520 A

Model: pure white anthracite aluminium

Radio frequency/technology:868.3 MHz (EnOcean), battery-free, photovoltaic (>200lx@3h)

Range:max. 30m inside

Metrics/mounting:(HxWxD) 71 x 71 x 20mmadhere or screw on all plane surfaces

dialog RC-T-rHWireless room temperature and rel. humidity sensor

Sensor for periodic transmission of room temperature and relative humidity

Compatible with radio receivers dialog RC-E and lumina MS4/RC

Adhesive or screw mounting on plane surfaces

Available in 3 colours, suitable for all 55mm frames (see above)

Page 54: spega e.control catalogue 2014

54

Specification Order No.Figure Technical data

apera RC-FWireless window contact

Magnetic contact for monitoring window or door status

Compatible with radio receivers dialog RC-E and lumina MS4/RC

Adhesive or screw mounting on plane surfaces

Model: white

Radio frequency/technology:868.3 MHz (EnOcean)

Range:max. 30m inside

Power supply:photovoltaic (>200lx@3h), battery-free

Metrics/mounting (HxWxD):Transmitter 110 x 19 x 15mmMagnet 15 x 10 x 37mmadhere or screw on window frame

412 901 W

apera RC-G1 whiteWireless window handle

Aluminium window handle with white coating and integrated radio transmitter for monitoring the win-dow status (open, tilted, closed)

Compatible with radio receivers dialog RC-E and lumina MS4/RC

Lockable (optional)

RC-G1: without lockRC-G1 S: with lock

Radio frequency/technology:868.3 MHz (EnOcean)

Range:max. 30m inside

Power supply:electrodynamic, battery-free

Mounting:on window frameplease specify square pin length

412 902 W412 903 W

apera RC-G1 aluminiumWireless window handle

Aluminium window handle with integrated radio transmitter for mo-nitoring the window status (open, tilted, closed)

Compatible with radio receivers dialog RC-E and lumina MS4/RC

Lockable (optional)

RC-G1: without lockRC-G1 S: with lock

Radio frequency/technology:868.3 MHz (EnOcean)

Range:max. 30m inside

Power supply:electrodynamic, battery-free

Mounting:on window frameplease specify square pin length

412 902 A412 903 A

apera RC-G2 stainless steelWireless window handle

Window handle made of stainless steel with integrated radio trans-mitter for monitoring the window status (open, tilted, closed)

Compatible with radio receivers dialog RC-E and lumina MS4/RC

Lockable (optional)

RC-G2: without lockRC-G2 S: with lock

Radio frequency/technology:868.3 MHz (EnOcean)

Range:max. 30m inside

Power supply:electrodynamic, battery-free

Mounting:on window frameplease specify square pin length

412 904 VA412 905 VA

Radio window handles and contacts

Page 55: spega e.control catalogue 2014

55

Page 56: spega e.control catalogue 2014

56

lumina MS4 – multisensors consistently imagined

The advantages

High-resolution presence detec-tion with ramp-up time adaptation

Extension of the detection range by connecting presence detectors

Perfect constant light regulation using two brightness sensors and artificial light correction

Complete room climate regulation with temperature sensor connec-tion and built-in regulator

Matching infrared remote control with LCD display

The lumina MS4 multisensor is the most important “sense organ” for an energy-effi-cient building. Its sensors allow it to detect the current room parameters, the essential basis for any demand-oriented room auto- mation. Since the quality of automation also ultimately depends on the quality of the multisensor, spega has put consistent thought into the development of the new lumina MS4.

Energy efficiency demands MS4

The large lens with computer-optimised segmentation, in combination with the highly efficient PIR sensor and digital signal processing, ensures that even the smallest movements of sitting people can be reliably detected. Automatic ramp-down time adaptation also increases energy effi-ciency, since shorter occupancy times result in quicker returns to stand-by mode. For large rooms, the detection area can also be extended by connecting additional lumina PM presence detectors.

Adaptive presence detection

To meet a wide variety of requirements, the lumina MS4 multisensor has two sensors for measuring brightness. Spot measurement in a 30° angle is perfect for correct lighting of workstations. The second sensor measures integral room brightness as the total of all light coming into the lens, making it the right choice for the even lighting of traffic areas or other rooms. Since the result from both sensors can be mixed by software, even in the form of a continuous fader, the multisensor is ready for any room situation.

Artificial light correction learned by software assistant even corrects for the frequent problem of measurement results falsified by the lights themselves. For ex-ample, it can correct for indirect light from suspended light fixtures.

Variable brightness measurement

Since the lumina MS4 multisensor has a connection for a room temperature sensor (for example built into the ceiling or as a suspended sensor), it can use its integrated controller to handle room temperature reg-ulation for any heating or cooling system.

Room temperature measurement

Spot measurement for workstations Integral measurement for common rooms

Page 57: spega e.control catalogue 2014

57

Specification Order No.Figure Technical data

Multisensors

911 113 Wlumina MS4-EB LON Multisensor for suspended ceilings

Combination of presence detec-tor, two light sensors and infrared receiver

Input for passive temperature sensors (Pt1000, Ni1000) or other lumina PM for range extension (see diagram on p. 58)

Application supports occpuancy evaluation, constant light control, thermal control and room climate control functions according to VDI 3813-2 and BAC Efficiency class A (EN 15232)

Model: pure white

Network / power supply:TP/FT-10 (FTT10)24V AC/DC, max. 65mA

Optical detection (height 3m): sedentary Ø 6.0m walking Ø 12.0m

Metrics: (ØxD) 83 x 65mm Fitting dimensions (ØxD): 68 x 45mm

dialog DRC-10 Remote control for multisensors

Infrared remote control for multi-sensor lumina MS4 (see above)

Control of: - 4 groups of lights - 4 groups of blinds - setpoint offset - fanspeed - presence

Backlit LC display

Power supply:2 x 1.5V LR03 Alkaline

Life of battery:approx. 2 years

Metrics:(HxWxD) 145 x 61 x 20mm

910 112

911 114 Wlumina MS4-AP LON Multisensor for surface mounting

Same as above but with surface-mounted housing

Ceiling mounting via screw holes Cable entries rearward or sideward

with cable duct 20 x 20mm

Model: pure white

Network / power supply:TP/FT-10 (FTT10)24V AC/DC, max. 65mA

Optical detection (height 3m): sedentary Ø 6.0m walking Ø 12.0m

Metrics: (Ø x D) 89 x 80mm

Page 58: spega e.control catalogue 2014

58

Specification Order No.Figure Technical data

910 121 Wlumina PM-EB Presence detector for suspended ceilings

PIR presence detector with high sensivity for suspended ceilings

Slave output for direct connection to lumina MS4(/RC) for detection range extension

Floating contact for connection to binary input modules such as lumina Bx or lumina T6

910 122 Wlumina PM-AP Presence detector for surface mounting

Same as above but with surface-mounted housing

Ceiling mounting via screw holes Cable entries rearward or sideward

with cable duct 20 x 20mm

Model: pure white

Power supply:24V AC/DC, max. 40mA

Terminals:- Presence: float. cont., 24V, <10mA- Slave in: connecting to other lumina PM

Optical detection (height 3m): sedentary Ø 6.0m walking Ø 12.0m

Metrics: (ØxD) 89 x 80mm

Model: pure white

Power supply:24V AC/DC, max. 40mA

Terminals:- Presence: float. cont., 24V, <10mA- Slave in: connecting to other lumina PM

Optical detection (height 3m): sedentary Ø 6.0m walking Ø 12.0m

Metrics: (ØxD) 83 x 65mm Fitting dimensions (ØxD): 68 x 45mm

Presence detectors

lumina MS4

dialog DRC-10

clima T-x lumina MS4 lumina PMlumina PMlumina PM

dialog DRC-10

Connecting scheme for lumina MS4(/RC) with external temperature sensor

Connecting scheme for lumina MS4(/RC) with additional presence detectors lumina PM to extend the detection area

Page 59: spega e.control catalogue 2014

59

Specification Order No.Figure Technical data

910 210 Wclima T-EB Temperature sensor

Sensor for measuring room tempe-rature in ceiling area

For connection to multisensors lumina MS4 and MS4/RC

Model: pure white

Cable:0.25mm2 diameter1 m length (others on request)

Sensor/ range: Ni10000 ... 70°C

Metrics: (Ø x D) 30 x 37mm Fitting: 26 x 30mm (Ø x D)

clima T-PK Radiation temperature sensor

Sensor for measuring operative temperature (average of air and radiation temperature) in large rooms

For connection to multisensors lumina MS4 and MS4/RC

Cable:0.25mm2 diameter1 m length (others on request)

Sensor/ range: Ni10000 ... 70°C

Metrics: (Ø) 40mm

910 212

910 211clima T-PS Pendulum temperature sensor

Sensor for measuring sectional room temperature in large rooms

For connection to multisensors lumina MS4 and MS4/RC

Cable:0.25mm2 diameter1 m length (others on request)

Sensor/ range: Ni10000 ... 70°C

Metrics: (L x Ø) 100 x 15mm

Accessories

Page 60: spega e.control catalogue 2014

60

M series – the modular system

The M series is the modular I/O system with the widest possible variety. Up to 8 differ-ent modules with up to 24 channels can be operated from a universal controller – all, thanks to application-oriented dimension-ing of outputs, without any need for an additional amplifier component or coupling relays. In addition conventional binary and analogue inputs and outputs, all intelligent field devices with DALI, SMI or MP-Bus in-terfaces are also supported. That makes the M series unbeatably compact and enormous-ly reduces the cost and effort of wiring.

S series system distribution boxes are manufactured on a project-specific basis and are characterised by short, error-free installation and connection times on the construction site. By using plug connectors, it is also possible to provide clearly defined guarantee limits. The size of the distributor, the arrangement and position of the plug connectors, the output of the power supply and additional devices such as overvoltage protection, transformers, etc. can all be defined on a project-specific basis.

R series system distribution boxes are also manufactured on a project-specific basis, but require less coordination on the con-struction site, since they are connected using terminal blocks. They are therefore perfect for smaller construction jobs.

Everything works together e.control distribution box S

e.control distribution box R

In room automation, installation concepts with decentralised installation or system distribution boxes are increasingly popular, thanks to prefabrication and lower fire risk. Since no construction plan is identical to any other, and since the variety of field devices to be connected is always changing, the e.control M series is the perfect solution here.

To address concerns in terms of prefabrica-tion and functional reliability, spega can also deliver ready-to-use and functionally tested sheet steel system distribution box-es in two variants:

Ideal for decentralised installations

A broad cable insertion opening with ten-sion relief and foam seals makes the con-nection of wires convenient and comforta-ble. R series system distribution boxes are available in multiple sizes and offer space for additional devices.

The advantages

Connection of up to 24 field devices from any system with arbitrary controls

Supports all intelligent field devices with DALI, SMI or MP-Bus interfaces

Ideal for decentralised distribu-tors due to compact, cost-effec-tive construction

Plug-and-play system distribu-tors with functional guarantee

sistema MC MP-BusDALI SMI AC

Various combinations: up to 8 modules with 24 channels can be connected to one controller

sistema MC (p.62)sistema SV (p.98)

lumina DALx (p.63)ombra BAx-SMI (p.65)

clima AAx-MP (p.67)

DALI busSMI bus

MP bus

LON/FTRoom panels

Mains

Page 61: spega e.control catalogue 2014

61

M series – Distribution boxes

Specification Order No.Figure Technical data

System distribution box S

Sheet steel cabinet with quick re-lease fastener, accepts all e.control devices for DIN rail mounting

Applicable for installation in sus-pended ceilings or false floors

Quick and accurate mounting without opening due to plug- connectors

Project-specific shipment, ready-to-use and pre-tested

Material/protection:Sheet steel 1mm zinc plated, IP40

Plug system:Project-specific

Power supply:24V DC via external supply unit or230V AC with optional switching power supply 10/30/60/100VA

Metrics:Project-specific, minimum height 70mm

SYS-S

System distribution box R

Sheet steel cabinet mit quick re-lease fastener and cable port with strain relief, accepts all e.control devices for DIN rail mounting

Quick and accurate connection of preassembled cables due to terminal blocks

Project-specific shipment, ready-to-use and pre-tested

Material/protection:Sheet steel 1mm zinc plated, IP40

Terminal block system:Project-specific

Power supply:24V DC via external supply unit or230V AC with optional switching power supply 10/30/60/100VA

Metrics:Project-specific, minimum height 70mm

SYS-R

Page 62: spega e.control catalogue 2014

62

Output ports (Type, quantity and power)

Digital, floating contact

Input ports (Type and quantity)

sistema MC

Order No.

Network type / transceiver

Supply voltage Current consumption (max.)Metrics (HxWxD)

LON Universal controller for modular actuators for connecting M series modules with up to 24 I/O‘s

121 000

TP/FT-10 FTT10

24 V DC 40mA

Parameterisable via LNS plug-in

Controller: supported I/O ports Modules: max. claimed ports

Relay 230V AC

Control output 1-10V (current sink)

24 (any combination)

Combinability (see also pages 64-67)

85(45) x 35 x 60mm

lumina SA4

Relay module 4 x 16A with high-current contacts, suitable for electric loads, optional with hand op.

120 104 (w/o op.) 120 105 (with op.)

via controller 110mA

85(45) x 53 x 60mm

4 (16A)

lumina SA8

Relay module 8 x 10A with high-current contacts, suitable for electric loads, optional with hand op.

120 108 (w/o op.) 120 109 (with op.)

via controller 200mA

85(45) x 70 x 60mm

8 (10A)

Controller Relay modules

DALI groups (max. number of devices)

4 8

Sensor or actuator type (symbol)

Input modulelumina BE8

Digital input 8 ports for floating contacts (e.g. window contacts, dew point or occup. sensors)

via controller 60mA

110 008

8

85(45) x 70 x 60mm

NO / NC

8

Presence detection Window monitoring

Dew point monitoringLight actuator

Control drive actuator

VDI 3813-2 Functions

Sensor functions

Actuator functions

Application functions Priority control Room utilisation control (Stairwell) Light control

Manipulated value limiting

Light actuator Control drive actuator

Priority control Room utilisation control (Stairwell) Light control

Manipulated value limiting

M series – Lighting modules

Page 63: spega e.control catalogue 2014

63

4 (max. 64 DALI devices)

DALI Controller 4 groups control and supply of 64 DALI devices in 4 groups

120 164

via controller 200mA

85(45) x 70 x 60mm

lumina DAL4

Control output 4 x 1-10V with 4 relays, suitable for electronic ballasts for fluorescent lamps

120 144 (w/o op.) 120 145 (with op.)

via controller 160mA

85(45) x 70 x 60mm

4 (10A)

lumina ST4

4

4 (40mA)

8 (max. 64 DALI devices)

DALI Controller 8 groups control and supply of 64 DALI devices in 8 groups

120 168

via controller 200mA

85(45) x 70 x 60mm

lumina DAL8

16 (max. 64 DALI devices)

DALI Controller 16 groups control and supply of 64 DALI devices in 16 groups

120 166

via controller 200mA

85(45) x 70 x 60mm

lumina DAL16

D A L I D A L ID A L I

Light actuator

Priority control Room utilisation control (Stairwell) Light control

Light actuator

Priority control Room utilisation control (Stairwell) Light control

Light actuator

Priority control Room utilisation control (Stairwell) Light control

Light actuator

Priority control Room utilisation control (Stairwell) Light control

4 8 16

DALI modules

Page 64: spega e.control catalogue 2014

64

Sunblind act. 2x230VAC for motors with 3 limit switches, interlocking con-tacts, optional hand op.

85(45) x 53 x 60mm

2

M~230V AC

ombra BA2 ombra BA2-3E

Sunblind act. 4x230VAC for motors with 2 limit switches, interlocking con-tacts, optional hand op.

120 232 (w/o op.) 120 233 (with op.)

via controller40mA

85(45) x 70 x 60mm

ombra BA4

120 204 (w/o op.) 120 205 (with op.)

via controller60mA

Sunblind act. 2x230VAC for motors with 2 limit switches, interlocking con-tacts, optional hand op.

120 202 (w/o op.) 120 203 (with op.)

via controller40mA

85(45) x 53 x 60mm

2 4

M~ M~230V AC 230V AC

sistema MC

LON Universal controller for modular actuators for connecting M series modules with up to 24 I/O‘s

121 000

TP/FT-10 FTT10

24 V DC 40mA

Motor 230V AC with 2 limit switches

Motor 24V DC

Motor SMI 230V

24 (any combination)

85(45) x 35 x 60mm

Output ports (Type, quantity and power)

Controller Relay modules

Motor SMI LoVo

2 (250W)

2 (250W)

4 (250W)

Priority evaluation Room utilisation control (Stairwell) Light control

Shadow correction

Light actuator Sunshade actuatorPriority evaluation

Room utilisation control (Stairwell) Light control

Shadow correction

Light actuator Sunshade actuatorPriority evaluation

Room utilisation control (Stairwell) Light control

Shadow correction

Motor 230V AC with 3 limit switches

Light actuator Sunshade actuator

Order No.

Network type / transceiver

Supply voltage Current consumption (max.)Metrics (HxWxD)

Parameterisable via LNS plug-in

Controller: supported I/O ports Modules: max. claimed ports

Combinability (see also pages 62-63, 66-67)

Sensor or actuator type (symbol)

VDI 3813-2 Functions

Sensor functions

Actuator functions

Application functions

M series – Sunblind modules

Page 65: spega e.control catalogue 2014

65

Sunblind act. 4 x 24V DC with pole-reversing output for 4 DC motors, optional with hand operation

85(45) x 70 x 60mm

4 (1.0A)

Sunblind act. 4 x SMI for 4 groups of 230V SMI motors (broadcast), with status feedback

230V AC 1,5VA

85(45) x 70 x 60mm

4 groups (broadcast) (max. 16 motors)

4 4

M_24V DC

ombra BA4-DC ombra BA4-SMI

120 214 (w/o op.) 120 215 (with op.)

via controller110mA

120 254 (w/o op.) 120 255 (with op.)

Sunblind act. 8 x SMI for 8 groups of 230V SMI motors (addressed), with status feedback

230V AC 1,5VA

85(45) x 70 x 60mm

8 groups (addressed) (max. 16 motors)

8

ombra BA8-SMI

120 258 (w/o op.) 120 259 (with op.)

Sunbl. act. 4 x SMI LoVo for 4 groups of 24V SMI motors (broadcast), with status feedback

230V AC 1,5VA

85(45) x 70 x 60mm

4 groups (broadcast) (max. 16 motors)

4

ombra BA4-SMI LoVo

120 264 (w/o op.) 120 265 (with op.)

Sunbl. act. 8 x SMI LoVo for 8 groups of 24V SMI motors (addressed), with status feedback

230V AC 1,5VA

85(45) x 70 x 60mm

8 groups (addressed) (max. 16 motors)

8

ombra BA8-SMI LoVo

120 268 (w/o op.) 120 269 (with op.)

LoVo LoVo

Sunshade actuator

Priority evaluation Room utilisation control

Shadow correction

Sunshade actuator

Priority evaluation Room utilisation control

Shadow correction

Sunshade actuator

Priority evaluation Room utilisation control

Shadow correction

Sunshade actuator

Priority evaluation Room utilisation control

Shadow correction

Sunshade actuator

Priority evaluation Room utilisation control

Shadow correction

SMI modules

Page 66: spega e.control catalogue 2014

66

via controller240mA

85(45) x 70 x 60mm

8 (output: 20mA)

120 348

8

Analogue I/O module 8 p. with reversible channels for sensors or actuators with 0-10V or 4-20mA

clima AA4

via controller140mA

85(45) x 53 x 60mm

clima AA8-10V

Analogue input/output 0(2)-10V, 0(4)-20mA

Universal ports (Type, quantity and power)

clima AA4-10V

Digital output 4 port for 4 thermoelectric or 2 motor-driven actuators with 24V or 230V AC

via controller40mA

4 / 2 (750mA)

Analogue I/O modules

Triac 24-230V AC 2-point (PWM) / 3-point (motor)Relays 3 stage (0-I-II-III)

MP Bus devices Actuators/sensors

120 324

sistema MC

121 000

TP/FT-10 FTT10

24 V DC 40mA

85(45) x 35 x 60mm

Controller

24 (any combination)

44

Analogue I/O module 4 p. with reversible channels for sensors or actuators with 0-10V or 4-20mA

120 344

2-P/3-P

M

0-10V

M

4 (output: 20mA)

LON Universal controller for modular actuators for connecting M series modules with up to 24 I/O‘s

85(45) x 53 x 60mm

Passive analogue (Pt1000, Ni1000, NTC<25k)

Input ports (Type and quantity)

Output ports (Type, quantity and power)

Digital output modules

0-10V/4-20mA 0-10V

M

0-10V/4-20mA

Control drive actuator

VDI 3813-2 Functions

Sensor functions

Actuator functions

Application functions Priority evaluation Sequence control

Manipulated value limiting

Control drive actuator

Priority evaluation Sequence control

Manipulated value limiting

Light actuator Control drive actuator

Priority evaluation Sequence control

Manipulated value limiting

Temperature measurementAir quality measurement

Rel. humidity measurement

Temperature measurementAir quality measurement

Rel. humidity measurement

Order No.

Network type / transceiver

Supply voltage Current consumption (max.)Metrics (HxWxD)

Parameterisable via LNS plug-in

Controller: supported I/O ports Modules: max. claimed ports

Combinability (see also pages 62-65)

Sensor or actuator type (symbol)

M series – Analogue and digital I/0 modules

Page 67: spega e.control catalogue 2014

67

clima LA2-3

Multi-stage switch 230V 2 x 3 stages for two 3-speed fans with interlocking relays

via controller40mA

85(45) x 53 x 60mm

clima AA4-MP

MP-Bus Controller 4 port for 4 MP-Bus-compatible flap, valve or VAV actuators plus sensors

via controller45mA

85(45) x 53 x 60mm

120 332

2 (250W)

120 354

4 / 4

clima AA8

2 4 actuators 4 sensors

I-II-III

M~

via controller70mA

85(45) x 70 x 60mm

8 / 4 (500mA)

8

Digital output 8 port for 8 thermoelectric or 4 motor-driven actuators with 24V or 230V AC

120 328

2-P/3-P

M

Light actuator Control drive actuator

Priority evaluation Sequence control

Manipulated value limiting

Control drive actuator

Priority evaluation Sequence control

Manipulated value limiting

Control drive actuator

Priority evaluation Sequence control

Manipulated value limiting

Temperature measurementAir quality measurement

Rel. humidity measurement

clima AA8-MP

MP-Bus Controller 8 port for 8 MP-Bus-compatible flap, valve or VAV actuators plus sensors

via controller45mA

85(45) x 53 x 60mm

120 358

8 / 8

8 actuators 8 sensors

Control drive actuator

Priority evaluation Sequence control

Manipulated value limiting

Temperature measurementAir quality measurement

Rel. humidity measurement

MP-Bus modules

Page 68: spega e.control catalogue 2014

68

R series – widest selection for distribution boards

In the R series, e.control offers an exten-sive line of LON actuators for distribution boards. They include both binary and analogue inputs and outputs, as well as actuators for intelligent field devices for all functions in room automation, with up to 32 channels.

The R series also offers a comprehensive actuator program for sun protection tech-nology, with 230V blind drives with 2 or 3 limit switches, 24V direct-current motors, and SMI or SMI LoVo drives. For convention-al motors, actuators are available with 4, 8 or 12 outputs, while the SMI actuators can even control up to 32 SMI drives. Status responses from motors are available to the building control system, just as for DALI. All actuators manage perfect positioning of the sunblind in any intermediate position and at any slat angle, and in combination with the ombra BST slat tracking controller are suit-able for slat tracking control and shadow correction. They can also handle the prior-ity-dependent management of movement commands for weather protection and even complete automation functions.

Field devices in HVAC systems can be connected to the extensive analogue and digital I/O actuator line of the R series. This

Modules for all systems Sunblind actuators

HVAC actuators

The R series offers suitable actuators for all lighting technologies, whether switched with high-voltage relays, with 1-10V inter-faces, dimmed with universal dimmers or controlled via DALI. And all that with 4, 8, 12 or 16 channels. DALI actuators can even operate up to 128 lights in up to 32 groups. Bidirectional communication between the DALI controllers and the actuator even permits the detection of lamp failures and other conditions. All actuators have param-eterisable lights-on and lights-off delays, stairway automation and integrated scene administration.

Lighting actuators

includes both inputs for 0-10V or 4-20mA signals as well as outputs for all types of positioning drives with 4 to 16 channels. Every output has functions for position limitation, calibration and valve service to prevent freezing. The MP-Bus actuator permits up to 16 bus-capable positioning drives to be positioned, their response and status values evaluated and also values to be read out from measurement sensors connected to the positioning drives.

The advantages

Widest selection of actuators with 4 to 32 channels for all systems

Actuators for DALI, SMI and MP-Bus field devices

Manual operation optional

Ideal for installation in local networks

Page 69: spega e.control catalogue 2014

69

Specification Order No.Figure Technical data

Switch actuators

121 104 121 105

lumina RSA4 LON Switch actuator 4 ports, 16A

Relay module for independent switching of 4 electric loads with separate feed-in for each output

High-current relay contacts (120A) for capacitive lamp loads: incandiscent lamps: 3000W halogen lamps: 2500W fluorescent lamps: 1500W comp.

Stairwell lighting, switch-on/off delay and scene memory with 10 scenes per channel

RSA4 w/o hand operationRSA4-b with hand operation Network/power supply:Type: TP/FT-10 (FTT10)Voltage: 24V DC, max. 150mA

Metrics/mounting: (HxWxD) 85(45) x 88 x 60mmDIN rail mounting

121 108 121 109

lumina RSA8 LON Switch actuator 8 ports, 10A

Relay module for independent switching of 8 electric loads with separate feed-in for 2 outputs

High-current relay contacts (120A) for capacitive lamp loads: incandiscent lamps: 2000W halogen lamps: 1700W fluorescent lamps: 1000W comp.

Stairwell lighting, switch-on/off delay and scene memory with 10 scenes per channel

RSA8 w/o hand operationRSA8-b with hand operation Network/power supply:Type: TP/FT-10 (FTT10)Voltage: 24V DC, max. 240mA

Metrics/mounting: (HxWxD) 85(45) x 105 x 60mmDIN rail mounting

121 112 121 113

lumina RSA12 LON Switch actuator 12 ports, 16A

Relay module for independent switching of 12 electric loads with separate feed-in for each output

High-current relay contacts (120A) for capacitive lamp loads: incandiscent lamps: 3000W halogen lamps: 2500W fluorescent lamps: 1500W comp.

Stairwell lighting, switch-on/off delay and scene memory with 10 scenes per channel

RSA12 w/o hand operationRSA12-b with hand operation Network/power supply:Type: TP/FT-10 (FTT10)Voltage: 24V DC, max. 370mA

Metrics/mounting: (HxWxD) 85(45) x 192 x 60mmDIN rail mounting

121 116 121 117

lumina RSA16 LON Switch actuator 16 ports, 10A

Relay module for independent switching of 16 electric loads with separate feed-in for 2 outputs

High-current relay contacts (120A) for capacitive lamp loads: incandiscent lamps: 2000W halogen lamps: 1700W fluorescent lamps: 1000W comp.

Stairwell lighting, switch-on/off delay and scene memory with 10 scenes per channel

RSA16 w/o hand operationRSA16-b with hand operation Network/power supply:Type: TP/FT-10 (FTT10)Voltage: 24V DC, max. 440mA

Metrics/mounting: (HxWxD) 85(45) x 175 x 60mmDIN rail mounting

4x

8x

12x

16x

Page 70: spega e.control catalogue 2014

70

Specification Order No.Figure Technical data

121 164

121 166

lumina RDAL4 LON DALI Controller 4 groups

Module for supplying and indepen-dent controlling of up to 64 DALI devices devided in up to 4 groups

Monitoring of lamp status

Manual switch on/off operation

Commissioning via LNS plug-in or directly with notebook

Stairwell lighting, switch-on/off delay, variable dimming ramp and scene memory for 10 scenes

lumina RDAL16 LON DALI Controller 16 groups

Module for supplying and indepen-dent controlling of up to 64 DALI devices devided in up to 16 groups

Monitoring of lamp status

Manual switch on/off operation

Commissioning via LNS plug-in or directly with notebook

Stairwell lighting, switch-on/off delay, variable dimming ramp and scene memory for 10 scenes

Network/power supply:Type: TP/FT-10 (FTT10)Voltage: 24V DC, max. 240mA

Load:Supply of max. 64 DALI devices

Metrics/mounting: (HxWxD) 85(45) x 105 x 60mmDIN rail mounting

Network/power supply:Type: TP/FT-10 (FTT10)Voltage: 24V DC, max. 240mA

Load:Supply of max. 64 DALI devices

Metrics/mounting: (HxWxD) 85(45) x 105 x 60mmDIN rail mounting

121 168

121 162

lumina RDAL8 LON DALI Controller 8 groups

Module for supplying and indepen-dent controlling of up to 64 DALI devices devided in up to 8 groups

Monitoring of lamp status

Manual switch on/off operation

Commissioning via LNS plug-in or directly with notebook

Stairwell lighting, switch-on/off delay, variable dimming ramp and scene memory for 10 scenes

lumina RDAL32 LON DALI Controller 32 groups

Module for supplying and indepen-dent controlling of up to 128 DALI devices devided in up to 32 groups

Monitoring of lamp status

Manual switch on/off operation

Commissioning via LNS plug-in or directly with notebook

Stairwell lighting, switch-on/off delay, variable dimming ramp and scene memory for 10 scenes

Network/power supply:Type: TP/FT-10 (FTT10)Voltage: 24V DC, max. 240mA

Load:Supply of max. 64 DALI devices

Metrics/mounting: (HxWxD) 85(45) x 105 x 60mmDIN rail mounting

Network/power supply:Type: TP/FT-10 (FTT10)Voltage: 24V DC, max. 440mA

Load:Supply of 2 lines with up to 64 DALI devices each

Metrics/mounting: (HxWxD) 85(45) x 175 x 60mmDIN rail mounting

4x

16x

8x

32x

D A L I

D A L I

D A L I

D A L I

DALI Lighting controllers

Page 71: spega e.control catalogue 2014

71

Specification Order No.Figure Technical data

121 144 121 145

lumina RST4 LON Control output 1-10V, 4 ports

Module for independent switching and dimming of 4 groups of elec-tronic ballasts with 1-10V interface

High current relay contacts (120A) for fluorescent lamps with max. 1000W (comp.) per channel

Stairwell lighting, switch-on/off delay, variable dimming ramp and scene memory with 10 scenes per channel

RST4 w/o hand operationRST4-b with hand operation Network/power supply:Type: TP/FT-10 (FTT10)Voltage: 24V DC, max. 200mA

Metrics/mounting: (HxWxD) 85(45) x 105 x 60mmDIN rail mounting

121 148 121 149

lumina RST8 LON Control output 1-10V, 8 ports

Module for independent switching and dimming of 8 groups of elec-tronic ballasts with 1-10V interface

High current relay contacts (120A) for fluorescent lamps with max. 1000W (comp.) per channel

Stairwell lighting, switch-on/off delay, variable dimming ramp and scene memory with 10 scenes per channel

RST8 w/o hand operationRST8-b with hand operation Network/power supply:Type: TP/FT-10 (FTT10)Voltage: 24V DC, max. 360mA

Metrics/mounting: (HxWxD) 85(45) x 175 x 60mmDIN rail mounting

1-10V

1-10V

4x

8x

1-10V Lighting controllers and dimmers

121 152lumina RDA2-UNLON Universal dimmer 2 x 570W

2 port universal dimmer for incan-discent lamps, high-voltage halo-gen lamps or low-voltage halogen lamps with wound or electronic transformers

Automatic load detection and overload protection

Stairwell lighting, switch-on/off delay, variable dimming ramp and scene memory for each channel

Network:TP/FT-10 (FTT10)

Power supply:24V AC/DC, max. 40mA

Load:2 x 10... 570VA or 1 x 10...1140VA resistive, inductive or capacitive load with auto-detection

Metrics/mounting:(HxWxD) 90 x 123 x 50mmDIN rail mounting

121 154lumina RDA4-UNLON Universal dimmer 4 x 570W

4 port universal dimmer for incan-discent lamps, high-voltage halo-gen lamps or low-voltage halogen lamps with wound or electronic transformers

Automatic load detection and overload protection

Stairwell lighting, switch-on/off delay, variable dimming ramp and scene memory for each channel

Network:TP/FT-10 (FTT10)

Power supply:24V AC/DC, max. 40mA

Load:4 x 10... 570VA or 2 x 10...1140VA resistive, inductive or capacitive load with auto-detection

Metrics/mounting:(HxWxD) 90 x 210 x 50mmDIN rail mounting

R,L,C

2x

R,L,C

4x

Page 72: spega e.control catalogue 2014

72

Specification Order No.Figure Technical data

121 202 121 203

ombra RBA2 LON Sunblind actuator 2 ports

Relay module for 2 AC motors for sunblinds, shutters or windows

Max. motor power 250W, inter- locked contacts and separate feed-in for each port

Appropriate to slat tracking and shadow correction control

Parameterisable power-on and protection behaviour as well as scene memory for each channel

RBA2 w/o hand operationRBA2-b with hand operation

Network/power supply:Type: TP/FT-10 (FTT10)Voltage: 24V DC, max. 80mA

Metrics/mounting: (HxWxD) 85(45) x 88 x 60mmDIN rail mounting

121 204 121 205

ombra RBA4 LON Sunblind actuator 4 ports

Relay module for 4 AC motors for sunblinds, shutters or windows

Max. motor power 250W, inter- locked contacts and separate feed-in for each port

Appropriate to slat tracking and shadow correction control

Parameterisable power-on and protection behaviour as well as scene memory for each channel

RBA4 w/o hand operationRBA4-b with hand operation

Network/power supply:Type: TP/FT-10 (FTT10)Voltage: 24V DC, max. 100mA

Metrics/mounting: (HxWxD) 85(45) x 105 x 60mmDIN rail mounting

121 208 121 209

ombra RBA8 LON Sunblind actuator 8 ports

Relay module for 8 AC motors for sunblinds, shutters or windows

Max. motor power 250W, inter- locked contacts and separate feed-in for each port

Appropriate to slat tracking and shadow correction control

Parameterisable power-on and protection behaviour as well as scene memory for each channel

RBA8 w/o hand operationRBA8-b with hand operation

Network/power supply:Type: TP/FT-10 (FTT10)Voltage: 24V DC, max. 160mA

Metrics/mounting: (HxWxD) 85(45) x 175 x 60mmDIN rail mounting

121 212 121 213

RBA12 w/o hand operationRBA12-b with hand operation

Network/power supply:Type: TP/FT-10 (FTT10)Voltage: 24V DC, max. 220mA

Metrics/mounting: (HxWxD) 85(45) x 245 x 60mmDIN rail mounting

ombra RBA12 LON Sunblind actuator 12 ports

Relay module for 12 AC motors for sunblinds, shutters or windows

Max. motor power 250W, inter- locked contacts and separate feed-in for each port

Appropriate to slat tracking and shadow correction control

Parameterisable power-on and protection behaviour as well as scene memory for each channel

M~

M~

M~

M~

2 x

4 x

8 x

12 x

Sunblind actuators

Page 73: spega e.control catalogue 2014

73

Specification Order No.Figure Technical data

121 214 121 215

ombra RBA4-DC LON Sunblind actuator 4 ports for 24V DC motors

Relay module for 24V DC motors for sunblinds, shutters or windows

4 pole-reversing outputs for max. current of 1 A per channel, requires no separate control unit

Appropriate to slat tracking and shadow correction control

Parameterisable power-on and protection behaviour as well as scene memory for each channel

RBA4-DC w/o hand operation RBA4-DC-b with hand operation Network/power supply:Type: TP/FT-10 (FTT10)Voltage: 24V DC, max. 150mA

Metrics/mounting: (HxWxD) 85(45) x 105 x 60mmDIN rail mounting

M_4 x

121 218 121 219

ombra RBA8-DC LON Sunblind actuator 8 ports for 24V DC motors

Relay module for 24V DC motors for sunblinds, shutters or windows

8 pole-reversing outputs for max. current of 1 A per channel, requires no separate control unit

Appropriate to slat tracking and shadow correction control

Parameterisable power-on and protection behaviour as well as scene memory for each channel

RBA8-DC w/o hand operation RBA8-DC-b with hand operation Network/power supply:Type: TP/FT-10 (FTT10)Voltage: 24V DC, max. 260mA

Metrics/mounting: (HxWxD) 85(45) x 175 x 60mmDIN rail mounting

M_8 x

121 232 121 233

ombra RBA2-3E LON Sunblind actuator 2 ports for AC motors with 3 limit switches

Relay module for 2 sunblind mo-tors with 3 limit switches

Max. motor power 250W, inter- locked contacts and separate feed-in for each port

Appropriate to slat tracking and shadow correction control

Parameterisable power-on and protection behaviour as well as scene memory for each channel

RBA2-3E w/o hand operationRBA2-3E-b with hand operation

Network/power supply:Type: TP/FT-10 (FTT10)Voltage: 24V DC, max. 80mA

Metrics/mounting: (HxWxD) 85(45) x 88 x 60mmDIN rail mounting

M~

M~

2x

4x

121 234 121 235

ombra RBA4-3E LON Sunblind actuator 4 ports for AC motors with 3 limit switches

Relay module for 4 sunblind mo-tors with 3 limit switches

Max. motor power 250W, inter- locked contacts and separate feed-in for each port

Appropriate to slat tracking and shadow correction control

Parameterisable power-on and protection behaviour as well as scene memory for each channel

RBA4-3E w/o hand operationRBA4-3E-b with hand operation

Network/power supply:Type: TP/FT-10 (FTT10)Voltage: 24V DC, max. 120mA

Metrics/mounting: (HxWxD) 85(45) x 140 x 60mmDIN rail mounting

Sunblind actuators

Page 74: spega e.control catalogue 2014

74

Specification Order No.Figure Technical data

SMI Sunblind actuators

121 254121 255

121 256121 257

ombra RBA4-SMI LON SMI Sunblind actuator 4 ports

Module for accurate positioning of max. 4 groups of 230V SMI sunblind motors

Monitoring of motor status

Appropriate to slat tracking and shadow correction control due to accurate positioning control (<2°)

Parameterisable power-on and protection behaviour as well as scene memory for each channel

ombra RBA16-SMI LON SMI Sunblind act. 16 groups

Module for accurate positioning of max. 16 SMI sunblind motors 230V in up to16 user-defined groups

Monitoring of motor status

Appropriate to slat tracking and shadow correction control due to accurate positioning control (<2°)

Parameterisable power-on and protection behaviour as well as scene memory for each group

RBA4-SMI w/o hand operationRBA4-SMI-b with hand operation

Network/power supply:Type: TP/FT-10 (FTT10)Voltage: 24V DC, max. 50mA Mains: 230V AC max. 1.5W

Ports:4 SMI (broadcast), max. 16 motors

Metrics/mounting: (HxWxD) 85(45) x 105 x 60mmDIN rail mouting

RBA16-SMI w/o hand operationRBA16-SMI-b with hand operation

Network/power supply:Type: TP/FT-10 (FTT10)Voltage: 24V DC, max. 50mA Mains: 230V AC max. 1.5W

Ports:SMI (addressed), max. 16 motors

Metrics/mounting: (HxWxD) 85(45) x 105 x 60mmDIN rail mouting

121 258121 259

121 252121 253

ombra RBA8-SMI LON SMI Sunblind act. 8 groups

Module for accurate positioning of max. 16 SMI sunblind motors 230V in up to 8 user-defined groups

Monitoring of motor status

Appropriate to slat tracking and shadow correction control due to accurate positioning control (<2°)

Parameterisable power-on and protection behaviour as well as scene memory for each group

ombra RBA32-SMI LON SMI Sunblind act. 32 groups

Module for accurate positioning of max. 32 SMI sunblind motors 230V in up to 32 user-defined groups

Monitoring of motor status

Appropriate to slat tracking and shadow correction control due to accurate positioning control (<2°)

Parameterisable power-on and protection behaviour as well as scene memory for each group

RBA8-SMI w/o hand operationRBA8-SMI-b with hand operation

Network/power supply:Type: TP/FT-10 (FTT10)Voltage: 24V DC, max. 50mA Mains: 230V AC max. 1.5W

Ports:SMI (addressed), max. 16 motors

Metrics/mounting: (HxWxD) 85(45) x 105 x 60mmDIN rail mouting

RBA32-SMI w/o hand operationRBA32-SMI-b with hand operation

Network/power supply:Type: TP/FT-10 (FTT10)Voltage: 24V DC, max. 50mA Mains: 230V AC max. 3.0W

Ports:2 SMI (addressed), max. 32 motors

Metrics/mounting: (HxWxD) 85(45) x 175 x 60mmDIN rail mouting

M~

M~

M~

M~

4x

16x

8x

32x

Page 75: spega e.control catalogue 2014

75

Specification Order No.Figure Technical data

SMI LoVo Sunblind actuators

121 264121 265

121 266121 267

ombra RBA4-SMI LoVo LON SMI Sunblind actuator 4 ports

Module for accurate positioning of max. 4 groups of low-voltage SMI sunblind motors (24V)

Monitoring of motor status

Appropriate to slat tracking and shadow correction control due to accurate positioning control (<2°)

Parameterisable power-on and protection behaviour as well as scene memory for each channel

ombra RBA16-SMI LoVo LON SMI Sunblind act. 16 groups

Module for accurate positioning of max. 16 low-voltage SMI sunblind motors in user-defined groups

Monitoring of motor status

Appropriate to slat tracking and shadow correction control due to accurate positioning control (<2°)

Parameterisable power-on and protection behaviour as well as scene memory for each group

RBA4-LoVo w/o hand operationRBA4-LoVo-b with hand operation

Network/power supply:Type: TP/FT-10 (FTT10)Voltage: 24V DC, max. 50mA Mains: 230V AC max. 1.5W

Ports:4 SMI (broadcast), max. 16 motors

Metrics: (HxWxD) 85(45) x 105 x 60mm

RBA16-LoVo w/o hand operationRBA16-LoVo-b with hand operation

Network/power supply:Type: TP/FT-10 (FTT10)Voltage: 24V DC, max. 50mA Mains: 230V AC max. 1.5W

Ports:4 SMI (broadcast), max. 16 motors

Metrics: (HxWxD) 85(45) x 105 x 60mm

121 268121 269

121 262121 263

ombra RBA8-SMI LoVo LON SMI Sunblind act. 8 groups

Module for accurate positioning of max. 16 low-voltage SMI sunblind motors in 8 user-defined groups

Monitoring of motor status

Appropriate to slat tracking and shadow correction control due to accurate positioning control (<2°)

Parameterisable power-on and protection behaviour as well as scene memory for each group

ombra RBA32-SMI LoVo LON SMI Sunblind act. 32 groups

Module for accurate positioning of max. 32 low-voltage SMI sunblind motors in user-defined groups

Monitoring of motor status

Appropriate to slat tracking and shadow correction control due to accurate positioning control (<2°)

Parameterisable power-on and protection behaviour as well as scene memory for each group

RBA8-LoVo w/o hand operationRBA8-LoVo-b with hand operation

Network/power supply:Type: TP/FT-10 (FTT10)Voltage: 24V DC, max. 50mA Mains: 230V AC max. 1.5W

Ports:SMI (addressed), max. 16 motors

Metrics/mounting: (HxWxD) 85(45) x 105 x 60mmDIN rail mounting

RBA32-LoVo w/o hand operationRBA32-LoVo-b with hand operation

Network/power supply:Type: TP/FT-10 (FTT10)Voltage: 24V DC, max. 50mA Mains: 230V AC max. 3.0W

Ports:2 SMI (addressed), max. 32 motors

Metrics/mounting: (HxWxD) 85(45) x 175 x 60mmDIN rail mounting

16x

32x

M_

M_

LoVo

LoVo

4xM_

LoVo

8xM_

LoVo

Page 76: spega e.control catalogue 2014

76

Specification Order No.Figure Technical data

lumina B8 LON Digital input 8 ports

8 inputs for installation push but-tons or other devices with floating contacts (e.g. window contacts, dew point sensors or presence detectors)

Powerful application for switching and dimming lamps, controlling sunblinds and recalling or storing scenes

lumina B16 LON Digital input 16 ports

16 inputs for installation push but-tons or other devices with floating contacts (e.g. window contacts, dew point sensors or presence detectors)

Powerful application for switching and dimming lamps, controlling sunblinds and recalling or storing scenes

Network:TP/FT-10 (FTT10)

Power supply:24V DC, max. 60mA

Metrics/mounting:(HxWxD) 85(45) x 70 x 60mmDIN rail mounting

Network:TP/FT-10 (FTT10)

Power supply:24V DC, max. 160mA

Metrics/mounting:(HxWxD) 85(45) x 175 x 60mmDIN rail mounting

111 016

111 008

NO / NC

NO / NC

8x

16x

411 408lumina BK8LON Digital input module

8 inputs for push buttons or other devices with floating contacts (e.g. window contacts, dew point sensors or occupancy sensors)

Plastic case, cable entry points with strain relief, protection class IP54 (IP65 on request)

External 24V power supply via bus cable

Network:TP/FT-10 (FTT10)

Power supply:24V AC/DC, max. 65mA

Metrics: (HxWxD) 63 x 254 x 180mm

8 x

NO / NC

Digital inputs

lumina B24 LON Digital input 24 ports

24 inputs for installation push but-tons or other devices with floating contacts (e.g. window contacts, dew point sensors or presence detectors)

Powerful application for switching and dimming lamps, controlling sunblinds and recalling or storing scenes

Network:TP/FT-10 (FTT10)

Power supply:24V DC, max. 220mA

Metrics/mounting:(HxWxD) 85(45) x 245 x 60mmDIN rail mounting

111 024

NO / NC

24x

Page 77: spega e.control catalogue 2014

77

Specification Order No.Figure Technical data

121 324clima RAA4LON Digital output 4 ports

Triac outputs for 4 thermoelectric or 2 motor-driven actuators with 24 - 230V AC operating voltage

On/off, open/close or pulse width modulated operation selectable via software

Parameterisable pulse-duration, output limits and motor runtime

Automatic valve maintenance function during non-use periods

Network:TP/FT-10 (FTT10)

Power supply:24V DC, max. 80mA

Load:24-230V AC, max. 750mA per output

Metrics/mounting: (HxWxD) 85(45) x 88 x 60mmDIN rail mounting

4x

121 328clima RAA8LON Digital output 8 ports

Triac outputs for 8 thermoelectric or 4 motor-driven actuators with 24 - 230V AC operating voltage

On/off, open/close or pulse width modulated operation selectable via software

Parameterisable pulse-duration, output limits and motor runtime

Automatic valve maintenance function during non-use periods

Network:TP/FT-10 (FTT10)

Power supply:24V DC, max. 110mA

Load:24-230V AC, max. 500mA per output

Metrics/mounting: (HxWxD) 85(45) x 105 x 60mm DIN rail mounting

8x

121 322

121 326

clima RAA12LON Digital output 12 ports

Triac outputs for 12 thermoelectric or 6 motor-driven actuators with 24 - 230V AC operating voltage

On/off, open/close or pulse width modulated operation selectable via software

Parameterisable pulse-duration, output limits and motor runtime

Automatic valve maintenance function during non-use periods

clima RAA16LON Digital output 16 ports

Triac outputs for 16 thermoelectric or 8 motor-driven actuators with 24 - 230V AC operating voltage

On/off, open/close or pulse width modulated operation selectable via software

Parameterisable pulse-duration, output limits and motor runtime

Automatic valve maintenance function during non-use periods

Network:TP/FT-10 (FTT10)

Power supply:24V DC, max. 150mA

Load:24-230V AC, max. 500mA per output

Metrics/mounting: (HxWxD) 85(45) x 158 x 60mm DIN rail mounting

Network:TP/FT-10 (FTT10)

Power supply:24V DC, max. 180mA

Load:24-230V AC, max. 500mA per output

Metrics/mounting: (HxWxD) 85(45) x 175 x 60mm DIN rail mounting

12x

16x

2x

4x

6x

8x

2-P/PDM

M

3-P

M

2-P/PDM

M

3-P

M

2-P/PDM

M

2-P/PDM

M

3-P

M

3-P

M

or

or

or

or

Digital outputs

Page 78: spega e.control catalogue 2014

78

Specification Order No.Figure Technical data

4x

0-10V 0-20mA

M

8x

0-10V 0-20mA

M

12x

0-10V 0-20mA

M

121 344clima RAA4-10VLON Analogue I/O module 4 ports

Module for 4 sensors or actuators with analogue control signal

Input or output signal adjustable per channel via software: 0-10V, 2-10V, 0-20mA or 4-20mA

Parameterisable output limitation and valve maintenance function during non-use periods, change-able network variables for input signal mapping

Network/power supply:TP/FT-10 (FTT10)24V DC, max. 180mA

Output current:max. 20mA each

Input:10 bit resolution, resistance 100kΩ

Metrics: (HxWxD) 85(45) x 88 x 60mm

121 348clima RAA8-10VLON Analogue I/O module 8 ports

Module for 8 sensors or actuators with analogue control signal

Input or output signal adjustable per channel via software: 0-10V, 2-10V, 0-20mA or 4-20mA

Parameterisable output limitation and valve maintenance function during non-use periods, change-able network variables for input signal mapping

Network/power supply:TP/FT-10 (FTT10)24V DC, max. 280mA

Output current:max. 20mA each

Input:10 bit resolution, resistance 100kΩ

Metrics: (HxWxD) 85(45) x 105 x 60mm

121 342clima RAA12-10VLON Analogue I/O module 12 ports

Module for 12 sensors or actuators with analogue control signal

Input or output signal adjustable per channel via software: 0-10V, 2-10V, 0-20mA or 4-20mA

Parameterisable output limitation and valve maintenance function during non-use periods, change-able network variables for input signal mapping

Network/power supply:TP/FT-10 (FTT10)24V DC, max. 420mA

Output current:max. 20mA each

Input:10 bit resolution, resistance 100kΩ

Metrics: (HxWxD) 85(45) x 158 x 60mm

16x

0-10V 0-20mA

M

121 346clima RAA16-10VLON Analogue I/O module 16 ports

Module for 16 sensors or actuators with analogue control signal

Input or output signal adjustable per channel via software: 0-10V, 2-10V, 0-20mA or 4-20mA

Parameterisable output limitation and valve maintenance function during non-use periods, change-able network variables for input signal mapping

Network/power supply:TP/FT-10 (FTT10)24V DC, max. 500mA

Output current:max. 20mA each

Input:10 bit resolution, resistance 100kΩ

Metrics: (HxWxD) 85(45) x 175 x 60mm

0-10V 0-20mA

0-10V 0-20mA

0-10V 0-20mA

0-10V 0-20mA

4x

8x

12x

16x

or

or

or

or

Analogue inputs/outputs

Page 79: spega e.control catalogue 2014

79

Specification Order No.Figure Technical data

clima RAA4-MP LON MP-Bus Controller 4 ports

Controller module for 4 damper, flap, valve or VAV actuators with MP-Bus interface

Monitoring of actuator status

Utilisation of sensors connected to MP-Bus actuators (0-10V, resistive or floating contact)

Parameterisable output limitation and valve maintenance function, changeable network variables for input signal mapping

Network:TP/FT-10 (FTT10)

Power supply:24V DC, max. 85mA

Bus connection:Actuators: 4Sensors: 4 (via actuators)

Metrics/mounting:(HxWxD) 85(45) x 88 x 60mmDIN rail mounting

121 354

clima RAA8-MP LON MP-Bus Controller 8 ports

Controller module for 8 damper, flap, valve or VAV actuators with MP-Bus interface

Monitoring of actuator status

Utilisation of sensors connected to MP-Bus actuators (0-10V, resistive or floating contact)

Parameterisable output limitation and valve maintenance function, changeable network variables for input signal mapping

Network:TP/FT-10 (FTT10)

Power supply:24V DC, max. 85mA

Bus connection:Actuators: 8Sensors: 8 (via actuators)

Metrics/mounting:(HxWxD) 85(45) x 88 x 60mmDIN rail mounting

121 358

MP-Bus Controllers

clima RAA16-MP LON MP-Bus Controller 16 ports

Controller module for 16 damper, flap, valve or VAV actuators with MP-Bus interface

Monitoring of actuator status

Utilisation of sensors connected to MP-Bus actuators (0-10V, resistive or floating contact)

Parameterisable output limitation and valve maintenance function, changeable network variables for input signal mapping

Network:TP/FT-10 (FTT10)

Power supply:24V DC, max. 130mA

Bus connection:Actuators: 16Sensors: 16 (via actuators)

Metrics/mounting:(HxWxD) 85(45) x 140 x 60mmDIN rail mounting

121 356

Page 80: spega e.control catalogue 2014

80

Universal room controllers

e.control Room controller - Ports

I/O DL-110 RCM-CC RO-CC RCM-FC R=-FC

DWM-xx 1 - - - -

DMS-20 1 - - - -

AI Temp 2* internal internal internal internal

AI 0-10V 1 - - - -

DO float. 4 6 6 6 6

AO 0-10V 2 2 2 2 (with FCB-10V)

DO 24V 2 - - 2 (with FCB-24)

DO 230V - - - 2 (with FCB-230)

DO 3R Fan 1 - - 1

DO 230V 8A 1 - - -

e.control room controllers are first-class when it comes to room climate, because they meet all heating, cooling and climate control requirements of EN 15232 BAC effi-ciency class A. Built-in regulators support every combination of heating and cooling systems, such as radiators, heating/cooling ceilings, fan convectors, facade ventilation units and VAV systems, as well as air quality regulation. They also have self-learning start optimisation, summer and winter compensation and built-in detection of the dew point temperature using an additional humidity sensor.

The new clima DL-110 is a universal room controller that has all the connections it needs for top energy efficiency. Wall mod-ules with built-in temperature and humidity sensors (optional) and optionally with LCD displays, as well as a multisensor, can all be connected directly. On the input side, the regulator provides a second temperature input and an analogue input, for example for air quality sensors. On the output side, thermal, motor or continuous positioning drives can be connected, a three-level fan and an additional electric consumer, such as a heating register.

The e.control room controller series also includes the familiar flush-mounted nova or clima RCM/RO-CC controllers and nova or clima RCM-/RO-FC fan coil controllers. As built-in wall units, they fit into a deep flush-mount or in-wall box and have both digital inputs and analogue positioning drive outputs. The FC variants are intended for connection to an external fan coil box mounted in the vicinity of the fan convector to handle its control (see connection dia-gram on page 84).

Room climate in Class A The new clima DL-110

Proven flush-mounted controllers

The advantages

Room controllers meet the re-quirements of EN 15232 BAC efficiency class A

One for everything: the clima DL-110 universal room controller is suitable for any HVAC system

Always matches: nova and clima RCM match your switch designs

Integrated humidity sensors permit the optimised regulation of cooling ceilings

* 1 integrated in DWM-xx, 1 additional NTC10k

Central o dialogDRC-10

Cooling valveHeating valveFan

climaDMS-20

climaDWM-20

clima DL-110

Window contact

Hotel card switch

Dew point sensor

Air quality sensor

Page 81: spega e.control catalogue 2014

81

Specification Order No.Figure Technical data

clima DL-110

331 110clima DL-110LON Universal room controller

Compact climate controller for fancoil units, static heating and cooling or VAV systems

Communication ports for wall module DWM-xx and multisensor DMS-20

Input for 2. temperature senor (NTC10k), air quality sensor (0-10V) and 4 floating contacts

Outputs for 3-staged fan (2A), 2 x 0-10V and 2 x 24V for actuators plus 1 relay 230V 8A e.g. for elec-trical heater

Application according to LonMark and VDI 3813-2 complies with BAC Efficiency Class A (EN 15232)

Network:TP/FT-10 (FTT10)

Power supply: 230V AC, max. 10A

Inputs:2 x RJ9 for DWM-xx and DMS-201 x NTC10k for temperature1 x 0-10V e.g. for CO2, VOC4 x DI for floating contacts

Outputs:1 x 230V AC, 8A for el. heater3 x 230V AC, 2A for fan2 x 0-10V for actuators or fans2 x 24V DC for therm./mot. act.

Metrics/mouting: (HxWxD) 102(63) x 140 x 52mm DIN rail mounting or with srew holes

2x

2-P/PDM

M

934 520clima DWM-20LCD Wall module with temperature sensor

Surface-mounting wall module with LC display and room temperature sensor

Display of current temperature, setpoint, fan stage and different controller states

Illuminated presence button and push buttons for setpoint and fanspeed adjustment

DWM-20 Temperature

Connection:via separate RJ9 cable (p. 83)

Metrics/mounting: (HxWxD) 91 x 84 x 23mm wall mounting

934 521934 526

clima DWM-21 (-rH)LCD Wall module with temperature and optional humidity sensor

Surface-mounting wall module with LC display, room temperature and relative humidiy sensor (optional)

Display of current temperature, setpoint and different controller states

Illuminated presence button and push buttons for setpoint adjust-ment

DWM-21 TemperatureDWM-21-rH Temperature, humidity

Connection:via separate RJ9 cable (p. 83)

Metrics/mounting: (HxWxD) 91 x 84 x 23mm wall mounting

2x

0-10V

M

0-10V

1x

NTC10k

1x

NO / NC

4x

I-II-III

M~1x

Page 82: spega e.control catalogue 2014

82

Specification Order No.Figure Technical data

clima DL-110

930 301934 311

clima DWM-01 / 11-rHTemperature sensor or Temperature and humidity sensor

Surface-mounting wall module with room temperature and relative humidiy sensor (optional)

DWM-01 equipped with NTC10k sensor for connecting to tempera-ture input of clima DL-110

DWM-11-rH equipped with tem-perature and rel. humidity sensor, serial communication with clima DL-110

DWM-01 TemperatureDWM-11-rH Temperature, humidity

Connection:DWM-01: via 2-wire cableDWM-11: via separate RJ9 cable (p. 83)

Metrics/mounting: (HxWxD) 91 x 84 x 23mm wall mounting

934 120 Wclima DMS-20Multisensor

Combination of presence detector, light sensor and infrared receiver

Transmits telegrames of the re-mote control dialog DRC-10 to the room controller clima DL-100

Model: pure white

Connection:via separate RJ9 cable (p. 83)

Optical detection (height 3m): sedentary Ø 4.0m walking Ø 6.0m

Metrics(M) / fitting dimensions(F): (Ø x D) M: 43 x 56mm, F: 35 x 43mm

dialog DRC-10 Remote control for multisensors

Infrared remote control for univer-sal controller clima DL-110 and multisensors MS4 and MS4/RC

Control of: - 4 groups of lights - 4 groups of blinds - setpoint offset - fanspeed - presence

Backlit LC display

Power supply:2 x 1.5V LR03 Alkaline

Life of battery:approx. 2 years

Metrics:(HxWxD) 145 x 61 x 20mm

910 112

Page 83: spega e.control catalogue 2014

83

Specification Order No.Figure Technical data

clima DL-110

930 001930 002930 003930 004930 005

Connection cable RJ9

RJ9 cable for connecting wall mo-dules DWM-10-RH, DWM-2x(-rH) or multisensor DMS-20 to univer-sal controller clima DL-110

Length 6 m Length 8 mLength 12 mLength 20 mLength 30 m

Connectors:RJ9 (4-pole) on both ends

930 110clima DMB-10Mounting box

Sheet steel enclosure with cover and DIN rail for mounting room controller clima DL-110

Cable entries with strain relief on both sides

Additional space for fuse terminal block, coupling relays etc.

Material/protection:Sheet steel 1mm zinc plated, IP40

Metrics:(HxWxD) 70 x 275 x 255mm

clima A24 Thermoelectric actuator

Noiseless thermoelectric actuator with optical position indicator

Type A24-T with on/off control, closed when de-energised

Type A24-10AC / A24-10DC with continuous positioning via 0-10V signal, closed when de-energised

clima A24-T 24V AC/DC, th.clima A24-10AC 24V AC, 0-10Vclima A24-10DC 24V DC, 0-10V

Operating current:typ. 80mA, <250mA on power-on

Cable length:1m

Travel / force / time: 4mm / 100N / approx. 120s

020 325020 345020 346

Matching valve adaptors VA 78VA 26VA 80VA 50VA 50H

Danfoss RAGiacominiHeimeier (M30x1,5)MNG (M30x1,5)MNG high (M30x1,5)Others on request

Page 84: spega e.control catalogue 2014

84

Specification Order No.Figure Technical data

Suitable frames on page 43

231 642 W 231 642 B 231 642 A 231 643 W 231 643 B 231 643 A231 652 W 231 652 B 231 652 A 231 653 W 231 653 B 231 653 A

RCM-CC pure white gl. black gl. aluminium RCM-CC-P pure white gl. black gl. aluminium RCM-CC-rH pure white gl. black gl. aluminium RCM-CC-rH-P pure white gl. black gl. aluminium

Network/power supply/outputs:TP/FT-10 (FTT10)24V AC/DC, max. 60mA0-10V, max. 5 mA each

Metrics/Mounting:(HxWxD) 70 x 70 x 49mmin cavity wall or flush mounting sockets

nova RCM-CC(-rH)LON Room climate controller with 6 DI / 2 AO 0-10V

Flush-mounting room controller with temperature and optional humidity sensor (-rH), setpoint adjuster and optional presence button (-P)

2 analogue outputs for actuators and 2 inputs for window contacts or presence detectors (p. 58)

4 inputs for floating contacts, e.g. light, sunblind or hotel card switch-es (p. 42)

Available in 3 colours for nova design, frame not included

Application according to LonMark and VDI 3813-2 complies with BAC Efficiency Class A (EN 15232)

231 641 W 231 641 B 231 641 A

RO-CC: pure white glossy black glossy aluminium

Network/power supply:TP/FT-10 (FTT10)24V AC/DC, max. 60mA

Outputs:0-10V, max. 5 mA each

Metrics/Mounting:(HxWxD) 70 x 70 x 49mmin cavity wall or flush mounting sockets

nova RO-CCLON Climate controller for public buildings with 6 DI / 2 AO 0-10V

Flush-mounting room controller with temperature sensor

2 analogue outputs for actuators and 2 inputs for window contacts or presence detectors (p. 58)

4 inputs for floating contacts, e.g. light, sunblind or hotel card switch-es (p. 42)

Available in 3 colours for nova design, frame not included

Application according to LonMark and VDI 3813-2 complies with BAC Efficiency Class A (EN 15232)Suitable frames on page 43

nova Room controllers for static heating/cooling

clima RCM-CCclima RO-CC4 Switches

Cooling valve

Heating valve

Window contact

Dew point sensor

clima RCM-FCclima RO-FC

clima FC-B

4 Switches

Heating valve

Cooling valve

Signal contactWindow contact

Fan

Window contact Signal contact

Connecting scheme for nova and clima RCM/RO-CC for static heating and cooling systems

Connecting scheme for nova and clima RCM/RO-FC for fan coil units

Page 85: spega e.control catalogue 2014

85

Specification Order No.Figure Technical data

231 634 W 231 634 B 231 634 A 231 635 W 231 635 B 231 635 A

RCM-FC pure white glossy black glossy aluminium RCM-FC-P pure white glossy black glossy aluminium

Network:TP/FT-10 (FTT10)

Power supply:24V AC/DC, max. 60mA

Metrics/Mounting:(HxWxD) 70 x 70 x 49mm, in cavity wall or flush mounting sockets

nova RCM-FCLON Fan coil controller with 6 DI and FCB connector

Flush-mounting fan coil controller with temperature sensor, setpoint and fan speed adjuster and pres-ence button (-P)

Integrated control of max. 2 fan coils with clima FCB boxes (see below) via 3-wire cable

6 inputs for floating contacts, e.g. light, sunblind or hotel card switch-es (p. 42), sensors (p. 58)

Available in 3 colours for nova design, frame not included

Application according to LonMark and VDI 3813-2 complies with BAC Efficiency Class A (EN 15232)

231 631 W 231 631 B 231 631 A

RO-FC: pure white glossy black glossy aluminium

Network:TP/FT-10 (FTT10)

Power supply:24V AC/DC, max. 60mA

Metrics/Mounting:(HxWxD) 70 x 70 x 49mmin cavity wall or flush mounting sockets

nova RO-FCLON Fan coil controller for public buildings with 6 DI and FCB conn.

Flush-mounting fan coil controller with temperature sensor

Integrated control of max. 2 fan coils with clima FCB boxes (see below) via 3-wire cable

6 inputs for floating contacts, e.g. light, sunblind or hotel card switch-es (p. 42), sensors (p. 58)

Available in 3 colours for nova design, frame not included

Application according to LonMark and VDI 3813-2 complies with BAC Efficiency Class A (EN 15232)

Suitable frames on page 43

Suitable frames on page 43

410 302 410 322 410 342

clima FCB-24 2 x 24V AC/DC + fanclima FCB-230 2 x 230V triac + fanclima FCB-10V 2 x 0-10V + fan

Power supply:24V AC/DC: via 3 wire bus 230V AC: separate feed line

Metrics/Mounting:(HxWxD) 85 x 130 x 38mmmounting on fan housing, IP 54

clima FCBFan coil box for controlling a fan coil unit

Junction box for three-stage fan and 2 thermoelectric or continous actuators (0-10V)

2 inputs for floating contacts

Connectable to nova RCM-FC or nova RO-FC via 3-wire cable. Two fan coil boxes can be operated in parallel

Scale of images approx. 1:3

nova Fan coil controllers

Page 86: spega e.control catalogue 2014

86

Specification Order No.Figure Technical data

231 342 W 231 342 B 231 342 A 231 343 W 231 343 B 231 343 A231 352 W 231 352 B 231 352 A 231 353 W 231 353 B 231 353 A

RCM-CC pure white anthracite aluminium RCM-CC-P pure white anthracite aluminiumRCM-CC-rH pure white anthracite aluminium RCM-CC-rH-P pure white anthracite aluminium

Network/power supply/outputs:TP/FT-10 (FTT10)24V AC/DC, max. 60mA0-10V, max. 5 mA each

Metrics/Mounting:(HxWxD) 70 x 70 x 49mmin cavity wall or flush mounting sockets

clima RCM-CC(-rH)LON Room climate controller with 6 DI / 2 AO 0-10V

Flush-mounting room controller with temperature and optional humidity sensor (-rH), setpoint adjuster and optional presence button (-P)

2 analogue outputs for actuators and 6 digital inputs for floating contacts or push buttons

Available in 3 colours, suitable for - Berker S1, B1, B3, B7 glass - Gira System 55 (E2, Event, Esprit) - Jung Series A 500, AS500 - Merten System M (1-M, M-xxx)

Application according to LonMark and VDI 3813-2 complies with BAC Efficiency Class A (EN 15232)

231 341 W 231 341 B 231 341 A

RO-CC: pure white anthracite aluminium

Network/power supply:TP/FT-10 (FTT10)24V AC/DC, max. 60mA

Outputs:0-10V, max. 5 mA each

Metrics/Mounting:(HxWxD) 70 x 70 x 49mmin cavity wall or flush mounting sockets

clima RO-CCLON Climate controller for public buildings with 6 DI / 2 AO 0-10V

Flush-mounting room controller with temperature sensor

2 analogue outputs for actuators

6 digital inputs for floating contacts, presence detectors or push buttons

Available in 3 colours, suitable for all USB/TAE cover plates of the following manufacturers: Berker, Busch-Jaeger, Gira, Jung, Merten, Peha and Siemens (cover plate not included)

Application according to LonMark and VDI 3813-2 complies with BAC Efficiency Class A (EN 15232)

231 544 W 231 544 B 231 544 A

LCD-CC pure white anthracite aluminium

Network:TP/FT-10 (FTT10)

Power supply:24V AC/DC, max. 65mA

Outputs:0-10V, max. 5 mA each

Metrics/Mounting:(HxWxD) 71 x 71 x 49mmin cavity wall or flush mounting sockets

clima LCD-CCLON LCD Room climate controller with 2 DI / 2 AO 0-10V

Flush-mounting room controller with temperature sensor, LCD and 4 buttons for setpoint or fan speed adjustment and presence

2 analogue outputs for actuators and 2 inputs for window contacts or presence detectors (p. 58)

Available in 3 colours, suitable for - Berker S1, B1, B3, B7 glass - Gira System 55 (E2, Event, Esprit) - Jung Series A 500, AS500 - Merten System M (1-M, M-xxx)

Application according to LonMark and VDI 3813-2 complies with BAC Efficiency Class A (EN 15232)

Standard 55 Room controllers for static heating/cooling

Page 87: spega e.control catalogue 2014

87

Specification Order No.Figure Technical data

231 334 W 231 334 B 231 334 A 231 335 W 231 335 B 231 335 A

RCM-FC pure white anthracite aluminium RCM-FC-P pure white anthracite aluminium

Network:TP/FT-10 (FTT10)

Power supply:24V AC/DC, max. 60mA

Metrics/Mounting:(HxWxD) 70 x 70 x 49mm, in cavity wall or flush mounting sockets

clima RCM-FCLON Fan coil controller with 6 DI and FCB connector

Fan coil controller with temperature sensor, setpoint and fan speed adjuster and presence button (-P)

Control of max. 2 fan coils with clima FCB boxes (see below) via 3-wire cable

6 inputs for floating contacts or bush buttons

Available in 3 colours, suitable for - Berker S1, B1, B3, B7 glass - Gira System 55 (E2, Event, Esprit) - Jung Series A 500, AS500 - Merten System M (1-M, M-xxx)

Application according to LonMark and VDI 3813-2 complies with BAC Efficiency Class A (EN 15232)

231 331 W 231 331 B 231 331 A

RO-FC: pure white anthracite aluminium

Network:TP/FT-10 (FTT10)

Power supply:24V AC/DC, max. 60mA

Metrics/Mounting:(HxWxD) 70 x 70 x 49mmin cavity wall or flush mounting sockets

clima RO-FCLON Fan coil controller for public buildings with 6 DI and FCB conn.

Flush-mounting fan coil controller with temperature sensor

Integrated control of max. 2 fan coils with clima FCB boxes (see below) via 3-wire cable

6 inputs for floating contacts and push buttons

Available in 3 colours, suitable for all USB/TAE cover plates of the following manufacturers: Berker, Busch-Jaeger, Gira, Jung, Merten, Peha and Siemens (cover plate not included)

Application according to LonMark and VDI 3813-2 complies with BAC Efficiency Class A (EN 15232)

410 302 410 322 410 342

clima FCB-24 2 x 24V AC/DC + fanclima FCB-230 2 x 230V triac + fanclima FCB-10V 2 x 0-10V + fan

Power supply:24V AC/DC: via 3 wire bus 230V AC: separate feed line

Metrics/Mounting:(HxWxD) 85 x 130 x 38mmmounting on fan housing, IP 54

clima FCBFan coil box for controlling a fan coil unit

Junction box for three-stage fan and 2 thermoelectric or continous drive actuators (0-10V)

2 inputs for floating contacts

Connectable to clima RCM-FC or clima RO-FC via 3-wire cable. Max. 2 fan coil boxes can be ope-rated in parallel

Standard 55 Fan coil controllers

Scale of images approx. 1:3

Page 88: spega e.control catalogue 2014

88

Monitoring of fire dampers

The clima BSK modules are perfect for the monitoring of thermal and control of mo-torised fire dampers. All modules include the standardised LonMark “Fire and Smoke Damper Actuator” functional profile, which significantly simplifies the integration of dampers in the control and maintenance of ventilation systems.

The BSK modules for motorised fire dampers include a test function that is activated centrally, and checks for unhindered func-tion during closing and opening. This test

The integration of motorised fire dampers into e.control room automation is signifi-cantly simplified by clima BSK, since both speak the same protocol language and can therefore be integrated into an overall system. For example, the specific closing of dampers whose fire section is not occupied can be very useful. This reduces the air vol-ume to be carried by the ventilation system, leading to significant energy savings.

Simplified monitoring

Build-in service function

Added-value with room controls

The advantages

4 modules for thermal and motor-ised fire dampers are available in 24V and 230V variants

Uniform software allows the com-bination of all modules in a single system

Built-in functional testing for maintenance-free fire dampers

Integration into room automation for more energy efficiency

function meets the requirements for month-ly functional testing of maintenance-free fire dampers.

Page 89: spega e.control catalogue 2014

89

Specification Order No.Figure Technical data

Fire damper modules

421 404clima BSK4-FLON Fire damper actuator 4 ports

Module to control 4 fire or smoke dampers with 24V AC/DC spring return drive

8 inputs for floating contacts to indicate open-end and closed-end position

External 24V power supply via bus cable

Application according to LonMark profile „Fire Smoke Damper Act.“

Network:TP/FT-10 (FTT10)

Power supply:24V AC/DC, max. 120mA

Max. load (per relay):24V AC/DC, 1A

Metrics: (HxWxD) 63 x 254 x 180mm

Application: SC421404EC 4 fire & smoke damper actuators

24V AC/DC

4 x

411 408clima BSK8-ELON Fire damper position indicator

Module with 8 inputs for position indicator switches of up to 8 fire dampers

Plastic case, cable entry points with strain relief, protection class IP54 (IP65 on request)

External 24V power supply via bus cable

Applications according to LonMark to initiate and forward fire alams or to monitor states of binary contacts

Network:TP/FT-10 (FTT10)

Power supply:24V AC/DC, max. 65mA

Metrics: (HxWxD) 63 x 254 x 180mm

Application: SC411408EC 8 fire & smoke damper actuators

8 x

411 409clima BSK8-E230LON Fire damper position indicator

Module with 8 inputs for position indicator switches of up to 8 fire dampers

Plastic case, cable entry points with strain relief, protection class IP54 (IP65 on request)

Integrated 230V power supply

Applications according to LonMark to initiate and forward fire alams or to monitor states of binary contacts

Network:TP/FT-10 (FTT10)

Power supply:230V AC, max. 2W

Metrics: (HxWxD) 63 x 254 x 180mm

Application: SC411408EC 8 fire & smoke damper actuators

8 x

230V AC

4 x

421 405clima BSK4-F230LON Fire damper actuator 4 ports

Module to control 4 fire or smoke dampers with 230V AC spring return drive

8 inputs for floating contacts to indicate open-end and closed-end position

Integrated 230V power supply

Application according to LonMark profile „Fire Smoke Damper Act.“

Network:TP/FT-10 (FTT10)

Power supply:230V AC, max. 4W

Max. load (per relay):230V AC, max. 250W

Metrics: (HxWxD) 63 x 254 x 180mm

Application: SC421404EC 4 fire & smoke damper actuators

NO / NC

NO / NC

Page 90: spega e.control catalogue 2014

90

Weather sensors and automation

ombra BST combines the many requirements for sun protection in the perfect manner. The slat tracking controller ensures glare-free work while simultaneously taking max-imum advantage of the daylight. Since it can calculate the exact position of the sun and can also use exterior brightness sen-sors to detect its intensity, it can cyclically and precisely adapt the position of blinds to the current situation. This ensures that every room receives the maximum possible amount of daylight – of course, while main-taining the glare protection needed.

In combination with the ombra BST slat tracking controller, all e.control sunblind actuators are ready to take shadows from

All necessary weather data is provided by e.control weather sensors. In addition to the ombra WSx central weather station with the capacity to connect up to 12 sensors, e.control also offers the ombra W2, a de-centralised weather sensor that is mounted directly onto the facade.

Optimised sun protection

Shadow correction

High-precision sensors

The advantages

Optimised daylight supply

Reliable protection from glare

Reduced thermal heating loads in rooms

Reliable protection from weath-er-related damage

Slat tracking control and shadow correction depending on the posi-tion of the sun, without external computers

surrounding buildings into account. Only those blinds are moved with the sun that are actually in the sunshine according to the shadows cast on the facade, while the blinds in windows in the shade can be positioned for maximum transparency.

It may seem highly complex, but it‘s easy to put it to work: The plug-ins for the parame-terisation of all the automation and safety functions, including slat tracking control and shadow correction, require no special expertise and can even be adapted during operation by Facility Management staff.

Simple system integration

Page 91: spega e.control catalogue 2014

91

Specification Order No.Figure Technical data

Slat tracking controller

341 298Network:TP/FT-10 (FTT10)

Power supply:24V DC, max. 80mA

Equipment:- Display 4x16 characters, backlit- Real-time clock, battery backed- 3 LEDs (red, yellow, green)

Metrics/mounting:(HxWxD) 125 x 125 x 40mmIncludes box for cavity wall or flush-mounting or mounting in switchboard front door

ombra BST LON Slat tracking controller

Sun position-dependent positio-ning of slat angles for up to 15 facades or venetian blind types

Supports e.control shadow correction in combination with all e.control sunblind actuators

Integrated processing of telegrams from multiple light sensors (e.g. ombra WSx or ombra W2)

Anti-glare or daylight guidance strategy independently selectable for each group of venetian blinds

Manual positioning of facade groups via user menu

Integrated time clock for time-dependent positioning commands

Password protected user access

Comprehensive plug-in for step-by-step parameterisation

Flat slat angles at noon ensure unobstructed view without the sun‘s rays directly entering the room.

The low sun position in the morning and evening requires steeper slat angles.

Surrounding shadow-producing buildings are dealt with by the built-in shadow correc-tion, i.e. shaded slats are temporarily moved up to ensure maximum daylight provision.

Page 92: spega e.control catalogue 2014

92

Specification Order No.Figure Technical data

411 298411 292

ombra WS8/WS12 LON weather station for 8 or 12 sensors

Sensor unit including power supply and terminals for connecting 8 or 12 analogue weather sensors

Compatible with weather sensor ombra W7-C, wind direction sen-sor ombra W1-D and 3 additional analogue sensors (WS12 only)

Integrated weather protection and sunblind automatic controllers for 4 facades

ombra WS8 for 8 sensorsombra WS12 for 12 sensors

Network/power supply:Type TP/FT-10 (FTT10)Voltage 230V 50/60Hz

Inputs:8 or 12 analogue inputs 0-10V

Material/safety class:Polycarbonate, weatherproof, IP65

Metrics:(HxWxD) 360 x 254 x 90mm

ombra W7-C Combined weather sensor

Sensor for measurement of: - wind speed - rain - outdoor brightness (3 x) - twilight - outdoor temperature - relative humidity

Integrated automatic heating as condensation protection

Safety class IP65, weatherproof

Power supply:24V AC/DC, max. 650mA

Metering range/accuarcy:wind: 1...40m/s / 0,5m/s rain: yes/nobrightness: 0...150kLx / 3%twilight: 0...250Lx / 5% temperature -20...60°C / 0,5°Chumidity: 0...100% (rel.) / 3% Metrics/mounting:(HxØ) 430 x 130 mmPole- or wall-mounting

ombra W1-D Wind direction sensor

Sensor for indicating wind direction

Integrated automatic heating for ice free usage up to -30°C

Safety class IP65, weatherproof

Power supply:24V AC/DC, max. 830mA

Metering range/accuracy:direction: 0...360° / 5°

Metrics/mounting:(HxØ) 220 x 50 mmLength of vane 165 mm Pole- or wall-mounting

410 207

410 204

Weather stations

Traverses

For pole mounting of one or two sensors, e.g. ombra W7-C or/and ombra W1-D

Single traverse suitable for one sensor

Double traverse suitable for two sensors

Single traverse for pole Ø 48-102 mmSingle traverse for pole Ø 116-200 mmDouble traverse for pole Ø 48-102 mmDouble traverse for pole Ø 116-200 mm

Length of bracket:0,4 m (single) 0.8 m (double)

950 208950 209950 206950 207

Page 93: spega e.control catalogue 2014

93

Specification Order No.Figure Technical data

411 202ombra W2LON compact weather sensor

Compact device for daylight and temperature-dependent controls

Integrated light and temperature sensor

With terminal for wind speed sen-sor ombra W1-Wh or rain sensor ombra W1-R

Safety class IP54, weatherproof, mounting angle enclosed

Network/power supply:Type TP/FT-10 (FTT10)Voltage 24V DC, max. 20mA

Metrics/mounting:(HxWxD) 93 x 72 x 57mmPole- or wall-mounting

ombra W1-Wh Wind speed sensor for ombra W2

Compact sensor for vectorial wind speed measurement

Connectable to compact weather sensor ombra W2

Integrated automatic heating for ice free usage up to -30°C

Safety class IP54, weatherproof, mounting angle enclosed

Power supply:24V DC, max. 1A

Measurement signal:Pulse, reed contact

Measurement range:0.5...40 m/s

Metrics/mounting:(HxØ) 160 x 134mmPole- or wall-mounting

410 203

ombra W1-R Rain sensor for ombra W2

Compact sensor for rain and snow detection

Connectable to compact weather sensor ombra W2 or to any binary input (e.g. lumina T6/B8)

Integrated automatic heating for ice free usage up to -30°C

Safety class IP54, weatherproof, mounting angle enclosed

Power supply:24V DC, max. 150mA

Measurement signal:Binary, floating contact

Metrics/mounting:(HxWxD) 18 x 76.5 x 54mmPole- or wall-mounting

410 202

ombra W1-K Terminal box for ombra W2

For wiring wind speed sensor or rain sensor to compact weather sensor ombra W2

With terminal block for power supply, LON bus and sensor signal

Safety class IP65, weatherproof

Material:Polycarbonate

Accessories:8 terminal blocks 2,5mm 3 screwed cable glands IP65

Metrics/mounting:(HxWxD) 140 x 140 x 80mm

950 201

Compact weather sensor

Page 94: spega e.control catalogue 2014

94

Network topology

LON networks can be of nearly any size. An IP network is used as the backbone and to connect to external systems. The transi-tion to the installation level is provided on each floor, using IP routers. These routers forward LON packets to room automation units through one or more twisted-pair lines in any topology. This permits networks to be built with 256 floors or areas and over 32,000 devices, with no problems at all (see diagram above).

Networks of any size

Universal IP backbone

The central backbone of the e.control room automation system is an IP network with the LON/IP protocol for communication be-tween room automation devices (for exam-ple, a packet from the weather station to all the sunblind actuators) and BACnet/IP for communication with external systems, for example, to talk to building management software or the DDC automation stations.

BACnet integration included

e.control floor controllers (see p. 95) han-dle all important automation functions for the rooms on a single floor, such as provi-sion of all data points, processing of timer programs, recording data trends and gen-erating messages. To do that, they use the BACnet protocol, ensuring that integration into building management systems takes place problem-free, quickly and clearly. The floor controllers guarantee that by automatically sorting all objects by room, even when the e.control room automation system is organised by segment in flexible buildings.

The advantages

High-performance room auto-mation network with up to 256 floors/areas and 32,000 devices

Use of a shared IP network back-bone with building automation

Automatic room-by-room BACnet integration using e.cntrol floor controllers

Integration of touch panels into the IP backbone fully supported

And because the floor controller is managed in the graphical e.control Designer soft-ware, even updates to all BACnet objects are automatic whenever rooms are changed. Room automation integration simply can’t be easier than that.

Thanks to the option of sharing use of an IP network with all the subsystems of building automation, a clear, high-performance system structure results.

* max. number of LON/IP devices per logical IP channel when using L-IP routers (Source: Echelon Wiring Guidelines, Version 10/2009)

NetworkTrans-ceiver

Transfer rate

Cable type

Topo- logy

max. devices

Device distance

max. bus length

TP/FT (LON/FT)

FTT10 78kbit/s

J-Y(St)Y 2x2x0,8

free line

64 64

320 m 900 m

500 m 900 m

Catego-ry 5

free line

64 64

250 m 900 m

450 m 900 m

Belden 8471/85102

free line

64 64

400 m 2.700 m

500 m 2.700 m

EIA 852 (LON/IP)

10BaseT >10Mbit/s various star 256* unlimited unlimited

Overview of maximum cable lengths

LON/IP, BACnet/IP

Floor controller Floor n

Floor 1

Basement

L-IP

LT

DDC DDC

e.control e.control

T

DDC

Floor controller

L-IP

LT e.control e.control

T

BMS

Page 95: spega e.control catalogue 2014

95

Specification Order No.Figure Technical data

Floor and application controllers

131 020sistema RC2 LON Application controller

Compact device for different con-trol applications or logic proces-sings

Various software applications available on CD or on request

Network:TP/FT-10 (FTT10)

Power supply:24V DC, max. 40mA

Metrics/mounting:(HxWxD) 85(45) x 35 x 60mmDIN rail mounting

Available applications (selection):131020FH: Floor hub for segmentation of central functions 131020PW: Partition wall controller 131020LG: logic controller 131020SC: 4 temperature controllers with thermal control

sistema LGATE950BACnet Floor controller

Server for automation level func-tions like data point presentation, time scheduling, trend logging and event notification as BACnet server objects

Room-by-room grouping of BAC-net objects for easy integration in building management software

BACnet Building Controller (B-BC)

LON/IP device, static network interface with separate function block per room

Automatic re-configuration with e.control Designer (p. 101)

Supplied with preconfigured pro-gram for different room types and LNS plug-in for free configuration

Network:Port 1 10/100 Base-T (BACnet/IP, LON/IP)Port 2 10/100 Base-T (BACnet/IP, LON/IP)

Resources:BACnet objects 1000BACnet trend logs 100BACnet not. class obj. 32LON network var. 1000Schedulers 100

Power supply:9-35V DC, 12-24V AC 50/60Hz max. 200mA@24V

Metrics/mounting:(HxWxD) 90(45) x 157 x 60mmDIN rail mounting

133 950

Page 96: spega e.control catalogue 2014

96

Specification Order No.Figure Technical data

L-IP 3ECTB LON/IP Router

Routes packets between TP/FT-10 segment and IP networks

Preferably used as LON/IP back-bone router

Build-in web server for admin. and LON/IP configuration server

Firmware update and network diagnostics via LSD tool

Protocol analysis via LPA-IP tool

Network:Port 1 10/100 Base-T (Ethernet)Port 2 TP/FT-10

Power supply:9-35V DC, 12-24V AC 50/60Hz max. 200mA@24V

Termination:external for TP/FT segment (p. 97)

Metrics/Mounting:(HxWxD) 90(45) x 104 x 60mmDIN rail mounting

LIP-3ECTB

L-IP 33ECTB LON/IP 2 port router

Routes packets between two TP/FT-10 segments and IP networks

Preferably used as LON/IP back-bone router

Build-in web server for admin. and LON/IP configuration server

Firmware update and network diagnostics via LSD tool

Protocol analysis via LPA-IP tool

Network:Port 1 10/100 Base-T (Ethernet)Port 2+3 TP/FT-10

Power supply:9-35V DC, 12-24V AC 50/60Hz max. 200mA@24V

Termination:external for TP/FT segments (p. 97)

Metrics/Mounting:(HxWxD) 90(45) x 104 x 60mmDIN rail mounting

LIP-33ECTB

L-IP 3333ECTB LON/IP 4 port router

Routes packets between four TP/FT-10 segments and IP networks

Preferably used as LON/IP back-bone router

Build-in web server for admin. and LON/IP configuration server

Firmware update and network diagnostics via LSD tool

Protocol analysis via LPA-IP tool

Network:Port 1 10/100 Base-T (Ethernet)Port 2-5 TP/FT-10

Power supply:9-35V DC, 12-24V AC 50/60Hz max. 200mA@24V

Termination:external for TP/FT segments (p. 97)

Metrics/Mounting:(HxWxD) 90(45) x 157 x 60mmDIN rail mounting

LIP-3333ECTB

L-PROXY LON Gateway

Gateway for transmitting tele-grams between 3 LON/IP and 2 TP/FT-10 segments

Provides data interchange across domain boundaries and different LNS databases

Proxy functionality by mapping input NV’s to output NV’s (e.g. to overcome alias limitations)

Configurable via LNS plug-in

Network:Port 1 10/100 Base-T (LON/IP)Port 2-3 TP/FT-10 (LON/TP)

Power supply:9-35V DC, 12-24V AC 50/60Hz max. 200mA@24V

Metrics/Mounting:(HxWxD) 90(45) x 104 x 60mmDIN rail mounting

LP-33E100

IP Routers and proxy

Page 97: spega e.control catalogue 2014

97

Specification Order No.Figure Technical data

RT-33RT-33 LON Repeater

Signal amplifier connecting two TP/FT-10 segments

Separate clamps for power supply and for electromagnetic shielding

Connection via coloured bus clamps

Network:Port 1-2: TP/FT-10

Power supply:24V DC, max. 20mA

Termination:external for TP/FT segments (see below)

Metrics/Mounting:(HxWxD) 85(45) x 53 x 60mmDIN rail mounting

LS-33 CB LON 2 port router

Routes packets between two phy-sically separated TP/FT segments

Configurable as self-learning switch (plug&play) or configured router

Service pin and diagnostic LED

Firmware update and network diagnostics via LSD tool

Network:Port 1-2: TP/FT-10

Power supply:9-35V DC, 12-24V AC 50/60Hz max. 200mA@24V

Termination:external for TP/FT segments (see below)

Metrics/Mounting:(HxWxD) 90(45) x 104 x 60mmDIN rail mounting

LS-33CB

LS-333CBLS-333 CB LON 3 port router

Routes packets between three physically separated TP/FT seg-ments

Configurable as self-learning switch (plug&play) or configured router

Service pin and diagnostic LED

Firmware update and network diagnostics via LSD tool

Network:Port 1-3: TP/FT-10

Power supply:9-35V DC, 12-24V AC 50/60Hz max. 200mA@24V

Termination:external for TP/FT segments (see below)

Metrics/Mounting:(HxWxD) 90(45) x 157 x 60mmDIN rail mounting

sistema LT-33 / LT-03 LON Terminators

Bus termination for TP/FT-10 segments (free topology or line topology)

LT-33 includes 2 termination ele-ments

LT-03 is equipped with RJ45 jack for connecting to NIC interfaces

Versions:LT-33 for 2 TP/FT-10 segments in free or line topologyLT-03 for 1 TP/FT-10 segment in free or line topology, RJ45 jack

Metrics/mounting:(HxWxD) 85(45) x 17 x 60mmDIN rail mounting

100 033

100 003

FT Routers and terminators

Page 98: spega e.control catalogue 2014

98

Specification Order No.Figure Technical data

sistema SV15 Power supply 24V DC

Regulated and stabilised power supply for LON devices with 24V DC operating voltage

Rated output current: 1.3A

Short-circuit and overload proof

High efficiency

Connectable in parallel

100 150

100 250

Voltage:primary 120-230V AC, 50/60Hzsecondary 24V DC

Power:30 W (1.3A secondary)

Metrics/mounting:(HxWxD) 90 x 54 x 55mmDIN rail mounting

sistema SV25 Power supply 24V DC

Regulated and stabilised power supply for LON devices with 24V DC operating voltage

Rated output current: 2.5A

Short-circuit and overload proof

High efficiency

Connectable in parallel

Voltage:primary 120-230V AC, 50/60Hzsecondary 24V DC

Power:60 W (2.5A secondary)

Metrics/mounting:(HxWxD) 90 x 72 x 55mmDIN rail mounting

NIC709-USBNIC709-USB100 LON Interface for USB

USB interface connecting to LON networks via TP/FT-10 segments

Compatible with LNS applications in high-performance LNS/VNI access mode

Simultaneous operation of LNS applications and LPA or LSD tools

Software driver for Windows 7, Vista, XP and 2000

Network:TP/FT-10 (78kbps)

USB port:Full speed USB (1.1)

Power supply:via USB port (5V, <130mA)

Metrics:(HxWxD) 23 x 69 x 116mm

Power supplies and interfaces

NIC709-IP3ENIC709-IP3E100 LON Interface for Ethernet

LAN interface connecting to LON networks via TP/FT-10 segments

Compatible with LNS applications in high-performance LNS/VNI access mode

Simultaneous operation of LNS applications and LPA or LSD tools

Software driver for Windows 7, Vista, XP and 2000

Network:TP/FT-10 (78kbps)

Ethernet port:10 Base-T

Power supply:9-35V DC, 12-24V AC 50/60Hz max. 200mA@24V

Metrics/mounting:(HxWxD) 90(45) x 104 x 60mm DIN rail mounting

Page 99: spega e.control catalogue 2014

99

Specification Order No.Figure Technical data

Touch panels

dialog LVIS5LON Touch panel 5.7“

Comfortable display and control panel for air conditioning, lighting, sunblinds, window control etc.

Front made of anodised aluminium

Supports static and dynamic LON network variables (max. 1,000) plus configuration properties

Supports local or remote alarming, scheduling and local trend logging

Integrated VNC server for remote destop access via IP network

Configurable via LNS plug-in in WYSIWYG design

341 511 A940 005

341 512 A940 012

341 515 A940 015

Model aluminium anodisedMounting frame

Network:Port 1 10/100 Base-T (Ethernet)Port 2 TP/FT-10 (LON)

Power supply:24V AC/DC, max. 330mA (8 W)

Equipment:- Display 320 x 240 pixel, 256 colors- Backlight- Touch-sensitive display- Integrated RNI remote interface

Metrics/Mounting:(HxWxD) 164 x 210 x 63mmMounting frame available separately

Model aluminium anodisedMounting frame

Network:Port 1+2 10/100 Base-T (Ethernet)Port 3 TP/FT-10 (LON)

Power supply:24V DC, max. 550mA (13 W) or 90 - 230V AC

Equipment:- Display 800 x 600 pixel, 65,535 colors- Dimmable backlight- Touch-sensitive display- 200 MB internal flash memory- Integrated RNI remote interface

Metrics/Mounting:(HxWxD) 269 x 329 x 65mmMounting frame available separately

Model aluminium anodisedMounting frame

Network:Port 1+2 10/100 Base-T (Ethernet)Port 3 TP/FT-10 (LON)

Power supply:24V DC, max. 660mA (16 W) or 90 - 230V AC

Equipment:- Display 1024 x 768 pixel, 65,535 colors- Dimmable backlight- Touch-sensitive display- 200 MB internal flash memory- Integrated RNI remote interface

Metrics/Mounting:(HxWxD) 318 x 394 x 65mmMounting frame available separately

dialog LVIS12LON Touch panel 12“

Comfortable display and control panel for air conditioning, lighting, sunblinds, window control etc.

Front made of anodised aluminium

Supports static and dynamic LON network variables (max. 1,000) plus configuration properties

Supports local or remote alarming, scheduling and local trend logging

Integrated VNC server for remote destop access via IP network

Configurable via LNS plug-in in WYSIWYG design

dialog LVIS15LON Touch panel 15“

Comfortable display and control panel for air conditioning, lighting, sunblinds, window control etc.

Front made of anodised aluminium

Supports static and dynamic LON network variables (max. 1,000) plus configuration properties

Supports local or remote alarming, scheduling and local trend logging

Integrated VNC server for remote destop access via IP network

Configurable via LNS plug-in in WYSIWYG design

Page 100: spega e.control catalogue 2014

100

e.control Designer - room management by mouse

The e.control Designer makes changes in area usage child‘s play. Its graphical user interface makes the generation, modifi-cation, and moving of floor plans easy. Corresponding changes to automation systems are handled automatically by the software afterwards. Since both the flexible adaptation of room layout as well as service to field devices takes place using the floor plan-oriented user interface, with e.control Designer, Facility Management has a power-ful tool available.

Simpler than ever

Access to the field level

All communications devices at the field level, regardless of whether they use DALI, SMI, MP-Bus or EnOcean interfaces, are just a mouse click away from the user interface.

Extensive function library

The e.control Designer has an extensive function library of all VDI 3813 room auto-mation functions, supporting the creation of a function macro for any room type. Even the most demanding of buildings with top energy efficiency, such as the main admi-nistration complex at ThyssenKrupp with a four-digit number of rooms, can be graphi-cally modelled and easily operated.

The advantages

Extensive function library compliant with VDI 3813

Room changes are carried out gra-phically on a building floor plan

Graphical user interface permits access to all communication-capable field devices

Device status and faults are dis-played on the user interface

Automatic room-by-room assignment of BACnet objects to e.control floor controllers

They can be parameterised, tested or repla-ced directly from e.control Designer. Even faults like burnt-out lights can be identified on the user interface. Since the work steps are the same regardless of the protocol in use, access is transparent and uniform for the operator and does not require any spe-cial knowledge of the technologies.

BACnet entirely automatically

e.control Designer even takes data transfer at the management level into consideration. To do this, the tool manages all e.control floor controllers and automatically ensures the room-by-room grouping of all data points as BACnet objects. This permits ad-aptations to the management software to be avoided when rooms are changed, or at least reduced to the creation of new rooms and the deletion of obsolete rooms.

The creation of one hatched area automatically defines a room over 2 segments

Modification of the hatched areas re-defines the room setup to two individual rooms

e.control Designer makes changes in area usage child‘s play. Its graphical and floor plan-oriented user interface makes it easy to create, modify or move rooms only by mouse click.

Page 101: spega e.control catalogue 2014

101

Specification Order No.Figure Technical data

Commissioning and management software

ALEX 4 Commissioning software

Professional software for system design and commissioning of LON networks

Runs as local LNS client or as light-weight or fullweight client for remote network access, thus multiple ALEX can access the same LON network concurrently

Integrated browser for monitoring and modifying network variables and configuration properties

Includes device manager for fast collecting, downloading and mana-ging large numbers of LON devices concurrently

Includes database for device and application management

Auto-backup automatically saves opened project database in back-ground

Includes Open LNS server license

Available Languages: English and German

090 042Consisting of: ALEX 4 Open LNS server

System requirements: Windows 7, XP, 2000 LON network interface for LON TP/FT-10 segment LAN port (10/100 Base-T) for LON/IP or remote access to LNS server

092 025092 050092 100092 150092 200

e.control Designer Graphical room management software

Graphical software tool for net-work design and commissioning of e.control room automation systems

Integrated function library for auto-matic binding and parameterisation of all e.control devices

Room layout and functionality can be changed graphically

Enables device management on mouse-click: test, reset, online, offline, download etc.

Software runs as local LNS client or as lightweight or fullweight client for remote network access

Includes Open LNS server licenseAvailable languages: English and

German

e.control Designer 250*e.control Designer 500*e.control Designer 1000*e.control Designer 1500*e.control Designer 2000*

Consisting of: e.control Designer Open LNS server

System requirements: Windows 7, XP, 2000 USB port for license dongle LON network interface for LON TP/FT-10 segment LAN port (10/100 Base-T) for LON/IP or remote access to LNS server

* includes license for the specified number of control devices with LON interface

Page 102: spega e.control catalogue 2014

102

Specification Order No.Figure Technical data

LPAProtocol analyser

Logging of all network telegrams in LON TP/XF1250 and TP/FT-10 respectively in LON/IP networks

Works together with all NIC network interfaces, even concurrently to ALEX or IPLONGATE

Allows longtime logging

Network adresses and variables will be interpreted automatically accor-ding to LNS database names

System requirements:Windows 7, Vista, XP, 2000 NIC interface orL-Switch, L-IP

LSD Network diagnostic tool

Collects and shows statistical information of LON networks during operation

Works together with all NIC network interfaces, even concurrently to ALEX or IPLONGATE

Diagnostics of complete networks through L-Switch or L-IP routers

Supports teleconfiguration, firmware upload of L-Switch or L-IP routers

LSD-SW

LPA-SW for TP/XF and TP/FT LPA-IP for LON/IP System requirements:Windows 7, Vista, XP, 2000LPA-SW: NIC interface LPA-IP: LAN port (10/100 Base-T)

LPA-SW LPA-IP

094 032094 042 094 052

IPLONGATEOPC Data server

High performance data server for connecting LON networks to super-visory control and data acquisition (SCADA) or building management systems (BMS)

Connects to LNS server locally or as lightweight client over TCP/IP networks

OPC® server compliance tested Integrated web server Up to 20 LNS databases, 3,000 LON

devices and 11,900 network variab-les manageable per IPLONGATE

Supports network variables, configu-ration properties and monitor sets

Fast project planning and admini-stration due to full LNS integration

LNS server license not included*Languages: English and German

IPLONGATE openIPLONGATE 150** IPLONGATE 600**

Consisting of: IPLONGATE OPC server

System requirements: Windows 7, Vista, XP, 2000 LNS server USB port for license dongle LON network interface for LON TP/FT-10 segment LAN port (10/100 Base-T) for LON/IP or remote access to LNS server

* Also available with Open LNS server on request. ** Such as IPLONGATE open, but limited to 150 respectively 600 LON network variables (can be upgraded)

OPC Data server, network diagnostics and analysis

Page 103: spega e.control catalogue 2014
Page 104: spega e.control catalogue 2014

spegaspelsberg gebäudeautomation gmbhZechenstr. 7047443 Moers Germany

fon: +49 2841 88049-0fax: +49 2841 88049-49

e-mail: [email protected]

Austria Benelux GermanySwitzerland

Delta Dore2 chemin du vieux chêneF-38240 Meylan

fon: +33 4 76 18 59 60fax: +33 4 76 18 59 69

France East

Delta Dore54 rue Eugène FreyssinetF-85290 Mortagne sur Sèvre

fon: +33 2 51 64 27 27fax: +33 2 51 65 19 76

France West

Delta Dore19 boulevard P. Vaillant CouturierF-94200 Ivry sur Seine

fon: +33 1 53 14 15 20fax: +33 1 53 14 15 39

France North

information

www.spega.comcontact spega

[email protected]

contact Delta [email protected]

Delta DoreRm 2008, Super Ocean Finance CenterNo. 2067, Yanan West RoadChang Ning District - Shanghai 200336

fon: +86 21 6070 2938fax: +86 21 6070 2933

China

Delta Dore Inc.La fuerza plaza 22241 China Roces AvenueMakati City

PhilippinesDelta Dore Pte. Ltd.120, Lower Delta Road #05-15Cendex centerSingapore 169208

fon: +85 6276 5220

Singapore