GENERAL The REGAL Series 7000 SMART- VALVE™ shall be a modular system component capable of automatically varying the gas chemical flow rate from a REGAL Gas Feed System using standard 4-20 milliamp DC analog input signals from field mounted transmitting devices such as water flowmeter transmitters or contact closures from pump motor starter auxiliary contacts. The REGAL SMARTVALVE™ shall offer the user a choice of two (2) automatic control schemes; “Flow Proportional Control (FPC)” or, “Step Rate Control (SRC)”. Model 7001 — FPC (10 to 500 PPD) Model 7002 — SRC (10 to 500 PPD) Model 7006 — FPC (1,000/2,000 PPD) Model 7007 — SRC (1,000/2,000 PPD) Each control scheme is briefly defined as follows: A.Flow Proportional Control (FPC) This control scheme is needed whenever the water flow rate to be treated varies and will work well as long as the quality of the water remains constant. In this control scheme, the SMARTVALVE™ automatically regulates the magnitude of gas flow rate through a REGAL Gas Feed System proportionally to the varying water flow rates. The required ratio “dosage” of chemical to the water flow rate is easily set by the operator to maintain the desired residual using the keypad on the SMARTVALVE™ enclosure. B.Step Rate Control (SRC) This control scheme can be used whenever fixed speed pumps (up to four) are used to move the water to be treated through a common line. The SMARTVALVE™ responds to on/off signals supplied by the pump circuits and automatically positions the valve plug so that the correct amount of chemical is added to the system regardless of which or how many pumps are running at any given time. SPECIFICATIONS The REGAL SMARTVALVE™ shall be available in eight (8) maximum capacities: 10, 25, 50, 100, 250, 500, 1,000, and 2,000 PPD (200, 500, 900, 2,000, and 5,000 gms/hr and, 10, 20, and 40 kg/hr) using only four (4) different valve plugs. The REGAL SMARTVALVE shall include a four phase linear, heavy duty stepper motor, feedback potentiometer and modulating gas flow control valve. The circuitry shall produce a series of pulses such that the motor position is a function of the number of pulses generated. Shaft direction shall be a function of phase sequence, and speed shall be a function of the pulse ratio. The rotary motion of the motor shall be converted to a linear motion driving a precision machined valve plug in an orifice via a lead screw. The valve plug shall move linearly a maximum of 1" for all capacities through 2,000 PPD based on a maximum of sixteen revolutions of the stepper motor with two hundred precise motor positioning points per revolution. The lead screw and valve plug shall move linearly a maximum of 0.0003125" per motor pulse. For maximum system accuracy, and to compensate for manufacturing tolerance differences in the various parts making up the complete gas feed system, the SMARTVALVE™ shall include a program by which the factory and/or the end user can easily “linearize” the valve’s digital display to precisely match the gas feed systems metering tube reading in PPD at 25%, 50%, 75%, and 100% of capacity. The SMARTVALVE™ must contain a program whereby the operator can easily reset “typical electrical linear values” by simply pressing two (2) keypad buttons at the same time. The SMARTVALVE™ shall include a program by which the factory and/or the end user can easily decrease or increase the speed of response of the stepper motor from one motor revolution every ten (10) seconds to one motor revolution every one (1) second. All REGAL SMARTVALVES™ shall include a manual feed rate adjustment knob with indicator pin and plate for use during times when electrical power to the SMARTVALVE™ is lost. This feature shall give the operator four (4) ways to operate the SMARTVALVE™; fully automatic, electric/manual and two (2) forms of manual ( manual via the adjust- ment knob on the SMARTVALVE™, and manual via the rate adjustment valve furnished as part of the gas feed system). Should an electrical surge, etc. upset or scramble the programmed “engineering” or “configuration” parameter settings, the operator must be able to re-load “TYPICAL” values into the microprocessor by pressing and holding one keypad button while reapplying AC electrical power to the SMARTVALVE™. The digital display of the REGAL SMART- VALVE™ shall indicate the following conditions without the need of meters or test equipment: an analog input signal is not being received; signal wires are reversed; analog signal is too high. REGAL SERIES 7000 SMARTVALVE SPECIFICATIONS 7000

Upload: tangouze

Post on 07-Sep-2015

226 views

Category:

Documents


2 download

DESCRIPTION

REGAL

TRANSCRIPT

  • GENERAL

    The REGAL Series 7000 SMART-VALVE shall be a modular systemcomponent capable of automaticallyvarying the gas chemical flow ratefrom a REGAL Gas Feed Systemusing standard 4-20 milliamp DCanalog input signals from fieldmounted transmitting devices suchas water flowmeter transmitters orcontact closures from pump motorstarter auxiliary contacts.

    The REGAL SMARTVALVE shalloffer the user a choice of two (2)automatic control schemes; FlowProportional Control (FPC) or,Step Rate Control (SRC).

    Model 7001 FPC (10 to 500 PPD)Model 7002 SRC (10 to 500 PPD)Model 7006 FPC (1,000/2,000 PPD)Model 7007 SRC (1,000/2,000 PPD)

    Each control scheme is briefly definedas follows:

    A.Flow Proportional Control (FPC)This control scheme is needed wheneverthe water flow rate to be treated variesand will work well as long as the qualityof the water remains constant. In thiscontrol scheme, the SMARTVALVEautomatically regulates the magnitudeof gas flow rate through a REGAL GasFeed System proportionally to the varyingwater flow rates. The required ratiodosage of chemical to the water flow rateis easily set by the operator to maintainthe desired residual using the keypad onthe SMARTVALVE enclosure.

    B.Step Rate Control (SRC)This control scheme can be usedwhenever fixed speed pumps (up tofour) are used to move the water to betreated through a common line. TheSMARTVALVE responds to on/offsignals supplied by the pump circuitsand automatically positions the valveplug so that the correct amount ofchemical is added to the systemregardless of which or how manypumps are running at any given time.

    SPECIFICATIONS

    The REGAL SMARTVALVE shall beavailable in eight (8) maximum capacities:10, 25, 50, 100, 250, 500, 1,000, and2,000 PPD (200, 500, 900, 2,000, and5,000 gms/hr and, 10, 20, and 40 kg/hr)using only four (4) different valve plugs.

    The REGAL SMARTVALVE shall includea four phase linear, heavy duty steppermotor, feedback potentiometer andmodulating gas flow control valve. Thecircuitry shall produce a series of pulsessuch that the motor position is a functionof the number of pulses generated. Shaftdirection shall be a function of phasesequence, and speed shall be a functionof the pulse ratio. The rotary motion of themotor shall be converted to a linearmotion driving a precision machinedvalve plug in an orifice via a lead screw.

    The valve plug shall move linearly amaximum of 1" for all capacities through2,000 PPD based on a maximum ofsixteen revolutions of the stepper motorwith two hundred precise motor positioningpoints per revolution. The lead screw andvalve plug shall move linearly a maximumof 0.0003125" per motor pulse.

    For maximum system accuracy, and tocompensate for manufacturing tolerancedifferences in the various parts makingup the complete gas feed system, theSMARTVALVE shall include a programby which the factory and/or the end usercan easily linearize the valves digitaldisplay to precisely match the gas feedsystems metering tube reading in PPD at25%, 50%, 75%, and 100% of capacity.

    The SMARTVALVE must contain aprogram whereby the operator can easilyreset typical electrical linear values bysimply pressing two (2) keypad buttons atthe same time.

    The SMARTVALVE shall include aprogram by which the factory and/or theend user can easily decrease or increasethe speed of response of the stepper motorfrom one motor revolution every ten (10)seconds to one motor revolution every one(1) second.

    Al l REGAL SMARTVALVES shal linclude a manual feed rate adjustmentknob with indicator pin and plate for useduring times when electrical power to theSMARTVALVE is lost. This featureshall give the operator four (4) ways tooperate the SMARTVALVE; ful lyautomatic, electric/manual and two (2)forms of manual ( manual via the adjust-ment knob on the SMARTVALVE, andmanual via the rate adjustment valvefurnished as part of the gas feed system).

    Should an electrical surge, etc. upset orscramble the programmed engineeringor configuration parameter settings, theoperator must be able to re- loadTYPICAL values into the microprocessorby pressing and holding one keypadbutton while reapplying AC electricalpower to the SMARTVALVE.

    The digital display of the REGAL SMART-VALVE shall indicate the followingconditions without the need of meters ortest equipment: an analog input signal isnot being received; signal wires arereversed; analog signal is too high.

    REGAL SERIES 7000SMARTVALVE

    SPECIFICATIONS 7000

  • The REGAL SMARTVALVE shall alsoinclude an "averaging" parameter in the"configuration mode" that can be used tosmooth out fluctuations caused by theflowmeter and/or the flowmeter transmitter.

    Operator interface in all program modesshall be via a four button keypad. The lefttwo buttons shall enable the operator toscroll up or down through the activeprogram parameters. The remaining twokeypad buttons shall allow the operator toview the value of, and/or change thevalue of, the active parameter. Scrollingto the next parameter shall automaticallyenter into the microcontroller, the valueselected in the previous parameter.There shall be no need for a separateenter key.

    The SMARTVALVE shall include a serialcommunications output. A 20 milliampdigital current loop shall be provided asstandard and shall be accessed (turnedon or off) through the Engineering mode.Two (2) choices of communications shallbe available. Selection of a continuousoutput will provide a digital output of valveplug position in PPD of instantaneous gasfeed rate. Selection of a full duplex outputwill allow serial data to flow both wayssimultaneously and will provide the userwith full control of the SMARTVALVEfrom a remote site.

    If the serial communications interface tofield mounted devices requires analograther than digital inputs, the optionalREGAL Serial to Analog Converter canbe used to convert the continuous digitaloutput to a 4-20 milliamp analog outputrepresenting instantaneous gas feed ratein PPD.

    The REGAL SMARTVALVE shall includethe following easy to read digital displaysand annunciator LEDs to indicate thefollowing conditions:

    A. Water flow rate being treated in actualnumbers or as a percent of flow.

    B. Current dosage setting.C. Valve plug position in PPD.D. Automatic or manual operation.E. Low flow rate alarm condition.F. Parameter and parameter value.

    SERIES 7000 SMARTVALVE DIMENSIONS

    ADDITIONAL SPECIFICATIONS

    Power Requirements: Field selectable115/230 VAC 15%, single phase.Operating frequency is 50 or 60 Hertz.

    Fusing: 1/4A @ 230V, 1/2A @ 115V(Time Delay, 250V).

    Power Consumption: 45 Watts.

    Input Signal: 0-10 Volts, d.c., 4-20 mA, d.c.

    Input Impedance: 60.4 Ohms for currentinputs. 100K Ohms for voltage inputs.

    Output Signals: Switch Contacts rated at 3amps @ 240 VAC or 28 VDC, resistive load.

    Environmental Limits: 32 to 120 F(0-50 C).

    Calibration Accuracy: 1/4% from zero.

    Speed of Response: Variable and fieldselectable.

    1044 SE Dixie Cutoff Road, Stuart, FL 34994 USA Tel: 772-288-4854 Fax: 772-287-3238 www.regalchlorinators.com E-mail: [email protected]

    1999 Chlorinators Inc. Printed in USA Pub. No. 602-1

    Operating Range: 10:1.

    Operator Interface: Four (4) button keypad.

    Display: 4 digit, red, .43" numeric LEDand six (6) annunciators.

    Control Mode: Automatic - Manual.

    Dosage Ratio: 4:1, via keypad.

    Serial Communications: Bi dir. 20 mACurrent Loop. RX is opto-coupled.

    Analog to Digital Converter: 12 bit,Unipolar, Successive Approximation.

    Reliability & Protection: Watchdog formicroprocessor, MOV & fuse for powersupply. Transorb for digital power supplyand analog input.

    EEPROM: 128 Byte of EEPROM. Storesconfiguration and engineering parameters.

    Memory: 8K RAM. 32K ROM.

    7500 REMOTE

    METER PANEL(Must be used with

    250 and 500 PPD only. Optional for 100 PPD

    or less).