TECHNICAL SPECIFICATION Marrone & Co., Inc. 2730 Maximilian Drive, Houston, Texas 77032 • Phone (800) 473-9178, (281) 227-8400 Fax (800) 473- 9175, (281) 227-8404 • www.waterchillers.com TechSpec_ACWC-150-E-_-_-_-_ (0718).doc Model: ACWC-150-E-__ 1 -__ 2 -__ 3 -__ 4 Description: Two stage portable air-cooled water chiller system. System capacity indicated on table is the approximate BTU/hr based on a leaving fluid temperature of 50°F with an ambient air temperature of 95°F. CAPACITY ±5% AT 50° LCWT / 95°F AMBIENT 150,000 BTU /HR COMPRESSOR / REFRIGERANT TANDEM HERMETIC SCROLL / R410A CONDENSER FANS / AIRFLOW 2 / 8000 CFM CONDENSER COILS TYPE COPPER TUBE / ALUMINUM FIN EVAPORATOR TYPE STAINLESS STEEL / COPPER BRAZED FLUID CONNECTIONS 2” MNPT (IN/OUT) ELECTRICAL: V - Ø - HZ COMP RLA / LRA FAN FLA (ea) PUMP FLA MCA MOCP -1 575 - 3 - 60 7.7 54 1 2.2 21.5 25 - 5 230 - 3 - 60 22.4 149 2.4 5.6 60.8 80 - 6 460 - 3 - 60 10.6 75 1.4 2.8 29.4 40 PUMP HP / OUTPUT 2.0 HP / 76 GPM @ 30 PSI TANK SIZE / CONSTRUCTION 80 GALLON / 304 STAINLESS STEEL TANK WITH LID DIMENSIONS 73 ½” L x 40” W x 70” H WEIGHT (APPROX.) 1500 LBS Note: All specifications subject to change without notice. Specify voltage and ambient condition upon ordering. MCA: Minimum circuit amps per UL 1995. MOCP: Maximum overcurrent protective device per UL 1995. STANDARD FEATURES: Controls: Electronic programmed temperature controller with constant (set point & process) temperature readout. Refrigeration Components: Efficient scroll compressors, sight glass/moisture indicators, balanced port expansion valves, filter drier, pump down valves, fan cycling head pressure controls. Process Fluid Components: Bronze “Y” strainer with 20 mesh stainless steel screen. Pumps are stainless steel centrifugal. Tanks are insulated with shoe box lid, fill port, and level sight glass. Portable systems will include a bypass flow valve. Safety Controls: High and low refrigerant pressure, high and low fluid temperature, freeze, low water flow, overloads for compressor and fan motors, safety fuses or overloads for pump. Construction: Welded steel powder coated frame and full metal cabinet, copper piping connections. Warranty: One year parts / five year compressor. SUITABLE AMBIENT CONDITIONS/FEATURES: IND: Indoor use only. Casters on frame. 40: Suitable for outdoor use with an ambient of 40°F ambient. Casters, optional. 0: Suitable for outdoor use to 0°F ambient. Includes low ambient fan speed controls with (LT) models. Casters, optional. M20: Suitable for outdoor use to -20°F ambient. Includes with low ambient fan speed controls with hot gas bypass. External Wind baffles. Casters, optional. 1 Flow Design (_=Portable, ST=Stationary, RF=Reverse Flow, EXCH=Extra Heat Exchanger, DP=Dual Pump, DR=Dual Return) 2 Leaving Fluid Temperature (_=Standard, LT=Low Temperature-specify lowest temperature in °F) 3 Ambient Temperature Conditions (see above) 4 Electrical Power Code (see above)

Upload: others

Post on 05-Apr-2021

5 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: SPACEX Q 150E 0903 0718.pdfMANUAL BYPASS PROCESS STRAINER TEMPERATURE CONTROLLER SENSOR TANK CHILLER/PROCESS PUMP STANDARD/PORTABLE/PACKAGE (-) Title Microsoft Word - SPACEX Q 150E

TECHNICAL SPECIFICATION

Marrone & Co., Inc. 2730 Maximilian Drive, Houston, Texas 77032 • Phone (800) 473-9178, (281) 227-8400

Fax (800) 473- 9175, (281) 227-8404 • www.waterchillers.com TechSpec_ACWC-150-E-_-_-_-_ (0718).doc

Model: ACWC-150-E-__1-__2-__3-__4 Description: Two stage portable air-cooled water chiller system. System capacity indicated on table is the approximate BTU/hr based on a leaving fluid temperature of 50°F with an ambient air temperature of 95°F.

CAPACITY ±5% AT 50° LCWT / 95°F AMBIENT

150,000 BTU /HR

COMPRESSOR / REFRIGERANT TANDEM HERMETIC SCROLL / R410A CONDENSER FANS / AIRFLOW 2 / 8000 CFM CONDENSER COILS TYPE COPPER TUBE / ALUMINUM FIN EVAPORATOR TYPE STAINLESS STEEL / COPPER BRAZED FLUID CONNECTIONS 2” MNPT (IN/OUT) ELECTRICAL: V - Ø - HZ COMP RLA / LRA FAN FLA (ea) PUMP FLA MCA MOCP

-1 575 - 3 - 60 7.7 54 1 2.2 21.5 25 - 5 230 - 3 - 60 22.4 149 2.4 5.6 60.8 80 - 6 460 - 3 - 60 10.6 75 1.4 2.8 29.4 40

PUMP HP / OUTPUT 2.0 HP / 76 GPM @ 30 PSI TANK SIZE / CONSTRUCTION 80 GALLON / 304 STAINLESS STEEL TANK WITH LID DIMENSIONS 73 ½” L x 40” W x 70” H WEIGHT (APPROX.) 1500 LBS

Note: All specifications subject to change without notice. Specify voltage and ambient condition upon ordering. MCA: Minimum circuit amps per UL 1995. MOCP: Maximum overcurrent protective device per UL 1995. STANDARD FEATURES: • Controls: Electronic programmed temperature controller with constant (set point & process) temperature readout. • Refrigeration Components: Efficient scroll compressors, sight glass/moisture indicators, balanced port expansion valves,

filter drier, pump down valves, fan cycling head pressure controls. • Process Fluid Components: Bronze “Y” strainer with 20 mesh stainless steel screen. Pumps are stainless steel centrifugal.

Tanks are insulated with shoe box lid, fill port, and level sight glass. Portable systems will include a bypass flow valve. • Safety Controls: High and low refrigerant pressure, high and low fluid temperature, freeze, low water flow, overloads for

compressor and fan motors, safety fuses or overloads for pump. • Construction: Welded steel powder coated frame and full metal cabinet, copper piping connections. • Warranty: One year parts / five year compressor.

SUITABLE AMBIENT CONDITIONS/FEATURES: • IND: Indoor use only. Casters on frame. • 40: Suitable for outdoor use with an ambient of 40°F ambient. Casters, optional. • 0: Suitable for outdoor use to 0°F ambient. Includes low ambient fan speed controls with (LT) models. Casters, optional. • M20: Suitable for outdoor use to -20°F ambient. Includes with low ambient fan speed controls with hot gas bypass.

External Wind baffles. Casters, optional.

1 Flow Design (_=Portable, ST=Stationary, RF=Reverse Flow, EXCH=Extra Heat Exchanger, DP=Dual Pump, DR=Dual Return) 2 Leaving Fluid Temperature (_=Standard, LT=Low Temperature-specify lowest temperature in °F) 3 Ambient Temperature Conditions (see above) 4 Electrical Power Code (see above)

Page 2: SPACEX Q 150E 0903 0718.pdfMANUAL BYPASS PROCESS STRAINER TEMPERATURE CONTROLLER SENSOR TANK CHILLER/PROCESS PUMP STANDARD/PORTABLE/PACKAGE (-) Title Microsoft Word - SPACEX Q 150E

COLD SHOT CHILLERS

DRAWN ENGINEERING

ISSUED

SIZE VIEW DWG NO REV

A Front-Right-Back-Left-TopINSTALLATION DRAWINGACWC-150-E- (Full Metal Cabinet)

1

7/11/2018 SCALE NONE DWG-INST_ACWC-150-E-(0718).vsd SHEET 1 OF 2

Notes

- Unit should be installed with at least 4' clearance on all sides and a minimum of 8' clear air space above the unit- Dimensions are in inches unless otherwise specified.- Casters – Optional.- All specifications subject to change without notice.

Condensing Area Access Panel

"Y" Strainer(INSIDE)

Casters(Swivel)

Casters(Fixed)

Condensing Area Access Panel Refrigerant

Pressure Ports

Coating Optional

Insulated Stainless Steel Tank

Control Panel

Temperature Controller

Power Switch

Electrical Power Entry

PUMP COOLOFF

6.5in.

High PressureReset

Inlet NPT-MALE

OutletNPT-MALE

Chiller Pump(INSIDE)

Condensing Area Access Panel

Tank Fill Port

Tank Drain Port

BACK

Tank LevelSightglass

70.0in.

73.5in.

Condenser Fans

FRONT RIGHT SIDE

LEFT SIDE

TOP

39.5in.

Page 3: SPACEX Q 150E 0903 0718.pdfMANUAL BYPASS PROCESS STRAINER TEMPERATURE CONTROLLER SENSOR TANK CHILLER/PROCESS PUMP STANDARD/PORTABLE/PACKAGE (-) Title Microsoft Word - SPACEX Q 150E

Line Guide

HOT FLUID

COLD CHILLED FLUID

COLD FLUID

WARM FLUID

DRAWN ENGINEERING

ISSUED

SIZE NOTE DESCRIPTION REV

A See upper Note list Typical FLOW OPTIONS for Chiller Circuits 1

6/21/2018 SCALE NTS DWG-CKT_ChillerCircuitFlowOptions-Typical_062218.vsd SHEET 1 / Standard/Portable

NOTES

- All designs are subject to change without notice.- The diagrams are to be used as a basic flow diagram only.- Color Code is for relative temperature comparison.- Additional components may be included.- Evaporator may be located in tank.

Refrigerant

Flui

dEVAPORATOR

MANUALBYPASS

PROCESS

STRAINER

TEMPERATURE CONTROLLER SENSOR

TANK

CHILLER/PROCESSPUMP

STANDARD/PORTABLE/PACKAGE (-)